Design Features Report

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 6

Design Features Report

St. Valentine’s Hospital

Submitted To: Joshua Le Mon

Submitted By: Aishwarya Rajan


Antony George
Jofy.P.George
Needhu Paul
INTRODUCTION
This document serves as a design features report for the electrical design of St. Valentine’s
Hospital owned by St. Valentine’s Medical Group. The hospital is currently a double floor
building with identical floors. There are plans for two more identical floors to be built.
The ceiling height is 2.4m and floor area is 1500 sq. m. The total load is estimated, and
lighting options are suggested.

ESTIMATED LOAD
The load is estimated based on Power Density Limits taken from NZS4243.2:2007 and
lumped loads.
Item Total Area Lighting (w/m^2) Power (w/m^2) Total lighting(kw) Total power(kw)
Staff Room 62.2 15 25 0.933 1.555
O/N Room 108.9 17 15 1.8513 1.6335
Two Bed Ward 230.8 17 8 3.9236 1.8464
Four Bed Ward 189.84 17 15 3.22728 2.8476
Kitchen 31.26 15 160 0.4689 5.0016
Equipment Room 18.96 13 263.7130802 0.24648 5

Procedure Room
29.18 17 90 0.49606 2.6262
Medicine Room 19.9 10 150.7537688 0.199 3
Ensuite 84.6 10 6 0.846 0.5076

Clean Utility room


64.64 13 115 0.84032 7.4336

Dirty Utility Room


25.94 13 75 0.33722 1.9455
Store 26.58 13 20 0.34554 0.5316
Clean-up Room 89.94 15 7 1.3491 0.62958
Corridor 360 17 5 6.12 1.8
Staff Station 45.2 15 15 0.678 0.678
Wash Room 32 13 20 0.416 0.64
Whanau Room 40 13 15 0.52 0.6
22.7978 38.27618
Total 61.07398

Lumped Load Power (kW)


Lifts 20
Heating 100
Exterior Lighting 50
STP 200
Fire Pumps 100
Total 470

Total Estimated Load 531.07398 kW


663.842475 kVA
POWER SUPPLY
A new transformer of 750 kVA is to be installed on site. When the hospital is expanded a
second transformer or a new transformer should be installed.

LOW VOLTAGE MAIN SWITCHBOARD


A new 400V main switch board will be installed.

SUBMAINS AND RISERS & DB’S


New submains and distribution boards will be installed. A ring main is used to maintain
continuity of supply even during faults.

GENERAL REQUIREMENTS
 New floor DBs will be surface mounted metal enclosed type.
 The DB’s will be designed according to standard construction and generally used
miniature circuit breaker (MCB) protection for sub circuits and

Residual current device (RCD) or

Isolation Transformers for body protected patient areas

with Line Indication Monitors (LIM) according to ASNZS2500-2004


 DB’s within public spaces will be non-lockable and located within lockable
cupboards detailed by the architect.
 DB’s within service areas that are not required to be within cupboards will be
lockable.

EMERGENCY POWER SUPPLY


Emergency backup options available are:
 A 100% Backup generator of 750kVA for the current two floor hospital with
expansion of a similar generator when the hospital building is expanded.
 A backup generator of 1500kVA catering for the future expansion now itself.

UPS SUPPLY
 Local UPS as required has be provided by the client.
 Central UPS system with UPS distribution board on each floor. Higher cost
installation due to new riser cabling and additional floor DB’s.
EARTHING
 The earthing system is required.

SUB CIRCUIT CABLING


Sub circuit cabling to final outlets will be via two-compartment skirting trunking surface
mounted (one for power, one for communication), provided to the perimeter of all office
spaces.

LIGHTING
The standards NZS4243.2-2007+A1 Energy efficiency of large buildings and
ASNZS1680.2.5-2018 Interior and workplace lighting: Hospital and medical tasks are used to
determine the needed illumination in the various areas of the hospital and options of possible
lightings are given as below.
Light fittings are taken from Fagerhult Lighting’s catalogue. All lights are LEDs.

Staff rooms
Targeted Illumination to be 240lx
Pozzo I Delta
Recessed Mounting
Delta Louvre – microprism louvre in acrylic TPb (PMMA) with a thin opal diffuser
(acrylic/PMMA) on the inside.
Luminaires with Tunable White (2700-6500 K)
Effect, W 15

Scoot 65/35, DALI/Phase-pulse


Installation Two point suspension c/c 48 mm
Louvre Opal - opal acrylic diffuser
Effect, W 29

Wards
 General Lighting
Targeted illumination to be 160 lx
Eira Recessed, DALI/Phase-pulse
Installation Recessed Protection class 1 IP rating 20 Light control DALI/Phase-pulse
Effect, W 55

Discover Evo
Recessed or surface mounting on ceilings or walls
Effect W 19
 Evening Lighting
Targeted illumination to be 1 lx

Pleiad Wallwasher G3
A symmetrical downlight for lighting on walls.
e-Sense Tune – PIR sensor with presence, daylight control. Tuneable White and dynamic
light. Controlled with Bluetooth unit. RF communications for slaves.
Effect W 20
Aluflex Medica
Wall bracket installation
Effect W 6
 Examination Lighting
Targetted illumination to be 320 lx
Combinations of Aluflex Medica and Eira used as a directed light.
Whanau Room
Pleiad Wallwasher G3
A symmetrical downlight for lighting on walls.
e-Sense Tune – PIR sensor with presence, daylight control. Tuneable White and dynamic
light. Controlled with Bluetooth unit. RF communications for slaves.
Effect W 20

Appareo 40/60
Installation Two-point wire pendant. External ballast box is mounted directly to ceiling or
placed. Louvre Delta.
Effect W 43
Corridoors
Sektor
Ceiling or wall mounted.
Luminaire body and Lamell – lamell louvre in enamelled sheet steel.
Effect W 15

Pleiad Wallwasher G3
A symmetrical downlight for lighting on walls.
e-Sense Tune – PIR sensor with presence, daylight control. Tuneable White and dynamic
light. Controlled with Bluetooth unit. RF communications for slaves.
Effect W 20
Staff Station
Aluflex Medica
Wall bracket installation
Effect W 19
Pleiad Wallwasher G3
A symmetrical downlight for lighting on walls.
e-Sense Tune – PIR sensor with presence, daylight control. Tuneable White and dynamic
light. Controlled with Bluetooth unit. RF communications for slaves.
Effect W 20

All other areas


Discover Evo
Recessed or surface mounting on ceilings or walls
Effect W 19
Eira Recessed, DALI/Phase-pulse
Installation Recessed Protection class 1 IP rating 20 Light control DALI/Phase-pulse
Effect, W 55

POWER OUTLETS
 To serve the proposed areas of the hospital
 RCD/Isolation transform with Line Indication Monitors for patient protected areas

Ducting
In skirting trunking on perimeter of building
And - Directly in walls in internal areas
And - Floor boxes (Staff Stations)

You might also like