APPLICATIONS
The Hochiki ALN-V Photoelectric Smoke Sensor is particularly
suited to detecting optically dense smoke typical of fires
involving materials such as soft furnishings, plastic, foam or
other similar materials which tend to smolder and produce
large visible smoke particles. Hochiki's unique design allows
fast response to flaming fires as well as smoldering fires while
preventing false alarms.
OPERATION
The detection chamber consists of a light-emitting diode
STANDARD FEATURES (LED) and photodiode arrangement. The chamber is designed
Low profile - only 2.00" high, including base such that light emitted by the LED cannot normally reach the
photo diode. In the event of fire, particles of smoke enter the
Simple and reliable device addressing chamber and scatter the light. As the smoke level increases,
the scattering effect increases, causing more light to hit the
Automatic compensation for sensor contamination photodiode. The chamber contains a unique baffle design
Built-in fire test feature which allows smoke to enter the chamber while preventing
external light from affecting the photodiode. The photodiode
Uses the noise-immune Digital Communication input level is sampled to sense smoke density.
Protocol (DCP), which utilizes interrupts for fast
response to fires When the smoke density exceeds a preset threshold the
sensor transmits an interrupt to the fire control panel indicat-
Two built-in power/alarm LEDs ing a fire condition. The fire alarm control panel can adjust the
sensor threshold to compensate for contamination.
Programmable non-polling LEDs
Up to 127 devices are permitted on each SLC loop. A sensor
Non-directional smoke chamber address is set by a hand-held programming unit. The sensor
Vandal resistant security locking feature mounts to an electronics-free base and incorporates a locking
mechanism for secure installation. The base provides mount-
Removable smoke labyrinth for cleaning or ing slots, terminals for field wiring and a third contact for a
replacement remote indicator/LED. The sensor incorporates dual LEDs for
SPECIFICATIONS easy viewing of sensor status.
Operating Voltage 17-41 VDC SENSOR SPACING
Standby Current 450μA
Smoke sensor spacing shall be in compliance with NFPA 72.
Alarm Current 540μA For smooth ceilings and in the absence of specific perfor-
Transmission Method DCP - Digital Communication Protocol mance-based design criteria, the distance between smoke
Maximum Humidity 95% RH Non-Condensing sensors shall not exceed a nominal spacing of 30 ft. (9.1m) or
UL Temperature Range 32°F to 115°F all points on the ceiling shall have a sensor within a distance
(0° C to 47° C) equal to or less than 0.7 times the nominal 30 ft. (9.1m)
spacing. Sensors shall be located within a distance of one-half
Operating Temperature 14°F to 122°F
the nominal spacing, measured at right angles from all walls
Range (-10°C to 50°C) or partitions extending upward to within the top 15 percent of
Sensitivity Range 0.7-4.0%/FT@300FPM the ceiling height. For additional instructions see NFPA 72.
0.7-3.86%/FT@2000FPM
0.7-2.65%/FT@4000FPM
PRODUCT LISTINGS
Air Velocity Range 0-4000 fpm
Color & Case Material Bone - ABS Blend California State
Weight 3.4oz (5.1 oz. with 4” base) Fire Marshal
Bases YBN-NSA-4, HSB-NSA-6, 7272-0410:0204
ASB, SCI-B4, SCI-B6, ASBL S1383 3054858
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install Hochiki’s ALN-V (Photoelectric Sensor) as indicated on the plans. The combination sensor
head and twist lock base is UL Listed and it’s compatible with an UL Listed fire alarm control panel.
The base permits direct interchange with the Hochiki AIE-EA ionization type smoke sensor, ALG-V, ALK-V/ALK-V2 photoelectric
type smoke sensors, ATG-EA, ATJ-EA heat sensors and the ACA-V, ACC-V multi-criteria sensors.
The sensitivity of the sensor is capable of being measured by the control panel.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature is
optional and can be implemented when required.
BASES
The Hochiki HSB-NSA-6 and the YBN-NSA-4 mounting bases are electronics free and are a simple rugged design with screw
terminals for wiring connections. A common mounting base allows sensor interchange and maintains loop continuity when
sensors are removed. A simple anti-tamper head locking system is provided which is enabled by removing a small plastic tab on
the back of the sensor. Once locked, the head can be removed using a small diameter screwdriver.
UL LISTED
POWER
LIMITED
SUPPLY
* HSB-NSA-6
8mA MAX. 8mA MAX.
OUTPUT OUTPUT
*-OPTIONAL WIRING CONFIGURATION FOR REMOTE OUTPUT
UL LISTED
COMPATIBLE
CONTROL
PANEL
8mA MAX.
OUTPUT
UL LISTED
POWER YBN-NSA-4
LIMITED
SUPPLY * 8mA MAX.
OUTPUT
NOTE: Fire alarm control panel compatibility is required for DCP products. DCP communications protocol allows system
components (DCP sensors AIE-EA, ALG-V, ACA-V, ACC-V, ALK-V, ALN-V, ATJEA and ATG-EA, bases and modules)
to be used concurrently on a system's SLC (Signaling Line Circuit).
Hochiki America Corporation ALN-V Photoelectric Smoke Sensor Specifications subject to change without notice.