BEAMS
Slab with beam between columns along exterior panels shall
be considered if f >0.8, in this case take f= 1.2.
Beam width equal CMU width = 400mm
f = Ib3 / IS3 = 400x hb3 /(4550x 2803 ) = 1.2
h=668 » 700mm.
REINFORCEMENT
**Longitudinal reinforcement: chapter 10 ACI318-14
• Min. reinf. ≥ 0.01 Ag,
• Max. reinf. ≤ 0.08 Ag, applies at all sections, including splice
regions, this means Max. reinf. not exceed 0.04Ag if the
COLUMN # 1
• From foundation up to 3rd floor
PU1=10X1.1X(17.5X22.75+(5+4.55)X23)= 6800 KN
Ag = 2x6800x10³/40 = 1340x10³ mm2
column Dim. = 583x583 » 600x600 mm
As = 16T20
• From 3rd floor up to 6th floor
PU1=6X1.1X(17.5X22.75+(5+4.55)X23)= 4756.87 KN
Ag = 2x 4756870 / 40 = 204000 mm2
column Dim. = 500x475 » 500x500 mm
As = 12T20
COLUMN # 1
• From 6th floor up to roof
PU1=4X1.1X(17.5X22.75+(5+4.55)X23)
= 2718.2 KN
COLUMN # 2
• From foundation up to 3rd floor
PU2=10X1.1X(17.5X45.5+10X23)= 11290KN
Ag = 2x 11290,000 / 40 = 564500 mm2
column Dim. = 700x800 mm
As = 24T20
• From 3rd floor up to 6th floor
PU2=7X1.1X(17.5X45.5+10X23)= 7902.125KN
Ag = 2x 7902125/ 40 = 395103 mm2
column Dim. = 700x564 » 700x600 mm
As = 18T20
COLUMN # 2
• From 6th floor up to roof
PU2=4X1.1X(17.5X45.5+10X23)= 4515.5KN
Ag = 2x 4515500 / 40 = 169350 mm2
column Dim. = 700x320 >> 700x400mm
As = 14T20
COLUMN # 3
From foundation to 3rd floor up to roof
PU3=10X1.1X(17.5X89)= 17132.5KN
Ag = 2x 17132,500 / 40 = 8566250 mm2
column Dim. = 800x10700 » 800x1100mm
As = 28T25
From 3rd floor up to 6th floor
PU3=7X1.1X(17.5X89)= 11992.75KN
Ag = 2x 11992,750 / 40 = 59963.7.5 mm2
column Dim. = 800x749 » 800x800mm
As = 24T25
COLUMN # 3
From 6th floor up to roof
PU3=4X1.1X(17.5X89)= 6853KN
Ag = 2x 6853,000 / 40 = 34265 mm2
column Dim. = 800x428 » 800x500mm
As = 18T20
MODELING
STAGE