Contactor Startor Motor
Contactor Startor Motor
Motor-Starters
D677E141
Index Page
General 2
Approvals 3
Technical Information 5
Mounting Information 6
Micro Contactors 7
Micro Contactors 8
Micro Contactor Relays 9
Micro Reversing Contactors 11
Technical Information 12
Dimensions 16
Mini Contactors 17
Mini Contactors 18
Interface Contactors 18
Micro Reversing Contactors 24
Technical Information 25
Dimensions 30
Contactor Relays 31
Contactor Relays 32
Technical Information 34
Dimensions 36
Contactors 37
Contactors Overview 38
Contactors, 3-pole 40
Contactors, 4-pole 42
Capacitor Switching Contactors 43
Accessories 44
Technical Information 54
Dimensions 74
Starters 83
Star-Delta Starters 84
Reversing Contactors 88
Pole Changing Starters 90
Technical Information 92
Dimensions 99
D.O.L. Starters 103
D.O.L. Starters 104
Enclosures 105
Accessories 105
Technical Information 106
Dimensions 108
Overload Relays 111
Thermal Overload Relays 112
Accessories 113
Technical Information 116
Dimensions 121
Modular Contactors 125
Contactors 126
Accessories 127
Technical Information 128
Dimensions 132
Representatives and Suppliers 132
Alphabetical Index 135
D677E 2014 1
General
Test Authorities, Registration Mark, Approvals CE-Marking
Low voltage switchgear from Benedict GmbH is built and tested The manufacturer has to sign his products with the CE-Marking. With the
to national and international specifications. All devices suit all CE-Marking the manufacturer confirms the accordance with the different
important specifications without any test obligation, like VDE, BS EEC Directives. The CE-Marking is absolutely necessary to sell the
and also relative to IEC Recommendations and to European Standards products in the EEC.
like IEC 947 and EN 60947. Below you find the EEC Directives concerning our products.
It is for this reason of our Low voltage switchgear is used all over the Low Voltage Directive 2006/95/EC
world. In order to provide special versions, limitations to the max. EMC Directive 2004/108/EC
voltages, currents and power ratings or special markings are RoHS + WEEE 2002/95/EC + "002/96/EC
sometimes necessary.
Explanations for choice and supply of low voltage switchgear in Canada and USA
Marking of auxiliary contacts
At several devices in UL-data are two voltages for auxiliary contacts Low voltage switchgear for auxiliary circuits (e. g. contactor relays, control
mentioned (e. g.: 600 volts at same potential, 150 volts at different units, auxiliary contacts in general) usually approved for "Heavy Duty" or
potentials). That means, if the voltage is higher than 150 volts, the control "Standard Duty" UL and besides these marked with the admissible max.
voltage applied to input terminals must be at the same potential. voltage or with short codes (see table).
2 D677E
Approvals
Country North America Switzerland Europe Russia China CENELEC
GOST CB-Certificates
UL SEV
Type
Micro Contactor Relays, Micro Contactors, Micro Reversing Contactors and Accessories
K0-04D.. - - - o - - -
K0-05D.. o - - o - - -
K0W05D.. o - - o - - -
Mini Contactor Relays, Mini Contactors, Mini Reversing Contactors K1 and Accessories
K1-07D..(=) o - - o o - o
K1-07L..(=) - o - o o - o
K1-07F..(=) - o - o - - -
K1-09D..(=) o - - o o o o
K1-09L..(=) - o - o o o o
K1-09F..(=) - o - o - o -
K1-12D..(=) o - - o - o -
K1W09D01(=) o - - o - o -
K1W12D01(=) o - - o - o -
K1W09L01(=) - o - o - o -
HK.., HKM.. o - - o - - o
RC-K1 o - - o - - -
K3-07ND..(=) o - - o - - -
K3-10N..(=) o - o o o o o
K3-14N..(=) o - o o o o o
K3-18N..(=) o - o o o o o
K3-22N..(=) o - o o o o o
K3-24A..(=) o - o o o o o
K3-32A..(=) o - o o o o o
K3-40A..(=) o - o o o o o
K3-50A..(=) o - o o o o o
K3-62A..(=) o - o o o o o
K3-74A..(=) o - o o o o o
K3-90A..(=) o - - o - o -
K3-115A..(=) o - - o - o -
K3-151A..(=) o - - o - - -
K3-176A..(=) o - - o - - -
K3-210A..(=) x - - o - - -
K3-260A..(=) x - - o - - -
K3-316A..(=) x - - o - - -
K3-450A..(=) o - - o - - -
K3-550A..(=) o - - o - - -
K3-700A..(=) o - - o - - -
K3-860A..(=) o - - o - - -
K3-1000A..(=) - - - o - - -
K3-1200A..(=) o - - o - - -
KG3-07.. o - - o - - o
KG3-10.., -14.. o - - o - - o
KG3-18.., -22.. o - - o - - o
KG3-24.., -32.. o - - o - - o
KG3-40.. o - - o - - o
K3-18K.. o - - o o o o
K3-24K.. o - - o o o o
K3-32K.. o - - o o o o
K3-50K.. o - - o o o o
K3-62K.. o - - o o o o
K3-74K.. o - - o o o o
K3-90K.. o - - o - o -
K3-115K.. o - - o - o -
Aux. contacts
HN.., HTN.. o - - o o o o
HA.. o - - o o - o
HB.. o - - o o o o
K2-DK, K2-SK o - - o - - -
HKA.., HKT.. o - - o - - -
HKF22 - - - o - - -
o In standard version approved x In test - Not provided for test till now
D677E 3
Approvals
Type
Accessories
K2-T..E, -A - - - o - - -
K2-TP o - - o - - -
K2-L o - - o - - -
K2-IN. o - - o - - -
K2-UN. o - - o - - -
K2-IM - - - o - - -
K2-E o - - o - - -
VG-K2 - - - o - - -
RC-K3 o - - o - - -
KW3-10 o - - o - - -
KW3-14 o - - o - - -
KW3-18 o - - o - - -
KW3-22 o - - o - - -
KW3-24 o - - o - - -
KW3-32 o - - o - - -
KW3-40 o - - o - - -
D.O.L. Starters
P1.. o - - o - - -
U3/32 o - - o o - o
U3/42 o - - o o - o
U3/74 o - - o o - o
U12/16E o - - o o - o
U12/16A - - - o o - o
U12/16EM - - - o o - o
U12/16EQ - - - o o - o
U32 o - - o o - o
U60 o - - o o - o
U85 o - - o o - o
U180 x - - o - - -
U320 x - - o - - -
U800 - - - o - - -
Modular Contactors
R20 o - o o o - o
R25 o - o o o - o
R40 o - o o o - o
R63 o - o o o - o
o In standard version approved x In test - Not provided for test till now
4 D677E
Technical Information
Degree of protection acc. to IEC 60947-1
Protection ratings are prefixed by the internationally agreed letters IP 2 nd Short description Definition
followed by two digits. digit
1 st digit: Pertains to solid objects 1 Protected against Dripping water (vertically falling drops)
2 nd digit: Pertains to water. dripping water shall have no harmful effect.
3 Protected against Excludes solid objects exceeding 2,5 mm 6 Protected against Water from heavy seas or water
solid objects in diameter or thickness. heavy seas projected in powerful jets shall not
greater than 2,5mm enter the enclosure in harmful
quanties.
4 Protected against Excludes solid objects exceeding 1 mm
solid objects in diameter or thickness. 7 Protected against Ingress of water in a harmful quantity
greater than 1 mm the effects of shall not be possible when the
immersion enclosure is immersed in water under
5 Dust protected Prevents ingress of dust in quantities standard conditions of pressure and
and locations that would interfere with time.
the intended operation of the equipment.
8 Protected against No ingress of water.
6 Dust tight Prevents ingress of dust. submersion
D677E 5
Technical Information
Mounting positions of contactors
K0-.. / K1-.. K2-..A00-40, K(G)3-07 bis K3-115, R.. K3-151.. bis K3-1200..
Terminal screws
Devices Kind of connection
Screw with Screw with Screw Screw driver Tightening torque
Type washer clamp box w. nut Nm lb. inch
6 D677E
Micro Contactors
Micro Contactors 9
Coil voltages 10
Technical Data 12
Dimensions 16
D677E 7
Micro Contactor Relays 4-pole AC Operated
AC15 Rated-
Current
230V 400V Ith acc. to Blocks ⏐ Pack Weight
A A A NO NC EN50011 Type W pcs. kg/pc.
8 D677E
Micro Contactors AC Operated
D677E 9
Micro Contactors AC Operated
90 100 100 90 100 100 105 240 230-240 230 240 250 260
95 95-100 105-110 95 100 105 110
100 100 110-115 100 105 110 115 Standard voltages in bold type letters
Operating range of magnet-coils: 0,85 x Us (min. value of rated
105 105-110 115-120 105 110 115 120 control voltage) up to 1,1 x Us (max. value of rated control voltage)
110 110-115 120-125 110 115 120 125
180 200 200 185 200 200 210 Coil not exchangeable
10 D677E
Micro Reversing Contactors, Mechanical Interlocked AC Operated
D677E 11
Micro Contactors
Data according to IEC 60947-4-1, VDE 0660, EN 60947-4-1
Main Contacts Type K0-05D..
380-400V A 5
415-440V A 5
380-400V A 5
415-440V A 5
1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 4kV.
Data for other conditions on request.
12 D677E
Micro Contactors
Data according to IEC 60947-4-1, VDE 0660, EN 60947-4-1
Main Contacts Type K0-05D..
Cable cross-sections
for contactors without thermal overload relay
main connector solid or stranded mm² 0,5 - 1,5
flexible mm² 0,5 - 1,5
flexible with multicore cable end mm² 0,5 - xxx2)
Cables per clamp 2
solid or stranded AWG 18 - 14
1) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3.
2) Data on request.
D677E 13
Micro Contactors
Data according to IEC 60947-5-1, VDE 0660, EN 60947-5-1
Auxiliary Contacts Type K0-04D..
K0-05D..
Cablecross-section
all connectors solid mm2 0,5 - 2,5
flexible mm2 0,5 - 2,5
flexible with multicore cable end mm2 0,5 - xxx5)
1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 4kV.
Data for other conditions on request.
2) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced thermal rated current Ith to Ie /AC15.
3) Summary switching time = release time + arc duration.
4) Release time of NC make time of NO increase when suppressor units for voltage peak protection are used (Varistor, RC-units, Diode units).
5) Data on request.
14 D677E
Micro Contactors for North America
Data according to UL508
Main Contacts (cULus) Type K0-05D.. K0-04D..
K0W05D01..
D677E 15
Micro Contactors
Dimensions
AC operated
with screw terminals
K0-04D..
K0-05D..
AC operated
with solder connections
K0-04L..
K0-05L..
Reversing Contactors
with screw terminals
K0W05D..MC
Reversing Contactors
with solder connections
K0W05L..MC
16 D677E
Mini Contactors
Mini Contactors 20
Auxiliary Contact Blocks
Coil voltages 22
Technical Data 26
Dimensions 30
D677E 17
Mini Contactor Relays 4-pole AC Operated
3 2 10 1 1 HK11 10 0,04
3 2 10 - 2 HK02 10 0,04
3 2 10 2 - HK20 10 0,04
3 2 10 4 - HK40 10 0,04
3 2 10 2 2 HK22 10 0,04
3 2 10 - 4 HK04 10 0,04
Wiring Diagrams
18 D677E
DC Solenoid Operated
D677E 19
Mini Contactors AC Operated
3 2 10 1 1 HKM11 10 0,04
3 2 10 - 2 HKM02 10 0,04
3 2 10 2 2 HKM22 10 0,04
Aux. Contact Blocks HKM11 HKM02 HKM22 HK11 HK02 HK40 HK22
Wiring Diagrams
20 D677E
DC Solenoid Operated
Type
Coil voltage 1) Aux. Contacts 2) Additional
24 24V= DC Built Additional Overload
24VS 24V= DC with in Relay
⏐ protection 3) see
⏐ page102 Pack Weight
W NO NC Type pcs. kg/pc. Wiring Diagrams
D677E 21
Mini Contactors AC Operated
4 4 16 - 1 - K1-09L01 . . . 10 0,16
90 100 100 90 100 100 105 240 230-240 230 240 250 260
95 95-100 105-110 95 100 105 110 400 380-400 400-440 380 400 400 440
100 100 110-115 100 105 110 115 500 475-500 520-545 475 500 520 545
550 525-550 600 525 550 570 600
105 105-110 115-120 105 110 115 120
110 110-115 120-125 110 115 120 125 Standard voltages in bold type letters
180 200 200 185 200 200 210 Operating range of magnet-coils: 0,85 x Us (min. value of rated
control voltage) up to 1,1 x Us (max. value of rated control voltage)
22 D677E
DC Solenoid Operated
Type
Coil voltage 1) Aux. Contacts 2) Additional
24 24V= DC Built Additional Overload
2 4 V S 24V= DC with in Relay see
⏐ protection 3) pages
⏐ 103, 105 Pack Weight
W NO NC Type pcs. kg/pc. Wiring Diagrams
K1-09L01= . . . - 1 - - 10 0,19
D677E 23
Mini Reversing Contactors, Mechanical Interlocked AC Operated
4 4 16 1 - - - K1W09L10MC . . . 1 0,32
3 2 10 1 1 HKM11V 10 0,04
3 2 10 1 1 HKM11X 10 0,04
Wiring Diagrams
For Reversing Starter Types, incl. Coil Connector Type Pack Weight
pcs. kg/pc.
24 D677E
DC Solenoid Operated
Type
Coil voltage 1) Additional
24 24V= DC Overload
24VS 24V= DC with Relay
⏐ protection 2) see
⏐ page102 Pack Weight
W Type pcs. kg/pc. Wiring Diagrams
K1W09L10MC= . . . - 1 0,32
D677E 25
Mini Contactors
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Main Contacts Type K1-09D.. K1-09F.. K1-09L.. K1-12D..
Rated operational power of three-phase resistive loads 230V kW 6,3 4,5 4,5 6,3
50-60Hz, cosϕ = 1 240V kW 6,7 5 5 6,7
400V kW 11 8 8 11
415V kW 11,5 8,5 8,5 11,5
Minimum cross-section of conductor at load with Ie (=Ith) mm² 2,5 2,5 - 2,5
380-400V A 9 9 9 12
415-440V A 8 8 8 11
500V A 7 7 7 9
660-690V A 5 5 5 6,5
380-400V A 9 9 9 12
415-440V A 8 8 8 11
500V A 7 7 7 9
660-690V A 5 5 5 6,5
1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
2) Suitable at 690V for pollution degree 2, Uimp = 6kV.
Pollution degree 3 Ui = 690V non-tracking of the printed circuit CTI ≥600
Pollution degree 3 Ui = 500V non-tracking of the printed circuit CTI ≥400
Pollution degree 3 Ui = 400V non-tracking of the printed circuit CTI ≥100
26 D677E
Mini Contactors
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Main Contacts Type K1-09D.. K1-09F.. K1-09L.. K1-12D..
Cable cross-sections
for contactors without thermal overload relay
main connector solid or stranded mm² 0,5 - 2,5 Fast on Solder connector 0,5 - 2,5
flexible mm² 0,5 - 2,5 1x 6,3 x 0,8 Ø 1,15 0,5 - 2,5
flexible with multicore cable end mm² 0,5 - 1,5 or 0,5 - 1,5
Cables per clamp 2 2x 2,8 x 0,8 - 2
solid or stranded AWG 18 - 14 18 - 14
Power loss per pole at Ie/AC3 400V W 0,15 0,15 0,15 0,25
DC operated NO g 8 8 8 8
NC g 6 6 6 6
1) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3
D677E 27
Mini Contactors
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Auxiliary Contacts Type K1-07D.. K1-07D..=
K1-09D.. K1-09D..= K1-07D..= 24VR K1-07L..(=)
K1-12D.. K1-12D..= K1-09D..= 24VR K1-09F..(=) K1-09L..(=) HK..
Power loss per pole at Ith W 0,5 0,5 0,5 0,5 0,5 0,5
Cable cross-section
all connectors solid mm2 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 Fast on Solder connector 0,5 - 2,5
flexible mm2 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 1x 6,3 x 0,8 Ø 1,15 0,5 - 2,5
flexible with multicore cable end mm2 0,5 - 1,5 0,5 - 1,5 0,5 - 1,5 or 0,5 - 1,5
2x 2,8 x 0,8
Clamps per pole 2 2 2 - - 2
1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
2) Suitable at 690V for pollution degree 2, Uimp = 6kV.
Pollution degree 3 Ui = 690V non-tracking of the printed circuit CTI ≥600
Pollution degree 3 Ui = 500V non-tracking of the printed circuit CTI ≥400
Pollution degree 3 Ui = 400V non-tracking of the printed circuit CTI ≥100
3) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced thermal rated current Ith to Ie /AC15
4) Summary switching time = release time + arc duration
5) Release time of NC make time of NO increase when suppressor units for voltage peak protection are used (Varistor, RC-units, Diode units).
28 D677E
Mini Contactors for North America
Data according to UL508
Main Contacts (cULus) Type K1-09D.. K1-09F.. K1-09L.. K1-07D.. K1-12D.. HK..
K1W09D01 K1W12D01
440-480V hp 5 5 5 - 7½ -
550-600V hp 7½ 7½ 7½ - 10 -
Auxiliary Contacts (cULus) heavy pilot duty AC A600 A600 A600 A600 A600 A600
standard pilot duty DC Q600 Q600 Q600 Q600 Q600 Q600
2 ≥ 100 600V
3 ≥ 400 480V
3 100 - 400 240V
D677E 29
Mini Contactors
Dimensions
AC and DC operated
with screw terminals with fast on terminals
K1-07D.. K1-07F..
K1-09D.. K1-09F..
K1-12D..
Suppressor Units
RC-K1
Reversing Contactors
K1W09D..MC
K1W12D..MC
K1W09D..MC + U12/16E K1
Reversing Contactors K1W09D..MC + U12/16E K1
K1W09L..MC
30 D677E
Contactor Relays
Technical Data 34
Dimensions 36
D677E 31
Contactor Relays AC Operated
32 D677E
DC Operated
A31, D31
A04, D04
ND31=
ND22=
ND04=
D677E 33
Contactor Relays
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Type K3-07ND K3-07ND= KG3-07A KG3-07D
Cable cross-section
Connector solid mm2 0,75 - 6
flexible mm2 1-4
flexible with multicore cable end mm2 0,75 - 4
Magnet coil solid mm2 0,75 - 2,5
flexible mm2 0,75 - 2,5
flexible with multicore cable end mm2 0,5 - 1,5
1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
2) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced thermal rated current Ith according to Ie /AC15 3) with built-in coil suppressor
34 D677E
Contactor Relays
Position of Terminals
AC operated DC operated with double wound coil
DC solenoid operated
D677E 35
Contactor Relays
Dimensions
AC operated DC solenoid operated
K3-07ND.. KG3-07..
K3-07ND.. =
36 D677E
Contactors
Contactor overview 38
Contactors 4-pole 42
Pneumatic Timers 45
Electronic Timers On-delay
Electronic Timers Off-delay
Mechanical Interlocks 46
Latches
Additional Terminals, Parallel Connectors
Indicator Units 47
Fuse Holders
Suppressor Units
Interface 48
Terminal Covers
Mounting Parts, Marking System
Control Voltages 50
Technical Data 54
Dimensions 74
D677E 37
Contactors 3-pole
Up to 1200A AC3
Up to 1350A AC1
DIN-rail mounting up to AC3 115A
International Approvals
Data according to IEC 947 / EN 60947
Ratings
AC3 400V Motor 10A 14A 18A 22A 24A 32A 40A 50A 62A 74A 90A 115A
380-400V 4kW 5,5kW 7,5kW 11kW 11kW 15kW 18,5kW 22kW 30kW 37kW 45kW 55kW
660-690V 5,5kW 7,5kW 10kW 10kW 15kW 18,5kW 18,5kW 30kW 37kW 45kW 55kW 55kW
AC1 690V at 40°C 25A 25A 32A 32A 50A 65A 80A 110A 120A 130A 160A 200A
Type K3- 10ND10 14ND10 18ND10 22ND10 24A00 32A00 40A00 50A00 62A00 74A00 90A00 115A00
Cable cross-section
Solid mm2 0,75 - 6 1,5 - 25 4 - 50 10 - 120
Flexible mm2 1-4 2,5 - 16 10 - 35 10 - 95
Auxiliary contact
Ith 40°C A 10 - - -
AC15 230V A 3 - - -
400V A 2 - - -
U12/16..K3 U3/42
Busbar sets - - - - -
38 D677E
150A 175A 210A 260A 315A 450A 550A 700A 860A 1000A 1200A
75kW 90kW 110kW 132kW 160kW 250kW 300kW 400kW 500kW 580kW 680kW
90kW 110kW 160kW 210kW 250kW 375kW 475kW 630kW 700kW 850kW 1000kW
230A 250A 350A 450A 500A 600A 760A 1000A 1100A 1200A 1350A
151A00 176A00 210A00 260A00 316A00 450A22 550A22 700A22 860A22 1000A12 1200A12
2 x 16-120 busbar busbar busbar busbar busbar busbar busbar busbar busbar
2 x 16-120 30x6 30x6 30x6 30x5 40x6 50x8 50x8 50x10 50x10
- - 10 10
- - 3 3
- - 2 2
350 350 360 360 360 800-950 800-950 1350-1600 1350-1600 2400 2400
5 5 5 5 5 9-11 9-11 21-25 21-25 70 70
0,85 - 1,1 0,85 - 1,1 0,85 - 1,1 0,85-1,1
base
HKA11 - - - - - -
1NO+1NC
max. 2 pcs.
1 2 3
120 - 180A 144 - 320A 240 - 800A
D677E 39
Contactors 3-pole AC Operated
11 10 32 1 - K3-22ND10 . . . 1 0,23
11 10 32 - 1 K3-22ND01 . . . 1 0,23
40 D677E
DC Operated
A00=
K3-50A00= . . . 200/6 U3/74 1 0,9
K3-62A00= . . . 200/6 1 0,9
K3-74A00= . . . 200/6 1 0,9
D677E 41
Contactors 3-pole DC Operated
11 10 32 1 - K3-22ND10= . . . 1 0,25
11 10 32 - 1 K3-22ND01= . . . 1 0,25
42 D677E
Capacitor Switching Contactors
for use with reactive or non-reactive capacitor banks
Rated Operational Power at 50/60Hz Aux. Type
Ambient Temperature Contacts
50°C 60°C Built-in Add. Coil voltage 1)
380V 415V 660V 380V 415V 660V 230 220-240V 50Hz
400V 440V 690V 400V 440V 690V ⏐ Pack Weight
kVAr kVAr kVAr kVAr kVAr kVAr NO NC pcs. W pcs. kg/pc.
12,5 0-13
0-12,5 0-20 0-12,5 0-13 0-20 1 - 1 2) K3-18NK10 . . . 1 0,34
0-12,5
12,5 0-13 0-20 0-12,5 0-13 0-20 - 1 1 2) K3-18NK01 . . . 1 0,34
10-20
20 10,5-22 17-33 10-20 10,5-22 17-33 - - 3 3) K3-24K00 . . . 1 0,62
25
10-25 10,5-27 17-41 10-25 10,5-27 17-41 - - 3 3) K3-32K00 . . . 1 0,62
20-33,3
33,3 23-36 36-55 20-33,3 23-36 36-55 - - 3 3) K3-50K00 . . . 1 1,0
50 23-53 36-82
20-50 20-50 23-53 36-82 - - 3 3) K3-62K00 . . . 1 1,0
754) 23-754) 36-1204) 20-60 23-64
20-75 36-100 - - 3 3) K3-74K00 . . . 1 1,0
33-80
80 36-82 57-120 33-75 36-77 57-120 - - 6 5) K3-90K00 . . . / VS 7) 1 2,3
1006) 36-1036) 57-1486) 33-906) 36-936) 57-1486) -
33-100 - 6 5) K3-115K00 . . . / VS 7) 1 2,3
Specification: Contactors K3-..K are suitable for switching low-inductive and low loss capacitors in capacitor banks
(IEC70 and 831, VDE 0560) without and with reactors.
Capacitor switching contactors are fitted with early make contacts and damping resistors, to reduce the value of make
current <70 x Ie.
Operating Conditions: Capacitor switching contactors are protected against contact welding for a prospective making
current of 200 x Ie.
Technical Data acc. to IEC 947-4-1, IEC 947-5-1, EN 60947-4-1, EN 60947-5-1, VDE 0660
Type K3-18K K3-24K K3-32K K3-50K K3-62K K3-74K K3-90K K3-115K
Fuses gL (gG) from / to A 35 / 63 50 / 80 63 / 100 80 / 160 125 / 160 160/200 160/200 160/250
Mounting instructions:
In the area of capacitor switching contactors,
difficulty inflammable and self-extinguishing
materials shall be used only, because
abnormal temperatures within the area of the
resistor spirals cannot be excluded.
D677E 43
Auxiliary Contact Blocks for contactors K(G)3-07.. to K3-115.., type HN.. for low level switching 1)
Rated Operational Current Contacts Type Pack Weight
AC15 AC15 AC1
230V 400V 690V
A A A NO NC EM LB pcs. kg/pc.
3 2 10 1 - - - HN10 10 0,02
3 2 10 - 1 - - HN01 10 0,02
3 2 10 - - 1 - HN10U 10 0,02
3 2 10 - - - 1 HN01U 10 0,02
6 3 25 1 - - - HA10 10 0,03
6 3 25 - 1 - - HA01 10 0,03
Auxiliary Contact Block for contactors K3-24.. to K3-115.., for low level switching 1)
Rated Operational Current Contacts Type Pack Weight
AC15 AC15 AC1 mounting:
230V 400V 690V 1 HB.. on left side
A A A and 1 HB.. on right side NO NC pcs. kg/pc.
3 2 10 1 1 HB11 10 0,02
3 2 10 - 2 HB02 10 0,02
Snap-on Momentary Contacts for K(G)3-07.. to K3-115.. for low level switching1)
Rated Operational Current Contacts Type Pack Weight
AC15 AC15 AC1
230V 400V 690V
A A A Specification NO NC pcs. kg/pc.
1)Contacts suitable for electronic circuits, according to IEC60947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA) Positively guided contacts
Technical data see page 62
2) Contact travel of make contacts adjustable, see page 63
44 D677E
Elektronic Timer
for mounting on DIN-rail, Control voltage 24-240V AC/DC, 1 changeover contact
OFF-delay without auxiliary voltage
Replace Pneumatic Timer K2-TP..
D677E 45
Interface for contactors K3-07.. to K3-74.. and K2-07.. to K2-60..
Fuse holder for fuse 5x20mm (max. 6,3A) 250V AC K2-F 1 0,02
Fuses are not included.
Rectifier with Fuse Holder for contactors K(G)3-07.. to K3-115.. and K2-..
Specifications Rated Voltage Type Pack Weight
pcs. kg/pc.
Voltage Indicator
Indicator, clear (glow-disc. l.) 220 - 415V AC/DC K2-UN 10 0,02
Voltage Indicator
Indicator, red (LED) 24 - 120V AC/DC K2-UNR 10 0,02
To connect parallel to the contactor coil. In case of applied
voltage the indication also lights at coil interruption.
Snap-On Adapter
For Type Specification Type Pack Weight
pcs. kg/pc.
46 D677E
Additional 4th Poles for contactors K3-315.. to K3-1200
For Ccontactors Thermal Current Ith Type Pack Weight
A pcs. kg/pc.
Mechanical Interlocks
Interlocks contactor with contactor Mounting Type Pack Weight
Type Type pcs. kg/pc.
Additional Terminals
For Contactors Cable Cross-sections to clamp mm² Type Pack Weight
solid or flex. with multi-
stranded flexible core cable end pcs. kg/pc.
D677E 47
Parallel Connectors
For Contactors Cable Cross-sections to clamp mm² Type Pack Weight
solid or flex. with multi-
stranded flexible core cable end pcs. kg/pc.
Suppressor Units
Voltage Range Mounting Type Pack Weight
V pcs. kg/pc.
RC-units for reversing contactors K3NWU10 - K3WU74 and contactors K3-07 - K3-74
Mounting Parts
Description For Type Specification Type Pack Weight
pcs. kg/pc.
Marking System for contactors K3-07.. to K3-115.., K2-.. and aux. contact blocks HN and HA
48 D677E
Coil voltages for AC operated contactors
Type-suffix for coil-types K6/.. to K45/... Type-suffix for coil-types K85/... and K110/...
for contactor-types K3-07.. to K3-74 for contactor-types K85 to K110
Suffix Voltage Marking Rated Control Voltage Us Suffix Voltage Marking Rated Control Voltage Us
to to to to
contactor coil at the coil range contactor coil at the coil range
type type for for for 50Hz for 60Hz type type for for for 50Hz for 60Hz
50Hz 60Hz min. max. min. max. 50Hz 60Hz min. max. min. max.
V V V V V V V V V V V V
11 41.11 11 12 11 12 12 13,2
12 41.12 12 12 13,2 13,2 14,5
13,2 41.13 13,2 13,2 14,5 14,5 16 Type-suffix for coil-types K3-1200/..
for contactor-types K3-1000.. to K3-1200..
14,5 41.14 14,5 14,5 16 16 18
16 41.16 16 16 18 18 20 110 4.110 110-115 - 110 115 110 115
18 41.18 18 18 20 20 22 230 4.230 220-230 - 220 230 220 230
400 4.400 380-400 - 380 400 380 400
20 41.20 20 20 22 22 24
24 4.24 24 24 22 24 24 27 440 4.440 440 - 440 440 440 440
25 41.25 25 24 27 27 30
27 41.27 27 32 27 30 30 33
32 41.32 32 36 30 33 33 36
33 41.33 36 36 33 36 36 39 Coil voltages for AC and DC operated contactors
36 41.36 36 42 36 39 39 42 Type-suffix for coil-types K3-115/.. to K3-860/..
40 41.40 42 42 39 42 42 47 for contactor-types K3-90.. to K3-860..
42 4.42 42 48 42 47 47 52
Suffix Voltage Marking Rated Control Voltage Us
48 41.48 48 48 44 48 48 52 to to
55 41.55 55 60 52 58 58 65 contactor coil at the coil range
60 41.60 60 58 65 65 72 type type for for for 50Hz for 60Hz
50/60Hz DC min. max. min. max.
65 41.65 65 65 72 72 80 V V V V V V
75 41.75 75 72 80 80 90
85 41.85 85 80 90 90 100 24 4.24 24 24 22 24 22 24
48 4.48 48 48 44 48 44 48
90 41.90 100 100 90 100 100 110 110 4.110 110-120 110 110 120 110 120
110 4.110 110 110-120 100 110 110 122
115 41.115 115 125 110 122 122 135 230 4.230 220-240 220 220 240 220 240
400 4.400 380-415 - 380 415 380 415
127 41.127 127 122 135 135 150
140 41.140 140 135 150 150 165
150 41.150 150 150 165 165 180
165 41.165 165 180-208 165 180 180 208 Coil voltages for AC operated contactors
180 41.180 180-2101) 200-2401) 180 2101) 200 2401)
200 41.200 200-2301) 220-240 200 2301) 220 240 Type-suffix for coil-types K3-115/..AC
for contactor-types K3-90..AC to K3-115..AC
230 4.230 220-240 230-264 220 240 230 264
254 41.254 254 277 240 264 264 290 Suffix Voltage Marking Rated Control Voltage Us
270 41.270 270 264 290 290 315 to to
contactor coil at the coil range
300 41.300 300 290 315 315 345 type type for for for 50Hz for 60Hz
320 41.320 320 315 345 345 380 50Hz 60Hz min. max. min. max.
345 41.345 345-4001) 380-4401) 345 4001) 380 4401) V V V V V V
400 4.400 380-415 400-440 380 415 400 460 110AC 4.110AC 110-122 132-146 110 122 132 146
415 41.415 415-440 440-480 400 440 440 480 230AC 4.230AC 220-240 277 220 240 264 288
440 41.440 440-480 480-500 440 480 480 530
Other coil voltages on request
480 41.480 480-500 530-580 480 530 530 580
500 41.500 500-550 550-600 500 550 550 600 Operating range of magnet-coils: 0,85 x Us (min. value of rated
control voltage) up to 1,1 x Us (max. value of rated control voltage)
550 41.550 550-600 600 550 600 600 (650)
With reduced control voltage range 0,9 up to 1,0 x Us at ambient
Standard voltages in bold type letters temperature 60 - 90°C
1) Operating range of magnet-coils: 0,85 x Us (min. value of rated control voltage) up to 1,05 x Us (max. value of rated control voltage)
D677E 49
Spare Coils for AC operated contactors
50 D677E
Spare Coils for DC operated contactors
Aux. Contact Block Type Coil voltage 1)
for double winding coil 47.24 24V DC
47.110 110V DC
47.220 220V DC
⏐ Pack Weight
For Contactors W pcs. kg/pc.
K85..=
K110..=
Adjustable dropout operating time for K3-450.. to K3-860..: Contactor K3-1000.., K3-1200..:
150-200ms: Wiring see above (delivery standard) For control voltages up to 125V
500-1000ms: Jumper device "Z" NC contacts 21-22 and 11-12 are connected parallel,
approx. 20ms: Special wiring see package folder for higher voltages contacts are connected in series (delivery standard).
D677E 51
Spare Contacts
Main Contacts Type Pack Weight
for Contactors pcs. kg/pc.
K3-260.. EK3-260/10 1
K3-315.. EK3-315/10 1 0,34
K3-316.. EK3-316/10 1
52 D677E
Approximate Values for three-phase Motors
Motor Full Load Currents
Approximate values of motor F.L.C. and minimum "slow blow" respectively "gL" short-circuit fuse
Motor Range 220-230V Value 240V Value 380-400V Value 415V Value 500V Value 660-690V Value
rating according to Motor of fusing at Motor of fusing at Motor of fusing at Motor of fusing at Motor of fusing at Motor of fusing at
BS for motor start motor start motor start motor start motor start motor start
415V F.L.C. D.O.L. YD F.L.C. D.O.L. YD F.L.C. D.O.L. YD F.L.C. D.O.L. YD F.L.C. D.O.L. YD F.L.C. D.O.L. YD
kW PS~hp hp cosϕ % A A A A A A A A A A A A A A A A A A
0,06 0,08 - 0,7 59 0,38 1 1 0,35 1 1 0,22 1 1 - - - 0,16 1 1 - - -
0,09 0,12 - 0,7 60 0,55 2 2 0,5 2 2 0,33 1 1 - - - 0,24 1 1 - - -
0,12 0,16 - 0,7 61 0,76 2 2 0,68 2 2 0,42 2 2 - - - 0,33 1 1 - - -
0,18 0,24 - 0,7 61 1,1 2 2 1 2 2 0,64 2 2 - - - 0,46 1 1 - - -
0,25 0,34 - 0,7 62 1,4 4 2 1,38 4 2 0,88 2 2 - - - 0,59 2 2 - - -
0,37 0,5 - 0,72 64 2,1 4 4 1,93 4 4 1,22 4 2 - - - 0,85 2 2 0,7 2 2
0,55 0,75 - 0,75 69 2,7 4 4 2,3 4 4 1,5 4 2 - - - 1,2 4 2 0,9 2 2
0,75 1 1 0,8 74 3,3 6 4 3,1 6 4 2 4 4 2 4 4 1,48 4 2 1,1 2 2
1,1 1,5 1,5 0,83 77 4,9 10 6 4,1 6 6 2,6 4 4 2,5 4 4 2,1 4 4 1,5 4 2
1,5 2 2 0,83 78 6,2 10 10 5,6 10 10 3,5 6 4 3,5 6 4 2,6 4 4 2 4 4
2,2 3 3 0,83 81 8,7 16 10 7,9 16 10 5 10 6 5 10 6 3,8 6 6 2,9 6 4
2,5 3,4 - 0,83 81 9,8 16 16 8,9 16 10 5,7 10 10 - - - 4,3 6 6 - - -
3 4 4 0,84 81 11,6 20 16 10,6 20 16 6,6 16 10 6,5 16 10 5,1 10 10 3,5 6 4
3,7 5 5 0,84 82 14,2 25 20 13 25 16 8,2 16 10 7,5 16 10 6,2 16 10 - - -
4 5,5 - 0,84 82 15,3 25 20 14 25 20 8,5 16 10 - - - 6,5 16 10 4,9 10 6
5,5 7,5 7,5 0,85 83 20,6 35 25 18,9 35 25 11,5 20 16 11 20 16 8,9 16 10 6,7 16 10
7,5 10 10 0,86 85 27,4 35 35 24,8 35 35 15,5 25 20 14 25 16 11,9 20 16 9 16 10
8 11 - 0,86 85 28,8 50 35 26,4 35 35 16,7 25 20 - - - 12,7 20 16 - - -
11 15 15 0,86 87 39,2 63 50 35,3 50 50 22 35 25 21 35 25 16,7 25 20 13 25 16
12,5 17 - 0,86 87 43,8 63 50 40,2 63 50 25 35 35 - - - 19 35 25 - - -
15 20 20 0,86 87 52,6 80 63 48,2 80 63 30 50 35 28 35 35 22,5 35 25 17,5 25 20
18,5 25 25 0,86 88 64,9 100 80 58,7 80 63 37 63 50 35 50 50 28,5 50 35 21 35 25
20 27 - 0,86 88 69,3 100 80 63,4 80 80 40 63 50 - - - 30,6 50 35 - - -
22 30 30 0,87 89 75,2 100 80 68 100 80 44 63 50 40 63 50 33 50 50 25 35 35
25 34 - 0,87 89 84,4 125 100 77,2 100 100 50 80 63 - - - 38 63 50 - - -
30 40 40 0,87 90 101 125 125 92,7 125 100 60 80 63 55 80 63 44 63 50 33 50 35
37 50 50 0,87 90 124 160 160 114 160 125 72 100 80 66 100 80 54 80 63 42 63 50
40 54 - 0,87 90 134 160 160 123 160 160 79 100 100 - - - 60 80 63 - - -
45 60 60 0,88 91 150 200 160 136 200 160 85 125 100 80 100 100 64,5 100 80 49 63 63
51 70 - 0,88 91 168 200 200 154 200 200 97 125 100 - - - 73,7 100 80 - - -
55 75 - 0,88 91 181 250 200 166 200 200 105 160 125 - - - 79 125 100 60 80 63
59 80 80 0,88 91 194 250 250 178 250 200 112 160 125 105 160 125 85,3 125 100 - - -
75 100 100 0,88 91 245 315 250 226 315 250 140 200 160 135 200 160 106 160 125 82 125 100
90 125 125 0,88 92 292 400 315 268 315 315 170 250 200 165 200 200 128 160 160 98 125 125
110 150 150 0,88 92 358 500 400 327 400 400 205 250 250 200 250 250 156 200 200 118 160 125
129 175 175 0,88 92 420 500 500 384 500 400 242 315 250 230 315 250 184 250 200 - - -
132 180 - 0,88 92 425 500 500 393 500 500 245 315 250 - - - 186 250 200 140 200 160
147 200 200 0,88 93 472 630 630 432 630 500 273 315 315 260 315 315 207 250 250 - - -
160 220 - 0,88 93 502 630 630 471 630 630 295 400 315 - - - 220 315 250 170 200 200
184 250 250 0,88 93 590 800 630 541 630 630 340 400 400 325 400 400 259 315 315 - - -
200 270 - 0,88 93 626 800 800 589 800 630 370 500 400 - - - 278 315 315 215 250 250
220 300 300 0,88 93 700 1000 800 647 800 800 408 500 500 385 500 400 310 400 400 - - -
250 340 - 0,88 93 803 1000 1000 736 1000 800 460 630 500 - - - 353 500 400 268 315 315
257 350 350 0,88 93 826 1000 1000 756 1000 800 475 630 630 450 630 500 363 500 400 - - -
295 400 400 0,88 93 948 1250 1000 868 1000 1000 546 800 630 500 630 630 416 500 500 - - -
315 430 - 0,88 93 990 1250 1250 927 1250 1000 580 800 630 - - - 445 630 500 337 400 400
355 483 - 0,89 95 - - - - - - 636 800 800 - - - 483 630 630 366 500 400
400 545 - 0,89 96 - - - - - - 710 1000 800 - - - 538 630 630 410 500 500
The motor F.L.C. be valid for standard internal and surface cooled three-pole motors with higher F.L.C., higher starting current and / or longer starting time, larger
motors with 1500 min-1. The fuses values be valid for the motor F.L.C. shown in the short-circuit fuses are required.
table and D.O.L.-start: starting current max. 6x motor F.L.C., starting time max. 5s; The maximum admissible value is dependent on the switchgear respectively
star-delta-start: starting current max. 2x motor F.L.C., starting time max. 15s. For thermal overload relay.
1) Determine the motor current for 200V and 208V by increasing the values for 220-240V at 200V about 15% and for 208V about 10%.
D677E 53
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74
Making capacity Ieff at Ue = 690V AC A 200 200 200 200 400 500 500 700 900 900
Breaking capacity Ieff 400V AC A 180 180 200 200 380 400 400 600 800 800
K2-09 to K3-22 cosϕ= 0,65 500V AC A 150 150 180 180 300 370 370 500 700 700
K3-24 to K3-1200 cosϕ= 0,35 690V AC A 100 100 150 150 260 340 340 400 500 500
1000V AC A - - - - - - - - -
380V kW 16,4 16,4 21,0 21,0 32,9 42,7 52,6 72,3 78,9 85,5
400V kW 17,3 17,3 22,1 22,1 34,6 45,0 55,4 76,1 83,0 90,0
415V kW 17,9 17,9 23,0 23,0 35,9 46,7 57,4 79,0 86,2 93,3
440V kW 19,0 19,0 24,4 24,4 38,1 49,5 60,9 83,7 91,3 99,0
500V kW 21,6 21,6 27,7 27,7 43,3 56,2 69,2 95,2 103,8 112,5
660V kW 28,5 28,5 36,5 36,5 57,1 74,2 91,3 125,6 137,0 148,4
690V kW 29,8 29,8 38,2 38,2 59,7 77,6 95,5 131,3 143,2 155,2
1000V kW - - - - - - - - -
380V kW 16,4 16,4 21,0 21,0 26,3 36,2 42,7 59,2 65,7 72,3
400V kW 17,3 17,3 22,1 22,1 27,7 38,1 45,0 62,3 69,2 76,1
415V kW 17,9 17,9 23,0 23,0 28,7 39,5 46,7 64,6 71,8 79,0
440V kW 19,0 19,0 24,4 24,4 30,4 41,9 49,5 68,5 76,1 83,7
500V kW 21,6 21,6 27,7 27,7 34,6 47,6 56,2 77,9 86,5 95,2
660V kW 28,5 28,5 36,5 36,5 45,7 62,8 74,2 102,8 114,2 125,6
690V kW 29,8 29,8 38,2 38,2 47,7 65,7 77,6 107,4 119,4 131,3
1000V kW - - - - - - - - -
Minimum cross-section of conductor
at load with Ie (=Ith) mm² 4 4 6 6 10 16 25 35 50 50
380-400V A 10 14 18 22 24 32 40 50 62 74
415V A 9 14 18 22 23 30 40 50 62 74
440V A 9 14 18 22 23 30 40 50 62 74
500V A 7 9 9 9 17,5 21 21 33 42 42
660-690V A 6,5 8,5 8,5 8,5 17 20 20 31 40 40
1000V A - - - - - - - - -
1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
54 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type K3-90 K3-115 K3-116 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200
V~ 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 690 690 690 690
A 1100 1200 1200 1500 2000 2100 2600 3200 4500 5500 7000 8600 10000 12000
A 950 1100 1000 1200 1500 1600 2100 2600 4500 5500 7000 8000 8000 10000
A 850 1000 1000 1200 1500 1600 2100 2600 4500 5500 7000 8000 8000 10000
A 600 600 800 1000 800 1200 1900 2300 3200 4400 5600 6900 7000 8000
A - - 400 500 600 700 850 1000 - - - - - -
A 160 200 200 230 250 350 450 500 700 760 1000 1100 1200 1350
kW 105 131 131 151 164 230 296 329 460 500 658 724 789 888
kW 110 138 138 159 173 242 311 346 485 526 692 762 831 935
kW 115 143 143 165 179 251 323 359 503 546 718 790 862 970
kW 121 152 152 175 190 266 342 381 533 579 762 838 914 1028
kW 138 173 173 199 216 303 389 453 606 658 866 952 1039 1169
kW 182 228 228 262 285 400 514 571 800 868 1143 1257 1371 1543
kW 191 239 239 274 298 418 537 597 836 908 1195 1314 1434 1613
kW 221 277 216 318 346 433 546 606 692 866 - - - -
A 145 170 170 180 200 280 360 400 550 600 800 875 960 1080
kW 95 111 111 118 131 184 237 263 362 395 526 575 631 710
kW 100 117 117 124 138 193 249 277 381 415 554 606 665 748
kW 104 122 122 129 143 201 259 287 395 431 575 628 690 776
kW 110 129 129 137 152 213 274 304 419 457 609 666 731 823
kW 125 147 147 155 173 242 312 346 476 519 692 757 831 935
kW 165 194 194 205 228 320 412 457 628 685 914 1000 1097 1234
kW 173 202 202 215 239 334 430 478 657 717 956 1045 1147 1290
kW 166 187 216 277 346 388 499 554 692 866 - - - -
mm² 95 120 95 95 120 240 2x150 2x(30x6) 2x(40x5) 2x(50x5) 2x(60x5) 2x(60x6) 2x(60x6) 2x(60x8)
A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200
A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200
A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200
A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200
A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200
A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200
A 60 60 115 150 175 210 260 315 450 550 700 860 1000 1200
A 58 58 100 120 140 150 180 240 400 500 630 700 860 1000
A 58 58 45 60 70 85 100 125 200 250 - - - -
kW 55 55 90 110 132 132 160 210 375 500 630 700 850 1000
kW 55 55 55 75 90 110 132 160 280 355 - - - -
D677E 55
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74
380-400V A 10 14 18 18 24 32 40 50 62 62
415V A 9 14 18 18 23 30 37 45 60 60
440V A 9 14 18 18 23 30 37 45 55 55
500V A 9 12 16 16 17,5 21 21 33 42 42
660V A 7 9 9 9 17 20 20 31 40 40
690V A 6,5 8,5 8,5 8,5 17 20 20 31 40 40
1000V A - - - - - - - - -
Fluorescent lamps,
uncompensated and serial compensated A 20 20 25 25 40 52 64 88 96 104
parallel compensated A 7 9 9 9 18 22 22 30 40 45
dual-connection A 22,5 22,5 28 28 45 58 72 98 108 117
Mercury-vapour lamps2),
uncompensated A 22,5 25 28 28 45 58 72 99 108 117
parallel compensated A 7 9 9 9 18 22 22 30 40 45
1) Metal halide lamps and sodium-vapour lamps (high- and low-pressure lamps)
2) High-pressure lamps
3) Blended lamps, containing a mercury high-pressure unit and a tungsten helix in a flourescent glass bulb (daylight lamps)
4) Current inrush approx. 16 x Ie
56 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type K3-90 K3-115 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200
A 85 85 - - - - - - - - - - -
A 60 60 - - - - - - - - - - -
A 57,5 57,5 - - - - - - - - - - -
A - - - - - - - - - - - - -
A 100 120 120 140 180 220 280 360 450 570 700 850 1000
A 55 70 85 100 130 160 200 300 360 460 550 660 800
A 112 144 120 140 180 220 280 360 450 570 700 850 1000
A 85 90 95 110 140 180 230 300 380 490 610 750 890
A 55 70 75 85 110 140 170 260 300 400 480 580 700
A 112 144 120 140 180 220 280 360 450 570 700 850 1000
A 55 70 75 85 110 140 170 260 300 400 480 580 700
A 100 120 100 120 160 200 250 320 400 500 600 700 800
A 69 75 100 120 160 190 220 260 315 440 500 560 630
D677E 57
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74
Rated operational power 220-230V kVA 1,8 2,2 3 3 4,2 5,4 5,4 8 10,7 13
dependent on inrush n 240V kVA 1,9 2,3 3,1 3,1 4,3 5,6 5,6 8,3 11,2 13,5
380-400V kVA 3,1 3,8 5,2 5,2 7,3 9,3 9,3 13,5 18,5 22,5
For different inrush-factors x 415-440V kVA 3,4 4,2 5,7 5,7 8 10,2 10,2 15 20,5 25
use the following formula: 500V kVA 3,9 4,8 6,5 6,5 9 11,5 11,5 17 23 28
Px=Pn*(n/x) 660-690V kVA 5,4 6,5 9 9 12,5 16 16 24 32 39
Switching of
reactive capacitor banks
Rated operational current Ie 690V A 8 13 18 20 28 36 42 48 72 108 1)
58 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type K3-90 K3-115 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200
n 30 30 30 30 30 30 30 30 30 30 30 30 30
A 38 50 65 80 90 120 142 203 248 315 390 450 540
k 20 20 20 20 25 20 20 20 20 20 20 20 20
A 87 100 120 155 195 225 255 300 370 440 520 680 760
kVAr 60 70 95 110 135 165 175 210 260 310 360 465 520
kVAr 70 80 100 130 170 194 220 260 320 380 450 590 660
kVAr 70 80 100 130 170 194 220 260 320 380 450 590 660
A 115 144 115 140 200 225 250 330 420 550 600 680 760
kVAr 100 120 80 100 140 160 170 230 290 380 420 470 530
kVAr 105 125 95 120 170 190 210 280 350 450 500 570 640
kVAr 120 148 125 150 200 230 260 350 450 600 650 700 800
kVAr 160 200 155 200 300 340 400 500 650 - - - -
A 160 200 - - - - - - - - - - -
A 160 200 - - - - - - - - - - -
A 20 25 - - - - - - - - - - -
A 2 2,5 - - - - - - - - - - -
A 160 200 200 250 350 400 450 600 760 1000 1100 1200 1350
A 160 200 200 250 350 400 450 600 760 1000 1100 1200 1350
A 160 200 150 170 250 280 315 400 480 560 630 800 900
A 100 160 80 100 150 180 200 250 315 400 450 500 600
A 160 200 - - - - - - - - - - -
A 85 110 - - - - - - - - - - -
A 2 2,5 - - - - - - - - - - -
A 0,5 0,5 - - - - - - - - - - -
A 160 200 - - - - - - - - - - -
A 100 110 - - - - - - - - - - -
A 100 110 - - - - - - - - - - -
A 7 8 - - - - - - - - - - -
D677E 59
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74
Cable cross-sections
for contactors without thermal overload relay
1 cable per clamp
main connector solid or stranded mm² 0,75 - 6 1,5 - 25 4 - 50
flexible mm² 1-4 2,5 - 16 10 - 35
flexible with multicore cable end mm² 0,75 - 4 1,5 - 16 6 - 35
Frequency of operations z
Contactors without thermal overload relay
without load 1/h 10000 7000 7000
AC3, Ie 1/h 600 600 400
AC4, Ie 1/h 120 120 120
DC3, Ie 1/h 600 600 400
Mechanical life
AC operated S x 106 10 10 10
DC operated S x 106 10 10 10
DC-solenoid operated (KG3) S x 106 50 50 -
Short time current 10s-current A 96 120 144 176 184 240 296 450 504 592
120s-current A 42 52 58 66 80 97 110 195 203 222
Power loss per pole at Ie/AC3 400V W 0,21 0,35 0,5 0,75 0,7 1,3 2 2,2 3,9 5,5
contact resistance mOhm 2,1 1,8 1,5 1,5 1,2 1,2 1,2 1 1 1
1) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3
60 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type K3-90 K3-115 K3-116 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200
A 250 250 200 250 315 400 450 500 630 630 800 1000 1000 1250
A 160 200 160 200 250 315 400 400 500 560 - - - -
AWG 18 - 10 -
AWG 18 - 3/0 8 - 4/0
AWG -
S x 106 5 10 5 5 5 3)
S x 106 5 10 5 5 5 3)
S x 106 - - - - -
A 680 880 920 1200 1400 1800 2200 2600 3600 4400 5600 6900 8000 9600
A 275 330 410 500 575 800 900 1000 1400 1750 2200 2600 3000 3600
g 7 7 - - - - - - - - - - - -
g 5 5 - - - - - - - - - - - -
1) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3
2) With reduced control voltage range 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3
3) After each 1x106 operations magnetic core and built-in auxiliary contact block must be changed
D677E 61
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Auxiliary Contacts Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74
Short circuit protection For contactors with thermal overload relay the device with the smaller admissible control
short-circuit current 1kA, fuse (contactor or thermal overload relay) determines the fuse.
contact welding not accepted
max. fuse size gL (gG) A 20 (25)5) - -
Control Circuit
Power consumption of coils
AC operated inrush VA 33-45 90-115 140-165
sealed VA 7-10 9-13 13-18
W 2,6-3 2,7-4 5,4-7
Cable cross-section
Auxiliary connector solid mm² 0,75-6 - -
flexible mm² 1-4 - -
flexible with multicore cable end mm² 0,75-4 - -
1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request
2) Total breaking time = release time + arc duration
3) Values for delay of the release time of the make contact and the make time of the break contact will be increased, if magnet coils are protected against voltage
peaks (varistor, RC-unit, diode-unit)
4) with built-in coil suppressor 5) for contactors KG3-..A.. only
62 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type K3-90 K3-115 K3-116 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200
A - - - 10 10 10
A - - - - - - -
- - - - - -
A - - - 3 3 3
A - - - 2 2 2
A - - - 1,5 1,5 1,5
A - - - - - -
A - - - 1 1 1
A - - - 0,5 0,5 0,5
A - - - 10 10 10
W - - - - - -
W - - - - - -
ms - - - - -
ms - - - - -
ms - - - - -
AWG - - - 16 - 12 16 - 12
AWG - - - 16 - 12 16 - 12
AWG 14 - 12 16 - 12 16 - 12 16 - 12 16 - 12
AWG 18 - 12 16 - 12 16 - 12 16 - 12 16 - 12
2 2 2 2 2
D677E 63
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K2-09 K2-12 K2-16 K2-23 K2-30 K2-37 K2-45 K2-60 K85 K110
Making capacity Ieff at Ue = 690V AC A 200 200 200 400 500 500 700 900 1100 1200
Breaking capacity Ieff 400V~ A 180 180 200 380 400 400 600 800 950 1100
K2-09 to K2-16 cosϕ = 0,65 500V AC A 150 150 180 300 370 370 500 700 850 1100
K2-23 to K3-1200 cosϕ = 0,35 690V AC A 100 100 150 260 340 340 400 500 600 600
1000V~ A - - - - - - - - - -
440V kW 15 19 19 26,5 30 30 48 61 71 95
500V kW 17 21,5 21,5 30 34 34 54 69 86 116
660V kW 22,5 28,5 28,5 40 45 45 72 91 114 142
380-400V A 10 12 16 23 30 37 45 60 85 110
415-440V A 9 12 16 23 30 37 45 60 85 110
500V A 9 12 16 23 30 30 45 55 85 110
660V A 7 9 9 17,5 21 21 33 42 60 60
690V A 6,5 8,5 8,5 17 20 20 31 40 58 58
1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
64 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K2-09 K2-12 K2-16 K2-23 K2-30 K2-37 K2-45 K2-60 K85 K110
380-400V A 10 12 16 23 30 37 45 60 85 85
415V A 9 12 16 21 28 37 45 60 85 85
440V A 9 12 16 21 28 37 45 60 85 85
500V A 9 12 16 17 23 23 45 55 85 85
660V A 7 9 9 13 17 17 33 42 60 60
690V A 6,5 8,5 8,5 12,5 16,5 16,5 31 40 57,5 57,5
Rated operational power 220-230V kVA 1,8 2,2 3 4,2 5,4 5,4 8 10,7 15 20
dependent on inrush n 240V kVA 1,9 2,3 3,1 4,3 5,6 5,6 8,3 11,2 15,5 20,5
380-400V kVA 3,1 3,8 5,2 7,3 9,3 9,3 13,5 18,5 26 34
For different inrush-factors x 415-440V kVA 3,4 4,2 5,7 8 10,2 10,2 15 20,5 29 38
use the following formula: 500V kVA 3,9 4,8 6,5 9 11,5 11,5 17 23 33 43
Px=Pn*(n/x) 660-690V kVA 5,4 6,5 9 12,5 16 16 24 32 45 60
1) Metal halide lamps and sodium-vapour lamps (high- and low-pressure lamps)
2) High-pressure lamps
3) Blended lamps, containing a mercury high-pressure unit and a tungsten helix in a flourescent glass bulb (daylight lamps)
4) Current inrush approx. 16 x Ie
5) With central compensation pay attention to the current inrush (capacitor switching contactors)
D677E 65
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K2-09 K2-12 K2-16 K2-23 K2-30 K2-37 K2-45 K2-60 K85 K110
Cable cross-sections
for contactors without thermal overload relay
main connector solid or stranded mm² 0,75 - 4 1,5-10 + 1,5-6 4 - 35 2) 10 - 70 2)
flexible mm² 0,75 - 2,5 1,5-6 + 1,5-4 6 - 25 2) 10 - 70 2)
flexible with multicore cable end mm² 0,5 - 2,5 1,5-6 + 1,5-4 4 - 25 10 - 35
Cables per clamp 2 1+1 1 1
Frequency of operations z
Contactors without thermal overload relay
without load 1/h 10000 7000 7000 3000
AC3, Ie 1/h 600 600 400 300
AC4, Ie 1/h 120 120 120 120
DC3, Ie 1/h 600 600 400 300
Mechanical life
AC operated S x 106 10 10 10 5
DC operated with economy resistor S x 106 10 10 10 5
Short time current 10s-current A 96 120 144 184 240 296 360 504 680 880
Power loss per pole at Ie/AC3 400V W 0,21 0,26 0,4 0,63 1,1 1,7 1,8 3,6 4,3 6,0
1) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3
2) Maximum cable cross-section with prepared conductor
66 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Auxiliary Contacts Type K2-09 K2-12 K2-16 K2-23 K2-30 K2-37 K2-45 K2-60 K85 K110
500V A 3 3 - 4
660-690V A 1 1 - 2
Control Circuit
Cable cross-section
1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request
2) Total breaking time = release time + arc duration
3) Values for delay of the release time of the make contact and the make time of the break contact will be increased, if magnet coils are protected against voltage
peaks (varistor, RC-unit, diode-unit)
D677E 67
Contactors for North America
Data according to UL508
Main Contacts (cULus) Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74
380-415V hp 5 5 10 10 10 15 20 25 30 40
440-480V hp 5 7½ 10 15 15 20 25 30 40 50
550-600V hp 7½ 10 15 20 20 25 30 40 50 50
380-415V hp 3 3 5 5 5 7½ 10 15 20 20
440-480V hp 3 5 5 7½ 7½ 10 15 20 25 25
550-600V hp 3 5 7½ 10 10 15 20 25 30 30
440-480V hp - - - - 10 15 - 20 25 -
550-600V hp - - - - 10 20 - 25 30 -
Fuse Class RK5 / Short-circuit current A/kA 50/5 50/5 70/5 90/5 90/5 125/5 175/5 200/5 250/5 300/5
Fuse Class T / Short-circuit current A/kA 45/100 50/100 70/100 90/100 110/100 150/100 150/100 175/100 175/100 175/100
Rated voltage V 600 600 600 600 600 600 600 600 600 600
Main Contacts (cULus) Type K2-09 K2-12 K2-16 K2-23 K2-30 K2-45 K2-60 K85 K110
440-480V hp 5 7½ 10 15 20 30 40 65 75
550-600V hp 7½ 10 15 20 25 40 50 85 100
Fuse / Short-circuit current A/kA 30/5 40/5 50/5 60/5 110/5 175/5 175/5 - 300/5
Rated voltage V 600 600 600 600 600 600 600 600 600
Auxiliary Contacts (cULus) A600 A600 A600 A600 A600 - - A600 A600
68 D677E
Contactors for North America
Data according to UL508
Type K3-90 K3-115 K3-116 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200
A 160 200 150 180 220 250 300 350 420 520 700 810 - 1215
A 85 99 125 150 190 240 300 300 400 550 700 - 1000
hp 15 20 - - - - - - - - - - -
hp 25 35 30 40 50 60 75 100 125 150 200 250 - 450
hp 35 40 40 50 60 75 100 125 125 150 250 300 - 450
hp - - - - - - - - - - - - - -
hp 50 60 - - - - - - - - - - - -
hp 65 75 75 100 125 150 200 250 250 350 500 600 - 900
hp 85 100 100 125 150 200 250 300 250 350 500 600 - 900
hp 8 10 10 15 25 - - - - - - - - -
hp 15 20 20 - - - - - - - - - - -
hp 20 25 - 25 30 40 50 50 - - - - - -
hp 20 25 - - - - - - - - - - - -
hp 30 40 - - - - - - - - - - - -
hp 40 50 - - - - - - - - - - - -
hp 50 60 - - - - - - - - - - - -
A - - - - - - - - - - - - - -
hp - - - - - - - - - - - - - -
hp - - - - - - - - - - - - -
hp - - - - - - - - - - - - - -
hp - - - - - - - - - - - - - -
hp - - - - - - - - - - - - - -
A - - - - - - - - - - - - - -
A/kA 300/10 300/10 225/10 300/10 350/10 400/18 500/18 500/18 1200/18 1200/18 2000/30 2000/30 - 2000/42
Main Contacts (cULus) Type K3-18NK K3-24K K3-32K K3-50K K3-62K K3-74K K3-90K K3-115K
440-480V kVAr 0-15 11,5-25 11,5-30 25-40 25-60 25-72 1) 40-95 40-114 2)
550-600V kVAr 0-18 14,5-30 14,5-35 31-50 31-75 31-90 1) 50-120 50-143 2)
Fuse Class RK5 / Short-circuit current A/kA 70/5 90/5 125/5 200/5 250/5 300/5 300/10 300/10
Fuse Class T / Short-circuit current A/kA 80/100 110/100 150/100 175/100 175/100 175/100 300/100 3) 300/100 3)
Rated voltage V 600 600 600 600 600 600 600 600
1) Consider the max. thermal current of the contactor K3-74A: Ith 130A
2) Consider the min. cross-section of conductor at max. load
3) Class T and Class RK1
D677E 69
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Contact Life
For selection of the suitable contactor-type according to supply voltage, For contactors frequently used under AC3/AC4-mixed service conditions
power rating and application (utilization category AC1, AC3 or AC4) use calculate contact life with the formula:
contact life characteristic diagram.
For the most common supply voltages four scales of power ratings Pn are AC3
M=
%AC4 AC3
provided for each utilization category.
Select contactor-type according to utilization category AC3 (breaking
1+
100
x( AC4
-1 )
current Ia = Ie) using the motor rating scales to the right, according to M = Contact life (switching cycles) for AC3/AC4-mixed operations
utilization category AC4 (breaking current Ia = 6 x Ie) using the motor rating AC3 = Contact life (switching cycles) for AC3 operations (normal switching conditions).
scales to the left. 1) Breaking current Ia = rated motor current In.
AC4 = Contact life (switching cycles) for AC4 operations (inching).
Select contactor-type according to utilization category AC1 (breaking Breaking current Ia= multiples of rated motor current In.
current Ia = Ie/AC1) using the breaking current scale. 1) %AC4 = Percents of AC4-operations related to the total cycles.
Millions of Operations
Millions of Operations
1) Pay attention to the approved rated values of the selected contactor according to the national approvals
70 D677E
Contactors
Utilization Categories
For easier choice of devices and in order to make the comparison control circuit devices and switching elements according to
of different products simplier are utilization categories for contactors IEC 947-5-1 and VDE 0660 Part 200 determind. The table offers different
and motor-starters according to IEC 947-4-1 and VDE 0660 Part 102, for utilization categories, typical applications and assorted test conditions.
Type of Cate- Typical applications Rated Test conditions for the number of Test conditions for
current gory operational on-load operating cycles making and breaking capacities
current Make Break Make Break
I/Ie U/Ue cosϕ Ic/Ie Ur/Ue cosϕ I/Ie U/Ue cosϕ Ic/Ie Ur/Ue cosϕ
Alter- Non-inductive or
nating AC1 slightly inductive loads all values 1 1 0,95 1 1 0,95 1,5 1,05 0,8 1,5 1,05 0,8
Current resistance furnaces
Slip-ring motors:
AC2 starting, switching off all values 2,5 1 0,65 2,5 1 0,65 4 1,05 0,65 4 1,05 0,65
Squirrel-cage motors: Ie≤ 17A 6 1 0,65 1 0,17 0,65 10 1,05 0,45 8 1,05 0,45
AC3 starting, switching off 17A< Ie≤ 100A 6 1 0,35 1 0,17 0,35 10 1,05 0,45 8 1,05 0,45
motors during running Ie> 100A 6 1 0,35 1 0,17 0,35 10 1,05 0,35 8 1,05 0,35
Squirrel-cage motors: Ie≤ 17A 6 1 0,65 6 1 0,65 12 1,05 0,45 10 1,05 0,45
AC4 starting, plugging, 17A< Ie≤ 100A 6 1 0,35 6 1 0,35 12 1,05 0,45 10 1,05 0,45
inching Ie> 100A 6 1 0,35 6 1 0,35 12 1,05 0,35 10 1,05 0,35
Switching of electric
AC5a discharge lamp controls all values - - - - - - 3 1,05 0,45 3 1,05 0,45
Switching of
AC5b incandescent lamps all values - - - - - - 1,5 1,05 1)
4 1,05 1)
Switching of
AC6a transformers Ie≤ 100A - - - - - - 4,5 1,05 0,45 3,6 1,05 0,45
Ie> 100A - - - - - - 4,5 1,05 0,35 3,6 1,05 0,35
Switching of
AC6b capacitors - - - - - - - 2) 2)
Control of
DC14 electromagnetic loads having all values - - - - - - 10 1,1 15 10 1,1 15
economy resistors in circuit
Ue Rated operational voltage, U Voltage before make, U r Recovery voltage, Ie Rated operational current, I Current make, Ic Current broken
1) Test with incandescent lamps
2) Test conditions according to standard
D677E 71
Accessories
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type HN HTN HA HB HKT HKF K2-DK K2-TP K2-L 2)
HKA HKB K2-SK
Cable cross-sections
solid or stranded mm² 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 1-2,5 0,75-2,5
flexible mm² 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5
flexible with multicore cable end mm² 0,5-1,5 0,5-1,5 0,5-1,5 0,5-1,5 0,5-1,5 0,5-1,5 0,75-2,5 0,5-1,5
solid AWG 14 - 12 14 - 12 14 - 12 14 - 12 14 - 12 14 - 12 14 - 12 14 - 12 14 - 12
flexible AWG 18 - 12 18 - 12 18 - 12 18 - 12 18 - 12 18 - 12 18 - 12 18 - 12 18 - 12
1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request.
2) Command duration min. 30ms, 10% duty cycle, max. 30 eec.
72 D677E
Contactors and Accessories
Wiring diagrams
Auxiliary contact blocks Snap-on momentary contact blocks
HKF22 HKT22
Indicator units
red
red
Regulation of switch position of aux. contakt block HKF22 for contactors K3-450 to K3-860
HKF22 NO NO NO
Contactor position:
18 16 14 12 10 8 6 4 2 0 open 18 16 14 12 10 8 6 4 2 0 18 16 14 12 10 8 6 4 2 0
Standard position of regulation screw Regulation screw position (unscrew by 4 turns) Regulation screw position (screw by 4 turns)
D677E 73
Contactors
Dimensions
AC operated DC operated
K3-10N.. KG3-10..
K3-14N.. KG3-14..
K3-18N.. KG3-18..
K3-22N.. KG3-22..
1)
K3-24.. KG3-24..
K3-32.. KG3-32..
K3-40.. KG3-40..
K3-50.. K3-50..=
K3-62.. K3-62..=
K3-74.. K3-74..=
AC and DC operated
K3-90..
K3-115..
74 D677E
Contactors
Dimensions
AC operated, DC operated
K3-151..
K3-176..
HKA11 HKT..
K3-210..
K3-260..
K3-316..
HKA11 HKT..
K3-450..
K3-550..
Typ A B C H N
D677E 75
Contactors
Dimensions
AC and DC operated
K3-700..
K3-860..
Typ B H N
K3-1000..
K3-1200..
1) for K3-1200 in UL conformity application only
K3-18NK.. K3-24K..
K3-32K..
K3-50K.. K3-90K..
K3-62K.. K3-115K..
K3-74K..
76 D677E
Contactors
Dimensions
Contactors DC operated
K3-10N..= K3-24..=
K3-14N..= K3-32..=
K3-18N..= K3-40..=
K3-22N..=
K3-10NA00-40 K2-23A00-40
K3-14NA00-40 K2-30A00-40
K3-18NA00-40 K2-37A00-40
K3-22NA00-40
K2-45A00-40 K3-116A00-40
K2-60A00-40 K3-151A00-40
K3-176A00-40
K3-210A00-40
K3-260A00-40
K3-316A00-40
D677E 77
Contactors
Dimensions Accessories
Aux. cont. blocks, terminal blocks Snap-on momentary cont. blocks Auxiliary contact blocks
HN10, HN01 K2-SK, K2-DK HTN10, HTN01 HA10, HA01 HB11, HB02
Type A B C D E F G H
78 D677E
Contactors
Dimensions Accessories
Mechanical interlocks
LG11478 K3-90 bis K3-115 K3-90 bis K3-115 90 12 90 100 100 75 27 75 5,5 5,5
LG11223H K3-151, -176 K3-151, -176 110 30 110 130 130 100 40 100 6 6 3-pole contactor
LG11223H K3-116,-151, -176 K3-116,-151, -176 147 30 147 130 130 135 42 135 6 6 4-pole contactor
LG11223H K3-210, -260, -316 K3-210, -260, -316 145 30 145 160 160 120 55 120 6 6 3-pole contactor
LG11223H K3-210, -260, -316 K3-210, -260, -316 193 30 193 160 160 170 55 170 6 6 4-pole contactor
LG10400H K3-450, K3-550 K3-450, K3-550 220 42 220 220 220 110 152 110 9 9
LG10402H K3-700, -860 K3-700, -860 280 32 280 280 280 175 137 175 11 11
LG10403H K3-1000, -1200 K3-1000, -1200 334 46 334 380 380 120 260 120 13,5 13,5
LG10399H K3-450, -550 K3-700, -860 220 37 280 220 280 110 144,5 175 9 11
LG10401H K3-700, -860 K3-1000, -1200 280 73 334 280 380 175 232,5 120 11 13,5
LG10400V K3-315 - K3-550 K3-315 - K3-550 250 134 220 94 220 110 110 - - 9 9
LG10402V K3-700, -860 K3-700, -860 302 162 280 200 280 175 175 - - 11 11
LG10403V K3-1000, -1200 K3-1000, -1200 - - 380 280 380 120 120 - - 13,5 13,5
LG10399V K3-450, -550 K3-700, -860 302 - 220 150 280 110 175 51 74,5 9 11
LG10401V K3-700, -860 K3-1000, -1200 - - 280 240 380 175 120 - - 11 13,5
D677E 79
Contactors
Dimensions Accessories
Latch
K2-L..
LG9339N (2 x 3 pieces)
for K3-10N. to K3-22N.
80 D677E
Contactors
Dimensions Accessories
Interface Snap-on adapter
K2-IM K2-SM
Suppressor units
RC-K3N .. RC-K3NW ..
Marking systems
marking label
P487-1 or P245-.
D677E 81
Contactors
Position of terminals
K3-10ND10 K3-10ND01 K3-24A00, K3-24K00 K3-50A00, K3-50K00 K3-10NA00-40 K85A22
K3-14ND10 K3-14ND01 K3-32A00, K3-32K00 K3-62A00, K3-62K00 K3-14NA00-40 K110A22
K3-18ND10 K3-18ND01 K3-40A00 K3-74A00, K3-74K00 K3-18NA00-40
K3-22ND10 K3-22ND01 K3-22NA00-40
K3-18NK10 K3-18NK01 K2-23A00-40 bis
K2-60A00-40
K3-116A00-40
K3-90A00 K3-151A00 K3-151A00-40 K3-450A22 K3-1000A12
K3-115A00 K3-176A00 K3-176A00-40 K3-550A22 K3-1200A12
K3-210A00 K3-210A00-40 K3-700A22
K3-260A00 K3-260A00-40 K3-860A22
K3-316A00 K3-316A00-40
82 D677E
Motor Starters
Accessories 87
Reversing Contactors 88
Technical Data 92
Wiring Diagrams 95
Dimensions 99
D677E 83
Star-Delta Starters Open Type AC Operated
30 37 30 60 K3Y52 . . . 1 1,8
Star-delta starters are wired to accept thermal overload relay. The thermal overload relay has to be ordered separately.
For full load current setting use the YD-dial of thermal overload relay.
Ordering Example: Star-Delta Starter, open type, rated AC3 at 400V 205A
rated control voltage 230V 50Hz - Order Type: K3Y200 230 + U85 120
18 - 24 U12/16E 14 K3 1 0,10
23 - 31 U12/16E 18 K3 1 0,10
manual eset
18 - 24 U3/32 14 1 0,14
23 - 31 U3/32 18 1 0,14
30 - 41 U3/32 24 1 0,14 manual and
auto reset
40 - 55 U3/32 32 1 0,14
84 D677E
Components for Combinations Auxiliary Contacts Free Space for
Line Delta Star Electronic Mechanical Star-Delta Built-in for use Aux. Contact Blocks
Contactor Contactor Contactor Timer Interlock Starter on Contactor on Contactor
between Connector Line Delta Star Line Delta Star
K1 K2 K3 K4 K2 and K3 K1 K2 K3 K1 K2 K3
Type Type Type Type Type Type NO/NCNO/NCNO/NC HN.. or HA..
The star-delta starting method is only practicable in such cases where the The transition from start (star configuration) to normal operation (delta
motor windings are connected in delta configuration for normal operation configuration) should be after the motor achieves practically full rotational
and the torque which is needed during the starting period is not higher speed. The use of star-delta timer Y9A with a dwell period of approx. 25ms
than approx. 30% of the rated torque. The starting current drawn from the provides a careful operation of motor and drive equipment.
line will be approx. 2 to 2,7 times the rated motor current.
manual and
auto reset
D677E 85
Star-Delta Starters Enclosed Type AC Operated
Plastic Enclosed
Enclosed, protected to IP65
15 18,5 15 30 ST U3/32 K3NY26P . . . 1 1,8
Ordering Example: Star-Delta Starter, steel sheet enclosed, with selector switch and run hour meter
rated AC3 at 400V 82A, rated control voltage 230V 50Hz - Order Type: K3Y80BWH 230 + U3/74 52
Plastic IP65
K3NY15, K3NY26 U3/32 K3Y26P-G3 1 1,0
K3Y40, K3Y52 U3/42, U3/32 K3Y40/52P-G3 1 2,4
86 D677E
Star-Delta Starter Connector
Additional Terminals
Mounting Bar
Specification Type Pack Weight
pcs. kg/pc.
D677E 87
Reversing Contactors with Mechanical Interlock AC Operated
Open Type
4 5,5 5,5 10 U3/32 K3NWU10 . . . 1 0,6
U12/16E K3
30 37 37 62 K3WU62 . . . 1 2,5
37 45 45 74 K3WU74 . . . 1 2,5
30 37 37 62 K3WU62B . . . 1 7,1
88 D677E
Components for Combinations Auxiliary Contacts Free Space for
Left Hand Side Right Hand Side Mechanical Reversing Built-in for use Aux. Contact Blocks
Contactor Contactor Interlock Starter on Contactor on Contactor
Connector
K1 K2 K1 K2 K1 K2
Type Type Type Type NO/NC NO/NC HN.. or HA..
D677E 89
Reversing Contactors for North America AC Operated
Open Type
4 5,5 5,5 10 U3/32 KNW3-10 . . . 1 0,6
U12/16E K3
Open Type
7,5 10 10 18 2 x U3/32 K3NPU18 . . . 1 1,0
2 x U12/16E K3
11 15 15 24 K3NPU24 . . . 1 1,5
30 37 37 62 K3PU62 . . . 1 3,9
11 15 15 24 K3NPU24B . . . 1 1,5
Ordering Example: Pole Changing Starter, open version, rated AC3 at 400V 28A and 15A, control voltage 230V 50Hz
Order Type: K3PU32 230 + U3/32 32 + U3/32 18
90 D677E
Components for Combinations Auxiliary Contacts Free Space for
Left Hand Side Right Hand Side Mechanical Built-in for use Aux. Contact Blocks
Contactor Contactor Interlock on Contactor on Contactor
K1 K2 K1 K2 K1 K2
Type Type Type NO/NC NO/NC HN.. or HA..
D677E 91
Star-Delta Starters
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Type K3NY15 K3NY26 K3Y40 K3Y52 K3Y80 K3Y100 K3Y140 K3Y200 K3Y240 K3Y300
Main Contacts
Rated insulation voltage Ui 1) V AC 690 690 690 690 690 690 690 690 690 690
Cable cross-sections
Line solid or stranded mm² 1,5 - 6 2) 1,5 - 16 10 - 70 3) 10 - 120 busbar
flexible mm² 1,5 - 4 2) 1,5 - 16 16 - 50 3) 10 - 95 18x5
lexible with multicore cable end mm² 1,5 - 4 2) 1,5 - 16 10 - 35 10 - 95 M8
Motor
solid or stranded mm² 1,5 - 6 1,5 - 16 4 - 35 3) 10 - 120 busbar
flexible mm² 1,5 - 4 1,5 - 16 6 - 25 3) 10 - 95 18x5
lexible with multicore cable end mm² 1,5 - 4 1,5 - 16 4 - 25 10 - 95 M8
Coil Voltage Ranges and Non Standard Voltages for Star-Delta Starters
24 24 24 24 27 24 24 24 24 24 24
42 42 47 47 52 48 48 48 48 48 48
110 100 110 110 122 110 110 120 110 120 110
180 180 210 200 240 230 220 240 220 240 220
230 220 240 230 264 400 380 415 380 415 -
400 380 415 400 415
92 D677E
Reversing Starters
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Type K3NWU10 K3NWU18 K3WU24 K3WU32 K3WU50 K3WU62 K3WU74
Main Contacts
Rated insulation voltage Ui 1) V AC 690 690 690 690 690 690 690
380-400V A 10 18 24 32 50 62 74
415-440V A 9 18 23 30 50 62 74
500V A 9 16 23 30 45 60 74
660-690V A 6,5 8,5 17 20 31 40 40
Cable cross-sections
Line solid or stranded mm² 0,75 - 6 1,5 - 25 4 - 50
flexible mm² 1-4 2,5 - 16 6 - 35
flexible with multicore cable end mm² 0,75 - 4 1,5 - 16 6 - 35
Cables per clamp 1 1 1
380-415V hp 5 10 10 15 20
440-480V hp 5 10 15 20 25
550-600V hp 7½ 15 20 25 30
Cable cross-sections
for main connectors solid AWG 18 - 10 16 - 10
flexible AWG 18 - 10 14 - 4
Cables per clamp 1 1
1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request.
D677E 93
Pole Changing Starters
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Type K3NPU18 K3NPU24 K3PU32 K3PU50 K3PU62
Main Contacts
Rated insulation voltage Ui 1) V AC 690 690 690 690 690
380-400V A 16 23 30 45 60
415V A 16 23 30 45 60
440V A 16 23 30 45 60
500V A 16 23 30 45 55
660V A 9 17,5 21 33 42
690V A 8,5 17 20 31 40
415-440V kW 8,5 12 16 24 33
500V kW 10 15 18,5 30 37
660-690V kW 7,5 15 18,5 30 37
Cable cross-sections
Line solid or stranded mm² 0,75 - 6 1,5 - 25 4 - 50
flexible mm² 1-4 2,5 - 16 6 - 35
flexible with multicore cable end mm² 0,75 - 4 1,5 - 16 6 - 35
cables per clamp 1 1 1
1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request.
94 D677E
Star-Delta Starters
Wiring Diagrams Main Circuit
Terminal markings of contactors and relays according to DIN EN 50012
Connections shown in main and circuits as broken lines are not included.
D677E 95
Star-Delta Starters
Wiring Diagrams Main Circuit
Terminal markings of contactors and relays according to DIN EN 50012
Connections shown in main and control circuits as broken lines are not included.
96 D677E
Reversing Contactors
Wiring Diagrams Main Circuit
Terminal markings of contactors and relays according to DIN EN 50012
Connections shown in main and control circuits as broken lines are not included.
K3NWU10 to K3WU74
with thermal overload relay U3/32, U3/42 or U3/74
D677E 97
Pole Changing Starters
Wiring Diagrams
Terminal markings of contactors and relays according to DIN EN 50012
Connections shown in main and control circuits as broken lines are not included.
98 D677E
Star-Delta Starters
Dimensions
Star-Delta Starters, AC operated, open type
D677E 99
Star-Delta Starters
Dimensions
Star-Delta Starters, plastic enclosed, protected to IP65
2 x Ø50,5/25,5 + Ø20,5
Type A B C D E ØF ØG H J
K3Y26B to K3Y52B
Type ØF ØG
K3Y80B to K2Y200B
Type A B C D E L M
Type ØF ØG H J K
100 D677E
Reversing Contactors
Dimensions
Reversing Starters, AC operated, open type
K3WU50 + U3/74
K3WU62
K3WU74
Type A B C D E F G H K
D677E 101
Pole Changing Starters
Dimensions
Pole Changing Starters, AC operated, open type
K3NPU18B to K3PU32B
Type ØF ØG
102 D677E
D.O.L
.L.. Starters
.O.L
Enclosures 105
Accessories 105
Dimensions 108
D677E 103
D.O.L. Starters In Plastic Enclosure
D.O.L. Starters with Selector Switch and Pneumatic Switch for moist rooms
7,5 K3-18ND10 2 U12/16 K3 IP65 Ø 20,5mm P1W18P . . . 1 0,6
Ordering Example: D.O.L. Starter with selector switch, plastic enclosed, rated AC3 at 400V 15,5A,
rated control voltage 230V 50Hz - Order Type: P1W18 230 + U12/16E 18 K3
4 - 6 U12/16E 6 K3 1 0,10
6 - 9 U12/16E 9 K3 1 0,10
8 - 11 U12/16E 11 K3 1 0,10
10 - 14 U12/16E 14 K3 1 0,10
13 - 18 U12/16E 18 K3 1 0,10
17 - 23 U12/16E 23 K3 1 0,10
22 - 30 U12/16E 30 K3 1 0,13
104 D677E
Enclosures for Contactors
Indicator Units
Specifications Voltage Range Type Pack Weight
pcs. kg/pc.
Voltage Indicator
Indicator, clear (glow-disc. l.) 220 - 415V AC/DC K2-UN 10 0,02
Voltage Indicator
Indicator, red (LED) 24 - 120V AC/DC K2-UNR 10 0,02
To be connected parallel to the contactor coil. In case of
applied voltage the indicator also lights at coil interruption.
Heating Element
Specifications Voltage Range Type Pack Weight
Power Consumption pcs. kg/pc.
1)
without auxiliary contact blocks
D677E 105
D.O.L. Starters
Wiring Diagrams Main Circuit
All fuses F0 shown in the main circuits are not included.
Terminal markings according to EN 50012
Coil phase to phase Coil phase to neutral Coil phase to phase Coil phase to neutral
(380-415V 50Hz) (220-240V 50Hz)
P1..
Remote 2-wire (switch) control Remote 3-wire (push button) control Remote start-stop control
(3 control stations)
106 D677E
D.O.L. Starters
Wiring Diagrams Control Circuits
Typical circuit diagram (for separate coil supply, control circuit connected between L1 and N)
Terminal markings according to EN 50012
push button
ON/OFF
D677E 107
D.O.L. Starters
Dimensions
D.O.L. Starters with Start-Stop/Reset Push Buttons, Plastic Enclosed D.O.L. Starters with Selector Switch, Plastic Enclosed
knockouts
4 x Ø 23
Earth Terminal LG9750 for K2-23 and K2-30 in Enclosure P1 Neutral Terminal LG9744
LG9750
LG9744
108 D677E
Enclosures
Dimensions
Enclosures for Contactors Enclosures for D.O.L. Starters
P1 P1R, P1P
knockouts
4 x Ø 23
D677E 109
D.O.L. Starters
Mounting and Wiring Instructions
Indicators and Lens Caps for D.O.L. Starters P1
K2-UN., K2-IN.
LG9743.
Wiring Examples
red
red
110 D677E
Thermal Overload Relays
Accessories 115
Dimensions 121
D677E 111
Thermal Overload Relays for plug-in mounting
10 - 14 18 - 24 U12/16E 14 K1 1 0,10
10 - 14 18 - 24 U12/16A 14 K1 1 0,10
With Quick Tripping Characteristic for EEx e motors and submersible pumps, f. contactors K1-..
0,4 - 0,6 - U12/16EQ 0,6 K1 1 0,10
0,6 - 0,9 - U12/16EQ 0,9 K1 1 0,10
0,8 - 1,2 - U12/16EQ 1,2 K1 1 0,10
10 - 14 18 - 24 U12/16EQ 14 K1 1 0,10
112 D677E
Thermal Overload Relays for plug-in mounting
10 - 14 18 - 24 U12/16E 14 K3 1 0,10
13 - 18 23 - 31 U12/16E 18 K3 1 0,10
17 - 23 30 - 40 U12/16E 23 K3 1 0,10
22 - 30 38 - 52 U12/16E 30 K3 1 0,13
With quick Tripping Characteristic for EEx e motors and under water pumps
0,4 - 0,6 - U12/16EQ 0,6 K3 1 0,10
0,6 - 0,9 - U12/16EQ 0,9 K3 1 0,10
0,8 - 1,2 - U12/16EQ 1,2 K3 1 0,10
10 - 14 18 - 24 U12/16EQ 14 K3 1 0,10
10 - 14 18 - 24 U3/32 14 1 0,14
13 - 18 23 - 31 U3/32 18 1 0,14
17 - 24 30 - 41 U3/32 24 1 0,14
23 - 32 40 - 55 U3/32 32 1 0,14
20 - 28 35 - 48 U3/42 28 1 0,30
28 - 42 48 - 73 U3/42 42 1 0,30 manual and
auto reset
D677E 113
Thermal Overload Relays for plug-in mounting
manual and
For contactors K3-210.. up to K3-316.., busbars included auto reset
144 - 216 250 - 374 U320 216 1 1,8
216 - 320 374 - 554 U320 320
With Slow Tripping Characteristic for heavy duty starting with long run up times
For separate mounting, suitable for all contactors
0,8 - 1,2 1,2 - 2,1 UAT21 1,2 1 1,0
1,2 - 1,8 2,1 - 3,1 UAT21 1,8 1 1,0
1,6 - 2,4 2,8 - 4,2 UAT21 2,4 1 1,0
114 D677E
Accessories
Busbar Sets
U800 K3-450.. , K3-550.. SU840/550 1 1,7
U800 K3-700.. , K3-860.. SU840/860 2,1
D677E 115
Thermal Overload Relays
Relays, tripping times for selection to motors of protection degree EEx e
Relays With Standard Tripping Characteristic Relays With Quick Tripping Characteristic
preferably for motors with short tE time
and for submersible pumps
Setting Range Tripping time depending on the multiple Setting Range Tripping time depending on the multiple
of the current setting from cold condition of the current setting from cold condition
(tolerance ±20% of the tripping time) (tolerance ±20% of the tripping time)
IA/I N IA/I N IA/IN IA/I N IA/IN IA/IN IA/IN IA/I N IA/I N IA/I N IA/IN IA/IN
A A 3 4 5 6 7,2 8 A A 3 4 5 6 7,2 8
U3/32 .. s s s s s s U12/16EQ .. s s s s s s
0,12 - 0,18 16,1 9,6 6,8 5,3 4,2 3,7 0,4 - 0,6 13,6 8,4 5,9 4,2 3,3 3,0
0,18 - 0,27 16,6 9,7 6,7 5,2 4,1 3,6 0,6 - 0,9 13,8 7,8 5,2 4,1 3,2 2,7
0,27 - 0,4 19,4 11,4 7,9 6,1 4,7 4,2 0,8 - 1,2 13,1 7,5 5,2 3,9 3,1 2,7
0,4 - 0,6 18,7 10,9 7,6 5,9 4,6 4,0 1,2 - 1,8 14,6 8,7 6,0 4,6 3,6 3,2
0,6 - 0,9 19,2 11,2 7,7 5,9 4,6 4,1 1,8 - 2,7 13,5 7,6 5,3 3,9 3,1 2,7
0,8 - 1,2 20,8 12,3 8,5 6,6 5,2 4,6 2,7 - 4 11,0 6,0 4,1 2,6 1,7 1,4
1,2 - 1,8 25,5 14,1 9,8 7,6 5,9 5,2 4 - 6 9,6 5,3 3,3 2,3 1,6 1,3
1,8 - 2,7 26,6 15,6 10,9 8,3 6,5 5,7 6 - 9 10,2 5,4 3,4 2,3 1,6 1,3
2,7 - 4 22,7 13,6 9,5 7,4 5,8 5,1 8 - 11 12,0 6,2 3,9 2,5 1,8 1,3
4 - 6 22,2 13,3 9,3 7,1 5,6 4,9 10 - 14 12,8 6,6 4,0 2,6 1,8 1,4
6 - 9 20,4 11,9 8,2 6,1 4,7 4,0
8 - 11 20,9 11,8 7,9 5,7 4,3 3,5 All tripping times of overload relays U12/16EQ are shorter than the
minimum values of the tE time for motors of protection degree EEx e acc.
10 - 14 21,3 11,7 7,4 5,1 3,7 3,0 to EN 50019 and therefore are suitable for all motors of protection
13 - 18 21,2 12,1 8,0 6,2 4,6 4,1 degree EEx e. For these overload relays the selection on basis of
17 - 24 20,4 12,0 8,6 6,3 4,5 3,7 tripping curves is thereby not necessary.
23 - 32 20,2 10,2 6,7 4,7 3,4 2,8
U3/42 s s s s s s When selecting a standard overload, refer to the tripping curve. Determine
the values of the starting current ratio IA/IN and the time tE which is marked
10 - 14 21,8 11,4 7,0 5,0 3,7 2,8 on the label of the motor. The overload must trip within the tE time, which
14 - 20 22,4 11,2 6,7 4,5 3,2 2,4 means that the tripping curve from cold condition must be (20% due to
20 - 28 21,8 10,8 6,5 4,5 3,3 2,5
tolerance) below the co-ordination point IA/IN and the time tE.
28 - 42 25,2 13,3 8,0 5,5 4,0 3,1
I A = Starting current of motor I N = Rated current of motor
U3/74 s s s s s s t E = tE-time of motor
20 - 28 21,8 10,8 6,5 4,5 3,3 2,5
28 - 42 25,2 13,3 8,0 5,5 4,0 3,1
52 Time tE /Tripping time
40 - 18,3 9,2 5,6 3,9 2,8 2,2
65 s
52 - 17,8 8,7 5,2 3,4 2,5 1,9
U85 .. s s s s s s
Typical tripping
60 - 90 19,5 13,5 11,0 10,0 9,5 8,5 curve for overload
80 - 120 18,0 11,0 10,0 9,0 8,5 8,0 relay U12/16E
116 D677E
Thermal Overload Relays
Fuses for U3/32, U3/42, U3/74, U12/16E, U85, U180, U320 and U800
Max. Fuse Size According to Coordination-type Fuse UL SCCR
Type Setting Range "2" 1) "1" 1)
DOL quick slow, gL(gG) slow, gL(gG) aM
A A A A A A A kA
(22)23 -(30)32
(30)32 (38)40 -(52)55 80 63 80 35 70 5
U3/42 10 - 14 18 - 24 50 35 80 16 40 5
14 - 20 24 - 35 63 50 80 25 60 5
20 - 28 35 - 48 80 63 80 35 80 5
28 - 42 48 - 73 100 80 150 50 110 5
Tripping time (Average value of typical tolerance curves Tripping time (Typical tolerance curve
min. s from cold condition) min. s from cold condition)
Proceeding from service condition the times decrease
decrease to 20-30% of the characteristic values
Proceeding from service condition the times
D677E 117
Thermal Overload Relays
Tripping Characteristics for U85, U180, U320, and U800
Detailed tripping times for each range of U85 see table page 106
U85 with three-phase load U180, U320 with three-phase load U800 with three-phase load
Tripping time (Average value of typical tolerance Tripping time (Average value of typical tolerance Tripping time (Average value of typical tolerance
min. s curves from cold condition) min. s curves from cold condition) min. s curves from cold condition)
Position of Terminals
U3/32 U12/16E, U12/16EM, U12/16EQ U12/16A U3/42, U3/74
118 D677E
Thermal Overload Relays in Special Version
Fuse for U12/16EQ Fuse for U12/16EM
Setting Range Maximum Fuse Acc. to Coordination-type Setting Range Maximum Fuse Acc. to Coordination-type "2" 1)
"2" 1) "1" 1) 380-400V 500V 660-690V
quick slow, gL(gG) slow, gL(gG) slow, gL(gG) slow, gL(gG) slow, gL(gG)
A A A A A A A A
10 - 14 50 35 63
F. L. C. multiplication factor
F. L. C. multiplication factor
F. L. C. multiplication factor
D677E 119
Thermal Overload Relays
Data according to IEC 947-4-1, IEC 947-5-1, VDE 0660, EN 60947-4-1, EN 60947-5-1
Type U3/32 U12/16 6) U3/42 U3/74 U85 U180 U320 U800 UAT21 UAT22 UAT23
V~ 690 690 690 690 750 1000 1000 1000 690 690 690
Permissible ambient temperature
operation open °C -25 to +60 -25 to +55 -25 to +60
storage °C -50 to +70 -40 to +70 -50 to +70
Cable cross-section
main connector solid or stranded mm² 0,75-6 0,75-6+0,75-2,5 2) 0,75-10 4-35 2) 3) 7) - 7) 0,5-10 0,5-16 0,5-25
flexible mm² 1-4 0,75-4+0,5-2,5 2 ) 0,75-6 6-25 2) 0,5-6 0,5-10 0,5-16
flexible with multicore cable end mm² 0,75-4 0,5-2,5+0,5-1,5 0,75-6 4-25 0,5-6 0,5-10 0,5-16
Cables per clamp number 2 1+1 2 1 1 1 1
Type U3/32 U12/16A U12/16E U12/16EQ U3/42 U85 U180 U800 UAT21
U12/16EM U3/74 U320 UAT22
Auxiliary contacts UAT23
Rated insulation voltage Ui 1)
same potential V~ 690 690 690 690 690 690 690 500 690
different potential V~ 440 - 440 440 250 440 440 500 440
Rated insulation voltage V~ 600 600 600 600 600 600 600
Rated current A 32 23 23 23 42 74 85
Auxiliary contacts
Rated voltage
same potential V AC 600 600 600 600 600 600 600
different potential V~ 150 - 150 150 150 150 150
Temperature Compensation
In case of higher ambient temperature use the following formula: Example: Ambient temperature 70°C, full load motor current 7A
(Ambient temperature - 20) x 0,125 = correction factor in % of the (70 - 20) x 0,125 = 6,25%
full load motor current Setting value: 7A + 6,25% = 7,44A
1) Suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 4kV (at 440V), 6kV (at 690V).
Data for other conditions on request.
2) Maximum cable cross-section with prepared conductor
3) Without terminals, suitable for bushing one connector 70mm² (stranded) per phase
4) Switching capacity of the start contact: AC15 300VA, max. 1,5A, DC13 (max. 220V) 30W, max. 1,5A
5) Switching capacity of the make contact: AC15 400VA, max. 1,7A, DC13 (max. 220V) 10W, max. 1A
6) U12/16E 30: Cable cross-section for main connector like type U3/42, one connector only
7) Busbar sets see accessories page 105
120 D677E
Thermal Overload Relays
Dimensions
K3-10N + U3/32 KG3-10 + U3/32
K3-14N KG3-14
K3-18N KG3-18
K3-22N KG3-22
D677E 121
Thermal Overload Relays
Dimensions
K1-09 + U12/16.. K1 K3-10 + U12/16..K3
K1-12 K3-14
K3-18
K3-22
U12SM K3
K3-50 + U3/74
K3-62
K3-74
122 D677E
Thermal Overload Relays
Dimensions
K3-90A + U85
K3-115A
D677E 123
Thermal Overload Relays
Dimensions
U800
U800 with A B C D E F G H J K
UAT21 UAT22
UAT23
124 D677E
Modular Contactors
Dimensions 132
D677E 125
Modular Contactors
1) Sealable with Sealing Cover P721, available aux. contact block RH11(see page 117)
2) Sealable with Sealing Cover P721, available aux. contact block RH11-1(see page 117)
126 D677E
Modular Contactors
Rated Heating Power Type coil voltage
Current AC1 at 24 24V 50/60Hz
AC1 1-phase 3-phase 230 220-240V 50Hz, 230-264V 60Hz
400V 230V 400V ⏐ Pack Weight
A kW kW W pcs. kg/pc. Wiring Diagram
40 9 - R40-22 24 4 0,35
40 9 - R40-22 230 4 0,35
Auxiliary Contact Block ½ module (8,8mm) for contactor R25 (4p.), R40, R63 (max. 1pc.)
3 2 10 R25-..VM
VM RH11-1 3 0,026
40 - 60°C
1) Sealable with Sealing Cover P690, available aux. contact block RH11
2) AC-operated R25-.., 4-pole
D677E 127
Day-Night Reloading Contactors
Pack Weight
Type pcs. kg/pc. Wiring Diagram
2 Switch positions:
Day (Reloading, contact 11-14 ... closed, remains in position Night, until the next occurs)
Night (Basis operation) contact 11-12 ... closed
4 Switch position:
Day (Reloading, contact 1-2 ... closed, remains in position Night, until the next occurs)
Night (automatic operation, contact 1-2 ... only at night closed)
On (Permanently On)
Off (permanently Off)
Modular Contactors
Switching of lamps
Lamp Type Power Current Capacitors Max. lamps per pole at 230V 50Hz and max. 60°C
W A μF R20.. R25.. R40.. R63..
300 1,36 - 4 10 19 26
500 2,27 - 3 6 11 16
1000 4,5 - 1 3 6 8
36 0,22 - 2 x 30 2 x 33 2 x 70 2 x 100
58 0,35 - 2 x 20 2 x 22 2 x 45 2 x 70
65 0,35 - 2 x 15 2 x 16 2 x 40 2 x 60
85 0,47 - 2 x 10 2 x 11 2 x 30 2 x 40
36 0,27 4 10 32 50 80
58 0,45 7 6 18 36 46
65 0,5 7 5 18 36 46
85 0,6 8 4 16 33 44
128 D677E
Modular Contactors
Switching of lamps
Lamp Type Power Current Capacitors Max. lamps per pole at 230V 50Hz and max. 60°C
W A μF R20.. R25.. R40.. R63..
2 x 18 0,17 - 20 20 50 60
2 x 28 0,25 - 15 15 37 45
2 x 36 0,32 - 10 10 25 30
2 x 58 0,49 - 7 7 15 20
2 x 80 0,7 - 4 4 8 10
250 3 - 4 5 10 12
400 3,5 - 3 4 8 10
1000 9,5 - 1 1 3 4
2000 16,5 - - - 2 2
400V per pole 2000 10,5 - - - 2 2
3500 18 - - - 1 1
250 1,5 33 1 4 9 11
400 2,1 35 1 4 9 10
1000 5,8 95 - 1 3 4
2000 11,5 148 - - 2 2
400V per pole 2000 6,6 58 - - 3 4
3500 11,6 100 - - 2 3
D677E 129
Modular Contactors
Switching of lamps
Lamp Type Power Current Capacitors Max. lamps per pole at 230V 50Hz and max. 60°C
W A μF R20.. R25.. R40.. R63..
135 0,94 45 1 3 7 8
150 1 40 1 3 8 9
180 1,16 40 1 3 8 9
200 1,32 25 - - 10 12
Main Contacts 5) 6) 7)
Rated insulation voltage Ui V~ 440 2) 440 2) 440 2) 440 2) 440 2) 440 2) 440 2) 440 2)
Rated operation voltage Ue V~ 440 440 440 440 440 440 440 440
Frequency of operations zzAC1, AC3 1/h300 300 600 600 300 600 600 600
Mechanical life S x 106 1 1 1 1 1 1 1 1
1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
2) Suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 4kV.
3) Maximum cable cross-section with prepared conductor
5) Rated frequency 50/60Hz 6) Max. occ. switching overvoltage <4kV 7) Duty cycle: 100%
130 D677E
Modular Contactors
Data according to IEC60 947-4-1, IEC 60947-5-1, VDE 0660-5-1
Type R20 R25 (2p.) R25 (4p.) R25-..VM R40 R63 RH11
Cable cross-sections
Main connector solid or stranded mm² 1,5 - 10 1,5 - 10 1,5 - 10 1,5 - 10 2,5 - 25 2,5 - 25 0,5 - 2,5 3)
flexible mm² 1,5 - 6 1,5 - 6 1,5 - 6 1,5 - 6 2,5 - 16 2,5 - 16 0,5 - 2,5 3)
flexible with multicore cable end mm² 1,5 - 6 1,5 - 6 1,5 - 6 1,5 - 6 2,5 - 16 2,5 - 16 0,5 - 1,5
Clamps per pole 1 1 1 1 1 1 2
Magnetic coil solid or stranded mm² 0,75 - 2,5 0,75 - 2,5 0,75 - 2,5 0,75 - 2,5 0,75 - 2,5 0,75 - 2,5 -
flexible mm² 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 -
flexible with multicore cable end mm² 0,5 - 1,5 0,5 - 2,5 0,5 - 1,5 0,5 - 1,5 0,5 - 1,5 0,5 - 1,5 -
Clamps per pole 1 1 1 1 1 1 -
Auxiliary Contacts 5) 6) 7)
Rated insulation voltage Ui 1) V AC - - 440 2) 440 2) 440 2) 440 2) 440 2)
Thermal rated current Ith 40°C A - - 25 25 40 40 10
Ambient temperature 60°C A - - 25 25 40 40 6
Fuses A 40 40 40 80 80 -
Suitable for use on a capability of delivering not more than rms A 5000 5000 5000 5000 5000 -
V 300 300 300 300 300 300
2) Suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 4kV.
3) Maximum cable cross-section with prepared conductor 4) AC7b motor 2-pole 230V 1,1kW
5) Rated frequency 50/60Hz 6) Max. occ. switching overvoltage <4kV 7) Duty cycle: 100%
D677E 131
Modular Contactors
Dimensions
R20-.., R25-.. (2-pole) R25-TN R25-.. (4-pole) (+RH11)
RC-R 230, RH25-20 R25-..VM (+RH11-1)
132 D677E
European Representations and Suppliers
Great Britain +44 Romania +40
IMO Precision Controls Ltd. Tel: 020 / 8452 6444 Megatech Trading & Consulting SRL Tel: 21 / 317 05 68
1000 North Circular Road Fax: 020 / 8450 2274 Str. Buzesti 61, Bl.A6, Sc. 1, Et.6 Fax: 21 / 317 05 68
GB - NW2 7JP London [email protected] RO - Bukarest 1 [email protected]
www.imopc.com www.megatech.ro
Greece +30
Russia +7
Geyer Hellas s.a. Tel: 22210 / 987 11
Electrical And Electronic Material Fax: 22210 / 987 12 Torgoviy Dom ChEAZ Tel: 095 / 99 53 100
PO Box 19038 [email protected] ChEAZ Trading House LLC Fax: 095 / 99 53 200
GR - 34100 Drosia-Chalkis www.geyer.gr 16/1ul. Dokukina, [email protected]
Moskau www.cheaz.ru
RU-129226 Russia
Hungaria +36
Dial-Comp GmbH Tel: 01 / 236 0427 DIAL Electrolux Ltd. Tel: 495 / 48 73 350
Keszkeno u. 46/b. Fax: 01 / 236 0430 Bld. 1, Block2, Fl. 7 Fax: 495 / 48 73 654 add. 131
H - 1131 Budapest [email protected] Deguninskaia St., Moscow [email protected]
www.dialcomp.hu RU-127486 Russia www.dialelectrolux.ru
Netherlands +31
Slovenia +386
Hirsch-Driebergen B.V
B.V.. Tel: 0343 / 515 534
Postbus 143 Fax: 0343 / 520 314 TDR T rading
Trading Tel: 02 / 22 94 650
NL - 3970 AC Driebergen [email protected] Cesta k Tamu 8 Fax: 02 / 46 14 450
www.hirsch-driebergen.nl 2000 Maribor [email protected]
www.tdr-trading.si
D677E 133
Oversea Representations and Suppliers
Australia +61 Singapore and Malaysia +65
IMO Pacific Pty Ltd Tel: 08 / 4059 0464 8 Mecomb Singapore Ltd. Tel: 646 98 833
PO Box 1015 Fax: #04-02 Sime Darby Centre Fax: 646 71 905
Joondalup DC, [email protected] 896 Dunearn Road [email protected]
WA 6919 SGP - 589472 Singapore
134 D677E
Alphabetical Index
Description Type Page Description Type Page
D677E 135
Notice
136 D677E