Digital Temperature Controller
Control Output 1
Indication Accuracy
• Relay output
• Thermocouple input:
• Voltage output (for driving SSR)
±0.3% of PV
• Linear current output
• Pt input: ±0.2% of PV
• Analog input:
±0.2% of FS
Control Output 2
• None
Sampling Period • Voltage output (for driving SSR)
• 50 ms
Auxiliary Outputs
Event Inputs •3
• None • PF (shift) Key
•2 • Temperature status display
•4 • Simple programming Transfer Output
• Independent heating and • None
cooling PID control •1
Remote SP Input • Changed parameter display
• None • Display brightness setting
•1
Serial Communications
• None
• RS-485
2
E5CC
Model Number Legend and Standard Models
Model Number Legend
E5CC-@@ @ @ @ @ -@@@ (Example: E5CC-RX3A5M-000)
−− − − − − −−−
A B C D E F
A B C D E F
Model No. of Power Meaning
Control outputs Terminal Input
auxiliary supply Options
1 and 2 type type
outputs voltage
E5CC 48 × 48 mm
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*1 *3 CX Linear current output *2 None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
CQ Linear current output *2
(for driving SSR)
3 3 (one common)
A 100 to 240 VAC
D 24 VAC/DC
5 Screw terminals (with cover)
M Universal input
HB alarm and Event Remote Transfer
Communications
HS alarm inputs SP Input output
000 --- --- --- --- ---
*1 001 1 --- 2 --- ---
2
*1 003 (for 3-phase RS-485 --- --- ---
heaters)
*3 004 --- RS-485 2 --- ---
005 --- --- 4 --- ---
006 --- --- 2 Provided.
007 --- --- 2 Provided. ---
*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output.
*2. The control output cannot be used as a transfer output.
*3. Option 004 can be selected only when "CX" is selected for the control outputs.
3
E5CC
Adapter
Model
Y92F-45
Note: Use this Adapter when the panel has already been prepared for
an E5B@ Controller.
Waterproof Cover
Model
Y92A-48N
Mounting Adapter
Model
Y92F-49
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
4
E5CC
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Models with option selection of 000: 5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or
Power consumption 1.6 W max. at 24 VDC
All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,
Relay output
minimum applicable load: 5 V, 10 mA *
Control
Voltage output
output Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000*
Number of outputs 3
Auxiliary
output SPST-NO relay outputs, 250 VAC, Models with 3 outputs: 2 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V
Number of inputs 2 or 4 (depends on model)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output Contact output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 kΩ max, resolution: Approx. 10,000
Setting method Digital setting using front panel keys
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)
Remote SP input
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)
11-segment digital display and individual indicators
Indication method
Character height: PV: 15.2 mm, SV: 7.1 mm
Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or
Multi SP
serial communications.
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital
Other functions filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, simple calculations, temperature status display, simple programming, moving
average of input value, and display brightness setting
-10 to 55°C (with no condensation or icing),
Ambient operating temperature
for 3-year warranty: -10 to 50°C (with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
* You cannot select a relay output or linear current output for control output 2.
5
E5CC
Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Platinum resistance Infrared temperature
Input type Thermocouple
thermometer sensor
10 to 60 to 115 to 140 to
Name Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
2300
2300
1800
1800
1700 1700
1700
1600
1500
1400
1300 1300 1300
1300
Temperature range (°C)
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Setting
number
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
●Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Setting number 25 26 27 28 29
6
E5CC
Alarm Outputs
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP
X X
Absolute-value upper-lim- ON ON The alarm will turn ON if the process value is larger than the
8 OFF PV OFF PV
it 0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
Absolute-value upper-lim- ON ON A standby sequence is added to the absolute-value upper-
10 OFF PV OFF PV
it with standby sequence 0 0 limit alarm (8). *6
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-
11 OFF PV OFF PV
with standby sequence 0 0 limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
14 OFF SP OFF SP
upper-limit alarm 0 0 is higher than the alarm value (X).
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
15 OFF SP OFF SP
lower-limit alarm 0 0 is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
X X
RSP absolute-value ON ON This alarm type turns ON the alarm when the remote SP
18 OFF RSP OFF RSP
upper-limit alarm *10 0 0 (RSP) is higher than the alarm value (X).
X X
RSP absolute-value ON ON This alarm type turns ON the alarm when the remote SP
19 OFF RSP OFF RSP
lower-limit alarm *10 0 0 (RSP) is lower than the alarm value (X).
7
E5CC
*1 With set values 1, 4 and 5, the upper and lower limit values can be set *4 Set value: 5, Upper- and lower-limit with standby sequence
independently for each alarm type, and are expressed as “L” and “H.” For Upper- and Lower-Limit Alarm Described Above *2
*2 Set value: 1, Upper- and lower-limit alarm
• Case 1 and 2
Case 1 Case 2 Case 3 (Always ON)
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
H<0, L<0
L H SP SP L H H SP L • Case 3: Always OFF
H<0, L>0 *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| Always OFF when the upper-limit and lower-limit hysteresis overlaps.
|H| < |L| |H| > |L|
*6 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H>0, L<0
H174) for information on the operation of the standby sequence.
SP H L |H| ≤ |L|
*7 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat.
*3 Set value: 4, Upper- and lower-limit range No.H174) for information on the loop burnout alarm (LBA).
Case 1 Case 2 Case 3 (Always OFF) *8 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H<0, L<0 H174) for information on the PV change rate alarm.
L H SP SP L H H SP L *9 When heating/cooling control is performed, the MV absolute upper limit
H<0, L>0 H>0, L<0 H<0, L>0 alarm functions only for the heating operation and the MV absolute lower
|H| < |L| |H| > |L| H L SP |H| ≥ |L| limit alarm functions only for the cooling operation.
*10 This value is displayed only when a remote SP input is used. It functions in
H>0, L<0
both Local SP Mode and Remote SP Mode.
SP H L |H| ≤ |L|
8
E5CC
Characteristics
Thermocouple: (±0.3% of PV or ±1°C, whichever is greater) ±1 digit max. *1
Indication accuracy Platinum resistance thermometer: (±0.2% of PV or ±0.8°C, whichever is greater) ±1 digit
(at the ambient temperature of 23°C) Analog input: ±0.2% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Transfer output accuracy ±0.3% FS max.
Remote SP Input Type ±0.2% FS ±1 digit max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *2 Analog input: ±1%FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Remote SP input: ±1% FS ±1 digit max.
Input sampling period 50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ωmax.)
Influence of signal source resistance
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,300 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
Weight Controller: Approx. 120 g, Mounting Bracket: Approx. 10 g
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.5 or higher
E5CC top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port on
Setup Tool port
the computer. *5
UL 61010-1, CSA C22.2 No. 611010-1 (evaluated by UL), KOSHA certified (some models) *6, Korean
Approved standards
Standards Radio Waves Act (Act 10564)
Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *7
EMI: EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and
L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and
S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C,
whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3% of PV or ±2°C, whichever is greater, ±1 digit max.
*2 Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3 K thermocouple at -100°C max.: ±10°C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6 Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html
*7 Refer to information on maritime standards in Shipping Standards on page 52 for compliance with Lloyd's Standards.
9
E5CC
500
300
Communications Functions
You can use the memory in the PLC to read and 100
write E5@C parameters, start and stop operation,
etc. The E5@C automatically performs communi- 50
cations with PLCs. No communications program-
30
ming is required.
Number of connected Temperature Controllers:
Programless
communications* 32 max.
10
Applicable PLCs
OMRON PLCs 5
SYSMAC CS Series, CJ Series, or E5CC
3 250 VAC, 30 VDC
CP Series (resistive load)
Mitsubishi Electric PLCs cosφ = 1
MELSEC Q Series or L Series
1
0 1 2 3 4 5 6
Switching current (A)
10
E5CC
External Connections
E5CC
Control output 1
Relay output E5CC-@@ 3 @ 5 M - @ @ @
250 VAC, 3A
(resistive load) (1) (2) (3) (4) (5) (6)
Voltage output ↑
(for driving SSR) Auxiliary outputs 1 to 3 Terminal type
12 VDC, 21 mA Control output 2 Relay outputs
Linear current output Models with 3 auxiliary
0 to 20 mA DC Voltage output The E5CC is set for a K-type thermocouple (input type = 5) by
(for driving SSR) outputs: 250 VAC, 2 A default. An input error (s.err) will occur if the input type setting does
4 to 20 mA DC
Load: 500 Ω max. 12 VDC, 21 mA (resistive load) not agree with the temperature sensor. Check the input type.
1 13 7
2 14 8
3 15 9
(5) Sensor (Temperature/Analog) Input (3) Input Power Supply
4 16 10
TC Pt I V 100 to 240 VAC 24 VAC/DC
A + 4 5 17 11
4 4 4
B mA 6 18 12 11 11
- 5 5 5 - 5
B - V 12 12
+ 6 6 6
+
6
(no polarity)
(6) Options
001 003 004 005 006 007
Event Inputs 1 Communications Communications Event Inputs Event Inputs Event Inputs
and 2, and CT1 (RS-485), CT1, (RS-485), and 1 to 4 1 and 2, and 1 and 2, and
and CT2 Event Inputs 3 and 4 Transfer Output Remote SP Input
B(+) B(+)
13 13 13 13 13 13
RS-485 RS-485
EV1
14 14 14 14 14 14
A(-) A(-) EV1 EV1 EV1
EV2 15 15 15 EV2
15 EV2
15 EV2
15
16 16 16 16 16 + + 16
CT1 CT1
+V V +
17 COM 17 EV3
17 17 17 mA 17
CT2 EV3 I
18 18 EV4 18 EV4
18 18 - - 18
Relay output
Auxiliary outputs 1, 2, 3
: Reinforced insulation
: Functional isolation
11
E5CC
Nomenclature
E5CC Front panel
Temperature unit
PV or specified parameter
Top View of E5CC
No. 2 display
Controllers
E5CC Panel Cutout
4
73.1 Mounted Separately Group Mounted
60 (48 × number of units - 2.5)+1.0
0
48 × 48 1
45+0.6
0
45+0.6
0
LED (SD)
10
Terminal Cover
(E53-COV23)
22 44.8
9.1
12
E5CC
● Waterproof Packing The Waterproof Packing is provided with the Temperature Controller.
Y92S-P8 (for DIN 48 × 48) Order the Waterproof Packing separately if it becomes lost or damaged.
The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site.
Consider three years a rough standard.)
The Waterproof Packing does not need to be attached if a waterproof structure is not required.
● Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15 (Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
25 3
Winding resistance: 18±2 Ω
10.5
10 100Ω
E54-CT3
2.36 dia.
30 RL=10Ω
1
12 dia.
9
100μV
10
40 × 40 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
100V
Frequency: 50 Hz
Armature Distortion
Approx. 3 dia. Plug ∞
10 factor
1kΩ
10%
Lead 500Ω 3%
1 1%
100mV
18
100Ω
50Ω
• Plug 10
RL=10Ω
1
Approx. 6 dia.
100μV
(22)
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
13
E5CC
● Adapter
Y92F-45 Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@.
2. Only black is available.
3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial
Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel.
Fixture (Accessory)
4.7 76
69.6 to 77.6
72 × 72
67 × 67 87
48 × 48
2.2 4.7
62.8
To back of the E5CC
Mounted to E5CC
48
80.5
14
E5CC
87.7 69
79.2
12
67.6
15
Digital Temperature Controller
Sampling Period
Control Output 2
• 50 ms
• Voltage output (for driving SSR)
• Relay output
Event Inputs • Linear current output
• None
• PF (shift) Key
•2 Auxiliary Outputs
• Setup Tool port on front panel
•4
• Temperature status display •4
•6
• Simple programming
Remote SP Input • Independent heating and
cooling PID control Transfer Output
• None • Changed parameter display • None
•1 • Display brightness setting •1
Serial Communications
• None
• RS-485
16
E5EC/E5AC
Model Number Legend and Standard Models
Model Number Legend
E5EC-@@ @ @ @ @ -@@@ (Example: E5EC-RX4A5M-000)
−− − − − − −−−
A B C D E F
E5AC-@@ @ @ @ @ -@@@ (Example: E5AC-RX4A5M-000)
−− − − − − −−−
A B C D E F
A B C D E F
Model No. of auxil- Power Meaning
Control outputs Terminal Input
iary out- supply Options
1 and 2 type type
puts voltage
E5EC 48 × 96 mm
E5AC 96 × 96 mm
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*2 CX Linear current output None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
QR Relay output
(for driving SSR)
RR Relay output Relay output
Linear current out-
*2 CC Linear current output
put
Voltage output
*2 CQ Linear current output
(for driving SSR)
Position-proportion-
PR Position-proportional relay output
al relay output
4 (auxiliary outputs 1 and 2 with same common and auxilia-
*3 4
ry outputs 3 and 4 with same common)
A 100 to 240 VAC
D 24 VAC/DC
Control outputs 1 and 2 5 Screw terminals (with cover)
For RX, M Universal input
QX, QQ, For CX or HB alarm
For PR Event Remote Transfer
QR, RR, or CC and Communications
inputs SP Input output
CQ HS alarm
Selectable Selectable Selectable 000 --- --- --- --- ---
Option Selectable Selectable 004 --- RS-485 2 --- ---
selection Selectable 005 --- --- 4 --- ---
conditions 2
*1 Selectable 009 (for 3-phase RS-485 2 --- ---
heaters)
Selectable 010 1 --- 4 --- ---
Selectable 011 1 --- 6 Provided. Provided.
Selectable 013 --- --- 6 Provided. Provided.
Selectable Selectable 014 --- RS-485 4 Provided. Provided.
*1. The options that can be selected depend on the type of control output.
*2. The control output cannot be used as a transfer output.
*3. A model with four auxiliary outputs must be selected.
17
E5EC/E5AC
Waterproof Packing
Applicable Controller Model
E5EC Y92S-P9
E5AC Y92S-P10
Note: This Waterproof Packing is provided with the Digital
Temperature Controller.
Waterproof Cover
Applicable Controller Model
E5EC Y92A-49N
E5AC Y92A-96N
Mounting Adapter
Model
Y92F-51
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
18
E5EC/E5AC
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Models with option selection of 000:6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or
E5EC 2.3 W max. at 24 VDC
All other models: 8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC
Power consumption
Models with option selection of 000:7.0 VA max. at 100 to 240 VAC, and 4.2 VA max. at 24 VAC or
E5AC 2.4 W max. at 24 VDC
All other models: 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF or 2-PID control (with autotuning)
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,
Relay output
minimum applicable load: 5 V, 10 mA
Control
Voltage output Output voltage: 12 VDC ±20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
output
(for driving SSR) (The maximum load current is 21 mA for models with two control outputs.)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Number of outputs 4
Auxiliary
output SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V
Number of inputs 2, 4 or 6 (depends on model)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output Current output: 4 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 kΩ max, Resolution: Approx. 10,000
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)
Remote SP input
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)
Potentiometer input 100 Ω to 10 kΩ
Setting method Digital setting using front panel keys
11-segment digital display and individual indicators
Character height: E5EC: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm
Indication method E5AC: PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm
Three displays Contents: PV/SV/MV, PV/SV/Multi-SP, or PV/SV/Remaining soak time
Numbers of digits: 4 digits each for PM, SV, and MV displays
Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or
Multi SP
serial communications.
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital
Other functions filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, simple calculations, temperature status display, simple programming, moving
average of input value, and display brightness setting
-10 to 55°C (with no condensation or icing),
Ambient operating temperature
for 3-year warranty: -10 to 50°C (with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
19
E5EC/E5AC
Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Platinum resistance Infrared temperature
Input type Thermocouple
thermometer sensor
10 to 60 to 115 to 140 to
Name Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
2300
2300
1800
1800
1700 1700
1700
1600
1500
1400
1300 1300 1300
1300
Temperature range (°C)
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 -199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Setting
range
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
●Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Setting number 25 26 27 28 29
20
E5EC/E5AC
Alarm type
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP
X X
Absolute-value upper-lim- ON ON The alarm will turn ON if the process value is larger than the
8 OFF PV OFF PV
it 0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
Absolute-value upper-lim- ON ON A standby sequence is added to the absolute-value upper-
10 OFF PV OFF PV
it with standby sequence 0 0 limit alarm (8). *6
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-
11 OFF PV OFF PV
with standby sequence 0 0 limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
14 OFF SP OFF SP
upper-limit alarm 0 0 is higher than the alarm value (X).
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
15 OFF SP OFF SP
lower-limit alarm 0 0 is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
X X
RSP absolute-value ON ON This alarm type turns ON the alarm when the remote SP
18 OFF RSP OFF RSP
upper-limit alarm *10 0 0 (RSP) is higher than the alarm value (X).
X X
RSP absolute-value ON ON This alarm type turns ON the alarm when the remote SP
19 OFF RSP OFF RSP
lower-limit alarm *10 0 0 (RSP) is lower than the alarm value (X).
21
E5EC/E5AC
*1 With set values 1, 4 and 5, the upper and lower limit values can be set *4. Set value: 5, Upper- and lower-limit with standby sequence
independently for each alarm type, and are expressed as “L” and “H.” For Upper- and Lower-Limit Alarm Described Above *2
*2. Set value: 1, Upper- and lower-limit alarm
Case 2
• Case 1 and 2
Case 1 Case 3 (Always ON)
H<0, L<0
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
L H SP SP L H H SP L • Case 3: Always OFF
H<0, L>0 *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| Always OFF when the upper-limit and lower-limit hysteresis overlaps.
|H| < |L| |H| > |L|
H>0, L<0
*6. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
SP H L |H| ≤ |L|
H174) for information on the operation of the standby sequence.
*7. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
*3. Set value: 4, Upper- and lower-limit range
H174) for information on the PV change rate alarm. This setting cannot be
Case 1 Case 2 Case 3 (Always OFF)
used with a position-proportional model.
H<0, L<0 *8. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
L H SP SP L H H SP L
H174) for information on the PV change rate alarm.
H<0, L>0 H>0, L<0 H<0, L>0 *9. When heating/cooling control is performed, the MV absolute upper limit
|H| < |L| |H| > |L| H L SP |H| ≥ |L| alarm functions only for the heating operation and the MV absolute lower
H>0, L<0 limit alarm functions only for the cooling operation.
|H| ≤ |L| *10. This value is displayed only when a remote SP input is used. It functions in
SP H L
both Local SP Mode and Remote SP Mode.
22
E5EC/E5AC
Characteristics
Thermocouple: (±0.3% of PV or ±1°C, whichever is greater) ±1 digit max. *1
Indication accuracy Platinum resistance thermometer: (±0.2% of PV or ±0.8°C, whichever is greater) ±1 digit
(at the ambient temperature of Analog input: ±0.2% FS ±1 digit max.
23°C) CT input: ±5% FS ±1 digit max.
Potentiometer input: ±5% FS ±1 digit max.
Transfer output accuracy ±0.3% FS max.
Remote SP Input Type ±0.2% FS ±1 digit max.
Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Influence of temperature *2
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: ±1%FS ±1 digit max.
Influence of voltage *2 CT input: ±5% FS ±1 digit max.
Remote SP input: ±1% FS ±1 digit max.
Input sampling period 50ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or°F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Standard, heating/cooling, or Position-proportional (Close): 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in
Integral time (I) units of 0.1 s)
Position-proportional (Floating): 1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s)*4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Influence of signal source resis- Thermocouple: 0.1°C/Ω max. (100 Ω max.)
tance Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,300 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
E5EC Controller: Approx. 210 g, Mounting Brackets: Approx. 4 g × 2
Weight
E5AC Controller: Approx. 250 g, Mounting Brackets: Approx. 4 g × 2
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.5 or higher
E5EC/E5AC top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port
on the computer.*5
Setup Tool port
E5EC/E5AC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion
Cable are used together to connect to a USB port on the computer.*5
Approved standards UL 61010-1, CSA C22.2 No. 611010-1 (evaluated by UL), Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *6
EMI EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and L thermocouples at
any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and S thermocouples
at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max. The
indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2 Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3 K thermocouple at -100°C max.: ±10°C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6 Refer to information on maritime standards in Shipping Standards on page 52 for compliance with Lloyd's Standards.
23
E5EC/E5AC
500
* The baud rate, data bit length, stop bit length, and vertical parity can be in- 300
dividually set using the Communications Setting Level.
E5EC/E5AC
Communications Functions 100 250 VAC, 30 VDC
(resistive load)
50 cosφ = 1
You can use the memory in the PLC to read and
write E5@C parameters, start and stop operation, 30
etc. The E5@C automatically performs communi-
cations with PLCs. No communications program-
ming is required. 10
Number of connected Temperature Controllers:
Programless
communications* 32 max. 5
Applicable PLCs 3
OMRON PLCs
SYSMAC CS Series, CJ Series, or CP Se-
ries 1
Mitsubishi Electric PLCs 0 1 2 3 4 5 6
MELSEC Q Series or L Series Switching current (A)
24
E5EC/E5AC
External Connections
E5EC/E5AC
E5EC-@@ 4 @ 5 M - @ @ @ E5AC-@@ 4 @ 5 M - @ @ @
(1) (2) (3) (4) (5) (6) (1) (2) (3) (4) (5) (6) The E5EC is set for a K-type thermocouple (input
↑ ↑ type = 5) by default. An input error (s.err) will occur
if the input type setting does not agree with the
Terminal type Terminal type temperature sensor. Check the input type.
Control output 1 Control output 2 Auxiliary outputs 1 to 4 (6) Options
Relay output Relay output Relay output 004 005 009 010
250 VAC, 5 A 250 VAC, 5 A Models with 4 auxiliary Communications 4 event inputs Communications, 2 event 4 event inputs
(resistive load) (resistive load) outputs: 250 VAC, 2 A and 2 event inputs inputs, and 2 CT inputs and 1 CT input
Voltage output Voltage output (resistive load) B(+) B(+)
(for driving SSR) 13 13 13 13
(for driving SSR) RS-485 RS-485
12 VDC, 40 mA 12 VDC, 21 mA 14 14 14 14
A(-) EV3 A(-) EV3
When There Is a Linear current output 15 15 15 15
EV4 EV4
Control Output 2: 0 to 20 mA DC 16 16 16 16
21 mA 4 to 20 mA DC 17 17 17 17
Linear current output Load: 500 Ω max. EV1 EV1 EV1 EV1
0 to 20 mA DC 18 18 18 18
EV2 EV2 EV2 EV2
4 to 20 mA DC 19 19 19 19
CT1 CT1
Load: 500 Ω max. 20 20 COM 20 20
CT2
21 21 21 21
(1) Control output
RX QX CX
011
Models with Models with 1 Models with 1
1 Relay Output
6 event Inputs, 1 CT input,
Voltage Output Linear Current Output
(for Driving SSR) transfer output, and remote SP input
Auxiliary outputs 1, 2
Auxiliary outputs 3, 4
: Reinforced insulation
: Functional isolation
25
E5EC/E5AC
Nomenclature
E5EC
Front panel
No. 1 display
PV or specified parameter Top View of E5EC
Temperature unit
No. 2 display
Operation indicators
SP or specified parameter value
E5AC
Front Panel
No. 2 display
Top-panel
Press the U or D Key to set the parameter.
Setup
Tool port
26
E5EC/E5AC
Dimensions (Unit: mm)
Controllers
E5EC
(64)
4
48 60 44
1
60 min.
45-0.6
0
92+0.8
0
92-0.8
0
120 min.
27
E5EC/E5AC
E5AC (64)
4
60
96 x 96 1 91 x 91
110 91
Waterproof
Packing (Accessory) Mounting Adapter
(Accessory)
The Setup Tool port is on the top of the Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.
92+0.8
0
28
E5EC/E5AC
LED(SD)
● Conversion Cable
E58-CIFQ2-E
Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510) 250 263 1510
29
E5EC/E5AC
21.9 21.9
(2) (2)
131.7 131.7
● Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15
(Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
25 3
Winding resistance: 18±2 Ω
10.5
40 10 ∞ Distortion
1kΩ factor
Two, 3.5 dia.
10%
1
10 3%
1%
100mV
30
10 100Ω
E54-CT3
2.36 dia. 1 RL=10Ω
30
12 dia.
9 100μV
10
1 10 100mA 1 10 100 1,000A
40 × 40
Thru-current (Io) A (r.m.s.)
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
Two, M3 (depth: 4) E54-CT3
Maximum continuous heater current: 120 A (50/60 Hz)
15
(Maximum continuous heater current for an OMRON Digital
Temperature Controller is 50 A.)
30
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
E54-CT3 Accessories
Output voltage (Eo) V (r.m.s.)
100V
Frequency: 50 Hz
• Armature Connection Example Distortion
∞
10 factor
Armature 1kΩ
10%
Approx. 3 dia. Plug 500Ω 3%
1 1%
Lead
100mV
100Ω
18 50Ω
10
RL=10Ω
• Plug
1
(22) 10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
30
MEMO
31
Digital Temperature Controller
Event Inputs
• None
• PF (shift) Key
•1
• Temperature status display
• Simple programming
Serial Communications
• Independent heating and
• None cooling PID control
• RS-485 • Changed parameter display
• Display brightness setting
32
E5DC
Model Number Legend and Standard Models
Model Number Legend
E5DC-@@ @ @ @ @ -@@@ (Example: E5DC-RX0ASM-015)
−− − − − − −−−
A B C D E F
A B C D E F
Model No. of Power Meaning
Control Terminal Input
auxiliary supply Options
output 1 type type
outputs voltage
E5DC 22.5 mm wide and mounts to DIN Track
Control output 1
RX Relay output
Voltage output
QX
(for driving SSR)
CX Linear current output *5
0 None
2 2 (one common)
A 100 to 240 VAC
D 24 VAC/DC
S Screw terminals
M Universal input
HB alarm and HS alarm Communications Event input
*1 000 --- --- ---
*2 002 1 RS-485 ---
*3 015 --- RS-485 ---
*4 016 --- --- 1
*2 017 1 --- 1
*1 Option 000 can be selected only if two auxiliary outputs are selected.
*2 Options 002 and 017 can be selected only if the control output is a relay output or voltage output and two auxiliary outputs are selected.
*3 Option 015 cannot be selected if the control output is a relay output or voltage output and two auxiliary outputs are selected.
*4 Options 016 can be selected only if the control output is a linear current output and two auxiliary outputs are selected.
*5 The control output cannot be used as a transfer output.
List of Models
Options Model Model
No. of auxiliary Power supply voltage Power supply voltage
Control output HB alarm and HS
outputs No. of event inputs Communications
alarm
100 to 240 VAC 24 VAC/DC
--- RS-485 E5DC-RX0ASM-015 E5DC-RX0DSM-015
---
--- --- E5DC-RX2ASM-000 E5DC-RX2DSM-000
Relay output
2 Detection for single- RS-485 E5DC-RX2ASM-002 E5DC-RX2DSM-002
phase heater 1 --- E5DC-RX2ASM-017 E5DC-RX2DSM-017
--- RS-485 E5DC-QX0ASM-015 E5DC-QX0DSM-015
---
Voltage output --- --- E5DC-QX2ASM-000 E5DC-QX2DSM-000
(for driving SSR) 2 RS-485 E5DC-QX2ASM-002 E5DC-QX2DSM-002
Detection for single-
phase heater 1 --- E5DC-QX2ASM-017 E5DC-QX2DSM-017
--- RS-485 E5DC-CX0ASM-015 E5DC-CX0DSM-015
Linear current --- --- E5DC-CX2ASM-000 E5DC-CX2DSM-000
---
output 2 RS-485 E5DC-CX2ASM-015 E5DC-CX2DSM-015
1 --- E5DC-CX2ASM-016 E5DC-CX2DSM-016
Note: These products are sold as a set with a terminal block (i.e., Terminal Unit).
33
E5DC
Short Bars
Model
Y92S-P11
34
E5DC
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 4.9 VA max. at 100 to 240 VAC, and 2.8 VA max. at 24 VDC or 1.5 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/
Input impedance
THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5
Relay output
V, 10 mA
Control
Voltage output
output Output voltage 12 VDC ±20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: Approx. 10,000
Number of outputs 2 (depends on model)
Auxiliary
outputs SPST-NO relay outputs: 250 VAC, 2 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V
Number of inputs 1 (depends on model)
Event Contact input ON: 1 kΩ max., OFF: 100 kΩ min.
inputs External contact input
Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.
specifications
Current flow: approx. 7 mA per contact
Setting method Digital setting using front panel keys
11-segment digital displays and individual indicators
Indication method
Character height: PV: 8.5 mm, SV: 8.0 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or
Multi SP
serial communications.*
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burn-
out (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self
Other functions tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change
rate limit, simple calculations, temperature status display, simple programming, moving average of input
value, and display brightness setting
−10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C (with no condensation or
Ambient operating temperature
icing)
Ambient operating humidity 25% to 85%
Storage temperature −25 to 65°C (with no condensation or icing)
* Only two set points are selectable for event inputs.
35
E5DC
Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Platinum resistance Infrared temperature
Input type Thermocouple
thermometer sensor
10 to 60 to 115 to 140 to
Name Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
2300
2300
1800
1800
1700 1700
1700
1600
1500
1400
1300 1300 1300
1300
Temperature range (°C)
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 -199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Setting
range
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
●Analog input
Input type Current Voltage
Input specification 4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Setting number 25 26 27 28 29
36
E5DC
Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.)
Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not
displayed.
To use alarm 1, set the output assignment to alarm 1.
X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP
X X
Absolute-value upper-lim- ON ON The alarm will turn ON if the process value is larger than the
8 OFF PV OFF PV
it 0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
Absolute-value upper-lim- ON ON A standby sequence is added to the absolute-value upper-
10 OFF PV OFF PV
it with standby sequence 0 0 limit alarm (8). *6
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-
11 OFF PV OFF PV
with standby sequence 0 0 limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
14 OFF SP OFF SP
upper-limit alarm 0 0 is higher than the alarm value (X).
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
15 OFF SP OFF SP
lower-limit alarm 0 0 is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
37
E5DC
*1 With set values 1, 4, and 5, the upper- and lower-limit values can *4 Set value: 5, Upper- and lower-limit with standby sequence
be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above at *2
“L” and “H.” • In cases 1 and 2 above, the alarm is always OFF if the upper-
*2 Set value: 1, Upper- and lower-limit alarm and lower-limit hysteresis overlaps.
Case 1 Case 2 Case 3 (Always OFF) • In case 3, the alarm is always OFF.
H<0, L<0 *5 Set value: 5, Upper- and lower-limit alarm with standby sequence
L H SP SP L H H SP L The alarm is always OFF if upper- and lower-limit hysteresis
H<0, L>0 overlaps.
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| *6 Refer to the E5@C Digital Temperature Controllers User’s Manual
|H| < |L| |H| > |L|
H>0, L<0 (Cat. No. H174) for information on the operation of the standby
SP H L |H| ≤ |L| sequence.
*3 Set value: 4, Upper- and lower-limit range *7 Refer to the E5@C Digital Temperature Controllers User’s Manual
Case 1 Case 2 Case 3 (Always ON) (Cat. No. H174) for information on the LBA.
H<0, L<0 *8 Refer to the E5@C Digital Temperature Controllers User’s Manual
L H SP SP L H H SP L (Cat. No. H174) for information on the PV change rate alarm.
H<0, L>0 H>0, L<0
H<0, L>0 *9 When heating/cooling control is performed, the MV absolute-
H L SP |H| ≥ |L| value upper-limit alarm functions only for the heating operation
|H| < |L| |H| > |L|
H>0, L<0 and the MV absolute-value lower-limit alarm functions only for the
SP H L |H| ≤ |L| cooling operation.
38
E5DC
Characteristics
Thermocouple:*1 (±0.3 % of PV or ±1°C, whichever is greater) ±1 digit max.
Indication accuracy
Platinum resistance thermometer: (±0.2 % of PV or ±0.8°C, whichever is greater) ±1 digit max.
(when mounted individually, ambi-
Analog input: ±0.2% FS ±1 digit max.
ent temperature of 23°C)
CT input: ±5% FS ±1 digit max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *2 Analog input: ±1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
R, S, B, W, or PLII thermocouple: (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Installation influence (E5DC only)
Other thermocouple: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3
Input sampling period 50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range −1,999 to 9,999 (decimal point position depends on input type)
Influence of signal source resis-
Thermocouple: 0.1°C/Ω max. (100 Ω max.), Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
tance
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,300 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hr each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
Weight Controller: Approx. 120 g
Degree of protection Main unit: IP20, Terminal unit: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.6 or higher
E5DC bottom panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the
computer. *5
Setup Tool port
E5DC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable are
used together to connect a USB port on the computer.*5
Approved standards UL 61010-1, CSA C22.2 No. 611010-1 (evaluated by UL), Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMI: EN61326
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A
Noise Terminal Voltage: EN55011 Group 1, class A
EMS: EN61326
ESD Immunity: EN61000-4-2
EMC
Electromagnetic Field Immunity: EN61000-4-3
Burst Noise Immunity: EN61000-4-4
Conduction Disturbance Immunity: EN61000-4-6
Surge Immunity: EN61000-4-5
Voltage Dip/Interrupting Immunity: EN61000-4-11
*1 The indication accuracy of K thermocouples in the −200 to 1,300°C range, T and N thermocouples at a temperature of −100°C or less, and U
and L thermocouples at any temperature is ±2°C ±1 digit max. The indication accuracy of B thermocouples at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max.
The indication accuracy of R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W
thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max.
The indication accuracy of PLII thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.
*2 Ambient temperature: −10 to 23 to 55°C, Voltage range: −15% to 10% of rated voltage
*3 K thermocouple at −100°C max: ±10°C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time.
39
E5DC
500
300
100
50
30
10
5
E5DC
3 250 VAC, 30 VDC
(resistive load)
cosφ = 1
1
0 1 2 3 4 5 6
Switching current (A)
40
E5DC
External Connections
E5DC
Control output Auxiliary outputs 1 and 2
The E5DC is set for a K-type thermocouple (input type = 5) by default.
Relay output Relay outputs An input error (s.err) will occur if the input type setting does not agree
250 VAC, 3 A (resistive load) 250 VAC: 2 A (resistive load) with the temperature sensor. Check the input type.
Voltage output (for driving SSR)
12 VDC, 21 mA
Linear current output E5DC
0 to 20 mA DC Control output Options
4 to 20 mA DC
Load: 500 Ω max. Input Power Supply Control Output
100 to 240 VAC 24 VAC/DC RX QX CX
1 relay 1 voltage output 1 linear
1 1 output (for driving SSR) current output
2 2 5 5 +Q 5 + C
R
6 6 - 6 -
(no polarity)
1 5 9
2 6 10 Auxiliary Outputs
Options
9
002 11 Auxiliary output 2
10
Communications and 1 CT Auxiliary output 1
B(+) 11
3 7
RS-485 CT1
4 8
A(-)
- 3 7
+ 4 8
EV1
017
One event input and one CT
- 3 7
CT1
+ 4 8
EV1
Relay output
: Reinforced insulation
: Functional isolation
41
E5DC
Nomenclature
E5DC Front panel
Use S Key to change the digit (default setting). Front-panel Setup Tool port
Controllers
E5DC (85)
4 81
22.5 22.5
96 35 110 91
Mounting Adapter
(Accessory: Sold separately)
The Setup Tool port is on the bottom of the Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the
connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use
the Digital Temperature Controller.
92 +0.8
0 92 +0.8 92 +0.8
0 0
120 min
42
E5DC
LED (RD)
USB connector
(type A plug)
LED (PWR) Serial connector
LED (SD)
● Conversion Cable
E58-CIFQ2-E
Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510) 250 263 1510
● Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values)
21
2.8
15 E54-CT1
5.8 dia.
Maximum continuous heater current: 50 A (50/60 Hz)
7.5
Number of windings: 400±2
Winding resistance: 18±2 Ω
25 3
100V
Output voltage (Eo) V (r.m.s.)
Frequency: 50 Hz
10.5
10 ∞
Distortion
40 1kΩ factor
10%
Two, 3.5 dia. 1
3%
1%
10
100mV
30
10 100Ω
E54-CT3 2.36 dia.
30
1 RL=10Ω
12 dia.
9
100μV
10
40 × 40 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
Frequency: 50 Hz
• Armature Connection Example Distortion
∞
10 factor
Armature 1kΩ
10%
Approx. 3 dia. Plug 500Ω 3%
1 1%
Lead
100mV
100Ω
18 50Ω
10
RL=10Ω
• Plug
1
10
(22) 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
43
E5DC
12
24.8
11.5
7.3±0.15
10 1.3
M4 spring washer 4.8 4.5
35±0.3 27±0.15
15 25 25 25 25 15 (5)* 1
10 10
1000 (500)*
* Dimensions in parentheses are for the PFP-50N.
16.5
44
MEMO
45
E5CC/E5EC/E5AC/E5DC
Operation
Setting Levels Diagram
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.
O Key once.
Operating
Advanced Function
Setting Level
Used to set application
functions.
Calibration Level
*1. To use a key procedure to move to Manual Control Level, set the Auto/Manual Select Addition parameter to ON and set the PF Setting parameter to a-m (Auto/
Manual).
*2. The No. 1 display will flash in the middle when the keys are pressed for 1 s or longer.
46
E5CC/E5EC/E5AC/E5DC
Error Displays (Troubleshooting)
When an error occurs, the No. 1 display or No. 2 display shows the error code.
Take necessary measure according to the error code, referring the following table.
Display Name Meaning Action Operation
After the error occurs and it is
The input value exceeded the control Check the wiring for input to be sure displayed, the alarm output will
range.* it is wired correctly, not broken, and operate as if the upper limit was
The input type is not set correctly. not shorted. Also check the input exceeded.
The sensor is disconnected or short- type. It will also operate as if transfer
circuited. If there are no problems in the wiring output exceeded the upper limit.
The sensor is not wired correctly. or input type settings, cycle the If an input error is assigned to a
The sensor is not wired. power supply. control output or auxiliary output, the
If the display remains the same, output will turn ON when the input
* Control Range replace the Digital Temperature error occurs.
s.err Input error Temperature resistance
thermometer or thermocouple input:
Controller. The error message will appear in the
If the display is restored to normal, display for the PV.
SP Lower Limit - 20°C to SP Upper then the probable cause is external
Limit + 20°C noise affecting the control system. Note: 1. The heating and cooling
(SP Lower Limit - 40°F to SP Upper Check for external noise. control outputs will turn
Limit + 40°F) OFF.
ESIB input: Note: For a temperature resistance 2. When the manual MV, MV
Same as specified input range. thermometer, the input is at stop, or MV at error is
Analog input: considered disconnected if set, the control output is
Scaling range -5% to 105% the A, B, or B’ line is broken. determined by the set
value.
This is not an error. It
is displayed when the
Control continues and operation is
[[[[ Below -1,999 control range is wider
than the display
normal.
range and the PV The value will appear in the display
Display for the PV.
range exceeds the display - Refer to the E5@C Digital
range. The PV is
exceeded displayed for the Temperature Controllers User’s
Manual (Cat. No. H174) for
range that is given on information on the
]]]] Above 9,999 the left (the number
controllable range.
without the decimal
point).
First, cycle the power supply.
If the display remains the same, the The control outputs, auxiliary
A/D controller must be repaired. outputs, and transfer outputs turn
There is an error in the internal
e333 converter
error
circuits.
If the display is restored to normal,
then a probable cause can be
OFF. (A current output will be approx.
0 mA and a linear voltage output will
external noise affecting the control be approx. 0V.)
system. Check for external noise.
First, cycle the power supply.
If the display remains the same, the The control outputs, auxiliary
controller must be repaired. outputs, and transfer outputs turn
Memory There is an error in the internal
e111 error memory operation.
If the display is restored to normal,
then a probable cause can be
OFF. (A current output will be approx.
0 mA and a linear voltage output will
external noise affecting the control be approx. 0V.)
system. Check for external noise.
Control continues and operation is
normal.
The error message will appear for the
This error is displayed when the peak following displays.
ffff Overcurrent
current exceeds 55.0 A.
-
Heater Current Value 1 Monitor
Heater Current Value 2 Monitor
Leakage Current Value 1 Monitor
Leakage Current Value 2 Monitor
The No. 1 display for the following
parameter flashes in Operation Level
ct1 or Adjustment Level.
If there is a HB or HS alarm, the No. Heater Current Value 1 Monitor
ct2 HB or HS 1 display will flash in the relevant - Heater Current Value 2 Monitor
alarm
lcr1 setting level. Leakage Current Value 1 Monitor
Leakage Current Value 2 Monitor
lcr2 However, control continues and
operation is normal.
"----" will be displayed for the Valve
Opening Monitor parameter if any of
the following error occurs.
• Motor calibration has not been
Potentiometer performed. Close control: The control output is
Input Error OFF or the value that is set for the
---- (Position- • The wiring of the potentiometer is Check for the above errors. MV at PV Error parameter is output.
proportional incorrect or broken. Floating control: Operation will be
Models Only) • The potentiometer input value is normal.
incorrect (e.g., the input is out of
range or the potentiometer has
failed).
47
E5CC/E5EC/E5AC/E5DC
Operation
Parameters
The related setting items in each level are described below. If you press the Mode Key at the last setting item, the display will return to the first
setting item in the same level.
S Key*2
Power ON
Starting in Manual Mode.
Press the O Key for at least 3 s. S Key*2
Starting in Other than the Auto/Manual Switch display
Manual Control Level Automatic
Press the O
Mode. Initial Setting Level
Press the S Key PID
for at least 1 s. C
25 Key or the S Press the Press the O Key for less than 1 s.
Control
0 only Key for at least O Key for
*1
PV/MV 1 s. *1 at least 1 s.
in-t Input Type
5
Adjustment Press the O Key less than 1 s.
M
Level Operation Level
Press the O Key less than 1 s. in-h Scaling Upper Limit
100
Adjustment Level
Display
Process Value/ M
Displayed only 25 al1h Alarm Value
l.adj once when
entering
0 Set Point 1 Upper Limit
0 1 in-l Scaling Lower Limit
adjustment level.
ins Process Value Input orl MV Change Rate
Limit M M
0
0.0 Shift 0
M
M M M 25 Process Value/
al1l Alarm Value
Decimal Point
0 Set Point 2 0 1
Lower Limit
dp
at AT Execute/Cancel inrt Process Value Slope
db Position 0 For input type of analog
off 1.000 Coefficient Proportional M M
M
M sdwt
Send Data Wait M
prlp Password to Move to 20 Time
Protect Level: *1. When the PF Setting parameter is set to A-M.
0 Password setting
M *2. When the PF Setting parameter is set to PFDP.
M *3. Used with component communications.
*4. Not displayed by the E5DC.
48
E5CC/E5EC/E5AC/E5DC
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
M
Automatic Display RT SP Tracking
alh2 Alarm 2 init Parameter Initialization
ret rt sptr
Hysteresis off off Return Time off off
0.2
M M M M M
alt3 Alarm 3 Type mspu Number of Multi-SP brgt Display Brightness hsu HS Alarm Use p-db PV Dead Band
off Points 3 on 0
2
M M M M M
Alarm 1 Latch Manual MV
alh3 Alarm 3 spru SP Ramp Time Unit a1lt hsl HS Alarm Latch manl Limit Enable
m off off off
0.2 Hysteresis
M M M M
M Direct Setting of
alt4 Alarm 4 Type rest Standby
Reset
Sequence a2lt Alarm 2 Latch
hsh HS Alarm Hysteresis pmvd Position Proportional
a off 0.1 off MV *4
2
M M M M
M
PV Rate of Change
alh4 Alarm 4 sb1n Auxiliary Output 1 a3lt Alarm 3 Latch lba LBA Detection Time pvrp
n-o Open in Alarm off 0 20 Calculation Period
0.2 Hysteresis
M M M M
M
o1st Control Output 1 Signal sb2n Auxiliary Output 2 a4lt Alarm 4 Latch
lbal LBA Level hctm Heating/Cooling
Tuning Method
n-o Open in Alarm off 8.0 off
4-20
M M M M
M
sb3n Auxiliary Output 3
prlt Move to Protect Level
Time lbab LBA Band ompw Minimum Output
o2st Control Output 2 Signal Open in Alarm
n-o *4 3 3.0 1.0 ON/OFF Band
4-20 *4
M M M M
M Auxiliary Output 4
Cold Junction Control Output 1 PF Setting
trst Transfer Output Signal sb4n Open in Alarm cjc Compensation out1 Assignment pf
*4 n-o on Method o shft
4-20 (E5EC/E5AC only) *4
M M M M
M
hbu HB ON/OFF a1on Alarm 1 ON Delay
out2 Control Output 2
Assignment *4 pfd1 Monitor/Setting Item 1
tr-t Transfer Output Type on 0 none 1
off *4
Linear output
M M M M
M
Auxiliary Output 1
tr-h Transfer Output hbl Heater Burnout Latch a2on Alarm 2 ON Delay
sub1 Assignment pfd2 Monitor/Setting Item 2
Upper Limit off 0 alm1 0
100.0
*4
M M M M
M Auxiliary Output 2
hbh Heater Burnout a3on Alarm 3 ON Delay sub2 Assignment pfd3 Monitor/Setting Item 3
tr-l Transfer Output
Lower Limit Hysteresis
0.1 0 alm2 0
0.0
*4
M M M M
M
st-b ST Stable Range a4on Alarm 4 ON Delay
sub3 Auxiliary Output 3
Assignment *4 pfd4 Monitor/Setting Item 4
ev-1 Event Input
Assignment 1 15.0
0 alm3 0
msp0
M M M M M
alfa α a1of Alarm 1 OFF Delay
sub4 Auxiliary Output 4
pfd5 Monitor/Setting Item 5
ev-2 Event Input
Assignment 2 0.65 0
Assignment
alm4 (E5EC/E5AC only) *4 0
stop
*4
M M M M
M
ev-3 Event Input tidu Integral/Derivative a2of Alarm 2 OFF Delay alma Integrated Alarm spd1 PV/SP No. 1 Display
Selection
Assignment 3 1 Time Unit 0 49 Assignment 4
none
*4
M M M M M
PV/SP No. 2 Display
Event Input at-g AT Calculated Gain a3of Alarm 3 OFF Delay
t-u Soak Time Unit spd2 Selection
ev-4 Assignment 4 0.8 0 m 0
none *4
M M M M
M Alarm 4 OFF Delay Alarm SP Selection MV Display Selection
ev-5 Event Input at-h AT Hysteresis a4of alsp odsl
0.8 0 sp-m o
Assignment 5
none
(E5EC/E5AC only) *4
M M M M
M PV Decimal Point
Remote SP Input *4
ev-6
Event Input lcma Limit Cycle MV mvse MV at Stop and Error
Addition rs-t pvdp Display
Assignment 6 20.0 Amplitude off 4-20 on
none (E5EC/E5AC only) *4
M M M M
M PV Status Display
clfl Close/Floating *4 inf Input Digital Filter amad Auto/Manual Select
Addition rspu Remote SP Enable *4 pvst Function
flot 0.0 off off off
M M M M M
calb Motor Calibration *4 mav Moving Average Count mant Manual Output Method rsph Remote SP
Upper Limit *4
svst SV Status Display
Function
off off hold 1300 off
M M M M M
MV Display Display Refresh
mot Travel Time *4 o-dp mani Manual MV Initial Value rspl Remote SP
d.ref Period
30 M
off M0.0
Lower Limit *4
-200 0.25
M M M M M
LCT Cooling Output
sqr Extraction of Square lcmt Minimum ON Time
Root Enable 0.2 (E5DC only)
off
49
E5CC/E5EC/E5AC/E5DC
Safety Precautions
● Be sure to read the precautions for all E5CC/E5EC/E5AC/E5DC models in the website at:
http://www.ia.omron.com/.
Warning Indications
Minor electric shock or fire may occasionally occur.
Indicates a potentially hazardous
Do not use any cables that are damaged.
situation which, if not avoided, may
CAUTION result in minor or moderate injury or in
property damage.
Never disassemble, modify, or repair the product or
Supplementary comments on what to touch any of the internal parts. Minor electric shock,
Precautions for
do or avoid doing, to use the product fire, or malfunction may occasionally occur.
Safe Use safely.
Supplementary comments on what to CAUTION - Risk of Fire and Electric Shock
Precautions for do or avoid doing, to prevent failure to a. This product is UL recognised as Open Type
Process Control Equipment. It must be mounted in
Correct Use operate, malfunction or undesirable
an enclosure that does not allow fire to escape
effect on product performance. externally.
b. More than one disconnect switch may be required to de-
Meaning of Product Safety Symbols energize the equipment before servicing the product.
c. Signal inputs are SELV, limited energy. *1
Used to warn of the risk of electric shock under d. Caution: To reduce the risk of fire or electric shock, do not
interconnect the outputs of different Class 2 circuits. *2
specific conditions.
If the output relays are used past their life expectancy,
contact fusing or burning may occasionally occur.
Used for general prohibitions for which there is no Always consider the application conditions and use
specific symbol. the output relays within their rated load and electrical
life expectancy. The life expectancy of output relays varies
Used to indicate prohibition when there is a risk of considerably with the output load and switching conditions.
minor injury from electrical shock or other source
Even if you replace only the Main Unit of the E5DC, check
if the product is disassembled.
the condition of the Terminal Unit.
Used for general CAUTION, WARNING, or If corroded terminals are used, contact failure in the
DANGER precautions for which there is no terminals may cause the temperature inside the
specified symbol. (This symbol is also used as the Digital Controller to increase, possibly resulting in fire.
alerting symbol, but shall not be used in this If the terminals are corroded, replace the Terminal Unit as well.
meaning on the product.)
Tighten the terminal screws to the rated torque of
Used for general mandatory action precautions between 0.43 and 0.58 N•m.
for which there is no specified symbol. Loose screws may occasionally result in fire.
*1. An SELV (separated extra-low voltage) system is one with a power supply
Electric shock, fire, or malfunction may occasionally that has double or reinforced insulation between the primary and the
occur. Do not allow metal objects, conductors, secondary circuits and has an output voltage of 30 V r.m.s. max. and 42.4
V peak max. or 60 VDC max.
cuttings from installation work, or moisture to enter *2. A class 2 circuit is one tested and certified by UL as having the current and
the Digital Temperature Controller or the Setup Tool voltage of the secondary output restricted to specific levels.
port or ports. Attach the cover to the front-panel Setup Tool port
whenever you are not using it to prevent foreign objects from
entering the port.
50
E5CC/E5EC/E5AC/E5DC
51
E5CC/E5EC/E5AC/E5DC
Shipping Standards
The E5CC, E5EC, and E5AC comply with Lloyd's standards. When ● Operating Precautions
applying the standards, the following installation and wiring 1. When starting operation after the Digital Temperature Controller
requirements must be met in the application. has warmed up, turn OFF the power and then turn it ON again at
the same time as turning ON power for the load. (Instead of turning
Application Conditions the Digital Temperature Controller OFF and ON again, switching
● Installation Location from STOP mode to RUN mode can also be used.)
2. Avoid using the Controller in places near a radio, television set, or
The E5CC, E5EC, and E5AC comply with installation category ENV1
wireless installing. These devices can cause radio disturbances
and ENV2 of Lloyd's standards. Therefore, they must be installed in a which adversely affect the performance of the Controller.
location equipped with air conditioning. They cannot be used on the
bridge or decks, or in a location subject to strong vibration. ● Others
1. Do not Connect or disconnect the Conversion Cable connector
repeatedly over a short period of time.
Precautions for Correct Use The computer may malfunction.
2. After connecting the Conversion Cable to the computer, check the
● Service Life COM port number before starting communications. The computer
1. Use the product within the following temperature and humidity ranges: requires time to recognize the cable connection. This delay does
Temperature: -10 to 55°C (with no icing or condensation) not indicate failure.
Humidity: 25% to 85% 3. Do not connect the Conversion Cable through a USB hub. Doing
If the product is installed inside a control board, the ambient so may damage the Conversion Cable.
temperature must be kept to under 55°C, including the temperature 4. Do not use an extension cable to extend the Conversion Cable
around the product. length when connecting to the computer. Doing so may damage
the Conversion Cable.
2. The service life of electronic devices like Digital Temperature
Controllers is determined not only by the number of times the relay is
switched but also by the service life of internal electronic components.
● Mounting
Component service life is affected by the ambient temperature: the Mounting to a Panel
higher the temperature, the shorter the service life and, the lower E5CC
the temperature, the longer the service life. Therefore, the service
life can be extended by lowering the temperature of the Digital There are two models of Terminal Covers that you can use with the E5CC.
Temperature Controller. Terminal Cover
Terminal Cover
(E53-COV17)
3. When two or more Digital Temperature Controllers are mounted (Sold separately) Adapter
(E53-COV23)
horizontally close to each other or vertically next to one another,
the internal temperature will increase due to heat radiated by the
Digital Temperature Controllers and the service life will decrease.
In such a case, use forced cooling by fans or other means of air
ventilation to cool down the Digital Temperature Controllers. When
providing forced cooling, however, be careful not to cool down the
terminals sections alone to avoid measurement errors.
Water Proof Packing
● Measurement Accuracy Panel
1. When extending or connecting the thermocouple lead wire, be sure to
1. For waterproof mounting, waterproof packing must be installed on
use compensating wires that match the thermocouple types.
the Controller. Waterproofing is not possible when group mounting
2. When extending or connecting the lead wire of the platinum resistance
several Controllers. Waterproof packing is not necessary when
thermometer, be sure to use wires that have low resistance and keep
there is no need for the waterproofing function.
the resistance of the three lead wires the same.
2. Insert the E5CC into the mounting hole in the panel.
3. Mount the product so that it is horizontally level.
3. Push the adapter from the terminals up to the panel, and
4. If the measurement accuracy is low, check to see if input shift has
temporarily fasten the E5CC.
been set correctly.
4. Tighten the two fastening screws on the adapter.
● Waterproofing (Not applicable to the E5DC.) Alternately tighten the two screws little by little to maintain a
balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
The degree of protection is as shown below. Sections without any
specification on their degree of protection or those with IP@0 are not
waterproof.
Front panel: IP66, Rear case: IP20, Terminal section: IP00
When waterproofing is required, insert the Waterproof Packing on the
backside of the front panel. Keep the Port Cover on the front-panel
Setup Tool port of the E5EC securely closed. The degree of
protection when the Waterproof Packing is used is IP66. To maintain
an IP66 degree of protection, the Waterproof Packing and the Port
Cover for the front-panel Setup Tool port must be periodically
replaced because they may deteriorate, shrink, or harden depending
on the operating environment. The replacement period will vary with
the operating environment. Check the required period in the actual
application. Use 3 years or sooner as a guideline. If the Waterproof
Packing and Port Cover are not periodically replaced, waterproof
performance may not be maintained. If a waterproof structure is not
required, then the Waterproof Packing does not need to be installed.
52
E5CC/E5EC/E5AC/E5DC
Terminal Cover
(E53-COV24)
A
Terminal Cover
(E53-COV24)
Terminal Unit
Removing the Main Unit
Main Unit
Press in the two hooks on the Main Unit and remove the Main Unit
from the Terminal Unit.
(1)
1. Insert the E5DC into the mounting hole in the panel. (Attach the
Terminal Unit after you insert the Main Unit.)
2. Push the Adapter from the Terminal Unit up to the panel, and
temporarily fasten the E5DC.
3. Tighten the two fastening screws on the Adapter. Alternately
(2) tighten the two screws little by little to maintain a balance. Tighten
the screws to a torque of 0.29 to 0.39 N·m.
(1)
53
E5CC/E5EC/E5AC/E5DC
E53-COV17 E53-COV23
5.8 mm max.
5.8 mm max.
Adapter
Terminal Cover
(E53-COV17) Enlarged illustration of
(Sold separately) Terminal Section
E5EC/E5AC
Slightly bend the E53-COV24 Terminal Cover to attach it to the
terminal block as shown in the following diagram. The Terminal Cover
cannot be attached in the opposite direction.
Enlarged illustration of
Three-year Guarantee
● Period of Guarantee Note: Average Operating Temperature
Refer to the process temperature of the Unit mounted to a
The guarantee period of the Unit is three years starting from the date
control panel and connected to peripheral devices on condition
the Unit is shipped from the factory. that the Unit is in stable operation, sensor input type K is
selected for the Unit, the positive and negative thermocouple
Scope of Guarantee input terminals of the Unit are short-circuited, and the ambient
The Unit is guaranteed under the temperature is stable.
following operating conditions. Top
1. Average Operating Temperature Should the Unit malfunction during the guarantee period, OMRON
(see note): −10°C to 50°C shall repair the Unit or replace any parts of the Unit at the expense of
2. Mounting Method: Standard mounting OMRON.
Bottom
54
Read and Understand this Catalog
Please read and understand this catalog before purchasing the product. Please consult your OMRON representative if you have
any questions or comments.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of the
product in the customer's application or use of the product.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
Note: Do not use this document to operate the Unit.
OMRON ASIA PACIFIC PTE. LTD. OMRON (CHINA) CO., LTD. © OMRON Corporation 2011-2013 All Rights Reserved.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Room 2211, Bank of China Tower, In the interest of product improvement,
Alexandra Technopark, 200 Yin Cheng Zhong Road, specifications are subject to change without notice.
Singapore 119967 PuDong New Area, Shanghai, 200120, China CSM_8_1_0713
Tel: (65) 6835-3011/Fax: (65) 6835-2711 Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 Cat. No. H177-E1-04 0613 (1111)
Mouser Electronics
Authorized Distributor
Omron:
E5AC-CC4D5M-005 E5AC-CQ4A5M-009 E5AC-CQ4D5M-009 E5AC-CC4A5M-005 E5AC-CC4D5M-004 E5AC-
CQ4A5M-000 E5AC-CQ4D5M-000 E5AC-CX1DSM-800 E5AC-CX3DSM-804 E5AC-CX4A5M-013 E5AC-CX4D5M-
005 E5AC-PR2ASM-800 E5AC-PR4A5M-014 E5AC-QQ4A5M-000 E5AC-QQ4D5M-000 E5AC-CC4A5M-000 E5AC-
CC4A5M-014 E5AC-CC4D5M-013 E5AC-CQ4A5M-010 E5AC-CQ4D5M-010 E5AC-CX3ASM-800 E5AC-CX1ASM-
800 E5AC-CX3DSM-800 E5AC-CX4A5M-005 E5AC-CX4D5M-004 E5AC-PR0ASM-800 E5AC-PR4A5M-004 E5AC-
CC4A5M-013 Y92A-48H Y92S-P8 E5AC-PR4D5M-014 E5AC-QQ4A5M-011 E5AC-QQ4D5M-011 E5AC-QR4A5M-
011 E5AC-QR4D5M-011 E5AC-QX3ASM-808 E5AC-QX3DSM-810 E5AC-QX4A5M-011 E5AC-QX4D5M-011
E5AC-RR4A5M-011 E5AC-CX3ASM-804 E5AC-CX4A5M-004 E5AC-CX4D5M-000 E5AC-CX4D5M-014 E5AC-
PR4A5M-000 E5AC-PR4D5M-004 E5AC-QQ4A5M-010 E5AC-CC4A5M-004 E5AC-CC4D5M-000 E5AC-CC4D5M-
014 E5AC-CQ4A5M-011 E5AC-CQ4D5M-011 E5AC-QX1DSM-800 E5AC-QX3DSM-800 E5AC-QX4A5M-009
E5AC-QX4D5M-009 E5AC-RR4A5M-009 E5AC-RR4D5M-010 E5EC-PR4A5M-014 E5AC-QR4A5M-009 E5AC-
QR4D5M-009 E5AC-RX1ASM-800 E5AC-RX3ASM-810 E5AC-RX4A5M-000 E5AC-RX4D5M-000 E5EC-CQ4A5M-
000 E5EC-CQ4D5M-000 E5EC-PR2ASM-804 E5EC-PR4D5M-000 E5AC-QQ4D5M-010 E5AC-QR4A5M-010
E5AC-QR4D5M-010 E5AC-QX3ASM-800 E5AC-QX3DSM-808 E5AC-QX4A5M-010 E5AC-QX4D5M-010 E5AC-
RR4A5M-010 E5AC-CX4A5M-000 E5AC-CX4A5M-014 E5AC-CX4D5M-013 E5AC-PR2ASM-804 E5AC-PR4D5M-
000 E5AC-QQ4A5M-009 E5AC-QQ4D5M-009 E5AC-RR4D5M-011 E5AC-RX3ASM-808 E5AC-RX3DSM-810
E5AC-RX4A5M-011 E5AC-RX4D5M-011 E5EC-CQ4A5M-011 E5EC-CQ4D5M-011 E5EC-PR2ASM-800 E5EC-
QR4A5M-000 E5EC-QR4D5M-000 E5EC-QX4A5M-000 E5EC-QX4D5M-000 E5EC-RR4A5M-000 E5EC-RR4D5M-
000 E5EC-RX4A5M-000 E5EC-RX4D5M-000