G16B 42A UKver2 VacuumDeaerator

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

CUSTOMER INFORMATION

VACUUM DEAERATOR
SERIES VA 1B – VA 11B

• SUITABLE FOR DISTRICT


HEATING PLANTS

• DEAERATION WITHOUT STEAM-


HEATING

• EFFICIENT AND STABLE


VACUUM PUMP

• PRODUCED IN GALVANIZED
AND STAINLESS STEEL

G16B-42A/E2
APPLICATION
A vacuum deaerator is used for treatment of circulating water
in heating plants. The circulating water should not contain
oxygen as this increases the risk of corrosion on the system.
The oxygen is dissolved in the make-up water and thereby
enters the tank together with the make-up water, which
normally contains 8-10 mg/l oxygen. The oxygen content can
be reduced to under 0.2 mg/l with a vacuum deaerator.

THEORY OF OPERATION
The oxygen-containing make-up water, preheated to 40-90 °C,
is led to the upper section of the deaeration tank. In order to
optimize the removal of oxygen, the deaeration tank is
equipped with fillers for division of the water into fine
particles. The vacuum pump creates the necessary vacuum so
that the make-up water boils. When the water boils, the oxygen
is liberated and removed by means of the vacuum pump. The
deaerated water is separated into two streams, which are
pumped partly into the district heating network, partly recycled
over the deaeration tank.

PLANT ARRANGEMENT
A vacuum deaerator consists of three main components: A
vacuum deaerator, a vacuum pump unit and a pump unit.

DEAERATION TANK
The deaeration tank is delivered in galvanized or stainless steel.
Inside the tank is equipped with an intermediate bottom, under
which a reservoir for deaerated water is mounted. Fillers are
installed on top of the intermediate bottom. The plant is
provided with switches for level control and is delivered with
bracket for wall-mounting.

VACUUM PUMP UNIT


The vacuum pump unit consists of a vacuum pump (liquid ring
pump) as well as a valve arrangement for setting of cooling
water quantity and vacuum force. The vacuum pump is
delivered on bracket for wall-mounting.

PUMP UNIT
The pump unit consists of a centrifugal pump and of a pipe
system with valves for setting of the make-up water quantity
and the circulating quantity. The pipe system can be delivered
in galvanized or stainless steel, and the pump in stainless steel

SPECIFICATIONS
MODULE FLOW RATE SPACE REQUIREMENTS
max. m³/h Height, m Width, m Length, m
VA 1B 2 5.5 0.8 2.5
VA 3B 6 5.6 1.0 2.7
VA 5B 10 5.6 1.1 2.9
VA 7B 14 5.6 1.2 3.1
VA 9B 18 5.6 1.3 3.3
VA 11B 22 5.7 1.4 3.4