Earthing Calculation
Earthing Calculation
Facility (CPF)
Khazzan Project
Security Classification:
Project Internal Contract No. CO-BPXO-12-0376
Rev
KZ01-EL-CAL-53-0002 B021
Khazzan Project CALCULATION – EARTHING SYSTEM
Revision History
Amendment Revision Amender Amendment
Date Number Initials
Related documents
Document number Document name Description of Content
Section 1.2
Holds
Section Number Short Description of Hold
Table of Contents
1 INTRODUCTION.................................................................................................................................. 4
1.1 PURPOSE............................................................................................................................................... 4
1.2 REFERENCE PROJECT DOCUMENTS................................................................................................ 4
1.3 ABBREVIATIONS AND DEFINATION..................................................................................................... 4
2 EARTHING SYSTEM DESIGN............................................................................................................ 5
2.1 DESIGN BASIS....................................................................................................................................... 5
2.2 MAXIMUM RESISTANCE OF THE EARTHING SYSTEM......................................................................5
2.3 INTERCONNECTION SYSTEM.............................................................................................................. 5
3 BASIC DESIGN DATA......................................................................................................................... 6
4 CALCULATION OF RESISTANCE AND NUMBER OF EARTH ELECTRODES AND DEEP WELL
ELECTRODE.......................................................................................................................................... 6
5 EARTHING CONDUCTOR SIZING......................................................................................................7
5.1 SUBSTATION EARTHING SYSTEM....................................................................................................... 7
5.2 EARTH BUSES....................................................................................................................................... 7
5.3 INTERCONNECTING CONDUCTOR..................................................................................................... 8
5.3.1 MAIN EARTH GRID AROUND SUBSTATION......................................................................................8
5.3.2 PLANT EARTHING GRID CONDUCTOR............................................................................................ 9
5.4 BRANCH EARTH CONDUCTOR.......................................................................................................... 10
5.4.1 GTG NEUTRAL EARTHING.............................................................................................................. 10
5.4.2 GENRATOR TRANSFORMER 11/34.65 kV NEUTRAL GROUNDING CABLE..................................11
5.4.3 HV SWITCHGEAR............................................................................................................................. 11
5.4.4 33/3.46 kV TRANSFORMER NEUTRAL EARTHING GROUNDING.................................................12
5.4.5 3.46 kV SDG NEUTRAL EARTHING GROUNDING..........................................................................12
5.4.6 TRANSFORMER NEUTRAL GROUNDING AND BODY EARTHING................................................12
5.4.7 LV SWITCHBOARD........................................................................................................................... 14
5.4.8 0.415 kV SDG NEUTRAL CONNECTION AND BODY EARTHING CONNECTION..........................14
6 INSTRUMENTATION AND TELECOM EARTHING SYSTEM...........................................................15
7 TOUCH POTENTIAL AND STEP POTENTIAL..................................................................................15
ANNEXURE – A: SOIL RESISTIVITY TEST CONDUCTED BY PETROFAC.......................................18
ANNEXURE – B: EARTHING CONDUCTOR SIZES............................................................................19
1 INTRODUCTION
1.1 PURPOSE
The purpose of this document is to finalize the design of earthing system and carry out the earthing grid study
for the Central Processing Facility (CPF) - Khazzan Gas Project located at Block 61 in Oman, approximately
350 km SW of Muscat.
Earthing and bonding shall be provided to minimise electric shock hazards to personnel and damage to
equipment during earth faults and static charges.
To achieve the above, an earthing system of type ‘TN-S’ will be provided where the connection to earth
through earth electrodes will be achieved only at the source i.e. at the neutral point of the transformer and
generator. The earthing system will be provided to meet the following requirement:
Complete earthing grid will be formed by stranded copper 450/750 V earthing cable with green/yellow PVC
sheathing. Hence, the return path for earth leakage current shall be through copper conductor PVC sheathed
cable.
The earth fault current entering the grid at any point of the earth grid divides itself into minimum two current
paths at the point of entry. This current division is not really equal at the point of entry, as the grid comprises
interconnected network. Therefore, a current division factor of 0.7 is considered for sizing the earth
conductor as per the prevalent general engineering practices.
So the earth grid around the substation shall be sized for the maximum earth fault current of 45.5 kA (i.e. LV
system fault current-65 kA x 0.7) for duration of 1 second. Whereas the earth grid around the plant shall be
sized to withstand the fault current and the time (based on let-through energy of the highest rated MCCB
provided on outgoing feeders in LV switchboards)
33kV & 3.3 kV systems shall be earthed by using a neutral earthing resistor. Neutral earthing resistor shall
be sized to limit the earth fault current to a maximum value of 200A. Tripping of the respective circuit
breakers / contactors will be carried out on sensing the earth fault. Three phase 415V systems shall have
their neutrals solidly connected to the plant earthing system.
415/240V AC UPS neutral shall be solidly earthed through the earth bus within the UPS cabinet.
110V DC UPS systems shall have positive and negative poles unearthed (floating)
The earthing systems for substation, plant, non-current carrying equipment and static electricity shall be
interconnected with each other and shall be designed such that the overall earth grid resistance is restricted
to less than 1.
The maximum specified value 1 of overall earth grid resistance is achieved with the help of 6 meter copper
earth electrodes and 20 meter deep well electrode.
Earthing system of different areas like substation building, plant and that of non-current carrying equipment
will be interconnected with each other at minimum 2 points.
The earthing calculations in this document have been carried out based on the following design data and
criteria.
Type of earthing cable laid below and : 450/750V grade, yellow-green colour PVC
above ground insulated, high conductivity stranded annealed
copper conductor
Soil Resistivity : 85.14 -m (Refer Annexure- A)
LV system around substation building : 65 kA x 0.7 = 45.5 kA (Refer clause 2.1 above)
Fault current duration for sizing the : 0.02 sec (Refer clause 5.3.2)
earthing grid around the plant
Where,
– Average soil resistivity in Ω-m = 85.14 Ω-m (Refer soil resistivity test results enclosed as Annexure –
A).
Hence,
In order to achieve overall earth grid resistance as 1Ω (as specified in KZ01-EL-PHI-53-0001), electrodes will
be connected in parallel.
N =R x F/R (gmax)
Where,
F – Multiplying factor for multiple rods = 1.36 for 6 rods, (Table 14, IEEE standard 142)
N = 15.96 x 1.92 / 1
= 30.66
= Say 31 Nos.
So 31 number of electrode will give overall grid resistance approximately 1 ohm .In order to get GPR value
within 300 V, grid resistance further reduced at 0.243 Ω. This value achieved through increasing the 115 nos.
of parallel rods and 4 number of deep well electrodes (Refer Attachment-2). Hence we have considered 6
meter long, 15 mm dia.115 number of electrodes and 20 meter long, 150 mm dia. 4 numbers of deep well
electrodes in all over the plant.
Main earthing system at the substation will consist of adequate number of main earth buses of hard-drawn
copper (mounted on the wall with spacers). Main earth grid shall comprise stranded copper earthing cables
with green/yellow stripped PVC sheathing and required number of earth electrodes. Metal enclosures of
electrical equipment will be connected to these main earth buses by means of suitably sized copper
conductor PVC insulated earthing cable. These earth busses shall be in turn be connected to main earthing
ring around substation.
The earth buses in the substation shall be sized to withstand maximum earth fault current of 65 kA for 1 sec.
Main earth grid conductor around substation shall however be sized to withstand 45.5 kA for 1 sec
(Considering 70% and 30% distribution of earth fault current in main grid.)
As per Equation (37) of IEEE-80, the minimum cross sectional area of the earth buses in mm 2 is:
Where,
= 242.5°C
As per the above calculation, minimum cross sectional area of the substation earth bus required to
withstand the maximum expected fault current is
Earth bus with standard cross-sectional area of 300mm2 (50mmx6mm) shall be used for earthing in the
substation.
Interconnecting conductors will be made of copper conductor PVC insulated yellow green stripped cables,
which will be used to:
From the main earthing grid in the plant and connect various groups of earth electrodes to it.
The main earth grid will be of copper conductor, PVC insulated cable. The minimum cross sectional area of
the main earth grid conductor in mm2 as per equation (37) of IEEE 80 shall be:
Where,
Ta is the ambient temperature in °C = 40°C (Ground temperature as the conductor will be buried
underground)
Based on above the minimum cross sectional area of the substation earth bus required to withstand the
maximum expected fault current is
Hence 1 run of 1C 400 mm 2 copper conductor, PVC insulated cable shall be used to form the main earth
grid around the substation.
As per Electrical design criteria (Doc.No.KZ01-EL-PHI-53-0001), the Earthing grid conductor for plant
area shall be PVC Insulated copper cable of 70 mm 2.
We have verified the main grid conductor size with following assumptions;
Maximum rating in the outgoing of LV switchboard is 630 A. Maximum let-through energy (I 2t) of 630 A
MCCB is 3.2 x 106 A2s (Refer Attachment-1). Hence, for fault current of 65kA (Considered max. fault level
of all Substations) the withstand time required is:
However, we have considered withstand time of 1 cycle i.e. 0.02 sec (worst condition) instead of
0.000757 sec.
The minimum cross sectional area for the plant earthing grid conductor in mm 2 is,
S = I √tc
K
Where,
K is the factor for copper conductor PVC insulated earthing cable = 0.133
S = 40 x √0.02
0.115
= 49.19 mm2
Hence the grid in the plant area shall be insulated copper conductor of size 70 mm 2 as stipulated in KZ01-
EL-PHI-53-0001.
Branch earth conductors will connect individual electrical equipment to the main earth grid and earth bus.
The branch conductors will be copper conductor PVC insulated cables.
They will be sized to carry the calculated earth fault current for the duration of the fault.
Earth conductor size for each of the main equipment in the sub-station is calculated as below. However final
selection of earthing cable will be standardized to suit the higher size cable.
S = I √tc
K
Where,
Where,
K = 0.143 as per IEC 60364-5-54 for copper conductor XLPE insulated cable
S = 0.01x √10
0.143
= 0.221 mm2.
Hence standard cable size 70mm2 (12/20kV grade cable) shall be used for earthing the GTG neutral to
NER.
Minimum cross sectional area of the cable between NER to earth is,
= 0.01 x √10
0.115
= 0.274 mm2
Where,
k = 0.115 as per IEC 60364-5-54 for copper conductor PVC insulated cable
Hence standard earthing cable size 70mm2 shall be used for earthing for NER to earth
= 0.2 x √10
0.143
Where,
k = 0.143 as per IEC 60364-5-54 for copper conductor XLPE insulated cable
= 4.42 mm2
Hence standard cable size 70mm2 (18/30kV grade cable) shall be used for earthing the transformer neutral
and NER.
Minimum cross sectional area of the cable between NER to earth is,
= 0.2 x √10
0.115
= 9.52 mm2
Where,
K = 0.115 as per IEC 60364-5-54 for copper conductor PVC insulated cable
Hence standard earthing cable size 70mm2 shall be used for earthing the NER to earth.
5.4.3 HV SWITCHGEAR
33 kV GIS SWITCHGEAR
33 kV distribution systems shall be grounded through Neutral Earth Resistor (NER) at secondary side of
11/34.65kV transformer. Maximum ground fault current is 1000Amps (All Five Source in parallel, with
each source is grounded with 200 A NER).
Hence, the minimum cross sectional area of the cable for 33kV switchgear is,
= 1 x √3
0.115
= 15.06 mm2
Where k = 0.115 as per IEC 60364-5-54 for copper conductor PVC insulated cable
Hence standard earthing cable size 70mm2 shall be used for earthing the 33kV Switchgear body to main
earth grid.
3.3 kV HV SWITCHGEAR
3.3 kV distribution systems shall be grounded through Neutral Earth Resistor (NER) at secondary side of
33/3.46 kV transformer. Maximum ground fault current is 200Amps
Hence, the minimum cross sectional area of the cable for 3.3kV switchgear is,
= 0.200 x √3
0.115
= 3.012 mm2
Where,
k = 0.115 as per IEC 60364-5-54 for copper conductor PVC insulated cable
Hence standard earthing cable size 70mm2 shall be used for earthing the 3.3kV Switchgear body to main
earth grid.
= 0.2 x √10
0.143
Where k = 0.143 as per IEC 60364-5-54 for copper conductor XLPE insulated cable
=4.422mm2
Hence standard cable size 70mm2 (1.8/3kV grade cable) shall be used for earthing the DG & 33/6.9kV
transformer neutral to NER.
Minimum cross sectional area of the cable between NER to earth is,
= 0.2 x √10
0.115
= 5.49 mm2
Where k = 0.115 as per IEC 60364-5-54 for copper conductor PVC insulated cable
Hence standard earthing cable size 70 mm2 shall be used for earthing the NER to earth.
= 0.2 x √10
0.143
Where k = 0.143 as per IEC 60364-5-54 for copper conductor XLPE insulated cable
=4.422mm2
Hence standard cable size 70mm2 (1.8/3kV grade cable) shall be used for earthing the DG & 33/6.9kV
transformer neutral to NER.
Minimum cross sectional area of the cable between NER to earth is,
= 0.2 x √10
0.115
= 5.49 mm2
Where k = 0.115 as per IEC 60364-5-54 for copper conductor PVC insulated cable
Hence standard earthing cable size 70mm2 shall be used for earthing the NER to earth.
The calculation are performed for highest rating transformer which is 3.3/0.435 kV, 2.5 MVA Transformer
The neutral of 3.3/0.435 kV transformer is solidly grounded. % impedance of 2.5 MVA transformers is 6%
If = 3 Ep
(X1 + X2 + X0+ 3Zn)
Where,
Ep is the p.u per phase voltage
X1 p.u positive sequence impedance
X2 p.u negative sequence impedance
X0 p.u zero sequence impedance
Zn impedance of return path, i.e. 0, as the fault is considered at the transformer terminals
For transformers, X1 = X2 = X0 = XT = 6 %, As per Key SLD, KZ01-EL-SLD-53-0001
Hence cable of 400 mm2 is considered for transformer body earthing as well as neutral earthing.
Similarly other 1.6 MVA, 0.63 MVA and 1 MVA transformer earthing cable requirements can be calculated.
Table shown below earthing cable size
Transformer neutral
3.3/0.435 kV,0.5 MVA, 4 % imp
400 2
Transformer Body
3.3/0.435 kV,1.6 MVA,6 % imp
400 1
Transformer neutral
3.3/0.435 kV,1.6 MVA, 6 % imp
400 2
Transformer Body
5.4.7 LV SWITCHBOARD
The conductor for earthing the LV switchboard body shall be sized to withstand a fault current of 65 kA for
1 second.
S = Ik √t
K
Where,
K is the factor for copper conductor PVC insulated earthing cable = 0.115
S = 65 x √1
0.115
= 565.21 mm2
Since the calculated conductor size is very large, we will use 2 runs of PVC insulated cable for earthing
LV switchboard enclosure:
Therefore the earth fault current shall divide itself into two current paths, through the 2 parallel runs. So
each run of the earthing conductor is required to carry only 50% of the fault current. So the minimum size
of each run of the earthing conductor is,
S = 65 x √1
2 x 0.115
= 282.60 mm2. i.e. 300 mm2
To standardize cable size we have considered higher size of 2 run of PVC insulated cable of 400mm 2 is
considered for LV switchboard enclosure earthing.
The Generator Neutral shall be earth through conductor which has sized as per earth fault current of the
SDG.
The diesel generator earth fault current is computed below:
If = 3 Ep
(X1 + X2 + X0+ 3Zn)
Where,
S = 29.09 x √0.5
0.115
= 178.8 mm2
Hence cable of 400 mm2 considered for SDG body earthing as well as neutral earthing.
For all the other equipment supplied from the outgoing feeders of the main switchboards, the protective
devices will operate much faster to clear the earth fault. Hence, the actual required earth cable sizes are
lower than what have been stipulated in Clause 5.0 The minimum size of earthing conductors for all the
electrical equipment are calculated and summarized in a table given in Annexure-B.
For instrumentation earthing in LER’s, 3 earth busses each of 50 x 6 mm (minimum) tinned copper shall
be provided for the following:
√ts
Where,
Etouch is the permissible touch potential in Volts
Cs is surface layer resistivity derating factor
ts is duration of shock for determining allowable body current in second = 1
s is surface layer resistivity in ohm-m = 3000
is soil resistivity in ohm-m = 85.14
As per IEEE 80, Eq. 27,
..…….Eq (2)
Where,
hs is surface layer thickness = 0.015 m
Hence, from Eq (2)
Cs = 0.775 .…..…….Eq (3)
From Eq (1) & Eq (2),
Etouch = (1000+1.5*0.773*3000) * 0.116
√3
= 300.7 V
Hence, the actual value of Touch potential shall be less than 300 V..............Eq (4)
The permissible value of Step potential as per equation no. 18 of IEEE 80:2000 is calculated as:
Estep = (1000+6Css) * 0.116 ………….Eq (5)
√ts
Where,
Estep is the permissible step potential in Volts
From Eq (3) & Eq (5)
Estep = (1000+6*0.773*3000)*0.116
√3
= 1002.18 V
Hence, the actual value of Step potential shall be less than 1000 V……........Eq (6)
Spacing between the two centre electrodes is a direct measure of the effective depth desired for the
resistivity. So average soil resistivity considered as 85.14 (-m), approximately 85 (-m)
The table below indicates the minimum size of the earthing conductors to be used for various applications,
taking into consideration the worst condition from the calculations carried out .
Number of
Equipment Earthing Cable Size (mm2)
Connections
Plant Earth Grid 70 -
Main Earth Grid around Substation/Control
400 -
Room
33 kV HV Switchgear 70 2
3.3 kV HV Switchgear 70 2
Number of
Equipment Earthing Cable Size (mm2)
Connections
3.3/0.435 kV,0.5 MVA Transformer Body 400 2
Transformer LV Box 70 1
Transformer HV Box 70 1
LV Switchgear 400 2
Number of
Equipment Earthing Cable Size (mm2)
Connections
Battery Rack 35 2
UPS Panel 35 2
Vessels,Tanks,Separators 35 2
Perimeters Fence 35 @ 50 m
Bus Duct 70 1
Note: Single earthing connection will be provide to the motors having single earthing stud as per
manufacture’s standard.