A Method of Analysis For Heat Pipe Heat Exchangers
A Method of Analysis For Heat Pipe Heat Exchangers
00
PrmtedinGreatBrltam Pergzimon
PrrssLtd.
Abstract -A method of analysis for the thermal performance of heat pipe heat exchangers based on the
conductance mode! wasdeveloped in the present study. In the analysis the specific heat conductance of the heat
pipe was obtained from a performance test of a single heat pipe described in the present paper and the well-
known universal correlations were used to calculate the convective heat transfer coefficients in tube banks. A
computer program based on the finite difference equations of the model was then developed to calculate the
thermal performance of heat pipe heat exchanger. The analysis was finally validated by an experiment and
shown to be applicable in engineering applications.
mm 28:sc 553
554 8. J. HUANG and J. T. TSIJEI
NOMENCLATURE
total area of heat pipe heat exchanger [m’] Q total energy transfer rate of heat exchanger
surface area of condensing section of a heat [WI
pipe Cm’1 4P
energy transfer rate of a heat pipe [W]
surface area of evaporating section of a qpj energy transfer rate in the jth row of heat
heat pipe [m2] pipes [W J
specific heat of cold air flow 4 overall heat transfer resistance in the jth
[KJ kg- ' "C- '1 section PC W-‘]
specific heat of hot air flow Re Reynolds number in tube banks, defined in
[KJ kg-’ “C-‘1 equation (11)
characteristic diameter of heat pipe heat T temperatures c”C]
exchanger [m] U characteristic velocity in tube banks
heat pipe O.D. [m] [m s- ‘1.
thermal conductivity of air [W m-l “C-‘1
Greek symbols
convective heat transfer coefficient
p density of air [kg m-“1
CWm -2 gc-‘l
p viscosity of air [N s m-‘1,
mass flowrate of cold air [kg s- ‘1
M, mass flowrate of hot air [kg s- ‘1 Subscripts
sj number of heat pipes injth row C condenser side ; cold air
Nu Nusselt number in tube banks, defined in h evaporator side; hot air
equation (11) w outside wall surface of heat pipe
Pr Prandtl number j section notation of heat exchanger.
applications for which the adiabatic sections ofthe heat can be applied to commercial heat pipes, it was not
pipes in the heat pipe heat exchanger had to be as small attempted in the present study to measure the
as possible. The condensing section of the heat pipe was temperatures or other properties in the interior of the
then sealed by use of a flange and o-rings in the water heat pipes. Instead, only temperatures over the outside
jacket through which a cooling water was allowed to surface of the heat pipe were measured using eleven T-
pass. In the evaporating section of the heat pipe, a type thermocouples which were fixed equally spaced
2.5 kW electric heating wire was uniformly wrapped onto the pipe surface and read by an Omega 2176A
over the pipe surface as the heating element. The rate of recorder to within f O.YC. Temperature measure-
heating was controlled by a power transformer. To ments were also made at the inlet and outlet of the water
eliminate the heat losses, the tested heat pipe including jacket. To determine the rate of energy removed in the
the water jacket was carefully insulated by 6 cm thick water jacket, the mass flowrate ofthe cooling water was
calcium silicate. Therefore, the overall energy transfer also measured by a rotameter which was calibrated to
rate through the heat pipe can be measured either by within rfi 5%.
measuring the rate of energy added by the electric Figure 2 shows the temperature distributions vs
heater or by measuring the rate of energy removed by energy transfer rates obtained from one of the test runs
the water jacket. These two measurements also for a performance test of a single heat pipe. At this stage,
provided a check for the insulation condition during it is very important to derive a method to correlate the
the experiment. It was observed in the present testing results. As a first-order approximation, it is
experiments that the two values obtained from the assumed that the longitudinal heat conduction in pipe
above two measurements all coincided within iS% wall and wick material is negligible. Thus, there are Eve
deviations. thermal resistances for the transfer of energy from the
As the present method of testing for the thermal hot to the cold side of the heat pipe as shown in Fig. 3,
performance ofasingle heat pipe is non-destructive and where R,., and R,., are the thermal resistances of the
pipe wall at the evaporating and the condensing
Table I. Specifications of heat pipes sections, respectively; R,,,and R,,, are the thermal
resistances in the wick materials at the evaporating and
Effective length 610 mm
Outside diameter 33.7 mm the condensing sections, respectively and R, is the
Wall thickness 1.6mm overall thermal resistance in the vapor core region
Wall materiak carbon steel including interphase condensing and evaporating
Wick structure wrapped screen (I 5 layers) resistances.
Wick material IOO-mesh bronze
For heat pipes operating below the sonic limit, the
Working fluid distilled water (I 15 g)
thermal resistance in the vapor core, R,,can be ignored
A method of analysis for heat pipe heat exchangers 555
rHEA7 PIPE
TRAN
PUMP UNIT
I , t I 8 t f
t
400 -
360-
320-
280-
240-
200-
160”
120-
80s
40-
01
0 0.1 0.2 0.3
I
04
1
Q5 06 0.7
1
0.8 0.9
1
1.0
HEAT OUT
In the present study, five out of 32 heat pipes made in
tttttt t
/PIPE WALL the laboratory were randomly selected to be separately
-SCREEN
tested according to the above testing method. It can be
seen from Fig. 4 that the specific conductance of each
heat pipe is approximately independent of the vapor
core temperature as can be expected from the heat pipe
/ti ttttt theory. Therefore, combining all the data, the mean
1 (Twh) heat conductance for this batch of heat pipes was
determined as 3.36 W “C- ’ with a standard deviation of
+ 0.59 W “C- I. The standard deviation will apparently
decrease with improving quality control. When the
quality control is excellent, as in commercial mass
production, this sampling test can be omitted and a
single performance test for a heat pipe of the same kind
TWh TWC
using the same procedure can directly give the heat
FIG.3. Thermal resistances network of a heat pipe. conductance.
It also can be seen that the heat transfer behavior of
the heat pipes made in the present study is not good.
toward the condensing section is not negligible cannot This is attributed to the fact that no other means which
be included. Therefore, care should be taken in can reduce the thermal resistance of the wick material
averaging the thermocouple readings on the pipe were employed in the present heat pipes. In addition, a
surface to preclude these points. tight contact between the wrapped bronze screen and
For the heat pipes made in the present study, the the pipe wall was produced by the elastic force induced
largest deviation of the surface temperature in the merely by the screen itself when carefully pressing the
evaporating section, precluding the point nearest to the wrapped screen into the pipe. Since the major purpose
pipe mid-point, was within + 12°C for temperatures ofthe present study is to develop a new method for the
around 360°C and even much less for temperatures thermal performance analysis of heat pipe heat
below this, as can be seen from Fig. 2. Thus the averaged exchanger, the study on the fabricating techniques
surface temperatures could give reasonably good which can produce highest efficiency heat pipes was
approximations. skipped over.
In addition, poor quality control in making the heat
pipes can lead to small deviations in heat conductance
THERMAL ANALYSIS OF
between each heat pipe. This necessitates a certain
HEAT PIPE HEAT EXCHANGER
amount oftesting of samples to determine a mean value
for the heat conductance which can statistically A finite difference method based on the conductance
represent the averaged thermal performance of the model is employed in the present study to analyze the
batch of heat pipes to be used to make a heat pipe heat overall heat transfer of the heat pipe heat exchanger.
exchanger. Assume that the heat pipe heat exchanger can be
10 I, I1 I I I I I I1 I I1 1 q
TEST SAMPLE NO. 1 - A
9 2 -m
a- 3 -v
;_
2 I & -0
5 -A
9
o,u 6-
UI
? 0.59 watt Ic
l-0
qi
A A A
Ya2 f+-A A
2 3 3.36 V
x &)A V-&+G m
k -.v A
n 6
om 0m0 n
z
% 2-
divided into N sections along the flow direction and the flows across each section can be written as
each section consists of a row of heat pipes of the same
Tc,j- Tc,j- I = n,(lIRJ(Gj- TJMcCc (7)
kind, as shown in Fig. 5. Neglecting the heat transfer
across the partition and the heat loss to the ambient, the x,j- q,j- 1 = -n,(lfRj)(Rj- T,)fM,C, (8)
total energy transfer in the jth section can be expressed
where M, and M, are the mass flowrates of the hot and
as
the cold flow, respectively, both are taken as positive for
4pj = n,llIRj)(Thj- Tj) (4) parallel-flow design and M, is taken as negative for
counter-flow design. To solve the temperature
where nj is the number of heat pipes in thejth section, Thj
distributions, the iteration method with relaxation
and TCjare the mean fluid temperatures of the hot and
factor is employed [S] with the follbwing equations
the cold flows, respectively, in the jth section, which is
which are derived from equations (7) and (8)
defined as
1 K,
xj=(Th,j+T,,j-,)/2 and T;j=(T,,j+T,,j-,)/2. T”,j=- T;,j_ I - -
l+K,j l+K,j
Rj in equation (4) represents the overall heat transfer
~[T~,j_1-~,j-C,j-1I (9)
resistance from the hot flow to the cold flow for a heat
pipe in the jth section and can be expressed by the 1 K.
following equation, ignoring fouling resistance in the T;,j = -T:,j-,-~
l+K,j l+K,j
pipe wall
CC’,j-l-TE,j-‘G,j-11 (10)
Rj = (lIh,A,)j+(lI~~),+(llh,A,)j (5)
where the superscripts, n and o, represent the new and
where h, and h, are the convective heat transfer the old value, respectively, during the iteration and
coefficients outside the heat pipe wall in the hot and the
cold flow, respectively; A, and A, are the outside K,j = nj/2M,C,,Rj and Kcj = nj/2M,C,Rj
surface areas of a heat pipe in the evaporating and the
The iteration procedure is as shown in Fig. 6. To
condensing sections. Therefore the overall energy
calculate the convective heat transfer coefficients in
transfer rate delivered by the whole heat pipe heat
tube banks, h, and h,, the universal correlation
exchanger can be calculated by an integration over the
obtained by Whitaker [6] is used
N sections
Nu .= f(0.5Re1”+ 0.2Re2/3)Pri/3(p/p,) (11)
Q = 2 qpj (6)
j= 1 where NM and Re are defined as
It is necessary to calculate the temperature
distributions in the hot and cold flows before Nu = (hDdk,)c,/( 1 -E,) (12)
calculating the overall energy transfer rate using
and
equations (4) through (6). By applying the energy
balance to the jth section, the temperature changes of Re = (~D,~/&d(l - s,). (13)
TOP VIEW
j;l
j-l j -1
“p
I II
I HOT - ;
1
- FLOW - 1
-I
I
-,
I
7
--I
COLD - )
FLOW - ,
-A,*
I I
i<,,>
_
j-th ROW 4
nj /he Ac nj/(UA)p nj/h,Ac
T hl - 44.w -7 CJ
Twhj Twcj
INPUT desqn data on the number of rows in the heat pipe heat exchanger
(UA), ,N , n, zL, L, > c71.
A computer program based on the above equations
D, fluld properties ,etc.
and the iteration process as shown in Fig. 6 was
developed in the present study to calculate the thermal
performance of a heat pipe heat exchanger.
EXPERIMENTS
Number of rows, N 4
FIG. 6. Flow chart of the iteration process in thermal analysis. Number of heat pipes in each row, n, 8
Total number of heat pipes 32
Condenser length of heat pipes, L, 305 mm
Evaporator length of heat pipes, L, 305 mm
D,is the characteristic diameter defined as 1.5D (D is the Pipe arrangement staggered
pipe O.D.) for tube banks and E, is the void fraction of Pipe pitch : longitudinal 44.1 mm
the heat pipe heat exchanger, u is the characteristic flow transverse 38.7 mm
Cross-section : for hot flow 305 x 380 mm’
velocity which is usually taken as the maximum
for cold flow 305 x 380 mm*
velocity in the tube bank and f is a parameter depending
FLOWRATE MEASURING
DEVICE
STRAIGHTENER TO AMBIENl
HEATER
r ^“‘“‘TE MEASURING
Table 3. Comparison ofexperiment with theory for total energy transfer rate of the heat pipe heat exchanger
and precision pressure gauges were used to measure the RESULTS AND DISCUSSION
velocity distribution at given cross sections. The
velocity was measured at 10 points along the radial Some test runs using the above heat pipe heat
direction in the present experiments to obtain the exchanger equipment were carried out for various air
velocity distribution. By integrating the velocity flow rates and temperatures in the present experiment.
distribution then multiplying by the air density at the Theoretical calculations based on the analytical model
same cross-section, the air mass flowrate in each duct described previously were also carried out for
was determined. The experimental uncertainties were comparisons. The results are listed in Table 3. It can be
estimated to be within f 5%. seen that the errors caused by the analysis in the total
Temperature measurements were made by T-type energy transfer rates are all within + 10% which is
thermocouples at the inlet and the oulet of the hot and acceptable in engineering applications. It is also shown
the cold air flows and all over the heat pipe heat from Table 4 that the measured temperature
exchanger. The mean outside wall temperatures of the distributions ofthe air flows in the heat exchanger are in
condensing and the evaporating sections of the heat fairly good agreement with the analytical results.
pipes at thejth row, TWcjand Twhj, were measured by 16 Larger errors in the predictions of the pipe wall
thermocouples. To do this, two pipes were selected at temperatures occur in the present experiment, as can be
each row and four thermocouples were separately fixed seen from Table 5. This probably resulted from the
at the middle points of the condensing and the contact resistances between the pipe wall and the
evaporating sections of the two heat pipes. The mean temperature probes which were introduced during the
wall temperature of the condensing or evaporating installation of the probes.
section at the jth row, Twcj or Twhj,then was obtained by In fact, the convective heat transfer in tube banks
averaging the two temperatures on the two heat pipes. increases along with the penetrating of the air how into
To measure the air temperatures between two the tube banks due to the transition of the flow pattern
adjacent rows ofheat pipes in the hot or cold channel of from laminar to turbulent [8]. Therefore, the use of the
the heat exchanger, Th,j or K,j, three thermocouples mean convective heat transfer coefficients in tube banks
were installed at each measuring cross-section and the in the present analysis could lead to the small errors in
average readings gave the bulk air temperatures. There temperature predictions as shown in Tables 4 and 5.
were five measuring cross-sections in each channel and From the experiment, we verified that the method of
30 thermocouples were used in this measurement. analysis for the thermal performance of heat pipe heat
Besides, two temperature measurements were also exchanger proposed in the present study is validated.
made at the velocity measuring ducts to obtain the air Although the present experiment was performed using
densities for determining the air mass flow rates. heat pipes without fins for the sake of simplicity, the
To process the 38 thermocouple readings and the present method of analysis still can be applied to heat
related calculations in the present experiment, a Kaye pipes with fins as long as the convective heat transfer
Digistrip II data acquisition and microcomputer coefficients for finned-tube banks are used.
system was used. The maximum uncertainties in Finally, it should be noted that, to ensure good
measuring the total rates of energy transfer of the heat accuracy, the present method of analysis is not valid
pipe heat exchanger were estimated to be within + 5%. when the operating conditions of any heat pipe in the
560 ES.J. HUANG and J. T. TSUEI
Air temp. in hot flow, Th., Air temp. in cold how, T,,,
Test (“CJ (‘C)
run No. j=O 1 2 3 4 j=O 1 2 3 4
~.
Experiment 244.1 236.0 223.2 213.8 200.7 49.7 42.2 35.7 29.8 25.1
I 25.1
Theory 244.1 233.5 223.1 213.0 203.2 48.3 42.2 36.4 30.7
Experiment 239.5 232.1 219.6 210.5 197.9 49.1 42.2 36.1 30.0 25.2
2
Theory 239.5 229.1 219.1 209.3 199.7 48.1 42.1 36.3 30.7 25.2
Experiment 238.4 231.1 218.9 210.0 197.5 47.5 40.8 35.1 29.2 24.6
3
Theory 238.4 228.0 211.8 207.9 198.2 47. i 41.2 35.5 30.0 24.6
Experiment 216.2 266.8 250.4 239.2 223.6 52.2 44.0 36.8 30.0 24.8
4
Theory 216.2 262.8 249.8 237.3 225.2 51.4 44.4 37.7 31.1 24.8
Experiment 297. I 288.7 267.0 254.1 235.2 57.3 47.7 39.5 33.2 28.8
5
Theory 297.1 279.6 262.9 246.9 231.6 59.0 50.9 43.2 35.9 28.8
Experiment 295.7 281.7 266.3 253.8 234.7 57.1 47.9 39.6 33.4 28.7
6
Theory 295.7 278.4 261.8 245.9 230.8 59.0 50.9 43.2 35.8 28.7
Experiment 274.4 266.9 253.1 244.4 230.7 73.0 61.3 47.5 37.5 32.0
7
Theory 274.4 263.6 253.0 242.5 232.0 71.8 61.7 51.7 41.8 32.0
Experiment 296.6 292.1 275.0 265.4 248.9 79.2 67.0 51.4 40.4 34.7
8
Theory 296.6 284.5 272.5 260.6 248.9 79.2 67.9 56.7 45.6 34.7
Experiment 261.6 258.1 244.6 237.2 223.8 67.2 57.3 45.2 36.4 31.7
9
Theory 261.6 251.2 241.0 230.9 220.8 70.0 60.3 50.7 41.2 31.7
Experiment 298.5 293.4 275.7 266.0 248.9 74.9 63.2 48.6 38.3 33.0
10
Theory 298.5 285.5 212.8 260.2 247.8 75.8 64.9 54.1 43.5 33.0
~x~riment 299.0 291.3 270.8 258.8 240.2 67.2 56.7 44.3 35.7 31.3
11
Theory 299.0 282.1 265.8 250.0 134.8 70.5 60.1 50.2 40.6 31.3
Experiment 300.7 292.7 272.0 259.6 241.0 61.7 57.1 44.6 36.0 31.4
12
Theory 300.7 283.6 267.2 251.3 235.9 10.7 60.4 so.4 40.7 31.4
Average error 0.0 6.2 2.5 4.8 1.2 -0.7 - 1.6 - 3.5 -3.1 0
-~ -_.- -
heat exchanger are beyond the testing range in the a wider range of operating conditions, as near the heat
performance test of a single heat pipe as described pipe operating limits as possible.
previously. Therefore, checks at any instant during the The present method of analysis can be applied to
analysis are always required and it is important to simulate the thermal performance of the heat pipe heat
perform the performance test for a single heat pipe over exchanger used in the experiment beycnd the testing
Wall temp. in hot air side, Twhj Wall temp. in cold air side, Twcj
Test i”Cl (“C)
run No. j=l 2 3 4 j= 1 2 3 4
-- - ___~ -- ..-..._~-
Experiment 169.2 160.3 144.6 140.5 100.2 92.6 83.2 80.0
Theory 165.6 156.6 147.9 139.4 108.0 100.7 93.6 86.7
Experiment 161.2 159.3 143.8 140.0 97.8 90.8 83.0 80.0
Theory 162.9 154.1 145.6 137.4 106.8 99.6 92.6 85.8
Experiment 173.8 160.6 144.4 140.8 95.2 88.0 79.6 78.9
Theory 161.2 152.5 144.0 135.7 105.3 98.2 91.2 84.4
Experiment 194.Q 1go.4 160.6 156.8 110.4 99.7 88.1 87.0
Theory 183.5 172.6 162.0 151.7 119.5 110.7 102.2 94.0
.5 Experiment 208.3 201.6 176.3 170.3 113.8 101.8 88.0 83.0
Theory 190.9 177.3 i 64.3 151.9 130.7 119.9 109.6 99.8
6 Experiment 207.8 201.4 176.0 170.2 113.2 101.0 87.3 82.4
Theory 190.4 176.8 164.0 151.6 130.6 119.8 109.6 99.7
7 Experiment 208.1 198.8 179.4 176.6 139.5 130.9 117.0 116.7
Theory 199.6 189.2 178.8 168.6 147.8 137.9 128.0 118.3
8 Experiment 223.5 216.9 193.4 190.8 150.4 141.8 126.0 125.8
Theory 215.5 203.8 192.2 180.7 161.3 150.2 139.2 128.4
9 Experiment 202.0 196.2 176.2 174.4 126.6 118.4 108.3 108.4
Theory 190.0 180.0 170.0 160.2 141.9 132.4 122.9 113.6
10 Experiment 223.0 216.7 192.8 189.8 145.2 134.9 120.3 120.2
Theory 213.1 201.0 189.0 171.2 157.6 146.3 135.3 124.4
11 Experiment 214.7 208.4 183.2 178.8 132.6 121.5 107.0 105.3
Theory 200.2 186.0 172.3 159.1 147.9 135.6 123.8 112.3
12 Experiment 215.8 209.2 183.8 179.4 133.6 122.4 107.6 105.8
Theory 201.2 186.9 173.1 159.8 148.5 136.2 124.3 112.8
Average error 11.1 14.4 ,4.3 11.3 - 12.3 -- 12.0 - 14.7 -7.2
A method of analysis for heat pipe heat exchangers 561
FIG. 8. Total energy transfer rate at various inlet temperatures of hot air.
conditions. Figure 8 shows the total energy transfer defined as in equations (12) and (13) and the ratio, Y,is
rates at various inlet temperatures of hot air, T&,, and defined as I”= Re,JRe,. The overall heat transfer
equal vofumetric air flow rates, V, = V,, in the hot and coeffkient, U, is defined as
the cold flows. For different combinations of Aowrates,
U=Q/A(LMTD) (14)
the overall heat transfer coefficient of the heat pipe heat
exchanger, U, can be determined in terms of the where (LMTD) is the log mean air temperature
Reynolds number of the cold air flow, I$, and the ratio difference of the heat exchanger, A is the total heat
oftheReynoldsnumbersofthetwoairflows,r,ascan be transfer area of the heat exchanger. It can be seen from
seen in Fig. 9. The Reynolds numbers, Re, and Re,,, are Figs 8 and 9 that the energy transfer rate as well as the
1 I111111 I ,
IO2 103 lOL lo5
FIG. 9. Overall heat transfer coefficients of heat pipe heat exchanger at various operating conditions.
562 B. J. HUANG and J. T. TSUEI
overall heat transfer coefficient increases with Acknowledgement-The present study was supported by the
increasing flowrate but tends to reach a constant. This Energy Research Laboratory at the Industrial Technology
Research Institute of the Republic of China.
is due to the fact that the convective heat transfer
resistances in tube banks decreases with increasing flow
REFERENCES
rate but the specific heat conductance of the heat pipes
still remains nearly constant over a wide range of 1. J. 0. Amode and K. T. Feldman, Preliminary analysis of
operating temperatures. heat pipe heat exchangers for heat recovery, ASME Paper
No. 75-WA/HT-36 (1976).
2. Y. Lee and A. Bedrossian, The characteristics of heat
exchangers using heat pipes or thermosyphons, Znt. J. Heat
Mass Transfer 21. 221-229 (1978).
CONCLUSIONS J. P. Holman, Heat Transfe;, p. 222. McGraw-Hill, New
York (1976).
A method of analysis based on the conductance
S. W. Chi, Heat Pipe Theory and Practice. McGraw-Hill,
model was developed in the present study. In the New York (1976).
analysis, the specific heat conductance of heat pipe was S. V. Patankar, Numerical Heat Transfer and Fluid Flow.
obtained from a thermal performance test for a single Hemisphere, New York (1975).
S. Whitaker, Forced convection heat transfer correlations
heat pipe and the universal correlations for the
for flow in pipes, past flat plates, single cylinders, single
convective heat transfer coefficients in tube banks were spheres, and for flow in packed beds and tube bundles, J.
used. A computer program using the finite difference AlChE l&361-371 (1972).
equations of the model was also developed to calculate I. W. M. Kays, Compact Heat Exchanger, 2nd ed., p. 128.
the thermal performance of heat pipe heat exchanger McGraw-Hill, New York (1964).
8. W. M. Kays, A. L. London and R. K. Lo, Heat-transfer and
and the present method of analysis has been validated
friction characteristics for gas flow normal to tube banks-
experimentally and shown to be applicable in use of a transient test technique. Trans. ASME 76,389-396
engineering applications. (1954).
R&u&-On dtveloppe une m6thode d’analyse des performances thermiques des Bchangeurs<aloducs ba&.e
sur le modtle de conductance. Dans l’analyse, la conductance thermique specifique du caloduc est obtenue B
partir d’essais d’un caloduc unique d&it dans cet article et les formules universelles classiques sont utilisies
pour calculer les coefficients de convection dans un arrangement de tubes. Un programme de calcul bast sur les
Equations aux diffkrences finies du modile est d&velopp& pour calculer la performance thermique de
l’tchangeur-caloduc. L’analyse est finalement valid&e par une exp&imentation et elle est montr6 applicable
aux problZmes de l’ingknierie.
ZusammenfassungpEs wurde ein Verfahren zur Untersuchung des thermischen Verhaltens von WLrmerohr-
Wlrmetauschern entwickelt, das auf einem Leitungs-Model1 basiert. Die spezifische Wgrmeleitfiihigkeit des
Wlrmerohreswurdemit HilfeeinesVersuchsamEinzelrohrermittelt.Zur Berechnungder Wlrmelbergangs-
Koeffizienten bei der Konvektion in Rohrbhndeln wurden die wohlbekannten universellen Korrelationen
verwendet. Damit wurde nach dem Finite-Differenzen-Verfahren ein Computer-Programm zur Berechnung
des thermischen Verhaltens von WBrmerohr-Wlrmetauschern entwickelt. Diese theoretische Untersuchung
wurde schliefilich experimentell iiberpriift und erwies sich fiir ingenieurmal3ige Anwendungen als geeignet.