GS690 Installation Manual Rev A
GS690 Installation Manual Rev A
1
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Product execution standard:UL864,Tenth Edition
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in this installation manual. These
instructions must be followed to avoid damage to this product and associated equipment. Product operation
and reliability depends upon proper installation.
DO NOT INSTALL ANY PRODUCT THAT APPEARS DAMAGED. Upon unpacking your equipment, inspect the
contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs.
Servicing should be performed by qualified personnel.
STATIC HAZARD - Static electricity can damage sensitive electronic components. Therefore, the following precautions must be followed:
• Ground yourself with a proper wrist strap before opening or handling any circuits or components.
• Prior to installation, keep components wrapped in anti-static wrapper at all times.
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency energy and if not
installed and used in accordance with the instruction manual, may cause interference to radio
communications. It has been tested and found to comply with the limits for a Class A computing device
pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against
such interference when operated in a commercial environment. Operation of this equipment in a residential
area may cause interference in which case the user at his own expense will be required to take whatever
measures may be required to correct the interference.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES -Reacceptance testing is required after any change,
addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In
addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
Copyright © 2018 SITERWELL ELECTRONICS CO.,LTD LIMITED. No portion of this manual may
be copied, reproduced in any form, modified or quoted without the written permission of
copyright holder.
This product will not be perfected and upgraded regularly. SITERWELL ELECTRONICS CO.,LTD LIMITED. Reserves the
right to revise this manual without prior notice.
2
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
目录
1. PRECAUTIONS FOR USE ..................................................................................................................................................... 6
2.4.2 Indications .............................................................................................................................................. 12
3.6.2 Relay ........................................................................................................................................................ 24
4. PROGRAMMING ................................................................................................................................................................... 26
4.3.8 General .................................................................................................................................................... 41
5 CONDITIONS .......................................................................................................................................................................... 49
7 SERVICE ................................................................................................................................................................................. 53
9 BATTERY CALCULATION................................................................................................................................................... 58
5
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
The GS690 addressable control and indicating panel forms the central part of a fire detection and alarm system. The
panel is available with 1 or 2 addressable loops and is easy to install and operate. A central microprocessor delivers
reliable operation and requires minimum maintenance.
The GS690 control and indicating panel is compatible with SITERWELL addressable detectors and other devices, such
as manual pull stations and audio/visual alarm devices. They are suitable for small and medium-sized buildings.
This Manual provides installers with instructions to install, use and service the GS690 control and indicating panel using
revision 1.0 operating firmware.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F and at a relative humidity of 93 ±2%
RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that
this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications section
for maximum allowable I.R. drop from the specified device voltage. Like all solid state electronic devices, this system
may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or
outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the
Technical Services Department if any problems are anticipated or encountered.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper
installation by authorized personnel.
7
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
2. INTRODUCTION
2.1 Feature
The GS690 includes features that provide a flexible solution for small and medium-sized buildings. The equipment
is easy to install and quick to configure and use. A reliable microprocessor delivers trouble-free operation,
lowering service costs and increasing up-time.
Features:
32 bit processor ARM Cortex-M3
High contrast backlit LCD provides 4 rows of 40 characters for device and system status
Separate individual detection zone fire LED indicators
Automatic device detection on start-up
Automatic device type-code verification
4 Access Levels
Real Time Clock
4000 event history log
Day/night mode configurable
Manual activation of alarm devices
Supervised auxiliary DC 24 V output (Only use to provide power for Strobes/Horns)
2 programmable non-addressable alarm output circuits
2 unmonitored relay contacts for Fire Alarm Condition outputs
1 unmonitored relay contact for Fault Condition output
Surface mounting enclosure
Supports up to 64 Repeater Panels (reserved)
LOOP:
Single loop only, single loop expandable to 2-loop, or2-loops
127 addressable devices per loop
40 configurable zones
64 configurable input groups
64 configurable output groups
10 addressable audio/visual alarm devices per loop
Class A or Class B wiring (Only Class B when connected with Strobes/Horns)
Network options:
RS485 Communication interface(reserved)
USB 2.0 Interface for PC Connectivity(reserved)
Ethernet interface for computer communication(reserved)
Circuits are Not Used:
5V/GND/OUT
GND/EV
GND/REM
8
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
2.2 Factory Default Settings
This control and indicating equipment is supplied ready to operate as a standard addressable control panel. Optional
functions and their configuration are described in following sections.
2.3 Specifications
Power Supply
Operating voltage AC(110~220)V,50/60Hz
Mains supply Current Limit 2.1A
Mains supply fuse 4A/AC 250V slow blow(20mm)
Power supply [email protected]
Standby battery maximum capacity (2xDC 12V) 12Ah
Maximum battery current draw 1.2A@maximum operating temperature
Charging Circuit 28V,±2% Nominal
Battery fuse 1A resettable(electronic fuse)
Battery fault threshold voltage < DC 20V
Quiescent current 100mA @ DC28.5V
Addressable Loops
Addressable loops 2
Number of connected devices per loop 127
Loop current(max) 100mA @40ohms(max) @24V DC per loop
Loop monitoring Open, short-circuit and Ground
Power Limited
Audio Alarms
Configurable audio alarm groups(max) 7
9
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Non-addressable audio alarm device driver 220mA (Line Drop: 2.4V) (Total)
Non-addressable audio alarm end-of-line resistor 10KΩ
Alarm zone monitoring Open , Ground, and short-circuit
Power Limited
Alarm zone voltage(max) DC 24V
Current Rating for Regulated, mA 22
Current Rating for Special Applications, mA 220
Alarm zone fuse 1A resettable(electronic fuse)
24-Aux Output (Use to power Strobes/Horns Only)
Nominal output voltage, Vdc 24
Recorded Voltage range for compatibility, V 17.2-27.7
Maximum circuit output current, A 1.35
Supervised and synchronized
Power Limited
Current Rating for Regulated, A 0.135 (max 1 NAC device)
Current Rating for Special Applications, A 1.35 (max 10 NAC devices)
Max line Impedance (ohms) 2 (per loop)
Ancillary Outputs
Number of programmable output relays 3(Power factor 1)
Ancillary fire C/O relay 2x(1.0A@DC30V)
Ancillary Inputs
Evacuation start/stop Non-latching, voltage-free
Miscellaneous
Terminal Wiring 28 -14AWG (0.5~+1.6)mm2
Operating temperature (0~+49)℃
Operating humidity (0~93)%RH, Non-condensing
Storage temperature (-25~+80)℃
Storage humidity (0~98)%RH, Non-condensing
Dimensions(LxWxH) 440x354x140.5mm
Weight (excluding batteries) ≤9.0kg
Ground Fault Impedance value 0 ohm.
10
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
2.4 Controls and Indicators
Figure – 1
RESET Key:
Resets the fire detection and alarm system after silence in alarm condition.
Key operation is a memory event when operated to reset the system.
User or Admin password protected.
MENU Key:
To enter or exit menu mode or return the previous menu. Under normal conditions, pressing the menu key will
display enter password within 10s, after entering the password with the NUMBER keys, press ENTER key to
confirm. Entering the correct password enables the menu mode, an incorrect password will revert to the default
display. Once in menu mode subsequent pressing of the menu within 10s. Enables access to additional functions
based on password access level.
11
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
CURSOR KEYS:
To move the cursor point in the LCD as required.
DISABLED Key:
To review the queue of disable items step by step or quickly. The disable item list includes the status of Zone
groups, in groups, out groups, loops, devices on two loops, NACs. An event in the queue will be displayed for 10s,
after which the LCD will revert to the default display.
ENTER Key:
To confirm the current operation.
ACK. Key:
To silence internal buzzer in alarm condition or fault condition.
This operation is recorded as memory as an event when operated to silence the internal buzzer.
User or Admin password protected.
TEST Key:
Illuminates all LEDs, LCD segments and activates the inner buzzer.
NUMBER Key:
These keys are used for entering password, date or time, etc.
FIRE Key:
The FIRE LED will flash if an input device is reporting a fire. Pressing the button will sequentially display the queue
of fire events step by step or quickly. Once the queue has been reviewed, the FIRE led will be on steady. If a new
event occurs, the LED will begin to flash. An event in the queue will be displayed for 10s, after which time the LCD
will display the first alarm event.
PREALARM Key:
The PREALARM LED will flash if a device is reaching the alarm threshold level. Pressing the button will
sequentially display the queue of pre-alarm events step by step or quickly. Once the queue has been reviewed,
the PREALARM led will be on steady. If a new event occurs, the LED will begin to flash. An event in the queue will
be displayed for 10s, after which time the LCD will display the first pre-alarm event or the first fire event if a Fire
Condition exists or the first fault event if a Fault Condition exists.
FAULT Key:
The FAULT LED will flash if an input device is reporting a fault. Pressing the button will sequentially display the
queue of fault events step by step or quickly. Once the queue has been reviewed, the FAULT LED will be on
steady. If a new event occurs, the LED will begin to flash again. An event in the queue will be displayed for 10s,
after which time the LCD will display the first fault event or the first fire event if a Fire Condition exists.
2.4.2 Indications
2.4.2.1 LCD Indication
The 40X4 Characters LCD is mainly used for programming of the panel. It also displays all events along with the LED
indication except system fault.
12
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
2.4.2.3 Common Indication
FAULT Yellow
Indicates a Fault Condition. The LED will flash with un-acknowledged faults and will be on steady when acknowledged.
(Fault information will be displayed on the LCD, and depending on the source of the fault, the corresponding indicator
will flash.)
FIRE Red
Indicates the Alarm Condition. The LED will flash with un-acknowledged alarms and will be on steady when
acknowledged. (Alarm zone information will be displayed on the FIRE indicators. Alarm device information will be
displayed on the LCD.)
Indicates an operating system software execution fault. The LED will illuminate concurrently the Fault LED will
illuminate and internal buzzer will continuously sound.
SYSTEM ON Green
Indicates the system is in working mode. The LED will flash in the INSTALLATION MODE and be steady on during the
ACTIVE MODE.
MAINS ON Green
Indicates the status of the primary power source. The LED flashing indicates that the primary source voltage is low,
steady illumination indicates that primary source is at full power extinguished indicates that the primary source is
unavailable (Fault information will be displayed on the LCD).
BATTERY ON Green
Indicates the status of standby source. The LED flashing indicates that the standby source voltage is low, steady
illumination indicates that standby source is fully charged and extinguished indicating that the standby source is
unavailable (discharged). (Fault information will be displayed on the LCD)
Indicates status of the charger circuit condition. The LED illuminating indicates that the charger circuit trouble,
extinguished is normal status l. (Fault information will be displayed on the LCD)
Indicates a ground fault. The LED illuminating indicates a ground fault or that the ground reference is disconnected.
Normal status is extinguished. (Fault information will be displayed on the LCD)
BUZZER Yellow
Indicates the status of internal buzzer. The LED flashing indicates the internal buzzer pulsing alarm and illuminating
indicates the inner buzzer continuous alarm.
DISABLED Yellow
Indicates a disabled condition. The LED illuminating indicates that disabled condition is present on the system.
Extinguished indicates no disablements on the system.
13
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
TEST Yellow
Indicates test mode. The LED illuminating indicates that system is in test mode and testing communication to devices.
PRE-ALARM Yellow
Indicates a device is reaching the alarm threshold level. The LED will flash with un-acknowledged alarms and be on
Steady when acknowledged. (Pre-alarm information will be displayed on the LCD.)
The LED illuminating indicates that it is operating in the Night Mode. When extinguish edit is operating in the Day Mode.
Indicates status of Notification Appliances Circuits. The LED will flash with un-acknowledged faults and be on steady
when acknowledged. (NAC fault information will be displayed on the LCD)
SILENCED/ALARM Yellow
Indicates the status of alarm circuit. The LED illuminating indicates that audio/visual alarm devices is activated。
2.5.1 General
The main circuit board provides system control and visual indication control and contains the system microcontroller,
programming part (USB-2.0) and non-volatile memory for system events storages. The main circuit board is used for
the critical functions like programmable logic and timing functions and non-critical functions, like customer zone and
device messages.
The visual display board consists of a series LED’s for common indication of power, alarm, and fault. The display board
has 40 X 4 characters LCD, which describes system information with real time clock and enables the user to easily
program the system options. It also contains the matrix touch key pad, which enables the user access.
The LCD, indicator and key are installed in front of the motherboard. Connectors are installed on the back of the
motherboard and at the top.
The rear of the motherboard has a connector for an optional single-loop expansion daughter board. When fitted, the
GS690 has 2 loops for up to 254 field devices. Most components are located on the rear of the motherboard, including
the internal sounder.
14
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Figure – 2
Figure – 3
15
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
2.5.3 Non-addressable Audio Alarm Devices
Two alarm output circuits (NAC1 and NAC2) are provided for non-addressable audio alarm devices, including bells.
These should not be confused with addressable audio/visual alarms, which are connected directly to, and powered
from the addressable loop.
The maximum combined output current is 220 mA. All audio alarm devices must be voltage polarity sensitive.
Non-polarized alarm devices will indicate a Fault Condition. The alarm zone circuits are protected against short-circuit.
An electronic fuse will reset when the short circuit is removed and the control panel is reset.
The audio/visual alarm device circuits are monitored for open-and short-circuit conditions. If no devices are installed, a
10kΩ resistor (P/N: Reol) should be fitted to the NAC1 and NAC2 terminals to prevent a Fault condition Being
Reported by the control and indicating equipment.
Figure – 4
The total current should not exceed the power rating of the control and indicating equipment. Refer to the
Technical Specifications.
Figure – 5
Figure – 6
16
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
2.5.6 PC connection (reserved)
An RS-485 connector is provided to connect the control and indicating equipment to the serial port of the PC. The
connection enableds the downloading of configuration data, including device descriptors.
Figure – 9
Figure – 10
2.7 Reset
One reset can be made.
A system reset is performed by pressing the RESET button and initiates a warm restart. During the reset, power is
removed from the addressable loop for 12s. Power is re-applied for 20s prior to loop polling commencing.
Figure –12
18
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Figure –13
Caution:The power limited and non-power limited circuit wiring must remain separated in the cabinet. All power
limited circuit wiring must remain at least 0.25inch (6.35mm) away from any other non- power limited circuit wiring and
non-power limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits.
NOT USED
NOT USED
Figure –14
19
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
3. INSTALLATION
20
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Figure –15
Warning: Shall only use stranded wires for all field wires.
Figure –16
21
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
3.5 Panel Wiring
Figure –17
Figure –18
22
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
3.6 Master Board
Figure –19
Figure 20
Caution:It is suggested that the ferrite beads be added into loop port, NAC port and auxiliary power port so as to
increase the ability of radio anti-interference. The operating instructions show as Figure 20.
Figure –21
When more than two nodes on RS485 network are present, please open the farthest end of the actuator, move
SW2 to ON position to enable the internal matching resistance, if is not convenient to open the internal
actuators, the impedance matching can be placed directly on the RS485 bus By a A, B side jumper 120 ohm
resistor.
3.6.2 Relay
Provide 3 relay output to control peripheral equipment and relay contact capacity1A, 30VDC,(Max. Output Res. load).
Figure –22
Note: If the relay outlet is to be used with the large current equipment, it is recommended to be used in conjunction with
a large power intermediate relay.
3.6.4 NAC
The total rated current of the supervised NAC is 0.22 ampere. It provides stable output for the NAC (notification device
circuit).
24
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Figure –23
25
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
cabled screens to earth.
Note: Bell circuits (NAC1/NAC2) shall not be installed in the same notification zone as the Strobe/Horns circuit (24-Aux)
4. PROGRAMMING
26
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
27
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
28
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
29
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
30
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
31
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
32
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
4.3 Program Menu
Program Menu is used to make changes to default system settings. The changes allow customization of the system to
enhance performance for a specific installation. Admin Level is required to enter the Program mode. In the Program
mode, the following menu items are available except Restore Factory Setting. For User Level, the default authority of the
Program Menu is denied and can improve the authority of User Level.
33
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
5-1-4 Inhibit Aux-Relay
5-1-5 Timed-Sens
The Control and indicating equipment is supplied from the factory in INSTALLATION mode.
The SYSTEM ON LED will flash to indicate INSTALLATION mode. When power is applied, the panel automatically detects
and memorizes all the devices connected to the addressable loop. Changing to ACTIVE mode, it will be reported Fault
condition if the devices removed from the loop, or other devices installed on the loop.
If an event occurs when in Program mode, the event condition will be reported and a manual operation is required to exit
Program mode to view the event information.
4.3.1.1.2 Operation
1) By pressing the 【1】key from View screen enters into the History mode.
2) Press the【UP】or 【DOWN】keys to look through the log step by step or quickly.
3) Press the 【MENU】key to return to the previous menu.
4.3.1.2.2 Operation
1) By pressing the 【2】key from View screen enters into the Read/Clear Auto-start count mode.
2) The count is displayed. Press 【ENTER】key to clear the auto-start count.
3) Press【MENU】key to return to the previous menu.
34
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
DD/MM/YY <Panel Status> HH:MM:SS
1. Zone Status
2. Zone to Device
3. Zone Delay [Zones]
4.3.2.1.2 Operation
1) By pressing the 【1】key from the Zones screen enters into the Zone Status mode.
2) Press the 【UP】or【DOWN】keys to select the zone number step by step or quickly. The status of the zone will
be displayed to the below of the zone number (ENABLED OR DISABLED).
3) Press the 【LEFT】or 【RIGHT】keys to move the cursor between zone number and zone status.
4) Press the 【UP】or 【DOWN】keys to select ENABLED or DISABLED status.
5) Press the 【ENTER】key to confirm the selected status.
6) Press 【MENU】key to return to previous menu.
4.3.2.2.2 Operation
1) By pressing the 【2】 key from the Zones screen enters into the Zone Device mode.
2) Press direction key to select loop number, device number or zones number. If the zone number shown is 000,
then no zone has been assigned to the device.
3) When the desired zone number is shown, press the 【ENTER】button to confirm the selection.
4) After that, it will change to the next device and the zone assignment process can be continued.
5) Press【MENU】key to return to the previous menu.
4.3.2.3.2 Operation
1) By pressing the 【3】 key from the Zones screen enters into the Zone Delay mode.
2) Press direction keys to select zone number, status, minutes, seconds.
3) The status of zone delay is the IMMEDIATE or DELAYED. DELAYED indicates the delay time will assigned to
35
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
the zone.
4) Press【ENTER】key to confirm the selection.
5) Press【MENU】key to return to the previous menu.
4.3.3.1.2 Operation
By pressing the 【1】 key from the Input screen enters into the In Grp Status mode.
Press the 【UP】or【DOWN】keys to select the input group number step by step or quickly. The status of the input
group will be displayed to the below of the input group number (ENABLEDOR DISABLED).
Press the【LEFT】or【RIGHT】keys to move the cursor between input group number and input group status.
Press the【UP】or【DOWN】keys to select ENABLED or DISABLED status.
Press the【ENTER】key to confirm the selected status.
Press 【MENU】key to return to previous menu.
4.3.3.2.2 Operation
By pressing the 【2】 key from the Input screen enters into the Out Grp to In Grp mode.
Press direction key to select Input group number and Output group. If the output group number shown is 000, then no
output group has been assigned to input group.
When the desired output group number is shown, press the 【ENTER】button to confirm the selection.
After that, it will change to the next input group and the output group assignment process can be continued.
Press 【MENU】key to return to the previous menu.
4.3.3.3 In Grp to Device(Menu Item 3-3)
4.3.3.3.1 Description
Input Devices like Detectors, Manual Call Point or Input Module can be grouped together in up to 64 discrete Input
group.
36
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
4.3.3.3.2 Operation
By pressing the 【3】 key from the Input screen enters into the In Grp to Device mode.
Press direction key to select loop number, device number or input group number. If the input group number shown is
000, then no input group has been assigned to the device.
When the desired input group number is shown, press the 【ENTER】button to confirm the selection.
After that, it will change to the next device and the input group assignment process can be continued.
Press【MENU】key to return to the previous menu.
4.3.4.1.2 Operation
1) By pressing the 【1】key from the Output screen enters into the Out Grp Status mode.
2) Press the 【UP】or 【DOWN】keys to select the output group number step by step or quickly. The status of the
output group will be displayed to the below of the output group number (ENABLED OR DISABLED).
3) Press the 【LEFT】or 【RIGHT】keys to move the cursor between output group number and output group status.
4) Press the 【UP】or 【DOWN】keys to select ENABLED or DISABLED status.
5) Press the 【ENTER】key to confirm the selected status.
6) Press 【MENU】key to return to previous menu.
4.3.4.2.2 Operation
1) By pressing the【2】key from the Output screen enters into the Fault Out Grp mode.
2) Press the 【UP】or 【DOWN】keys to select the output group number.
3) Press the 【ENTER】key to confirm the selected status.
4) Press【MENU】key to return to previous menu.
4.3.4.4.2 Operation
1) By pressing the 【4】 key from the Output screen enters into the Out Grp Delay mode.
2) Press direction keys to select output group number, status, minutes, seconds.
3) The status of output group delay is the IMMEDIATE or DELAYED. DELAYED indicates the delay time will
assigned to the output group.
4) Press【ENTER】key to confirm the selection.
5) Press【MENU】key to return to the previous menu.
4.3.5.1.2 Operation
1) By pressing the 【1】 key from the Device screen enters into the Loop Status mode.
2) Press the【UP】or【DOWN】keys to select the loop status (ENABLED OR DISABLED).
3) Press the【ENTER】key to confirm the selected status.
4) Press 【MENU】key to return to previous menu.
38
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
4.3.5.2 Device Status(Menu Item 5-1-2)
4.3.5.2.1 Description
An individual addressable device may be disabled or enabled. When disabled, the device will not report fire or fault
events and no outputs will activate.
However, audio/visual alarm devices will continue to operate in the Alarm Condition.
Disabled devices will be indicated on the LCD and can be reviewed using 【DISABLED】key.
4.3.5.2.2 Operation
1) By pressing the 【2】 key from the Device screen enters into the Device Status mode.
2) Press direction keys to select the loop number, devices number and status information.
3) Press the 【ENTER】key to confirm the selected status and it will change to the next device status for further
disabled/enabled assignments.
4) Press 【MENU】key to return to previous menu.
4.3.5.3.2 Operation
1) By pressing the 【3】 key from the Device screen enters into the Device to Evacuate mode.
2) Press direction keys to select the loop number, devices number and status information.
3) Select the status UNAFFECTED or IMMEDIATE.
4) Press the 【ENTER】key to confirm the selected status and it will change to the next device status for further
unaffected/immediate assignments.
5) Press 【MENU】key to return to previous menu.
4.3.5.4.2 Operation
1) By pressing the 【4】 key from the Device screen enters into the Inhibit Aux-Relay mode.
2) Press direction keys to select the loop number, devices number and inhibited information.
3) Select the inhibited status NONE or ALL.
4) Press the 【ENTER】key to confirm the selected status and it will change to the next device status for further
none/all assignments.
5) Press【MENU】key to return to previous menu.
39
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
4.3.5.5.2 Operation
1) By pressing the 【5】 key from the Device screen enters into the Timed-Sens mode.
2) Press direction keys to select sensitivity level for day sensitivity and night sensitivity.
3) Press the 【ENTER】 key to confirm the selected sensitivity level and it will automatically return to previous
menu.
4.3.6.1.2 Operation
1) By pressing the 【1】 key from the Device screen enters into the Set Device Heat Grade mode.
2) Press direction keys to loop number, devices number and heat level.
3) Press the【ENTER】key to confirm the selected heat level and it will automatically change to the next device to set
heat grade.
4) Press【MENU】key to return to previous menu.
4.3.6.2.2 Operation
1) By pressing the 【2】 key from the Device screen enters into the Set Device Smoke Sensitivity mode.
40
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
2) Press direction keys to select loop number, devices number and sensitivity level.
3) Press the 【ENTER】key to confirm the selected sensitivity level and it will automatically change to the next
device to set smoke sensitivity level.
4) Press 【MENU】key to return to previous menu.
4.3.7.1.2 Operation
1) By pressing the 【1】 key from the Test screen enters into the Device mode.
2) Press direction keys to select loop number, devices number.
3) Press【MENU】key to return to previous menu.
4.3.7.2.2 Operation
1) By pressing the 【2】 key from the Test screen enters into the Light mode.
2) Press direction keys to select loop number, devices number, and light status.
3) Press 【ENTER】 key to toggle between LIGHT ON and LIGHT OFF.
4) Press 【MENU】 key to return to previous menu.
4.3.8 General
4.3.8.1.2 Operation
1) By pressing the 【1】 key from the General screen enters into the RTC-Set mode.
2) Press direction keys to select date and time.
3) Press NUMBER keys to enter the corresponding date and time.
4) Press 【ENTER】 key to confirm, if correct the LCD will prompt MODIFY SUCCESSFUL and error the LCD will
prompt FORMAT ERROR! MODIFY AGAIN!
5) Press 【MENU】key to return to previous menu.
4.3.8.2.2 Operation
1) By pressing the 【2】 key from the General screen enters into the Day/Night mode.
2) Press direction keys to select day and night time.
3) Press NUMBER keys to enter the corresponding day and night time.
4) Press 【ENTER】 key to confirm, if correct the LCD will prompt MODIFY SUCCESSFUL and error the LCD will
prompt FORMAT ERROR! MODIFY AGAIN!
5) Press 【MENU】key to return to previous menu.
4.3.8.3.2 Operation
1) By pressing the 【3】 key from the General screen enters into the Delay Night mode.
2) Press the【UP】or【DOWN】key to select UNAFFECTED or OFF.
3) Press【ENTER】key to confirm the selection and it will automatically return to previous menu.
4.3.8.4.2 Operation
1) By pressing the 【4】 key from the General screen enters into the Config Eva-Timer mode
2) Press direction keys to select Mins, Secs and status.
3) Press【ENTER】key to confirm the selection and it will automatically return to previous menu.
4.3.8.5.2 Operation
1) By pressing the 【5】 key from the General screen enters into the Dev Eva-Timer mode.
2) Press direction keys to select loop number, devices number and the status of timer.
3) Select the status of timer UNAFFECTED or STARTED.
4) Press【ENTER】key to confirm the selection and it will change to the next device.
5) Press【MENU】key to return to previous menu.
4.3.9.1 Pre-alarm
Control panel setup in pre-alarm status, the pre-alarm indicator would flash when a device caused an
alarm.
4.3.9.1.1 Description
Any two devices can be configured to activate evacuation. it means when both of devices at same time detect the fire
43
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
signal. In this case, Disabled audio/visual alarm devices will also be activated.
4.3.9.1.2 Operation
1) By pressing the 【1】 key from the General screen enters into the Two Dev-Evacuate mode.
2) Press the【UP】and【DOWN】key to select DISABLED or ENABLED.
3) Press【ENTER】key to confirm the selection.
4) Press【MENU】key to return to previous menu.
4.3.9.2.2 Operation
1) By pressing the 【2】 key from the General screen enters into the Call Point Evacuate mode.
2) Press the【UP】and【DOWN】key to select DISABLED or ENABLED.
3) Press【ENTER】key to confirm the selection.
4) Press【MENU】key to return to previous menu.
4.3.9.3.2 Operation
1) By pressing the 【3】 key from the General screen enters into the NAC Status mode.
2) Press the direction keys to select status and type of NACs.
3) Press【ENTER】key to confirm the selection and it will automatically to return the previous menu.
44
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
devices are made or new devices are added without being in Installation mode, the changes will not be learnt and
errors will not be reported.
Active mode is used following completion of commissioning. The SYSTEM ON LED will illuminate under this mode. In
Active mode, any changes occur in devices which will be reported like removing the devices or adding a new device.
4.3.10.1.2 Operation
1) By pressing the 【1】 key from the General screen enters into the System Mode.
2) Press the【UP】or【DOWN】keys to select system status Active or Installation.
3) Press【ENTER】key to confirm the selection.
4) Press【MENU】key to return to previous menu.
4.3.10.2.2 Operation
1) By pressing the 【2】 key from the General screen enters into User Code mode.
2) According to the flow diagram can set User code.
4.3.10.3.2 Operation
1) By pressing the 【3】 key from the General screen enters into Admin Code mode.
2) According to the flow diagram can set Admin code.
4.3.10.4 User Authority (Menu Item 7-3-4)
4.3.10.4.1 Description
Functions available at User Level can be configured. Three optional authority may be selected:
NONE, where no authority are available at User Level.
READ ONLY, where the authority can be read but not configured.
FULL ACCESS, where the authority can be read and configured.
User Level do not have authority to set Menu Item 7-3-3 and 7-3-5, and Menu Item 7-3-4 cannot be set to FULL
ACCESS at User Level.
The default setting is NONE.
4.3.10.4.2 Operation
1) By pressing the 【4】 key from the General screen enters into User Authority mode.
2) Press direction keys to select the desired Menu Item or authority level.
3) Press【ENTER】key to confirm the setting and it will change to the next Menu Item setting.
4) Press【MENU】key to return to previous menu.
45
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
4.3.10.5 Restore Factory Settings (Menu Item 7-3-5)
4.3.10.5.1 Description
The factory default settings can be restored, erasing all configuration data. Restoring to default settings will also erase
any settings pre-configured during the equipment manufacture. The equipment will default to Installation mode.
Restoring to default settings is only available at Engineer Level.
4.3.10.5.2 Operation
Please contact Siterwell Customer Service.
4.3.10.6.1.2 Operation
1) By pressing the 【1】 key from the Commun screen enters into USB mode.
2) Press the【UP】and【DOWN】key to select the status DISABLED or ENABLED.
3) Press【ENTER】key to confirm the selection and it will automatically return to previous menu.
4.3.10.6.2.2 Operation
1) By pressing the 【2】 key from the Commun screen enters into RS485 mode.
2) Press the direction keys to select the status DISABLED or ENABLED or Main Panel ID number.
3) Press【ENTER】key to confirm the selection and it will automatically return to previous menu.
4.3.10.6.3
4.3.10.6.3.1 Description
The status of ETHERNET communication can be configured to DISABLED or ENABLED. Once setting the
ENABLED, it will enter into the configuration of Router IP Address, IPV4 Address, Mask Address and Port number.
46
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Maximum up to 8 Main Panels can make a network group by Ethernet port.
The default status of Ethernet communication is DISABLED.
Disabled Ethernet will be indicated on the LCD and can be reviewed using【DISABLED】key.
4.3.10.6.3.2 Operation
1) By pressing the 【3】 key from the Commun screen enters into Ethernet mode.
2) Press the【UP】or【DOWN】key to select the status DISABLED or ENABLED.
3) If select DISABLED, press【ENTER】key to confirm the selection and it will automatically return to previous
menu.
4) If select ENABLED, it will enter into the configuration of Router IP Address, IPV4 Address, Mask Address and
Port number.
5) Press【ENTER】key to confirm the selection and it will automatically return to previous menu.
Four access levels are used to operate or configure the control and indicating equipment.
48
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
5 CONDITIONS
Figure – 26
50
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Once all devices in fault have been viewed, the QUEUE REVIEW FAULT LED will be on steady. After 20 s, the
LCD will revert to the first fault event (or the first fire alarm event if a fire alarm is present).
Tests of the control and indicating equipment and connected devices confirm the correct operation of the fire detection
and alarm system.
Tests cannot be conducted in the following circumstances.
In the Fire Alarm condition.
When the audio/visual alarms have been activated.
When the control panel is in the INSTALLATION mode.
51
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
5.6.1 Indicator Test
Press the INDICATOR TEST button. All visual indicators, segments on the LCD, and the internal sounder will activate
until the INDICATOR 【TEST】 button is released.
Figure –27
52
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Battery Fault Indicates the unavailability of the battery power, Check that the battery connections are secure.
or a voltage level less the DC 20V. The battery Measure the battery voltage. If the battery
may be depleted because the mains supply has voltage is less than the manufacturer's minimum
been unavailable for an extended period of voltage, replace the batteries.
time, or there is a fault in the battery charger Measure the battery charging voltage to ensure
that prevents the batteries from being charged. the battery charger is operating correctly.
System Fault Indicates a fault with the internal supply Contact the service company to replace the
voltages used to supply power to the main controller.
microprocessor, or to the running of the control
program.
Earth Fault Indicates a current leakage from any of the fire Isolate each of the transmission paths in turn
detection and alarm system wires to Earth. This until the wires causing the Earth have been
may occur if there is damage to a single identified. Trace the faulty wires to locate the
conductor, and it contacts some conductive source of the connection to Earth, and prevent
equipment connected to Earth. the connection path.
7 SERVICE
7.1 Installation/Replacement
Figure –28
Figure –30
54
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Figure –31
Figure –32
If the mains fuse is blown, replace it with 4A/AC250V slow blow (20mm).
55
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
7.2 Service Functions
The following Menu Items will assist in ensuring the fire detection and alarm system operates at optimal performance.
Menu
Preference Title Description
Item
A rolling list of 4000 events are stored. The log assist in
forensic analysis of past events and can be used to
1-1 Display historic log
determine the timing and any relationship between
events.
Each time power is applied to the equipment, the count
increments. The count can assist in determining if
1-2 Read/clear auto start count power if interrupted in an uncontrolled or intermittent
manner.
A system reset does not increment the count.
The status of devices connected to the analogue loop,
including device type, value and dynamic analogue
sensing value, can be reviewed.
The function can be used to check that all loop devices
6-1 Device count, Type & value are present and to confirm the device address.
In installation Mode, the device count will change as the
control and indicating equipment detects additions or
removal of devices.
In Active Mode, the device value is dynamic.
Service intervals may be set by local regulations.
7.3 Inspections
Conduct the following inspections every 6 months.
1) Inspect detectors for any condition that is likely to adversely affect their operation, such as excessive deposition of
dust or coating of paint.
2) Inspect battery condition for signs of corrosion.
3) Inspect manual call points for clearance and ease of access.
4) Inspect alarm devices for clearance, visibility, and marking
5) Inspect the documentation to ensure it is available and complete.
7.4 Tests
8 WIRE REQUIREMENTS
Connecting external system accessories to the GS690 main circuits must be carefully considered to ensure proper
operation. It is important to use the correct type of wire, wire gauge and wire run length per each GS690 circuit.
Reference the chart below to specify wire requirements and limitations for each GS690.
RECOMMENDED
CIRCUIT CIRCUIT WIRE TYPE AND
MAX. DISTANCE WIRE GUAGE
TYPE FUNCTION LIMITATIONS
Feet (meters)
9 BATTERY CALCULATION
Use the table below to calculate the total standby and alarm load for ampere hour (AH).
This total load determines the battery size (in AH), required to support the control panel under the fail of the AC Power
Supply as follows:
1. Enter the NFPA standby and alarm times (refer to NFPA requirements below).
2. Calculate the ampere-hours for standby and Alarm, and then sum the standby and alarm ampere-hours.
3. Multiply the sum by the derating factor of 1.25 to calculate the proper battery size (in AH). Minimum battery derating
factor is 20%.
4. Write the ampere hour requirements on the protected premises label located inside the cabinet door.
Current Current
Device Type Qty Total Qty Total
Draw Draw
Main Circuit Board 1 x 0.100000 = 0.100000 1 x 0.160000 = 0.160000
Loop Board 2 x 0.040000 = 0.08 2 x 0.070000 = 0.14
Addressable Devices
GS620 0 x 0.000200 = 0 0 x 0.000400 0
GS621 0 x 0.000400 = 0 0 x 0.025000 0
GS22-A 0 x 0.000500 = 0 1 x 0.130000 0
GS623 0 x 0.000500 = 0 0 x 0.03000 0
GS650 0 x 0.000200 = 0 0 x 0.003000 0
GS670(future) 0 x 0.000200 = 0 0 x 0.003000 0
Sum each column for totals Total Standby Current 0.180000 Total Alarm Current 0.30000
58
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
24 Hours
Standby Load Current (Amps) 0.1800A x 24 = 2.400AH
Required Alarm Time in Hours
5 Minutes
Alarm Load Current (Amps) 0.30A x 0.084 = 0.0252AH
Standby and Alarm Load Subtotal = 4.3452AH
Derating Factor = x 1.25
59
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
TEST CERTIFICATE
We hereby certify that the items details hereon have been manufactured, inspected
and electrically tested to ensure the compliance with Siterwell products and process
specification.
Model No.:
Serial No.:
For SITERWELL ELECTRONICS CO.,LTD LIMITED
60
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
WARRANTY CERTIFICATE
Model No.:
Serial No.:
Siterwell Electronics warrants each product to be free from defects in material and workmanship.
This obligation is limited to servicing or part returned to the company for that purpose and making good any parts thereof
which shall be within warranty period, returned to the company under a written intimation and which to the company’s
satisfaction to be found defective. The company reserves the right to decide the workplace for the repair work. The freight
for defective material will have to be borne by the purchaser, and the transit risk for such material will rest with the
purchaser.
This warranty will last for a period of 12 months from the date of Invoice of the product from the factory. The
warranty is applicable only if the product is used within its specifications. The warranty for the replaced components will
lapse along with that of the main product.
Authorized Signatory
61
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Packing list
Please check whether the contents of the package are consistent with the following list.
62
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30
Manufacturer: Siterwell Electronics CO., Limited
Address: No.666 Qingfeng Road, Jiangbei District, Ningbo, Zhejiang Province, China
TEL: 0086-574-87729581
FAX: 0086-574-87729581
E-MAIL: [email protected]
201801VA
63
Document NO.: RD‐690‐39‐001 Version: A Date:2017.12.30