0% found this document useful (0 votes)
57 views3 pages

Diff Operating Characteristic - Otf:: Test Object - Differential Parameters

This document summarizes the results of a differential protection operating characteristic test on a transformer. The test was conducted on the primary and secondary windings of a 110kV/6.3kV transformer with a 16MVA rating. 10 test points were evaluated between 0.1 and 9.1 times the nominal current, with the differential current response compared to the expected characteristic. All 10 test points passed with deviations between the actual and nominal responses mostly within acceptable tolerance limits.

Uploaded by

Duna Flaviu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views3 pages

Diff Operating Characteristic - Otf:: Test Object - Differential Parameters

This document summarizes the results of a differential protection operating characteristic test on a transformer. The test was conducted on the primary and secondary windings of a 110kV/6.3kV transformer with a 16MVA rating. 10 test points were evaluated between 0.1 and 9.1 times the nominal current, with the differential current response compared to the expected characteristic. All 10 test points passed with deviations between the actual and nominal responses mostly within acceptable tolerance limits.

Uploaded by

Duna Flaviu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Diff Operating Characteristic.

otf:

Test Object - Differential Parameters


Protected Object:
Protected Object: Transformer
Vector Group: YD11
Winding/Leg Name: Primary Secondary
Voltage: 110.00 kV 6.30 kV
Power: 16.00 MVA 16.00 MVA
Starpoint Grounding: No No
Delta-connected CT: No No

CT:
Winding/Leg Name: Primary Secondary
CT Current Prim: 150.00 A 1500.00 A
CT Current Sec: 5.00 A 5.00 A
CT Grounding: tow. Prot. Obj. tow. Prot. Obj.
Gnd CT Prim Current: 200.00 A 800.00 A
Gnd CT Sec Current: 1.00 A 1.00 A
Gnd CT Grounding: n/a n/a

Protection device:
Reference Winding: Primary
Ibias Calculation: max ( Ip, Is ) (K1 = 1.00)
Zero Seq. Elimination: IL-I0
Reference Current: PO nominal current
Ground CT Used: No
Disable Comb. char.: Yes

Idiff>: 0.30 In tdiff>: 0.03 s


Idiff>>: 10.00 In tdiff>>: 0.03 s

Itol rel: 20.00 % ttol rel: 3.00 %


Itol abs: 0.05 In ttol abs: 0.01 s

Test Module
Name: OMICRON Diff Operating Version: 4.00
Characteristic
Test Start: 03-Oct-2019 11:24:52 Test End: 03-Oct-2019 11:28:19
User Name: D.FLW Manager:
Company:
Test Settings:

General Settings:
Testing: Primary / Secondary
Max. Test Time: 1.50 s Delay Time: 0.25 s
Prefault: No
Prefault current: 0.00 In Prefault time: 0.000 s
Vout enabled: No Vout winding: Primary
Time-triggered: No Winding/leg output: Primary

Search Test Settings:


Ignore Default Char.: No
Resolution Relative: 0.10 % Resolution Absolute: 0.010 In

Binary Outputs
Bin. out 1: 0
Bin. out 2: 0
Bin. out 3: 0
Bin. out 4: 0

Test Results for Fault Location R-S-T at Reference Side Primary


Idiff Check
Ibias Idiff Actual Dev (rel) Dev (abs) State Result
Nominal Test
0.10 In 0.300 In 0.311 In 3.75 % 0.0112 In Tested Passed
1.10 In 0.476 In 0.441 In -7.34 % -0.0349 In Tested Passed
2.10 In 0.916 In 0.806 In -12.02 % -0.1101 In Tested Passed
3.10 In 1.356 In 1.428 In 5.29 % 0.0718 In Tested Passed
4.10 In 1.796 In 2.222 In 23.70 % 0.4256 In Tested Passed
5.10 In 2.236 In 3.012 In 34.69 % 0.7756 In Tested Passed
6.10 In 2.826 In 3.801 In 34.51 % 0.9752 In Tested Passed
7.10 In 3.640 In 4.587 In 26.02 % 0.9471 In Tested Passed
8.10 In 4.453 In 5.381 In 20.82 % 0.9273 In Tested Passed
9.10 In 5.267 In 6.166 In 17.06 % 0.8989 In Tested Passed
Operating Characteristic Diagram
Idiff [In]

12
11
10
9
8
7
6
5
4
3
2
1
0
2 4 6 8 10 12 14 16
Ibias [In]

Test State:
Test passed
10 out of 10 points tested.
10 points passed.
0 points failed.