K5Bmc Electronic Interlocking Manual: Engineer Level
K5Bmc Electronic Interlocking Manual: Engineer Level
K5BMC
ELECTRONIC
INTERLOCKING
MANUAL
ENGINEER LEVEL
Troubleshooting Manual
© 2014 Kyosan Electric Mfg. Co., Ltd., All Rights Reserved, Printed in
Japan
THIS DOCUMENT AND ITS CONTENTS ARE THE PROPERTY OF KYOSAN ELECTRIC MFG. CO., LTD.
FURNISHED TO YOU ON THE FOLLOWING CONDITIONS : (1) NO RIGHT OR LICENSE IN RESPECT
TO THIS DOCUMENT OR ITS CONTENTS IS GIVEN OR WAIVED IN SUPPLYING THIS DOCUMENT TO
YOU. (2) THIS DOCUMENT OR ITS DETRIMENT ARE NOT TO BE COPIED, REPRODUCED,
DISCLOSED TO OTHERS, OR DISPOSED OF EXCEPT WITH PRIOR WRITTEN CONSENT.
Ver.
Date Nature of Revision Author(s)
No.
1 14.Mar.2014 First Edition Y. Kanno
2
3
Table of Contents
1 INTRODUCTION ............................................................................................................................ 8
2.5 SPHC-TT/PW............................................................................................................................. 14
3 TROUBLESHOOTING.................................................................................................................. 16
5.1.4 SPHC-TT.................................................................................................................................... 74
6 RECOVERY PROCEDURES......................................................................................................... 85
6.1.1.1.1 DC24/DC5.......................................................................................................................... 85
6.1.1.1.2 DC24/DC24........................................................................................................................ 86
6.1.1.2.2 IC CARD............................................................................................................................ 88
6.1.1.4.1 CTRL DATA RX, INDIC. DATA TX, ET CH4 TX, ET CH5 TX........................................ 97
6.1.2.1 LINE2B.................................................................................................................................. 99
6.1.2.1.1 DC24/DC5.......................................................................................................................... 99
6.1.3.4 ZSIO2....................................................................................................................................111
6.2.1.1 LINEM2................................................................................................................................114
6.2.1.1.1 DC24/DC5.........................................................................................................................114
6.2.1.2 MMIF2..................................................................................................................................117
1 Introduction
This manual provides general guidelines for troubleshooting and recovery of
K5BMC Electronic Interlocking System.
Personnel in charge of troubleshooting are requested to read thoroughly this
manual to ensure the safety of people and operation of the equipment.
2 Sub-rack Configurations
This section describes the sub-rack configuration used for K5BMC EI system.
a b cd
System 1 System 2
Front
a. IPU6C card
b. F486-4I card
c. FSIO card
d. FSIO-Ex
e f g h
System 2 System 1
Rear
e. EXTFIO7P card
f. FIO7-[P] card
g. DID card
h. IPU6C power input terminal
a b
Front
Rear
a. LINE2B card
b. PIO2-LOG card
c. LINE2B power input terminal
d. Optical Line Input
a b c
Front Rear
a. LINEM2 card
b. MMIF2 card
c. LINEM2 power input terminal
a b c d
Front
Rear
a. ZPEN3 card
b. ZNIO2-S1 and ZNIO2-S2 card
c. ZSIO2 card
d. KDD172-KY48-2 card
2.5 SPHC-TT/PW
System 1 System 2
Front
a. SPHC-TT card
b. SPHC-PW card
System 2 System 1
c d
Back
c. SPHC-PW power input terminal
d. SPHC-PW power output terminal
e. SPHC-TT power input terminal
3 Troubleshooting
If malfunction occurs, try the following steps to resolve the problem.
Malfunction
occured
Check if MTC is
operational
(refer to section 3.1)
YES NO
Operational?
YES
Recovered?
NO
Refer to section 4
Refer to
section 5
NO
Recovered?
YES
End
Operator
Console
(OPC)
Maintenance
Console
(MTC)
Start
NO
refer to section 4.2.1
Other
malfunctioned
rack/block
Return
Start
Malfunctioned
Sub-rack
Return
Start
YES
IPU6C card?
NO
refer to section 4.2.1.1.1
YES NO
Recovered?
Other
malfunctioned
units
F486-4I and DID card FSIO and FIO7-[P] card FSIO-EX and EXTFIO7P card
Return
Start
Malfunctioned part
DC24/DC5 DC24/DC24
NO YES
Recovered?
Return
Start
Malfunctioned part
CPU/ROM/RAM IC card Ctrl Data Tx Indic. Data Tx Inter-sys Tx/Rx Rx Inter-sys Tx/Rx Tx DID
refer to section refer to section refer to section refer to section refer to section refer to section refer to section
6.1.1.2.1 6.1.1.2.2 6.1.1.2.3 6.1.1.2.4 6.1.1.2.5 6.1.1.2.6 6.1.1.2.7
Return
Start
Malfunctioned part
Return
Start
Malfunctioned part
Return
Start
YES
LINE2B card?
NO
refer to section 4.2.1.2.1
YES NO
Recovered?
YES
ET-PIO2 card?
NO
refer to section 4.2.1.2.2
Return
Start
YES
DC24/DC5?
NO
refer to
section 6.1.2.1.1
Other
malfunctioned
part
refer to refer to
section 6.1.2.1.2 section 6.1.2.1.3
NO YES
Recovered?
Return
Start
YES
DC24/DC5?
NO
refer to
section 6.1.2.2.1
Other
malfunctioned
part
Return
Start
KDD172-KY48-2 YES
card?
NO
refer to section 6.1.3.1
YES NO
Recovered?
Other
malfunctioned
unit
Return
Start
refer to
section 4.2.2.1
Return
Start
YES
LINEM2 card?
NO
refer to section 4.2.2.1.1
YES NO
Recovered?
YES
MMIF2 card?
NO
refer to section 4.2.2.1.2
Return
Start
YES
DC24/DC5?
NO
refer to
section 6.2.1.1.1
Other
malfunctioned
part
refer to refer to
section 6.2.1.1.2 section 6.2.1.1.3
NO YES
Recovered?
Return
In this screen, the indication of I/O port and the right side from No.1 to 64 shall
be totally colored gray, since there is no indication condition.
Start
Malfunctioned
part
Return
Check the
Logic Rack
(refer to section 5.1)
NO YES
Recovered?
Check the
ET Rack
(refer to section 5.1.2)
YES
Recovered?
NO
Check the
CCIP
(refer to section 5.2)
Check the
MTC
(refer to section 5.3)
Check the
OPC
(refer to section 5.4)
Return
Start
Return
Start
IPU6C card NO
Recovered?
YES
Return
PW ON = Normal
Start
YES
Normal?
NO
NO YES
Recovered?
Return
WT Blinking = Normal
Start
YES
Normal?
NO
NO YES
Recovered?
NO YES
Recovered?
NO YES
Recovered?
Return
Start
YES
All normal?
NO
Malfunctioned part
Return
Start
YES
All normal?
NO
Malfunctioned part
ET CH4 Rx ET CH5 Rx
ET CH4 Tx/
ET CH5 Tx
Return
NO
Recovered?
YES
Return
Start
YES
Normal?
NO
NO YES
Recovered?
Return
Start
YES
Normal?
NO
Return
Start
NO
Recovered?
YES
Return
Start
YES
All normal?
NO
Return
WT LED ON = Normal
Start
YES
Normal?
NO
Return
Start
YES
Normal?
NO
Return
Start
YES
Normal?
NO
Return
5.1.4 SPHC-TT
Start
YES
Normal?
NO
NO YES
Recovered?
Return
Start
NO
Recovered?
YES
Return
Start
YES
Normal?
NO
NO YES
Recovered?
Return
LED 5 ON = Tx Normal
LED 6 ON = Rx Normal
Start
YES
All Normal?
NO
Malfunctioned
part
ET Ctrl ET Indic.
Data Rx Data Tx
refer to refer to
section 6.2.1.2.1 section 6.2.1.2.2
Return
Start
YES
Normal?
NO
NO YES
Recovered?
NO YES
Recovered?
NO YES
Recovered?
Return
Start
YES
Normal?
NO
NO YES
Recovered?
NO YES
Recovered?
NO YES
Recovered?
Return
6 Recovery Procedures
This section contains a series of flowcharts and figures that describe the
procedures and possible solutions to recover from malfunction that occurred.
Unit replacement might be required to recover from malfunction. However, if
spare parts are not available for replacement, skip and try to proceed to the next
step to resolve the problem.
Start
NO YES
21.6V to 26.4V?
NO YES NO YES
21.6V to 26.4V? 5V to 5.25V?
Return
6.1.1.1.2 DC24/DC24
Start
NO YES
21.6V to 26.4V?
NO YES NO YES
21.6V to 26.4V? 21.6V to 26.4V?
Return
Start
NO YES
Recovered?
Return
6.1.1.2.2 IC CARD
Start
NO YES
Recovered?
NO YES
Recovered?
Return
Start
YES NO
Normal?
Return
Start
YES NO
Normal?
NO YES
Recovered?
Change FSIO or
FSIO-EX card
(refer to sections 7.1 and 7.2)
Return
Start
YES NO
Normal?
NO YES
Recovered?
Return
Start
NO YES
Recovered?
Return
6.1.1.2.7 DID
Start
YES NO
Normal?
NO YES
Recovered?
Return
Start
NO YES
Recovered?
Return
6.1.1.3.2 MTC CH Rx
Start
NO YES
Recovered?
NO YES
Recovered?
Return
6.1.1.3.3 ET CH1/CH2/CH3 Rx
Start
Check that ET CH is
connected to
Electronic Terminal
(CN1R & CN1T/CN2R &
CN2T/CN3R & CN3T of
FIO7-[P])
YES NO
Connected?
NO YES
Recovered?
NO YES
Recovered?
Return
Start
NO YES
Recovered?
Return
6.1.1.4.2 ET CH4/CH5 Rx
Start
YES NO
Connected?
NO YES
Recovered?
NO YES
Recovered?
Return
NO YES
21.6V to 26.4V?
NO YES NO YES
21.6V to 26.4V? 5V to 5.25V?
Return
Start
NO YES
Recovered?
Return
Start
NO YES
Recovered?
Return
6.1.2.2 ET-PIO2
6.1.2.2.1 DC24/DC5
Start
NO YES
21.6V to 26.4V?
NO YES
21.6V to 26.4V?
Return
Start
NO YES
Recovered?
NO YES
Recovered?
NO YES
Recovered?
Return
Start
NO YES
Recovered?
NO YES
Recovered?
Return
Start
Restart the
PIO2-LOG card
(refer to section 9.2.2)
NO YES
Recovered?
Change the
PIO2-LOG card
(refer to sections 7.1 and 7.3)
YES NO
Recovered?
YES Malfunction NO
occured
again?
Return
Start
Restart the
PIO2-LOG card
(refer to section 9.2.2)
NO YES
Recovered?
NO YES
Recovered?
Change the
ET-PIO Sub-rack
Return
YES DC24V NO
LED OFF?
NO YES
21.6V to 26.4V?
Restart the
NO YES KDD172-KY48-2 card
21.6V to 26.4V?
(refer to section 9.3)
Return
6.1.3.2 ZPEN3
Start
Restart the
Journal Module
(refer to section 9.3)
NO YES
Recovered?
Return
6.1.3.3 ZNIO2
Start
YES NO
Normal?
NO YES
Recovered?
NO YES
Recovered?
Return
6.1.3.4 ZSIO2
Start
NO YES
Normal?
NO YES
Recovered?
NO YES
Recovered?
Return
6.1.3.5 SPHC-TT
Start
NO YES
5V to 5.25V?
NO YES
5V to 5.25V?
NO YES
21.6V to 26.4V?
NO YES
21.6V to 26.4V?
Return
NO YES
21.6V to 26.4V?
NO YES NO YES
21.6V to 26.4V? 5V to 5.25V?
Return
Start
NO YES
Recovered?
Return
Start
NO YES
Recovered?
Return
6.2.1.2 MMIF2
6.2.1.2.1 ET Ctrl Data Rx
Start
NO YES
Recovered?
NO YES
Recovered?
NO YES
Recovered?
Return
Start
NO YES
Recovered?
NO YES
Recovered?
Return
Start
Restart the
MMIF2 card
(refer to section 9.5.2)
NO YES
Recovered?
Return
7 Handling Methods
7.1 Card and IC Card replacing method
If the card fails sporadically, or F486-4I card is replaced, or LDC circuit
diagram is modified, replace the card and IC Card and maintain the equipment.
7.1.1 Card Replacing Method
(a) Removing the card
Turn OFF the power switch of each card. Remove card fixing screws.
Next, pull out the card straight.
Unfitted
Fit the card with
for the
the rail, and
insert the card
Push the
After this,
button
Pull out the
fully
Card
Inject
WARNING
!
If the power switch is inadvertently turned OFF, the EI
equipment might fail or stop functioning. Do not switch OFF
the Logic Module in operation.
CAUTION
!
The EI Logic Module consists of a number of cards. If a card
is inserted into an incorrect slot, the card might fail and
interlocking functions might stop.
Because the power card is hot, when replacing the card, grip
the front panel with both hands. Otherwise, your hands might
be scalded.
WARNING
!
Do not turn OFF the power switch without performing
prescribed preparations, otherwise Electronic Interlocking
functions might stop.
CAUTION
!
When replacing a card, pull out the card board while taking
care not to insert finger etc. between the housing and the card.
If you drop the card board, the card might fail or you might be
injured.
Because the power card is hot, when replacing the card, grip
the front panel with both hands. Otherwise, your hands
might be scalded.
Cabling precautions
Minimum bending
30(mm)
radius
Short permissible
98(N)
tension
WARNING
!
Do not bend an optical fiber with a radius of less
than rated
value. Otherwise, the optical fiber might break
down.
CAUTION
!
Do not disassemble the optical fiber cable.
Otherwise, the optical fiber connector or cable may
be destroyed.
1 2
2
1
24Vdc
output terminal
5Vdc
output terminal
Front
24Vdc from
DC/DC converter
Back
5Vdc
output terminal
Front
24Vdc
input terminal
Back
5Vdc
output terminal
Front
24Vdc
input terminal
Back
Journal Module
24Vdc input
terminal
8.5 SPHC-TT/PW
SPHC-TT 5Vdc
SPHC-PW 24Vdc
input terminal
input terminal
Back
9 Power Switches
This section describes the units with power switches used to turn on/off the unit
itself or the whole sub-rack where the unit belongs in some cases.
9.2.2 PIO2-LOG
9.4 SPHC-TT/PW
System 2 System 1
9.5.2 MMIF2
9.6 MTC/OPC