Siemens Firmware Update

The document summarizes the steps taken to perform a firmware update on a Siemens 7SJ8021 relay from version 04.74.05 to 04.77.03. This involved downloading the necessary device drivers and firmware update files from the Siemens website, connecting to the device to download settings, and performing the update without changing parameter sets as recommended. During the update process, communication errors were encountered but resolved by changing COM ports and device addresses. The updated firmware required modifying parameter sets in DIGSI software to finally enable successful communication with the relay.

Uploaded by

in4meganesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
841 views2 pages

Siemens Firmware Update

The document summarizes the steps taken to perform a firmware update on a Siemens 7SJ8021 relay from version 04.74.05 to 04.77.03. This involved downloading the necessary device drivers and firmware update files from the Siemens website, connecting to the device to download settings, and performing the update without changing parameter sets as recommended. During the update process, communication errors were encountered but resolved by changing COM ports and device addresses. The updated firmware required modifying parameter sets in DIGSI software to finally enable successful communication with the relay.

Uploaded by

in4meganesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Siemens Firmware Update

Location: Marmul – DWD – New 33kV GIS – SIEMENS – Panel – L4

Feeder: To DWD Pump - P1565, 5.4MW, 33/11.5kV

Date: 22/09/2019

Relay: 7SJ8021 – 5EB96 – 1FA0 / DD

Author: J Ganesh

Old Firmware: 04.74.05 New Firmware: 04.77.03


Old Parameter set: 04.74.05 New Parameter Set: 04.77.03

STEPS:

1. Download Digsi Device driver from Siemens website and install in PC


 7SJ80x_V047703_GerTreiDig0492_V01.00.00.exe
2. Download Firmware update from Siemens website and install in PC
 Setup_7SJ80x_04.77.03.EXE
3. Connect to Device & download settings via Plug & Play.
 Use selection USB instead of Direct during connection
4. Proceeded without Parameter set update as recommended in the manual
 If the firmware update changes the designation of the version only by the second number
behind the decimal point, (e.g. from V4.02 to V4.03), then the existing parameter set
does not need to be updated (for exception's see appendix table 1). In this case you may
skip this chapter from now on and reload the stored parameter set into the device after
the firmware update using DIGSI.
5. No need to open DIGSI for firmware update.
6. Start the Firmware update ICON created on the Desktop during Step 2.
7. Started update but error pops up, “COM1 NOT OPEN”
 In the same update window select PREFERENCE, select available ports COM5, COM6 etc
8. Updated in <3 minutes.
9. Confirmed communicating with default variant created during step.3
10. Insert new device with MLFB version in DISI and tried communicating.
 No communication
11. Found the device VD address in the MLFB version is different from default. Changed the MLFB
version VD address with the default address.
12. Started communication with relay via DIGSI but ended with error
 Unable to combine settings
 Internal fault
 Unable to continue device processing
13. Under Object properties, found the following,
 New MLFB version – Parameter set: V4.77.03
 Old Default version – Parameter set: V4.74.05
14. Keep a second copy of default variant.
15. With copy of default variant, right click and select “update parameter set”
 This updates the parameter set in DIGSI and not in device
16. From Default variant with updated parameter set connect by “DiGSI to DEVICE”
 After succesfull communication the Device P.SET is updated to new Version.
17. Now start communication with device again via created MLFB variant.
 Device to PC
 Finally successful
18. But still the DEVICE CONFIGURATION is in Disabled mode.
 But found enabled in offline mode, do changes in offline mode & send to relay.
19. FINISH.