Design Guide For Cold-Formed Steel Trusses: Scholars' Mine
Design Guide For Cold-Formed Steel Trusses: Scholars' Mine
Scholars' Mine
Wei-Wen Yu Center for Cold-Formed Steel
Center for Cold-Formed Steel Structures Library
Structures
12-1-1995
Recommended Citation
Steel in Residential Construction Advisory Group, "Design guide for cold-formed steel trusses" (1995). Center for Cold-Formed Steel
Structures Library. 73.
https://scholarsmine.mst.edu/ccfss-library/73
This Report - Technical is brought to you for free and open access by Scholars' Mine. It has been accepted for inclusion in Center for Cold-Formed Steel
Structures Library by an authorized administrator of Scholars' Mine. This work is protected by U. S. Copyright Law. Unauthorized use including
reproduction for redistribution requires the permission of the copyright holder. For more information, please contact [email protected].
DESIGN GUIDE
FOR COLD-FORMED
STEEL TRUSSES
PUBLICATION RG-9518
DECEMBER 1995
Steel in Residential
Construction Advisory Group
This publication was developed by the American Iron and Steel Institute with guidance from the
AISI Residential Advisory Group. Special appreciation is given to Dr. Roger LaBoube as the
author and primary researcher, and to the Light Gauge Structural Engineers Association for their
valuable input. The development of this publication was funded by the American Iron and Steel
Institute and the National Science Foundation. This document is intended to provide designers
with guidance on design of cold-formed steel roof and floor trusses. AISI believes the information
contained in this publication substantially represents industry practice and related scientific and
technical information, but the information is not intended to represent an official position of AISI
or to restrict or exclude any other construction or design techniques.
building geometry. To alleviate the burden of defining the dy- assemblies. These guidelines do not preclude to use of more
namic wind load, an equivalent static load is used for struc- rigorous analysis or design assumptions as determined by ra-
tural design. The applicable building code or ASCE 7 may be tional analysis and/or testing.
used to define the minimum load intensity.
Unbraced Length
Rain Load The unbraced length of a compression member is defined
Rain loads only become a design consideration if adequate as either the center-to-center distance between truss panel
drainage systems are not provided. In such cases where such points, or connection spacing interval as prescribed by the mem-
drainage systems are not provided, rain loads must be addressed. ber design.
For guidance refer to ASCE 7. The effective length factor, K, may be determined by ra-
tional analysis and/or testing. In the absence of such analysis,
Seismic Load either of the following design alternatives may be used because
Design seismic load requirements attempt to convey the they give similar results:
complicated dynamic earthquake forces into simplified equiva- ( 1) Where a continuous compression chord, i.e. over one
lent static lateral forces. Definition of the minimum static lat- intermediate panel point, is used from heel to ridge of the truss,
eral forces is given by building codes or ASCE 7. Kx, Ky, and Kt may be taken as 0.75 when sheathing is at-
tached directly to the top flange of the top chord. For other
Other Load Considerations compression chords applications, Kx, Ky, and Kt may be taken
as unity.
In addition to the above commonly considered loads, the
design engineer must consider other load conditions. Such con- For web members which are assumed to be pinned at both
ditions may be unsymmetrical loads or hanging concentrated ends, Kx, Ky and Kt may be taken as unity.
loads. (2) For chords or web members in compression, the ef-
fective length may be taken as the distance between two adja-
Load Combinations cent points of contraflexure. The effective length factor is to
One or more of the above loads may occur during the life of be taken as unity.
a building. It is the responsibility of the design engineer to
determine the applicable loads and combination of loads that Cm and Cb
are to be considered. Design loads are to be combined based The end moment coefficient, Cm, maybe taken as 0.85, un-
on their probability of occurrence. Such combinations are speci- less a more rigorous analysis is performed to justify another
fied by building codes or ASCE 7. value.
For an unbraced segment, the strength amplification factor
STRENGTH PERFORMANCE Cb should be computed in accordance with Section C3.1.2 of
the Specification .
.a The members and connections of a truss must possess ad-
equate strength to safely support the design loads. Strength Compression Chord
determinations shall be in accordance with the Specification The compression chord should be evaluated for combined
for the Design of Cold-Formed Steel Structural Members. For axial load and bending behavior using Section C5 of the Speci-
situations not addressed by the Specification, design criterion fication (1986): at panel points, Specification Equation CS-2
shall be determined by test or rational analysis. applies and between panel points, use Specification Equation
C5-l.
Analysis
Between panel points, the compression chord should be
Applied forces and deflections are to be determined by ac- evaluated for axial load, and major axis bending. Specifica-
ceptable structural engineering procedures. In lieu of a rigor- tion Equation C5-l applies with Lx and Lt equal to the dis-
ous analysis to define joint flexibility, the following analysis tance between the panel points. Ly is taken as the distance
model assumptions may be used: between sheathing connectors to the top chord, or the distance
Chord- Assume the member is continuous, except at between braces.
the member's ends, assume pin ends. A splice must
be designed for the forces applied to it. Tension Chord
Webs -Assume the member connections to be pins at The tension chord is to be designed for both axial loaded
each end. and bending. The axial load may be taken as acting through
the centroid of the section.
Member Design Issues Tension Web Members
The following design guidelines are based on available in- For a web member connected to the web of the chord mem-
formation pertaining to the behavior of cold-formed steel truss bers, or connected to gusset plates, the axial tension load may
4
RESIDENTIAL STEEL FRAMING
ii~·!
~e
Truss
'hied~
as not to induce additional unintentional secondary stresses into line. Deflections are read on a scale with a mirror backing.
the test truss as it deforms under load. The mirror-scale deflection measuring device is read by visu-
Where lateral support is used, it shall not interfere with the ally lining up the top of the wire with its image on the mirror
free in-plane displacement of the truss assembly. The test and then reading the scale.
trusses shall not be laterally supported in a manner that will Other commonly used deflection measuring devices are such
exceed that intended in a typical installation. Lateral bracing things as direct reading micrometer dial gages, optical levers
used to read scales attached to the truss, linearly variable dif-
between trusses tested in pairs shall be installed in a manner to
ferential transformers (LVDT), or a combination of flexible
prevent both trusses from buckling together. Care shall be taken wire attached at deflection points and monitored remotely
when testing a single truss horizontally to keep the test truss through a system of pulleys attached to dial gages. Deflection
flat to minimize any adverse lateral displacement caused by readings and measuring devices shall have an accuracy of ±
gravity. 2% of design load deflection.
The loading devices shall result in the desired truss loading Strain measurements may be taken on truss elements using
situation regardless of whether uniform, concentrated, or a com- electrical or mechanical strain gages. Approximate stress dis-
bination of both. The loading system shall be such as to allow tribution and magnitude may be observed by the application of
special brittle lacquers made by personnel experienced in the
the application of loads during the test to approximate the over- application and operation of the methods employed on the ma-
all intended in-service load distribution. Care should be taken terial being tested.
to avoid eccentrically applied loads unless this type of loading
is desired. Loading Procedures
When loads are to be applied using dead weight, such as Both dead and superimposed load must be considered when
sand, masonry units, or water, the arrangement of dead load performing a load test. Because these loads are independent
material shall be such as to prevent any arching action that can load types, they must be introduced independently.
seriously alter the intended load pattern. When water is used, Initially the design dead load must be applied. This load
care shall be taken to compartmentalize the water in cells to should be held for no less than 5 minutes. at which time de-
prevent a non-uniform load as the truss and elements deflect. flection readings should be recorded. These deflections are to
Uplift forces such as those caused by wind loads may be be considered the dead load deflections. The design dead load
simulated by reversing the direction of the applied gravity loads; must be maintained during the duration of the load test.
or if the fixture will permit it, testing the truss upside down. It As a minimum, the dead load and total design load dellec-
is preferable to test the truss in its normally installed orienta- tions should measured along the bottom chord at midspan and
tion in order to more typically allow for the uplift forces work- at quarter points. When testing trusses in pairs. the dellections
ing against gravity forces. of two trusses at corresponding locations may be averaged.
When deflection measuring systems that do not compen-
Load and Deflection Measuring Devices sate for support settlement are used, measurement of support
displacement under load is needed to obtain an accurate load-
Loads may be measured using one or more of the following
deflection response.
devices. Pressure gages or hydraulic load cells can be incor-
Although the superimposed load increments may vary with
porated into a hydraulic loading system. These devices must
the intent of the test, satisfactory load-response data can usu-
be calibrated with the jacks or cylinders at different positions
ally be obtained if each of the first four increments of load
of piston travel to ensure a true loading history. Spring dyna-
does not exceed 25ck of the total design live/snow load. Load
mometers, electronic load cells, or the weighing tables of uni-
shall be slowly applied to the truss assembly so as to provide a
versal testing machines have also been successfully used. The static loading condition. The above mentioned load increments
load measuring device or devices used shall be capable of apply to both uniform and concentrated loads.
measuring loads to an accuracy of ± 2% of design load.
The confirmatory test load may be achieved by applying
Deflection readings may be taken in a variety of ways. One load in equal increments of 0.10 times the calculated nominal
of the simplest methods is by the use of a taut wire or mono- load. Nominal load is the design load multiplied by the im-
filament line stretched between supports in combination with plied design factor of safety. If the confirmatory test load is
a mirror-scale located at the desired deflection measuring points. achieved without failure of the truss. the test may be halted.
Such a device avoids any magnification of defection readings
due to a settlement of supports during loading. When the taut Interpretation of Test Results
wire method is used, care must be taken to ensure that the wire Evaluation of the test results shall be made in accordance
will remain under tension during the entire test. This can be with F2 Tests for Confirming Structural Performance of the
accomplished by incorporating a spring into the line or by let- Specification for the Design of Cold-Formed Steel Structural
ting one end run over a pulley with a weight attached to the Members.
6
RESIDENTIAL STEEL FRAMING
,~~teet·,1
li Truss
"'6 • '!I.e
'hted ;.,.o
APPENDIX A with the state's statues and regulations governing the profes-
STANDARD PRACTICE sional registration and certification of architects or engineers.
Also referred to as truss engineer, design engineer, registered
FOR COLD-FORMED STEEL TRUSS engineer, and engineer, but hereinafter will be referred to as
DESIGN RESPONSIBILITIES truss designer.
1.2.9 "Truss Design Drawing" shall mean the graphic de-
1.0 SCOPE AND DEFINITIONS piction of an individual Truss prepared by the truss designer.
1.2.10 "Truss Manufacturer" shall mean an individual or
1.1 This standard defines the design responsibilities of organization regularly engaged in the manufacturing of trusses.
the individuals and organizations involved in the preparation, 1.2.11 "Truss Placement Plan" is the drawing identifying
submittal, review and approval of each truss design drawing the location assumed for each Truss based on the truss
and truss placement plan associated with the use of cold-formed manufacturer's interpretation of the construction design docu-
steel trusses. These guidelines are presented as industry stan- ments.
dard practice. The guidelines are not intended to preclude al-
ternate provisions as agreed upon by the parties involved. 2.0 OWNER RESPONSIBILITIES
1.2 The following definitions shall apply:
2.1 Directly or through its representatives. which may
1.2.1 "Architect" shall mean the individual registered ar- include the contractor and/or building designer: (a) review
chitect responsible for the architectural design of the structure and approve each truss design drawing; (b) review and ap-
and who produces the architectural drawings included in the prove the truss placement plan; (c) resolve and approve all
design issues arising out of the preparation of each. tntss de-
construction design documents.
sign drawing and truss placement plan: and {d) coordinate the
1.2.2 "Building Designer" is the individual or organization return of each approved truss design drawing and truss place-
having responsibility for the overall building or structure de- ment plan to the truss manufacturer prior to truss manufactur-
sign in accordance with the state's statutes and regulations gov- mg.
erning the professio.nal registration and certification of archi-
tects or engineers. This responsibility includes but is not lim- 3.0 BUILDING DESIGNER RESPONSIBILITIES
ited to foundation design. structural member sizing, load trans-
3.1 Design a structure suitable to ensure that the intended
fer, bearing conditions, and the structure's compliance with the function of each truss is not affected by adverse intluenccs including.
applicable building codes. Also referred to as registered archi- but not limited to, moisture, temperature, corrosive chemicals and
tect or engineer, building designer, and registered building de- gases;
signer, but hereinafter will be referred to as building designer. 3.2 Prepare the construction design documents. showing
1.2.3 "Construction Design Documents" are the architec- all trussed areas, which must provide as a minimum the fol-
tural drawings, structural drawings, mechanical drawings, elec- lowing:
trical drawings, and any other drawings, specifications, and 3.2.1 All truss orientations and locations:
addenda which set forth the overall design of the structure and 3.2.2 Information to fully determine all truss profi lcs:
issued by the building designer 3.2.3 Adequate support of the truss and all truss bearing
1.2.4 "Contractor" shall mean the individual or organiza- conditions;
tion responsible for the field storage, handling, and installa- 3.2.4 Permanent bracing design for the structure includ-
tion of trusses including, but not limited to, temporary bracing, ing the trusses, except as provided in 3.4 and 6.2.11.
permanent bracing, anchorage, connections and field assem- 3.2.5 The location, direction and magnitude of all dead and
bly. The term "Contractor" shall include those subcontractors live loads applicable to each truss including. but not limited to.
who have a direct contract with the Contractor to perform all loads attributable to: roof, floor. partition. mechanical. fire sprin-
or a portion of the storage, handling, and installation of the kler, attic, storage, wind, snow drift and seismic;
trusses. 3.2.6 All truss anchorage designs required to resist uplift.
1.2.5 "Engineer-of-Record" shall mean the registered pro- gravity, and lateral loads:
fessional engineer for the structural design of the structure and 3.2.7 Allowable vertical and horizontal detlection criteria:
who produces the structural drawings included in the construc- 3.2.8 Proper transfer of design loads affecting the truss:
tion design documents. and
1.2.6 "Owner" shall mean the individual or organization 3.2.9 Adequate connections between truss and non-truss
for whom the structure is designed. components, except as noted in Section 6.2X
1.2.7 "Truss" is an individual cold-formed steel open web 3.3 Review and approve the truss placement plan and
structural component manufactured by the truss manufacturer. each truss design drawing for conformance with the require-
ments and intent of the construction design documents. thee f-
1.2.8 'Truss Designer" is the design professional, individual fect of each truss design drawing and truss placement plan on
or organization, having responsibility for the design of the cold- other parts of the structure, and the effect of the structure on
formed steel truss. This responsibility shall be in accordance each truss.
'hlecl ~
~·
3.4 Specify permanent lateral bracing where indicated 6.2.4.2 Top chord dead load;
by the truss designer on the truss design drawings, to prevent 6.2.4.3 Bottom chord live load;
buckling of the individual truss members due to design loads. 6.2.4.4 Bottom chord dead load;
The building designer shall specify how the permanent lateral
6.2.4.5 Concentrated loads and their points of appli-
bracing is to be anchored or restrained to prevent lateral move-
cation; and
ment if all truss members, so braced, buckle together. This shall
6.2.4.6 Controlling wind and earthquake loads;
be accomplished by: (a) anchorage to solid end walls; (b) per-
manent diagonal bracing in the plane of the web members; or 6.2.5 Each reaction force and direction;
(c) other means when demonstrated by the Building Designer to
provide equivalent bracing. 6.2.6 Joint connector type (gusset plate, etc.), size, thickness;
6.0 TRUSS DESIGNER RESPONSIBILITIES Harper, M. M., LaBoube, R. A., and Yu, W. W. (1995), "Behavior of
Cold-Formed Steel RoofTrusses," Summazy Report, Civil Engineer-
6.1 Prepare the truss design drawings using the "DESIGN ing Study 95-3, Cold-Formed Steel Series, Center for Cold-Formed
GUIDE FOR COLD-FORMED STEEL TRUSSES". Steel Structures, Department of Civil Engineering, University of Mis-
souri-Rolla, Rolla, MO
6.2 For each truss design drawing, set forth as a minimum Minimum Design Loads forB uildings and Other Structures ( 1995),
the following:
American Society of Civil Engineers, ASCE 7-93, New York, NY
6.2.1 Slope or depth, span and spacing; Specification for the Design of Cold-Formed Steel Structurdl Mem-
6.2.2 Location of all joints; bers ( 1986), with 1989 Addendum,American Iron and Steel Institute,
Washington, OC
6.2.3 Required bearing widths;
Specification for Structural Steel Buildings Allowable Stress Design
6.2.4 Design loads as applicable; and Plastic Design ( 1989), American Institute of Steel Construction, Chi-
6.2.4.1 Top chord live load (including snow loads); cago,IL