Dometic Service Manual
Dometic Service Manual
Dometic Service Manual
This program will address the most common system problems associated with the Duo-Therm Comfort Control
Center supplied by The Dometic Corporation. Our intent is to provide you with a guideline of checks to make,
DC Volts 4
Fuse 5.15
Reset 1 M
Configuration 2
Wiring 3.3
Configuration 2
Wiring 3.3
B1,B2,B3,
Operation 1
B7,B8,C,D
AC Voltage 3.1
DC Voltage 4
Breaker 3.2
Fuse 5.15
Compressor 5.7
Cold Control
Compressor 5.7
1
Diagnostic Service Manuals
Duo-Therm ®
4. Fan operates: compressor runs for a short while, Short Cycle 6.1
Compressor 5.7
Motor 5.3
Motor 5.3
9. Air distribution box unit: Insufficient cooling, Air Flow Obstruction 6.2
Compressor 5.7
10. Duct in ceiling unit: Insufficient cooling, compressor Air Flow Obstruction 6.2
Compressor 5.7
2
Duo-Therm ®
11. Air distribution box unit: Insufficient cooling with Air Flow Obstruction 6.2
12. Duct in ceiling unit: Insufficient cooling with reduced Air flow Obstruction 6.2
A4,B3,
1. Unit does not run: No fan, no compressor. Configuration 2
B4,B8
Operation 1
C,D
AC Voltage 3.1
DC Voltage 4
Breaker 3.2
Fuse 5.15
Compressor 5.7
PTCR 5.6
Compressor 5.7
Compressor 5.7
3
Duo-Therm ®
Motor 5.3
Motor 5.3
9. Air Distribution Box Unit: Insufficient cooling or Air Flow Obstruction 6.2
Compressor 5.7
10. Duct in ceiling unit: Insufficient cooling or heating, Air Flow Obstruction 6.2
Compressor 5.7
11. Air distribution box unit: Insufficient cooling or Air Flow Obstruction 6.2
12. Duct in ceiling unit: Insufficient cooling or heating Air Flow Obstruction 6.2
4
Duo-Therm ®
Operation 1
AC Voltage 3.1
DC Voltage 4
Breaker 3.2
Fuse 5.15
Compressor 5.7
Compressor 5.7
4. Fan operates; compressor runs for a short time, cycles Short Cycle 6.1
Compressor 5.7
5
Duo-Therm ®
continued)
Motor 5.3
Motor 5.3
Compressor 5.7
9. Insufficient cooling with reduced air output. Air Flow Obstruction 6.2
AC Voltage 3.1
DC Voltage 4
Breaker 3.2
Fuse 5.15
6
Duo-Therm ®
continued)
Compressor 5.7
Compressor 5.7
4. Fan operates; compressor runs for a short while, Short Cycle 6.1
Compressor 5.7
Motor 5.3
Motor 5.3
Compressor 5.7
7
Duo-Therm ®
continued)
9. Insufficient cooling or heating with reduced air output. Air Flow Obstruction 6.2
Operation 1
AC Voltage 3.1
DC Voltage 4
Breaker 3.2
Fuse 5.15
Compressor 5.7
Compressor 5.7
8
Duo-Therm ®
continued)
4. Fan operates; compressor runs for a short while, Short Cycle 6.1
Compressor 5.7
Motor 5.3
Motor 5.3
Compressor 5.7
9. Insufficient cooling with reduced air output. Air Flow Obstruction 6.2
9
Duo-Therm ®
SECTION:
Operation 1
AC Voltage 3.1
DC Voltage 4
Breaker 3.2
Fuse 5.15
Compressor 5.7
Compressor 5.7
Compressor 5.7
Motor 5.3
Motor 5.3
10
Duo-Therm ®
continued)
8. Insufficient cooling or heating; compressor runs con- Air Flow Obstruction 6.2
Compressor 5.7
9. Insufficient cooling or heating with reduced air output. Air Flow Obstruction 6.2
11
Duo-Therm ®
The recreational vehicle manufacturer has equipped the the appliances installed on your vehicle. To select the
vehicle with Duo-Therm's Comfort Control Center ™. The mode of operation, momentarily depress the MODE
Comfort Control Center has been designed for you to push-button. You will need to continue to depress and
easily operate all the air conditioning and gas heating release the button until the desired mode is shown in
appliances found in your vehicle from one location. the LCD readout area on the Comfort Control Center.
In order to familiarize yourself with the operation of the To determine the Comfort Control Center options
Comfort Control Center, the following diagram along with available to you, depress and release the MODE
the accompanying text will explain all the functional char- push-button until it goes through all selections.
Button
a n d MODE push-buttons.
13
Duo-Therm ®
F. ON/OFF SWITCH –The ON/OFF switch is located on 4. After approximately 5 seconds, the selected fan
the lower right hand edge of the Comfort Control speed will come on. TheMODE a n d FAN speed you
Center. Move the lever from side to side to change have selected will remain shown in the LCD area of
usage.
etc. The air conditioner removes this moisture from the (To set cooling temperatures and fan speeds on Duo-
air during normal operation. Keeping doors and win- Therm Air Conditioners & the cooling mode of Duo-
dows closed when this air conditioner is in operation Therm Heat Pumps)
will minimize condensed moisture on cold surfaces. 1. Momentarily depress and release theMODE push-
nel and some states require these people to be 2. Depress and release the FAN push-button to select
A. FAN ONLY MODE OF OPERATION decrease the desired temperature. The final se-
1. Begin by placing the power switch on the lower right lectedSET-POINT will be displayed in the LCD area
hand edge of the Control Center on theON position. of the Comfort Control Center.
To do this, simply move the lever to the right. 4. After a delay of approximately 2 minutes the air
2. Momentarily depress and release theMODE push- conditioner's compressor will come on and the cool-
button until the FAN ONLY indicator on the Liquid ing process will begin. Once the room temperature
Crystal Display (LCD) is illuminated. reaches the selected SET-POINT, the compressor
3. Momentarily depress and release the FAN push- will cycle off. Once the Comfort Control Center
button until the desired fan speed indicator (LOW, senses the need for cooling, the compressor will
MED, HIGH, AUTO) is illuminated. If your vehicle is restart in approximately two minutes. At this point,
equipped with a heat pump or a dual basement air the fan will either:
conditioning system, your selection choice will be a. continue to operate in the single selected fan speed
14
Duo-Therm ®
ditional Special
tures.
15
Duo-Therm ®
(For Duo-Therm air conditioners with an electric heat When AUTO FAN is selected, the fan speed will be
2. The fan will operate inLOW, MED o r AUTO. You will the temperature SET-POINT and the room tem-
crease the temperature or the DN push-button to 4° or below The fan will operate on LOW
POINT will be displayed in the LCD area of the COOL OR HEAT PUMP MODE – If the vehicle is
press the FAN and MODE push-buttons simulta- HEAT STRIP MODE – When HEAT STRIP mode is
neously to select ZONE 2, and repeat procedures selected, the fan will automatically run in the LOW
DELAY
H. POWER INTERRUPTION
I. ZONE CONTROL
16
Duo-Therm ®
designed, you have the freedom of selecting the 2) Momentarily depress the FAN push-button until the
MODE of operation for each zone independently. To desired fan speed indicator is illuminated (LOW,
This completes the setup for the primary stage of the Dual
If the vehicle is equipped with a Duo-Therm Dual 1) Simultaneously depress and release the FAN and
Basement Air Conditioner or a Dual Basement Heat MODE push-buttons until the STAGE indicator on
Pump, you have an air conditioning system that is the LCD is illuminated.`
point and the differential temperature set-point which 4) Momentarily depress the UP o r DN push-button to
activates the secondary stage. After turning on your set the desired differential temperature set-point
set and activate the stage control operation. actual room temperature reaches the differential
17
Duo-Therm ®
°
point is set at 5 F. The secondary stage will activate °
greater than 24 F, a defrost timing cycle will begin. The
when the actual room temperature reaches 77 F ° defrost timing cycle will allow operation of the heat
° °
(72 F + 5 F), and will continue to operate until the pump for 40 minutes. The fan will then be shut off, the
room once again becomes 72 F. ° refrigerant flow reversed and run for 4-1/2 minutes,
°
42 F or until the temperature becomes less than 24 F, °
at which time the furnace will activate. (See AUX.
K. AUX. HEAT
°
temperature is measured to be below 24 F, the control
listed:
next step. If data and light are not present, see Sec.
5.1.
6.
°
allows the heat pump to operate down to 24 F. When
°
the outside ambient temperature is less than 42 F and
18
Duo-Therm ®
damage.
TELEPHONE CABLE
COMMUNICATIONS
LINE
115V AC
COMFORT
CONTROL
12V DC
INPUT
2 WIRES
19
Duo-Therm ®
2. ONE ROOFTOP AIR CONDITIONER PLUS ONE NOTE: If a remote sensor is used, it must be plugged
component damage.
FURNACE
2 WIRES
FURNACE
CIRCUIT
BREAKER BOX
TELEPHONE CABLE
COMMUNICATIONS LINE
115V AC
Typical installation for one
be used.
20
Duo-Therm ®
3. ONE ROOFTOP AIR CONDITIONER WITH HEAT NOTE: If a remote sensor is used, it must be plugged
strip plus one gas furnace, turn heat strip (#1) Dip
FURNACE
2 WIRES
FURNACE
CIRCUIT
BREAKER BOX
TELEPHONE CABLE
COMMUNICATIONS LINE
115V AC
Typical installation for one
21
Duo-Therm ®
4. ONE ROOFTOP HEAT PUMP PLUS ONE GAS NOTE: If a remote sensor is used, it must be plugged
(P5). The ambient sensor is plugged into the proper Improper connections can cause
FURNACE
2 WIRES
FURNACE
CIRCUIT
BREAKER BOX
TELEPHONE CABLE
COMMUNICATIONS LINE
115V AC
Typical installation for one
22
Duo-Therm ®
DUO-THERM
COMFORT CONTROL
BOX
FURNACE
115V AC 2 WIRES
BASEMENT AIR
Typical installation for one
may be used.
12V DC INPUT
2 WIRES
23
Duo-Therm ®
6. ONE BASEMENT HEAT PUMP PLUS ONE GAS NOTE: If a remote sensor is used, it must be plugged
115VAC, 12VDC, two thermostat wires from the Improper connections can cause
DUO-THERM
COMFORT CONTROL
BOX
FURNACE
115V AC 2 WIRES
12V DC INPUT
2 WIRES
24
Duo-Therm ®
DUO-THERM
COMFORT CONTROL
TELEPHONE CABLE
COMMUNICATIONS LINE
CIRCUIT
BREAKER
BOX
115V AC FURNACE
CIRCUIT 2
DUAL
Typical installation for one BASEMENT
25
Duo-Therm ®
8. ONE DUAL BASEMENT HEAT PUMP PLUS ONE properly connected to Circuit 1 AC power module in
one gas furnace, the STAGE Dip switch on AC NOTE: If a remote sensor(s) is used, it must be
power module for Circuit 2 must be turned to ON. All plugged into the P4 (white) connector.
tor (red) on each AC power module. 115VAC (Circuit Improper connections can cause
DUO-THERM
COMFORT CONTROL
TELEPHONE CABLE
COMMUNICATIONS LINE
CIRCUIT
BREAKER
BOX
115V AC FURNACE
CIRCUIT 2
DUAL
26
Duo-Therm ®
unit.
ONE unit.
(front) unit.
component damage.
27
Duo-Therm ®
REAR REMOTE
SENSOR
ZONE 2
FURNACE
115V AC
2 WIRES
REAR AC
CIRCUIT
TELEPHONE CABLE
BREAKER
COMMUNICATIONS LINE
ZONE 1 BOX
FURNACE
TELEPHONE
CABLE COMMUNI-
CATIONS
LINE
115V AC
FRONT REMOTE
FRONT A/C
SENSOR *(OPTIONAL)
unit.
ONE unit.
(front) unit.
28
Duo-Therm ®
ZONE 2 configuration should have Dip switch 1 (heat NOTE: If a remote sensor(s) is used, it must be con-
strip) and 5 (ZONE 2) to ON position. The cold nected into the P4 (white) connector.
component damage.
REAR REMOTE
SENSOR
ZONE 2
FURNACE
115V AC
2 WIRES
REAR AC
CIRCUIT
TELEPHONE CABLE
BREAKER
COMMUNICATIONS LINE
ZONE 1 BOX
FURNACE
TELEPHONE
CABLE COMMUNI-
CATIONS
LINE
115V AC
FRONT REMOTE
FRONT A/C
SENSOR *(OPTIONAL)
29
Duo-Therm ®
3. ONE ROOFTOP AIR CONDITIONER PLUS ONE ZONE 2 (Air Conditioner) configuration should have
ROOFTOP HEAT PUMP PLUS ONE GAS Dip switch 5 (ZONE 2) to ON position and all other
To configure one rooftop air conditioner plus one control should be plugged into P5 (blue) connector
rooftop heat pump plus one gas furnace, ZONES and remote sensor plugged into P4 (white) connec-
need to be established. For explanation purposes tor on the AC power module. (Refer to Figure "ZONE
unit.
ONE unit.
(front) unit.
P3 (red) connector on the AC power module. (Refer NOTE: If a remote sensor(s) is used, it must be con-
component damage.
30
Duo-Therm ®
REAR REMOTE
SENSOR
ZONE 2
FURNACE
115V AC
2 WIRES
REAR AC
CIRCUIT
TELEPHONE CABLE
BREAKER
COMMUNICATIONS LINE
ZONE 1 BOX
FURNACE
TELEPHONE
CABLE COMMUNI-
CATIONS
LINE
115V AC
FRONT REMOTE
FRONT A/C
SENSOR *(OPTIONAL)
FURNACE
To configure two rooftop heat pumps plus one gas ZONE 1 configuration should have all Dip switches to
furnace, ZONES need to be established. For expla- OFF position. The cold (freeze) control is NOT used.
nation purposes, the front unit will be ZONE 1 and The P5 (blue) connector must stay open. The ambi-
the rear unit will be ZONE 2. Zones can be arranged ent sensor must be plugged into the P3 (red) con-
per the customer's wishes. nector on the AC power module. (Refer to Figure
"ZONE 1")
EACH unit must have 115VAC. Only one unit re-
unit.
ONE unit.
(front) unit.
31
Duo-Therm ®
REAR REMOTE
SENSOR
ZONE 2
FURNACE
115V AC
2 WIRES
REAR AC
CIRCUIT
TELEPHONE CABLE
BREAKER
COMMUNICATIONS LINE
ZONE 1 BOX
FURNACE
TELEPHONE
CABLE COMMUNI-
CATIONS
LINE
115V AC
FRONT REMOTE
FRONT A/C
SENSOR *(OPTIONAL)
32
Duo-Therm ®
5. TWO BASEMENT AIR CONDITIONERS PLUS ONE ZONE 1 configuration should have all Dip switches to
arranged per the customer's wishes. NOTE: If a remote sensor(s) is used, it must be con-
unit.
Improper connections can cause
ONE unit.
ZONE 2
(front) unit.
ZONE 1
33
Duo-Therm ®
DUO-THERM
REAR A/C
REAR REMOTE
SENSOR
TELEPHONE CABLE
REAR BASEMENT AIR
COMMUNICATIONS LINE
ZONE 2
CIRCUIT
BREAKER
BOX
FURNACE
115V AC FURNACE
COMMUNICATIONS LINE
ZONE 1
may be used.
one furnace.
12V DC INPUT
2 WIRES
EACH unit must have 115VAC. Only one unit re- into P3 (red) connector. (Refer to Figure "ZONE 1",
Another telephone communications line must be position. The ambient sensor should be plugged
between the two units. into P3 (red) connector. The remote sensor should
34
Duo-Therm ®
component damage.
ZONE 1
ZONE 2
DUO-THERM
COMFORT
CONTROL
115V AC
REAR A/C
REAR REMOTE
SENSOR
TELEPHONE CABLE
COMMUNICATIONS LINE
CIRCUIT
REAR BASEMENT AIR
BREAKER
ZONE 2
BOX
FURNACE
115V AC FURNACE
COMMUNICATIONS LINE
ZONE 1
may be used.
12V DC INPUT
Typical installation for two comfort zones
2 WIRES
with two basement heat pumps and one
furnace.
35
Duo-Therm ®
7. TWO ROOFTOP AIR CONDITIONERS PLUS TWO The two (2) furnace thermostat wires from rear
gas furnaces, ZONES need to be established. For ZONE 1 configuration should have all Dip switches to
explanation purposes, the front air conditioner and OFF position and the cold (freeze) control plugged
one furnace will be Zone 1, and the rear air condi- into P5 (blue) connector. (Refer to Figure "ZONE 1")
EACH air conditioner must have 115VAC. Only one position. The cold (freeze) control should be plugged
air conditioner requires 12VDC. Telephone commu- into P5 (blue) connector. The remote sensor (if
nications line must be between the Comfort Control used) must be plugged into P4 (white) connector.
Center and ONE air conditioner only. (Refer to Figure "ZONE 2")
Another telephone communications line must be NOTE: If a remote sensor(s) is used, it must be con-
between the two air conditioners. nected into the P4 (white) connector.
36
Duo-Therm ®
furnaces.
REAR REMOTE
SENSOR
ZONE 2
FURNACE
115V AC
2 WIRES FURNACE
REAR A/C
2 WIRES
BREAKER
COMMUNICATIONS
ZONE 1 BOX
LINE
FURNACE
TELEPHONE CABLE
COMMUNICATIONS
LNE
FURNACE
115V AC
FRONT A/C
FRONT REMOTE
SENSOR *(OPTIONAL)
2 WIRES
37
Duo-Therm ®
8. ONE ROOFTOP HEAT PUMP PLUS ONE ROOF- ZONE 2 (air conditioner) configuration should have Dip
TOP AIR CONDITIONER PLUS TWO GAS FUR- switch 5 (ZONE 2) to ON position and all other Dip
To configure one rooftop heat pump plus one rooftop should be plugged into P5 (blue) connector. The
air conditioner plus two gas furnaces, ZONES need remote sensor (if used) must be plugged into P4
to be established. For explanation purposes, the (white) connector. (Refer to Figure "ZONE 2")
customer's wishes.
furnace.
The two (2) furnace thermostat wires from rear nected into the P4 (white) connector.
switches to OFF position. The cold (freeze) control Improper connections can cause
ZONE 1
38
Duo-Therm ®
SENSOR
with rooftop air conditioner plus heat
ZONE 2
FURNACE
115V AC
2 WIRES FURNACE
REAR A/C
2 WIRES
CIRCUIT
TELEPHONE CABLE
BREAKER COMMUNICATIONS
FURNACE
TELEPHONE CABLE
COMMUNICATIONS
LNE
FURNACE
115V AC
FRONT A/C
FRONT REMOTE
SENSOR *(OPTIONAL)
2 WIRES
To configure three units, ZONES need to be estab- To configure four units, ZONES need to be established.
lished. Refer to Section 2A and 2B for Zone 1 and Zone Refer to Section 2A, 2B and 2C for Zone 1, Zone 2 and
115V AC must be to ZONE 3 unit. A telephone commu- 115V AC must be to ZONE 4 unit. A telephone commu-
nication line must be between ZONE 2 and ZONE 3 nication line must be between ZONE 3 and ZONE 4
units. units.
Configure ZONE 3 unit the same as other like units, Configure ZONE 4 unit the same as other like units,
EXCEPT for the Dip Switches. Dip Switch 4 (ZONE 3) EXCEPT for the Dip Switches. Dip Switch 3 (ZONE 4)
to ON position, and all other Dip Switches to OFF to ON position, and all other Dip Switches to OFF
position. position.
39
Duo-Therm ®
The unit is a 115V AC, 60 Hz. appliance. The proper Place a clamp-on type ammeter around the black wire
operation range is between 103 volts and 126.5 volts. The from the breaker going to the unit. Turn on the unit and
voltage reading should be taken at the unit power supply record amp draw. If the breaker trips before the rated
leads. One test should be performed when the unit is amperage, replace the breaker.
ING.
3.2 BREAKER
40
Duo-Therm ®
HEAT PUMP
YEL
RED
RED
41
Duo-Therm ®
42
Duo-Therm ®
FB1
43
Duo-Therm ®
units.
ROOFTOP UNITS
SECTION 5
COMPONENTS
an outside wall.
from them.
44
Duo-Therm ®
To check the Comfort Control Center, first verify the ON/ NOTE: Be sure polarity is the same on each plug. Ex-
OFF switch is in the ON position. Next, verify DC volts (10 ample: Black on left (viewing plug from top, spring clip
to 30) and polarity are correct (see Sec. 4). Then do a side).
(see Sec. 1), replace it. If the correct function does not
Center.
A. ROOFTOP UNITS
for continuity between the white wire and each of the other
Cut the modular cable to the desired length. When cutting,
wires.
make sure ends are cut straight, not diagonally. Next, use
conductors.
RJ-11 modular plug. Lack of continuity between the white wire and any of the
and that the conductors are flush with the tip of the plug
the RJ-11 modular plug with the cable into the tool's
procedure.
45
Duo-Therm ®
MOTOR Verify there are not AC volts to the unit before doing any
tests.
UNTIL DISCHARGED.
COIL
tor. Next, set the dial-type VOM meter to the highest ohm
CIRCUIT 1 CIRCUIT 2
Lack of continuity between the white wire and any of the Use a dial-type meter ONLY, most digital meters will not
other wires indicates an open circuit and requires that the do a proper test. Turn the unit's circuit breaker OFF. Verify
motor be changed. Next, check for continuity between there is no AC volts to the unit before doing any tests.
leads.
46
Duo-Therm ®
COMPRESSOR
different ways:
! W ARNING
sor replacement.
47
Duo-Therm ®
according to occupants' desires. NOTE: A defective switch can cause a cycle problem with
the unit.
mode, this line will be cool or cold to the touch. In the HEAT
not correct.
proper; and connection is completed through it. Next, 600 & 630 FREEZE CONTROL
verify AC power module board is correct. If AC volts are
D
kd o
m kd
fm
f
continuity).
48
Duo-Therm ®
The relay is used on basement air conditioner Model The ambient sensor is the outside air temperature
39125 and Basement heat pump Model 39335 ONLY. sensor and is used on heat pump units only. This
The relay has five (5) terminals. It is used to complete component allows the heat pump to operate down to
(terminals 1 and 3) is not energized (no power to terminals To check the ambient sensor, first measure outside
1 and 3), continuity should exist between terminals 4 to 5; temperature surround the sensor. This is called "ambi-
and no continuity between terminals 2 to 4. ent". Next, unplug the ambient sensor (red plug) from
RELAY
When the coil (terminals 1 and 3) is energized (power to AtAmbientTemperature You ShouldHave
terminals 1 and 3), continuity should exist between termi- of: OhmsReadingof:
nals 2 to 4 and no continuity between terminals 4 to 5. 55°F 11667
This relay is used to energize the furnace blower any time 60°F 10212
the compressor is energized. This circuit has been added 65°F 8959
to enhance both the cooling and heating operation. 70°F 7876
75°F 6939
NOTE: This circuit will not work with all furnaces. 80°F 6126
Before using this circuit, check with the furnace manufac- 85°F 5418
turer for proper wire connection to the furnace. Other 90°F 4802
components may or may not be required. Read and follow 95°F 4264
the instructions provided with the furnace. 100°F 3793
INSTRUCTIONS FOR FURNACE CONNEC- NOTE: Any ohms reading has a tolerance of plus or
TIONS:
minus ( ±) 10% to be a good component. A very
precise and accurate ohm meter must be used
connector.
49
Duo-Therm ®
Ensure that the compressor is operational by: n Locate the Remote Sensor 54" above the floor.
A. Placing mode switch to cool. Install the Remote Sensor on a partition, not on an
boards.
For the specific temperature surrounding the sensor, the Improper location can cause improper operation of the
location.
50
Duo-Therm ®
necessary.
51
Duo-Therm ®
D. SINGLE BASEMENT HEAT PUMP Using a 115 volt incandescent bulb, check from AC white
To verify circuits are being completed by the AC power (common) of incoming 115V AC; one lead from incandes-
module board, you would first remove the electric box cent bulb and the other lead from incandescent bulb to the
cover and locate the AC power module board. terminals listed below to determine if a particular circuit is
sor circuit.
or the component.
HEAT PUMP
52
Duo-Therm ®
Terminal 1 is black wire and is compressor circuit No continuity requires the fuse be replaced. Continuity
Terminal 2 is white wire and is run circuit to compres- means the fuse is good. Another test can be done
sor. DO NOT TEST. without removing the fuse. Use a DC volt meter to
Terminal 3 is red wire and is start circuit to compressor. check between ground or negative ( –) DC to each side
DO NOT TEST. of fuse. If there is voltage on each side, the fuse is
Terminal 4 is white wire and is 115V common good. If there is voltage on one side only, the fuse is
Terminal 5 is brown wire and is fan capacitor circuit to defective and requires replacement.
start of diagnosis.
When the coil is energized (power to the coil terminals),
NOTE: DO NOT use a volt meter to do these checks as
continuity should exist between COM to NO and no
it will give erroneous readings.
continuity between COM to NC.
5.15 FUSE
gram.
53
Duo-Therm ®
ADDITIONAL FEATURE; to provide a circuit for the Short cycle could be caused by air being circulated
furnace blower motor to enhance both the cooling and directly on the remote sensor. Make sure you do not have
heating operation. a register too close to the remote sensor. Verify the duct
connection at the unit is not leaking into the return air. Seal
THE FOLLOWING FURNACE CONNECTION IN- stalling; a wet filter can cause insufficient cooling or
TO YOUR INSTALLATION.
AIR
FILTER
connector. COVER
SECTION 6
AIR FLOW
Short cycle is caused by cold air being drawn back into the
the compressor.
6.3 AIR DISTRIBUTION SYSTEM
Two possible causes of this condition are the air box and A. ROOFTOP UNITS
the discharge duct. If the air box is not sealed tightly SIZING & DESIGN
against the ceiling, it will allow cold air to cross over into The installer of this air conditioner system must design the
the return air portion of the air box. Also, if the discharge air distribution system for his particular application. Sev-
duct is not installed properly, it can allow cold air to cross eral requirements for this system MUST be met for the air
over into the return portion of the air conditioner. Make conditioner to operate properly. These requirements are
sure you have the correct discharge duct for the thickness as follows:
54
Duo-Therm ®
The total cross-sectional discharge area of outlet ducts Total System Pressure must be between the following:
from the plenum area under the air conditioner must be as 0.55 to 0.90 in. W.C. for 579 Series
follows: 0.40 to 1.10 in. W.C. for 591, 595 & 630
1. 579 & 600 Series 17.5 sq.in. 0.12 to 0.65 in W.C. for 600 Series
Duct Sizing Requirements as Follows: operation on high speed and return air filter and grille in
Duct Length (short run) 1/3 Total Length The Dometic Corporation recommends the basic configu-
Register Requirements as Follows: System. We have found by testing, that this configuration
Distance from End of Elbow 15" — — It is the responsibility of the Installer of this System to
Distance between Registers 24" — — review each RV floor plan and determine the following:
Total Number Required/AC 4 8
A. Duct size
Number required per Run/AC 2 — — B. Duct layout
Free Area per Register 14 sq. in. — —
C. Register size
D. Register locations
The duct material must meet or exceed any agency or
E. Thermostat location.
RVIA Standard that may be in existence at the time the RV
These items must be determined in conjunction with the
is produced.
Air Distribution System Sizing and Design Requirements
listed.
THIS SYSTEM TO ENSURE THE DUCTWORK WILL EVER, THESE ALTERNATE CONFIGURATIONS
NOT COLLAPSE OR BEN DURING OR AFTER THE AND METHODS MUST BE APPROVED BY THE
THE DOMETIC CORPORATION WILL NOT BE HELD be run from the furnace to the Dometic A/C. Read all of
LIABLE FOR ROOF STRUCTURAL OR CEILING the following instructions before beginning the in-
SEALED DUCTWORK.
surface.
55
Duo-Therm ®
ROOF AND CEILING OPENING PREPARATION d. Wiring must comply with all National, State and
1) A 14" x 14" opening must be cut through the roof and Local Wiring Codes.
ceiling of the RV. This opening must be located e. Use a steel sleeve and a grommet or equivalent
between the roof and reinforcing members. methods to protect the wire where it passes into the
opening.
2) Mark a 14" x 14" square on the roof and carefully cut c. In a multiple zone installation, this wiring is
4) The opening created must be framed to provide ad- connector end must be routed to the roof opening of
equate support and prevent air from being drawn from the system which it will control. Make sure that at least
the roof cavity. Lumber 3/4" or more in thickness must 15" of the sensor cable extends into the roof opening.
power supplies, furnace wiring, 4-conductor telephone 9) If a furnace is to be controlled by the system, the two
cable, remote sensing and load shed options as furnace thermostat leads must be routed to the roof
desired. opening of the air conditioner that will control it. Make
5) The 14" opening is part of the return air system of the sure at least 15" of the furnace thermostat wires
Air Conditioner and must be finished in accordance extend into the roof opening.
6) Route a copper 12 AWG, with ground, 115 VAC supply 10) If an Energy Management System- EMS (load shed)
line from the fuse or circuit breaker box to the roof is to be used with the control, two wires must be routed
a. This supply line must be located in the front portion signal required for this function is a normally open
of the 14" opening. relay contact. When the EMS calls for the compressor
b. The power supply MUST be on a separate Time to shut off, the relay contacts should close. Make sure
Delay Fuse or HACR Circuit Breaker. that at least 15" of the EMS wires extend into the roof
TOTAL OUTLET
21.0 sq. in. - 591, 595 & 630 & 595 Series
REGISTERS
VEHICLE
ROOF RAFTERS FRONT
56
Duo-Therm ®
extends into the roof opening and 6" extend from the
Center ™.
that at least 15" of the wire extends into each of the roof
57
Duo-Therm ®
MODELS 39335 AND 39125 B e s u r e NOT to block the inlet or discharge air, or service
square inches) for supply air and a 15" x 22" opening (330
INDOOR SECTION
square inches) for discharge air. Use the cross flow
CLEARANCES
method for good air circulation.
The minimum clearances to the evaporator are zero
PERFORM AS DESIGNED.
type of restrictive opening, the FREE AREA of the opening INLET AIR
must be at least 260 square inches. The evaporator section must have free access to room air.
FREE AREA — is the opening that remains in a grill or opening is required. Where the return air must be provided
louvered panel after the restrictions are taken away. For through louvers or mesh screen, the FREE AREA per-
example, an opening of 10 x 20 inches has 200 square centage of the material used shall be taken into consider-
inches. When this opening is covered with a grill that is 56 ation when making this determination. An example of how
percent open, the FREE AREA is (200 x .56), 112 square to determine FREE AREA is included under "2. OUT-
NOTE: The return air grill must have the same square
EXAMPLE OF HOW TO DETERMINE FREE
1/2
AREA OR % OPEN AREA:
2 surface as the coil face (15"H x 17"L).
1/2 TOTAL AREA = 8 X 8 = 64
8
For each air conditioning system, there must be a
2
1/2
FREE AREA = 2 X 2 X 9 openings
return grill to bring cabin air back into the unit. There
= 36
2 must also be at least four discharge grills per unit.
36
1/2 % OPEN AREA = = 56%
64 Each return air grille must be filtered and accessible for
cleaning or replacement.
square inches of FREE AREA is available to the face of The central air conditioning unit is designed to use a
the condenser. discharge air duct with a static pressure of .10 to .25
MOUNTING
All air handling ducts must be properly insulated to pre-
Vibration eliminators are supplied to prevent the transmit-
vent condensation forming on their surface during opera-
tance of vibration into the living area.
tion. A vapor barrier must also be supplied on the outer
58
Duo-Therm ®
RISER X 2
heat exchanger, unless furnace is so equipped to utilize
DUCT (MIN.)
90 SQ. IN.
FILTERED
(MIN. X 2)
DISCHARGE
2" X 10" CLOSEABLE
CONDENSER
GRILL (MIN. X 4))
AIR
FLOOR CUTOUT
SUPPLY AIR
INSULATED
FLOORING
RETURN SYSTEM
REQUIRED OPENING
C. BASEMENT UNITS
CONDENSER SECTION:
SUPPLY AIR
air supply.
59
Duo-Therm ®
tion.
8
EXAMPLE OF HOW TO DETERMINE FREE
1/2
EVAPORATION SECTION
AREA OR % OPEN AREA:
2
8 2
INLET AIR
FREE AREA = 2 X 2 X 9 openings
1/2
The evaporation section must have free access to room
= 36
2
air. A minimum of 128 square inches of FREE AREA
36
1/2 % OPEN AREA = = 56%
opening is required. Where the return air must be provided
64
NOTE: Service access must always be supplied either as centage of the material used shall be taken into consider-
clearance or as a defined access panel. ation when making this determination. An example of how
SECTION".
RETURN SYSTEM
INSULATED DUCT
Return to be 6 ft. minimum from floor.
Minimum return required per duct sizing for unit to (3 " depth Min.)
RETURN AIR
& outlets
return.
breaker
REQ. SIZE MIN. QTY.
4 X 6 4
4 X 8 4
Condenser inlet air 2 places.
ADDITIONAL REQUIREMENTS: 4 X 10 4
Damper required in furnace.
4 X 12 4 Condenser air outlet ( X2 in bottom)
Vibration isolators should be used
Must be isolated from condenser inlet air.
at each mounting point.
Control operation.
60
Duo-Therm ®
GRILLS
7.3 TUBING VIBRATION
NOTE: The return air grill must have the same square
If any of the copper tubing is rubbing against itself or any
surface as the return air duct.
other part, verify that the proper tubing has been installed.
tor. If this is not possible, make sure there is nothing 7.4 CONDENSER OR BLOWER FAN
blocking the air flow from the grill to the evaporator.
The blower motor will have either a squirrel-cage or blade-
essary.
OUTLET AIR
SEALED SYSTEM
All air handling ducts must be properly insulated to pre-
8.1 RECHARGING
vent condensation forming on their surface during opera-
NOTE: The Clean Air Act of 1990 set guidelines in
tion. A vapor barrier must also be supplied on the outer
regard to recapturing or disposition of refrigerants.
surface of the insulation to prevent moisture from travel-
Check with local authorities for proper handling or
ing through the insulation and condensing on the cold
evacuation of refrigerants.
ductwork.
tube.
61
Duo-Therm ®
Slowly drain the R-22 refrigerant by using recapturing or pound gauges to the charging port on the low side
recycling equipment. Do not leave the clamp-on saddle pressure tubing. Next, connect the red colored high
valve on the unit as it will cause leaks. pressure line of the compound gauges to the charging
and cut the tube near the end. Do this on both the low and
CHARGE
CYLINDER
high side processing tubes.
SERVICE
GAUGES
REFRIGERATION
PRESSURE GAUGES
BLUE
HOSE
RED
HOSE
YELLOW
HOSE
ELECTRONIC
LEAK DETECTOR
SUCTION LINE
YELLOW
SERVICE HOSE
GAUGES VACUUM
Next weld the process tube in place. We recommend PUMP
using a brazing material which melts between 950° and
BLUE HOSE
62
Duo-Therm ®
Open the pressure relief valve on the vacuum pump. This Allow the refrigerant charge to equalize by waiting 10
allows the major contaminants from the sealed system to minutes before starting the system. After 10 minutes, do
escape into the atmosphere rather than enter the oil in the a cooling performance test to determine whether the
set should be opened and the vacuum pump turned on. Now the blue low side and the red high side lines should
ness. If the low side gauge does not change, there is a leak
low and high side valves on the compound gauge set and your ambient temperature. Find that temperature on the
turn off the vacuum pump. chart on Page 27. The pressure listed to the right of the
pressures.
SERVICE Low side restriction will cause lower than normal amp
sures.
other side.
63
Duo-Therm ®
A restriction would cause a temperature drop at the point Replace any parts that are found to be bad. Whenever a
of the restriction. A buildup of frost or sweat could be component is replaced in the sealed system, or the
evident if operated long enough. system has been opened to the atmosphere, a good,
64
Duo-Therm ®
SECTION 1
OPERATION.............. .......................................................................... 1 3
SECTION 2
CONFIGURATION................ ................................................................ 1 9
SECTION 3
AC VOLTAGE REQUIREMENTS
SECTION 4
SECTION 5
COMPONENTS
SECTION 6
AIR FLOW
SECTION 7
OTHER
SECTION 8
SEALED SYSTEM
65
!"
! #$% & '
( & '