Modbus/RTU/IO GPRS Gateway
WCT-805M
INPUT READ/WRITE
SERVER PROTOCOL
Version 1.0
Wiman Communication Technologies
No.1/7, First Floor,
Narasingapuram Main Road, Maduvankarai
Guindy, Chennai - 6000032.
Ph : +91-44 22444074
[email protected] | www.wiman.in
ELGI Modbus/RTU Gateway User Manual Ver.1.0
WT-801M
SERVER COMMAND
1 Read Input Register
Comman
$IPCFG,<DEVCMD: MBCMD=01040000000585C9 >
d Eg:
Respons $WMRPY,P10,868324027795785,20170603125507,01030A000C000D000E000F0010
e Eg: F57,10,11#
Command Structure for More details
Field Name Value
SLAVEID 01
FUNCODE 04
STARTING ADDRESS HI 00
STARTING ADDRESS LOW 00
WORD COUNT HI 00
WORD COUNT LOW 05
ERROR CHECK HI 58
ERROR CHECK LOW C9
Response structure for more details
Field Name Value
HEADER $WMRPY
VERSION P10
IMEI NO 868324027795785
TIME 20170603105802
MODBUS PACKET 01030A000C000D000E000F0010F57
ERROR CHECK HI 10
ERROR CHECK LOW 11
Modbus Packet
Modbus
01030A000C000D000E000F0010F57
Packet
Modbus Packet Structure
Field Name Value
SLAVE ID 01
FUNCTION CODE 03
WORD COUNT 0A
DATA PACKET 01030A000C000D000E000F0010
MODBUS CHECKSUM F57
ERROR CHECK HI 10
ERROR CHECK LOW 11
Wiman Communication Technologies, Chennai
www.wiman.in
[email protected] Page : 2
ELGI Modbus/RTU Gateway User Manual Ver.1.0
WT-801M
2 Write Input Register
Command
$IPCFG,<DEVCMD: MBCMD=0106006300010200996fa9 >
Eg:
Command Structure for More details
Field Name Value
SLAVEID 01
FUNCODE 06
STARTING ADDRESS HI 00
STARTING ADDRESS LOW 63
WORD COUNT HI 00
WORD COUNT LOW 01
BYTE 02
WRITE DATA HI 00
WRITE DATA LOW 99
ERROR CHECK HI 6f
ERROR CHECK LOW a9
Note: Function code (06-write single register , 10- write multiple register )
Wiman Communication Technologies, Chennai
www.wiman.in