Chapter 5
Chapter 5
Chapter 5
voltage control only controls the motor speed from zero to motor base speed. If higher motor
speeds are needed the motor field current can be lowered, however by doing this the available
torque at the motor armature will be reduced. Another advantage for this method is that the speed
of the motor can be controlled in both directions of rotation.
80.) Describe the operation of the simplified Ward Leonard system of control of Fig. 112, in which two
series machines are used. What important magnetic design features must the machine possess for a good
operation?
The controlling generator is driven by a prime mover; usually a constant speed ac motor and
speed control of the controlled motor is affected by shunting the series field on the generator with
a variable resistance. The terminal voltage of a series generator depends upon the series-field
current or excitation.
81.) How does the effect of armature reaction in motors differ from its effect in operators?
The armature current in a motor is opposite to that of a generator for the same direction of
rotation, it follows that the shift of the magnetic axis is opposite to the shift produced in the
generator. The result is that the magnetic neutral in a motor always tends to shift in a direction
opposite to that on the armature rotation.
82.) If no interpoles are used, how must the brushes be shifted in generators? In motors?
When the interpoles are not used, brushes must be shifted backward beyond the resultant
magnetic neutral, so that armature reactance may be effectively neutralized. It is only the way that
the currents in the coils may be made to reverse effectively and smoothly without the
objectionable commutator sparking.
83.) What are the polarities of the interpoles with respect to the main poles in generators? In motors?
The interpoles for dc motors are always made somewhat stronger than would be required to
neutralize the armature reaction flux in the interpole zones. He reason for this is exactly the same
way as was given in the discussion of generators; that is, the interpoles must help the commutated
coils generate sufficient voltage to overcome the reactance voltage due to the inductance and thus
anticipate the new current directions.
84.) Why is it possible to use half as many interpoles as main poles in some small motors? What
advantage would this have?
In small machine, it is often found possible to use half as many interpoles as main poles, thus
reducing the cost of manufacture. The reason for this practice is that the apan of every coil is 180
electrical degrees. Therefore, if an interpole is made doubly strong, its effect on one coil side is
equivalent to the action f two interpoles, each acting on one coil side.
85.) What two fundamental methods may be used to reverse a dc motor? Which is preferable in
compound machines?
The two fundamental methods for reversing the direction of rotation of a dc motor (1) changing
the direction of current flow through the armature and (2) changing the direction of current flow
through the circuit on circuits. In compound motor, it is necessary to reverse the current flow
through the armature winding only.
86.) When a DPDT switch is used in the field circuit of a shunt motor for reversing purposes, what
precaution must be taken when the motor is started? Is this precaution necessaty if the DPDT switch is
placed in the armature circuit?
CHAPTER 5
When the switch is closed to the left, the current will be down through both field and armature.
When the switch is closed to the right, the current will be up through the one of the elements and
down through the other. The wiring is much simpler when the first two method is used because
the reversal of the current through a single element.
87.) Describe the operation of the automatic reversing starter of Fig. 118.
It is provide with two acceleration contactors and resistors, designated by 1A, 2A and R1, R2.
Arrangement is made for armature reversing through forward contacts F and reversing contacts R.
The push button station is equipped with for and rev buttons, each of which, when pressed, closes
one set of contacts and simultaneously opens another set.
88.) Carefully explain why the control relay CR in Fig. 118 has a normally closed contact in the F
contactor circuit.
When the “for” button is pressed, the F contactor is energized and the R circuit is opened at f as a
safety measure; this seals the “for” button at F1, closes the F contacts and the current passes
through the armature circuit from a to b.
89.) In fig. 118, explain why each of the push buttons, “for” and “rev”, has one normally open and one
normally closed set of contacts.
The motor is permitted to come to rest; then, the “rev” button is pressed. This energizes the
control relay which opens normally and momentarily opens the contacts as a further safety
measure. The “for” button is pressed, the F contactor is energized and the R circuit is opened at f
as a safety measure; this seals the “for” button at F1, closes the F contacts and the current passes
through the armature circuit from a to b.
90.) What would happen in Fig. 118 if the “for” and “rev” buttons were pressed simultaneously?
It normally contacts then close to energize the contactor, and the operation of the latter seals the
reversing circuit, closes contacts and causes the main contacts to close. The motor now pick up
speed in the opposite direction since current passes through the armature circuit from b to a.
further actions of the proceed as explained for forward action.
CHAPTER 5
𝑉𝐵.𝐶 = 2 𝑉𝑂𝐿𝑇𝑆
AT NO LOAD:
𝐼𝐴 = 6 𝐴𝑀𝑃
𝑆𝑁.𝐿 = 180 𝑅𝑃𝑀
𝐼𝐿 = 62 𝐴𝑀𝑃.
SOLUTION:
LET: 𝐼𝑎.𝐹.𝐿 = 𝐼𝑆 𝑇𝐻𝐸 𝐴𝑅𝑀𝐴𝑇𝑈𝑅𝐸 𝐶𝑈𝑅𝑅𝐸𝑁𝑇 𝐴𝑇 𝐹𝑈𝐿𝐿 𝐿𝑂𝐴𝐷
𝐼𝐿 = 𝐼𝑆 𝑇𝐻𝐸 𝑅𝐴𝑇𝐸𝐷 𝐿𝐼𝑁𝐸 𝐶𝑈𝑅𝑅𝐸𝑁𝑇
𝐼𝑓 = 𝑆𝐻𝑈𝑁𝑇 − 𝐹𝐼𝐸𝐿𝐷 𝐶𝑈𝑅𝑅𝐸𝑁𝑇
𝐼𝐿 = 𝐼𝐴 + 𝐼𝑓
𝐼𝐴 = 62 − 2 = 60 𝐴𝑀𝑃.
SINCE:
CHAPTER 5
𝐼𝐴 (𝑅𝐴 + 𝑅) = 𝑉𝐴 − 𝐸𝐶 (0.8)
550−418.4
𝑅𝐴 + 𝑅 = (75)(0.7)
0.36 + 𝑅 = 2.5
𝑅 = 2.5 − 0.36
𝑅 = 2.14Ω, 𝑇𝐻𝐸 𝑉𝐴𝐿𝑈𝐸 𝑂𝐹 𝑅𝐸𝑆𝐼𝑆𝑇𝑂𝑅 𝐼𝑁𝑆𝐸𝑅𝑇𝐸𝐷 𝐼𝑁 𝑇𝐻𝐸 𝐴𝑅𝑀𝐴𝑇𝑈𝑅𝐸 𝐶𝐼𝑅𝐶𝑈𝐼𝑇.
17.) A 240-VOLT SERIES MOTOR HAS AN ARMATURE RESISTANCE OF 0.42 OHM AND A
SERIES-FIELD RESISTANCE OF 0.18 OHM. IF THE SPEED IS 500 RPM WHEN THE CURRENT
IS 36 AMP, WHAT WILL BE THE MOTOR SPEED WHEN THE LOAAD REDUCES THE LINE
CURRENT TO 21 AMP? (ASSUME A 3-VOLT BRUSH DROP AND THAT THE FLUX IS
PROPORTIONAL TO THE CURRENT)
GIVEN:
𝑉𝐴 = 240 𝑉𝑂𝐿𝑇𝑆
𝑅𝐴 = 0.42Ω
𝑅𝑆 = 0.18Ω
𝑆1 = 500 𝑅𝑃𝑀
𝐼1 = 36 𝐴𝑀𝑃
𝐼2 = 21 𝐴𝑀𝑃
𝑉𝐵.𝐶 = 3 𝑉𝑂𝐿𝑇𝑆
SOLUTION:
LET: 𝑆2 = 𝐼𝑆 𝑇𝐻𝐸 𝑈𝑁𝐾𝑁𝑂𝑊𝑁 𝑆𝑃𝐸𝐸𝐷 𝑂𝐹 𝑇𝐻𝐸 𝑀𝑂𝑇𝑂𝑅
SINCE:
21
THE CURRENT IS REDUCES FROM 36 AMP. TO 21 AMP. OR × 100% = 58.33% AND
36
THE FLUX IS PROPORTIONAL TO HE CURRENT
FLUX IS ALSO REDUCES BY 41.67%
THUS,
(𝑉𝐴 −𝑉𝐵𝐶 )−𝐼2 (𝑅𝐴 +𝑅𝑆 )
𝑆2 =
𝐾Φ
(240−3)−21(0.42+0.18)
𝑆2 = 0.4167 𝐾Φ
(𝑉𝐴 −𝑉𝐵𝐶 )−𝐼1 (𝑅𝐴 +𝑅𝑆 )
𝑆1 = 𝐾Φ
(240−3)−36(0.42+0.18)
𝑆1 = 𝐾Φ
𝑆2 237−12.6⁄
0.4167𝐾Φ
500
= 237−12.6⁄
𝐾Φ
214.4
𝑆2 = 500 [215.4 ] = 1194 𝑅𝑃𝑀
⁄0.4167