Taiko Marketing Sdn. BHD: Sizing Blower Np3

This document provides calculations to size a blower for cooling sulphuric acid storage tanks. It determines that: 1) The heat release rate from cooling 50% concentration sulphuric acid in two stages is 1,800,000 kJ per stage over 8 hours. 2) The required power to remove this heat is 62.5 kJ/s. 3) Based on the heat capacity of air and a desired final air temperature, the required air mass flowrate is 1.07 kg/s. 4) The corresponding air volume flowrate is 0.89 m3/s or 53 m3/min (2,254 cfm).

Uploaded by

Jiong Soon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
231 views10 pages

Taiko Marketing Sdn. BHD: Sizing Blower Np3

This document provides calculations to size a blower for cooling sulphuric acid storage tanks. It determines that: 1) The heat release rate from cooling 50% concentration sulphuric acid in two stages is 1,800,000 kJ per stage over 8 hours. 2) The required power to remove this heat is 62.5 kJ/s. 3) Based on the heat capacity of air and a desired final air temperature, the required air mass flowrate is 1.07 kg/s. 4) The corresponding air volume flowrate is 0.89 m3/s or 53 m3/min (2,254 cfm).

Uploaded by

Jiong Soon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 10

TAIKO MARKETING SDN.

BHD

SIZING BLOWER NP3


Date: 9/5/2019

BLOWER SIZING (find heat release rate kJ/s )

from above figure 8.1-1, to maintain temperature at 90 degC, at 50% wt concentration


A enthalpy release is 60 kJ/kg

B total volume of storage tanks 40 m3


C 50% sulphuric acid SG 1.5
D mass of sulphuric acid 60000 kg (B*C*1000)
E heat release will be 3600000 kJ (A*E)

because we are doing 2 stage dilution, therefore heat release divide by half
F new heat per stage 1800000 kJ (E/2)
G duration set to finish 1st stage 8 hrs
H power need to remove 62.50 kJ/s (F/G)

BLOWER SIZING (find mass flowrate kg/s)

(use Q = m*Cp*deltaT)
Q= power remove kJ/s
m= mass flowrate kg/s
Cp= heat capacity of air at KJ/kg.K
deltaT= temperature different in kelvin

I heat capacity of ambient air 1.006 kJ/kg.K (at constant pressure and 0 degC)
J assume air initial temp. 305 K
K final air temp desired. 363 K
L different temperature 58 K (K-J)
M cp*delta T 58.3 kJ/kg ( I*L )
N air mass flowrate 1.07 kg/s (H/M)

Q given air density 15C, 1 atm 1.208 kg/m3


R air volume flowrate I 0.89 m3/s (N/Q)
S air volume flowrate II 53 m3/min (R*60)
T air volume flowrate III 2254 cfm (O*35.31*120%)

blower specifications website https://www.taiko-kk.com/pdf/R_E.pdf


, at 50% wt concentration

(B*C*1000)
onstant pressure and 0 degC)

5.31*120%)
3500mm Note: Air bubble fo

sulphuric acid 5
50% 0
0 2
0 3
m 0
m 0
c
f
m
0
0 2
0 3
m 0
m 0
c
f
air bubble m

5 3
0 1
0 0
m m
m m
Note: Air bubble for cooling purpose
blower
TAIKO MARKETING SDN. BHD

Physical properties

You might also like