Contactor Startor Motor

Benedict GmbH motor starters and contactors are approved for use globally based on meeting various international and national specifications without requiring individual testing. They are CE marked, meeting European directives on low voltage, electromagnetic compatibility, and RoHS/WEEE. Benedict GmbH also maintains a quality control system certified to ISO 9001 standards to ensure product quality. The devices can be used worldwide but sometimes require limitations or special markings for specific country or regional approvals.

Uploaded by

AmiEn AbYss
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
516 views137 pages

Contactor Startor Motor

Benedict GmbH motor starters and contactors are approved for use globally based on meeting various international and national specifications without requiring individual testing. They are CE marked, meeting European directives on low voltage, electromagnetic compatibility, and RoHS/WEEE. Benedict GmbH also maintains a quality control system certified to ISO 9001 standards to ensure product quality. The devices can be used worldwide but sometimes require limitations or special markings for specific country or regional approvals.

Uploaded by

AmiEn AbYss
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 137

Contactors

Motor-Starters

D677E141
Index Page
General 2
Approvals 3
Technical Information 5
Mounting Information 6
Micro Contactors 7
Micro Contactors 8
Micro Contactor Relays 9
Micro Reversing Contactors 11
Technical Information 12
Dimensions 16
Mini Contactors 17
Mini Contactors 18
Interface Contactors 18
Micro Reversing Contactors 24
Technical Information 25
Dimensions 30
Contactor Relays 31
Contactor Relays 32
Technical Information 34
Dimensions 36
Contactors 37
Contactors Overview 38
Contactors, 3-pole 40
Contactors, 4-pole 42
Capacitor Switching Contactors 43
Accessories 44
Technical Information 54
Dimensions 74
Starters 83
Star-Delta Starters 84
Reversing Contactors 88
Pole Changing Starters 90
Technical Information 92
Dimensions 99
D.O.L. Starters 103
D.O.L. Starters 104
Enclosures 105
Accessories 105
Technical Information 106
Dimensions 108
Overload Relays 111
Thermal Overload Relays 112
Accessories 113
Technical Information 116
Dimensions 121
Modular Contactors 125
Contactors 126
Accessories 127
Technical Information 128
Dimensions 132
Representatives and Suppliers 132
Alphabetical Index 135

Detailed Table of Contents may be found at beginning of each section


Technical data, dimension sketches, illustration and weights given in our list and printed matter, are subject to change without notice.

D677E 2014 1
General
Test Authorities, Registration Mark, Approvals CE-Marking
Low voltage switchgear from Benedict GmbH is built and tested The manufacturer has to sign his products with the CE-Marking. With the
to national and international specifications. All devices suit all CE-Marking the manufacturer confirms the accordance with the different
important specifications without any test obligation, like VDE, BS EEC Directives. The CE-Marking is absolutely necessary to sell the
and also relative to IEC Recommendations and to European Standards products in the EEC.
like IEC 947 and EN 60947. Below you find the EEC Directives concerning our products.
It is for this reason of our Low voltage switchgear is used all over the Low Voltage Directive 2006/95/EC
world. In order to provide special versions, limitations to the max. EMC Directive 2004/108/EC
voltages, currents and power ratings or special markings are RoHS + WEEE 2002/95/EC + "002/96/EC
sometimes necessary.

Quality Control System


Since November 1991 Benedict GmbH has been certified according to
the quality control system ÖNORM EN ISO 2900129001. The target of the ISO-
certification is, to grant the customer the quality of the performance of
his supplier, who is audited in accordance with this standard.

Country North America Russia China

State deputy or private examination UL GOST CCC


(state admitted) Canada, USA

Label marking Listed


of examination boards
Component

Duty of approvals all switchgear all switchgear all switchgear

Explanations for choice and supply of low voltage switchgear in Canada and USA
Marking of auxiliary contacts
At several devices in UL-data are two voltages for auxiliary contacts Low voltage switchgear for auxiliary circuits (e. g. contactor relays, control
mentioned (e. g.: 600 volts at same potential, 150 volts at different units, auxiliary contacts in general) usually approved for "Heavy Duty" or
potentials). That means, if the voltage is higher than 150 volts, the control "Standard Duty" UL and besides these marked with the admissible max.
voltage applied to input terminals must be at the same potential. voltage or with short codes (see table).

Marking of Max. rated values per pole Contact Discernment at UL-Standards


auxiliary contacts Voltage Current Cont. Rating
according to Make Break Current Code
CSA and UL V A A A Designation Recognized Component Listed
Industrial Control Equipment Industrial Control Equipment
Heavy Duty AC 120 60 6 10 A150
(HD or HVY DTY) AC 240 30 3 10 A300 UL issues yellow "Guide cards" UL issues white "Guide cards"
AC 480 15 1,5 10 A600 with Guide- and File-No. with Guide- and File-No.
AC 600 12 1,2 10 A600
Devices have permission to be Devices have to be marked
DC 125 2,2 2,2 10 N150 marked with with the
DC 250 1,1 1,1 10 N300 on the label "UL-Listing Mark"
DC 600 0,4 0,4 10 N600
Standard Duty AC 120 30 3 5 B150 Devices as components approved for Devices approved for "field wiring",
(SD or STD DTY) AC 240 15 1,5 5 B300 "factory wiring":
AC 480 7,5 0,75 5 B600 devices for employment in control
AC 600 6 0,6 5 B600 panels, when they are selected, a) devices for employment
mounted and wired according to in control panels, when
DC 125 1,1 1,1 5 P150 the charging conditions by skilled they are mounted and
DC 250 0,55 0,55 5 P300 worker. wired by skilled worker.
DC 600 0,2 0,2 5 P600 b) devices for retail in USA
- AC 120 15 1,5 2,5 C150
AC 240 7,5 0,75 2,5 C300
AC 480 3,75 0,375 2,5 C600 Valid UL-Standards: Valid UL-Standards:
AC 600 3 0,3 2,5 C600 UL 508 "Standard for Industrial UL 508 "Standard for Industrial Control
DC 125 0,55 0,55 2,5 Q150 Control Equipment" Equipment" (unlimited)
DC 250 0,27 0,27 2,5 Q300 (partly limited)
DC 600 0,1 0,1 2,5 Q600
- AC 120 3,6 0,6 1 D150 Are devices approved as "Listed Equipment" the approval is also valid
AC 240 1,8 0,3 1 D300
DC 125 0,22 0,22 1 R150 for using as "Recognized Component" .
DC 250 0,11 0,11 1 R300
- AC 120 1,8 0,3 0,5 E150

2 D677E
Approvals
Country North America Switzerland Europe Russia China CENELEC
GOST CB-Certificates
UL SEV

Type

Micro Contactor Relays, Micro Contactors, Micro Reversing Contactors and Accessories

K0-04D.. - - - o - - -
K0-05D.. o - - o - - -
K0W05D.. o - - o - - -

Mini Contactor Relays, Mini Contactors, Mini Reversing Contactors K1 and Accessories

K1-07D..(=) o - - o o - o
K1-07L..(=) - o - o o - o
K1-07F..(=) - o - o - - -

K1-09D..(=) o - - o o o o
K1-09L..(=) - o - o o o o
K1-09F..(=) - o - o - o -

K1-12D..(=) o - - o - o -

K1W09D01(=) o - - o - o -
K1W12D01(=) o - - o - o -
K1W09L01(=) - o - o - o -

HK.., HKM.. o - - o - - o
RC-K1 o - - o - - -

Contactor Relays, Contactors Series K3

K3-07ND..(=) o - - o - - -
K3-10N..(=) o - o o o o o
K3-14N..(=) o - o o o o o
K3-18N..(=) o - o o o o o
K3-22N..(=) o - o o o o o

K3-24A..(=) o - o o o o o
K3-32A..(=) o - o o o o o
K3-40A..(=) o - o o o o o

K3-50A..(=) o - o o o o o
K3-62A..(=) o - o o o o o
K3-74A..(=) o - o o o o o

K3-90A..(=) o - - o - o -
K3-115A..(=) o - - o - o -

K3-151A..(=) o - - o - - -
K3-176A..(=) o - - o - - -

K3-210A..(=) x - - o - - -
K3-260A..(=) x - - o - - -
K3-316A..(=) x - - o - - -

K3-450A..(=) o - - o - - -
K3-550A..(=) o - - o - - -

K3-700A..(=) o - - o - - -
K3-860A..(=) o - - o - - -
K3-1000A..(=) - - - o - - -
K3-1200A..(=) o - - o - - -

Contactor Relays, Contactors DC-operated Series KG3

KG3-07.. o - - o - - o
KG3-10.., -14.. o - - o - - o
KG3-18.., -22.. o - - o - - o
KG3-24.., -32.. o - - o - - o
KG3-40.. o - - o - - o

Capacitor Contactors Series K3

K3-18K.. o - - o o o o
K3-24K.. o - - o o o o
K3-32K.. o - - o o o o

K3-50K.. o - - o o o o
K3-62K.. o - - o o o o
K3-74K.. o - - o o o o
K3-90K.. o - - o - o -
K3-115K.. o - - o - o -

Aux. contacts

HN.., HTN.. o - - o o o o
HA.. o - - o o - o
HB.. o - - o o o o
K2-DK, K2-SK o - - o - - -

HKA.., HKT.. o - - o - - -
HKF22 - - - o - - -

o In standard version approved x In test - Not provided for test till now

D677E 3
Approvals

Country North America Switzerland Europe Russia China CENELEC


GOST CB-Certificates
UL SEV

Type

Accessories

K2-T..E, -A - - - o - - -
K2-TP o - - o - - -
K2-L o - - o - - -

K2-IN. o - - o - - -
K2-UN. o - - o - - -

K2-IM - - - o - - -
K2-E o - - o - - -
VG-K2 - - - o - - -

RC-K3 o - - o - - -

Reversing Contactors , Serie KW3

KW3-10 o - - o - - -
KW3-14 o - - o - - -
KW3-18 o - - o - - -
KW3-22 o - - o - - -

KW3-24 o - - o - - -
KW3-32 o - - o - - -
KW3-40 o - - o - - -

D.O.L. Starters

P1.. o - - o - - -

Thermal Overload Relays

U3/32 o - - o o - o
U3/42 o - - o o - o
U3/74 o - - o o - o

U12/16E o - - o o - o
U12/16A - - - o o - o
U12/16EM - - - o o - o
U12/16EQ - - - o o - o

U32 o - - o o - o
U60 o - - o o - o
U85 o - - o o - o

U180 x - - o - - -
U320 x - - o - - -
U800 - - - o - - -

Modular Contactors

R20 o - o o o - o
R25 o - o o o - o
R40 o - o o o - o
R63 o - o o o - o

R40, R63 2-pole - - - o o - o


RH11 o - - o o - o

o In standard version approved x In test - Not provided for test till now

- and - Guide- and File-No.


These data are important for UL-inspecting engineers.
Devices Guide-No. File-No.

Kanada USA Kanada USA


Contactors NLDX7 NLDX NLDX8 NLDX2 E41502
Reversing Contactors NLDX7 NLDX - - E41502
Control Relays, Accessories NKCR7 NKCR NKCR8 NKCR2 E66273
Thermal Overload Relays NKCR7 NKCR - - E66273
Cam Switches NLRV7 NLRV - -
Circuit Breakers as Manual Motor Controller NLRV7 NLRV - - E129916
Circuit Breakers as Combination Motor Controller NKJH7 NKJH - - E197641
Bus Bar Assemblies NLRV7 NLRV - - E129916
Accessories NKCR7 NKCR - - E66273

4 D677E
Technical Information
Degree of protection acc. to IEC 60947-1
Protection ratings are prefixed by the internationally agreed letters IP 2 nd Short description Definition
followed by two digits. digit

1 st digit: Pertains to solid objects 1 Protected against Dripping water (vertically falling drops)
2 nd digit: Pertains to water. dripping water shall have no harmful effect.

2 Protected against Vertically dripping water shall have no


1 st Short description Definition dripping water harmful effect when the enclosure is tilted
digit when tilted at any angle up to 15° from its normal
up to 15° position.
1 Protected against Excludes solid objects exceeding 50 mm
solid objects in diameter and protects against contact 3 Protected against Water falling as a spray at an angle up
greater than 50 mm with live and moving parts by a large body spraying water to 60° from the vertical shall have no
surface such as a hand (but not against harmful effect.
deliberate access).
4 Protected against Water splashed against the enclosure
2L Protected against Excludes solid objects exceeding splashing water from any direction shall have no harmful
solid objects 12,5 mm in diameter and protects against effect.
greater than contact with live and moving parts by a
12,5 mm and standard test finger or similar objects 5 Protected against Water protected by a nozzle against the
against contact by not exceeding 80 mm in length. water jets enclosure from any direction shall have
standard test finger no harmful effect.

3 Protected against Excludes solid objects exceeding 2,5 mm 6 Protected against Water from heavy seas or water
solid objects in diameter or thickness. heavy seas projected in powerful jets shall not
greater than 2,5mm enter the enclosure in harmful
quanties.
4 Protected against Excludes solid objects exceeding 1 mm
solid objects in diameter or thickness. 7 Protected against Ingress of water in a harmful quantity
greater than 1 mm the effects of shall not be possible when the
immersion enclosure is immersed in water under
5 Dust protected Prevents ingress of dust in quantities standard conditions of pressure and
and locations that would interfere with time.
the intended operation of the equipment.
8 Protected against No ingress of water.
6 Dust tight Prevents ingress of dust. submersion

Terminal markings acc. to EN50011 Resistance to climatic conditions acc. to IEC60068


Auxiliary contacts of AC contactors and contacts of contactor relays and Open-type devices are climate-resistant in the constant climate according
thermal overload relays are particularly marked. The terminal markings of to IEC60068-2-3 (this is a climate with an ambient temperature of 40°C and
normally-open contacts are printed as positive figures, they of normally- an atmospheric humidity of 90 to 95%).
closed contacts as negative figures. Enclosed devices are climate-resistant in an alternating climate according
This gives a clear indication of the function of the contacts. to IEC 68-2-30 (this is a moist alternating climate with a 24-hour cycle
The figure below illustrates the determination of terminal markings for between climates with an ambient temperature of 25°C, and an atmospheric
contactors with auxiliary contact blocks. humidity of 95 to 100% and an ambient temperature of 40°C, and an
atmospheric humidity of 90 to 96% in the presence of condensation during
rises in temperature).
Data are valid up to an altitude of 2000m above sea level.
Sequence number
Short circuit protection
Back up fuses should be used to protect contactors and starters against
Function number short circuits. For starters the device with the smaller admissible fuse at
the main and at the control circuit (contactor or thermal overload) determines
the fuse size.
After a short circuit devices have to be checked for correct operation.
Disconnect power before proceeding with any work on the equipment!
The complete terminal marking according to EN
50011 and EN 50012 results from the sequence
numbers on the contactor relay or ac contactor
(2., 3.) and the function numbers on the auxiliary
contact blocks (e. g. .1, .2, or .3, .4).

D677E 5
Technical Information
Mounting positions of contactors
K0-.. / K1-.. K2-..A00-40, K(G)3-07 bis K3-115, R.. K3-151.. bis K3-1200..

Terminal screws
Devices Kind of connection
Screw with Screw with Screw Screw driver Tightening torque
Type washer clamp box w. nut Nm lb. inch

Micro Contactors, all conductors


K0-.. M2,5 - - - Pz1 0.6 - 0,8 5-7
Mini Contactors, all conductors
K1-.. M3,5
Contactor Relays, all conductors
K(G)3-07.. M3,5 - - - Pz2 0,8 - 1,4 7 - 12
Contactors
Main conductor
K(G)3-10.. bis K3-22.. M3,5 - - - Pz2 0,8 - 1,4 7 - 12
K(G)3-24.. bis K3-40.. - M5 - - Pz2 2,5 - 3 22 - 26
K3-50.. bis K3-74.. - M6 - - Pz3 3,5 - 4,5 31 - 40

K2-23, -30, -37A00-40 M4 - - - Pz2 1,2 - 1,8 11 - 16


K2-45, -60A00-40 - M6 - - Pz3 3,5 - 4,5 31 - 40

K3-90, K3-115 - - M8 - 4mm hex socket 4 - 6,5 35 - 57

K3-116.. bis K3-176.. - - - M8 17 150


K3-210.. bis K3-316.. - - - M10 35 315
K3-450.. bis K3-700.. - - - M12 60 540
K3-860.. - - - M14 75 675
K3-1000.., K3-1200.. - - - M12 60 540
Auxiliary conductor
K(G)3-10 bis K3-22 M3,5 - - - Pz2 0,8 - 1,4 7 - 12
Coil conductor
K(G)3-10 bis K3-1200 M3,5 - - - Pz2 0,8 - 1,4 7 - 12
Accessories
HK, HKM M3,5 - - - Pz2 0,8 - 1,4 7 - 12
HA, HN, K2-.., HB.. M3,5 - - - Pz2 0,8 - 1,4 7 - 12
Thermal Overload Relays
Main conductor
U12/16 M4 - - - Pz2 1,2 - 1,8 11 - 16

U3/32 M3,5 - - - Pz2 0,8 - 1,4 7 - 12


U3/42 M5 - - - Pz2 2,5 - 3 22 - 26
U3/74 - M6 - - Pz3 3,5 - 4,5 31 - 40
UAT21 - M4 - - Size 3, 4 1,2 - 1,8 11 - 16
UAT22 - M4 - - Size 3, 4 1,2 - 1,8 11 - 16
UAT23 - M5 - - Size 3, 4, 5 2,5 - 3 22 - 26
Auxiliary conductor
All devices M3,5 - - - Pz2 0,8 - 1,4 7 - 12
Contactors for Distribution Boards
Conductors
R20, R25 - M3,5 - - Pz1 0,8 - 1,4 7 - 12
R40, R63 - M5 - - Pz2 2,5 - 3 22 - 26
K1R M3,5 - - - Pz2 0,8 - 1,4 7 - 12
Coil conductor
R20, R25 - M3 - - Pz1 0,6 - 1,2 5 - 11
R40, R63 - M3 - - Pz2 0,6 - 1,2 5 - 11
K1R M3,5 - - - Pz2 0,8 - 1,4 7 - 12

6 D677E
Micro Contactors

Micro Contactor Relays 8

Micro Contactors 9

Micro Contactors With Solder Pins 10

Coil voltages 10

Micro Reversing Contactor 11

Technical Data 12

Dimensions 16

D677E 7
Micro Contactor Relays 4-pole AC Operated

Ratings Therm. Contacts 2) Type Coil voltage 1)


Distinc. Additional 24 24V 50/60Hz
Number Contact 230 220-230V 50Hz

AC15 Rated-
Current
230V 400V Ith acc. to Blocks ⏐ Pack Weight
A A A NO NC EN50011 Type W pcs. kg/pc.

4-pole, With Screw Terminals


xxx3) xxx3) xxx3) 4 - 40E - K0-04D40 . . . 10 0,064

xxx3) xxx3) xxx3) 3 1 31E - K0-04D31 . . . 10 0,064

xxx3) xxx3) xxx3) 2 2 22E - K0-04D22 . . . 10 0,064

K0-04D40 K0-04D31 K0-04D22

1) Other coil voltages on request.


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA). Positively guided contacts.
3) Data on request.

8 D677E
Micro Contactors AC Operated

Power Ratings Rated Aux. Contacts2) Type Coil voltage 1)


Current Built-in Additional 24 24V 50/60Hz
230 220-230V 50Hz

AC2, AC3 AC1


380V
400V 660V
415V 690V 440V ⏐ Pack Weight
kW kW A NO NC Type W pcs. kg/pc.

3-pole, With Screw Terminals


2,2 - 12 1 - - K0-05D10 . . . 10 0,064

2,2 - 12 - 1 - K0-05D01 . . . 10 0,064

4-pole, With Screw Terminals


2,2 - 12 - - - K0-05D00-40 . . . 10 0,064

K0-05D10 K0-05D01 K0-05D00-40

1) Other coil voltages see page 12.


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA). Positively guided contacts.

D677E 9
Micro Contactors AC Operated

Power Ratings Rated Aux. Contacts2) Type Coil voltage 1)


Current Built Additional 24 24V 50/60Hz
in 230 220-230V 50Hz

AC2, AC3 AC1


380V
400V 660V
415V 690V 690V ⏐ Pack Weight
kW kW A NO NC Type W pcs. kg/pc.

3-pole, with Solder Pins Ø1,15 for Printed Circuit Applications


2,2 - xxx3) 1 - - K0-05L10 . . . 10 0,064

2,2 - xxx3) - 1 - K0-05L01 . . . 10 0,064

4-pole, with Solder Pins Ø1,15 for Printed Circuit Applications


2,2 - xxx3) - - - K0-05L00-40 . . . 10 0,064

K0-05L10 K0-05L01 K0-05L00-40

Coil voltages for AC operated contactors


Suffix Voltage Marking Rated Control Voltage Us Suffix Voltage Marking Rated Control Voltage Us
to to
contactor at the coil range contactor at the coil range
type for for for 50Hz for 60Hz type for for for 50Hz for 60Hz
e.g. 50Hz 60Hz min. max. min. max. e.g. 50Hz 60Hz min. max. min. max.
K1-09D10 24 V V V V V V K1-09D10 230 V V V V V V

12 12 12 11 12 12 12 200 200 200-220 195 205 200 220


24 24 24 22 24 24 24 210 205-215 220-230 205 215 220 230
42 42 42 38,5 42 42 42 220 210-220 220-240 210 220 220 240
48 48 48 48 50 48 52 230 220-230 230-250 220 230 230 250

90 100 100 90 100 100 105 240 230-240 230 240 250 260
95 95-100 105-110 95 100 105 110
100 100 110-115 100 105 110 115 Standard voltages in bold type letters
Operating range of magnet-coils: 0,85 x Us (min. value of rated
105 105-110 115-120 105 110 115 120 control voltage) up to 1,1 x Us (max. value of rated control voltage)
110 110-115 120-125 110 115 120 125
180 200 200 185 200 200 210 Coil not exchangeable

1) Other coil voltages see page 12.


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA). Positively guided contacts.
3) Data on request.

10 D677E
Micro Reversing Contactors, Mechanical Interlocked AC Operated

Power Ratings Rated Aux. Contacts2) Type Coil voltage 1)


Current Built-in Additional 24 24V 50/60Hz
on left on right 230 220-230V 50Hz
hand side hand side
AC2, AC3 AC1 Contactor Contactor
380V
400V 660V
415V 690V 690V K1 K2 ⏐ Pack Weight
kW kW A NO NC Type Type W pcs. kg/pc.

3-pole, with Screw Terminals


2,2 - 12 - 1 - - K0W05D01MC . . . 1 0,13

2,2 - 12 1 - - - K0W05D10MC . . . 1 0,13

4-pole, with Screw Terminals


2,2 - 12 - - - - K0W05D00-40MC . . . 1 0,13

3-pole, with Solder Pins Ø1,15 for Printed Circuit Applications


2,2 - xxx3) - 1 - - K0W05L01MC . . . 1 0,13

2,2 - xxx3) 1 - - - K0W05L10MC . . . 1 0,13

K0W05D01MC K0W05D10MC K0W05D00-40MC

1) Other coil voltages see page 12.


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA). Positively guided contacts.
3) Data on request.

D677E 11
Micro Contactors
Data according to IEC 60947-4-1, VDE 0660, EN 60947-4-1
Main Contacts Type K0-05D..

Rated insulation voltage Ui V AC 440 1)

Making capacity Ieff at Ue = 440V AC A 65

Breaking capacity Ieff 400V AC A 50


cosϕ = 0,65
Utilization category AC1
Switching of resistive load
Rated operational current Ie (=Ith) at 40°C, open A 12

Rated operational power of three-phase resistive loads 230V kW 4,7


50-60Hz, cosj = 1 240V kW 4,8
400V kW 8,3
415V kW 8,6

Rated operational current Ie (=Ith) at 60°C, enclosed A 8

Rated operational power of three-phase resistive loads 230V kW 3,1


50-60Hz, cosj = 1 240V kW 3,3
400V kW 5,5
415V kW 5,7

Minimum cross-section of conductor at load with Ie (=Ith) mm² 1,5

Utilization category AC2 and AC3


Switching of three-phase motors
Rated operational current Ie 220V A 6,2
open and enclosed 230V A 6,2
240V A 5,6

380-400V A 5
415-440V A 5

Rated operational power of three-phase motors 220-240V kW 1,5


50-60Hz 380-440V kW 2,2

Utilization category AC4


Switching of squirrel cage motors, inching
Rated operational current Ie 220V A 4,9
open and enclosed 230V A 4,9
240V A 4,1

380-400V A 5
415-440V A 5

Rated operational power of three-phase motors 220-240V kW 1,1


50-60Hz 380-440V kW 2,2

1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 4kV.
Data for other conditions on request.

12 D677E
Micro Contactors
Data according to IEC 60947-4-1, VDE 0660, EN 60947-4-1
Main Contacts Type K0-05D..

Utilization category DC1


Switching of resistive load 1 pole 24V A 12
Time constant L/R ≤1ms 60V A 12
Rated operational current Ie 110V A -
220V A -

3 poles in series 24V A 12


60V A 12
110V A 12
220V A -

Utilization category DC3 and DC5


Switching of shunt motors 1 pole 24V A 12
and series motors 60V A -
Time constant L/R ≤15ms 110V A -
Rated operational current Ie 220V A -

3 Pole in Serie 24V A 12


60V A 12
110V A 12
220V A -

Maximum ambient temperature


Operation open °C -40 to +60 (+90) 1)
enclosed °C -40 to +40
with therminal overload relay open °C -25 to +60
enclosed °C -25 to +40

Storage °C -50 to +90

Short circuit protection


for contactors without thermal overload relay

Coordination-type "1" according to IEC 947-4-1


Contact welding without hazard of persons
max. fuse size gL (gG) A 20
Coordination-type “2” according to IEC 947-4-1
Light contact welding accepted
max. fuse size gL (gG) A -
Contact welding not accepted
max. fuse size gL (gG) A -
For contactors with thermal overload relay the
device with the smaller admissible backup fuse
(contactor or thermal overload relay) determines the fuse size.

Cable cross-sections
for contactors without thermal overload relay
main connector solid or stranded mm² 0,5 - 1,5
flexible mm² 0,5 - 1,5
flexible with multicore cable end mm² 0,5 - xxx2)
Cables per clamp 2
solid or stranded AWG 18 - 14

Frequency of operation z without load 1/h 10000


contactors without therminal oberload relay AC3, Ie 1/h 600
AC4, Ie 1/h 120
DC3, Ie 1/h 600

Mechanical life AC operated Sx 106 xxx2)


DC operated Sx 106 xxx2)

Short time current 10s-current A 50

Power loss per pole at Ie /AC3 400V W xxx 2)

Resistance to shock according to IEC 68-2-27


Shock time 20ms sine-wave
AC operated NO g 2,5
NC g 2,5

1) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3.
2) Data on request.

D677E 13
Micro Contactors
Data according to IEC 60947-5-1, VDE 0660, EN 60947-5-1
Auxiliary Contacts Type K0-04D..
K0-05D..

Rated insulation voltage Ui VAC 440 1)


Thermal rated current Ith bis 440V
Ambient temperature 40°C A 10
60°C A 6

Verlustleistung pro Pol bei Ith W 0,5

Utilization category AC15


Rated operational currrent Ie 220-240V A xxx5)
380-415V A xxx5)
440V A xxx5)

Utilization category DC13


Rated operational current Ie 60V A xxx5)
-
-

Maximum ambient temperature


Operation open °C -40 bis +60 (+90) 2)
enclosed °C -40 bis +40
Storage °C -40 bis +90

Short circuit protection


short-circuit current 1kA,
contact welding not accepted
max. fuse size gL (gG) A xxx5)

For contactors with thermal overload relay the


device with the smaller admissible control fuse
(contactor or thermal overload relay)
determines the fuse size.

Power consumption of coils


AC operated inrush VA 17
sealed VA 2,5
W xxx5)

Operation rage of coils


in multiples of control voltage Us 0,85 - 1,1

Switching time at control voltage Us ±10% 3) 4)

AC operated make time ms xxx5)


release time ms xxx5)
arc duration ms xxx5)

DC operated make time ms -


release time ms -
arc duration ms -

Cablecross-section
all connectors solid mm2 0,5 - 2,5
flexible mm2 0,5 - 2,5
flexible with multicore cable end mm2 0,5 - xxx5)

Clamps per pole 2


solid or stranded AWG 18 - 14

1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 4kV.
Data for other conditions on request.
2) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced thermal rated current Ith to Ie /AC15.
3) Summary switching time = release time + arc duration.
4) Release time of NC make time of NO increase when suppressor units for voltage peak protection are used (Varistor, RC-units, Diode units).
5) Data on request.

14 D677E
Micro Contactors for North America
Data according to UL508
Main Contacts (cULus) Type K0-05D.. K0-04D..
K0W05D01..

Rated operational current "General Use" A 12 5

Rated operational power of three motors 110-120V hp ½ -


at 60Hz (3ph) 200-208V hp 1 -
220-240V hp 1 -
277V hp 1½
440-480V hp - -
550-600V hp - -

Rated operational power of AC motors 110-120V hp ½6 -


at 60Hz (1ph) 200-208V hp ½ -
220-240V hp ¾

Fuse / Short-circuit current A/kA 30/5 -

Rated voltage VAC 300 300

Auxiliary Contacts (cULus) heavy pilot duty AC B300 B300


standard pilot duty DC R300 R300

D677E 15
Micro Contactors
Dimensions
AC operated
with screw terminals

K0-04D..
K0-05D..

AC operated
with solder connections

K0-04L..
K0-05L..

Reversing Contactors
with screw terminals

K0W05D..MC

Reversing Contactors
with solder connections
K0W05L..MC

16 D677E
Mini Contactors

Mini Contactor Relays 4-pole 18


Auxiliary Contact Blocks

Interface Contactor Relays

Mini Contactors 20
Auxiliary Contact Blocks

Mini Contactors With Fast On Tab Connectors 22

Mini Contactors With Solder Pins 22

Coil voltages 22

Mini Reversing Contactors 24


Auxiliary Contact Blocks

Technical Data 26

Dimensions 30

D677E 17
Mini Contactor Relays 4-pole AC Operated

Ratings Therm. Contacts 2) Type Coil voltage 1)


Distinc. Additional 24 24V 50/60Hz
Number Contact 230 220-230V 50Hz
24VS 24V 50/60Hz w. protection 3)
230VS 220-230V 50Hz w. protection 3)
AC15 Rated 24VM 24V 50/60Hz 24V= DC
Current 230VM 220-240V 50/60Hz 220V= DC
230V 400V Ith acc. to Blocks ⏐ Pack Weight
A A A NO NC EN50011 Type W pcs. kg/pc.

4-pole, With Screw Terminals


3 2 10 4 - 40E 1 HK.. K1-07D40 . . . 10 0,16

3 2 10 3 1 31E 1 HK.. K1-07D31 . . . 10 0,16

3 2 10 2 2 22E 1 HK.. K1-07D22 . . . 10 0,16

Auxiliary Contact Blocks For Contactor Relays


Ratings Thermal Contacts 2) Type
AC15 Rated
230V 400V Current Pack Weight
A A A NO NC pcs. kg/pc.

3 2 10 1 1 HK11 10 0,04
3 2 10 - 2 HK02 10 0,04
3 2 10 2 - HK20 10 0,04

3 2 10 4 - HK40 10 0,04
3 2 10 2 2 HK22 10 0,04
3 2 10 - 4 HK04 10 0,04

Aux. Contact Blocks HK11 HK02 HK20 HK40 HK22 HK04

Wiring Diagrams

Distinc. Number according to EN50011


for Contactor Relay with Auxiliary Contact Block

K1-07D40 51E 42E 60E 80E 62E 44E


K1-07D31 42Y 33Y 51Y 71Y 53Y 35Y
K1-07D22 33Y 24Y 42Y 62Y 44Y 26Y

Preferable combinations with distinctive letter "E" according to DIN EN 50011

1) Other coil voltages see page 12


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA) Positively guided contacts
3) with built-in coil suppressor (varistor)

18 D677E
DC Solenoid Operated

Type Coil voltage 1) Contacts 2) Additional


24 24V= DC Distinc. Contact
24VS 24V= DC with Number Blocks
⏐ protection 2) acc. to Pack Weight
W NO NC EN50011 Type pcs. kg/pc. Wiring Diagrams

4-pole, With Screw Terminals, Coil 2,5W


K1-07D40= ... 4 - 40E 1 HK.. 10 0,19

K1-07D31= ... 3 1 31E 1 HK.. 10 0,19

K1-07D22= ... 2 2 22E 1 HK.. 10 0,19

4-pole, With Screw Terminals, Coil 1,5W, 19 to 30V DC with suppressor 3)

K1-07D40= 24VR 4 - - 10 0,20

K1-07D31= 24VR 3 1 - 10 0,20

K1-07D22= 24VR 2 2 - 10 0,20

1) Other coil voltages on request


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA) Positively guided contacts
3) with integrated coil suppressor (Transient Voltage Suppressor Diode)

D677E 19
Mini Contactors AC Operated

Power Ratings Rated Aux. Contacts2) Type Coil voltage 1)


Current Built-in Additional 24 24V 50/60Hz
230 220-230V 50Hz
24VS 24V 50/60Hz w. protection 3)
AC2, AC3 AC1 230VS 220-230V 50Hz w. protection 3)
380V 24VM 24V 50/60Hz 24V= DC
400V 660V 230VM 220-240V 50/60Hz 220V= DC
415V 690V 690V ⏐ Pack Weight
kW kW A NO NC Type W pcs. kg/pc.

3-pole, With Screw Terminals


4 4 20 1 - 1 HKM.. K1-09D10 . . . 10 0,16
5,5 5,5 20 1 - 1 HKM.. K1-12D10 . . . 10 0,16

4 4 20 - 1 1HK.. K1-09D01 . . . 10 0,16


5,5 5,5 20 - 1 1HK.. K1-12D01 . . . 10 0,16

4-pole, With Screw Terminals


4 4 20 - - 1HK.. K1-09D00-40 . . . 10 0,16
5,5 5,5 20 - - 1HK.. K1-12D00-40 . . . 10 0,16

Auxiliary Contact Blocks for Contactors K1-..


Ratings Thermal Contacts 2) Type
AC15 Rated
230V 400V Current Pack Weight
A A A NO NC pcs. kg/pc.

3 2 10 1 1 HKM11 10 0,04
3 2 10 - 2 HKM02 10 0,04
3 2 10 2 2 HKM22 10 0,04

Aux. Contact Blocks HKM11 HKM02 HKM22 HK11 HK02 HK40 HK22

Wiring Diagrams

Contactors with Auxiliary Contact Block


Contacts according to EN50012
K1-..D10 21 12 32 - - - -

Contacts according to DIN EN50005


K1-..D01 - - - 12 03 41 23
K1-..D00-40 - - - 11 02 40 22

Prefer combinations according to EN50012

Suppressor Units for Contactors K1-..


Voltage Range Type Pack Weight
V pcs. kg/pc.

12 - 48V AC/DC 1600nF / 22 Ohm RC-K1 24 10 0,01


48 - 127V AC/DC 680nF / 270 Ohm RC-K1 110 10 0,01
110 - 250V AC/DC 220nF / 2200 Ohm RC-K1 230 10 0,01

1) Other coil voltages see page 12


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA) Positively guided contacts
3) with built-in coil suppressor (varistor)

20 D677E
DC Solenoid Operated

Type
Coil voltage 1) Aux. Contacts 2) Additional
24 24V= DC Built Additional Overload
24VS 24V= DC with in Relay
⏐ protection 3) see
⏐ page102 Pack Weight
W NO NC Type pcs. kg/pc. Wiring Diagrams

3-pole, With Screw Terminals, Coil 2,5W


K1-09D10= . . . 1 - 1 HKM.. U12/16..K1 10 0,19
K1-12D10= . . . 1 - 1 HKM.. U12/16..K1 10 0,19

K1-09D01= . . . - 1 1 HK.. U12/16..K1 10 0,19


K1-12D01= . . . - 1 1 HK.. U12/16..K1 10 0,19

4-pole, With Screw Terminals, Coil 2,5W


K1-09D00-40= . . . - - - U12/16..K1 10 0,19
K1-12D00-40= . . . - - - U12/16..K1 10 0,19

3-pole, With Screw Terminals, Coil 1,5W, 19 to 30V DC with suppressor 3)

K1-09D10=24VR 1 - - U12/16..K1 10 0,20

K1-09D01= 24VR - - 1 - U12/16..K1 10 0,20

1) Other coil voltages on request


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA) Positively guided contacts
3) with integrated coil suppressor (Transient Voltage Suppressor Diode)

D677E 21
Mini Contactors AC Operated

Power Ratings Rated Aux. Contacts2) Type Coil voltage 1)


Current Built Additional 24 24V 50/60Hz
in 230 220-230V 50Hz
24VS 24V 50/60Hz w. protection 2)
AC2, AC3 AC1 230VS 220-230V 50Hz w. protection 2)
380V 24VM 24V 50/60Hz 24V DC
400V 660V 230VM 220-240V 50/60Hz 220V DC
415V 690V 690V ⏐ Pack Weight
kW kW A NO NC Type W pcs. kg/pc.

3-pole, with Fast On Tab Connectors 1 x 6,3mm or 2 x 2,8mm


4 4 16 1 - 1 HKM.. K1-09F10 . . . 10 0,16

4 4 16 - 1 1 HK.. K1-09F01 . . . 10 0,16

3-pole, with Solder Pins Ø1,15 for Printed Circuit Applications


4 4 16 1 - - K1-09L10 . . . 10 0,16

4 4 16 - 1 - K1-09L01 . . . 10 0,16

4-pole, with Solder Pins Ø1,15 for Printed Circuit Applications


4 4 16 - - - K1-09L00-40 . . . 10 0,16

Coil voltages for AC operated contactors


Suffix Voltage Marking Rated Control Voltage Us Suffix Voltage Marking Rated Control Voltage Us
to to
contactor at the coil range contactor at the coil range
type for for for 50Hz for 60Hz type for for for 50Hz for 60Hz
e.g. 50Hz 60Hz min. max. min. max. e.g. 50Hz 60Hz min. max. min. max.
K1-09D10 24 V V V V V V K1-09D10 230 V V V V V V

12 12 12 11 12 12 12 200 200 200-220 195 205 200 220


24 24 24 22 24 24 24 210 205-215 220-230 205 215 220 230
42 42 42 38,5 42 42 42 220 210-220 220-240 210 220 220 240
48 48 48 48 50 48 52 230 220-230 230-250 220 230 230 250

90 100 100 90 100 100 105 240 230-240 230 240 250 260
95 95-100 105-110 95 100 105 110 400 380-400 400-440 380 400 400 440
100 100 110-115 100 105 110 115 500 475-500 520-545 475 500 520 545
550 525-550 600 525 550 570 600
105 105-110 115-120 105 110 115 120
110 110-115 120-125 110 115 120 125 Standard voltages in bold type letters
180 200 200 185 200 200 210 Operating range of magnet-coils: 0,85 x Us (min. value of rated
control voltage) up to 1,1 x Us (max. value of rated control voltage)

Coil not exchangeable

1) Other coil voltages see page 12


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA) Positively guided contacts
3) with built-in coil suppressor (varistor)

22 D677E
DC Solenoid Operated

Type
Coil voltage 1) Aux. Contacts 2) Additional
24 24V= DC Built Additional Overload
2 4 V S 24V= DC with in Relay see
⏐ protection 3) pages
⏐ 103, 105 Pack Weight
W NO NC Type pcs. kg/pc. Wiring Diagrams

3-pole, with Fast On Tab Connectors 1 x 6,3mm or 2 x 2,8mm


K1-09F10= . . . 1 - 1 HKM.. 4) 10 0,19

K1-09F01= . . . - 1 1 HK.. 4) 10 0,19

3-pole, with Solder Pins Ø1,15 for Printed Circuit Applications


K1-09L10= . . . 1 - - - 10 0,19

K1-09L01= . . . - 1 - - 10 0,19

4-pole, with Solder Pins Ø1,15 for Printed Circuit Applications


K1-09L00-40= . . . - - - - 10 0,19

1) Other coil voltages on request


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA) Positively guided contacts
3) with integrated coil suppressor (Transient Voltage Suppressor Diode)
4) U12/16E K3 with U12SMK3 for single mounting

D677E 23
Mini Reversing Contactors, Mechanical Interlocked AC Operated

Power Ratings Rated Aux. Contacts2) Type Coil voltage 1)


Current Built-in Additional 24 24V 50/60Hz
on left on right 230 220-230V 50Hz
hand side hand side 24VS 24V 50/60Hz w. protection 3)
AC2, AC3 AC1 Contactor Contactor 230VS 220-230V 50Hz w. prot. 3)
380V 24VM 24V 50/60Hz 24V DC
400V 660V 230VM 220-240V 50/60Hz 220V DC
415V 690V 690V K1 K2 ⏐ Pack Weight
kW kW A NO NC Type Type W pcs. kg/pc.

3-pole, with Screw Terminals


4 4 20 - 1 HKM11V HKM11X K1W09D01MC . . . 1 0,32
5,5 5,5 20 - 1 HKM11V HKM11X K1W12D01MC . . . 1 0,32

4 4 20 1 - - HKM.. K1W09D10MC . . . 1 0,32


5,5 5,5 20 1 - - HKM.. K1W12D10MC . . . 1 0,32

4-pole, with Screw Terminals


4 4 20 - - - HKM.. K1W09D00-40MC . . 1 0,32
5,5 5,5 20 - - - HKM.. K1W12D00-40MC . . 1 0,32

3-pole, with Solder Pins Ø1,15 for Printed Circuit Applications


4 4 16 - 1 - - K1W09L01MC . . . 1 0,32

4 4 16 1 - - - K1W09L10MC . . . 1 0,32

Auxiliary Contact Blocks for Mini Reversing Contactors K1-..


Ratings Thermal Contacts 2) Type
AC15 Rated
230V 400V Current Pack Weight
A A A NO NC pcs. kg/pc.

3 2 10 1 1 HKM11V 10 0,04
3 2 10 1 1 HKM11X 10 0,04

Aux. Contact BlocksAux. Contact Blocks HKM11V HKM11X

Wiring Diagrams

Reversing Starter Connector

For Reversing Starter Types, incl. Coil Connector Type Pack Weight
pcs. kg/pc.

K1W09D..MC, K1W12D..MC K1W-VB 1 0,01

1) Other coil voltages see page 12


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA) Positively guided contacts
3) with built-in coil suppressor (varistor)

24 D677E
DC Solenoid Operated

Type
Coil voltage 1) Additional
24 24V= DC Overload
24VS 24V= DC with Relay
⏐ protection 2) see
⏐ page102 Pack Weight
W Type pcs. kg/pc. Wiring Diagrams

3-pole, with Screw Terminals


K1W09D01MC= . . . U12/16..K1 1 0,32
K1W12D01MC= . . . U12/16..K1 1 0,32

K1W09D10MC= . . . U12/16..K1 1 0,32


K1W12D10MC= . . . U12/16..K1 1 0,32

4-pole, with Screw Terminals


K1W09D00-40MC= . . U12/16..K1 1 0,32
K1W12D00-40MC= . . U12/16..K1 1 0,32

3-pole, with Solder Pins Ø1,15 for Printed Circuits Applications


K1W09L01MC= . . . - 1 0,32

K1W09L10MC= . . . - 1 0,32

1) Other coil voltages on request


2) with integrated coil suppressor (Transient Voltage Suppressor Diode)

D677E 25
Mini Contactors
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Main Contacts Type K1-09D.. K1-09F.. K1-09L.. K1-12D..

Rated insulation voltage Ui V AC 690 1)


690 1)
690 2)
690 1)

Making capacity Ieff at Ue = 690V AC A 165 165 165 165

Breaking capacity Ieff 400V AC A 100 100 100 100


cosϕ = 0,65 500V AC A 90 90 90 90
690V AC A 80 80 80 80

Utilization category AC1


Switching of resistive load
Rated operational current Ie (=Ith) at 40°C, open A 20 16 16 20

Rated operational power of three-phase resistive loads 230V kW 7,9 6 6 7,9


50-60Hz, cosϕ = 1 240V kW 8,3 6,5 6,5 8,3
400V kW 13,8 11 11 13,8
415V kW 14,3 11,5 11,5 14,3

Rated operational current Ie (=Ithe) at 60°C, enclosed A 16 12 12 16

Rated operational power of three-phase resistive loads 230V kW 6,3 4,5 4,5 6,3
50-60Hz, cosϕ = 1 240V kW 6,7 5 5 6,7
400V kW 11 8 8 11
415V kW 11,5 8,5 8,5 11,5

Minimum cross-section of conductor at load with Ie (=Ith) mm² 2,5 2,5 - 2,5

Utilization category AC2 and AC3


Switching of three-phase motors
Rated operational current Ie 220V A 12 12 12 15
open and enclosed 230V A 11,5 11,5 11,5 14,5
240V A 11 11 11 14

380-400V A 9 9 9 12
415-440V A 8 8 8 11
500V A 7 7 7 9
660-690V A 5 5 5 6,5

Rated operational power of three-phase motors 220-240V kW 3 3 3 4


50-60Hz 380-440V kW 4 4 4 5,5
500-690V kW 4 4 4 5,5

Utilization category AC4


Switching of squirrel cage motors, inching
Rated operational current Ie 220V A 12 12 12 15
open and enclosed 230V A 11,5 11,5 11,5 14,5
240V A 11 11 11 14

380-400V A 9 9 9 12
415-440V A 8 8 8 11
500V A 7 7 7 9
660-690V A 5 5 5 6,5

Rated operational power of three-phase motors 220-240V kW 3 3 3 4


50-60Hz 380-440V kW 4 4 4 5,5
500-690V kW 4 4 4 5,5

1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
2) Suitable at 690V for pollution degree 2, Uimp = 6kV.
Pollution degree 3 Ui = 690V non-tracking of the printed circuit CTI ≥600
Pollution degree 3 Ui = 500V non-tracking of the printed circuit CTI ≥400
Pollution degree 3 Ui = 400V non-tracking of the printed circuit CTI ≥100

26 D677E
Mini Contactors
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Main Contacts Type K1-09D.. K1-09F.. K1-09L.. K1-12D..

Utilization category DC1


Switching of resistive load 1 pole 24V A 20 16 16 20
Time constant L/R ≤1ms 60V A 20 16 16 20
Rated operational current Ie 110V A 5 5 5 5
220V A 0,6 0,6 0,6 0,6

3 poles in series 24V A 20 20 20 20


60V A 20 20 20 20
110V A 20 20 20 20
220V A 16 16 16 16

Utilization category DC3 and DC5


Switching of shunt motors 1 pole 24V A 20 16 16 20
and series motors 60V A 5 5 5 5
Time constant L/R ≤15ms 110V A 1 1 1 1
Rated operational current Ie 220V A 0,15 0,15 0,15 0,15

3 poles in series 24V A 20 16 16 20


60V A 20 16 16 20
110V A 20 16 16 20
220V A 2 2 2 2

Maximum ambient temperature


Operation open °C -40 to +60 (+90) 1)
enclosed °C -40 to +40
with thermal overload relay open °C -25 to +60
enclosed °C -25 to +40

Storage °C -50 to +90

Short circuit protection


for contactors without thermal overload relay

Coordination-type "1" according to IEC 947-4-1


Contact welding without hazard of persons
max. fuse size gL (gG) A 40 40 40 40
Coordination-type “2” according to IEC 947-4-1
Light contact welding accepted
max. fuse size gL (gG) A 25 25 25 25
Contact welding not accepted
max. fuse size gL (gG) A 10 10 10 10
For contactors with thermal overload relay the
device with the smaller admissible backup fuse
(contactor or thermal overload relay) determines the fuse size.

Cable cross-sections
for contactors without thermal overload relay
main connector solid or stranded mm² 0,5 - 2,5 Fast on Solder connector 0,5 - 2,5
flexible mm² 0,5 - 2,5 1x 6,3 x 0,8 Ø 1,15 0,5 - 2,5
flexible with multicore cable end mm² 0,5 - 1,5 or 0,5 - 1,5
Cables per clamp 2 2x 2,8 x 0,8 - 2
solid or stranded AWG 18 - 14 18 - 14

Frequency of operations z without load 1/h 10000 10000 10000 10000


Contactors without thermal overload relay AC3, Ie 1/h 600 600 600 700
AC4, Ie 1/h 120 120 120 150
DC3, Ie 1/h 600 600 600 700

Mechanical life AC operated Sx 106 5 5 5 5


DC operated Sx 106 15 15 15 15

Short time current 10s-current A 96 96 96 120

Power loss per pole at Ie/AC3 400V W 0,15 0,15 0,15 0,25

Resistance to shock according to IEC 68-2-27


Shock time 20ms sine-wave
AC operated NO g 5 5 5 5
NC g 5 5 5 5

DC operated NO g 8 8 8 8
NC g 6 6 6 6

1) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3

D677E 27
Mini Contactors
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Auxiliary Contacts Type K1-07D.. K1-07D..=
K1-09D.. K1-09D..= K1-07D..= 24VR K1-07L..(=)
K1-12D.. K1-12D..= K1-09D..= 24VR K1-09F..(=) K1-09L..(=) HK..

Rated insulation voltage Ui V AC 690 1)


690 1)
690 1)
690 1) 690 2) 690 1)

Thermal rated current Ith to 690V


Ambient temperature 40°C A 10 10 10 10 10 10
60°C A 6 6 6 6 6 6

Power loss per pole at Ith W 0,5 0,5 0,5 0,5 0,5 0,5

Utilization category AC15


Rated operational current Ie 220-240V A 3 3 3 3 3 3
380-415V A 2 2 2 2 2 2
440V A 1,6 1,6 1,6 1,6 1,6 1,6

500V A 1,2 1,2 1,2 1,2 1,2 1,2


660-690V A 0,6 0,6 0,6 0,6 0,6 0,6

Utilization category DC13


Rated operational current Ie 60V A 2 2 2 2 2 2
110V A 0,4 0,4 0,4 0,4 0,4 0,4
220V A 0,1 0,1 0,1 0,1 0,1 0,1

Maximum ambient temperature


Operation open °C -40 to +60 (+90) 3)
enclosed °C -40 to +40
Storage °C -40 to +90

Short circuit protection


short-circuit current 1kA,
contact welding not accepted
max. fuse size gL (gG) A 20 20 20 20 20 20
For contactors with thermal overload relay the
device with the smaller admissible control fuse
(contactor or thermal overload relay)
determines the fuse size.

Power consumption of coils


AC operated inrush VA 25 - - 25 25 -
sealed VA 4-5 - - 4-5 4-5 -
W 1,2 - - 1,2 1,2 -

DC operated inrush W - 2,5 1,5 2,5 2,5 -


sealed W - 2,5 1,5 2,5 2,5 -

Operation range of coils 19 - 30V DC


in multiples of control voltage Us 0,85 - 1,1 0,8 - 1,1 0,85 - 1,1 0,85 - 1,1 -

Switching time at control voltage Us ±10% 4) 5)

AC operated make time ms 15 - 19 - - 15 - 19 15 - 19 -


release time ms 8 - 25 - - 8 - 25 8 - 25 -
arc duration ms 10 -15 - - 10 -15 10 -15 -

DC operated make time ms - 15 - 25 15 - 25 15 - 25 15 - 25 -


release time ms - 8 - 25 8 - 25 8 - 25 8 - 25 -
arc duration ms - 10 -15 10 -15 10 -15 10 -15 -

Cable cross-section
all connectors solid mm2 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 Fast on Solder connector 0,5 - 2,5
flexible mm2 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 1x 6,3 x 0,8 Ø 1,15 0,5 - 2,5
flexible with multicore cable end mm2 0,5 - 1,5 0,5 - 1,5 0,5 - 1,5 or 0,5 - 1,5
2x 2,8 x 0,8
Clamps per pole 2 2 2 - - 2

solid or stranded AWG 18 - 14 18 - 14 18 - 14 18 - 14

1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
2) Suitable at 690V for pollution degree 2, Uimp = 6kV.
Pollution degree 3 Ui = 690V non-tracking of the printed circuit CTI ≥600
Pollution degree 3 Ui = 500V non-tracking of the printed circuit CTI ≥400
Pollution degree 3 Ui = 400V non-tracking of the printed circuit CTI ≥100
3) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced thermal rated current Ith to Ie /AC15
4) Summary switching time = release time + arc duration
5) Release time of NC make time of NO increase when suppressor units for voltage peak protection are used (Varistor, RC-units, Diode units).

28 D677E
Mini Contactors for North America
Data according to UL508
Main Contacts (cULus) Type K1-09D.. K1-09F.. K1-09L.. K1-07D.. K1-12D.. HK..
K1W09D01 K1W12D01

Rated operational current "General Use" A 15 15 20 10 20 10

Rated operational power of three-phase motors 110-120V hp 1½ 1½ 1½ - 2 -


at 60Hz (3ph) 200-208V hp 3 3 3 - 3 -
220-240V hp 3 3 3 - 3 -

440-480V hp 5 5 5 - 7½ -
550-600V hp 7½ 7½ 7½ - 10 -

Rated operational power of of AC motors 110-120V hp ½ ½ ½ - ¾ -


at 60Hz (1ph) 200-208V hp 1 1 1 - 1½ -
220-240V hp 1½ 1½ 1½ - 2 -

Fuse / Short-circuit current A/kA 30/5 30/5 30/5 - 30/5 -

Rated voltage V AC 600 600 600 1) 600 600 600

Auxiliary Contacts (cULus) heavy pilot duty AC A600 A600 A600 A600 A600 A600
standard pilot duty DC Q600 Q600 Q600 Q600 Q600 Q600

1) Pollution degree CTI - PWB Ui

2 ≥ 100 600V
3 ≥ 400 480V
3 100 - 400 240V

D677E 29
Mini Contactors
Dimensions
AC and DC operated
with screw terminals with fast on terminals

K1-07D.. K1-07F..
K1-09D.. K1-09F..
K1-12D..

AC and DC operated Auxiliary Contact Blocks


with solder connections
HK..
K1-07L..
K1-09L..

Suppressor Units

RC-K1

Reversing Contactors

K1W09D..MC
K1W12D..MC

K1W09D..MC + U12/16E K1
Reversing Contactors K1W09D..MC + U12/16E K1

K1W09L..MC

30 D677E
Contactor Relays

Contactor Relays 4-pole, AC Operated 32

Auxiliary Contact Blocks 1-pole 32

Contactor Relays 4-pole, DC Operated 33

Technical Data 34

Dimensions 36

D677E 31
Contactor Relays AC Operated

Ratings Contacts Type Coil voltage 1)


Therm. Built-in Distinc. Additional 24 24V 50/60Hz
Rated Number Contact 110 110V 50Hz 110-120V 60Hz
Current acc. to Blocks 230 220-240V 50Hz 230-264V 60Hz
AC15 400 380-415V 50Hz 400-440V 60Hz
230V 400V Ith ⏐ Pack Weight
A A A NO NC EN50011 Type W pcs. kg/pc.

4-pole, contacts suitable for electronic circuits according to EN947-5-42)


4 2 10 4 - 40E max. 4 K3-07ND40 . . . 1 0,22
4 2 10 3 1 31E HN.. K3-07ND31 . . . 1 0,22
4 2 10 2 2 22E K3-07ND22 . . . 1 0,22
4 2 10 - 4 04E K3-07ND04 . . . 1 0,22

Auxiliary Contact Blocks 3)

Ratings Thermal Contacts 2) Type


AC15 Rated
230V 400V Current Pack Weight
A A A NO NC EM LB pcs. kg/pc.

1-pole, contacts suitable for electronic circuits according to EN947-5-42)


3 2 10 1 - - - HN10 10 0,02
3 2 10 - 1 - - HN01 10 0,02
3 2 10 - - 1 - HN10U 10 0,02
3 2 10 - - - 1 HN01U 10 0,02

1-pole, for high switching capacity


6 3 25 1 - - - HA10 10 0,03
6 3 25 - 1 - - HA01 10 0,03

Accessories see page 34 - 38

1) Other coil voltages see page 40


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA) Positively guided contacts
3) Technical Data see page 62

32 D677E
DC Operated

Type Coil voltage 1) Contacts


24 24V DC Built-in Distinc. Additional
60 60V DC Number Contact
110 110V DC acc. to Blocks
220 220V DC
⏐ Pack Weight
W NO NC EN50011 Type pcs. kg/pc. Wiring Diagrams

3W Coil power, for high switching capacity 3)


KG3-07A40 . . . 4 - 40E max. 4 1 0,53 A40, D40
KG3-07A31 . . . 3 1 31E HN.. 1 0,53
KG3-07A22 . . . 2 2 22E oder 1 0,53
KG3-07A04 . . . - 4 04E HA.. 1 0,53

A31, D31

3W Coil power, for electronic circuits 2)3)

KG3-07D40 . . . 4 - 40E max. 4 1 0,53


KG3-07D31 . . . 3 1 31E HN.. 1 0,53 A22, D22
KG3-07D22 . . . 2 2 22E 1 0,53
KG3-07D04 . . . - 4 04E 1 0,53

A04, D04

with double winding coil, for electronic circuits 2)

K3-07ND40= . . . 4 - 40E max. 3 1 0,25 ND40=


K3-07ND31= . . . 3 1 31E HN.. 1 0,25
K3-07ND22= . . . 2 2 22E 1 0,25
K3-07ND04= . . . -4 04E 1 0,25

ND31=

ND22=

ND04=

1) Other coil voltages on request


2) Contacts suitable for electronic circuits, according to EN947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA) Positively guided contacts
3) with integrated coil suppressor (Transient Voltage Suppressor Diode)

D677E 33
Contactor Relays
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
Type K3-07ND K3-07ND= KG3-07A KG3-07D

Rated insulation voltage Ui 1)


V AC 690 690 690 690

Thermal rated current Ithto 690V


Ambient temperature 40°C A 10 10 20 10
60°C A 6 6 16 6

Frequency of operations z 1/h 10000 10000 10000 10000


Mechanical life S x 106 10 10 10 50

Utilization category AC15


Rated operational 220-240V A 4 4 12 4
current Ie 380-415V A 2 2 4 2
440V A 1,6 1,6 4 1,6

500V A 1,2 1,2 3 1,2


660-690V A 0,6 0,6 1 0,6

Utilization category DC13


Rated operational 24-60V A 3,5 3,5 8 3,5
current Ie 110V A 0,5 0,5 1 0,5
per pole 220V A 0,1 0,1 0,1 0,1

Power consumption of coils


AC operated inrush VA 30 - 45 - - -
sealed VA 7 - 10 - - -
W 2,6 - 3 - - -
DC operated inrush W - 75 3 3
sealed W - 2 3 3

Operation range of coils


in multiples of control voltage Us 0,85 - 1,1 0,8 - 1,1 0,8 - 1,1 0,8 - 1,1

Switching time at control voltage Us±10%


make time ms 8 - 16 8 - 16 65 - 85 65 - 85
release time ms 5 - 13 5 - 13 20 - 30 3) 20 - 30 3)

Maximum ambient temperature


Operation open °C -40 to +60 (+90) 2)
enclosed °C -40 to +40
Storage °C -40 to +90

Short circuit protection


short-circuit current 1kA,
contact welding not accepted
max. fuse size gL (gG) A 20 20 25 20

Cable cross-section
Connector solid mm2 0,75 - 6
flexible mm2 1-4
flexible with multicore cable end mm2 0,75 - 4
Magnet coil solid mm2 0,75 - 2,5
flexible mm2 0,75 - 2,5
flexible with multicore cable end mm2 0,5 - 1,5

Clamps per pole 2

Connector solid AWG 18 - 10


flexible AWG 18 - 10
Clamps per pole 2

Magnet coil solid AWG 14 - 12


flexible AWG 18 - 12
Clamps per pole 2

Data according to UL508


Rated operational current A 10 10 20 10
"General Use"
Rated operational voltage max. V AC 600 600 600 600
Auxiliary Contacts heavy pilot duty A600 A600 A600 A600

1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.
2) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced thermal rated current Ith according to Ie /AC15 3) with built-in coil suppressor

34 D677E
Contactor Relays
Position of Terminals
AC operated DC operated with double wound coil

K3-07ND22 K3-07ND31 K3-07ND40 K3-07ND04 K3-07ND22= K3-07ND31= K3-07ND40= K3-07ND04=

DC solenoid operated

KG3-07A22 KG3-07A31 KG3-07A40 KG3-07A04


KG3-07D22 KG3-07D31 KG3-07D40 KG3-07D04

D677E 35
Contactor Relays
Dimensions
AC operated DC solenoid operated

K3-07ND.. KG3-07..

DC operated with double winding coil

K3-07ND.. =

Auxiliary contact blocks

HN10, HN01 HA10, HA01

36 D677E
Contactors

Contactor overview 38

Contactors 3-pole, AC Operated 40

Contactors 3-pole, DC Operated 41

Contactors 4-pole 42

Capacitor Switching Contactors 43

Auxiliary Contact Blocks 44


Snap-on Momentary Contacts
Additional Fourth Poles for Contactors

Pneumatic Timers 45
Electronic Timers On-delay
Electronic Timers Off-delay

Mechanical Interlocks 46
Latches
Additional Terminals, Parallel Connectors

Indicator Units 47
Fuse Holders
Suppressor Units

Interface 48
Terminal Covers
Mounting Parts, Marking System

Control Voltages 50

Spare Coils AC-operated 50


Feeder Groups

Spare Coils DC-operated 51


Spare Contacts

Technical Data 54

Dimensions 74

D677E 37
Contactors 3-pole
Up to 1200A AC3
Up to 1350A AC1
DIN-rail mounting up to AC3 115A
International Approvals
Data according to IEC 947 / EN 60947

Ratings
AC3 400V Motor 10A 14A 18A 22A 24A 32A 40A 50A 62A 74A 90A 115A

380-400V 4kW 5,5kW 7,5kW 11kW 11kW 15kW 18,5kW 22kW 30kW 37kW 45kW 55kW
660-690V 5,5kW 7,5kW 10kW 10kW 15kW 18,5kW 18,5kW 30kW 37kW 45kW 55kW 55kW

AC1 690V at 40°C 25A 25A 32A 32A 50A 65A 80A 110A 120A 130A 160A 200A

Type K3- 10ND10 14ND10 18ND10 22ND10 24A00 32A00 40A00 50A00 62A00 74A00 90A00 115A00

Auxiliary contacts 1NO 1NO 1NO 1NO - - - - - -

Type K3- 10ND01 14ND01 18ND01 22ND01

Auxiliary contacts 1NC 1NC 1NC 1NC

Cable cross-section
Solid mm2 0,75 - 6 1,5 - 25 4 - 50 10 - 120
Flexible mm2 1-4 2,5 - 16 10 - 35 10 - 95

Auxiliary contact
Ith 40°C A 10 - - -
AC15 230V A 3 - - -
400V A 2 - - -

Power consumption Inrush VA 33 - 45 90 - 115 140 - 165 280


of coils hold VA 7 - 10 9 - 13 13 - 18 5
Operation range of coils 0,85 - 1,1 0,85 - 1,1 0,85 - 1,1 0,85 - 1,1

Mounting 35mm DIN-rail or base 2x DIN-rail


or base

Additional aux. contact blocks


Front mounting Type HN10 HN01 HA10 HA01 max. max.
contacts 1NO 1NC 1NO 1NC 4 HN.. 7 HN..
f. low level f. low level 25A Ith 25A Ith or or
switching switching 4 HA.. 7 HA..

Additional aux. contact blocks


Side mounting Type - - - - HB11 HB02 max.
contacts 1NO+1NC 2NC 2 HB..
f. low level f. low level
switching switching

Overload Relay (thermal)


Single phase protection
Temperature compensation
Trip and alarm contacts

Type U3/32 U3/74 U85

U12/16..K3 U3/42

Number of Setting Ranges 16 16 4 5 2


from 0,12 - 30A 0,12 - 32A 10 - 42A 20 - 74A 60 - 120A

Busbar sets - - - - -

38 D677E
150A 175A 210A 260A 315A 450A 550A 700A 860A 1000A 1200A

75kW 90kW 110kW 132kW 160kW 250kW 300kW 400kW 500kW 580kW 680kW
90kW 110kW 160kW 210kW 250kW 375kW 475kW 630kW 700kW 850kW 1000kW

230A 250A 350A 450A 500A 600A 760A 1000A 1100A 1200A 1350A

151A00 176A00 210A00 260A00 316A00 450A22 550A22 700A22 860A22 1000A12 1200A12

- - - - - 2NO+2NC 2NO+2NC 2NO+2NC 2NO+2NC 1NO+2NC 1NO+2NC

2 x 16-120 busbar busbar busbar busbar busbar busbar busbar busbar busbar
2 x 16-120 30x6 30x6 30x6 30x5 40x6 50x8 50x8 50x10 50x10

- - 10 10
- - 3 3
- - 2 2

350 350 360 360 360 800-950 800-950 1350-1600 1350-1600 2400 2400
5 5 5 5 5 9-11 9-11 21-25 21-25 70 70
0,85 - 1,1 0,85 - 1,1 0,85 - 1,1 0,85-1,1

base

HKT11 HKT22 HKF22 HKB11


1NO+1NC 2NO+2NC 2NO+2NC 1NO+1NC
max. 1 pc. max. 1 pc. max. 2 pcs.

HKA11 - - - - - -
1NO+1NC
max. 2 pcs.

U180 U320 U800

1 2 3
120 - 180A 144 - 320A 240 - 800A

integrated integrated SU840/550 SU840/860

D677E 39
Contactors 3-pole AC Operated

Ratings Rated Aux. Contacts Type Coil voltage 1)


AC2, AC3 Current Built-in Additional 24 24V 50/60Hz
380V see 110 110V 50/60Hz
400V 660V AC1 page 34 230 220-240V 50Hz
415V 690V 690V 400 380-415V 50Hz Pack Weight
kW kW A NO NC Typ W pcs. kg/pc.

4 5,5 25 1 - max. 4 K3-10ND10 . . . 1 0,23


4 5,5 25 - 1 HN.. or K3-10ND01 . . . 1 0,23
HA..
5,5 7,5 25 1 - K3-14ND10 . . . 1 0,23
5,5 7,5 25 - 1 K3-14ND01 . . . 1 0,23

7,5 10 32 1 - K3-18ND10 . . . 1 0,23


7,5 10 32 - 1 K3-18ND01 . . . 1 0,23

11 10 32 1 - K3-22ND10 . . . 1 0,23
11 10 32 - 1 K3-22ND01 . . . 1 0,23

11 15 50 - - max. 4 K3-24A00 . . . 1 0,48


15 18,5 65 - - HN.. or K3-32A00 . . . 1 0,48
18,5 18,5 80 - - HA.. K3-40A00 . . . 1 0,48
and 2HB..

22 30 110 - - max. 4 (3)4) K3-50A00 . . . 1 0,85


30 37 120 - - HN.. or K3-62A00 . . . 1 0,85
37 45 130 - - HA.. K3-74A00 . . . 1 0,85
and 2HB..

45 55 160 - - max. 7 K3-90A00 . . . 2) / VS 3) 1 2,2


55 55 200 - - HN.. or K3-115A00 . . . 2) / VS 3) 1 2,2
HA..
and 2HB..

75 110 230 - - 1 HKT.. K3-151A00 . . . 2) 1 4


90 132 250 - - and K3-176A00 . . . 2) 1 4
2 HKA11

110 160 350 - - K3-210A00 . . . 2) 1 7,2


132 210 450 - - K3-260A00 . . . 2) 1 7,2
160 250 500 - - K3-316A00 . . . 2) 1 7,2

250 375 600 2 2 1 HKF22 K3-450A22 . . . 2) 1 13


300 475 760 2 2 K3-550A22 . . . 2) 1 13,5

400 630 1000 2 2 K3-700A22 . . . 2) 1 26,5


500 700 1100 2 2 K3-860A22 . . . 2) 1 27,6

580 850 1200 1 2 2 HKB11 K3-1000A12 . . . 1 49


680 1000 1350 1 2 K3-1200A12 . . . 1 53

1) Coil voltage range and other coil voltages see page 39


2) Type 230 for AC- and DC-operating 220-240V 50/60Hz and 220V DC ( with integrated coil suppressor )
3) Type 230VS for AC-operating 220-240V 50Hz ( with integrated coil suppressor )
4) max. 3 HN.. or HA.. for DC-operated Contactors

40 D677E
DC Operated

Type Coil Additional Wiring Diagram


Coil voltage 1) power Overload
24 24V DC Relay Coil Circuits
48 48V DC inrush/ see see page 41
110 110V DC hold page 102 Pack Weight
W W/W Type pcs. kg/pc. Terminal Markings

KG3-10A10 . . . 5) 3/3 U3/32 1 0,53 D10


KG3-10A01 . . . 5) 3/3 U12/16E 1 0,53
U12/16EQ
KG3-14A10 . . . 5) 3/3 UAT21 1 0,53
KG3-14A01 . . . 5) 3/3 1 0,53

KG3-18A10 . . . 5) 3/3 1 0,53 D01


KG3-18A01 . . . 5) 3/3 1 0,53

KG3-22A10 . . . 5) 3/3 1 0,53


KG3-22A01 . . . 5) 3/3 1 0,53

KG3-24A00 . . . 5) 4/4 U3/32 1 0,57 A00


KG3-32A00 . . . 5) 4/4 U3/42 1 0,57
KG3-40A00 . . . 5) 4/4 UAT.. 1 0,57

A00=
K3-50A00= . . . 200/6 U3/74 1 0,9
K3-62A00= . . . 200/6 1 0,9
K3-74A00= . . . 200/6 1 0,9

K3-90A00 . . . 2) 280/5 U85 1 2,2 A00


K3-115A00 . . . 2) 280/5 1 2,3

K3-151A00 . . . 2) 350/5 U180 1 4


K3-176A00 . . . 2) 350/5 1 4

K3-210A00 . . . 2) 360/5 U320 1 7,2


K3-260A00 . . . 2) 360/5 1 7,2
K3-316A00 . . . 2) 360/5 1 7,2

K3-450A22 . . . 2) 800/10 U800 1 13 A22


K3-550A22 . . . 2) 800/10 +SU840/550 1 13,5

K3-700A22 . . . 2) 1500/20 U800 1 26,5


K3-860A22 . . . 2) 1500/20 +SU840/860 1 27,6

K3-1000A12= . . . 2100/60 1 49 A12


K3-1200A12= . . . 2100/60 1 53

1) Other coil voltages on request


2) Type 230 for AC- and DC-operating 220-240V 50/60Hz and 220V DC ( with integrated coil suppressor )
5) with integrated coil suppressor

D677E 41
Contactors 3-pole DC Operated

Ratings Rated Aux. Contacts Type Coil voltage 1)


AC2 Current Built-in Additional 24 24V= DC
AC3 see 60 60V= DC
380V AC1 page 34 110 110V= DC
400V 660V 220 220V= DC
415V 690V 690V ⏐ Pack Weight Wiring Diagram
kW kW A NO NC Type W pcs. kg/pc.

4 5,5 25 1 - max. 3 K3-10ND10= . . . 1 0,25 D10=


4 5,5 25 - 1 HN.. K3-10ND01= . . . 1 0,25
or
5,5 7,5 25 1 - HA.. K3-14ND10= . . . 1 0,25
5,5 7,5 25 - 1 K3-14ND01= . . . 1 0,25

7,5 10 32 1 - K3-18ND10= . . . 1 0,25 D01=


7,5 10 32 - 1 K3-18ND01= . . . 1 0,25

11 10 32 1 - K3-22ND10= . . . 1 0,25
11 10 32 - 1 K3-22ND01= . . . 1 0,25

11 15 50 - - max. 4 K3-24A00= . . . 1 0,55 ... A00=


15 18,5 65 - - HN.. or K3-32A00= . . . 1 0,55
18,5 18,5 80 - - HA.. K3-40A00= . . . 1 0,55
+ 2HB..

Contactors 4-pole AC Operated

Ratings Rated Aux. Contacts Type Coil voltage 2)


AC2 AC1 Current Built-in Additional 24 24V 50/60Hz
AC3 see 110 110V 50/60Hz
380V AC1 page 34 230 220-240V 50Hz
400V 400 380-415V 50Hz
415V 400V 690V ⏐ Pack Weight Wiring Diagram
kW kW A NO NC Type W pcs. kg/pc.

4 17,5 25 - - max. 4 K3-10NA00-40 . . . 1 0,22 A00-40


5,5 17,5 25 - - HN.. or K3-14NA00-40 . . . 1 0,22
HA..
7,5 22 32 - - K3-18NA00-40 . . . 1 0,22
11 22 32 - - K3-22NA00-40 . . . 1 0,22

11 31 45 - - max. 4 K2-23A00-40 . . . 1 0,65


15 34,5 50 - - HN.. K2-30A00-40 . . . 1 0,65
18,5 34,5 50 - - or K2-37A00-40 . . . 1 0,65
HA..

22 55 80 - - max. 6 K2-45A00-40 . . . 1 1,1


30 69 100 - - HN.. or K2-60A00-40 . . . 1 1,1
HA..

55 139 200 - - 1HKT.. K3-116A00-40 . . .3) 1 4,7


75 159 230 - - + K3-151A00-40 . . .3) 1 4,7
90 173 250 - - 2xHKA11 K3-176A00-40 . . .3) 1 4,7

110 242 350 - - K3-210A00-40 . . .3) 1 8


132 310 450 - - K3-260A00-40 . . .3) 1 8
160 346 500 - - K3-316A00-40 . . .3) 1 8

Latch for Contactors 4-pole see page 36

1) Other coil voltages on request


2) Coil voltage range and non-standard coil voltages see page 39
3) with integrated coil suppressor

42 D677E
Capacitor Switching Contactors
for use with reactive or non-reactive capacitor banks
Rated Operational Power at 50/60Hz Aux. Type
Ambient Temperature Contacts
50°C 60°C Built-in Add. Coil voltage 1)
380V 415V 660V 380V 415V 660V 230 220-240V 50Hz
400V 440V 690V 400V 440V 690V ⏐ Pack Weight
kVAr kVAr kVAr kVAr kVAr kVAr NO NC pcs. W pcs. kg/pc.

12,5 0-13
0-12,5 0-20 0-12,5 0-13 0-20 1 - 1 2) K3-18NK10 . . . 1 0,34
0-12,5
12,5 0-13 0-20 0-12,5 0-13 0-20 - 1 1 2) K3-18NK01 . . . 1 0,34

10-20
20 10,5-22 17-33 10-20 10,5-22 17-33 - - 3 3) K3-24K00 . . . 1 0,62
25
10-25 10,5-27 17-41 10-25 10,5-27 17-41 - - 3 3) K3-32K00 . . . 1 0,62

20-33,3
33,3 23-36 36-55 20-33,3 23-36 36-55 - - 3 3) K3-50K00 . . . 1 1,0
50 23-53 36-82
20-50 20-50 23-53 36-82 - - 3 3) K3-62K00 . . . 1 1,0
754) 23-754) 36-1204) 20-60 23-64
20-75 36-100 - - 3 3) K3-74K00 . . . 1 1,0

33-80
80 36-82 57-120 33-75 36-77 57-120 - - 6 5) K3-90K00 . . . / VS 7) 1 2,3
1006) 36-1036) 57-1486) 33-906) 36-936) 57-1486) -
33-100 - 6 5) K3-115K00 . . . / VS 7) 1 2,3

Specification: Contactors K3-..K are suitable for switching low-inductive and low loss capacitors in capacitor banks
(IEC70 and 831, VDE 0560) without and with reactors.
Capacitor switching contactors are fitted with early make contacts and damping resistors, to reduce the value of make
current <70 x Ie.
Operating Conditions: Capacitor switching contactors are protected against contact welding for a prospective making
current of 200 x Ie.

Technical Data acc. to IEC 947-4-1, IEC 947-5-1, EN 60947-4-1, EN 60947-5-1, VDE 0660
Type K3-18K K3-24K K3-32K K3-50K K3-62K K3-74K K3-90K K3-115K

Max. frequency of operations z 1/h 120 120 120 120 120 80 80 80


Contact life non reactive capacitor banks Sx 103 250 150 150 150 150 120 120 120
reactive capacitor banks S x 103 400 300 300 300 300 200 200 200
Rated operational current Ie at 50°C A 0-18 14-28 14-36 30-48 30-72 30-108 50-115 50-144
AC6b at 60°C A 0-18 14-28 14-36 30-48 30-72 30-87 50-108 50-130
Rated operational current Ith at 50°C A 32 45 60 100 110 120 155 190
AC1 at 60°C A 32 40 55 90 100 110 145 170
Overload factor at 50°C % 78 60 67 108 53 11 35 32
acc. to EN 61921: 30% min. at 60°C % 78 43 53 88 39 26 34 31

Fuses gL (gG) from / to A 35 / 63 50 / 80 63 / 100 80 / 160 125 / 160 160/200 160/200 160/250

Typical Wiring Diagram for


Circuit Diagram Quick Discharge Resistors
Make sure that the current of the discharge
resistors is not higher than the rated current
(AC1) of the auxiliary contacts

Mounting instructions:
In the area of capacitor switching contactors,
difficulty inflammable and self-extinguishing
materials shall be used only, because
abnormal temperatures within the area of the
resistor spirals cannot be excluded.

1) Coil voltage range and non-standard coil voltages see page 39


2) 1 HN.. or HA.. snap-on
3) 2HB.. for side mounting and 1 HN.. or HA.. snap-on
4) Consider the max. thermal current of the contactor K3-74A: Ith 130A
5) 2 HB.. on the left or right side and 4 HN.. or HA.. snap-on
6) Consider the min. cross-section of conductor at max. load
7) Type 230 for AC- and DC-operating 220-240V 50/60Hz and 220V DC ( with integrated coil suppressor )
Type 230VS for AC-operating 220-240V 50Hz ( with integrated coil suppressor )

D677E 43
Auxiliary Contact Blocks for contactors K(G)3-07.. to K3-115.., type HN.. for low level switching 1)
Rated Operational Current Contacts Type Pack Weight
AC15 AC15 AC1
230V 400V 690V
A A A NO NC EM LB pcs. kg/pc.

3 2 10 1 - - - HN10 10 0,02
3 2 10 - 1 - - HN01 10 0,02

3 2 10 - - 1 - HN10U 10 0,02
3 2 10 - - - 1 HN01U 10 0,02

6 3 25 1 - - - HA10 10 0,03
6 3 25 - 1 - - HA01 10 0,03

Auxiliary Contact Block for contactors K3-24.. to K3-115.., for low level switching 1)
Rated Operational Current Contacts Type Pack Weight
AC15 AC15 AC1 mounting:
230V 400V 690V 1 HB.. on left side
A A A and 1 HB.. on right side NO NC pcs. kg/pc.

3 2 10 1 1 HB11 10 0,02
3 2 10 - 2 HB02 10 0,02

Auxiliary Contact Blocks for contactors K3-116.. to K3-1200


Rated Operational Current Contacts Type Pack Weight
AC15 AC15 AC1
230V 400V 690V
A A A For contactors NO NC pcs. kg/pc.

3 2 10 K3-116 to K3-316 top 1 1 HKT11 1 0,04


3 2 10 K3-116 to K3-316 top 2 2 HKT22 1 0,05
3 2 10 K3-116 to K3-316 outside 1 1 HKA11 1 0,05

6 3 16 K3-200 to K3-860 2) 2 2) 2 HKF22 1 0,12


6 3 16 K3-1000, K3-1200 inside 1 1 HKB11 1 0,17

Snap-on Momentary Contacts for K(G)3-07.. to K3-115.. for low level switching1)
Rated Operational Current Contacts Type Pack Weight
AC15 AC15 AC1
230V 400V 690V
A A A Specification NO NC pcs. kg/pc.

3 2 10 manual operated 1 - HTN10 10 0,02


3 2 10 manual operated - 1 HTN01 10 0,02

Terminal Blocks for contactors K(G)3-07.. to K3-115.. and K2-..


Specification Thermal Current Ith Type Pack Weight
A pcs. kg/pc.

2 terminals interconnected 26 K2-DK 10 0,02


2 terminals insulated 26 K2-SK 10 0,02

1)Contacts suitable for electronic circuits, according to IEC60947-5-4 for rated voltage 24V DC
(test ratings 17V DC, 5mA) Positively guided contacts
Technical data see page 62
2) Contact travel of make contacts adjustable, see page 63

44 D677E
Elektronic Timer
for mounting on DIN-rail, Control voltage 24-240V AC/DC, 1 changeover contact
OFF-delay without auxiliary voltage
Replace Pneumatic Timer K2-TP..

5 Functions 4 Time ranges Rated Current T y p e Pack Weight


AC1 250V
s A pcs. kg/pc.

ON-delay 0,1 - 1 5 K3-T180 240 1 0,085


OFF-delay 1 - 10
Single shot trailing edge 6 - 60
Single shot leding edge 18 - 180
Single shot leading and
trailing edge

Electronic Timer On-delay for contactors K(G)3-07.. to K3-115.. and K2-..


Timer will be connected with the contactor coil, can be snapped onto the contactor and occupies 2 add-on spaces. Contactor switches On-
delay.

Operational Time Range Rated Current T y p e Pack Weight


Voltage AC15
V s A pcs. kg/pc.

24 - 60V AC/DC 1 - 30 0,75 K2-TE30 60 1 0,08


100 - 250V AC/DC 1 - 30 0,75 K2-TE30 250 1 0,08

24 - 60V AC/DC 10 - 180 0,75 K2-TE180 60 1 0,08


100 - 250V AC/DC 10 - 180 0,75 K2-TE180 250 1 0,08

24 - 60V AC/DC 30 - 600 0,75 K2-TE600 60 1 0,08


100 - 250V AC/DC 30 - 600 0,75 K2-TE600 250 1 0,08

Wiring Diagram Timing Chart Operation Range 0,8 - 1,1 x Us


Time repeat accuracy ≤1%
Control voltage
Recovery time (typical) 50ms

Voltage Drop after the time delay te <3V


LED (Control voltage 24V: use contactor with 20V-coil)
Max. inrush current (peak value) 25A <10ms
brown
Contactor
Duty Cycle 100%
Ambient temperature -40o - +60oC
Short circuit protection 2A

Electronic Timer Off-delay for contactors K(G)3-07.. to K3-74.. and K2-..


Timer will be connected with the contactor coil, can be snapped onto the contactor and occupies 2 add-on spaces. Contactor switches Off-delay.

Operational Time Range Rated Current T y p e Pack Weight


Voltage AC15
V s A pcs. kg/pc.

24 - 60V AC 1 - 30 0,75 K2-TA30 60 1 0,08


100 - 120V AC 1 - 30 0,3 K2-TA30 120 1 0,08
200 - 250V AC 1 - 30 0,15 K2-TA30 250 1 0,08

24 - 60V AC 10 - 180 0,75 K2-TA180 60 1 0,08


100 - 120V AC 10 - 180 0,3 K2-TA180 120 1 0,08
200 - 250V AC 10 - 180 0,15 K2-TA180 250 1 0,08

24 - 60V AC 30 - 600 0,75 K2-TA600 60 1 0,08


100 - 120V AC 30 - 600 0,3 K2-TA600 120 1 0,08
200 - 250V AC 30 - 600 0,15 K2-TA600 250 1 0,08
Wiring Diagram Timing Chart Operation Range 0,8 - 1,1 x Us
Time repeat accuracy ≤1%
Contact S Min. start time 15ms
Recovery time (typical) 15ms
Voltage Drop <0,7V
LED Max. inrush current (peak value) 25A <10ms
white brown Contactor
Duty Cycle 100%
Ambient temperature -40o - +40oC
Short circuit protection 2A
Utilization Category AC15 24 - 60V 100 - 120V 200 - 250V
0,75A 0,3A 0,15A

D677E 45
Interface for contactors K3-07.. to K3-74.. and K2-07.. to K2-60..

Input Power Rated Current Ie AC15 Type Pack Weight


Voltage Ue Consumption 250V AC 400V AC pcs. kg/pc.

24V DC 0,35W 0,75A 0,5A K2-IM 1 0,03


Amplifier element for contactor control
by programmable controller

Fuse Holders for contactors K(G)3-07.. to K3-115.. and K2-..


Specifications Rated Voltage Type Pack Weight
pcs. kg/pc.

Fuse holder for fuse 5x20mm (max. 6,3A) 250V AC K2-F 1 0,02
Fuses are not included.

Rectifier with Fuse Holder for contactors K(G)3-07.. to K3-115.. and K2-..
Specifications Rated Voltage Type Pack Weight
pcs. kg/pc.

with built-in rectifier 1A 250V AC K2-RF1 1 0,03


with built-in rectifier 3A 250V AC K2-RF3 1 0,03

Latch for contactors K(G)3-07.. to K3-74.. and K2-..


with NC aux. contact Type Coil voltage
24 22-26V 50/60Hz
power consumption max. 30VA 110 100-120V 50/60Hz
230 210 -250V 50/60Hz
400 360-440V 50/60Hz
⏐ Pack Weight
For Contactors W pcs. kg/pc.

K3-07 to K3-22, K2-07 to K2-16 K2-L22 . . . 1 0,08

K3-24 to K3-40, K2-23 to K2-37, KG3-10 to KG3-40 K2-L40 . . . 1 0,08

K3-50 to K3-74, K2-45 to K2-60 K2-L74 . . . 1 0,08

Technical data see page 62


Latch for Contactors K3-200 to K3-860 on request

Indicator Units for contactors K(G)3-07.. to K3-115.. and K2-..


Specifications Voltage Type Pack Weight
Range pcs. kg/pc.

Coil Current Indicator


Indicator, green (LED) 24 - 660V AC/DC K2-ING 10 0,02
Coil Current Indicator,
Indicator red (LED) 24 - 660V AC/DC K2-INR 10 0,02
To connect in series with the contactor coil. In case of coil
interruption the indication goes out. Voltage drop appr. 2 volts

Voltage Indicator
Indicator, clear (glow-disc. l.) 220 - 415V AC/DC K2-UN 10 0,02
Voltage Indicator
Indicator, red (LED) 24 - 120V AC/DC K2-UNR 10 0,02
To connect parallel to the contactor coil. In case of applied
voltage the indication also lights at coil interruption.

Snap-On Adapter
For Type Specification Type Pack Weight
pcs. kg/pc.

K2-DK, K2-SK, K2-TE, K2-TA for snap-on mounting of K2-SM 10 0,009


K2-IM, K2-F, K2-RF accessories on 35mm
K2-IN., K2-UN. DIN-rail acc. DIN EN 50022

46 D677E
Additional 4th Poles for contactors K3-315.. to K3-1200
For Ccontactors Thermal Current Ith Type Pack Weight
A pcs. kg/pc.

K3-315, K3-450, K3-550 325 NP325 1 0,7


K3-315, K3-450, K3-550 500 NP500 1 1,3
K3-450, K3-550 760 NP760 1 1,4

K3-700, K3-860 500 NP501 1 1,3


K3-700, K3-860 1000 NP1000 1 1,6
K3-1000, K3-1200 1000 NP1001 1 1,6

Mechanical Interlocks
Interlocks contactor with contactor Mounting Type Pack Weight
Type Type pcs. kg/pc.

K3-07 to K3-40 K3-07 to K3-40 horizontal LG10889 1) 10 0,006


KG3-07 to KG3-22 KG3-07 to KG3-22
KG3-24 to KG3-40 KG3-24 to KG3-40
K2-07 to K2-37 K2-07 to K2-37

K3-24 to K3-74 K3-50 to K3-74 horizontal LG10890 1) 1 0,010


K2-23 to K2-60 K2-45 to K2-60

K3-90, K3-115 K3-90, K3-115 horizontal LG11478 1) 1 0,010

K65 to K110 K65 to K110 horizontal LG8511 1 0,076

K3-116 to K3-316 K3-116 to K3-316 horizontal LG11223H 1 0,06

K3-315 to K3-550 K3-315 to K3-550 horizontal LG10400H 1 0,8


K3-315 to K3-550 K3-315 to K3-550 vertical LG10400V 1 0,8
K3-450, K3-550 K3-700, K3-860 horizontal LG10399H 1 1,6
K3-450, K3-550 K3-700, K3-860 vertical LG10399V 1 0,9

K3-700, K3-860 K3-700, K3-860 horizontal LG10402H 1 1,5


K3-700, K3-860 K3-700, K3-860 vertical LG10402V 1 0,9
K3-700, K3-860 K3-1000, K3-1200 horizontal LG10401H 1 1,9
K3-700, K3-860 K3-1000, K3-1200 vertical LG10401V 1 1,6

K3-1000, K3-1200 K3-1000, K3-1200 horizontal LG10403H 1 1,8


1) clamps for mounting incl. K3-1000, K3-1200 K3-1000, K3-1200 vertical LG10403V 1 1,5

Terminal Covers for terminal protection according to DIN 57106, VBG 4


For Contactors Specification Type Pack Weight
pcs. kg/pc.

K65 to K110 (spare part) for 6 terminals LG9333 1 0,045

K3-151, K3-176 3-pole for 3 terminals LG10404 1 0,12


K3-116 to K3-176 4-pole for 4 terminals LG104044 1 0,14
K3-210, K3-260, K3-316 for 3 terminals LG11457 1 0,14

K3-200 for 3 terminals LG10405 1 0,18


K3-315, K3-450 for 3 terminals LG10406 1 0,28

K3-550 for 3 terminals LG10407 1 0,34


K3-700 for 3 terminals LG10408 1 0,39
K3-860 for 3 terminals LG10409 1 0,49

Additional Terminals
For Contactors Cable Cross-sections to clamp mm² Type Pack Weight
solid or flex. with multi-
stranded flexible core cable end pcs. kg/pc.

Additional Terminal Single Pole, with fingertouch protection


K(G)3-10 to K(G)3-22 0,75 - 10 0,75 - 6 0,75 - 6 LG9339N 6 0,009
K2-09 to K2-16
K3-151 to K3-176 16 - 120 + 16 - 95 LG11224 1 0,10

Additional Terminal Single Pole, set with 3 pieces


K3-50 to K3-74, 4 - 35 6 - 25 4 - 25 LG9030 1 0,052
K2-45, K2-60
K3-50 to K3-74 10 - 70 16 - 50 10 - 35 LG9031 1 0,170
K2-45, K2-60

D677E 47
Parallel Connectors
For Contactors Cable Cross-sections to clamp mm² Type Pack Weight
solid or flex. with multi-
stranded flexible core cable end pcs. kg/pc.

Parallel Connectors, 3 Poles Parallel


Current-carrying capacity: 2,5 x AC1-value of the contactor
K(G)3-10 to K(G)3-22 terminal hole for screw M5 LG9241 50 0,004
K2-09 to K2-16
K2-23 to K2-37 4 - 35 6 - 25 4 - 25 LG5587 10 0,022

Parallel Connectors, 4 Poles Parallel


Current-carrying capacity: 3,2 x AC1-value of the contactor
K(G)3-10 to K(G)3-22 terminal hole for screw M5 LG7360 10 0,006
K2-09 to K2-16

Suppressor Units
Voltage Range Mounting Type Pack Weight
V pcs. kg/pc.

RC-units for contactors K3-07 - K3-74

12 - 48V AC/DC to snap 1600nF / 22 Ohm RC-K3N 24 10 0,01


48 - 127V AC/DC on the 680nF / 270 Ohm RC-K3N 110 10 0,01
110 - 230V AC/DC contactor 220nF / 2200 Ohm RC-K3N 230 10 0,01
230 - 415V AC/DC 120nF / 620 Ohm RC-K3N 400 10 0,01

RC-units for reversing contactors K3NWU10 - K3WU74 and contactors K3-07 - K3-74

12 - 48V AC/DC to snap 1600nF / 22 Ohm RC-K3NW 24 10 0,01


48 - 127V AC/DC on the 680nF / 270 Ohm RC-K3NW 110 10 0,01
110 - 230V AC/DC contactor 220nF / 2200 Ohm RC-K3NW 230 10 0,01
230 - 415V AC/DC 120nF / 620 Ohm RC-K3NW 400 10 0,01

Mounting Parts
Description For Type Specification Type Pack Weight
pcs. kg/pc.

Clamp, K3-07 to K3-115 To join contactors P426-1 50 0,001


no distance K2-07 to K2-37 without distance,
2 pieces required

Clamp, K3-07 to K3-115 To join contactors P418-1 10 0,002


7mm distance K2-07 to K2-37 with 7mm distance,
2 pieces required

Clamp, K3-07 to K3-115 To join contactors P807-1 10 0,002


12mm distance K2-07 to K2-37 with 12mm distance,
2 pieces required

Clamp K3-07 to K3-40 To join contactors P785-1 10 0,002


asymmetric with K3-50 - K3-74 with 12mm distance,
2 pieces required

Marking System for contactors K3-07.. to K3-115.., K2-.. and aux. contact blocks HN and HA

Description Specification Type Pack Weight


pcs. kg/100pc

Marking Plate 2-section without marking, divisible P487-1 100 0,025


Marking Plate 3-section without marking, divisible P971-1 100 0,038
Marking Plate 4-section without marking, divisible P245-1 100 0,050

Marking Plate marked, choice of K1...K32 P245-K.. 100 0,013

48 D677E
Coil voltages for AC operated contactors

Type-suffix for coil-types K6/.. to K45/... Type-suffix for coil-types K85/... and K110/...
for contactor-types K3-07.. to K3-74 for contactor-types K85 to K110

Suffix Voltage Marking Rated Control Voltage Us Suffix Voltage Marking Rated Control Voltage Us
to to to to
contactor coil at the coil range contactor coil at the coil range
type type for for for 50Hz for 60Hz type type for for for 50Hz for 60Hz
50Hz 60Hz min. max. min. max. 50Hz 60Hz min. max. min. max.
V V V V V V V V V V V V

6 41.6 6 6 6,6 6,6 7,3 20 4.20 20 24 20 22 24 26


6,6 41.6,6 6,6 6,6 7,3 7,3 8 24 4.24 24 24 27 29 32
7,3 41.7,3 7,3 7,3 8 8 9 42 4.42 42 42 47 50 56

8 41.8 8 8 9 9 10 110 4.110 110-120 110 122 132 146


9 41.9 9 9 10 10 11 230 4.230 220-240 277 220 240 264 288
10 41.10 10 10 11 11 12 400 4.400 380-415 460-480 380 415 455 498

11 41.11 11 12 11 12 12 13,2
12 41.12 12 12 13,2 13,2 14,5
13,2 41.13 13,2 13,2 14,5 14,5 16 Type-suffix for coil-types K3-1200/..
for contactor-types K3-1000.. to K3-1200..
14,5 41.14 14,5 14,5 16 16 18
16 41.16 16 16 18 18 20 110 4.110 110-115 - 110 115 110 115
18 41.18 18 18 20 20 22 230 4.230 220-230 - 220 230 220 230
400 4.400 380-400 - 380 400 380 400
20 41.20 20 20 22 22 24
24 4.24 24 24 22 24 24 27 440 4.440 440 - 440 440 440 440
25 41.25 25 24 27 27 30

27 41.27 27 32 27 30 30 33
32 41.32 32 36 30 33 33 36
33 41.33 36 36 33 36 36 39 Coil voltages for AC and DC operated contactors
36 41.36 36 42 36 39 39 42 Type-suffix for coil-types K3-115/.. to K3-860/..
40 41.40 42 42 39 42 42 47 for contactor-types K3-90.. to K3-860..
42 4.42 42 48 42 47 47 52
Suffix Voltage Marking Rated Control Voltage Us
48 41.48 48 48 44 48 48 52 to to
55 41.55 55 60 52 58 58 65 contactor coil at the coil range
60 41.60 60 58 65 65 72 type type for for for 50Hz for 60Hz
50/60Hz DC min. max. min. max.
65 41.65 65 65 72 72 80 V V V V V V
75 41.75 75 72 80 80 90
85 41.85 85 80 90 90 100 24 4.24 24 24 22 24 22 24
48 4.48 48 48 44 48 44 48
90 41.90 100 100 90 100 100 110 110 4.110 110-120 110 110 120 110 120
110 4.110 110 110-120 100 110 110 122
115 41.115 115 125 110 122 122 135 230 4.230 220-240 220 220 240 220 240
400 4.400 380-415 - 380 415 380 415
127 41.127 127 122 135 135 150
140 41.140 140 135 150 150 165
150 41.150 150 150 165 165 180

165 41.165 165 180-208 165 180 180 208 Coil voltages for AC operated contactors
180 41.180 180-2101) 200-2401) 180 2101) 200 2401)
200 41.200 200-2301) 220-240 200 2301) 220 240 Type-suffix for coil-types K3-115/..AC
for contactor-types K3-90..AC to K3-115..AC
230 4.230 220-240 230-264 220 240 230 264
254 41.254 254 277 240 264 264 290 Suffix Voltage Marking Rated Control Voltage Us
270 41.270 270 264 290 290 315 to to
contactor coil at the coil range
300 41.300 300 290 315 315 345 type type for for for 50Hz for 60Hz
320 41.320 320 315 345 345 380 50Hz 60Hz min. max. min. max.
345 41.345 345-4001) 380-4401) 345 4001) 380 4401) V V V V V V

400 4.400 380-415 400-440 380 415 400 460 110AC 4.110AC 110-122 132-146 110 122 132 146
415 41.415 415-440 440-480 400 440 440 480 230AC 4.230AC 220-240 277 220 240 264 288
440 41.440 440-480 480-500 440 480 480 530
Other coil voltages on request
480 41.480 480-500 530-580 480 530 530 580
500 41.500 500-550 550-600 500 550 550 600 Operating range of magnet-coils: 0,85 x Us (min. value of rated
control voltage) up to 1,1 x Us (max. value of rated control voltage)
550 41.550 550-600 600 550 600 600 (650)
With reduced control voltage range 0,9 up to 1,0 x Us at ambient
Standard voltages in bold type letters temperature 60 - 90°C

1) Operating range of magnet-coils: 0,85 x Us (min. value of rated control voltage) up to 1,05 x Us (max. value of rated control voltage)

D677E 49
Spare Coils for AC operated contactors

Type Coil voltage 1)


4.24 24V 50Hz
4.42 42V 50Hz
4.110 110V 50Hz
41.180 180V 50Hz, 220V 60Hz
4.230 220-240V 50Hz
4.400 380-415V 50Hz
⏐ Pack Weight
For Contactors W pcs. kg/pc.

K3-07N.. up to K3-22N.. K10N/ . . .EUR 1 0,053


K3-07.. up to K3-22.. K3-6/ . . . 10 0,040
K2-07.. up to K2-16.. K6/ . . . 10 0,040

K3-24.. up to K3-40.. K24/ . . . 1 0,085


K2-23.. up to K2-37.. K23/ . . . 1 0,085
K3-50.. up to K3-74.., K2-45.., K2-60.. K45/ . . . 1 0,110

K65.., K85.. K85/ . . . 1 0,215


K110.. K110/ . . . 1 0,220

Type Coil voltage 1)


4.110 110V 50Hz, 110-115V 60Hz
4.230 220-230V 50Hz
4.400 380-400V 50Hz
For Contactors W pcs. kg/pc.

K3-150.., K3-175.. K3-175/ . . . 1 0,38


K3-1000.., K3-1200.. without feeder group 2) K3-1200/ . . . 1 3,12

Spare Coils for AC and DC operated contactors


Type Coil voltage 1)
4.24 24V 50/60Hz / 24V DC
4.110 110-120V 50/60Hz / 110V DC
4.230 220-240V 50/60Hz / 220V DC
4.400 380-415V 50/60Hz
For Contactors W pcs. kg/pc.

K3-90.., K3-115.. with feeder group K3-115/ . . . 1 0,30


K3-151.., K3-176.. with feeder group K3-176/ . . . 1 0,68
K3-210.., K3-316.. with feeder group K3-316/ . . . 1 0,68

K3-450.., K3-550.. without feeder group 2) K3-550/ . . . 1 1,63


K3-700.., K3-860.. without feeder group 2) K3-860/ . . . 1 2,44

Spare Feeder Groups for contactors K3-450.. to K3-860..


In case of changing control voltage, Type Coil voltage 1)
change coil and feeder group too 110 110-120V 50/60Hz / 110V DC
230 220-240V 50/60Hz / 220V DC
400 380-415V 50/60Hz
⏐ Pack Weight
For Contactors for coils W pcs. kg/pc.

K3-450.., K3-550.. K3-550/4... K3-550/FG . . . 1 0,33


K3-700.., K3-860.. K3-860/4.. K3-860/FG . . . 1 0,54

1) Coil voltage range and non-standard coil voltages see page 39


2) In case of changing control voltage, change coil and feeder group too

50 D677E
Spare Coils for DC operated contactors
Aux. Contact Block Type Coil voltage 1)
for double winding coil 47.24 24V DC
47.110 110V DC
47.220 220V DC
⏐ Pack Weight
For Contactors W pcs. kg/pc.

K3-07N..= up to K3-22N..= HN01U K10N/ . . . 1 0,052


K3-07..= up to K3-22..= HN01U K3-6/ . . . 1 0,042
K2-07..= up to K2-16..= HN01U K6/ . . . 1 0,042

K3-24..= up to K3-40..= HN01X K24/ . . . 1 0,090


K2-23..= up to K2-37..= HN01X K23/ . . . 1 0,090
K3-50..= up to K3-74..=, K2-45..=, K2-60..= HN01Z K45/ . . . 1 0,115

K65..=, K85..= - K85/ . . . 1 0,220


K110..= - K110/ . . . 1 0,225

Type Coil voltage 1)


43.110 110V DC
43.220 220V DC
For Contactors W pcs. kg/pc.

K3-1000..=, K3-1200..= without feeder group 2) K3-1200/ . . . 1 3,12

Wiring Diagrams for Coil Circuit


AC operated, DC operated DC operated
with double winding coil
K3-07.. K3-07..= KG3..
up to K110.. up to K3-22..=

AC and DC operated AC and DC operated


with double winding coil K3-24..= with series resistor
K3-90A00, K3-115A00 to K3-200A21
K3-151A00, K3-176A00 K3-74..= K3-315A21
K3-210A00 to K3-316A00

K85..=
K110..=

AC and DC operated DC operated AC operated


with series resistor with DC coil with DC coil
K3-450.. up to K3-860.. K3-1000.., K3-1200.. K3-1000.., K3-1200..

Adjustable dropout operating time for K3-450.. to K3-860..: Contactor K3-1000.., K3-1200..:
150-200ms: Wiring see above (delivery standard) For control voltages up to 125V
500-1000ms: Jumper device "Z" NC contacts 21-22 and 11-12 are connected parallel,
approx. 20ms: Special wiring see package folder for higher voltages contacts are connected in series (delivery standard).

1) Other coil voltages on request


2) In case of changing control voltage, change coil and feeder group too

D677E 51
Spare Contacts
Main Contacts Type Pack Weight
for Contactors pcs. kg/pc.

K85.. EK85/1 3 0,235


K110.. EK110/1 3 0,275

K3-150.. EK3-150/10 1 0,32


K3-151.. EK3-151/10 1 0,16
K3-175.. EK3-175/10 1 0,32

K3-176.. EK3-176/10 1 0,16


K3-200.. EK3-200/10 1 0,18
K3-210.. EK3-210/10 1

K3-260.. EK3-260/10 1
K3-315.. EK3-315/10 1 0,34
K3-316.. EK3-316/10 1

K3-450.. EK3-450/10 1 0,35


K3-550.. EK3-550/10 1 0,35
K3-700.. EK3-700/10 1 0,85

K3-860.. EK3-860/10 1 1,0


K3-1000.. EK3-1000/10 1 1,4
K3-1200.. EK3-1200/10 1 1,4

52 D677E
Approximate Values for three-phase Motors
Motor Full Load Currents
Approximate values of motor F.L.C. and minimum "slow blow" respectively "gL" short-circuit fuse

Motor Range 220-230V Value 240V Value 380-400V Value 415V Value 500V Value 660-690V Value
rating according to Motor of fusing at Motor of fusing at Motor of fusing at Motor of fusing at Motor of fusing at Motor of fusing at
BS for motor start motor start motor start motor start motor start motor start
415V F.L.C. D.O.L. YD F.L.C. D.O.L. YD F.L.C. D.O.L. YD F.L.C. D.O.L. YD F.L.C. D.O.L. YD F.L.C. D.O.L. YD
kW PS~hp hp cosϕ % A A A A A A A A A A A A A A A A A A
0,06 0,08 - 0,7 59 0,38 1 1 0,35 1 1 0,22 1 1 - - - 0,16 1 1 - - -
0,09 0,12 - 0,7 60 0,55 2 2 0,5 2 2 0,33 1 1 - - - 0,24 1 1 - - -
0,12 0,16 - 0,7 61 0,76 2 2 0,68 2 2 0,42 2 2 - - - 0,33 1 1 - - -
0,18 0,24 - 0,7 61 1,1 2 2 1 2 2 0,64 2 2 - - - 0,46 1 1 - - -
0,25 0,34 - 0,7 62 1,4 4 2 1,38 4 2 0,88 2 2 - - - 0,59 2 2 - - -
0,37 0,5 - 0,72 64 2,1 4 4 1,93 4 4 1,22 4 2 - - - 0,85 2 2 0,7 2 2
0,55 0,75 - 0,75 69 2,7 4 4 2,3 4 4 1,5 4 2 - - - 1,2 4 2 0,9 2 2
0,75 1 1 0,8 74 3,3 6 4 3,1 6 4 2 4 4 2 4 4 1,48 4 2 1,1 2 2
1,1 1,5 1,5 0,83 77 4,9 10 6 4,1 6 6 2,6 4 4 2,5 4 4 2,1 4 4 1,5 4 2
1,5 2 2 0,83 78 6,2 10 10 5,6 10 10 3,5 6 4 3,5 6 4 2,6 4 4 2 4 4
2,2 3 3 0,83 81 8,7 16 10 7,9 16 10 5 10 6 5 10 6 3,8 6 6 2,9 6 4
2,5 3,4 - 0,83 81 9,8 16 16 8,9 16 10 5,7 10 10 - - - 4,3 6 6 - - -
3 4 4 0,84 81 11,6 20 16 10,6 20 16 6,6 16 10 6,5 16 10 5,1 10 10 3,5 6 4
3,7 5 5 0,84 82 14,2 25 20 13 25 16 8,2 16 10 7,5 16 10 6,2 16 10 - - -
4 5,5 - 0,84 82 15,3 25 20 14 25 20 8,5 16 10 - - - 6,5 16 10 4,9 10 6
5,5 7,5 7,5 0,85 83 20,6 35 25 18,9 35 25 11,5 20 16 11 20 16 8,9 16 10 6,7 16 10
7,5 10 10 0,86 85 27,4 35 35 24,8 35 35 15,5 25 20 14 25 16 11,9 20 16 9 16 10
8 11 - 0,86 85 28,8 50 35 26,4 35 35 16,7 25 20 - - - 12,7 20 16 - - -
11 15 15 0,86 87 39,2 63 50 35,3 50 50 22 35 25 21 35 25 16,7 25 20 13 25 16
12,5 17 - 0,86 87 43,8 63 50 40,2 63 50 25 35 35 - - - 19 35 25 - - -
15 20 20 0,86 87 52,6 80 63 48,2 80 63 30 50 35 28 35 35 22,5 35 25 17,5 25 20
18,5 25 25 0,86 88 64,9 100 80 58,7 80 63 37 63 50 35 50 50 28,5 50 35 21 35 25
20 27 - 0,86 88 69,3 100 80 63,4 80 80 40 63 50 - - - 30,6 50 35 - - -
22 30 30 0,87 89 75,2 100 80 68 100 80 44 63 50 40 63 50 33 50 50 25 35 35
25 34 - 0,87 89 84,4 125 100 77,2 100 100 50 80 63 - - - 38 63 50 - - -
30 40 40 0,87 90 101 125 125 92,7 125 100 60 80 63 55 80 63 44 63 50 33 50 35
37 50 50 0,87 90 124 160 160 114 160 125 72 100 80 66 100 80 54 80 63 42 63 50
40 54 - 0,87 90 134 160 160 123 160 160 79 100 100 - - - 60 80 63 - - -
45 60 60 0,88 91 150 200 160 136 200 160 85 125 100 80 100 100 64,5 100 80 49 63 63
51 70 - 0,88 91 168 200 200 154 200 200 97 125 100 - - - 73,7 100 80 - - -
55 75 - 0,88 91 181 250 200 166 200 200 105 160 125 - - - 79 125 100 60 80 63
59 80 80 0,88 91 194 250 250 178 250 200 112 160 125 105 160 125 85,3 125 100 - - -
75 100 100 0,88 91 245 315 250 226 315 250 140 200 160 135 200 160 106 160 125 82 125 100
90 125 125 0,88 92 292 400 315 268 315 315 170 250 200 165 200 200 128 160 160 98 125 125
110 150 150 0,88 92 358 500 400 327 400 400 205 250 250 200 250 250 156 200 200 118 160 125
129 175 175 0,88 92 420 500 500 384 500 400 242 315 250 230 315 250 184 250 200 - - -
132 180 - 0,88 92 425 500 500 393 500 500 245 315 250 - - - 186 250 200 140 200 160
147 200 200 0,88 93 472 630 630 432 630 500 273 315 315 260 315 315 207 250 250 - - -
160 220 - 0,88 93 502 630 630 471 630 630 295 400 315 - - - 220 315 250 170 200 200
184 250 250 0,88 93 590 800 630 541 630 630 340 400 400 325 400 400 259 315 315 - - -
200 270 - 0,88 93 626 800 800 589 800 630 370 500 400 - - - 278 315 315 215 250 250
220 300 300 0,88 93 700 1000 800 647 800 800 408 500 500 385 500 400 310 400 400 - - -
250 340 - 0,88 93 803 1000 1000 736 1000 800 460 630 500 - - - 353 500 400 268 315 315
257 350 350 0,88 93 826 1000 1000 756 1000 800 475 630 630 450 630 500 363 500 400 - - -
295 400 400 0,88 93 948 1250 1000 868 1000 1000 546 800 630 500 630 630 416 500 500 - - -
315 430 - 0,88 93 990 1250 1250 927 1250 1000 580 800 630 - - - 445 630 500 337 400 400
355 483 - 0,89 95 - - - - - - 636 800 800 - - - 483 630 630 366 500 400
400 545 - 0,89 96 - - - - - - 710 1000 800 - - - 538 630 630 410 500 500

The motor F.L.C. be valid for standard internal and surface cooled three-pole motors with higher F.L.C., higher starting current and / or longer starting time, larger
motors with 1500 min-1. The fuses values be valid for the motor F.L.C. shown in the short-circuit fuses are required.
table and D.O.L.-start: starting current max. 6x motor F.L.C., starting time max. 5s; The maximum admissible value is dependent on the switchgear respectively
star-delta-start: starting current max. 2x motor F.L.C., starting time max. 15s. For thermal overload relay.

Approximate values of motor F.L.C. according to CSA and UL


Motor Motor F.L.C. at 110-120V Motor F.L.C. at 220-240V1) Motor F.L.C. at 440-480V Motor F.L.C. at 550-600V
rating 1-phase 2-phase 3-phase 1-phase 2-phase 3-phase 1-phase 2-phase 3-phase 1-phase 2-phase 3-phase
hp A A A A A A A A A A A A
1/2 9.8 4.0 4.4 4.9 2.0 2.2 2.5 1.0 1.1 2.0 0.8 0.9
3/4 13.8 4.8 6.4 6.9 2.4 3.2 3.5 1.2 1.6 2.8 1.0 1.3
1 16.0 6.4 8.4 8.0 3.2 4.2 4.0 1.6 2.1 3.2 1.3 1.7
1-1/2 20.0 9.0 12.0 10.0 4.5 6.0 5.0 2.3 3.0 4.0 1.8 2.4
2 24.0 11.8 13.6 12.0 5.9 6.8 6.0 3.0 3.4 4.8 2.4 2.7
3 34.0 16.6 19.2 17.0 8.3 9.6 8.5 4.2 4.8 6.8 3.3 3.9
5 56.0 26.4 30.4 28.0 13.2 15.2 14.0 6.6 7.6 11.2 5.3 6.1
7-1/2 80.0 38.0 44.0 40.0 19.0 22.0 21.0 9.0 11.0 16.0 8.0 9.0
10 100.0 48.0 56.0 50.0 24.0 28.0 26.0 12.0 14.0 20.0 10.0 11.0
15 135.0 72.0 84.0 68.0 36.0 42.0 34.0 18.0 21.0 27.0 14.0 17.0
20 - 94.0 108.0 88.0 47.0 54.0 44.0 23.0 27.0 35.0 19.0 22.0
25 - 118.0 136.0 110.0 59.0 68.0 55.0 29.0 34.0 44.0 24.0 27.0
30 - 138.0 160.0 136.0 69.0 80.0 68.0 35.0 40.0 54.0 28.0 32.0
40 - 180.0 208.0 176.0 90.0 104.0 88.0 45.0 52.0 70.0 36.0 41.0
50 - 226.0 260.0 216.0 113.0 130.0 108.0 56.0 65.0 86.0 45.0 52.0
60 - - - - 133.0 145.0 - 67.0 77.0 - 53.0 62.0
75 - - - - 166.0 192.0 - 83.0 96.0 - 66.0 77.0
100 - - - - 218.0 248.0 - 109.0 124.0 - 87.0 99.0
125 - - - - - 312.0 - 135.0 156.0 - 108.0 125.0
150 - - - - - 360.0 - 156.0 180.0 - 125.0 144.0
200 - - - - - 480.0 - 208.0 240.0 - 167.0 192.0
250 - - - - - 602.0 - - 302.0 - - 242.0
300 - - - - - - - - 361.0 - - 289.0
350 - - - - - - - - 414.0 - - 336.0
400 - - - - - - - - 477.0 - - 382.0
500 - - - - - - - - 590.0 - - 472.0

1) Determine the motor current for 200V and 208V by increasing the values for 220-240V at 200V about 15% and for 208V about 10%.

D677E 53
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74

Rated insulation voltage Ui 1)


V AC 690 690 690 690 690 690 690 690 690 690

Making capacity Ieff at Ue = 690V AC A 200 200 200 200 400 500 500 700 900 900

Breaking capacity Ieff 400V AC A 180 180 200 200 380 400 400 600 800 800
K2-09 to K3-22 cosϕ= 0,65 500V AC A 150 150 180 180 300 370 370 500 700 700
K3-24 to K3-1200 cosϕ= 0,35 690V AC A 100 100 150 150 260 340 340 400 500 500
1000V AC A - - - - - - - - -

Utilization category AC1


Switching of resistive load
Rated operational current Ie (=Ith) 690V A 25 25 32 32 50 65 80 110 120 130
at 40°C, open
Rated operational power 220V kW 9,5 9,5 12,2 12,2 19,0 24,7 30,4 41,9 45,7 49,5
of three-phase resistive loads 230V kW 9,9 9,9 12,7 12,7 19,9 25,9 31,8 43,8 47,7 51,7
50-60Hz, cosϕ= 1 240V kW 10,4 10,4 13,3 13,3 20,8 27,0 33,2 45,7 49,8 54,0

380V kW 16,4 16,4 21,0 21,0 32,9 42,7 52,6 72,3 78,9 85,5
400V kW 17,3 17,3 22,1 22,1 34,6 45,0 55,4 76,1 83,0 90,0
415V kW 17,9 17,9 23,0 23,0 35,9 46,7 57,4 79,0 86,2 93,3

440V kW 19,0 19,0 24,4 24,4 38,1 49,5 60,9 83,7 91,3 99,0
500V kW 21,6 21,6 27,7 27,7 43,3 56,2 69,2 95,2 103,8 112,5
660V kW 28,5 28,5 36,5 36,5 57,1 74,2 91,3 125,6 137,0 148,4

690V kW 29,8 29,8 38,2 38,2 59,7 77,6 95,5 131,3 143,2 155,2
1000V kW - - - - - - - - -

Rated operational current Ie (=Ithe) 690V A 25 25 32 32 40 55 65 90 100 110


at 60°C, enclosed
Rated operational power 220V kW 9,5 9,5 12,2 12,2 15,2 20,9 24,7 34,3 38,1 41,9
of three-phase resistive loads 230V kW 9,9 9,9 12,7 12,7 15,9 21,9 25,9 35,8 39,8 43,8
50-60Hz, cosϕ= 1 240V kW 10,4 10,4 13,3 13,3 16,6 22,8 27,0 37,4 41,5 45,7

380V kW 16,4 16,4 21,0 21,0 26,3 36,2 42,7 59,2 65,7 72,3
400V kW 17,3 17,3 22,1 22,1 27,7 38,1 45,0 62,3 69,2 76,1
415V kW 17,9 17,9 23,0 23,0 28,7 39,5 46,7 64,6 71,8 79,0

440V kW 19,0 19,0 24,4 24,4 30,4 41,9 49,5 68,5 76,1 83,7
500V kW 21,6 21,6 27,7 27,7 34,6 47,6 56,2 77,9 86,5 95,2
660V kW 28,5 28,5 36,5 36,5 45,7 62,8 74,2 102,8 114,2 125,6

690V kW 29,8 29,8 38,2 38,2 47,7 65,7 77,6 107,4 119,4 131,3
1000V kW - - - - - - - - -
Minimum cross-section of conductor
at load with Ie (=Ith) mm² 4 4 6 6 10 16 25 35 50 50

Utilization category AC2 and AC3


Switching of three-phase motors
Rated operational current Ie 220V A 12 15 18 22 24 30 40 50 63 74
open and enclosed 230V A 11,5 14,5 18 22 24 30 40 50 62 74
240V A 11 14 18 22 24 32 40 50 62 74

380-400V A 10 14 18 22 24 32 40 50 62 74
415V A 9 14 18 22 23 30 40 50 62 74
440V A 9 14 18 22 23 30 40 50 62 74

500V A 7 9 9 9 17,5 21 21 33 42 42
660-690V A 6,5 8,5 8,5 8,5 17 20 20 31 40 40
1000V A - - - - - - - - -

Rated operational power 220-230V kW 3 4 5 6 6 8,5 11 12,5 18,5 22


of three-phase motors 240V kW 3 4 5 7 7 9 11,5 13,5 19 23
50-60Hz 380-400V kW 4 5,5 7,5 11 11 15 18,5 22 30 37

415V kW 4,5 6 8,5 12 12 16 20 24 33 40


440V kW 4,5 6 8,5 12 12 16 20 24 33 40
500V kW 5,5 7,5 10 10 15 18,5 18,5 30 37 45

660-690V kW 5,5 7,5 10 10 15 18,5 18,5 30 37 45


1000V kW - - - - - - - - - -

1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.

54 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type K3-90 K3-115 K3-116 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200

V~ 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 690 690 690 690

A 1100 1200 1200 1500 2000 2100 2600 3200 4500 5500 7000 8600 10000 12000

A 950 1100 1000 1200 1500 1600 2100 2600 4500 5500 7000 8000 8000 10000
A 850 1000 1000 1200 1500 1600 2100 2600 4500 5500 7000 8000 8000 10000
A 600 600 800 1000 800 1200 1900 2300 3200 4400 5600 6900 7000 8000
A - - 400 500 600 700 850 1000 - - - - - -

A 160 200 200 230 250 350 450 500 700 760 1000 1100 1200 1350

kW 60 76 76 87 95 133 171 190 266 289 381 419 457 514


kW 63 79 79 91 99 139 179 199 279 302 398 438 478 537
kW 66 83 83 95 103 145 187 207 291 315 415 457 498 561

kW 105 131 131 151 164 230 296 329 460 500 658 724 789 888
kW 110 138 138 159 173 242 311 346 485 526 692 762 831 935
kW 115 143 143 165 179 251 323 359 503 546 718 790 862 970

kW 121 152 152 175 190 266 342 381 533 579 762 838 914 1028
kW 138 173 173 199 216 303 389 453 606 658 866 952 1039 1169
kW 182 228 228 262 285 400 514 571 800 868 1143 1257 1371 1543

kW 191 239 239 274 298 418 537 597 836 908 1195 1314 1434 1613
kW 221 277 216 318 346 433 546 606 692 866 - - - -

A 145 170 170 180 200 280 360 400 550 600 800 875 960 1080

kW 55 64 64 68 76 106 137 152 209 228 304 333 365 411


kW 57 67 67 71 79 111 143 159 219 239 318 348 382 430
kW 59 70 70 74 83 116 150 166 228 249 332 363 399 448

kW 95 111 111 118 131 184 237 263 362 395 526 575 631 710
kW 100 117 117 124 138 193 249 277 381 415 554 606 665 748
kW 104 122 122 129 143 201 259 287 395 431 575 628 690 776

kW 110 129 129 137 152 213 274 304 419 457 609 666 731 823
kW 125 147 147 155 173 242 312 346 476 519 692 757 831 935
kW 165 194 194 205 228 320 412 457 628 685 914 1000 1097 1234

kW 173 202 202 215 239 334 430 478 657 717 956 1045 1147 1290
kW 166 187 216 277 346 388 499 554 692 866 - - - -

mm² 95 120 95 95 120 240 2x150 2x(30x6) 2x(40x5) 2x(50x5) 2x(60x5) 2x(60x6) 2x(60x6) 2x(60x8)

A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200
A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200
A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200

A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200
A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200
A 90 115 115 150 175 210 260 315 450 550 700 860 1000 1200

A 60 60 115 150 175 210 260 315 450 550 700 860 1000 1200
A 58 58 100 120 140 150 180 240 400 500 630 700 860 1000
A 58 58 45 60 70 85 100 125 200 250 - - - -

kW 25 33 30 40 50 60 75 90 132 175 225 280 325 390


kW 27 35 35 45 55 65 80 100 140 185 235 290 335 400
kW 45 55 55 75 90 110 132 160 250 300 400 500 580 680

kW 49 63 59 80 95 115 140 180 257 315 415 515 600 710


kW 49 63 63 85 100 125 150 190 270 335 450 530 630 750
kW 55 55 75 90 100 132 160 210 300 375 500 600 720 850

kW 55 55 90 110 132 132 160 210 375 500 630 700 850 1000
kW 55 55 55 75 90 110 132 160 280 355 - - - -

D677E 55
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74

Utilization category AC4


Switching of squirrel cage motors, inching
Rated operational current Ie 220V A 12 15 18 18 24 30 40 50 63 63
open and enclosed 230V A 11,5 14,5 18 18 24 30 40 50 62 62
240V A 11 14 18 18 24 32 40 50 62 62

380-400V A 10 14 18 18 24 32 40 50 62 62
415V A 9 14 18 18 23 30 37 45 60 60
440V A 9 14 18 18 23 30 37 45 55 55

500V A 9 12 16 16 17,5 21 21 33 42 42
660V A 7 9 9 9 17 20 20 31 40 40
690V A 6,5 8,5 8,5 8,5 17 20 20 31 40 40
1000V A - - - - - - - - -

Rated operational power 220-230V kW 3 4 5 5 6 8,5 11 12,5 18,5 18,5


of three-phase motors 240V kW 3 4 5 5 7 9 11,5 13,5 19 19
50-60Hz 380-400V kW 4 5,5 7,5 7,5 11 15 18,5 22 30 30

415V kW 4,5 6 8,5 8,5 12 16 20 24 33 33


440V kW 4,5 6 8,5 8,5 12 16 20 24 33 33
500V kW 5,5 7,5 10 10 15 18,5 18,5 30 37 37

660-690V kW 5,5 7,5 10 10 15 18,5 18,5 30 37 37


1000V kW - - - - - - - - - -

Utilization category AC5a


Switching of gas discharge lamps
Rated operational current Ie
per pole at 220/230V

Fluorescent lamps,
uncompensated and serial compensated A 20 20 25 25 40 52 64 88 96 104
parallel compensated A 7 9 9 9 18 22 22 30 40 45
dual-connection A 22,5 22,5 28 28 45 58 72 98 108 117

Metal halide lamps1),


uncompensated A 12 15 19 19 30 39 48 66 72 78
parallel compensated A 7 9 9 9 18 22 22 30 40 45

Mercury-vapour lamps2),
uncompensated A 22,5 25 28 28 45 58 72 99 108 117
parallel compensated A 7 9 9 9 18 22 22 30 40 45

Mixed light lamps3) A 20 20 25 25 40 52 64 88 96 104

Utilization category AC5b


Switching of incandescent lamps4)
Rated operational current Ie
per pole at 220/230V A 12,5 12,5 12,5 12,5 25 31 31 43 56 56

1) Metal halide lamps and sodium-vapour lamps (high- and low-pressure lamps)
2) High-pressure lamps
3) Blended lamps, containing a mercury high-pressure unit and a tungsten helix in a flourescent glass bulb (daylight lamps)
4) Current inrush approx. 16 x Ie

56 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type K3-90 K3-115 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200

A 85 98 55 63 85 100 120 150 180 230 280 340 400


A 85 98 55 63 85 100 120 150 180 230 280 340 400
A 85 98 55 63 85 100 120 150 180 230 280 340 400

A 85 85 55 63 85 100 120 150 180 230 280 340 400


A 85 85 55 63 85 100 120 150 180 230 280 340 400
A 85 85 55 63 85 100 120 150 180 230 280 340 400

A 85 85 - - - - - - - - - - -
A 60 60 - - - - - - - - - - -
A 57,5 57,5 - - - - - - - - - - -
A - - - - - - - - - - - - -

kW 25 30 15 18,5 25 30 37 45 51 68 80 110 132


kW 27 32 15,5 19 26 31 38 47 53 71 83 115 137
kW 45 45 25 30 45 55 63 75 90 120 150 185 220

kW 49 49 25 33 45 55 65 80 100 132 160 200 230


kW 49 49 30 34 48 55 67 85 100 132 160 200 230
kW 55 55 25 30 55 65 75 100 110 150 185 220 257

kW 55 55 25 30 55 65 75 100 110 150 185 220 257


kW - - - - - - - - - - - - -

A 100 120 120 140 180 220 280 360 450 570 700 850 1000
A 55 70 85 100 130 160 200 300 360 460 550 660 800
A 112 144 120 140 180 220 280 360 450 570 700 850 1000

A 85 90 95 110 140 180 230 300 380 490 610 750 890
A 55 70 75 85 110 140 170 260 300 400 480 580 700

A 112 144 120 140 180 220 280 360 450 570 700 850 1000
A 55 70 75 85 110 140 170 260 300 400 480 580 700

A 100 120 100 120 160 200 250 320 400 500 600 700 800

A 69 75 100 120 160 190 220 260 315 440 500 560 630

D677E 57
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74

Utilization category AC6a


Transformer primary switching
at inrush n 30 30 30 30 30 30 30 30 30 30
Rated operational current Ie 400V A 4,5 5,5 7,5 7,5 10,5 13,5 13,5 20 27 33

Rated operational power 220-230V kVA 1,8 2,2 3 3 4,2 5,4 5,4 8 10,7 13
dependent on inrush n 240V kVA 1,9 2,3 3,1 3,1 4,3 5,6 5,6 8,3 11,2 13,5
380-400V kVA 3,1 3,8 5,2 5,2 7,3 9,3 9,3 13,5 18,5 22,5

For different inrush-factors x 415-440V kVA 3,4 4,2 5,7 5,7 8 10,2 10,2 15 20,5 25
use the following formula: 500V kVA 3,9 4,8 6,5 6,5 9 11,5 11,5 17 23 28
Px=Pn*(n/x) 660-690V kVA 5,4 6,5 9 9 12,5 16 16 24 32 39

Utilization category AC6b


Switching of three-phase capacitors
Maximum inrush current (peak value)
as multiple k of the
capacitor rated current k 35 25 20 20 25 25 25 25 25 20
Rated operational current Ie 500V A 8 12 15,5 15,5 23 32 32 45 60 70

Rated operational power 220-230V kVAr 3 4,5 6 6 8,5 12 12 17 24 28


(sinϕ→1) 240V kVAr 3,5 5 6,5 6,5 9,5 13 13 18,5 25 29
380-400V kVAr 5 7,5 10 10 15 20 20 29 39 46

For different multiples x 415-440V kVAr 5,5 8 11 11 16 22 22 32 43 50


use the following formula: 500V kVAr 7 10 13 13 20 26 26 39 50 58
Px=Pk*(k/x) 660-690V kVAr 7 10 13 13 20 26 26 40 50 58

Switching of
reactive capacitor banks
Rated operational current Ie 690V A 8 13 18 20 28 36 42 48 72 108 1)

Rated operational power 220-230V kVAr 2,9 5 7 7,5 11 14 16 20 28 33


240V kVAr 3,1 5,4 7 8 11 14 17 20 28 36
380-400V kVAr 5 9 12,5 13 20 25 27,5 33,3 50 75 1)

415-440V kVAr 5,5 9,5 13 14 22 27 30 36 53 75 1)


500V kVAr 6 11 15 17 25 30 36 40 60 75
660-690V kVAr 8 15 20 22 33 41 48 55 82 100
1000V kVAr - - - - - - - - - -

Utilization category DC1


Switching of resistive load
Time constant L/R ≤1ms
Rated operational current Ie 1 pole 24V A 20 25 32 32 50 65 80 110 120 130
60V A 20 25 32 32 50 65 80 110 120 130
110V A 6 6 6 6 10 10 10 12 12 12
220V A 0,8 0,8 0,8 0,8 1,4 1,4 1,4 1,4 1,4 1,4

3 poles in series 24V A 20 25 32 32 50 65 80 110 120 130


60V A 20 25 32 32 50 65 80 110 120 130
110V A 20 25 32 32 50 65 80 110 120 130
220V A 16 20 20 20 30 35 35 63 80 80

Utilization category DC3 and DC5


Switching of shunt motors
and series motors
Time constant L/R ≤15ms
Rated operational current Ie 1 pole 24V A 20 25 32 32 50 65 80 110 120 130
60V A 6 6 6 6 30 30 30 60 60 60
110V A 1,2 1,2 1,2 1,2 1,8 1,8 1,8 1,8 1,8 1,8
220V A 0,2 0,2 0,2 0,2 0,2 0,2 0,2 0,25 0,25 0,25

3 poles in series 24V A 20 25 32 32 50 65 80 110 120 130


60V A 20 25 32 32 40 40 40 80 80 80
110V A 20 20 20 20 40 40 40 80 80 80
220V A 2,5 2,5 2,5 2,5 4 4 4 5 5 5

1) Consider resistive load (Ith). see page 44

58 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type K3-90 K3-115 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200

n 30 30 30 30 30 30 30 30 30 30 30 30 30
A 38 50 65 80 90 120 142 203 248 315 390 450 540

kVA 15 20 25 30 34 45 54 77 95 120 148 170 200


kVA 15,5 20,5 27 33 37 50 59 80 100 130 160 185 220
kVA 26 34 45 55 60 80 95 140 170 210 270 310 370

kVA 29 38 46 57 63 85 100 145 175 220 280 320 380


kVA 33 43 55 69 75 100 120 170 210 270 330 380 460
kVA 45 60 56 69 100 135 160 200 250 320 350 500 600

k 20 20 20 20 25 20 20 20 20 20 20 20 20
A 87 100 120 155 195 225 255 300 370 440 520 680 760

kVAr 33 38 45 60 75 90 100 115 145 170 200 260 290


kVAr 36 42 52 62 78 94 104 120 150 175 205 270 300
kVAr 57 65 80 100 130 155 170 200 250 300 350 450 500

kVAr 60 70 95 110 135 165 175 210 260 310 360 465 520
kVAr 70 80 100 130 170 194 220 260 320 380 450 590 660
kVAr 70 80 100 130 170 194 220 260 320 380 450 590 660

A 115 144 115 140 200 225 250 330 420 550 600 680 760

kVAr 45 55 43 53 76 85 95 125 160 209 228 260 290


kVAr 45 55 45 55 80 90 100 130 170 220 240 280 310
kVAr 80 100 75 90 130 145 160 210 270 350 390 440 480

kVAr 100 120 80 100 140 160 170 230 290 380 420 470 530
kVAr 105 125 95 120 170 190 210 280 350 450 500 570 640
kVAr 120 148 125 150 200 230 260 350 450 600 650 700 800
kVAr 160 200 155 200 300 340 400 500 650 - - - -

A 160 200 - - - - - - - - - - -
A 160 200 - - - - - - - - - - -
A 20 25 - - - - - - - - - - -
A 2 2,5 - - - - - - - - - - -

A 160 200 200 250 350 400 450 600 760 1000 1100 1200 1350
A 160 200 200 250 350 400 450 600 760 1000 1100 1200 1350
A 160 200 150 170 250 280 315 400 480 560 630 800 900
A 100 160 80 100 150 180 200 250 315 400 450 500 600

A 160 200 - - - - - - - - - - -
A 85 110 - - - - - - - - - - -
A 2 2,5 - - - - - - - - - - -
A 0,5 0,5 - - - - - - - - - - -

A 160 200 - - - - - - - - - - -
A 100 110 - - - - - - - - - - -
A 100 110 - - - - - - - - - - -
A 7 8 - - - - - - - - - - -

D677E 59
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74

Maximum ambient temperature


Operation open °C -40 to +60 (+90) 1)
enclosed °C -40 to +40
with thermal overload relay open °C -25 to +60
enclosed °C -25 to +40
Storage °C -50 to +90

Short circuit protection


for contactors without thermal overload relay

Coordination-type "1" according to IEC 947-4-1


Contact welding without
hazard of persons
max. fuse size gL (gG) A 63 63 63 63 80 80 80 160 160 160

Coordination-type “2” according to IEC 947-4-1


Light contact welding accepted
max. fuse size gL (gG) A 25 35 35 35 50 50 50 100 125 125

Contact welding not accepted


max. fuse size gL (gG) A 16 16 16 16 25 35 35 50 63 63
For contactors with thermal overload relay the
device with the smaller admissible backup fuse
(contactor or thermal overload relay)
determines the fuse size.

Cable cross-sections
for contactors without thermal overload relay
1 cable per clamp
main connector solid or stranded mm² 0,75 - 6 1,5 - 25 4 - 50
flexible mm² 1-4 2,5 - 16 10 - 35
flexible with multicore cable end mm² 0,75 - 4 1,5 - 16 6 - 35

2 cables per clamp


solid or stranded mm² 6+(1-6) / 4+(0,75-4) 16+(2,5-16) / 10+(4-16) 50+4 / 35+6 / 25+(6-16)
2,5+(0,75-2,5) / 1,5+(0,75-1,5) 6+(4-16) / 4+(2,5-16) 16+(6-16) / 10+(6-16)
flexible mm² 6+(1,5-4) / 4+(1-4) 16+(2,5-6) / 10+(4-10) 50+(4-10) / 35+(4-16)
2,5+(0,75-2,5) / 1,5+(0,75-1,5) 6+(4-16) / 4+(2,5-16) 25+(4-25) / 16+(4-16)

1 cable per clamp


main connector solid AWG 18 - 10 16 - 10 12 - 10
flexible AWG 18 - 10 14 - 4 10 - 0

2 cables per clamp


solid AWG 10+(16-10) / 12+(18-12) 10+(16-10) / 12+(18-12) 10+(12-10) / 12+12
14+(18-14) / 16+(18-16) 14+(18-14) / 16+(18-16)
flexible AWG 10+(14-10) / 12+(18-12) 4+(18-12) / 6+(18-8) 1+(12-10) / 2+(8-12)
14+(18-14) / 16+(18-16) 8+(18-8) / 10+(18-12) 3+(12-8) / 4+(10-6)

Frequency of operations z
Contactors without thermal overload relay
without load 1/h 10000 7000 7000
AC3, Ie 1/h 600 600 400
AC4, Ie 1/h 120 120 120
DC3, Ie 1/h 600 600 400

Mechanical life
AC operated S x 106 10 10 10
DC operated S x 106 10 10 10
DC-solenoid operated (KG3) S x 106 50 50 -

Short time current 10s-current A 96 120 144 176 184 240 296 450 504 592
120s-current A 42 52 58 66 80 97 110 195 203 222

Power loss per pole at Ie/AC3 400V W 0,21 0,35 0,5 0,75 0,7 1,3 2 2,2 3,9 5,5
contact resistance mOhm 2,1 1,8 1,5 1,5 1,2 1,2 1,2 1 1 1

Resistance to shock acc. to IEC 68-2-27


Shock time 20ms sine-wave NO g 10 10 10 10 8 8 8 8 8 8
NC g 6 6 6 6 - - - - - -

1) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3

60 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type K3-90 K3-115 K3-116 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200

°C -40 to +60 (+90)1) -25 to +55 (+70) 2)


°C -40 to +40 -25 to +40
°C -25 to +60 -25 to +55
°C -25 to +40 -25 to +40
°C -50 to +90 -55 to +80

A 250 250 200 250 315 400 450 500 630 630 800 1000 1000 1250

A 160 200 160 200 250 315 400 400 500 560 - - - -

A 100 125 125 160 200 250 315 - - - - - - -

busbar busbar busbar busbar busbar busbar busbar


mm² 0,5 - 95 10 - 120 18 x 4 25 x 6 30 x 5 40 x 6 50 x 8 50 x 8 50 x 10
mm² 0,5 - 70 25 - 95 screw screw screw screw screw screw screw
mm² 0,5 - 70 10 - 95 M8 M10 M12 M12 M12 M14 2 x M12

mm² 0,5 - 95 + 10 - 120


mm²
mm² 0,5 - 70 + 25 - 95

AWG 18 - 10 -
AWG 18 - 3/0 8 - 4/0

AWG -

AWG 18 - 3/0 + 8 - 4/0

1/h 3000 1200 1200 1200 300


1/h 300 - - - -
1/h 120 - - - -
1/h 300 - - - -

S x 106 5 10 5 5 5 3)
S x 106 5 10 5 5 5 3)
S x 106 - - - - -

A 680 880 920 1200 1400 1800 2200 2600 3600 4400 5600 6900 8000 9600
A 275 330 410 500 575 800 900 1000 1400 1750 2200 2600 3000 3600

W 4,8 7,9 7,9 9 11 8 11 14,9 26,3 33,3 49 59,2 60 72


mOhm 0,6 0,5 0,5 0,4 0,35 0,18 0,16 0,15

g 7 7 - - - - - - - - - - - -
g 5 5 - - - - - - - - - - - -

1) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3
2) With reduced control voltage range 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3
3) After each 1x106 operations magnetic core and built-in auxiliary contact block must be changed

D677E 61
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Auxiliary Contacts Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74

Rated insulation voltage Ui 1)


V~ 690 - -

Thermal rated current Ith to 690V


Ambient temperature 40°C A 10 (16)5) - -
60°C A 6 (12)5) - -

Utilization category AC15


Rated operational current Ie 220-240V A 3 (12)5) - -
380-415V A 2 (4)5) - -
440V A 1,6 (4)5) - -

500V A 1,2 (3)5) - -


660-690V A 0,6 (1)5) - -

Utilization category DC13


Rated operational current Ie 60V A 3,5 (8)5) - -
110V A 0,5 (1)5) - -
220V A 0,1 - -

Short circuit protection For contactors with thermal overload relay the device with the smaller admissible control
short-circuit current 1kA, fuse (contactor or thermal overload relay) determines the fuse.
contact welding not accepted
max. fuse size gL (gG) A 20 (25)5) - -

Control Circuit
Power consumption of coils
AC operated inrush VA 33-45 90-115 140-165
sealed VA 7-10 9-13 13-18
W 2,6-3 2,7-4 5,4-7

DC operated inrush W 75 140 200


double winding coil sealed W 2 2 6

DC solenoid operated inrush W 3 4 -


(KG3) sealed W 3 4 -

Operation range of coils


in multiples of control voltage Us
AC operated 0,85-1,1 0,85-1,1 0,85-1,1
DC operated 0,8-1,1 0,8-1,1 0,8-1,1

Switching time at control voltage Us ±10% 2) 3)


AC operated make time ms 8-16 10-25 12-28
release time ms 5-13 8-15 8-15
arc duration ms 10-15 10-15 10-15

DC operated make time ms 8-12 10-20 12-23


double winding coil release time ms 8-13 10-15 10-18
arc duration ms 10-15 10-15 10-15

DC solenoid operated make time ms 65 - 85 65 - 85 -


(KG3) release time ms 20 - 30 4) 20 - 30 4) -
arc duration ms 10-15 10-15 -

Cable cross-section
Auxiliary connector solid mm² 0,75-6 - -
flexible mm² 1-4 - -
flexible with multicore cable end mm² 0,75-4 - -

Magnet coil solid mm² 0,75-2,5 0,75-2,5 0,75-2,5


flexible mm² 0,5-2,5 0,5-2,5 0,5-2,5
flexible with multicore cable end mm² 0,5-1,5 0,5-1,5 0,5-1,5
Clamps per pole 2 2 2

Auxiliary connector solid AWG 18 - 10 - -


flexible AWG 18 - 10 - -

Magnet coil solid AWG 14 - 12 14 - 12 14 - 12


flexible AWG 18 - 12 18 - 12 18 - 12
Clamps per pole 2 2 2

1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request
2) Total breaking time = release time + arc duration
3) Values for delay of the release time of the make contact and the make time of the break contact will be increased, if magnet coils are protected against voltage
peaks (varistor, RC-unit, diode-unit)
4) with built-in coil suppressor 5) for contactors KG3-..A.. only

62 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type K3-90 K3-115 K3-116 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200

V~ - - - 690 690 690

A - - - 10 10 10
A - - - - - - -
- - - - - -

A - - - 3 3 3
A - - - 2 2 2
A - - - 1,5 1,5 1,5

A - - - 1,5 1,5 1,5


A - - - 1 1 1

A - - - - - -
A - - - 1 1 1
A - - - 0,5 0,5 0,5

A - - - 10 10 10

VA 165-220 350 360 800-950 1350-1600 2400


VA 2,5-5 5 5 9-11 21-25 70
W 2,5-5 5 5 9-11 21-25 70

W 250 350 360 700-850 1300-1550 2100


W 5 5 5 8-10 18-22 60

W - - - - - -
W - - - - - -

0,85-1,1 0,85-1,1 0,85-1,1 0,85-1,1 0,85-1,1


0,8-1,1 0,85-1,1 0,85-1,1 0,85-1,1 0,85-1,1

ms 20-35 30-60 40-60 50-100 50-100


ms 35-50 30-80 15-45 150-200 / 500-10001) 25-50
ms 10-15 - - -

ms 20-35 30-60 40-60 - -


ms 35-50 30-80 15-45 - -
ms 10-15 - - - -

ms - - - - -
ms - - - - -
ms - - - - -

mm² - - - 0,75-2,5 0,75-2,5


mm² - - - 0,75-2,5 0,75-2,5
mm² - - - - -

mm² 0,75-2,5 1-2,5 1-2,5 1-2,5 1-2,5


mm² 0,5-2,5 1-2,5 1-2,5 1-2,5 1-2,5
mm² 0,5-1,5 - - - -
2 2 2 2 2

AWG - - - 16 - 12 16 - 12
AWG - - - 16 - 12 16 - 12

AWG 14 - 12 16 - 12 16 - 12 16 - 12 16 - 12
AWG 18 - 12 16 - 12 16 - 12 16 - 12 16 - 12
2 2 2 2 2

1) Normal or delayed drop is adjustable

D677E 63
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K2-09 K2-12 K2-16 K2-23 K2-30 K2-37 K2-45 K2-60 K85 K110

Rated insulation voltage Ui 1)


V~ 690 690 690 690 690 690 690 690 750 750

Making capacity Ieff at Ue = 690V AC A 200 200 200 400 500 500 700 900 1100 1200

Breaking capacity Ieff 400V~ A 180 180 200 380 400 400 600 800 950 1100
K2-09 to K2-16 cosϕ = 0,65 500V AC A 150 150 180 300 370 370 500 700 850 1100
K2-23 to K3-1200 cosϕ = 0,35 690V AC A 100 100 150 260 340 340 400 500 600 600
1000V~ A - - - - - - - - - -

Utilization category AC1


Switching of resistive load
Rated operational current Ie (=Ith) A 25 25 25 45 50 50 80 100 150 170
at 40°C, open
Rated operational power 220V kW 9,5 9,5 9,5 17 19 19 30 38 57 64
of three-phase resistive loads 230V kW 10 10 10 18 20 20 31,5 40 59 67
50-60Hz, cosϕ = 1 240V kW 10,5 10,5 10,5 18,5 20,5 20,5 33 41 62 70

380V kW 16,5 16,5 16,5 29,5 33 33 52 65 98 111


400V kW 17,5 17,5 17,5 31 34,5 34,5 55 69 103 117
415V kW 18 18 18 32 36 36 57 71 107 122

440V kW 19 19 19 34 38 38 61 76 114 129


500V kW 21,5 21,5 21,5 39 43 43 69 86 130 147
660V kW 28,5 28,5 28,5 51 57 57 91 114 171 194

690V kW 29,5 29,5 29,5 53,5 60 60 95 119 179 203

Rated operational current Ie (=Ithe) A 20 25 25 35 40 40 63 80 100 125


at 60°C, enclosed
Rated operational power 220V kW 7,5 9,5 9,5 13 15 15 24 30 38 47
of three-phase resistive loads 230V kW 8 10 10 13,5 16 16 25 31,5 40 49
50-60Hz, cosϕ = 1 240V kW 8 10,5 10,5 14,5 16,5 16,5 26 33 41 52

380V kW 13 16,5 16,5 23 26 26 41 52 65 82


400V kW 13,5 17,5 17,5 24 27,5 27,5 43 55 69 86
415V kW 14 18 18 25 28,5 28,5 45 57 71 89

440V kW 15 19 19 26,5 30 30 48 61 71 95
500V kW 17 21,5 21,5 30 34 34 54 69 86 116
660V kW 22,5 28,5 28,5 40 45 45 72 91 114 142

690V kW 23,5 29,5 29,5 42 48 48 75 95 119 149


Minimum cross-section of conductor
at load with Ie (=Ith) mm² 4 4 4 10 10 10 25 35 50 70

Utilization category AC2 and AC3


Switching of three-phase motors
Rated operational current Ie 220V A 12 15 18 23 30 37 45 63 85 110
open and enclosed 230V A 11,5 14,5 17,5 23 30 37 45 61 85 110
240V A 11 14 17 23 30 37 45 60 85 110

380-400V A 10 12 16 23 30 37 45 60 85 110
415-440V A 9 12 16 23 30 37 45 60 85 110
500V A 9 12 16 23 30 30 45 55 85 110

660V A 7 9 9 17,5 21 21 33 42 60 60
690V A 6,5 8,5 8,5 17 20 20 31 40 58 58

Rated operational power 220-230V kW 3 4 5 6 8,5 11 12,5 18,5 25 33


of three-phase motors 240V kW 3 4 5 7 9 11,5 13,5 19 27 35
50-60Hz 380-400V kW 4 5,5 7,5 11 15 18,5 22 30 45 55

415V kW 4,5 6 8,5 12 16 20 24 33 49 63


440V kW 4,5 6 8,5 12 16 20 24 33 49 63
500V kW 5,5 7,5 10 15 18,5 18,5 30 37 55 55

660-690V kW 5,5 7,5 7,5 15 18,5 18,5 30 37 55 55

1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
Data for other conditions on request.

64 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K2-09 K2-12 K2-16 K2-23 K2-30 K2-37 K2-45 K2-60 K85 K110

Utilization category AC4


Switching of squirrel cage motors, inching
Rated operational current Ie 220V A 12 15 16 23 30 37 45 63 85 98
open and enclosed 230V A 11,5 14,5 16 23 30 37 45 61 85 98
240V A 11 14 16 23 30 37 45 60 85 98

380-400V A 10 12 16 23 30 37 45 60 85 85
415V A 9 12 16 21 28 37 45 60 85 85
440V A 9 12 16 21 28 37 45 60 85 85

500V A 9 12 16 17 23 23 45 55 85 85
660V A 7 9 9 13 17 17 33 42 60 60
690V A 6,5 8,5 8,5 12,5 16,5 16,5 31 40 57,5 57,5

Rated operational power 220-230V kW 3 4 5 6 8,5 11 12,5 18,5 25 30


of three-phase motors 240V kW 3 4 5 7 9 11,5 13,5 19 27 32
50-60Hz 380-400V kW 4 5,5 7,5 11 15 18,5 22 30 45 45

415-440V kW 4,5 6 8,5 11 15 20 24 33 49 49


500V kW 5,5 7,5 10 11 15 15 30 37 55 55
660-690V kW 5,5 7,5 7,5 11 15 15 30 37 55 55

Utilization category AC5a


Switching of gas discharge lamps
Rated operational current Ie
per pole at 220/230V

Fluorescent lamps, uncompensated A 20 20 20 35 40 40 65 85 100 120


Fluorescent lamps, compensated A 7 9 9 18 22 22 30 40 55 70
Fluorescent lamps, dual-connection A 22,5 22,5 22,5 41 45 45 72 90 112 144

Metal-halide lamps1), uncompensated A 12 15 15 28 30 30 50 62 85 90


Metal-halide lamps1), compensated A 7 9 9 18 22 22 30 40 55 70

Mercury-vapour lamps2), uncompensated A 22,5 25 25 41 45 45 72 90 112 144


Mercury-vapour lamps2), compensated A 7 9 9 18 22 22 30 40 55 70

Mixed light lamps3) A 20 20 20 35 40 40 65 85 100 120

Utilization category AC5b


Switching of incandescent lamps 4)
Rated operational current Ie
per pole at 220/230V A 12,5 12,5 12,5 25 31 31 43 56 69 75

Utilization category AC6a


Transformer primary switching
at inrush n 30 30 30 30 30 30 30 30 30 30
Rated operational current Ie 400V A 4,5 5,5 7,5 10,5 13,5 13,5 20 27 38 50

Rated operational power 220-230V kVA 1,8 2,2 3 4,2 5,4 5,4 8 10,7 15 20
dependent on inrush n 240V kVA 1,9 2,3 3,1 4,3 5,6 5,6 8,3 11,2 15,5 20,5
380-400V kVA 3,1 3,8 5,2 7,3 9,3 9,3 13,5 18,5 26 34

For different inrush-factors x 415-440V kVA 3,4 4,2 5,7 8 10,2 10,2 15 20,5 29 38
use the following formula: 500V kVA 3,9 4,8 6,5 9 11,5 11,5 17 23 33 43
Px=Pn*(n/x) 660-690V kVA 5,4 6,5 9 12,5 16 16 24 32 45 60

Utilization category DC1


Switching of resistive load
Time constant L/R ≤1ms
Rated operational current Ie 1 pole 24V A 20 25 25 45 50 50 80 100 150 170
60V A 20 25 25 45 50 50 80 100 150 170
110V A 6 6 6 10 10 10 12 12 20 25
220V A 0,8 0,8 0,8 1,4 1,4 1,4 1,4 1,4 2 2,5

3 poles in series 24V A 20 25 25 45 50 50 80 100 150 170


60V A 20 25 25 45 50 50 80 100 150 170
110V A 20 25 25 45 50 50 80 100 150 170
220V A 16 20 20 30 35 35 63 80 100 160

1) Metal halide lamps and sodium-vapour lamps (high- and low-pressure lamps)
2) High-pressure lamps
3) Blended lamps, containing a mercury high-pressure unit and a tungsten helix in a flourescent glass bulb (daylight lamps)
4) Current inrush approx. 16 x Ie
5) With central compensation pay attention to the current inrush (capacitor switching contactors)

D677E 65
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Main Contacts Type K2-09 K2-12 K2-16 K2-23 K2-30 K2-37 K2-45 K2-60 K85 K110

Utilization category DC3 and DC5


Switching of shunt motors
and series motors
Time constant L/R ≤15ms
Rated operational current Ie 1 pole 24V A 20 25 25 45 50 50 80 100 150 170
60V A 6 6 6 30 30 30 60 60 85 110
110V A 1,2 1,2 1,2 1,8 1,8 1,8 1,8 1,8 2 2,5
220V A 0,2 0,2 0,2 0,2 0,2 0,2 0,25 0,25 0,5 0,5

3 poles in series 24V A 20 25 25 45 50 50 80 100 150 170


60V A 20 25 25 40 40 40 80 80 100 110
110V A 20 20 20 40 40 40 80 80 100 110
220V A 2,5 2,5 2,5 4 4 4 5 5 7 8

Maximum ambient temperature


Operation open °C -40 to +60 (+90) 1)
enclosed °C -40 to +40
with thermal overload relay open °C -25 to +60
enclosed °C -25 to +40

Storage °C -50 to +90

Short circuit protection


for contactors without thermal overload relay

Coordination-type "1" according to IEC 947-4-1


Contact welding without
hazard of persons
max. fuse size gL (gG) A 63 63 63 80 80 80 160 160 250 250

Coordination-type “2” according to IEC 947-4-1


Light contact welding accepted
max. fuse size gL (gG) A 25 35 35 50 50 50 100 125 160 200

Contact welding not accepted


max. fuse size gL (gG) A 16 16 16 25 35 35 50 63 100 125
For contactors with thermal overload relay the
device with the smaller admissible backup fuse
(contactor or thermal overload relay)
determines the fuse size.

Cable cross-sections
for contactors without thermal overload relay
main connector solid or stranded mm² 0,75 - 4 1,5-10 + 1,5-6 4 - 35 2) 10 - 70 2)
flexible mm² 0,75 - 2,5 1,5-6 + 1,5-4 6 - 25 2) 10 - 70 2)
flexible with multicore cable end mm² 0,5 - 2,5 1,5-6 + 1,5-4 4 - 25 10 - 35
Cables per clamp 2 1+1 1 1

main connector solid AWG 14 - 10 14 - 10 + 14 - 10 10 10


flexible AWG 18 - 10 14 - 8 + 14 - 10 10 - 2 6-0
Cables per clamp 2 1+1 1 1

Frequency of operations z
Contactors without thermal overload relay
without load 1/h 10000 7000 7000 3000
AC3, Ie 1/h 600 600 400 300
AC4, Ie 1/h 120 120 120 120
DC3, Ie 1/h 600 600 400 300

Mechanical life
AC operated S x 106 10 10 10 5
DC operated with economy resistor S x 106 10 10 10 5

Short time current 10s-current A 96 120 144 184 240 296 360 504 680 880

Power loss per pole at Ie/AC3 400V W 0,21 0,26 0,4 0,63 1,1 1,7 1,8 3,6 4,3 6,0

Resistance to shock acc. to IEC 68-2-27


Shock time 20ms sine-wave NO g 10 10 10 8 8 8 8 8 7 7
NC g 6 6 6 5 5 5 - - 5 5

1) With reduced control voltage range 0,9 up to 1,0 x Us and with reduced rated current Ie /AC1according to Ie /AC3
2) Maximum cable cross-section with prepared conductor

66 D677E
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Auxiliary Contacts Type K2-09 K2-12 K2-16 K2-23 K2-30 K2-37 K2-45 K2-60 K85 K110

Rated insulation voltage Ui 1)


V AC 690 690 - 690

Thermal rated current Ith to 690V


Ambient temperature 40°C A 16 16 - 16
60°C A 12 12 - 12

Utilization category AC15


Rated operational current Ie 220-240V A 12 12 - 12
380-415V A 4 4 - 6
440V A 4 4 - 6

500V A 3 3 - 4
660-690V A 1 1 - 2

Utilization category DC13


Rated operational current Ie 60V A 8 8 - 8
110V A 1 1 - 1
220V A 0,1 0,1 - 0,1

Short circuit protection


short-circuit current 1kA,
contact welding not accepted
max. fuse size gL (gG) A 25 - - 25
For contactors with thermal overload relay the
device with the smaller admissible control fuse
(contactor or thermal overload relay)
determines the fuse.

Control Circuit

Power consumption of coils

AC operated inrush VA 33-45 90-115 140-165 280-350 350-420


sealed VA 7-10 9-13 13-18 16-23 23-29
W 2,6-3 2,7-4 5,4-7 4-6 6-7,3

DC operated inrush W 75 140 200 170 320


with economic circuit sealed W 2 2 6 2 4

Operation range of coils


in multiples of control voltage Us
AC operated 0,85-1,1 0,85-1,1 0,85-1,1 0,85-1,1
DC operated 0,8-1,1 0,8-1,1 0,8-1,1 0,8-1,1

Switching time at control voltage Us ±10% 2) 3)

AC operated make time ms 8-16 10-25 12-28 13-30


release time ms 5-13 8-15 8-15 8-15
arc duration ms 10-15 10-15 10-15 10-15

DC operated make time ms 8-12 10-20 12-23 20-30


with AC magnet system release time ms 8-13 10-15 10-18 10-18
arc duration ms 10-15 10-15 10-15 10-15

Cable cross-section

Auxiliary connector solid mm² 0,75-4 - - 0,75-2,5


flexible mm² 0,75-2,5 - - 0,75-2,5
flexible with multicore cable end mm² 0,5-2,5 - - 0,5-1,5

Magnet coil solid mm² 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5


flexible mm² 0,5-2,5 0,5-2,5 0,5-2,5 0,5-2,5
flexible with multicore cable end mm² 0,5-1,5 0,5-1,5 0,5-1,5 0,5-1,5

Clamps per pole 2 2 2 2

1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request
2) Total breaking time = release time + arc duration
3) Values for delay of the release time of the make contact and the make time of the break contact will be increased, if magnet coils are protected against voltage
peaks (varistor, RC-unit, diode-unit)

D677E 67
Contactors for North America
Data according to UL508
Main Contacts (cULus) Type K(G)3-10 K(G)3-14 K(G)3-18 K(G)3-22 K(G)3-24 K(G)3-32 K(G)3-40 K3-50 K3-62 K3-74

Rated operational current A 25 25 30 30 50 65 80 110 120 130


"General Use"

Motor DOL 3-phase at 60Hz


Rated operational current 600V A 10 14 18 22 22 27 34 44 52 66

Rated operational power 110-120V hp 1½ 2 2 3 5 5 7½ 10 10 10


200V hp 3 3 5 5 7½ 10 10 15 20 25
220-240V hp 3 3 7½ 7½ 10 10 15 20 25 30
277V hp 3 5 7½ 7½ 7½ 10 15 20 25 30

380-415V hp 5 5 10 10 10 15 20 25 30 40
440-480V hp 5 7½ 10 15 15 20 25 30 40 50
550-600V hp 7½ 10 15 20 20 25 30 40 50 50

Motor DOL 1-phase at 60Hz


Rated operational current 600V A 10 14 18 22 22 27 34 44 52 66

Rated operational power 110-120V hp ½ ¾ 1 1½ 1½ 2 3 3 5 7½


of AC motors 200V hp 1 1,5 2 3 3 5 7½ 7½ 10 15
at 60Hz (1ph) 220-240V hp 1½ 2 3 3 5 5 7½ 10 15 15
277V hp 2 3 3 5 5 7½ 10 10 15 15

380-415V hp 3 3 5 5 5 7½ 10 15 20 20
440-480V hp 3 5 5 7½ 7½ 10 15 20 25 25
550-600V hp 3 5 7½ 10 10 15 20 25 30 30

Motor DOL 3-phase according to ANSI A17.5


Rated operational current 600V A - - - - 15 22 - 27 37 -

Rated operational power 110-120V hp - - - - 2 3 - 3 5 -


of 3-phase motors for elevators 200V hp - - - - 3 5 - 7½ 10 -
(500.000 operations) 220-240V hp - - - - 5 7½ - 7½ 10 -

440-480V hp - - - - 10 15 - 20 25 -
550-600V hp - - - - 10 20 - 25 30 -

Rated current 2 series contacts 600V A - - - - 22 27 - 44 52 66

Fuse Class RK5 / Short-circuit current A/kA 50/5 50/5 70/5 90/5 90/5 125/5 175/5 200/5 250/5 300/5

Fuse Class T / Short-circuit current A/kA 45/100 50/100 70/100 90/100 110/100 150/100 150/100 175/100 175/100 175/100
Rated voltage V 600 600 600 600 600 600 600 600 600 600

Auxiliary Contacts (cULus) A600 A600 A600 A600 - - - - - -

Main Contacts (cULus) Type K2-09 K2-12 K2-16 K2-23 K2-30 K2-45 K2-60 K85 K110

Rated operational current A 25 25 25 40 40 72 90 125 150


"General Use"

Motor DOL 3-phase at 60Hz


Rated operational power 110-120V hp 1½ 2 2 3 5 - - 15 -
200V hp 2 3 3 5 7½ 10 15 - 30
220-240V hp 3 3 5 7½ 10 15 20 35 40

440-480V hp 5 7½ 10 15 20 30 40 65 75
550-600V hp 7½ 10 15 20 25 40 50 85 100

Motor DOL 1-phase at 60Hz


Rated operational power 110-120V hp ½ ¾ 1 1½ 2 3 5 8 10
200V hp 1 2 2 3 3 5 7½ - 20
220-240V hp 1½ 2 3 3 5 7½ 10 20 20

Fuse / Short-circuit current A/kA 30/5 40/5 50/5 60/5 110/5 175/5 175/5 - 300/5

Rated voltage V 600 600 600 600 600 600 600 600 600

Auxiliary Contacts (cULus) A600 A600 A600 A600 A600 - - A600 A600

68 D677E
Contactors for North America
Data according to UL508
Type K3-90 K3-115 K3-116 K3-151 K3-176 K3-210 K3-260 K3-316 K3-450 K3-550 K3-700 K3-860 K3-1000 K3-1200

A 160 200 150 180 220 250 300 350 420 520 700 810 - 1215

A 85 99 125 150 190 240 300 300 400 550 700 - 1000

hp 15 20 - - - - - - - - - - -
hp 25 35 30 40 50 60 75 100 125 150 200 250 - 450
hp 35 40 40 50 60 75 100 125 125 150 250 300 - 450
hp - - - - - - - - - - - - - -

hp 50 60 - - - - - - - - - - - -
hp 65 75 75 100 125 150 200 250 250 350 500 600 - 900
hp 85 100 100 125 150 200 250 300 250 350 500 600 - 900

A 86 103 125 150 - - - - - - - - -

hp 8 10 10 15 25 - - - - - - - - -
hp 15 20 20 - - - - - - - - - - -
hp 20 25 - 25 30 40 50 50 - - - - - -
hp 20 25 - - - - - - - - - - - -

hp 30 40 - - - - - - - - - - - -
hp 40 50 - - - - - - - - - - - -
hp 50 60 - - - - - - - - - - - -

A - - - - - - - - - - - - - -

hp - - - - - - - - - - - - - -
hp - - - - - - - - - - - - -
hp - - - - - - - - - - - - - -

hp - - - - - - - - - - - - - -
hp - - - - - - - - - - - - - -

A - - - - - - - - - - - - - -

A/kA 300/10 300/10 225/10 300/10 350/10 400/18 500/18 500/18 1200/18 1200/18 2000/30 2000/30 - 2000/42

A/kA 300/100 3) 300/100 3) - - - - - - - - - - - -


V 600 600 600 600 600 600 600 600 600 600 600 600 - 600

- - - - - - - - A600 A600 A600 A600 - A600

Main Contacts (cULus) Type K3-18NK K3-24K K3-32K K3-50K K3-62K K3-74K K3-90K K3-115K

Rated operational power


of 3-phase capacitor banks 110-120V kVAr 0-3,5 3-5,5 3-7 6,5-10 6,5-15 6,5-18 1) 10-24 10-28 2)
at 60Hz (3ph) 200V kVAr 0-6 4,5-10 4,5-12,5 10-16,7 10-25 10-32 1) 17-40 17-46 2)
220-240V kVAr 0-7 5,5-11 5,5-15 12,5-20 12,5-30 12,5-36 1) 20-47 20-56 2)

440-480V kVAr 0-15 11,5-25 11,5-30 25-40 25-60 25-72 1) 40-95 40-114 2)
550-600V kVAr 0-18 14,5-30 14,5-35 31-50 31-75 31-90 1) 50-120 50-143 2)

Fuse Class RK5 / Short-circuit current A/kA 70/5 90/5 125/5 200/5 250/5 300/5 300/10 300/10

Fuse Class T / Short-circuit current A/kA 80/100 110/100 150/100 175/100 175/100 175/100 300/100 3) 300/100 3)
Rated voltage V 600 600 600 600 600 600 600 600

Auxiliary Contacts (cULus) A600 - - - - - - -

1) Consider the max. thermal current of the contactor K3-74A: Ith 130A
2) Consider the min. cross-section of conductor at max. load
3) Class T and Class RK1

D677E 69
Contactors
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Contact Life

For selection of the suitable contactor-type according to supply voltage, For contactors frequently used under AC3/AC4-mixed service conditions
power rating and application (utilization category AC1, AC3 or AC4) use calculate contact life with the formula:
contact life characteristic diagram.
For the most common supply voltages four scales of power ratings Pn are AC3
M=
%AC4 AC3
provided for each utilization category.
Select contactor-type according to utilization category AC3 (breaking
1+
100
x( AC4
-1 )
current Ia = Ie) using the motor rating scales to the right, according to M = Contact life (switching cycles) for AC3/AC4-mixed operations
utilization category AC4 (breaking current Ia = 6 x Ie) using the motor rating AC3 = Contact life (switching cycles) for AC3 operations (normal switching conditions).
scales to the left. 1) Breaking current Ia = rated motor current In.
AC4 = Contact life (switching cycles) for AC4 operations (inching).
Select contactor-type according to utilization category AC1 (breaking Breaking current Ia= multiples of rated motor current In.
current Ia = Ie/AC1) using the breaking current scale. 1) %AC4 = Percents of AC4-operations related to the total cycles.

Motor Rating Motor Rating Breaking Current


Pn = AC4 Pn = AC3 Ia ( = Ie = AC1)
A

Millions of Operations

Motor Rating Motor Rating Breaking Current


Pn = AC4 Pn = AC3 Ia ( = Ie = AC1)
A

Millions of Operations

1) Pay attention to the approved rated values of the selected contactor according to the national approvals

70 D677E
Contactors
Utilization Categories
For easier choice of devices and in order to make the comparison control circuit devices and switching elements according to
of different products simplier are utilization categories for contactors IEC 947-5-1 and VDE 0660 Part 200 determind. The table offers different
and motor-starters according to IEC 947-4-1 and VDE 0660 Part 102, for utilization categories, typical applications and assorted test conditions.

Type of Cate- Typical applications Rated Test conditions for the number of Test conditions for
current gory operational on-load operating cycles making and breaking capacities
current Make Break Make Break
I/Ie U/Ue cosϕ Ic/Ie Ur/Ue cosϕ I/Ie U/Ue cosϕ Ic/Ie Ur/Ue cosϕ
Alter- Non-inductive or
nating AC1 slightly inductive loads all values 1 1 0,95 1 1 0,95 1,5 1,05 0,8 1,5 1,05 0,8
Current resistance furnaces
Slip-ring motors:
AC2 starting, switching off all values 2,5 1 0,65 2,5 1 0,65 4 1,05 0,65 4 1,05 0,65

Squirrel-cage motors: Ie≤ 17A 6 1 0,65 1 0,17 0,65 10 1,05 0,45 8 1,05 0,45
AC3 starting, switching off 17A< Ie≤ 100A 6 1 0,35 1 0,17 0,35 10 1,05 0,45 8 1,05 0,45
motors during running Ie> 100A 6 1 0,35 1 0,17 0,35 10 1,05 0,35 8 1,05 0,35
Squirrel-cage motors: Ie≤ 17A 6 1 0,65 6 1 0,65 12 1,05 0,45 10 1,05 0,45
AC4 starting, plugging, 17A< Ie≤ 100A 6 1 0,35 6 1 0,35 12 1,05 0,45 10 1,05 0,45
inching Ie> 100A 6 1 0,35 6 1 0,35 12 1,05 0,35 10 1,05 0,35
Switching of electric
AC5a discharge lamp controls all values - - - - - - 3 1,05 0,45 3 1,05 0,45

Switching of
AC5b incandescent lamps all values - - - - - - 1,5 1,05 1)
4 1,05 1)

Switching of
AC6a transformers Ie≤ 100A - - - - - - 4,5 1,05 0,45 3,6 1,05 0,45
Ie> 100A - - - - - - 4,5 1,05 0,35 3,6 1,05 0,35
Switching of
AC6b capacitors - - - - - - - 2) 2)

Slightly inductive loads


AC7a in household appliances all values - - - - - - 1,5 1,05 0,8 1,5 1,05 0,8
and similar applications
Motor loads
AC7b for household applications Ie≤ 100A - - - - - - 8 1,05 0,45 6 1,05 0,45
Ie> 100A - - - - - - 8 1,05 0,35 6 1,05 0,35
Hermetic refrigerant compressor
AC8a motor control with manual Ie≤ 100A - - - - - - 6 1,05 0,45 6 1,05 0,45
resetting of overload releases Ie> 100A - - - - - - 6 1,05 0,35 6 1,05 0,35
Hermetic refrigerant compressor
AC8b motor control with automatic Ie≤ 100A - - - - - - 6 1,05 0,45 6 1,05 0,45
resetting of overload releases Ie> 100A - - - - - - 6 1,05 0,35 6 1,05 0,35
Control of resistive loads and
AC12 solid state loads with all values - - - - - - 1 1 0,9 1 1 0.9
isolation by opto couplers
Control of
AC13 solid state loads with all values - - - - - - 10 1,1 0,65 1,1 1,1 0,65
transformer isolation
Control of
AC14 small electromagnetic loads - - - - - - - 6 1,1 0,7 6 1,1 0,7
(≤72VA)
Control of
AC15 electromagnetic load - 10 1 0,7 1 1 0,4 10 1,1 0,3 10 1,1 0,3
(>72VA)
Make L/R Break L/R Make L/R Break L/R
I/Ie U/Ue [ms] Ic/Ie Ur/Ue [ms] I/Ie U/Ue [ms] Ic/Ie Ur/Ue [ms]
Direct Non-inductive or
Current DC1 slightly inductive loads all values 1 1 1 1 1 1 1,5 1,05 1 1,5 1,05 1
resistance furnaces
Shunt-motors:
DC3 starting, plugging, inching all values 2,5 1 2 2,5 1 2 4 1,05 2,5 4 1,05 2,5
dynamic braking of d.c. motors
Series-motors:
DC5 starting, plugging, inching all values 2,5 1 7,5 2,5 1 7,5 4 1,05 15 4 1,05 15
dynamic braking of d.c. motors
Switching of
DC6 incandescent lamps all values - - - - - - 1,5 1,05 1)
4 1,05 1)

Control of resistive loads and


DC12 solid state loads with all values - - - - - - 1 1 1 1 1 1
isolation by opto couplers
Control of
DC13 electromagnets all values 1 1 ≤300 1 1 ≤300 1,1 1,1 ≤300 1,1 1,1 ≤300

Control of
DC14 electromagnetic loads having all values - - - - - - 10 1,1 15 10 1,1 15
economy resistors in circuit
Ue Rated operational voltage, U Voltage before make, U r Recovery voltage, Ie Rated operational current, I Current make, Ic Current broken
1) Test with incandescent lamps
2) Test conditions according to standard

D677E 71
Accessories
Data according to IEC 947-4-1, EN 60947-4-1, VDE 0660
Type HN HTN HA HB HKT HKF K2-DK K2-TP K2-L 2)
HKA HKB K2-SK

Rated insulation voltage Ui 1)


V AC 690 690 690 690 690 690 690 690 690

Thermal rated current Ith to 690V


Ambient temperature max. 40°C A 10 10 25 10 10 16 26 10 10
max. 60°C A 6 6 20 6 - - - - 6

Frequency of operations z 1/h 3000 - 3000 3000 - - - 1200 3000


Mechanical life S x 106 10 10 10 10 - - - 1 10

Power loss per pole at Ie/AC1 W 0,5 0,5 1,5 0,5 - - -

Utilization category AC15


Rated operational 220-240V A 3 3 6 3 3 3 - 4 3
current Ie 380-400V A 2 2 3 2 2 2 - 3 2
440V A 1,6 1,6 2 1,6 1,5 1,5 - 2 1,6

500V A 1,2 1,2 2 1,2 1,5 1,5 - 2 1


660-690V A 0,6 0,6 1 0,6 1 1 - 2 0,5

Utilization category DC13


Rated operational 60V A 2 2 8 2 - - - 2,5 2
current Ie 110V A 0,4 0,4 1 0,4 0,5 0,5 - 1,5 0,4
220V A 0,1 0,1 0,1 0,1 0,2 0,2 - 0,2 0,1

Short circuit protection


short-circuit current 1kA,
contact welding not accepted
max. fuse size gL (gG) A 20 20 25 20 10 10 - 10 10

For contactors with thermal overload relay or


auxiliary contacts the device with the smaller
admissible control fuse (contactor or thermal
overload relay) determines the fuse size.

Cable cross-sections
solid or stranded mm² 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 1-2,5 0,75-2,5
flexible mm² 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5 0,75-2,5
flexible with multicore cable end mm² 0,5-1,5 0,5-1,5 0,5-1,5 0,5-1,5 0,5-1,5 0,5-1,5 0,75-2,5 0,5-1,5

solid AWG 14 - 12 14 - 12 14 - 12 14 - 12 14 - 12 14 - 12 14 - 12 14 - 12 14 - 12
flexible AWG 18 - 12 18 - 12 18 - 12 18 - 12 18 - 12 18 - 12 18 - 12 18 - 12 18 - 12

Cables per clamp 2 2 2 2 2 2 2 2

Data according to CSA, UL and CUL


Type HN HTN HA HB.. HKT, HKA K2-DK K2-TP K2-L 2)
HKF K2-SK

Rated operational current A 10 10 16 10 10 - 10 -


"General Use"
Rated operational voltage max. V AC 600 600 600 600 600 - 600 600

Auxiliary Contacts A600 A600 A600 A600 A600 - A600 Intermittent


duty

1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request.
2) Command duration min. 30ms, 10% duty cycle, max. 30 eec.

72 D677E
Contactors and Accessories
Wiring diagrams
Auxiliary contact blocks Snap-on momentary contact blocks

HN10 HN01 HN10U HN01U HTN10 HTN01


HA10 HA01

HKS11 HB11 HB02 HKT11 HB11, HB02:


HKA11 Correct terminal marking
is given by mounting.

HKF22 HKT22

Indicator units

Electronic timer Coil current indicator Voltage indicator

K3-T180 240 K2-ING K2-UN


K2-INR K2-UNR

red

red

Latch Fuse holder Interface


with rectifier

K2-L.. K2-F K2-RF1 K2-IM


K2-RF3

red black Colours mentioned in


wiring diagram refer
to the outgoing
connection wires
of the device.

Regulation of switch position of aux. contakt block HKF22 for contactors K3-450 to K3-860

state of delivery NO/NC overlapped NO delayed


HKF22 NC NC NC

HKF22 NO NO NO

Contactor position:
18 16 14 12 10 8 6 4 2 0 open 18 16 14 12 10 8 6 4 2 0 18 16 14 12 10 8 6 4 2 0

Standard position of regulation screw Regulation screw position (unscrew by 4 turns) Regulation screw position (screw by 4 turns)

D677E 73
Contactors
Dimensions
AC operated DC operated

K3-10N.. KG3-10..
K3-14N.. KG3-14..
K3-18N.. KG3-18..
K3-22N.. KG3-22..

1)

K3-24.. KG3-24..
K3-32.. KG3-32..
K3-40.. KG3-40..

K3-50.. K3-50..=
K3-62.. K3-62..=
K3-74.. K3-74..=

AC and DC operated

K3-90..
K3-115..

1) Minimum side distance to


conductive parts for coil voltage:
500V Uimp=6kV 2mm
660-690V Uimp=8kV 4,5mm

74 D677E
Contactors
Dimensions
AC operated, DC operated

K3-151..
K3-176..

HKA11 HKT..

K3-210..
K3-260..
K3-316..

HKA11 HKT..

K3-450..
K3-550..

Typ A B C H N

K3-450 40 10,5 4 233 206


K3-550 40 12,5 6 258 228

D677E 75
Contactors
Dimensions
AC and DC operated

K3-700..
K3-860..

Typ B H N

K3-700 13 310 277


K3-860 15 361 325

K3-1000..
K3-1200..
1) for K3-1200 in UL conformity application only

Capacitor switching contactors, AC operated

K3-18NK.. K3-24K..
K3-32K..

K3-50K.. K3-90K..
K3-62K.. K3-115K..
K3-74K..

76 D677E
Contactors
Dimensions
Contactors DC operated

K3-10N..= K3-24..=
K3-14N..= K3-32..=
K3-18N..= K3-40..=
K3-22N..=

Contactors 4-pole, AC operated

K3-10NA00-40 K2-23A00-40
K3-14NA00-40 K2-30A00-40
K3-18NA00-40 K2-37A00-40
K3-22NA00-40

Contactors 4-pole, AC operated

K2-45A00-40 K3-116A00-40
K2-60A00-40 K3-151A00-40
K3-176A00-40

Contactors 4-pole, AC and DC operated

K3-210A00-40
K3-260A00-40
K3-316A00-40

D677E 77
Contactors
Dimensions Accessories
Aux. cont. blocks, terminal blocks Snap-on momentary cont. blocks Auxiliary contact blocks

HN10, HN01 K2-SK, K2-DK HTN10, HTN01 HA10, HA01 HB11, HB02

4. pole for contactors K3-200 to K3-1200

Type A B C D E F G H

NP175 223 148 26 52 98 5 122 M8


NP350 223 148 26 52 98 5 122 M8

NP325 262 148 26 55 116 5 122 M10


NP500 294 220 53 72 138 5 152 M12
NP760 294 220 53 72 138 5 152 M12

NP501 348 220 53 73 145 5 152 M12


NP1000 348 220 53 73 145 8 152 M12

NP1001 410 220 53 110 157 8 152 M12

Electronic timer Electronic timer on-delay Electronic timer off-delay

K3-T180 240 K2-TE.. K2-TA..

78 D677E
Contactors
Dimensions Accessories
Mechanical interlocks

Type Contactor 1 Contactor 2 A1 A2 A3 B1 B2 C1 C2 C3 D1 D2

LG10889 K3-07 to K3-40 K3-07 to K3-40 45 7 45 50 50 35 17 35 4,5 4,5


LG10889 KG3-07 to KG3-22 KG3-07 to KG3-22 45 7 45 80 50 35 17 35 4,5 4,5
LG10889 KG3-24 to KG3-40 KG3-22 to KG3-40 45 7 45 80 50 35 17 35 4,5 4,5

LG10890 K3-50 to K3-74 K3-24 to K3-40 60 12 55 100 65 50 22 45 5,5 4,5


LG10890 K3-50 to K3-74 K3-50 to K3-74 60 12 60 100 100 50 22 50 5,5 5,5

LG11478 K3-90 bis K3-115 K3-90 bis K3-115 90 12 90 100 100 75 27 75 5,5 5,5

LG8511 K65 - K110 K65 - K110 90 12 90 100 100 75 27 75 6 6

LG11223H K3-151, -176 K3-151, -176 110 30 110 130 130 100 40 100 6 6 3-pole contactor
LG11223H K3-116,-151, -176 K3-116,-151, -176 147 30 147 130 130 135 42 135 6 6 4-pole contactor

LG11223H K3-210, -260, -316 K3-210, -260, -316 145 30 145 160 160 120 55 120 6 6 3-pole contactor
LG11223H K3-210, -260, -316 K3-210, -260, -316 193 30 193 160 160 170 55 170 6 6 4-pole contactor

LG10400H K3-450, K3-550 K3-450, K3-550 220 42 220 220 220 110 152 110 9 9
LG10402H K3-700, -860 K3-700, -860 280 32 280 280 280 175 137 175 11 11

LG10403H K3-1000, -1200 K3-1000, -1200 334 46 334 380 380 120 260 120 13,5 13,5
LG10399H K3-450, -550 K3-700, -860 220 37 280 220 280 110 144,5 175 9 11
LG10401H K3-700, -860 K3-1000, -1200 280 73 334 280 380 175 232,5 120 11 13,5

LG10400V, LG10402V LG10399V LG10403V, LG10401V

Type Contactor 1 Contactor 2 A A1 B1 B2 B3 C1 C2 C3 C4 D1 D2

LG10400V K3-315 - K3-550 K3-315 - K3-550 250 134 220 94 220 110 110 - - 9 9
LG10402V K3-700, -860 K3-700, -860 302 162 280 200 280 175 175 - - 11 11

LG10403V K3-1000, -1200 K3-1000, -1200 - - 380 280 380 120 120 - - 13,5 13,5
LG10399V K3-450, -550 K3-700, -860 302 - 220 150 280 110 175 51 74,5 9 11
LG10401V K3-700, -860 K3-1000, -1200 - - 280 240 380 175 120 - - 11 13,5

D677E 79
Contactors
Dimensions Accessories
Latch

K2-L..

Contactors with additional terminals

LG9339N (2 x 3 pieces)
for K3-10N. to K3-22N.

Indicator units Fuse holder Fuse holder with rectifier

K2-ING, K2-INR K2-RF K2-RF1


K2-UN, K2-UNR K2-RF3

80 D677E
Contactors
Dimensions Accessories
Interface Snap-on adapter

K2-IM K2-SM

Suppressor units

RC-K3N .. RC-K3NW ..

Marking systems

marking label
P487-1 or P245-.

D677E 81
Contactors
Position of terminals
K3-10ND10 K3-10ND01 K3-24A00, K3-24K00 K3-50A00, K3-50K00 K3-10NA00-40 K85A22
K3-14ND10 K3-14ND01 K3-32A00, K3-32K00 K3-62A00, K3-62K00 K3-14NA00-40 K110A22
K3-18ND10 K3-18ND01 K3-40A00 K3-74A00, K3-74K00 K3-18NA00-40
K3-22ND10 K3-22ND01 K3-22NA00-40
K3-18NK10 K3-18NK01 K2-23A00-40 bis
K2-60A00-40

K3-116A00-40
K3-90A00 K3-151A00 K3-151A00-40 K3-450A22 K3-1000A12
K3-115A00 K3-176A00 K3-176A00-40 K3-550A22 K3-1200A12
K3-210A00 K3-210A00-40 K3-700A22
K3-260A00 K3-260A00-40 K3-860A22
K3-316A00 K3-316A00-40

KG3-10A10 KG3-10A01 KG3-10A00-40 KG3-24A00


KG3-14A10 KG3-14A01 KG3-14A00-40 KG3-32A00
KG3-18A10 KG3-18A01 KG3-18A00-40 KG3-40A00
KG3-22A10 KG3-22A01 KG3-22A00-40

K3-10ND10= K3-10ND01= K3-24A00= K3-50A00= K85A21= K3-1000A12=


K3-14ND10= K3-14ND01= K3-32A00= K3-62A00= K110A21= K3-1200A12=
K3-18ND10= K3-18ND01= K3-40A00= K3-74A00=
K3-22ND10= K3-22ND01=

1) Type-suffux "EUR" with additional coil terminal


Ordering example: K3-10A10EUR 230

82 D677E
Motor Starters

Star-Delta Starters Open Type 84

Star-Delta Starters Enclosed 86


Enclosure for Star-Delta Starters 86

Accessories 87

Reversing Contactors 88

Pole Changing Starters 90

Technical Data 92

Wiring Diagrams 95

Dimensions 99

D677E 83
Star-Delta Starters Open Type AC Operated

Ratings Rated order separately Type Coil voltage 1)


AC3 Current 230 220-240V 50Hz
380V 400 380-415V 50Hz
400V 660V AC3 Overload Relay ⏐
415V 500V 690V 400V ⏐ Pack Weight
kW kW kW A Type W pcs. kg/pc.

7,5 7,5 11 16 U3/32 K3NY15 . . . 1 0,9


U12/16E K3

15 18,5 15 30 K3NY26 . . . 1 0,9

22 30 22 45 U3/42 K3Y40 . . . 1 1,4

30 37 30 60 K3Y52 . . . 1 1,8

45 55 45 85 U3/74 K3Y80 . . . 1 3,5

55 75 55 109 K3Y100 . . . 1 3,7

75 90 90 150 U85 K3Y140 . . . 1 6,6

110 132 110 205 K3Y200 . . . 1 7

132 160 160 240 U180 K3Y240 . . . 1 15

160 180 180 300 K3Y300 . . . 1 15

Star-delta starters are wired to accept thermal overload relay. The thermal overload relay has to be ordered separately.
For full load current setting use the YD-dial of thermal overload relay.

Ordering Example: Star-Delta Starter, open type, rated AC3 at 400V 205A
rated control voltage 230V 50Hz - Order Type: K3Y200 230 + U85 120

Thermal Overload Relays


Rated Motor Current Type Pack Weight
A pcs. kg/pc. Wiring Diagram

For Star-Delta Starters K3NY15.. to K3Y40..


7 - 10,5 U12/16E 6 K3 1 0,10
10,5 - 15,5 U12/16E 9 K3 1 0,10
14 - 19 U12/16E 11 K3 1 0,10

18 - 24 U12/16E 14 K3 1 0,10
23 - 31 U12/16E 18 K3 1 0,10
manual eset

For Star-Delta Starters K3NY15.. to K3Y52..


7 - 10,5 U3/32 6 1 0,14
10,5 - 15,5 U3/32 9 1 0,14
14 - 19 U3/32 11 1 0,14

18 - 24 U3/32 14 1 0,14
23 - 31 U3/32 18 1 0,14
30 - 41 U3/32 24 1 0,14 manual and
auto reset
40 - 55 U3/32 32 1 0,14

For Star-Delta Starters K3Y40.., K3Y52..


24 - 35 U3/42 20 1 0,30
35 - 48 U3/42 28 1 0,30
48 - 73 U3/42 42 1 0,30
manual and
auto reset
1) Coil voltage range and other coil voltages see page 82

84 D677E
Components for Combinations Auxiliary Contacts Free Space for
Line Delta Star Electronic Mechanical Star-Delta Built-in for use Aux. Contact Blocks
Contactor Contactor Contactor Timer Interlock Starter on Contactor on Contactor
between Connector Line Delta Star Line Delta Star
K1 K2 K3 K4 K2 and K3 K1 K2 K3 K1 K2 K3
Type Type Type Type Type Type NO/NCNO/NCNO/NC HN.. or HA..

K3-10ND01 K3-10ND01 K3-10ND10 Y9A LG10889 K3NY-VB10 - - - 3 4 2


+ HN10 + HN10 + HN01

K3-18ND01 K3-18ND01 K3-14ND10 Y9A LG10889 K3NY-VB10 - - - 3 4 2


+ HN10 + HN10 + HN01

K3-24A00 K3-24A00 K3-24A00 Y9A LG10889 K3Y-VB24 - - - 2 3 1


+ HN10 + HN01 + HN01 + 2HN10 + HN01

K3-32A00 K3-32A00 K3-24A00 Y9A LG10889 K3Y-VB24 - - - 2 3 1


+ HN10 + HN01 + HN01 + 2HN10 + HN01

K3-50A00 K3-50A00 K3-32A00 Y9A LG10890 - - - - 2 3 1


+ HN01 + HN10 + HN01 + 2HN10 + HN01

K3-62A00 K3-62A00 K3-50A00 Y9A LG10890 - - - - 2 3 1


+ HN01 + HN10 + HN01 + 2HN10 + HN01

K3-90A00 K3-90A00 K3-90A00 Y9AL LG11478 - - - - 5 6 4


+ HN01 + HN10 + HN01 + 2HN10 + HN01

K3-115A00 K3-115A00 K3-90A00 Y9AL LG11478 - - - - 5 6 4


+ HN01 + HN10 + HN01 + 2HN10 + HN01

K3-151A00 K3-151A00 K3-151A00 Y9AL LG11223H - - 1/- -/1 2 1 1


+ HKT11 + HKT11 + HKT22

K3-176A00 K3-176A00 K3-151A00 Y9AL LG11223H - - 1/- -/1 2 1 1


+ HKT11 + HKT11 + HKT22

Applications Time setting

The star-delta starting method is only practicable in such cases where the The transition from start (star configuration) to normal operation (delta
motor windings are connected in delta configuration for normal operation configuration) should be after the motor achieves practically full rotational
and the torque which is needed during the starting period is not higher speed. The use of star-delta timer Y9A with a dwell period of approx. 25ms
than approx. 30% of the rated torque. The starting current drawn from the provides a careful operation of motor and drive equipment.
line will be approx. 2 to 2,7 times the rated motor current.

Thermal Overload Relays


Rated Motor Current Type Pack Weight
A pcs. kg/pc. Wiring Diagram

For Star-Delta Starters K3Y80.., K3Y100..


35 - 48 U3/74 28 1 0,40
48 - 73 U3/74 42 1 0,40
70 - 90 U3/74 52 1 0,40

90 -112 U3/74 65 1 0,40 manual and


auto reset

For Star-Delta Starters K3Y140.., K3Y200..


104 -156 U85 90 1 0,90
140 -207 U85 120 1 0,90 manual eset

For Star-Delta Starters K3Y240.., K3Y300..


208 - 312 U180 180 1 1,5

manual and
auto reset

D677E 85
Star-Delta Starters Enclosed Type AC Operated

Ratings Rated Optional Wired Type Coil voltage 1)


AC3 Current Extras to accept 230 220-240V 50Hz
380V Overload 400 380-415V 50Hz
400V 660V AC3 Relay ⏐
415V 500V 690V 400V ⏐ Pack Weight
kW kW kW A Type W pcs. kg/pc.

Plastic Enclosed
Enclosed, protected to IP65
15 18,5 15 30 ST U3/32 K3NY26P . . . 1 1,8

22 30 22 45 ST, H U3/42 K3Y40P . . . 1 3,8

30 37 30 60 ST, H K3Y52P . . . 1 4,2

45 55 45 85 ST, H U3/74 K3Y80P . . . 1 5,9

55 75 55 109 ST, H K3Y100P . . . 1 8,7

Sheet Steel Enclosed


Enclosed, protected to IP54
15 18,5 15 30 ST, H U3/32 K3NY26B . . . 1 4,8

22 30 22 45 ST, H U3/42 K3Y40B . . . 1 4,8

30 37 30 60 ST, H K3Y52B . . . 1 5,2

45 55 45 85 ST, H U3/74 K3Y80B . . . 1 15

55 75 55 109 ST, H K3Y100B . . . 1 15

75 90 90 150 ST, H U85 K3Y140B . . . 1 22

110 132 110 205 ST, H K3Y200B . . . 1 22

1) Coil voltage range and other coil voltages see page 82

Type-suffix for optional extras


Start-Stop Push Buttons . . . . . . .T . . .
Selector Switch . . . . . . .W . . .
Typical wiring diagrams see page 86

Control Circuit Fuse <250V (1 piece) . . . . . . .ST . . .


>250V (2 pieces) . . . . . . .ST . . .
Run Hour Meter . . . . . . .H . . .

Ordering Example: Star-Delta Starter, steel sheet enclosed, with selector switch and run hour meter
rated AC3 at 400V 82A, rated control voltage 230V 50Hz - Order Type: K3Y80BWH 230 + U3/74 52

Enclosures for Star Delta Starter


accept Type Pack Weight
for Starter Overload Relay pcs. kg/pc.

Plastic IP65
K3NY15, K3NY26 U3/32 K3Y26P-G3 1 1,0
K3Y40, K3Y52 U3/42, U3/32 K3Y40/52P-G3 1 2,4

Sheet Steel IP54


K3NY15, K3NY26 U3/32 K3Y26B-G3 1 3,4
K3Y40, K3Y52 U3/42, U3/32 K3Y40/52B-G3 1 3,4

86 D677E
Star-Delta Starter Connector

For Star-Delta Starter Types Type Pack Weight


pcs. kg/pc.

K3NY15, K3NY26 K3NY-VB10 1 0,02


K3Y40, K3Y52 K3Y-VB24 1 0,03

Additional Terminals

For Star-Delta Starter Types Cable Type Pack Weight


Line Conn. Motor Conn. cross-section
Line Contactor Overload Relay mm² pcs. kg/pc.

Single pole with Fingertouch Protection

K3NY15, K3NY26 U12/16 0,75 - 10 solid LG9339 6 0,009


0,75 - 6 flex.

Three-pole with Fingertouch Protection

U3/42 4 - 35 strand. LG7559 1 0,052


4 - 25 flex.

Electronic Timers for Star-Delta Starters1)


Rated Control Time Range Delay Time Rated Current AC15 Type Pack Weight
Voltage 230V 400V
V s ms A A pcs. kg/pc.

24 - 60V AC 1 - 20 20 - 25 6 4 Y9A 60 1 0,075


110 - 415V AC 1 - 20 20 - 25 6 4 Y9A 415 1 0,075

24 - 60V~ 1 - 20 40 - 80 6 4 Y9AL 60 1 0,075


110 - 415V~ 1 - 20 40 - 80 6 4 Y9AL 415 1 0,075

Time repeat accuracy ± 1% Power consumption at 24V 0,2VA


60V 5VA
Minimum interval between operations 2s
220-240V 2VA
Short circuit protection 4A gl (gG) 380-415V 7VA

1) not suitable for contactors K3-450 - K3-1200

Mounting Bar
Specification Type Pack Weight
pcs. kg/pc.

For screw mounting of electronic timer Y9.. LG7735 10 0,09

Star-Delta Starters in Special Versions


Starters for Longer Starting Time
For longer starting times the thermal overload relay is mounted on delta-contactor. The motor is not protected in
Y-connection. The timer used for this starter-type is the type Y91A, time range is 10 to 60s.
Principal wiring diagram see page 86.

Ordering Example: K3YL


L52 230

Starters with two Thermal Overload Relays on request


Basic circuit diagram see page 86

D677E 87
Reversing Contactors with Mechanical Interlock AC Operated

Ratings Rated Wired Type Coil voltage 1)


AC3 Current to accept 110 110V 50Hz
380V Overload 230 220-240V 50Hz
400V 660V AC3 Relay 400 380-415 50Hz
415V 500V 690V 400V page 102 ⏐ Pack Weight>
kW kW kW A Type W pcs. kg/pc.

Open Type
4 5,5 5,5 10 U3/32 K3NWU10 . . . 1 0,6
U12/16E K3

7,5 10 7,5 18 K3NWU18 . . . 1 0,6

11 15 15 24 U3/42 K3WU24 . . . 1 1,2

15 18,5 18,5 32 K3WU32 . . . 1 1,4

22 30 30 50 U3/74 K3WU50 . . . 1 2,5

30 37 37 62 K3WU62 . . . 1 2,5

37 45 45 74 K3WU74 . . . 1 2,5

Sheet Steel Enclosed, protected to IP54


4 5,5 5,5 10 U3/32 K3NWU10B . . . 1 3,9

7,5 10 7,5 18 K3NWU18B . . . 1 4,1

11 15 15 24 U3/42 K3WU24B . . . 1 4,5

15 18,5 18,5 32 K3WU32B . . . 1 4,7

22 30 30 50 U3/74 K3WU50B . . . 1 7,1

30 37 37 62 K3WU62B . . . 1 7,1

Reversing Starter Connector

For Reversing Starter Types Type Pack Weight


pcs. kg/pc.

K3NWU10, K3NWU18 K3NW-VB10 1 0,02


K3WU24, K3WU32 K3W-VB24 1 0,025

1) Other coil voltages see page 39

88 D677E
Components for Combinations Auxiliary Contacts Free Space for
Left Hand Side Right Hand Side Mechanical Reversing Built-in for use Aux. Contact Blocks
Contactor Contactor Interlock Starter on Contactor on Contactor
Connector
K1 K2 K1 K2 K1 K2
Type Type Type Type NO/NC NO/NC HN.. or HA..

K3-10ND10 K3-10ND10 LG10889 K3NW-VB10 - - 3 3


+ HN01 + HN01

K3-18ND10 K3-18ND10 LG10889 K3NW-VB10 - - 3 3


+ HN01 + HN01

K3-24A00 K3-24A00 LG10889 K3W-VB24 - - 2 2


+ HN10 + HN01 + HN10 + HN01

K3-32A00 K3-32A00 LG10889 K3W-VB24 - - 2 2


+ HN10 + HN01 + HN10 + HN01

K3-50A00 K3-50A00 LG10890 - - - 2 2


+ HN10 + HN01 + HN10 + HN01

K3-62A00 K3-62A00 LG10890 - - - 2 2


+ HN10 + HN01 + HN10 + HN01

K3-74A00 K3-74A00 LG10890 - - - 2 2


+ HN10 + HN01 + HN10 + HN01

K3-10ND10 K3-10ND10 LG10889 K3NW-VB10 - - 3 3


+ HN01 + HN01

K3-18ND10 K3-18ND10 LG10889 K3NW-VB10 - - 3 3


+ HN01 + HN01

K3-24A00 K3-24A00 LG10889 K3W-VB24 - - 2 2


+ HN10 + HN01 + HN10 + HN01

K3-32A00 K3-32A00 LG10889 K3W-VB24 - - 2 2


+ HN10 + HN01 + HN10 + HN01

K3-50A00 K3-50A00 LG10890 - - - 2 2


+ HN10 + HN01 + HN10 + HN01

K3-62A00 K3-62A00 LG10890 - - - 2 2


+ HN10 + HN01 + HN10 + HN01

D677E 89
Reversing Contactors for North America AC Operated

Ratings Rated Wired Type Coil voltage 1)


AC3 Current to accept 230 220-240V 50Hz
380V Overload 400 380-415V 50Hz
400V 660V AC3 Relay ⏐
415V 500V 690V 400V page 102 ⏐ Pack Weight>
kW kW kW A Type W pcs. kg/pc.

Open Type
4 5,5 5,5 10 U3/32 KNW3-10 . . . 1 0,6
U12/16E K3

7,5 10 10 18 KNW3-18 . . . 1 0,6

11 15 15 24 U3/42 KW3-24 . . . 1 1,2

15 18,5 18,5 32 KW3-32 . . . 1 1,4

18,5 18,5 18,5 40 KW3-40 . . . 1 1,4

Pole Changing Starters AC Operated

Ratings Rated Wired Type Coil voltage 1)


AC3 at Current to accept 230 220-240V 50Hz
380V Overload 400 380-415V 50Hz
400V 660V AC3 Relay ⏐
415V 500V 690V 400V page 102 ⏐ Pack Weight>
kW kW kW A Type W pcs. kg/pc.

Open Type
7,5 10 10 18 2 x U3/32 K3NPU18 . . . 1 1,0
2 x U12/16E K3

11 15 15 24 K3NPU24 . . . 1 1,5

15 18,5 18,5 32 2 x U3/32 K3PU32 . . . 1 1,9

22 30 30 50 2 x U3/74 K3PU50 . . . 1 3,9

30 37 37 62 K3PU62 . . . 1 3,9

Sheet Steel Enclosed


Enclosed, protected to IP54
7,5 10 7,5 18 2x U3/32 K3NPU18B . . . 1 1,0

11 15 15 24 K3NPU24B . . . 1 1,5

15 18,5 18,5 32 K3PU32B . . . 1 1,9

1) Other coil voltages see page 40

Ordering Example: Pole Changing Starter, open version, rated AC3 at 400V 28A and 15A, control voltage 230V 50Hz
Order Type: K3PU32 230 + U3/32 32 + U3/32 18

Pole Changing Starters for Star-Delta Operation on request

1) Other coil voltages see page 39

90 D677E
Components for Combinations Auxiliary Contacts Free Space for
Left Hand Side Right Hand Side Mechanical Built-in for use Aux. Contact Blocks
Contactor Contactor Interlock on Contactor on Contactor

K1 K2 K1 K2 K1 K2
Type Type Type NO/NC NO/NC HN.. or HA..

K3-10ND01 K3-10ND01 LG10889 - - 4 4

K3-18ND01 K3-18ND01 LG10889 - - 4 4

K3-24A00 K3-24A00 LG10889 - - 3 3


+ HN01 + HN01

K3-32A00 K3-32A00 LG10889 - - 3 3


+ HN01 + HN01

K3-40A00 K3-40A00 LG10890 - - 3 3


+ HN01 + HN01

Components for Combinations Free Space for


High Low Star Aux. Contact Blocks on Contactor
Speed Speed Contactor High Low Star
Speed Speed
K1 K2 K3 K1 K2 K3
Type Type Type HN.. or HA..

K3-18ND01 K3-18ND01 K3-14ND10 2 3 4


+ 2 x HN10 + HN10

K3-24A00 K3-24A00 K3-18ND10 1 2 4


+ HN01 + 2 x HN10 + HN01 + HN10

K3-32A00 K3-32A00 K3-24A00 1 2 3


+ HN01 + 2 x HN10 + HN01 + HN10 + HN10

K3-50A00 K3-50A00 K3-32A00 1 2 3


+ HN01 + 2 x HN10 + HN01 + HN10 + HN10

K3-62A00 K3-62A00 K3-50A00 1 2 3


+ HN01 + 2 x HN10 + HN01 + HN10 + HN10

K3-18ND01 K3-18ND01 K3-14ND10 2 3 4


+ 2 x HN10 + HN10

K3-24A00 K3-24A00 K3-18ND10 1 2 4


+ HN01 + 2 x HN10 + HN01 + HN10

K3-32A00 K3-32A00 K3-24A00 1 2 3


+ HN01 + 2 x HN10 + HN01 + HN10 + HN10

D677E 91
Star-Delta Starters
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Type K3NY15 K3NY26 K3Y40 K3Y52 K3Y80 K3Y100 K3Y140 K3Y200 K3Y240 K3Y300

Main Contacts
Rated insulation voltage Ui 1) V AC 690 690 690 690 690 690 690 690 690 690

Frequency of operations z AC3, Ie 1/h 15


Change-over time max. (Y-step) s 20 (Type K3YL ... 60)

Utilization category AC3


Switching of three-phase motors
Rated operational 220-230V A 16 30 45 60 85 109 150 205 240 300
current Ie 240V A 16 30 45 60 85 109 150 205 240 300
380-400V A 16 30 45 60 85 109 150 205 240 300

415-440V A 15 30 45 60 85 109 150 205 240 300


500V A 15 30 45 60 85 95 150 205 190 240
660-690V A 13 17 30 36 57 72 103 118 147 180

Rated operational power 220-230V kW 4 7,5 11 15 22 30 45 55 75 90


of three-phase motors 240V kW 5,5 11 15 18,5 22 30 45 55 75 90
50-60Hz 380-400V kW 7,5 15 22 30 45 55 75 110 132 160

415-440V kW 7,5 15 22 30 45 55 75 110 140 170


500V kW 7,5 18,5 30 37 55 75 90 132 132 180
660-690V kW 11 15 22 30 45 55 90 110 132 180

Cable cross-sections
Line solid or stranded mm² 1,5 - 6 2) 1,5 - 16 10 - 70 3) 10 - 120 busbar
flexible mm² 1,5 - 4 2) 1,5 - 16 16 - 50 3) 10 - 95 18x5
lexible with multicore cable end mm² 1,5 - 4 2) 1,5 - 16 10 - 35 10 - 95 M8

Motor
solid or stranded mm² 1,5 - 6 1,5 - 16 4 - 35 3) 10 - 120 busbar
flexible mm² 1,5 - 4 1,5 - 16 6 - 25 3) 10 - 95 18x5
lexible with multicore cable end mm² 1,5 - 4 1,5 - 16 4 - 25 10 - 95 M8

Power consumption of the combination


inrush and change-over VA 55 130 183 560 700
sealed VA 20 26 36 10 10
W 6 8 14 10 10

Coil Voltage Ranges and Non Standard Voltages for Star-Delta Starters

K3NY15.. to K3Y100.. K3Y140, to K3Y300..

Suffix to Rated Control Voltage Us Suffix to Rated Control Voltage Us


Star-Delta Starter range for 50Hz range for 60Hz Star-Delta Starter range for 50Hz range for 60Hz for DC
type min. max. min. max. type min. max. min. max.
e.g. K3Y80 400 V V V V e.g. K3Y300 230 V V V V V

24 24 24 24 27 24 24 24 24 24 24
42 42 47 47 52 48 48 48 48 48 48
110 100 110 110 122 110 110 120 110 120 110

180 180 210 200 240 230 220 240 220 240 220
230 220 240 230 264 400 380 415 380 415 -
400 380 415 400 415

Standard voltages in bold type letters

1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution


degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request.
2) Additional terminals see page 77
3) Maximum cable cross-section with prepared conductor

92 D677E
Reversing Starters
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Type K3NWU10 K3NWU18 K3WU24 K3WU32 K3WU50 K3WU62 K3WU74

Main Contacts
Rated insulation voltage Ui 1) V AC 690 690 690 690 690 690 690

Utilization category AC3


Switching of three-phase motors
Rated operational current Ie 220V A 12 18 23 30 45 63
230V A 11,5 18 24 32 50 62 74
240V A 11 18 24 32 50 62 74

380-400V A 10 18 24 32 50 62 74
415-440V A 9 18 23 30 50 62 74
500V A 9 16 23 30 45 60 74
660-690V A 6,5 8,5 17 20 31 40 40

Rated operational power 220-230V kW 3 5 6 8,5 12,5 18,5


of three-phase motors 240V kW 3 5 7 9 13,5 19 23
50-60Hz 380-400V kW 4 7,5 11 15 22 30 37

415-440V kW 4,5 8,5 12 16 24 33 40


500V kW 5,5 10 15 18,5 30 37 45
660-690V kW 5,5 10 15 18,5 30 37 45

Cable cross-sections
Line solid or stranded mm² 0,75 - 6 1,5 - 25 4 - 50
flexible mm² 1-4 2,5 - 16 6 - 35
flexible with multicore cable end mm² 0,75 - 4 1,5 - 16 6 - 35
Cables per clamp 1 1 1

Power consumption of the combination


inrush and change-over VA 33 - 45 90 - 115 140 - 185
sealed VA 7 - 10 9 - 13 13 - 18
W 2,6 - 3 2,7 - 4 5,4 - 7

Technical Data according to UL508


Main Contacts (cULus) Type KNW3-10 KNW3-18 KW3-24 KW3-32 KW3-40

Rated operational power 110-120V hp 1½ 2 5 5 7½


of three-phase motors 200V hp 3 5 7½ 10 10
at 60Hz (3ph) 220-240V hp 3 7½ 10 10 15
277V hp 3 7½ 7½ 10 15

380-415V hp 5 10 10 15 20
440-480V hp 5 10 15 20 25
550-600V hp 7½ 15 20 25 30

Fuse / Short-circuit current A/kA 30/5 50/5 90/5 125/5 175/5

Rated voltage V 600 600 600 600 600

Auxiliary Contacts (cULus) A600 A600 A600 A600 A600

Cable cross-sections
for main connectors solid AWG 18 - 10 16 - 10
flexible AWG 18 - 10 14 - 4
Cables per clamp 1 1

1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request.

D677E 93
Pole Changing Starters
Data according to IEC 947-4-1, VDE 0660, EN 60947-4-1
Type K3NPU18 K3NPU24 K3PU32 K3PU50 K3PU62

Main Contacts
Rated insulation voltage Ui 1) V AC 690 690 690 690 690

Utilization category AC3


Switching of three-phase motors
Rated operational current Ie 220V A 18 23 30 45 63
230V A 17,5 23 30 45 60
240V A 17 23 30 45 60

380-400V A 16 23 30 45 60
415V A 16 23 30 45 60
440V A 16 23 30 45 60

500V A 16 23 30 45 55
660V A 9 17,5 21 33 42
690V A 8,5 17 20 31 40

Rated operational power 220-230V kW 5 6 8,5 12,5 18,5


of three-phase motors 240V kW 5 7 9 13,5 19
50-60Hz 380-400V kW 7,5 11 15 22 30

415-440V kW 8,5 12 16 24 33
500V kW 10 15 18,5 30 37
660-690V kW 7,5 15 18,5 30 37

Cable cross-sections
Line solid or stranded mm² 0,75 - 6 1,5 - 25 4 - 50
flexible mm² 1-4 2,5 - 16 6 - 35
flexible with multicore cable end mm² 0,75 - 4 1,5 - 16 6 - 35
cables per clamp 1 1 1

Power consumption of the combination


inrush and change-over VA 55 128 178
sealed VA 20 26 31
W 6 8 11

1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV. Data for other conditions on request.

94 D677E
Star-Delta Starters
Wiring Diagrams Main Circuit
Terminal markings of contactors and relays according to DIN EN 50012
Connections shown in main and circuits as broken lines are not included.

K3NY15 to K3Y100 K3Y140 to K3Y300


with thermal overload relay U3/.. or U12/16 with thermal overload relay U85 or U180

Wiring Diagrams Control Circuit


K3NY15 to K3Y52 K3NY15 to K3Y52 K3Y80 to K3Y200
operating with control switch operating with push buttons operating with control switch

K3Y80 to K3Y200 K3Y240 to K3Y300 K3Y240 to K3Y300


operating with push buttons operating with control switch operating with push buttons

D677E 95
Star-Delta Starters
Wiring Diagrams Main Circuit
Terminal markings of contactors and relays according to DIN EN 50012
Connections shown in main and control circuits as broken lines are not included.

K3YL.. K3Y.. with 2 Thermal Overload Relays


Typical circuit diagram Typical circuit diagram

Wiring Diagrams Control Circuit


with selector switch with push buttons
K3Y..W K3Y..T
Typical circuit diagram Typical circuit diagram Typical circuit diagram
operating with control switch operating with push buttons

96 D677E
Reversing Contactors
Wiring Diagrams Main Circuit
Terminal markings of contactors and relays according to DIN EN 50012
Connections shown in main and control circuits as broken lines are not included.

K3NWU10 to K3WU74
with thermal overload relay U3/32, U3/42 or U3/74

Wiring Diagrams Control Circuit


K3NWU10 to K3WU32
operating with control switch operating with push buttons
Reversing over off-position Reversing direct

K3WU50, K3WU62, K3WU74


operating with control switch operating with push buttons

D677E 97
Pole Changing Starters
Wiring Diagrams
Terminal markings of contactors and relays according to DIN EN 50012
Connections shown in main and control circuits as broken lines are not included.

Main Circuit Principal Control Circuit Wiring Diagram


operating with control switch operating with push buttons

Low High Low High


speed speed speed speed

Operation Delta Double-Star Star Double-Star


Speed relation 1 2 1 2
Power relation 1 1,5 - 1,8 0,3 1

98 D677E
Star-Delta Starters
Dimensions
Star-Delta Starters, AC operated, open type

K3NY15 + U3/32 K3NY15 + U12/16E G3


K3NY26 K3NY26

K3Y40 + U3/32 K3Y40 + U3/42


K3Y52 + U3/32 K3Y52 + U3/42

K3Y80 + U3/74 K3Y100 + U3/74

K3Y140 + U85 K3Y240 + U180 + SU180/176


K3Y200 K3Y300

D677E 99
Star-Delta Starters
Dimensions
Star-Delta Starters, plastic enclosed, protected to IP65

K3NY26P K3Y40P to K2Y100P

2 x Ø50,5/25,5 + Ø20,5

Type A B C D E ØF ØG H J

K3Y40P 300 346 180 272 320 6,5 32,5 32,5 60 60


K3Y52P 300 346 180 272 320 6,5 32,5 32,5 60 60

K3Y80P 300 446 180 272 420 6,5 40,5 40,5 70 70


K3Y100P 300 446 180 272 420 6,5 50,5 40,5 70 70

Star-Delta Starters, sheet steel enclosed, protected to IP54

K3Y26B to K3Y52B

Type ØF ØG

K3NY26B 25,5 25,5


K3Y40B 32,5 32,5
K3Y52B 32,5 32,5

Mounting by included fixing link

K3Y80B to K2Y200B

Type A B C D E L M

K3Y80B 380 380 210 340 340 8,7 65


K3Y100B 380 380 210 340 340 8,7 65

K3Y140B 380 600 210 560 340 8,7 65


K3Y200B 380 600 210 560 340 8,7 65

Type ØF ØG H J K

K3Y80B 40,5 40,5 70 70 60


K3Y100B 50,5 40,5 80 70 60

K3Y140B 50,5 50,5 80 80 70


K3Y200B 50,5 50,5 80 80 70

100 D677E
Reversing Contactors
Dimensions
Reversing Starters, AC operated, open type

K3NWU10 + U3/32 K3NWU10 + U12/16E G3


K3NWU18 K3NWU18

K3WU24 + U3/32 K3WU24 + U3/42


K3WU32 K3WU32
K3WU40 K3WU40

K3WU50 + U3/74
K3WU62
K3WU74

Reversing Contactors, sheet steel enclosed, protected to IP54

Type A B C D E F G H K

K3NWU18B 300 300 150 250 250 30 30 Ø25,5 41


K3WU24B 300 300 150 250 250 30 30 Ø32,5 41
K3WU32B 300 300 150 250 250 30 30 Ø32,5 41

K3WU50B 300 300 150 250 250 40 40 Ø32,5 59


K3WU62B 300 300 150 250 250 40 40 Ø32,5 59

Mounting by included fixing link

D677E 101
Pole Changing Starters
Dimensions
Pole Changing Starters, AC operated, open type

K3NPU18 + 2x U3/32 K3NPU18 + 2x U12/16

K3PU24 +2x U3/32 K3PU50 + 2x U3/74


K3PU32 K3PU62

Pole Changing Starters, sheet steel enclosed, protected to IP54

K3NPU18B to K3PU32B

Type ØF ØG

K3NPU18B 25,5 25,5


K3PU24B 32,3 32,5
K3PU32B 32,3 32,5

Mounting by included fixing link

102 D677E
D.O.L
.L.. Starters
.O.L

D.O.L. Starters With Start-Stop Buttons 104

D.O.L. Starters With Selector Switch 104

D.O.L. Starters With Selector Switch And 104


Pneumatic Switch For Use In Moist Rooms

Enclosures 105

Accessories 105

Wiring Diagrams 106

Dimensions 108

D677E 103
D.O.L. Starters In Plastic Enclosure

Ratings Included Free order Protec- Conduit Type Coil voltage 1)


AC3 at Contactor Space extra tion Entries 230 220-240V 50Hz 230-264V 60Hz
380V f. Aux. Degree 400 380-415V 50Hz 400-440V 60Hz
400V Cont. Overload ⏐
415V HN.. Relay ⏐ Pack Weight
kW Type pcs. Type W pcs. kg/pc.

D.O.L. Starters with Start-Stop/Reset Push Buttons


4 K3-10ND10 2 U12/16 K3 IP65 Ø 20,5mm P1T10 . . . 1 0,6

7,5 K3-18ND10 2 U12/16 K3 IP65 Ø 20,5mm P1T18 . . . 1 0,6

11 K3-22ND10 2 U12/16 K3 IP65 Ø 20,5mm P1T22 . . . 1 0,6

D.O.L. Starters with Selector Switch


4 K3-10ND10 2 U12/16 K3 IP65 Ø 20,5mm P1W10 . . . 1 0,6

7,5 K3-18ND10 2 U12/16 K3 IP65 Ø 20,5mm P1W18 . . . 1 0,6

11 K3-22ND10 2 U12/16 K3 IP65 Ø 20,5mm P1W22 . . . 1 0,6

D.O.L. Starters with Selector Switch and Pneumatic Switch for moist rooms
7,5 K3-18ND10 2 U12/16 K3 IP65 Ø 20,5mm P1W18P . . . 1 0,6

Push button and tube on request

Ordering Example: D.O.L. Starter with selector switch, plastic enclosed, rated AC3 at 400V 15,5A,
rated control voltage 230V 50Hz - Order Type: P1W18 230 + U12/16E 18 K3

Thermal Overload Relays

Setting range Type Pack Weight


A pcs. kg/pc.

0,12 - 0,18 U12/16E 0,18 K3 1 0,10


0,18 - 0,27 U12/16E 0,27 K3 1 0,10
0,27 - 0,4 U12/16E 0,4 K3 1 0,10

0,4 - 0,6 U12/16E 0,6 K3 1 0,10


0,6 - 0,9 U12/16E 0,9 K3 1 0,10
0,8 - 1,2 U12/16E 1,2 K3 1 0,10
manual reset
1,2 - 1,8 U12/16E 1,8 K3 1 0,10
1,8 - 2,7 U12/16E 2,7 K3 1 0,10
2,7 - 4 U12/16E 4 K3 1 0,10

4 - 6 U12/16E 6 K3 1 0,10
6 - 9 U12/16E 9 K3 1 0,10
8 - 11 U12/16E 11 K3 1 0,10

10 - 14 U12/16E 14 K3 1 0,10
13 - 18 U12/16E 18 K3 1 0,10
17 - 23 U12/16E 23 K3 1 0,10

22 - 30 U12/16E 30 K3 1 0,13

Overload Relays with Quick Tripping Characteristic see page 103


Technical data see contactors page 44 and thermal overload relays page 107

1) Non-standard coil voltages see page 39

104 D677E
Enclosures for Contactors

Suitable for Protection Conduit Entries Type Pack Weight


contactor Degree Top Bottom pcs. kg/pc.

K3-07.. to K3-22.. IP65 2 x Ø 20,5mm 2 x Ø 20,5mm P1 1 0,35


K3-24..1) to K3-40.. 1)

Enclosures for D.O.L. Starters with reset button

Suitable for Protection Conduit Entries Type Pack Weight


contactor Degree Top Bottom pcs. kg/pc.

K3-10.. to K3-22.. IP65 2 x Ø 20,5mm 2 x Ø 20,5mm P1R 1 0,35


+U12/16.. K3

Indicator Units
Specifications Voltage Range Type Pack Weight
pcs. kg/pc.

Coil Current Indicator


Indicator, green (LED) 24 - 660V AC/DC K2-ING 10 0,02
Coil Current Indicator,
Indicator red (LED) 24 - 660V AC/DC K2-INR 10 0,02
To be connected in series with the contactor coil. In case of coil
interruption the indicator goes out. Voltage drop approx. 2 volts

Voltage Indicator
Indicator, clear (glow-disc. l.) 220 - 415V AC/DC K2-UN 10 0,02
Voltage Indicator
Indicator, red (LED) 24 - 120V AC/DC K2-UNR 10 0,02
To be connected parallel to the contactor coil. In case of
applied voltage the indicator also lights at coil interruption.

Lens Caps For Indicator Units


Lens cap transparent LG9743T 10 0,005
Lens cap red LG9743R 10 0,005
Lens cap green LG9743GR 10 0,005
Mounting instructions see page 100

Heating Element
Specifications Voltage Range Type Pack Weight
Power Consumption pcs. kg/pc.

To avoid condensed water on places 380 - 415V, 1,5W K2-HR 10 0,02


where high humidity is given together 220 - 240V, 1,5W K2-HR 230 10 0,02
with alterations of ambient temperature

Additional Terminals, Start Contact


Specification Cable Cross-sections to clamp mm² Type Pack Weight
solid or flexib. w. multi-
stranded flexible core cable end pcs. kg/pc.

Neutral Terminal 2 x 0,75-4 2 x 0,75-2,5 2 x 0,5-2,5 LG9744 10 0,009


Earth Terminal 2,5-16 1,5-10 1,5-10 LG9750 10 0,052
Mounting instructions see page 100

Start Contact for contactor to be snapped on top of LG9319-K3 10 0,03


K3-10 to K3-22 the auxiliary contact

1)
without auxiliary contact blocks

D677E 105
D.O.L. Starters
Wiring Diagrams Main Circuit
All fuses F0 shown in the main circuits are not included.
Terminal markings according to EN 50012

P1... Wiring for single phase motors


with overload relay U12/16.. K3

Wiring Diagrams Control Circuit


D.O.L. Starters P1 with standard coil voltages (see page 94) are supplied with connectors between main circuit and control circuit.

Coil connectors Separate coil supply


Coils for 380-415V 50Hz and 400-440V 60Hz:
60Hz The starter is supplied with Coils for 380-415V 50Hz and 400-440V 60Hz
60Hz: Remove connectors A1-1
control circuit connectors between terminals1 (L1) and 5 (L3). and 95-5, connect supply to terminals A1 and 95.
Coils for 220-240V 50Hz and 230-264V 60Hz:
60Hz The starter is supplied with Coils for 220-240V 50Hz and 230-264V 60Hz
60Hz: Remove connectors 95-5
control circuit connectors between terminals 95 and 5 (L3). Connect connect supply to terminals A1 and 95.
neutral wire to terminal A1. Coils for other voltages
voltages: Connect supply to terminals A1 and 95.
Coils for other voltages
voltages: Without connectors between supply and control
circuit. Connect supply to terminals A1 and 95.

Coil phase to phase Coil phase to neutral Coil phase to phase Coil phase to neutral
(380-415V 50Hz) (220-240V 50Hz)

local control local control local control local control


or remote control or remote control or remote control or remote control

D.O.L. Starters with remote control

P1..
Remote 2-wire (switch) control Remote 3-wire (push button) control Remote start-stop control
(3 control stations)

106 D677E
D.O.L. Starters
Wiring Diagrams Control Circuits
Typical circuit diagram (for separate coil supply, control circuit connected between L1 and N)
Terminal markings according to EN 50012

D.O.L. Starters with Start-Stop/Reset Push Buttons

P1T10, P1T18, P1T22 P1T10, P1T18, P1T22


with overload relay U12/16.. K3 with external push buttons

D.O.L. Starters with Selector Switch

P1W10, P1W18, P1W22 P1W10, P1W18, P1W22


with external control switch with external push buttons

D.O.L. Starters with Selector Switch and Pneumatic Switch


for Swimmingpool Control Gear and for use in Moist Rooms
P1W18P
with overload relay U12/16.. K3

push button
ON/OFF

D677E 107
D.O.L. Starters
Dimensions
D.O.L. Starters with Start-Stop/Reset Push Buttons, Plastic Enclosed D.O.L. Starters with Selector Switch, Plastic Enclosed

P1T.., P1TP.. P1W.., P1W18P

P1W18P: plug-in for air tube inside diameter 3mm

Rear Conduit Entries

knockouts
4 x Ø 23

Earth Terminal LG9750 for K2-23 and K2-30 in Enclosure P1 Neutral Terminal LG9744

for K2-23 and K2-30 remove spacing piece

LG9750

LG9744

108 D677E
Enclosures
Dimensions
Enclosures for Contactors Enclosures for D.O.L. Starters

P1 P1R, P1P

Rear Conduit Entries

knockouts
4 x Ø 23

D677E 109
D.O.L. Starters
Mounting and Wiring Instructions
Indicators and Lens Caps for D.O.L. Starters P1

K2-UN., K2-IN.

LG9743.

Wiring Examples

Coil Current Indicator Voltage Indicator Heating Element

K2-ING K2-UN K2-HR K2-HR 230


K2-INR K2-UNR

red
red

Colour mentioned in wiring diagrams refer to


the outgoing connection wire of the device.

Start Contact LG9319-K3 for K3-10ND10 up to K3-22ND10

110 D677E
Thermal Overload Relays

Thermal Overload Relays for Direct Mounting 112

Thermal Overload Relays for Separate Mounting 114

Accessories 115

Technical Data 116

Dimensions 121

D677E 111
Thermal Overload Relays for plug-in mounting

Setting Range Type Pack Weight


D.O.L. (A) (A) pcs. kg/pc. Wiring Diagram

With Manual Reset


Reset, for contactors K1-..
0,12 - 0,18 - U12/16E 0,18 K1 1 0,10
0,18 - 0,27 - U12/16E 0,27 K1 1 0,10
0,27 - 0,4 - U12/16E 0,4 K1 1 0,10

0,4 - 0,6 - U12/16E 0,6 K1 1 0,10


0,6 - 0,9 - U12/16E 0,9 K1 1 0,10 manual reset
0,8 - 1,2 - U12/16E 1,2 K1 1 0,10

1,2 - 1,8 - U12/16E 1,8 K1 1 0,10


1,8 - 2,7 - U12/16E 2,7 K1 1 0,10
2,7 - 4 - U12/16E 4 K1 1 0,10

4 - 6 7 - 10,5 U12/16E 6 K1 1 0,10


6 - 9 10,5 - 15,5 U12/16E 9 K1 1 0,10
8 - 11 14 - 19 U12/16E 11 K1 1 0,10

10 - 14 18 - 24 U12/16E 14 K1 1 0,10

With Auto Reset


Reset, for contactors K1-..
0,12 - 0,18 - U12/16A 0,18 K1 1 0,10
0,18 - 0,27 - U12/16A 0,27 K1 1 0,10
0,27 - 0,4 - U12/16A 0,4 K1 1 0,10

0,4 - 0,6 - U12/16A 0,6 K1 1 0,10


0,6 - 0,9 - U12/16A 0,9 K1 1 0,10
0,8 - 1,2 - U12/16A 1,2 K1 1 0,10 auto reset
or manual reset
1,2 - 1,8 - U12/16A 1,8 K1 1 0,10
1,8 - 2,7 - U12/16A 2,7 K1 1 0,10
2,7 - 4 - U12/16A 4 K1 1 0,10

4 - 6 7 - 10,5 U12/16A 6 K1 1 0,10


6 - 9 10,5 - 15,5 U12/16A 9 K1 1 0,10
8 - 11 14 - 19 U12/16A 11 K1 1 0,10

10 - 14 18 - 24 U12/16A 14 K1 1 0,10

With Quick Tripping Characteristic for EEx e motors and submersible pumps, f. contactors K1-..
0,4 - 0,6 - U12/16EQ 0,6 K1 1 0,10
0,6 - 0,9 - U12/16EQ 0,9 K1 1 0,10
0,8 - 1,2 - U12/16EQ 1,2 K1 1 0,10

1,2 - 1,8 - U12/16EQ 1,8 K1 1 0,10


1,8 - 2,7 - U12/16EQ 2,7 K1 1 0,10
2,7 - 4 - U12/16EQ 4 K1 1 0,10 manual reset

4 - 6 7 - 10,5 U12/16EQ 6 K1 1 0,10


6 - 9 10,5 - 15,5 U12/16EQ 9 K1 1 0,10
8 - 11 14 - 19 U12/16EQ 11 K1 1 0,10

10 - 14 18 - 24 U12/16EQ 14 K1 1 0,10

112 D677E
Thermal Overload Relays for plug-in mounting

Setting Range Type Pack Weight


D.O.L. (A) (A) pcs. kg/pc. Wiring Diagram

With Manual Reset


Reset, for contactors K(G)3-10.. to K(G)3-22.. ..
0,12 - 0,18 - U12/16E 0,18 K3 1 0,10
0,18 - 0,27 - U12/16E 0,27 K3 1 0,10
0,27 - 0,4 - U12/16E 0,4 K3 1 0,10

0,4 - 0,6 - U12/16E 0,6 K3 1 0,10


0,6 - 0,9 - U12/16E 0,9 K3 1 0,10
0,8 - 1,2 - U12/16E 1,2 K3 1 0,10 manual reset

1,2 - 1,8 - U12/16E 1,8 K3 1 0,10


1,8 - 2,7 - U12/16E 2,7 K3 1 0,10
2,7 - 4 - U12/16E 4 K3 1 0,10

4 - 6 7 - 10,5 U12/16E 6 K3 1 0,10


6 - 9 10,5 - 15,5 U12/16E 9 K3 1 0,10
8 - 11 14 - 19 U12/16E 11 K3 1 0,10

10 - 14 18 - 24 U12/16E 14 K3 1 0,10
13 - 18 23 - 31 U12/16E 18 K3 1 0,10
17 - 23 30 - 40 U12/16E 23 K3 1 0,10

22 - 30 38 - 52 U12/16E 30 K3 1 0,13

With quick Tripping Characteristic for EEx e motors and under water pumps
0,4 - 0,6 - U12/16EQ 0,6 K3 1 0,10
0,6 - 0,9 - U12/16EQ 0,9 K3 1 0,10
0,8 - 1,2 - U12/16EQ 1,2 K3 1 0,10

1,2 - 1,8 - U12/16EQ 1,8 K3 1 0,10


1,8 - 2,7 - U12/16EQ 2,7 K3 1 0,10
2,7 - 4 - U12/16EQ 4 K3 1 0,10 manual reset

4 - 6 7 - 10,5 U12/16EQ 6 K3 1 0,10


6 - 9 10,5 - 15,5 U12/16EQ 9 K3 1 0,10
8 - 11 14 - 19 U12/16EQ 11 K3 1 0,10

10 - 14 18 - 24 U12/16EQ 14 K3 1 0,10

For contactors K(G)3-10.. to K(G)3-40A..


0,12 - 0,18 - U3/32 0,18 1 0,14
0,18 - 0,27 - U3/32 0,27 1 0,14
0,27 - 0,4 - U3/32 0,4 1 0,14

0,4 - 0,6 - U3/32 0,6 1 0,14


0,6 - 0,9 - U3/32 0,9 1 0,14
0,8 - 1,2 - U3/32 1,2 1 0,14 manual and
auto reset
1,2 - 1,8 - U3/32 1,8 1 0,14
1,8 - 2,7 - U3/32 2,7 1 0,14
2,7 - 4 - U3/32 4 1 0,14

4 - 6 7 - 10,5 U3/32 6 1 0,14


6 - 9 10,5 - 15,5 U3/32 9 1 0,14
8 - 11 14 - 19 U3/32 11 1 0,14

10 - 14 18 - 24 U3/32 14 1 0,14
13 - 18 23 - 31 U3/32 18 1 0,14
17 - 24 30 - 41 U3/32 24 1 0,14

23 - 32 40 - 55 U3/32 32 1 0,14

For contactors K(G)3-24A.. to K(G)3-40A ..


10 - 14 18 - 24 U3/42 14 1 0,30
14 - 20 24 - 35 U3/42 20 1 0,30

20 - 28 35 - 48 U3/42 28 1 0,30
28 - 42 48 - 73 U3/42 42 1 0,30 manual and
auto reset

D677E 113
Thermal Overload Relays for plug-in mounting

Setting Range Type Pack Weight


D.O.L. (A) (A) pcs. kg/pc. Wiring Diagram

For contactors K3-50A.. to K3-74A..


20 - 28 35 - 48 U3/74 28 1 0,40
28 - 42 48 - 73 U3/74 42 1 0,40
40 - 52 70 - 90 U3/74 52 1 0,40

52 - 65 90 - 112 U3/74 65 1 0,40


60 - 74 104 - 128 U3/74 74 1 0,40
manual and
auto reset

Thermal Overload Relays for separate mounting

Setting Range Type Pack Weight


D.O.L. (A) (A) pcs. kg/pc. Wiring Diagram

For contactors K3-90, K3-115, K85, K110


60 - 90 104 - 156 U85 90 1 0,90
80 -120
120 140 - 207 U85 120
manual reset

For contactors K3-151.. and K3-176.., busbars included


120 - 180 208 - 312 U180 180 1 1,5

manual and
For contactors K3-210.. up to K3-316.., busbars included auto reset
144 - 216 250 - 374 U320 216 1 1,8
216 - 320 374 - 554 U320 320

For contactors K3-315.. , K3-450.. , K3-550.. , K3-700.. , K3-860..


240 - 360 416 - 623 U800 360 1 4,1
360 - 540 623 - 935 U800 540 1 4,1

540 - 800 935 - 1385 U800 800 1 4,1

With Slow Tripping Characteristic for heavy duty starting with long run up times
For separate mounting, suitable for all contactors
0,8 - 1,2 1,2 - 2,1 UAT21 1,2 1 1,0
1,2 - 1,8 2,1 - 3,1 UAT21 1,8 1 1,0
1,6 - 2,4 2,8 - 4,2 UAT21 2,4 1 1,0

2,4 - 3,7 4,2 - 6,4 UAT21 3,7 1 1,0 manual reset


3,7 - 5,7 6,4 - 9,9 UAT21 5,7 1 1,0
5,3 - 8,2 9,2 - 14,2 UAT21 8,2 1 1,0

8 - 12 13,9 - 20,1 UAT21 12 1 1,0


12 - 18 20,1 - 31,2 UAT21 18 1 1,0

16 - 24 27,7 - 41,6 UAT22 24 1 1,1

24 - 37 41,6 - 64 UAT23 37 1 1,3


32 - 49 55,4 - 85 UAT23 49 1 1,3
48 - 72 83 - 125 UAT23 72 1 1,3

114 D677E
Accessories

Type Pack Weight


for overload relays for contactors set kg/set

Busbar Sets
U800 K3-450.. , K3-550.. SU840/550 1 1,7
U800 K3-700.. , K3-860.. SU840/860 2,1

Cable Cross-section (mm2) Type


solid or Pack Weight
for overload relay stranded flexible pcs. kg/pc.

Set for Single Mounting on DIN-rail with terminals


U12/16..K3 0,75 - 6 0,75 - 4 U12SM K3 1 0,035

Additional Terminals with fingertouch protection


U3/32 0,75 - 6 0,75 - 4 U3/32SM 1 0,035

Set for Single Mounting on DIN-rail


U3/42, U3/74 - - U3/42G 1 0,030

Connecting Wire Set for U3/42, U3/74 with Single Mounting


U3/42, U3/74 150mm lang 10mm2 LG5830-4 1 0,060
U3/42, U3/74 250mm lang 10mm2 LG5830-2 1 0,100

Additional Terminals with fingertouch protection


1-pole f. U12/16, U3/32 0,75 - 10 0,75 - 6 LG9339 1 0,009

3-pole for U3/42 4 - 35 6 - 25 LG7559 1 0,052

D677E 115
Thermal Overload Relays
Relays, tripping times for selection to motors of protection degree EEx e
Relays With Standard Tripping Characteristic Relays With Quick Tripping Characteristic
preferably for motors with short tE time
and for submersible pumps
Setting Range Tripping time depending on the multiple Setting Range Tripping time depending on the multiple
of the current setting from cold condition of the current setting from cold condition
(tolerance ±20% of the tripping time) (tolerance ±20% of the tripping time)
IA/I N IA/I N IA/IN IA/I N IA/IN IA/IN IA/IN IA/I N IA/I N IA/I N IA/IN IA/IN
A A 3 4 5 6 7,2 8 A A 3 4 5 6 7,2 8

U3/32 .. s s s s s s U12/16EQ .. s s s s s s
0,12 - 0,18 16,1 9,6 6,8 5,3 4,2 3,7 0,4 - 0,6 13,6 8,4 5,9 4,2 3,3 3,0
0,18 - 0,27 16,6 9,7 6,7 5,2 4,1 3,6 0,6 - 0,9 13,8 7,8 5,2 4,1 3,2 2,7
0,27 - 0,4 19,4 11,4 7,9 6,1 4,7 4,2 0,8 - 1,2 13,1 7,5 5,2 3,9 3,1 2,7
0,4 - 0,6 18,7 10,9 7,6 5,9 4,6 4,0 1,2 - 1,8 14,6 8,7 6,0 4,6 3,6 3,2

0,6 - 0,9 19,2 11,2 7,7 5,9 4,6 4,1 1,8 - 2,7 13,5 7,6 5,3 3,9 3,1 2,7
0,8 - 1,2 20,8 12,3 8,5 6,6 5,2 4,6 2,7 - 4 11,0 6,0 4,1 2,6 1,7 1,4
1,2 - 1,8 25,5 14,1 9,8 7,6 5,9 5,2 4 - 6 9,6 5,3 3,3 2,3 1,6 1,3
1,8 - 2,7 26,6 15,6 10,9 8,3 6,5 5,7 6 - 9 10,2 5,4 3,4 2,3 1,6 1,3

2,7 - 4 22,7 13,6 9,5 7,4 5,8 5,1 8 - 11 12,0 6,2 3,9 2,5 1,8 1,3
4 - 6 22,2 13,3 9,3 7,1 5,6 4,9 10 - 14 12,8 6,6 4,0 2,6 1,8 1,4
6 - 9 20,4 11,9 8,2 6,1 4,7 4,0
8 - 11 20,9 11,8 7,9 5,7 4,3 3,5 All tripping times of overload relays U12/16EQ are shorter than the
minimum values of the tE time for motors of protection degree EEx e acc.
10 - 14 21,3 11,7 7,4 5,1 3,7 3,0 to EN 50019 and therefore are suitable for all motors of protection
13 - 18 21,2 12,1 8,0 6,2 4,6 4,1 degree EEx e. For these overload relays the selection on basis of
17 - 24 20,4 12,0 8,6 6,3 4,5 3,7 tripping curves is thereby not necessary.
23 - 32 20,2 10,2 6,7 4,7 3,4 2,8

U3/42 s s s s s s When selecting a standard overload, refer to the tripping curve. Determine
the values of the starting current ratio IA/IN and the time tE which is marked
10 - 14 21,8 11,4 7,0 5,0 3,7 2,8 on the label of the motor. The overload must trip within the tE time, which
14 - 20 22,4 11,2 6,7 4,5 3,2 2,4 means that the tripping curve from cold condition must be (20% due to
20 - 28 21,8 10,8 6,5 4,5 3,3 2,5
tolerance) below the co-ordination point IA/IN and the time tE.
28 - 42 25,2 13,3 8,0 5,5 4,0 3,1
I A = Starting current of motor I N = Rated current of motor
U3/74 s s s s s s t E = tE-time of motor
20 - 28 21,8 10,8 6,5 4,5 3,3 2,5
28 - 42 25,2 13,3 8,0 5,5 4,0 3,1
52 Time tE /Tripping time
40 - 18,3 9,2 5,6 3,9 2,8 2,2
65 s
52 - 17,8 8,7 5,2 3,4 2,5 1,9

U85 .. s s s s s s
Typical tripping
60 - 90 19,5 13,5 11,0 10,0 9,5 8,5 curve for overload
80 - 120 18,0 11,0 10,0 9,0 8,5 8,0 relay U12/16E

U840 .. s s s s s s Minimum values of


260 - 360 23,3 14,1 10,0 7,6 6,1 5,4 tE time (motor)
340 - 480 23,0 13,8 9,6 7,6 6,1 5,4 acc. to EN50019
440 - 620 20,5 12,4 9,0 7,0 5,5 5,0
560 - 800 21,0 12,5 9,0 7,0 5,6 5,2 Typical tripping
curve for overload
U12/16E(A) .. s s s s s s relay U12/16EQ
0,12 - 0,18 18,5 10,4 7,2 5,5 4,3 3,6 ratio IA/IN
0,18 - 0,27 16,7 9,8 6,5 5,0 4,1 3,5
0,27 - 0,4 19,4 12,1 8,2 5,9 4,9 4,2
0,4 - 0,6 18,7 11,2 8,0 6,0 4,9 4,1 Labels of tripping curves for each setting range, sized 148x105mm
(self-adhesive) are available on request.
0,6 - 0,9 19,7 11,6 8,1 6,1 4,9 4,2 Order No. D588, specify type and setting range.
0,8 - 1,2 22,9 13,6 10,0 7,3 6,0 5,2
1,2 - 1,8 22,2 13,2 9,2 7,6 5,8 5,3
1,8 - 2,7 23,0 13,7 9,3 7,6 5,7 5,1 Example of selection for thermal overload relay:
Technical data of a motor protection EEx e
2,7 - 4 24,0 14,4 9,9 7,8 5,9 5,1 PN= 1,5kW IN = 3,6A IA/IN = 5 tE time = 8s
4 - 6 24,7 13,8 9,9 7,3 5,6 4,8
6 - 9 22,0 13,4 8 5,7 4,1 3,5 1) U12/16E 4 (2,7 - 4A)
8 - 11 17,4 9,2 5,9 4,1 2,9 2,3 Tripping time at 5 x IN = 9,9s
9,9s + 20% tolerance = 11,9s > tE Motor = 8s
10 - 14 26,4 12,9 7,6 5,2 3,5 2,8
13 - 18 14,7 7,7 4,8 3,2 2,3 1,7 The device U12/16E 4 is not suitable
suitable.
17 - 23 16,2 8,4 5,0 3,6 2,4 1,8
22 - 30 16,8 8,5 5,0 3,6 2,3 1,9 2) U12/16EQ 4 (2,7 - 4A)
Tripping time at 5 x IN = 4,1s
4,1s + 20% tolerance = 4,9s < tE Motor = 8s
The device U12/16EQ 4 is therefore suitable
for motor protection

116 D677E
Thermal Overload Relays
Fuses for U3/32, U3/42, U3/74, U12/16E, U85, U180, U320 and U800
Max. Fuse Size According to Coordination-type Fuse UL SCCR
Type Setting Range "2" 1) "1" 1)
DOL quick slow, gL(gG) slow, gL(gG) aM
A A A A A A A kA

U3/32 0,12 - 0,18 - 0,5 2) 0,5 2) 25 - 15 5


(U12/16E) 0,18 - 0,27 - 1,0 2) 1,0 2) 25 - 15 5
0,27 - 0,4 - 2 2 25 - 15 5
0,4 - 0,6 - 2 2 25 - 15 5
0,6 - 0,9 - 4 4 25 - 15 5
0,8 - 1,2 - 4 4 25 2 15 5
1,2 - 1,8 - 6 6 25 2 15 5
1,8 - 2,7 - 10 10 25 4 15 5
2,7 - 4 - 16 10 25 4 15 5
4 - 6 7 - 10,5 20 16 25 6 15 5
6 - 9 10,5 - 15,5 35 25 35 10 25 5
8 - 11 14 - 19 35 25 35 16 30 5
10 - 14 18 - 24 50 35 63 16 40 5
13 - 18 23 - 31 50 35 63 20 50 5
17 (23)24
-(23)24 30 -(40)41 63 50 63 25 60 5

(22)23 -(30)32
(30)32 (38)40 -(52)55 80 63 80 35 70 5

U3/42 10 - 14 18 - 24 50 35 80 16 40 5
14 - 20 24 - 35 63 50 80 25 60 5
20 - 28 35 - 48 80 63 80 35 80 5
28 - 42 48 - 73 100 80 150 50 110 5

U3/74 20 - 28 35 - 48 100 80 150 35 80 5


28 - 42 48 - 73 125 100 150 50 110 5
40 - 52 70 - 90 160 100 150 63 200 5
52 - 65 90 - 112 160 125 150 80 250 10
60 - 74 104 - 128 160 125 150 80 250 10

U85 60 - 90 104 - 156 300 10


80 120
-120 140 - 207 - 10
For short circuit protecting overload relays with
U180, U320 all ranges current transformer use fuse according to the - -
U800 all ranges contactor of the combination. - -

Tripping Characteristics for U3/32, U3/42, U3/74 and U12/16E


Detailed tripping times for each range see table page 106

with three-phase load with two-pole load

Tripping time (Average value of typical tolerance curves Tripping time (Typical tolerance curve
min. s from cold condition) min. s from cold condition)
Proceeding from service condition the times decrease
decrease to 20-30% of the characteristic values
Proceeding from service condition the times

to 70-80% of the characteristic values

F. L. C. multiplication factor K =Imax /Ie Imax = max. phase current


Ie = max. scale value
1) Coordination-type according to IEC 947-4-1:
"2": Light contact welding accepted. Thermal overload relay must not be damaged.
"1": Welding of contactor and damage of the thermal overload relay allowed.
2) Miniature fuse 3) Suitable for use on a capability of delivering not more than

D677E 117
Thermal Overload Relays
Tripping Characteristics for U85, U180, U320, and U800
Detailed tripping times for each range of U85 see table page 106

U85 with three-phase load U180, U320 with three-phase load U800 with three-phase load

Tripping time (Average value of typical tolerance Tripping time (Average value of typical tolerance Tripping time (Average value of typical tolerance
min. s curves from cold condition) min. s curves from cold condition) min. s curves from cold condition)

decrease to 20-30% of the characteristic values

decrease to 20-30% of the characteristic values

decrease to 20-30% of the characteristic values


Proceeding from service condition the times

Proceeding from service condition the times

Proceeding from service condition the times


F. L. C. multiplication factor F. L. C. multiplication factor F. L. C. multiplication factor

U85 with two-pole load

Tripping time (Typical tolerance curve


min. s from cold condition)
Proceeding from service condition the times decrease
to 70-80% of the characteristic values

K =Imax / Ie Imax = max. phase current


Ie = max. scale value

Position of Terminals
U3/32 U12/16E, U12/16EM, U12/16EQ U12/16A U3/42, U3/74

118 D677E
Thermal Overload Relays in Special Version
Fuse for U12/16EQ Fuse for U12/16EM
Setting Range Maximum Fuse Acc. to Coordination-type Setting Range Maximum Fuse Acc. to Coordination-type "2" 1)
"2" 1) "1" 1) 380-400V 500V 660-690V
quick slow, gL(gG) slow, gL(gG) slow, gL(gG) slow, gL(gG) slow, gL(gG)
A A A A A A A A

0,4 - 0,6 2 2 25 0,12 - 0,18 none none on request


0,6 - 0,9 4 4 25 0,18 - 0,27 none none on request
0,8 - 1,2 4 4 25 0,27 - 0,4 none none on request

1,2 - 1,8 6 6 25 0,4 - 0,6 none none on request


1,8 - 2,7 10 10 25 0,6 - 0,9 none none on request
2,7 - 4 16 10 25 0,8 - 1,2 none 10 on request

4 - 6 20 16 25 1,2 - 1,8 none 16 on request


6 - 9 35 25 35 1,8 - 2,7 20 20 on request
8 - 11 35 25 35 2,7 - 4 35 35 on request

10 - 14 50 35 63

Tripping Characteristic for U12/16EQ Tripping Characteristic for U12/16EM


Detailed tripping times for each range see table page 106

with three-phase load with three-phase load

Proceeding from service condition the times decrease


range 0,4-0,6 to 1,8-2,7A Tripping time (Average value of typical tolerance
Tripping time (Typical tolerance curve min. s curves from cold condition)
min. s from cold condition)
Proceeding from service condition the times decrease

to 20-30% of the characteristic values


to 20-30% of the characteristic values

Lower scale value


Upper scale value
F. L. C. multiplication factor

F. L. C. multiplication factor

range 2,7-4 to 10-14A Fuse for UAT21, UAT22, UAT23


Tripping time (Typical tolerance curve
min. s from cold condition) For short circuit protecting thermal overload relays with current
transformer use fuse according to the contactor of the combination.
Proceeding from service condition the times decrease

Tripping characteristic for UAT21, UAT22, UAT23


to 20-30% of the characteristic values

with three-phase load

Tripping time in s (Typical tolerance curve from cold condition)

Proceeding from service


condition the times decrease
to 20-30% of the
characteristic values

F. L. C. multiplication factor
F. L. C. multiplication factor

1) Coordination-type according to IEC 947-4-1:


"2": Light contact welding accepted. Thermal overload relay must not be damaged.
"1": Welding of contactor and damage of the thermal overload relay allowed.

D677E 119
Thermal Overload Relays
Data according to IEC 947-4-1, IEC 947-5-1, VDE 0660, EN 60947-4-1, EN 60947-5-1
Type U3/32 U12/16 6) U3/42 U3/74 U85 U180 U320 U800 UAT21 UAT22 UAT23

Rated insulation voltage Ui 1)

V~ 690 690 690 690 750 1000 1000 1000 690 690 690
Permissible ambient temperature
operation open °C -25 to +60 -25 to +55 -25 to +60
storage °C -50 to +70 -40 to +70 -50 to +70

Trip class according to IEC 947-4-1


947-4-110A 10A 10A 10A 10A 20 10A 10A 10 30 30 30

Cable cross-section
main connector solid or stranded mm² 0,75-6 0,75-6+0,75-2,5 2) 0,75-10 4-35 2) 3) 7) - 7) 0,5-10 0,5-16 0,5-25
flexible mm² 1-4 0,75-4+0,5-2,5 2 ) 0,75-6 6-25 2) 0,5-6 0,5-10 0,5-16
flexible with multicore cable end mm² 0,75-4 0,5-2,5+0,5-1,5 0,75-6 4-25 0,5-6 0,5-10 0,5-16
Cables per clamp number 2 1+1 2 1 1 1 1

auxiliary connector solid mm² 0,75-2,5 2) 1-2,52) 0,75-2,5 2)


flexible mm² 0,5-2,5 2) 1-2,5 2) 0,5-2,5 2)
flexible with multicore cable end mm² 0,5-1,5 1-2,5 2) 0,5-1,5
Cables per clamp number 2 2 2

Type U3/32 U12/16A U12/16E U12/16EQ U3/42 U85 U180 U800 UAT21
U12/16EM U3/74 U320 UAT22
Auxiliary contacts UAT23
Rated insulation voltage Ui 1)
same potential V~ 690 690 690 690 690 690 690 500 690
different potential V~ 440 - 440 440 250 440 440 500 440

Utilization category AC15


Rated operational 24V A 3 4 5 5 4 5 3 4 5) 5
current Ie 230V A 2 2,5 3 3 2,5 3 2 2,5 3
400V A 1 1,5 2 2 1,5 2 1 1,5 2
690V A 0,5 0,6 0,6 0,6 0,6 0,6 0,5 0,6 0,6

Utilization category DC13


Rated operational 24V A 1 1,2 1,2 1,2 1,2 1,2 1,2 1,2 1,2
current Ie 110V A 0,15 0,15 0,15 0,15 0,15 0,15 0,15 0,15 0,15
220V A 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1

Short circuit prot. (without welding 1kA)


highest fuse rating gL (gG) A 4 4 6 6 6 6 4 6 6

Type U3/32 U12/16 U12/16E U3/42 U3/42 U3/74 U3/74 U85


Setting range all to 23A 22 - 30A to 28A 28 - 42A to 52A 52 - 65A all

Power loss per current path (max.)


minimum setting value W 1,1 1,1 1,7 1,3 1,3 2,0 2,9 1,1
maximum setting value W 2,3 2,3 3,7 2,6 3,3 3,7 4,5 2,5

Data according to cULus


Type U3/32 U12/16A U12/16E U12/16EQ U3/42 U3/74 U85

Rated insulation voltage V~ 600 600 600 600 600 600 600
Rated current A 32 23 23 23 42 74 85

Auxiliary contacts
Rated voltage
same potential V AC 600 600 600 600 600 600 600
different potential V~ 150 - 150 150 150 150 150

Switching capacity AC VA 500 500 500 500 600 600 600


of aux. contacts A 2 3 4 4 4 4 4

Temperature Compensation
In case of higher ambient temperature use the following formula: Example: Ambient temperature 70°C, full load motor current 7A
(Ambient temperature - 20) x 0,125 = correction factor in % of the (70 - 20) x 0,125 = 6,25%
full load motor current Setting value: 7A + 6,25% = 7,44A

1) Suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 4kV (at 440V), 6kV (at 690V).
Data for other conditions on request.
2) Maximum cable cross-section with prepared conductor
3) Without terminals, suitable for bushing one connector 70mm² (stranded) per phase
4) Switching capacity of the start contact: AC15 300VA, max. 1,5A, DC13 (max. 220V) 30W, max. 1,5A
5) Switching capacity of the make contact: AC15 400VA, max. 1,7A, DC13 (max. 220V) 10W, max. 1A
6) U12/16E 30: Cable cross-section for main connector like type U3/42, one connector only
7) Busbar sets see accessories page 105

120 D677E
Thermal Overload Relays
Dimensions
K3-10N + U3/32 KG3-10 + U3/32
K3-14N KG3-14
K3-18N KG3-18
K3-22N KG3-22

K3-24 + U3/32 KG3-24 + U3/32


K3-32 KG3-32
K3-40 KG3-40

K3-24 + U3/42 KG3-24 + U3/42


K3-32 KG3-32
K3-40 KG3-40

U3/32SM U3/42G +LG5830-.


Changing of connecting wire with 1,8Nm

D677E 121
Thermal Overload Relays
Dimensions
K1-09 + U12/16.. K1 K3-10 + U12/16..K3
K1-12 K3-14
K3-18
K3-22

K3-10N + U12/16..K3 KG3-10 + U12/16..K3


K3-14N KG3-14
K3-18N KG3-18
K3-22N KG3-22

U12SM K3

U12/16..K3 + U12SM K3 for snap-on 35mm DIN-rail according to


DIN EN50022 and screw mounting (single mounting)

K3-50 + U3/74
K3-62
K3-74

122 D677E
Thermal Overload Relays
Dimensions
K3-90A + U85
K3-115A

K3-151A00 + U180 Bohrplan


K3-176A00

K3-210A00 + U320 Bohrplan


K3-260A00
K3-316A00

D677E 123
Thermal Overload Relays
Dimensions
U800

U800 with A B C D E F G H J K

K3-450 220 372 110 220 158 40 185 225 12,5 9


K3-550 220 395 110 220 158 40 196 225 12,5 9

K3-700 280 487 175 280 202 50 257 291 14,5 11


K3-860 280 540 175 280 202 50 280 291 14,5 11

UAT21 UAT22

UAT23

Type Setting Range A B

UAT23 37 23-37A 105,5 97,5


UAT23 49 32-49A 94 86
UAT23 72 48-72A 94 86

124 D677E
Modular Contactors

Modular Contactors 126

Auxiliary Contact Block 127


Accessories 127

Day-Night Reloading Contactors 128

Switching Of Lamps 128

Technical Data 130

Dimensions 132

D677E 125
Modular Contactors

Rated Heating Power Type coil voltage


Current AC1 at 24 24V 50/60Hz
230 220-240V 50Hz, 230-264V 60Hz
24VM 24V 50/60Hz, 24V DC
AC1 1-phase 3-phase 230VM 220-240V 50/60Hz, 220V DC
400V 230V 400V ⏐ Pack Weight
A kW kW W pcs. kg/pc. Wiring Diagram

One-pole 1 module (17,5mm)


20 4,6 - R20-10 24 12 0,12
20 4,6 - R20-10 230 12 0,12

Two-pole 1 module (17,5mm)


20 4,6 - R20-20 24 12 0,12
20 4,6 - R20-20 230 12 0,12

20 4,6 - R20-11 24 12 0,12


20 4,6 - R20-11 230 12 0,12

20 4,6 - R20-02 24 12 0,12


20 4,6 - R20-02 230 12 0,12

25 5,5 - R25-20 24 12 0,14


25 5,5 - R25-20 230 12 0,14

25 5,5 - R25-11 24 12 0,14


25 5,5 - R25-11 230 12 0,14

25 5,5 - R25-02 24 12 0,14


25 5,5 - R25-02 230 12 0,14

Four-pole 2 modules (35mm) 1


25 5,7 17 R25-40 24 6 0,21
25 5,7 17 R25-40 230 6 0,21

25 5,7 17 R25-31 24 6 0,21


25 5,7 17 R25-31 230 6 0,21

25 5,7 17 R25-13 24 6 0,21


25 5,7 17 R25-13 230 6 0,21

25 5,7 - R25-22 24 6 0,21


25 5,7 - R25-22 230 6 0,21

25 5,7 17 R25-04 24 6 0,21


25 5,7 17 R25-04 230 6 0,21

Four-pole 2 modules(35mm), AC/DC-operated 1)


25 5,7 17 R25-40 24VM 6 0,22
25 5,7 17 R25-40 230VM 6 0,22

25 5,7 17 R25-31 24VM 6 0,22


25 5,7 17 R25-31 230VM 6 0,22

25 5,7 17 R25-13 24VM 6 0,22


25 5,7 17 R25-13 230VM 6 0,22

25 5,7 - R25-22 24VM 6 0,22


25 5,7 - R25-22 230VM 6 0,22

25 5,7 17 R25-04 24VM 6 0,22


25 5,7 17 R25-04 230VM 6 0,22

1) Sealable with Sealing Cover P721, available aux. contact block RH11(see page 117)
2) Sealable with Sealing Cover P721, available aux. contact block RH11-1(see page 117)

126 D677E
Modular Contactors
Rated Heating Power Type coil voltage
Current AC1 at 24 24V 50/60Hz
AC1 1-phase 3-phase 230 220-240V 50Hz, 230-264V 60Hz
400V 230V 400V ⏐ Pack Weight
A kW kW W pcs. kg/pc. Wiring Diagram

Two-pole 2 modules (35mm)


40 9 - R40-20 24 6 0,23
40 9 - R40-20 230 6 0,23

63 14,3 - R63-20 24 6 0,23


63 14,3 - R63-20 230 6 0,23

Four-pole 3 modules (52,5mm) 1)


40 9 27,5 R40-40 24 4 0,35
40 9 27,5 R40-40 230 4 0,35

40 9 27,5 R40-31 24 4 0,35


40 9 27,5 R40-31 230 4 0,35

40 9 - R40-22 24 4 0,35
40 9 - R40-22 230 4 0,35

40 9 27,5 R40-04 24 4 0,35


40 9 27,5 R40-04 230 4 0,35

63 14,3 43 R63-40 24 4 0,36


63 14,3 43 R63-40 230 4 0,36

63 14,3 43 R63-31 24 4 0,36


63 14,3 43 R63-31 230 4 0,36

63 14,3 - R63-22 24 4 0,36


63 14,3 - R63-22 230 4 0,36

63 14,3 43 R63-04 24 4 0,36


63 14,3 43 R63-04 230 4 0,36

Auxiliary Contact Block ½ module (8,8mm) for contactor R25 (4p.), R40, R63 (max. 1pc.)

Rated current Type Pack Weight


AC15 AC15 AC1
230V 400V 690V
A A A for contactor pcs. kg/pc. Wiring Diagram

3 2 10 R25 2), R40, R63 RH11 3 0,026

3 2 10 R25-..VM
VM RH11-1 3 0,026

Accessories Type Pack Weight


pcs. kg/pc.

RC-unit 2x for R20.. to R63.. RC-R 230 2 0,05


for 12V to 250V AC
220nF / 100 Ohm
not for R25-..VM

Spacing piece ½ module (8,8mm) P730 10 0,012


for R20.. to R63..
for ambient temperature >40°C
≤ 40°C

40 - 60°C

Sealing cover for R25.. (4p.) P721 10 0,002


Sealing cover for R40.., R63.. P690 10 0,003

1) Sealable with Sealing Cover P690, available aux. contact block RH11
2) AC-operated R25-.., 4-pole

D677E 127
Day-Night Reloading Contactors

Pack Weight
Type pcs. kg/pc. Wiring Diagram

Compact Module, for separate tarif counters 2 modules (35mm)


3-pole 400V 25A R25-TN 230 1 0,22

2 Switch positions:
Day (Reloading, contact 11-14 ... closed, remains in position Night, until the next occurs)
Night (Basis operation) contact 11-12 ... closed

Contactor Module, for double tarif counters 1 module (17,5mm)


2-pole 400V 25A R25-TN20 230 1 0,13

4 Switch position:
Day (Reloading, contact 1-2 ... closed, remains in position Night, until the next occurs)
Night (automatic operation, contact 1-2 ... only at night closed)
On (Permanently On)
Off (permanently Off)

Switch Module 1 module (17,5mm)


2-pole 400V 25A RH25-20 1 0,13

Modular Contactors
Switching of lamps
Lamp Type Power Current Capacitors Max. lamps per pole at 230V 50Hz and max. 60°C
W A μF R20.. R25.. R40.. R63..

Incandescent lamps 60 0,27 - 22 50 92 129


100 0,45 - 13 30 55 77
200 0,91 - 10 15 27 38

300 1,36 - 4 10 19 26
500 2,27 - 3 6 11 16
1000 4,5 - 1 3 6 8

Fluorescent lamps 11 0,16 1,3 60 75 210 310


uncompensated or 18 0,37 2,7 25 30 90 140
serial compensated 24 0,35 2,5 25 30 90 140

36 0,43 3,4 20 25 70 140


58 0,67 5,3 14 17 45 70
65 0,67 5,3 13 16 40 65
85 0,8 5,3 11 14 35 60

Fluorescent lamps 11 0,07 - 2 x 100 2 x 110 2 x 220 2 x 250


dual-connection 18 0,11 - 2 x 50 2 x 55 2 x 130 2 x 200
24 0,14 - 2 x 40 2 x 44 2 x 110 2 x 160

36 0,22 - 2 x 30 2 x 33 2 x 70 2 x 100
58 0,35 - 2 x 20 2 x 22 2 x 45 2 x 70
65 0,35 - 2 x 15 2 x 16 2 x 40 2 x 60
85 0,47 - 2 x 10 2 x 11 2 x 30 2 x 40

Fluorescent lamps 11 0,09 2,0 30 43 67 107


parallel compensated 18 0,13 2 20 32 50 80
24 0,16 3 15 32 50 80

36 0,27 4 10 32 50 80
58 0,45 7 6 18 36 46
65 0,5 7 5 18 36 46
85 0,6 8 4 16 33 44

128 D677E
Modular Contactors
Switching of lamps
Lamp Type Power Current Capacitors Max. lamps per pole at 230V 50Hz and max. 60°C
W A μF R20.. R25.. R40.. R63..

Fluorescent lamps 18 0,09 - 40 40 100 150


with electronic fluorescent 36 0,16 - 20 20 52 75
lamp ballast 58 0,25 - 15 15 30 55
80 0,4 - 7 10 20 30

2 x 18 0,17 - 20 20 50 60
2 x 28 0,25 - 15 15 37 45
2 x 36 0,32 - 10 10 25 30
2 x 58 0,49 - 7 7 15 20
2 x 80 0,7 - 4 4 8 10

Transformers 20 0,09 - 40 52 110 174


for metal halid 50 0,22 - 20 24 50 80
low voltage lamps 75 0,33 - 13 16 35 54
100 0,43 - 10 12 27 43
150 0,65 - 7 9 19 29
200 0,87 - 5 5 14 23
300 1,30 - 3 4 9 14

Mercury-vapour lamps 50 0,61 - 16 21 38 55


(high-pressure lamps), 80 0,8 - 12 16 29 40
uncompensated 125 1,15 - 8 11 20 28
e. g. HQL, HPL
250 2,15 - 4 6 11 15
400 3,25 - 3 4 7 10
700 5,4 - 1 2 4 6
1000 7,5 - 1 1 3 4

Mercury-vapour lamps 50 0,28 7 7 18 36 50


(high-pressure lamps), 80 0,41 8 5 16 31 44
compensated 125 0,65 10 3 13 25 35
e. g. HQL, HPL
250 1,22 18 2 7 14 19
400 1,95 25 1 5 10 14
700 3,45 45 1 3 6 8
1000 4,8 60 - 2 4 6

Metal halide lamps 35 0,53 - 22 24 57 65


uncompensated 70 1 - 12 14 30 35
e. g. HQI, HPI, CDM 150 1,8 - 6 8 17 18

250 3 - 4 5 10 12
400 3,5 - 3 4 8 10
1000 9,5 - 1 1 3 4
2000 16,5 - - - 2 2
400V per pole 2000 10,5 - - - 2 2
3500 18 - - - 1 1

Metal halide lamps 35 0,25 6 8 21 42 58


compensated 70 0,45 12 4 11 21 29
e. g. HQI, HPI, CDM 150 0,75 20 2 7 13 18

250 1,5 33 1 4 9 11
400 2,1 35 1 4 9 10
1000 5,8 95 - 1 3 4
2000 11,5 148 - - 2 2
400V per pole 2000 6,6 58 - - 3 4
3500 11,6 100 - - 2 3

Metal halide lamps 20 0,1 integrated 9 9 18 20


with electronic fluorescent 28 0,15 integriert - - - 18
with electronic fluorescent 35 0,2 integrated 6 6 11 13
lamp ballast (e. g.: PCI) 70 0,36 integrated 5 5 10 12
50-125 x In lamp for 0,6ms 150 0,7 integrated 4 4 8 10

Sodium-vapour lamps 35 1,5 - 7 9 22 30


(low pressure lamps), 55 1,5 - 7 9 22 30
uncompensated 90 2,4 - 4 6 13 19
135 3,3 - 3 4 10 14
150 3,3 - 3 4 10 14
180 3,3 - 3 4 10 14
200 3,3 - 3 4 10 14

D677E 129
Modular Contactors
Switching of lamps
Lamp Type Power Current Capacitors Max. lamps per pole at 230V 50Hz and max. 60°C
W A μF R20.. R25.. R40.. R63..

Sodium-vapour lamps 35 0,31 20 3 6 15 18


(low pressure lamps), 55 0,42 20 2 6 15 18
compensated 90 0,63 30 1 4 10 12

135 0,94 45 1 3 7 8
150 1 40 1 3 8 9
180 1,16 40 1 3 8 9
200 1,32 25 - - 10 12

Sodium-vapour lamps 150 1,8 - 5 8 17 22


(high pressure lamps), 250 3 - 4 5 10 13
uncompensated 330 3,7 - 3 4 8 10
400 4,7 - 2 3 6 8
1000 10,3 - 1 1 3 4

Sodium-vapour lamps 150 0,83 20 2 7 20 25


(high pressure lamps), 250 1,5 33 1 4 12 15
compensated 330 2 40 1 3 10 13
400 2,4 48 1 2 8 12
1000 6,3 106 - 1 4 6

Sodium-vapour lamps 20 0,1 integrated 9 9 18 20


(high pressure lamps) 35 0,2 integrated 6 6 11 13
with serial electronic 70 0,36 integrated 5 5 10 12
(e. g.: PCI) 150 0,7 integrated 4 4 8 10
50-125 x Inlamp for 0,6ms

Data according to IEC60 947-4-1, IEC 60947-5-1, VDE 0660-5-1


2-pole 4-pole
Type R20 R25 R40 R63 R25 R40 R63 RH11

Main Contacts 5) 6) 7)
Rated insulation voltage Ui V~ 440 2) 440 2) 440 2) 440 2) 440 2) 440 2) 440 2) 440 2)
Rated operation voltage Ue V~ 440 440 440 440 440 440 440 440
Frequency of operations zzAC1, AC3 1/h300 300 600 600 300 600 600 600
Mechanical life S x 106 1 1 1 1 1 1 1 1

Utilization category AC1


Rated operational current Ie (=Ith)
open at 60°C A 20 25 40 63 25 40 63 -
Contact life Sx 106 0,1 0,1 0,1 0,1 0,1 0,1 0,1 -
Minimum Switch Voltage V/mA 24/100 24/100 24/100 24/100 24/100 24/100 24/100 17/5
Short time current 10s-current A 72 72 216 240 72 216 240 -
Power loss per pole at Ie/AC1 W 2 3 3 7 2 3 7 0,5

Utilization category AC3 / AC7b


Switching of three-phase motors
Rated operational current Ie A - - - - 9 27 30 -
Rated operational power
of three-phase motors 220V kW - - - - 2,2 7,5 8 -
50-60Hz 230-240V kW - - - - 2,5 8 8,5 -
380-415V kW - - - - 4 12,5 15 -
2-pole motors 230V kW 1,1 1,3 2,6 5 - - - -
Contact life S x 106 0,15 0,15 0,15 0,15 0,15 0,15 0,15 -

Power consumption of coils


AC operated inrush VA 7-9 7-9 20 - 25 33 - 45 33 - 45 -
sealed VA 2,2 - 4,2 2,2 - 4,2 5-7 5-7 4-6 6-8 6-8 -
W 0,8 - 1,6 0,8 - 1,6 1,5 - 2,5 2,6 2,6 -
AC and DC-operated W - - 3-4 - - -

Operation range of coils


in multiples of control voltage Us (-40°--+40°C) 0,85 - 1,1 0,85 - 1,1 0,85 - 1,1 0,85 - 1,1 0,85 - 1,1 0,85 - 1,1 0,85 - 1,1 -

1) Suitable for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): Uimp = 8kV.
2) Suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 4kV.
3) Maximum cable cross-section with prepared conductor
5) Rated frequency 50/60Hz 6) Max. occ. switching overvoltage <4kV 7) Duty cycle: 100%

130 D677E
Modular Contactors
Data according to IEC60 947-4-1, IEC 60947-5-1, VDE 0660-5-1
Type R20 R25 (2p.) R25 (4p.) R25-..VM R40 R63 RH11

Short circuit protection


max. fuse Coordination-type "1"gL (gG) A 35 35 35 35 63 80 -
Rated short circuit current "r" kA 3 3 3 3 3 3 -
"Iq" kA 3 3 10 10 10 10 -

Switching time at control voltage Us ±10%


make time ms 7 - 16 7 - 16 9 - 15 17 - 24 11 - 15 11 - 15 -
release time ms 6 - 12 6 - 12 4-8 17 - 23 6 - 13 6 - 13 -
arc duration ms 10 - 15 10 - 15 10 - 15 10 - 15 10 - 15 10 - 15 -

Cable cross-sections
Main connector solid or stranded mm² 1,5 - 10 1,5 - 10 1,5 - 10 1,5 - 10 2,5 - 25 2,5 - 25 0,5 - 2,5 3)
flexible mm² 1,5 - 6 1,5 - 6 1,5 - 6 1,5 - 6 2,5 - 16 2,5 - 16 0,5 - 2,5 3)
flexible with multicore cable end mm² 1,5 - 6 1,5 - 6 1,5 - 6 1,5 - 6 2,5 - 16 2,5 - 16 0,5 - 1,5
Clamps per pole 1 1 1 1 1 1 2

Magnetic coil solid or stranded mm² 0,75 - 2,5 0,75 - 2,5 0,75 - 2,5 0,75 - 2,5 0,75 - 2,5 0,75 - 2,5 -
flexible mm² 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 0,5 - 2,5 -
flexible with multicore cable end mm² 0,5 - 1,5 0,5 - 2,5 0,5 - 1,5 0,5 - 1,5 0,5 - 1,5 0,5 - 1,5 -
Clamps per pole 1 1 1 1 1 1 -

Auxiliary Contacts 5) 6) 7)
Rated insulation voltage Ui 1) V AC - - 440 2) 440 2) 440 2) 440 2) 440 2)
Thermal rated current Ith 40°C A - - 25 25 40 40 10
Ambient temperature 60°C A - - 25 25 40 40 6

Utilization category AC15


Rated operational 220-240V A - - 3 3 3 3 3
current Ie 380-415V A - - 2 2 2 2 2
440V A - - 1,6 1,6 1,6 1,6 1,6

Utilization category DC13


Rated operational 24-60V A - - 2 2 2 2 2
current Ie 110V A - - 0,4 0,4 0,4 0,4 0,4
per pole 220V A - - 0,1 0,1 0,1 0,1 0,1

Short circuit protection


short-circuit current 1kA,
contact welding not accepted
max. fuse size gL (gG) A - - 10 10 10 10 10

Data according to UL508


Main Contacts (cULus) Type R20 R25 (2p.) R25 (4p.) R40 R63 RH11

Rated operational current "General Use" A 20 25 25 40 63 10

Rated operational power of three-phase motors 110-120V hp - - 1 2 3 -


at 60Hz (3ph) 200-208V hp - - 2 5 7½ -
220-240V hp - - 3 7½ 10 -
265-277V hp - - 3 7½ 10 -

Rated operational power of of AC motors 110-120V hp ½ ½ ½ 1 1½ -


at 60Hz (1ph) 200-208V hp 1 1 1 2 3 -
220-240V hp 1½ 1½ 1½ 3 5 -
265-277V hp 1½ 2 2 3 5 -

Fuses A 40 40 40 80 80 -
Suitable for use on a capability of delivering not more than rms A 5000 5000 5000 5000 5000 -
V 300 300 300 300 300 300

Rated operation voltage V~ 300 300 300 300 300 300

Auxiliary Contacts (cULus) heavy pilot duty AC - - - - - C300

2) Suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 4kV.
3) Maximum cable cross-section with prepared conductor 4) AC7b motor 2-pole 230V 1,1kW
5) Rated frequency 50/60Hz 6) Max. occ. switching overvoltage <4kV 7) Duty cycle: 100%

D677E 131
Modular Contactors
Dimensions
R20-.., R25-.. (2-pole) R25-TN R25-.. (4-pole) (+RH11)
RC-R 230, RH25-20 R25-..VM (+RH11-1)

R40-.. (2-pole) R40-.. (4-pole) (+RH11) Aux. contact block


R63-.. (2-pole) R63-.. (4-pole) (+RH11) RH11, RH11-1

European Representations and Suppliers


Belgium +32 France +32
Teconex Tel: 04 / 355 88 26 Teconex Tel: 04 / 358 85 75
Material Electrique Fax: 04 / 358 21 97 Material Electrique Fax:
Rue de Magnee 108 [email protected] Rue de Magnee 108 [email protected]
B - 4610 Beyne-Heusay www.teconex.eu B - 4610 Beyne-Heusay www.teconex.eu

Bulgaria +359 Germany +49


Schrabul Ltd Tel: 02 / 958 76 54 TVB - ENSYPA GmbH Tel: 040 / 671 02 17-0
Yordan Yovkov Str. 8 Fax: 02 / 958 59 95 Neuer Höltingbaum 36 Fax: 040 / 671 02 17-69
BG - 1408 Sofia [email protected] D - 22143 Hamburg www.tvb-ensypa.com
[email protected]
Schleswig-Holstein, Hamburg, Mecklenburg-Vorpommern, Niedersachsen
Cyprus +357
Messtechnik GmbH Tel: 0341 / 550 16 06
M. Hadjioannou Ltd. Tel: 22 / 348 262 Rudolf Kiesewetter Fax: 0341 / 550 16 09
Electrotechnical & Lighting Specialists Fax: 22 / 430 107 Prager Straße 34 [email protected]
Aegeos 8c, Pallouriotissa [email protected] D - 04317 Leipzig www.kiesewetter-mt.de
CY - Nicosia Representation for Brandenburg, Sachsen-Anhalt, Sachsen, Thüringen

Czech +420 Wagner GmbH Tel: 02058 / 782 800-0


Elektrotechnische Systemlösungen Fax: 02058 / 752 800-49
Schmachtl CZ s.r .o.
s.r.o. Tel: 244 001 500 Robert Bosch Straße 35 [email protected]
Vestec 185 Fax: 244 910 700 D - 42489 Wülfrath www.wagnergmbh.de
252 42 Jesenice u Prahy [email protected] Representation for Nordrhein-Westfalen, Rheinland-Pfalz, Saarland
www.schmachtl.cz
Denmark +45 Wilhelm Becker Tel: 06002 / 992 525 0
Elektrohandelsvertretung Fax: 06002 / 992 525 1
MTO electric a/s Tel: 075 / 800 310 Elisabethenstraße 4 [email protected]
Stiftsvej 14 Fax: 075 / 800 320 D - 61239 Ober-Mörlen www.becker-ehv.de
DK - 7100 Vejle [email protected] Representation for Hessen, Baden-Württemberg
www.mto-electric.dk
SBV - Gawehn GmbH Tel: 09101 / 9099-0
Finland +358 Industrievertretungen Fax: 09101 / 9099-30
Zollnerstraße 2 [email protected]
UTU Powel Oy Tel: 09 / 274 64 128 D - 90579 Langenzenn
Valimotie 26B Fax: 09 / 274 64 141 Representation for Bayern
PL 252 [email protected]
FIN - 01531 Vantaa www.utu.eu

132 D677E
European Representations and Suppliers
Great Britain +44 Romania +40
IMO Precision Controls Ltd. Tel: 020 / 8452 6444 Megatech Trading & Consulting SRL Tel: 21 / 317 05 68
1000 North Circular Road Fax: 020 / 8450 2274 Str. Buzesti 61, Bl.A6, Sc. 1, Et.6 Fax: 21 / 317 05 68
GB - NW2 7JP London [email protected] RO - Bukarest 1 [email protected]
www.imopc.com www.megatech.ro

Greece +30
Russia +7
Geyer Hellas s.a. Tel: 22210 / 987 11
Electrical And Electronic Material Fax: 22210 / 987 12 Torgoviy Dom ChEAZ Tel: 095 / 99 53 100
PO Box 19038 [email protected] ChEAZ Trading House LLC Fax: 095 / 99 53 200
GR - 34100 Drosia-Chalkis www.geyer.gr 16/1ul. Dokukina, [email protected]
Moskau www.cheaz.ru
RU-129226 Russia
Hungaria +36
Dial-Comp GmbH Tel: 01 / 236 0427 DIAL Electrolux Ltd. Tel: 495 / 48 73 350
Keszkeno u. 46/b. Fax: 01 / 236 0430 Bld. 1, Block2, Fl. 7 Fax: 495 / 48 73 654 add. 131
H - 1131 Budapest [email protected] Deguninskaia St., Moscow [email protected]
www.dialcomp.hu RU-127486 Russia www.dialelectrolux.ru

Italy +39 Slowakia +35


SIF sas Tel: 035 / 592 931 DNA Slovakia s.r.o.
s.r.o. Tel: 6400 616
Via del Carraccio 104/1 Fax: 035 / 455 9358 Komaroanska cesta 13 Fax: 6401 907
I - 24040 Stezzano [email protected] 940 43 Nove Zamky [email protected]
www.dnacap.sk

Netherlands +31
Slovenia +386
Hirsch-Driebergen B.V
B.V.. Tel: 0343 / 515 534
Postbus 143 Fax: 0343 / 520 314 TDR T rading
Trading Tel: 02 / 22 94 650
NL - 3970 AC Driebergen [email protected] Cesta k Tamu 8 Fax: 02 / 46 14 450
www.hirsch-driebergen.nl 2000 Maribor [email protected]
www.tdr-trading.si

Norway +47 Spain +34


Gylling Teknikk AS
Teknikk Tel: 67 / 15 14 00 Cydesa Tel: 93 / 656 59 50
P. O. Box 103 Fax: 67 / 15 14 01 Construcciones y Distribuciones, Fax: 93 / 656 65 59
Rudssletta 71 [email protected] Eléctricas, S.A. [email protected]
N - 1351 Rud www.gylling.no C.Poligono Industriel Sant www.cydesa.com
Antoni Parcela 2 Nave A
E - 08620 Sant Vicenc Dels Horts
Poland +48 Barcelona

ASTAT Sp. z o.o. Tel: 61 / 848 88 71 Sweden +46


Ul. Dabrowskiego 441 Fax: 61 / 848 82 76
PL - 60-451 Poznan [email protected] Wallin & Co AB Tel: 8 / 860 102
www.astat,com.pl Götlundagatan 10 Fax: 8 / 997 050
Box 420 [email protected]
S - 12404 Bandhagen www.wallin-co.se
Automatech Sp. z o.o. Tel: 22 / 723 06 62
Ul. Ryzowa 84 Fax: 22 / 723 06 06
PL - 05-816 Opacz-Kolonia [email protected] Switzerland +41
www.automatech.pl
Benedict Swiss AG Tel: 44 / 213 66 00
Grindelstraße 19 Fax: 44 / 213 66 09
Dukat Sp. z o.o. Tel: 422 / 152 571 CH - 8303 Bassersdorf [email protected]
Ul. 20 Stycznia 95/5 Fax: 422 / 152 571 www.benedict-swiss.ch
PL - 95-200 Pabianice [email protected]
www.dukatad.pl
Serbia and Montenegro +381
Portugal +351 Elektro-Koil d.o.o.
Elektro-Koil Tel: 11 / 75 71 906
Ulica Breza 9/13 Fax: 11 / 75 42 931
Jayme da Costa Tel: 22 / 74 70 250 SRJ-11136 Belgrad [email protected]
Mecanica e Electricidade, S.A. Fax: 22 / 76 40 548 www.elektrokoil.rs
Rua de Murraceses, 216 [email protected]
P - 4416 - 901 Pedroso www.jaymedacosta.pt
Turkey +90
Ergun Elektrik Co Ltd. Tel: 232 462 72 00
Kazim Dirik Mahallesi Fax: 232 462 72 04
Sanayi Caddesi No: 66 [email protected]
Bornova, Izmir www.ergunelektrik.com
35100 TURKEY

D677E 133
Oversea Representations and Suppliers
Australia +61 Singapore and Malaysia +65
IMO Pacific Pty Ltd Tel: 08 / 4059 0464 8 Mecomb Singapore Ltd. Tel: 646 98 833
PO Box 1015 Fax: #04-02 Sime Darby Centre Fax: 646 71 905
Joondalup DC, [email protected] 896 Dunearn Road [email protected]
WA 6919 SGP - 589472 Singapore

Bolivia +591 South Africa +27


Agencias Generales S.A. Tel: 04 / 425 10 62 Deebar Tel: 021 / 873 43 32
Calle Bolivar E-520 Fax: 04 / 425 10 61 Mining & Ind. Supplies Fax: 021 / 825 69 84
[email protected] P.O. Box 40325 [email protected]
BO - 0253 Cochabamba www.agsa.com RSA - 2022 Cleveland

Electric Assemblies Tel: 021 / 52 3023


Canada +1 Unit 2A Simplex Ind. Park Fax: 021 / 52 2704
Engine Road, [email protected]
Brook Crompton Ltd. Tel: 0416 / 675 38 44 RSA - 7441 Cape Town
264 Attwell Drive Fax: 0416 / 675 68 85
Toronto, ON [email protected]
CDN - M9W 5B2 www.brookcromtonna.com Syria +963
T. S. Boyadjian Tel: 011 / 221 14 45
Egypt +20 Electrical Equipments Fax: 011 / 221 67 45
Halbouni Street no. 9 [email protected]
Economic Co. Tel: 02 / 592 91 80 P.O. Box 2822
Electrical Commerce & Import Fax: 02 / 590 78 82 SYR - Damaskus
ee, Naguib El-Rihani St. [email protected]
ET - Cairo
Taiwan +886
Hong Kong +852 Vinmajor Enterprise Co., Ltd. Tel: 02 / 2643 6183
8F-2, No. 306, Section 1 Fax: 02 / 8691 6288
Creation Building Services Ta-Tung Road, Hsi-Chih [email protected]
Materials Limited Tel: 2398 2106 Taipei Hsien, Taiwan
5th Floor, Hing Yip Centre Fax: 2191 5808 R.O.C.
37 Beech Street, Tai Kok Tsui [email protected]
HK-Kowloon www.creation-trading.com
Hong Kong - China SAR U.A.E. +971
Doepke International Trading LLC Tel: 4 25 11 123
Kenia +254 Al Ahbabi Building Fax: 4 25 11 322
Al Quasis - Suite 123 info@doepke. ae
G.F. Corvin Ltd. Tel: 02 / 856 06 08 P.O.Box 48767 Dubai www.doepke.ae
P.O. Box 30747 Fax: 02 / 856 19 74
00100 Nairobi [email protected]
Kenia USA +1
B&J USA Inc. Tel: 0800 989 7357
Libanon +961 120-101 North Tech Drive Fax: 919/553 5565
Post Office Box 877 [email protected]
Industrial Technologies. S.A.L. Tel: 1 491 161 Clayton, N.C. 27528 www.bnj-usa.com
Afrah PLAZA Center Fax: 1 491 162
Blvd Fouad Chehab, [email protected]
Sin El Fil, Beirut www.iteclb.com Zimbabwe +263
Star Delta Electrix Tel: 9 / 715 24
Mexico +52 No 2 Bristol Road South Fax: 9 / 764 75
Belmont East [email protected]
B&J USA Inc. Tel: 0800 989 7357 P.O. Box 3592 www.stardelta.net
120-101 North Tech Drive Fax: 919/553 5565 ZW - Bulawayo
Post Office Box 877 [email protected]
Clayton, N.C. 27528 www.bnj-usa.com

New Zealand +64


Eurotec Instruments Ltd. Tel: 09 / 579 1990
P.O.Box 14-543 Panmure Fax: 09 /525 33 34
750 Gt South Rd, Penrose [email protected]
NZ - Auckland www.eurotec.co.nz

134 D677E
Alphabetical Index
Description Type Page Description Type Page

A dditional Terminals for Contactors LG.. 37 Electronic Timer K3-T180 35


for D.O.L. Starters LG.. 97 Electronic Timer Off-delay K2-TA.. 35
for Star-Delta Starters LG.. 77 Electronic Timer On-delay K2-TE.. 35
for Thermal Overload Relays LG.. 105 Electronic Timer for Star-Delta Starters Y9.. 77
Auxiliary Contact Blocks for Contactors K1-07 HK.. 8 Enclosures for Contactors P1 97
for Contactors K1-09, -12 HKM.. 10, 14 Enclosures for D.O.L. Starters P1R 97
for Contactors K3 HA.. 22, 34
for Contactors K3 HB11 34 F eeder Groups for Contactors K3 K3-../FG... 40
for Contactors K3 HN.. 22, 34 Fourth Pole for Contactors K3 NP.. 37
for Contactors K3 HK.. 34 Fuse Holders K2-F 36
for Contactors R.. RH11 117
H eating Element for D.O.L. Starters K2-HR 97
Busbar Sets for Thermal Overload Relays SU840/... 99
Indicator Units, Coil Current Indicator K2-IN. 36, 97
Capacitor Switching Contactors K3-18K.. 33 Indicator Units, Lens Caps for Indicator Units LG9743.. 97
K3-24K.. 33 Indicator Units, Voltage Indicator K2-UN. 36, 97
K3-32K.. 33 Interface K2-IM 36
K3-50K.. 33
K3-62K.. 33 Latch K2-L.. 36
K3-74K.. 33
K3-90K.. 33 Marking Systems for Contactors LG.., P... 38
K3-115K.. 33 Mechanical Interlock LG.. 37
Coil Voltage Ranges for Contactors K1 12 Mini Contactor Relays K1-07D.. 8
for Contactors K3 39 Mini Contactors K1-09.. 10
Contactor Relays, AC Operated K3-07.. 20, 21 K1-12D.. 10
Contactor Relays, DC Operated KG3-07A.. 21 K1-09F.. 12
Contactors, AC and DC Operated K3-10A.. 30, 31 K1-09L.. 12
K3-14A.. 30, 31 Mini Reversing Starters K1W09D.. 14
K3-18A.. 30, 31 K1W12D.. 14
K3-22A.. 30, 31 K1W09L.. 14
K3-24A.. 30, 31 Modular Contactors R20.. 116
K3-32A.. 30, 31 R25.. 116
K3-40A.. 30, 31 R40.. 116
K3-50A.. 30, 31 R63.. 116
K3-62A.. 30, 31 Momentary Contacts for Contactors K2 HTN.. 34
K3-74A.. 30, 31 Mounting Bar for Electronic Timer Y9.. LG7735 77
K3-90A.. 30, 31 Mounting Parts for Contactors K2-..SM, P... 36, 38
K3-115A.. 30, 31
K3-151A.. 30, 31 Parallel Connectors LG.. 38
K3-176A.. 30, 31 Pole Changing Starters Open Type K3PU.. 80
K3-210A.. 30, 31 Pole Changing Starters Steel Sheet Enclosed K3PU..B 80
K3-260A.. 30, 31
K3-316A.. 30, 31 Rectifier with Fuse Holder K2-RF. 36
K3-450A.. 30, 31 Reversing Starters Connector K1W-VB 14
K3-550A.. 30, 31 K3W-VB.. 78
K3-700A.. 30, 31 Reversing Starters Open Type K3WU.. 78
K3-860A.. 30, 31 KW3-.. 80
K3-1000A.. 30, 31 Reversing Starters Steel Sheet Enclosed K2WU..B 78
K3-1200A.. 30, 31
Contactors, DC Solenoid Operated KG3-10A.. 31 Sets for Single Mounting Thermal Overload Relays U12SM 105
KG3-14A.. 31 U3/32SM 105
KG3-18A.. 31 U3/42G 105
KG3-22A.. 31 Spare Contacts for Contactors EK../.. 42
KG3-24A00 32 Spare Coils for Contactors K../4.. 40, 41
KG3-32A00 32 Star-Delta Starter Connector K3Y-VB.. 77
KG3-40A00 32 Star-Delta Starters Open Type K3Y.. 74
Contactors 4-pole K3-10A00-40 32 Star-Delta Starters Plastic Enclosed Type K3Y..P 76
K3-14A00-40 32 Star-Delta Starters Steel Sheet Enclosed Type K3Y..B 76
K3-18A00-40 32 Suppressor Units, RC-units RC-K1 10
K3-22A00-40 32 RC-units RC-K3 38
K2-23A00-40 32 RC-units RC-R.. 117
K2-30A00-40 32
K2-37A00-40 32 T erminal Block (2 term. insulated) f. Contactors K2 K2-SK 34
K2-45A00-40 32 Terminal Block (2 term. interconn.) f. Contactors K2 K2-DK 34
K2-60A00-40 32 Terminal Covers for Contactors LG.. 37
K3-116A00-40 32 Thermal Overload Relays U12/16A .. K1 102
K3-151A00-40 32 U12/16E .. K1 102
K3-176A00-40 32 U12/16EQ .. K1 102
K3-210A00-40 32 U12/16E .. K3 103
K3-260A00-40 32 U12/16EQ .. K3 103
K3-316A00-40 32 U3/32 .. 74,103
U3/42 .. 74,103
D .O.L. Starters with Start-Stop Push Buttons P1T, K2U..PT 96 U3/74 .. 75,104
D.O.L. Starters with Selector Switch P1W, K2U..PW 96 U85 .. 75,104
D.O.L. Starters with Selector and Pneumatic Switch P1W18P 96 U180 .. 75,104
U320 .. 104
U800 .. 104
with Slow Tripping Characteristic UAT.. 104

D677E 135
Notice

136 D677E