650 Series ANSI: Operation Manual
650 Series ANSI: Operation Manual
The software and hardware described in this document is furnished under a license and
may be used or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB Inc.
1021 Main Campus Drive
Raleigh, NC 27606, USA
Toll Free: 1-800-HELP-365, menu option #8
ABB Inc.
3450 Harvester Road
Burlington, ON L7N 3W5, Canada
Toll Free: 1-800-HELP-365, menu option #8
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2006/95/EC). This
conformity is the result of tests conducted by ABB in accordance with the product
standards EN 50263 and EN 60255-26 for the EMC directive, and with the product
standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is
designed in accordance with the international standards of the IEC 60255 series and
ANSI C37.90. The DNP protocol implementation in the IED conforms to "DNP3
Intelligent Electronic Device (IED) Certification Procedure Subset Level 2", available
at www.dnp.org .
Safety information
Dangerous voltages can occur on the connectors, even though the
auxiliary voltage has been disconnected.
Table of contents
Section 1 Introduction............................................................................5
This manual..............................................................................................5
Intended audience....................................................................................5
Product documentation.............................................................................6
Product documentation set..................................................................6
Document revision history...................................................................7
Related documents..............................................................................8
Symbols and conventions.........................................................................9
Symbols...............................................................................................9
Document conventions......................................................................10
Functions included in 650 series IEDs..............................................11
Logging on.........................................................................................41
Logging off.........................................................................................44
Turning the display backlight on........................................................45
Selecting local or remote use............................................................45
Identifying the device.........................................................................46
Adjusting the display contrast............................................................47
Changing the local HMI language.....................................................48
Navigating in the menu......................................................................48
Menu structure..............................................................................49
Scrolling the display......................................................................49
Changing the default view............................................................50
Using function buttons.......................................................................50
Using the single-line diagram............................................................51
Browsing setting values.....................................................................52
Editing values....................................................................................54
Editing numerical values...............................................................54
Editing string values.....................................................................55
Editing enumerated values...........................................................56
Changing time settings in LHMI....................................................56
Saving settings..................................................................................56
Clearing and acknowledging.............................................................57
Using the local HMI help....................................................................58
Measured values..........................................................................67
Using the local HMI for monitoring...............................................67
Recorded data...................................................................................67
Creating disturbance recordings...................................................67
Monitoring disturbance recorder data...........................................68
Controlling and uploading DFR recorder data..............................69
Monitoring events.........................................................................70
Remote monitoring............................................................................70
Monitoring the IED remotely.........................................................71
Controlling...............................................................................................71
Controlling circuit breakers and disconnectors..................................71
Resetting the IED....................................................................................73
Clearing and acknowledging via the local HMI..................................73
Changing the IED functionality...............................................................74
Defining the setting group..................................................................74
Activating a setting group.............................................................74
Browsing and editing setting group values...................................76
Activating LEDs.................................................................................78
Section 8 Glossary..............................................................................91
Section 1 Introduction
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for monitoring, controlling and
setting the IED. The manual also describes how to identify disturbances and how to
view calculated and measured power grid data to determine the cause of a fault.
This manual addresses the operator, who operates the IED on a daily basis.
The operator must be trained in and have a basic knowledge of how to operate
protection equipment. The manual contains terms and expressions commonly used to
describe this kind of equipment.
Decommissioning
Commissioning
Maintenance
Engineering
Operation
Installing
Engineering manual
Installation manual
Commissioning manual
Operation manual
Service manual
Application manual
Technical manual
Communication protocol
manual
en07000220.vsd
IEC07000220 V1 EN
The engineering manual contains instructions on how to engineer the IEDs using the
different tools in PCM600. The manual provides instructions on how to set up a
PCM600 project and insert IEDs to the project structure. The manual also recommends
a sequence for engineering of protection and control functions, LHMI functions as well
as communication engineering for IEC 60870-5-103, IEC 61850 and DNP3.
The installation manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are
organized in chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED. The
manual can also be used by system engineers and maintenance personnel for assistance
during the testing phase. The manual provides procedures for checking of external
circuitry and energizing the IED, parameter setting and configuration as well as
verifying settings by secondary injection. The manual describes the process of testing
an IED in a substation which is not in service. The chapters are organized in
chronological order in which the IED should be commissioned.
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for monitoring, controlling and
setting the IED. The manual also describes how to identify disturbances and how to
view calculated and measured power grid data to determine the cause of a fault.
The service manual contains instructions on how to service and maintain the IED. The
manual also provides procedures for de-energizing, de-commissioning and disposal of
the IED.
The application manual contains application descriptions and setting guidelines sorted
per function. The manual can be used to find out when and for what purpose a typical
protection function can be used. The manual can also be used when calculating settings.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during normal
service.
The point list manual describes the outlook and properties of the data points specific to
the IED. The manual should be used in conjunction with the corresponding
communication protocol manual.
1.4.1 Symbols
The warning icon indicates the presence of a hazard which could result
in personal injury.
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push
button icons.
To navigate between the options, use and .
• HMI menu paths are presented in bold.
Select Main menu/Settings.
• LHMI messages are shown in Courier font.
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set an own signal name in
PCM600.
• The * character after an input or output signal name in the function block symbol
given for a function, indicates that the signal must be connected to another
function block in the application configuration to achieve a valid application
configuration.
• Dimensions are provided both in inches and mm. If it is not specifically mentioned
then the dimension is in mm.
Differential protection
T2WPDIF 87T Transformer differential protection, two winding
T3WPDIF 87T Transformer differential protection, three winding
REFPDIF 87N Restricted ground fault protection, low impedance
HZPDIF 87 1Ph High impedance differential protection
GENPDIF 87G Generator differential protection
Impedance protection
ZQMPDIS 21 Five-zone distance protection, Quadrilateral and Mho characteristic
FDPSPDIS 21 Phase selection with load enchroachment, quadrilateral characteristic
FMPSPDIS 21 Faulty phase identification with load enchroachment for mho
ZDARDIR 21 Additional distance protection directional function for ground faults
ZDNRDIR 21 Directional impedance quadrilateral and mho
PPLPHIZ Phase preference logic
ZMRPSB 68 Power swing detection
ZCVPSOF Automatic switch onto fault logic, voltage-and current-based
ZGCPDIS 21G Underimpedance protection for generators and transformers
LEXPDIS 40 Loss of excitation
OOSPPAM 78 Out-of-step protection
LEPDIS Load enchroachment
Current protection
PHPIOC 50 Instantaneous phase overcurrent protection
SPTPIOC 50 Instantaneous phase overcurrent protection
OC4PTOC 51/67 Four-step phase overcurrent protection
OC4SPTOC 51/67 Four-step phase overcurrent protection
EFPIOC 50N Instantaneous residual overcurrent protection
EF4PTOC 51N/67N Four-step directional residual overcurrent protection
SDEPSDE 67N Sensitive directional residual overcurrent and power protection
Table continues on next page
Control
SESRSYN 25 Synchrocheck, energizing check and synchronizing
SMBRREC 79 Autorecloser
STBRREC 79 Autorecloser
Table continues on next page
Station communication
IEC61850-8-1 IEC61850 communication protocol
DNPSER DNP3.0 for serial communication EIA485
DNPGEN DNP3.0 for TCP/IP communication protocol
RS485DNP DNP3.0 for EIA-485 communication protocol
DNPFREC DNP3.0 fault records for TCP/IP communication protocol
CH1TCP - CH4TCP DNP3.0 for TCP/IP communication protocol
OPTICALDNP DNP3.0 for TCP/IP communication protocol
MSTSERIAL DNP3.0 for optical RS-232 communication protocol
MST1TCP - MST4TCP DNP3.0 for serial communication protocol
RS485GEN RS485
OPTICALPROT Operation selection for optical serial
RS485PROT Operation selection for RS485
DNPFREC DNP3.0 fault records for TCP/IP communication protocol
GOOSEINTLKRCV Horizontal communication via GOOSE for interlocking
GOOSEBINRCV GOOSE binary receive
GOOSEVCTRCONF GOOSE VCTR configuration for send and receive
VCTRSEND Voltage control sending block for GOOSE
GOOSEVCTRRCV Voltage control receiving block for GOOSE
ETHFRNT Ethernet configuration of front port, LAN1 port and gateway
ETHLAN1
GATEWAY
GOOSEDPRCV GOOSE function block to receive a double point value
GOOSEINTRCV GOOSE function block to receive an integer value
GOOSEMVRCV GOOSE function block to receive a measurand value
GOOSESPRCV GOOSE function block to receive a single point value
Scheme communication
ZCPSCH 85 Scheme communication logic with delta based blocking scheme signal transmit
ZCRWPSCH 85 Current reversal and weak end infeed logic for distance protection
ZCWSPSCH 85 Current reversal and weak end infeed logic for distance protection
ZCLCPLAL Local acceleration logic
ECPSCH 85 Scheme communication logic for residual overcurrent protection
ECRWPSCH 85 Current reversal and weak end infeed logic for residual overcurrent protection
Sustainability has been taken into account from the beginning of the product design
including the pro-environmental manufacturing process, long life time, operation
reliability and disposing of the IED.
The choice of materials and the suppliers have been made according to the EU RoHS
directive (2002/95/EC). This directive limits the use of hazardous substances which are
the following:
Operational reliability and long life time have been assured with extensive testing
during the design and manufacturing processes. Moreover, long life time is supported
by maintenance and repair services as well as by the availability of spare parts.
Design and manufacturing have been done under a certified environmental system. The
effectiveness of the environmental system is constantly evaluated by an external
auditing body. We follow environmental rules and regulations systematically to
evaluate their effect on our products and processes.
All parts used in this product are recyclable. When disposing of an IED or its parts
contact a local waste handler who is authorized and specialized in disposing electronic
waste. These handlers can sort the material by using dedicated sorting processes and
dispose of the product according to the local requirements.
1) Polycarbonate
2) Liquid crystal polymer
ANSI12000175 V1 EN
3.1.1 Display
The LHMI includes a graphical monochrome display with a resolution of 320 x 240
pixels. The character size can vary.
GUID-97DA85DD-DB01-449B-AD1F-EEC75A955D25 V2 EN
1 Path
2 Content
3 Status
4 Scroll bar (appears when needed)
• The path shows the current location in the menu structure. If the path is too long to
be shown, it is truncated from the beginning, and the truncation is indicated with
three dots.
• The content area shows the menu content.
• The status area shows the current IED time, the user that is currently logged in and
the object identification string which is settable via the LHMI or with PCM600.
• If text, pictures or other items do not fit in the display, a vertical scroll bar appears
on the right. The text in content area is truncated from the beginning if it does not
fit in the display horizontally. Truncation is indicated with three dots.
GUID-1ECF507D-322A-4B94-B09C-49F6A0085384 V1 EN
The number before the function instance, for example 1:ETHFRNT, indicates the
instance number.
The display is updated either cyclically or based on changes in the source data such as
parameters or events.
The function button panel shows on request what actions are possible with the function
buttons. Each function button has a LED indication that can be used as a feedback
signal for the function button control action. The LED is connected to the required
signal with PCM600.
ANSI12000025-1-en.vsd
ANSI12000025 V1 EN
The alarm LED panel shows on request the alarm text labels for the alarm LEDs.
GUID-D20BB1F1-FDF7-49AD-9980-F91A38B2107D V1 EN
The function button and alarm LED panels are not visible at the same time. Each panel
is shown by pressing one of the function buttons or the Multipage button. Pressing the
ESC button clears the panel from the display. Both the panels have dynamic width that
depends on the label string length that the panel contains.
3.1.2 LEDs
The LHMI includes three protection status LEDs above the display: Normal, Pickup
and Trip.
There are 15 programmable alarm LEDs on the front of the LHMI. Each LED can
indicate three states with the colors: green, yellow and red. The alarm texts related to
each three-color LED are divided into three pages and can be browsed with the
Multipage button.
There are 3 separate pages of LEDs available. The 15 physical three-color LEDs in one
LED group can indicate 45 different signals. Altogether, 135 signals can be indicated
since there are three LED groups. The LEDs can be configured with PCM600 and the
operation mode can be selected with the LHMI or PCM600.
There are two additional LEDs which are embedded into the control buttons and
. They represent the status of the circuit breaker.
3.1.3 Keypad
The LHMI keypad contains push-buttons which are used to navigate in different views
or menus. With the push-buttons you can give open or close commands to one primary
object, for example, a circuit breaker, disconnector or an grounding switch. The push-
buttons are also used to acknowledge alarms, reset indications, provide help and switch
between local and remote control mode.
The keypad also contains programmable push-buttons that can be configured either as
menu shortcut or control buttons.
ANSI11000247 V1 EN
Figure 7: LHMI keypad with object control, navigation and command push
buttons and RJ-45 communication port
Object control
If the control position of the IED is set to local with the R/L button, the IED can be
controlled using the object control buttons.
Navigation
The arrow buttons are used for navigation. To scroll information, press the arrow
button several times or simply keep it pressed down.
• Activating the authorization procedure, when the user is not logged in.
Key • Logging out, when the user is currently logged in.
Commands
Table 10: Command push-buttons
Name Description
• Moving directly to Main menu, if currently
Menu
in any other menu or view.
• Moving to the default view, if currently in
Main menu.
Function buttons
Table 11: Function buttons
Name Description
Executing the defined function: OFF, menu short cut or binary control.
Function
button
Protection indicators
The protection indicator LEDs are Normal, Pickup and Trip.
• If several protection functions Pickup within a short time, the last Pickup
is indicated on the display.
Flashing A flashing yellow LED has a higher priority than a steady yellow LED.
The IED is in test mode and protection functions are blocked.
• The indication disappears when the IED is no longer in test mode and
blocking is removed.
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An individual
alarm/status signal, connected to any of the LED function blocks, can be assigned to
one of the three LED colors when configuring the IED.
The LHMI is used to access the IED parameters. Three types of parameters can be read
and written.
• Numerical values
• String values
• Enumerated values
Numerical values are presented either in integer or in decimal format with minimum
and maximum values. Character strings can be edited character by character.
Enumerated values have a predefined set of selectable values.
• The green uplink LED on the left is lit when the cable is successfully connected to
the port.
GUID-D71BA06D-3769-4ACB-8A32-5D02EA473326 V1 EN
1 RJ-45 connector
2 Green indicator LED
When a computer is connected to the IED front port with a crossed-over cable, the
IED's DHCP server for the front interface assigns an IP address to the computer if
DHCPServer = Enabled. The default IP address for the front port is 10.1.150.3.
Do not connect the IED front port to a LAN. Connect only a single
local PC with PCM600 to the front port.
Single-line diagram is used for bay monitoring and/or control. It shows a graphical
presentation of the bay which is configured with PCM600.
ANSI11000181 V1 EN
ANSI11000180 V1 EN
ANSI11000182 V1 EN
3.2 Authorization
The user categories with different access rights are predefined in the IED .
The IED users can be created, deleted and edited only with PCM600. One user can
belong to one or several user categories.
At delivery, the IED user has full access as SuperUser until users are
created with PCM600. Logging on is not required for the LHMI.
3.3 Communication
All operational information and controls are available through these protocols.
However, some communication functionality, for example, horizontal communication
(GOOSE) between the IEDs, is only enabled by the IEC 61850-8-1 communication
protocol.
The serial communication follows the EIA-485 standard and is intended to be used in
multi-point communication.
Disturbance files are accessed using the IEC 61850 or IEC 60870-5-103 protocols.
Disturbance files are also available to any Ethernet based application in the standard
COMTRADE format. The IED can send binary signals to other IEDs (so called
horizontal communication) using the IEC 61850-8-1 GOOSE (Generic Object Oriented
Substation Event) profile. Binary GOOSE messaging can, for example, be employed
for protection and interlocking-based protection schemes. The IED meets the GOOSE
performance requirements for tripping applications in distribution substations, as
defined by the IEC 61850 standard. Further, the IED supports the sending and
receiving of analog values using GOOSE messaging. Analog GOOSE messaging
enables fast transfer of analog measurement values over the station bus, thus
facilitating for example sharing of RTD input values, such as surrounding temperature
values, to other IED applications. The IED interoperates with other IEC 61850
compliant IEDs, tools and systems and simultaneously reports events to five different
clients on the IEC 61850 station bus. For a system using DNP3 over TCP/IP, events
can be sent to four different masters. For systems using IEC 60870-5-103 IED can be
connected to one master in a station bus with star-topology.
All communication connectors, except for the front port connector, are placed on
integrated communication modules. The IED is connected to Ethernet-based
communication systems via the RJ-45 connector (10/100BASE-TX) or the fibre-optic
multimode LC connector (100BASE-FX).
IEC 60870-5-103 is available from optical serial port where it is possible to use serial
glass fibre (ST connector).
The IED supports SNTP, DNP3 and IRIG-B time synchronization methods with a time-
stamping resolution of 1 ms.
The IED supports the following time synchronization methods with a timestamping
resolution of 1 ms:
Protection and Control IED Manager PCM600 offers all the necessary functionality to
work throughout all stages of the IED life cycle.
• Planning
• Engineering
• Commissioning
• Operation and disturbance handling
• Functional analysis
When using PCM600 for writing to the IED, ensure that the LHMI is
not in a menu position where settings can be made. Only one active
transaction, from LHMI or PCM600, is allowed at a time.
With the individual tool components, you can perform different tasks and functions
and control the whole substation. PCM600 can operate with many different topologies,
depending on the customer needs.
A connectivity package includes all of the data which is used to describe the IED. For
example it contains a list of what parameters exist, which data format is used, the units,
the setting range, the access rights and visibility of the parameter. In addition it
contains code which allows software packages that consume the connectivity package
to properly communicate with the IED. It also allows for localization of text even when
its read from the IED in a standard format such as COMTRADE.
Update Manager is a tool that helps in defining the right connectivity package versions
for different system products and tools. Update Manager is included with products that
use connectivity packages.
Be sure that the user logged on to the IED has the access required when
writing particular data to the IED from PCM600. For more information
about setting user access rights see the PCM600 documentation.
• R= Read
• W= Write
• - = No access rights
The IED users can be created, deleted and edited only with the User Management Tool
(UMT) within PCM600. The user can only Logon or Logoff on the local HMI on the
IED, there are no users, groups or functions that can be defined on local HMI.
At delivery, the IED has a default user defined with full access rights. PCM600 use this
default user to access the IED. This user will automatically be removed in IED when
users are defined via User Management Tool (UMT) in PCM600.
Password: Administrator
To setup an IP firewall the following table summarizes the IP ports used in the 650
series. The ports are listed in ascending order. The column “Default state” defines
whether a port is open or closed by default. All ports that are closed by default are
opened by configuration enabling.
The 650 series supports two Ethernet communication protocols, these protocols are
IEC61850 and DNP3/TCP. These communication protocols are enabled by
configuration. This means that the IP port is closed and not available if the
configuration of the 650 series doesn't contain a communication line of the protocol. If
a protocol is configured the corresponding IP port is open all the time.
See the 650 series technical manual and the corresponding protocol
documentation on how to configure a certain communication protocol
for the 650 series.
• The IP port used for file transfer (default port 21) is fixed and cannot be changed.
• The IP port used for DHCP (default port 67) between the IED and a computer is
fixed and cannot be changed.
• The IP port used for IEC61850 (default port 102) is fixed and can not be changed.
• The IP ports used for DNP3 are configurable. The communication protocol DNP3
could operate on UDP (default port 20 000) or TCP (default port 20 000). It is
defined in the configuration which type of Ethernet communication is used. Only
one type is possible for a specific configuration.
Two ports are used by PCM600; for configuration and parameter settings the IP port
for a proprietary ODBC protocol is used (port 2100), the port is fixed and cannot be
changed. For monitoring events and clear commands the IP port for a proprietary SPA
protocol is used (port 7001), the port is fixed and cannot be changed.
These security constraints are acceptable in limited local networks. For wide area
networks in particular with connection to the Internet, the 650 series Ethernet
communication must be protected against illegal access. This protection must be
handled by external devices to setup a secure virtual private network (VPN).
ANSI12000172-1-en.vsd
ANSI12000172 V1 EN
IEC12000171-1-en.vsd
IEC12000171 V1 EN
At delivery, logging on is not required and the user has full access until users and
passwords are created with PCM600 and written into the IED.
Commands, changing parameter values and resetting indications, for example, are
actions requiring password when the password protection is activated. Reading
information on the LHMI is always allowed without password.
Do not switch off the auxiliary power supply to the IED before
changes, for example, setting parameter or local/remote control state
changes are saved.
A mechanism for limiting the number of writings per time period is included in the
IED to prevent the flash memory to be worn out due to too many writings. As a
consequence it may take up to an hour to save changes. If the auxiliary power is
interrupted before a change is saved, that change is lost.
4.1.1 Logging on
IEC12000161-1-en.vsd
IEC12000161 V1 EN
3. Enter the password when prompted digit by digit and select OK.
• Activate the digit to be entered with and .
• Enter the character with and .
Upper and lower case letters are also found by scrolling the 255 characters with
and .
IEC12000157-1-en.vsd
IEC12000157 V1 EN
IEC12000158-1-en.vsd
IEC12000158 V1 EN
The logon dialog will open if the attempted operation requires another
level of user rights.
Once a user is created and written into the IED, logon is possible with
the password assigned in the tool. If there is no user created, an attempt
to log on causes the display to show a corresponding message.
IEC12000160-1-en.vsd
IEC12000160 V1 EN
1. Press .
2. To confirm logoff, select Yes and press .
IEC12000159-1-en.vsd
IEC12000159 V1 EN
If the panel has not been used for a predefined timeout period, the backlight is switched
off. The user is logged out from the current user level after the display backlight has
turned off. The factory default for display timeout is 60 minutes.
The display returns to the default view and all unconfirmed operations, for example
parameter editing and breaker selection are cancelled.
LHMI. In remote position, control operations are possible only from a higher level,
that is from a control center.
• Press .
• When the L LED is lit, local control is enabled and remote control disabled.
• When the R LED is lit, remote control is enabled and local control disabled.
• When neither of the LEDs is lit, both control positions are disabled.
GUID-B576428B-C6B0-44C1-9F03-452F132BCEAF V1 EN
IEC10000338 V3 EN
The display contrast is not stored in any memory if changed using the
keys from local HMI. After an auxiliary power failure, the display
contrast is restored to set value for parameter ContrastLevel.
GUID-74F4A0C6-C7E6-4456-8824-1639BCCC7896 V1 EN
The Main menu contains main groups which are divided further into more detailed
submenus.
• Control
• Events
• Measurements
• Disturbance records
• Settings
• Configuration
• Diagnostics
• Tests
• Clear
• Languages
If a menu contains more rows than the display can show at a time, a scroll bar is
displayed on the right.
GUID-941D3A33-21D3-4734-9AAA-CE06FC311F00 V2 EN
The default view of the display is Main menu unless set otherwise.
GUID-11D6D98C-A2C9-4B2C-B5E0-FF7E308EC847 V1 EN
GUID-28771BAD-A125-4319-9DCA-6274D9F16D26 V1 EN
Select the single-line diagram for the default view in Main menu/
Configuration/HMI/Screen/1:SCREEN/DefaultScreen.
A080004 V2 EN
A071198 V2 EN
6. To browse the settings, scroll the list with and and to select a setting press
. To move back to the list, press .
GUID-74F4A0C6-C7E6-4456-8824-1639BCCC7896 V1 EN
GUID-B3180332-3CDC-44A7-88F1-68D07BCA23C5 V2 EN
For parameters with defined steps, digits smaller than the step
value cannot be edited.
After pressing , the previous value can be restored by pressing once, and
vice versa. Another press of or sets the value to the lower or higher limit.
The symbol in front of the value is ↕, when the previous value is shown.
GUID-315CA4B1-AE03-4B45-8921-B10D28CA75B4 V2 EN
If there is a need to change the time setting in the LHMI (Main menu/Configuration/
Time) the change will take affect immediately. To confirm the new setting press .
To remove the change, press .
A071206 V2 EN
Pressing Cancel in the Save changes dialog closes only the Save
changes dialog box, but the IED remains in editing mode. All the
changes applied to any setting are not lost and the user can continue to
change settings. To leave the change setting mode, select No or Yes in
the Save changes dialog.
GUID-E4D9067B-1168-4287-9EF3-E251C6D13C4C V3 EN
The content of the Clear menu depends on the configuration configured with
PCM600.
2. Select the item to be cleared with or .
3. Press , select OK to confirm the selection or Cancel to cancel the selection,
and press .
4. Repeat steps 2 and 3 to clear other items.
In a normal IED use situation, the basic operation includes monitoring and checking
procedures.
• Monitoring measured values
• Checking object states
• Checking function setting parameters
• Checking events and alarms
All basic operations can be performed via the LHMI or with PCM600.
Disturbances and their causes can be identified by indicator LEDs: Normal, Pickup and
Trip. During normal operation, the Normal LED is steady green.
For the LEDs to operate, the disturbance recorder has to be defined in the configuration.
Document the disturbance before clearing the information from the IED.
Internal faults can be divided to hardware errors, run-time errors in the application or
operating system and communication errors. Further actions always depend on the
cause of the error.
Only authorized and skilled personnel should analyze the errors and
decide on further actions.
Document all the recorded data from the IED before resetting the
tripping and IED lockout functions.
Do not switch off the auxiliary power supply to the IED before
changes, for example, setting parameter or local/remote control state
changes are saved.
A mechanism for limiting the number of writings per time period is included in the
IED to prevent the flash memory to be worn out due to too many writings. As a
consequence it may take up to an hour to save changes. If the auxiliary power is
interrupted before a change is saved, that change is lost.
After completing the editing of setting group values, the new values are activated. The
user can either commit the edited values or discard them.
6.1 Monitoring
6.1.1 Indications
The operation of the IED can be monitored via three different indications on the LHMI.
• Three indicator LEDs with fixed functionality: Normal, Pickup and Trip
• 15 programmable three-color alarm LEDs which can present 45 virtual LED states
• For each on state LED color and for the LED off state, texts can be
programmed with PCM600 and via LHMI. These texts are displayed on the
LHMI.
• An auto-indicating message on the display.
Auto-indication messages are shown in a dialog box that is displayed when the
disturbance recorder is triggered. The indication dialog box shows a list of current
disturbance recordings one by one. To scroll the dialog, use and .
IEC10000339 V2 EN
Active alarms are indicated by the alarm LEDs and the LED in the Multipage button.
The alarms are configured with PCM600. The alarm type and information depend on
the application configuration.
GUID-A217B75F-4252-4778-A7C4-644C64A0DBB0 V2 EN
GUID-B6FF7B05-1D9E-47BB-B4E6-0D9317D6A7D0 V1 EN
The flashing green LED indicates an internal IED fault. The fault messages are found
in the LHMI menu.
GUID-4F637E6B-3E81-4030-BE08-03C1DF7CAED0 V1 EN
The internal event list is not updated dynamically. To update the list,
leave the Internal events menu and then select it again.
With PCM600 the user can map output signals from condition monitoring related
function blocks to the appropriate destinations.
• DFR records
• Events
• Load profile record
Normally disturbance recordings are triggered by the IED applications but the
recording can also be triggered manually.
A071208 V3 EN
Read individual disturbance recordings from the IED with the PCM600 software to
monitor disturbance recorder data.
GUID-48497E0F-735B-4259-B80E-29329F8E6C53 V2 EN
GUID-CECFCDAB-06F4-4C5E-8244-6E43E89CF47C V2 EN
4. To select a category and view the items under it, press or and then .
The event view contains a list of events produced by the application configuration. The
events are grouped by day, and each event takes one line. Select the order of events
with the setting Main menu/Configuration/HMI/Screen/1:SCREEN/
EvListSrtOrder.
GUID-EACAC424-3DC5-480C-A06A-4ED1E225ADCA V2 EN
The event list is not updated dynamically. To update the list, leave the
Events menu and then select it again.
6.2 Controlling
ANSI12000007-1-en.vsd
ANSI12000007 V1 EN
IEC10000340 V2 EN
The time between selecting the object and giving a control command is
restricted by an adjustable timeout [(set by the parameter tSelect for
GUID-E4D9067B-1168-4287-9EF3-E251C6D13C4C V3 EN
The content of the Clear menu depends on the configuration configured with
PCM600.
2. Select the item to be cleared with or .
3. Press , select OK to confirm the selection or Cancel to cancel the selection.
4. To clear other items, repeat the steps.
Do not switch off the auxiliary power supply to the IED before
changes, for example, setting parameter or local/remote control state
changes are saved.
A mechanism for limiting the number of writings per time period is included in the
IED to prevent the flash memory to be worn out due to too many writings. As a
consequence it may take up to an hour to save changes. If the auxiliary power is
interrupted before a change is saved, that change is lost.
IED settings are planned in advance for different operation conditions by calculating
setting values to different setting groups. The active setting group can be changed by
the IED application or manually from the menu.
GUID-5E1B23B0-CE97-4C87-85B5-A36071F5B921 V1 EN
GUID-4D11206D-7E35-4806-8EA6-99DE70285B0E V1 EN
GUID-8CC9E092-4488-4E5D-AB9E-E08927B10BEB V1 EN
2. Press on the Setting group line in the dialog box to activate selection mode.
3. Select the wanted setting group with or and press .
GUID-EFA31026-0E80-47D4-BFCF-07662203C6BA V1 EN
GUID-18645E71-B6E8-401B-B24E-A8D204876ACF V1 EN
GUID-9E2A4A62-25C9-4C86-95BB-5432AA33D8C2 V2 EN
The # character on the right indicates that the parameter belongs to a setting group.
8. To browse the settings, scroll the list with and .
9. To edit the selected setting, press .
GUID-B3180332-3CDC-44A7-88F1-68D07BCA23C5 V2 EN
GUID-2DC502A7-ED9B-42DD-82BD-59FC26DC9771 V1 EN
The list can contain three alarm groups at the maximum. The amount of groups
depends on the amount of LEDs taken into use.
2. Select an alarm group with or and press .
3. Select an Alarm LED with or .
4. Press to confirm the selection and to change the Alarm LED mode.
5. Press or to change the value and to confirm the selection.
Section 7 Troubleshooting
1. Check the error origin from IED's internal event list Main menu/Diagnostics/
IED status/General.
2. Reboot the IED and recheck the supervision events to see if the fault has cleared.
3. In case of persistent faults, contact ABB for corrective actions.
• Check the IEC61850 and DNP3 communication status in internal event list in
Main menu/Diagnostics/IED Status/General.
• In case of persistent faults originating from IED's internal faults such as
component breakdown, contact ABB for repair or replacement actions.
There are several different communication links on the product. First check that all
communication ports that are used for communication are turned on.
2. Check the communication status of the rear port X1 via the LHMI in Main menu/
Test/Function status/Communication/1:DOSLAN1/Outputs.
The X1 communication port on the rear side of the IED is for optical Ethernet via
LC connector or electrical via RJ-45 connector of the IEC 61850-8-1 station bus
communication.
• Check that the LINKUP value is 1, that is, the communication is working.
When the value is 0, there is no communication link.
Different actions are taken depending on the severity of the fault. If the fault is found
to be permanent, the IED stays in internal fault mode. The IED continues to perform
internal tests during the fault situation.
When a fault appears, the fault indication message is to be recorded and stated when
requesting support or service.
7.2.2 Warnings
The warning message associated with the fault is found in the internal event list in the
LHMI menu Main menu/Diagnostics/Internal events. The message includes the date,
time, description and signal state for the fault. The current status of the internal fault
signals can also be checked via the LHMI in Main menu/Diagnostics/IED status/
General.
When a fault appears, record the fault indication message and state it when ordering
service.
The messages are listed in the LHMI menu under the event list. The signal status data
is found under the IED status and in the internal event list.
The physical inspection of wiring connections often reveals the wrong connection for
phase currents or voltages. However, even though the phase current or voltage
connections to IED terminals might be correct, wrong polarity of one or more
measurement transformers can cause problems.
• Check the current or voltage measurements and their phase information from
Main menu/Measurements/Analog primary values or Analog secondary
voltages.
• Check that the phase information and phase shift between phases is correct.
• Correct the wiring if needed.
• Change the parameter Negation in Configuration/Analog modules/
3PhaseAnalogGroup/1:SMAI_20_n (n= the number of the SMAI used).
V 2
A 1 3
4
GUID-BBAEAF55-8D01-4711-A71D-BBC76B60BA3D V1 EN
Figure 50: Testing output contacts using the voltage drop method
1 Contact current
2 Contact voltage drop
3 Load
4 Supply voltage
1 V
GUID-31DF5495-91F1-4A4B-8FD5-50625038961E V1 EN
• To check the status of the output circuits driving the output relay via the LHMI,
select Main menu/Tests/Binary output values/Binary output modules and then
navigate to the board with the actual binary output to be checked.
• Test and change the relay state manually.
1. To set the IED to test mode, select Main menu/Tests/IED
testmode1:TESTMODE/TestMode and set the parameter to enable.
2. To operate or force the output relay to operate, select and then navigate to
the board with the actual binary output relay to be operated/forced.
3. Select the BOn_PO to be operated/forced and use and or to
operate the actual output relay.
88 650 series ANSI
Operation Manual
1MRK 500 095-UUS A Section 7
Troubleshooting
Each BOn_PO is represented by two signals. The first signal in LHMI is the
actual value 1 or 0 of the output, and in PCM600 a lit or dimmed diode. The
second signal is the status Normal or Forced. Forced status is only achieved
when the BO is set to Forced or operated on the LHMI.
An initially high contact resistance does not cause problems as it is reduced quickly by
the electrical cleaning effect of fritting and thermal destruction of layers, bringing the
contact resistance back to the mOhm range. As a result, practically the full voltage is
available at the load.
Section 8 Glossary
AC Alternating current
ACT Application configuration tool within PCM600
A/D converter Analog-to-digital converter
ADBS Amplitude deadband supervision
AI Analog input
ANSI American National Standards Institute
AR Autoreclosing
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
AWG American Wire Gauge standard
BI Binary input
BOS Binary outputs status
BR External bistable relay
BS British Standards
CAN Controller Area Network. ISO standard (ISO 11898) for serial
communication
CB Circuit breaker
CCITT Consultative Committee for International Telegraph and
Telephony. A United Nations-sponsored standards body within
the International Telecommunications Union.
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined megapulses per second
CMT Communication Management tool in PCM600
CO cycle Close-open cycle
Codirectional Way of transmitting G.703 over a balanced line. Involves two
twisted pairs making it possible to transmit information in both
directions
3VO Three times the zero sequence voltage. Often referred to as the
residual voltage or the neutral point voltage
ABB Inc.
3450 Harvester Road
Burlington, ON L7N 3W5, Canada
Phone Toll Free: 1-800-HELP-365,
menu option #8