Ifx4N: User Manual
Ifx4N: User Manual
Ifx4N: User Manual
IFX4N
USER MANUAL
INDEX
1 GENERAL CHARACTERISTICS..................................................................................1
2 FRONT PANEL KEYS ..................................................................................................4
3 FRONT PANEL LED SIGNALINGS..............................................................................5
4 PROGRAMMING AND TEST .......................................................................................6
4.1 How to program the protection relay......................................................................6
4.2 How to modify a visualized parameter...................................................................7
4.3 Reset .....................................................................................................................7
4.4 Test of output relays ..............................................................................................8
5 DISPLAY AND PROGRAMMING .................................................................................9
5.1 Standard display....................................................................................................9
5.2 Visualization structure .........................................................................................10
5.3 Address and Time (fig. 1) ....................................................................................13
5.4 Protection function selection (fig. 1).....................................................................14
5.5 Nominal values set-up (fig. 2) ..............................................................................14
5.6 Thresholds and time delays set-up (fig. 2)...........................................................16
5.7 Output relays programming (fig. 2) ......................................................................18
5.8 Digital inputs function programming (fig. 2) .........................................................19
5.9 Parameter values visualization (fig. 3).................................................................20
5.10 Events (fig. 3) ......................................................................................................21
5.11 TRIPS COUNTERS.............................................................................................23
6 INSTALLATION ..........................................................................................................25
6.1 Supplied kit ..........................................................................................................25
6.2 Cabling ................................................................................................................26
6.3 Relays R3 and R4 - Signaling / Command set-up ...............................................29
6.4 RS485 serial communication port........................................................................29
7 TIME DEPENDENT CURVES ....................................................................................30
8 TECHNICAL CHARACTERISTICS.............................................................................31
9 TABLES......................................................................................................................32
1 GENERAL CHARACTERISTICS
The protection relay IFX4N performs functions such as overcurrent and earth fault relay;
the user can select one of the functions listed in the table below.
All the set-up and measured parameters can be visualized on the front panel display and
transmitted on the RS485 communication serial port.
Related to each threshold, partial and total counters of TRIP conditions are available.
TRIP DELAYS - a programmable time delay (TI) is available for each threshold; it can be
programmed as definite time or dependent time in compliance with IEC 255-4 standard.
For each threshold programmed as definite time, an additional programmable time delay
(TA) is available; the additional time delay is added to time delay TI. The additional time
delay activation is controlled by the digital inputs to allow the use of the IFX4N relay with
cooperating protection relays.
OUTPUT RELAYS - the IFX4N controls 4 output relays (named R1, R2, R3 and R4);
these relays can be programmed to be activated on START or TRIP conditions of one or
more thresholds.
The quiescent state of each single relay R1, R2, R3 and R4 can be programmed as
normally energized (ON) or normally de-energized (OFF).
1
SEB Divisione Elettronica e Sistemi GENERAL CHARACTERISTICS
DIGITAL INPUTS - there are available 3 digital inputs to activate the following functions
(when enabled by the programmed set-up):
For each digital input can be programmed the condition that activates the related
functions:
HI voltage = > 20 V dc / ac
LO voltage = 0 ÷ 10 V dc / ac
The digital input acquisition is valid when the voltage value stays in the range HI or LO for
at least 40 ms.
DISPLAY OF MEASURES - the user can select the continuous display of a measured
current (primary values); all the current measures can be transmitted to an external
controller through the RS485 port.
EVENTS - information related to the last 8 events (TRIP or STATUS) are recorded in the
EEPROM memory.
Information includes the threshold set-up and activated relays (TRIP event only), the
measured currents, the digital input status, date and time of the event.
SELF-DIAGNOSIS - the software includes a non stop monitoring module that controls the
functionality of all hardware and software resources of the protection relay.
The fault condition signaling stays until faults are pointed out by the monitoring module;
during this condition the protection functions are suspended to avoid unsuitable tripping.
STATUS FUNCTION - when the STATUS function is activated by one of the digital input
(when programmed) the protection relay memorizes information related to measured
currents and digital input status (see par. 5.10 - EVENTS). The recorded information
allows an analysis of trip causes in co-operative protection relays systems.
2
SEB Divisione Elettronica e Sistemi GENERAL CHARACTERISTICS
PILOT WIRE FAULT MONITORING - when the function is programmed, the digital input
DIG2 is used to control the correct functionality of the pilot wire. Digital input DIG2 is
always expected to be complementary of DIG1 input (HI-LO or LO-HI) to identify faults on
pilot wire.
The fault condition is reported as detected by the self-diagnosis module but the protection
functions are not suspended; only the functions related to DIG1 digital input are
suspended as the DIG1 status cannot be longer considered as true.
The fault condition is reported when DIG1 and DIG2 signals are not complementary for
more then 100 ms.
All the set-up and measured parameters can be transmitted on the RS485 communication
serial port; when communication is active (LED REMOTE glows), the operator on front
panel can view the relay set-up but changes of parameters are disabled (ENTER and
buttons disabled).
3
SEB Divisione Elettronica e Sistemi FRONT PANEL KEYS
right arrow
down arrow
VISUALIZATION OF PARAMETERS
• all visualizations are circular and they can be displayed using the two arrow push-
buttons.
• the structure of the visualizations and their contents are showed in Figures 1, 2, and
3.
• when the sealable transparent front panel is installed only the arrow push-buttons
and the RESET push-button are accessible to prevent unauthorized modification of
the protection set-up.
MODIFICATION OF PARAMETERS
• remove the transparent sealable front panel to access ENTER and push-
buttons.
4
SEB Divisione Elettronica e Sistemi FRONT PANEL LED SIGNALINGS
The last trip condition (threshold indication) is also showed on front panel display; more
information on trip condition are presented in the recorded EVENT (see par. 5.10).
5
SEB Divisione Elettronica e Sistemi PROGRAMMING AND TEST
All parameters can be freely modified; the proper protection set- up as required by the
plant management is submitted to the operator's judgment.
1) SELECT the visualization (on display) of the parameter to be modified using the
arrow push-buttons
3) END the parameter modification session depressing again the [ENTER] push-
button
4) REPEAT the procedure from 1) to 3) for all the parameters required to obtain the
new protection relay set-up
5) CONFIRM the new protection relay set-up at the visualization CONFIRM PROG?
(Fig. 2, ref. H1) within 5 minutes depressing the push-buttons buttons [ENTER],
up to visualize YES and [ENTER] again to confirm.
NOTE: The protection relay continues to operate using the previous set-up until the new
set-up is confirmed as at point 5) above; the visualization of the modified parameters
before the new set-up confirmation is only temporary to allow an easy definition of the new
protection set-up.
If the new set-up is not confirmed within 5 minutes from the last pressed push-button, the
protection relay visualizes again the previous set-up (the parameters set-up that the
protection relay is still using).
6
SEB Divisione Elettronica e Sistemi PROGRAMMING AND TEST
If one or more parameters are modifiable, on the first of them will appear a blinking cursor.
NOTE: if a numerical parameter is selected out of the accepted range (as shown in Table
A) when the push-button [ENTER] is pressed for few seconds an error message will be
displayed as:
Data
Error
and the parameter will be displayed again with the former value.
4.3 Reset
When the push-button [RESET] is pressed, the protection relays returns to the standard
condition:
7
SEB Divisione Elettronica e Sistemi PROGRAMMING AND TEST
TEST R1
OFF
2) PRESS [ENTER] to activate the test session; the message OFF will start to blink.
TEST R1
ON
4) PRESS [ENTER] to command the instantaneous trip of the output relay (change of
the current status).
8
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
NORMAL FUCTIONING
During this state the following information can be visualized (as defined by set-up):
Protection function (ANSI code) - the display shows the ANSI codes of the selected
functions (ref. C1 - FUNCTION SELECTION).
Measured current - the display shows one of the measured currents; the current to be
visualized is selected by operator (ref. D4).
The current is visualized as primary value; if the selection of the current to be visualized
refers to a current not measured (depending on FUCTION SELECTION) no values are
presented.
ON TRIP CONDITION
When a trip condition occurs the protection relay visualizes the TRIP message that
includes the threshold related to the trip; the displayed messages are as the following:
The information of the trip, as well the glowing of the related LEDs, is displayed until the
[RESET] push-button is pressed.
If a new trip condition occurs, the displayed information will be updated; information related
to previous trips are recorded in EVENTS memory.
FAULT CONDITION
When a permanent or temporary fault condition is detected by the self-diagnosis module,
the following message is displayed:
FAIL
eeeeeeee
F.PILOT Detected fault condition on pilot wire; the function related to DIG1 digital
input is suspended
Corrective action - verify pilot wire (short or open circuit)
9
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
B1 B2 B3 B4 B5 B6 B7
IFX4N PROTOCOL BAUDRATE NR RELAY SER. NR. VERS SW dd/mm/yy
mod nn yyyyyyyy nnnn xxx zzzzzzzz zz.zz hh:mm:ss
C1
FUNCTION 2 PHASE, 3 PHASE, 2 PH+Io, 3PH+Io
aaaaaaaa EARTH, STATOR95, CASE TR
H1
CONFIRM
PROG?..
Figure 1
10
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
From FIGURE 1 D1 D2 D3 D4 D5
SET-UP NOMINAL In = x A In prim Ion prim DISPLAY CONTRAST
VALUES Ion= j A ccccc A ccccc A eeeeeeee LEV n
E1 E2 E3 E4 E5
THRESHOL I> ccc I> TI eeeee TA I> TA I>
SET-UP nn.nn xxxxxx A xx.xx s zz.zz s eeeeeeee
F1 F2 F3 F4 F5 F6 F7
RELAYS R1 R1 I> R1 I>> R1 I>>> R1 Io> R1 Io>> R1 Io>>>
FUNCTION NORM ccc xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx
F8
R2 TEST R1
NORM ccc yyyyyyyy
R3
NORM ccc
R4
NORM ccc
G1 G2 G3
DIGITAL DIG1 cc DIG2 cc DIG3 cc
INPUT xxxxxxxx xxxxxxxx xxxxxxxx
H1
CONFIRM
PROG?..
To FIGURE 3
Figure 2
11
From FIGURE 2 L1 L2 L3 L4 L5 L6
MEASURES SIGNALS THRESHOL I> I>> I>>> Io> Io>> Io>>>
& EVENTS STATUS STATUS status status status status status status
M1 M2
RELAYS R1 ccc R3 ccc
STATUS R2 ccc R4 ccc
N1 N2
DIGITAL DIG1 ww DIG3 ww
STATUS DIG2 ww
P1 P2 P3 P4
MEASURES I1=xx.xx I2=xx.xx I3=xx.xx Io=xx.xx
SEB Divisione Elettronica e Sistemi
Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9 Q10
EVENTS E1 E1 aaaa E1 RELAY E1 T-Tot E1 DIG E1 I1 E1 I2 E1 I3 E1 Io E1
aaaaaaaa xx.xx In i,j,k ww.ww s eeeeeeee nn.nn In nn.nn In nn.nn In nn.nnIon DIG1 vv
12
E8
aaaaaaaa
R1 R2 R3 R4 R5 R6 R7 R8 R9 R10
COUNTERS I> I> I>> I>> I>>> I>>> Io> Io> Io>> Io>>
P eeee T eeee P eeee T eeee P eeee T eeee P eeee T eeee P eeee T eeee
Figure 3
DISPLAY AND PROGRAMMING
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
When the MODBUS protocol is selected the following display is showed to allow the
selection of the transmission speed:
B3
BAUDRATE
xxxx
When the STANDARD protocol is selected the baud rate is automatically selected by the
protection relay.
B4 - ADDRESS (programmable)
NR RELAY
001
The number is used on RS485 port to address a specific relay when two or more
protection relays are linked on the same serial line.
13
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
B7 - TIME/DATE (programmable)
dd/mm/yy
hh:mm:ss
Time and date are programmable and they are used to mark recorded events.
NOTE: the clock is not provided with back-up battery, therefore a loss of auxiliary supply
will force time/date to the following condition:
01/01/90
00:00:00
Examples:
FUNCTION FUNCTION FUNCTION
2 PHASE 3 PH+Io EARTH FT
14
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
Primary phase current value of the installed phase CTs; the value is programmable from
0001 to 18500 A.
Primary current value of the installed earth CT; the value is programmable from 0001 to
18500 A.
It allows to select the standard displayed information (ref. A1) when no trip condition
occurs and no fault condition have been detected by the self-diagnosis module; the
available selections are the following:
The list of the selectable currents depends on the programmed FUNCTION SELECTION
(ref. C1); the current is displayed in primary values (the value depends on D2 and D3 set-
ups).
Selection examples:
15
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
The information and set-ups related to threshold I> in the following points (references
E1÷E5) are effective for all the thresholds I>>, I>>>, Io>, Io>>, Io>>> just taking into
consideration the change of the threshold identification (with limits as presented in table
A).
Examples:
I> ON I>>> OFF Io>> ON
01.50 12.00 05.00
The programmed threshold (ref. E1) is shown in terms of primary current; the value
depends on the programmed CTs primary values (ref. D2 and D3 – paragraph 5.5).
Set-up of time-delay to the activation (TRIP) of the programmed output relays when the
measured current exceeds the threshold level.
For I> and Io> thresholds, the time delay can be selected between one of the following:
16
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
For the remaining thresholds the TI parameter is fixed as INDIP (independent time).
Parameter xx.xx:
Time independent - time delay (seconds) to activate the programmed output relays: the
output relay trips when the measured current exceeds the threshold level for at least xx.xx
seconds.
TA I>
xx.xx s
The additional time delay TA is programmable from 00.00 to 99.99 seconds; please note
that at least one of the digital inputs should be programmed to activate time delay function
(ref. G1, G2, G3 – paragraph 5.8).
The additional time delay TA is added to the time delay TI to obtain the output relay trip
when the TI+TA time expires.
The additional time delay TA will be added if the time delay TI is programmed at least
equals to 50 ms (digital input acquisition time - 40 ms)
It shows the digital input programmed to activate the additional time delay TA on the
displayed threshold.
17
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
In the programming session are displayed only the thresholds available depending on
FUNCTION SELECTION set-up (ref. C1 – paragraph 5.4).
Equivalent information and set-up related to relay R1 is available for the relays R2, R3 and
R4 just changing the relay identification.
Programming of the R1 relay status when no START or TRIP conditions are activated
(none of the measured currents exceed their thresholds).
TRIP output relay R1 activation when one of the measured phase currents
exceeds the programmed threshold level I> for at least TI or TI+TA
seconds
18
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
When the function of more than one digital input refers to a threshold, the priority will be
the following:
Parameter cc: programming of the condition that activates the function related to digital
input DIG1; the condition is selectable between HI and LO.
Parameter xxxxxxx: programming of the function related to digital input DIG1; the
following functions are selectable:
19
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
Programming of the function related to digital input channel 2 (DIG2); the selections
available are the same as presented for DIG1 (ref. G1) plus the following:
Programming of the function related to digital input channel 3 (DIG3); the selections
available are the same as presented for DIG1 (ref. G1).
For each threshold are displayed the threshold identification (I>, I>> etc.) and the
threshold status; the status can show one of the following values:
ON active threshold
OFF disabled threshold (programmed OFF at ref. E1, par. 5.6)
OFF_DIG threshold programmed active but momentary disabled by a digital
input actual status.
Examples:
20
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
Note that ON/OFF do not necessary mean energized or de-energized (see ref. F1).
P1 - P2 - P3 - P4 - MEASUREMENT DISPLAY
The actual value of the measured currents is displayed; only the measured currents
(depending on FUNCTION SELECTION - ref. C1, paragraph 5.4) are displayed.
The 8 events are recorded and identified with a progressive number from 1 to 8; the more
recent event shows a lower number.
Q1 - EVENT NUMBER
E1
cccccccc
The parameter cccccccc gives information on the kind of event and it can show one of the
following values:
21
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
For the events NONE and POWER ON no other information is presented: for the other
events the following displays give more detailed information on the event.
Q2 - TRIP THRESHOLD
E1 I>
xx.xx In
It shows the threshold related to the TRIP condition of the protection relay and the value of
the threshold (in relative terms). The information is not shown on STATUS or POWER ON
events.
It shows the list of the output relay activated by the threshold trip.
Examples:
E1 RELAY E3 RELAY
1,3,4 1,4
When no output relays have been activated (no relays programmed to TRIP on the
threshold) the following message will be displayed:
E1 RELAY
NONE
It is shown the total delay to the TRIP of the output relays from the overcurrent detection;
when additional delays are activated, the change of the status of the digital input that
controls the additional delay during the delay itself could bring to a total time different from
the sum of the programmed delays. If the total time is greater than 999 seconds the
display of tenths is omitted.
When the event is memorized on external command (STATUS), the message N/A (Not
Applicable) is shown instead of the number of seconds.
E1 T-Tot
N/A
22
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
The list of the digital inputs related to the memorized event is displayed (STATUS function
command or additional time TA enabled - ref. E4 par. 5.6).
The values of the measured currents at the event are displayed; the values are expressed
as In and Ion terms.
There are presented only the currents measured coherently with the selection on
FUNCTION SELECTION set-up (ref. C1 – paragraph 5.4).
The total counters, the number of confirmed programming sessions and the date and time
of the last confirmed programming session are not modifiable or resettable; the information
related to the last programming session are used to control unauthorized access.
The partial counter can be modified following the standard set-up procedure for
parameters as described at paragraph 4.2; the partial counters are immediately modified in
the memory (the recorded values are immediately resetted without the need of the
programming confirmation).
23
SEB Divisione Elettronica e Sistemi DISPLAY AND PROGRAMMING
Display of the partial (P) and total (T) counters of the TRIP condition related to each
threshold.
When the value exceed 9999 the counter starts again from 0000.
The counters are identified by the threshold name (I>, Io>, etc.); there are presented only
the counters related to the active thresholds coherently with the selection on FUNCTION
SELECTION set-up (ref. C1 – paragraph 5.4).
The partial counters are modifiable in the range from 0000 to 9999 following the standard
set-up procedure (paragraph 4.2).
Display of the number of confirmed programming sessions (from the factory set-up) and
the date and time of the last confirmed programming session.
24
SEB Divisione Elettronica e Sistemi INSTALLATION
6 INSTALLATION
6.1 Supplied kit
RK VERSION - 19" rack installation (the proper rack is supplied by SEB)
1 2 3 6
Sacchetto BLISTER
The knobs to fix the transparent front panel must be screwed through the panel the front
panel itself; the operation will create a screw thread in the plastic material and the knobs
will never be missed.
25
SEB Divisione Elettronica e Sistemi INSTALLATION
6.2 Cabling
Current circuits
It is suggested to terminate the current wirings using eyelet terminals.
With reference to the insertion diagram in the next page, the currents measured by the
protection relay have the following matching:
I1 terminals A1 - A2
I2 terminals B1 - B2
I3 terminals C1 - C2
Io terminals D1 - D2
For the functions as earth fault overcurrent , stator earth fault 95% (64S) and transformer
case earth fault (64T) only the current Io is measured.
Io terminals D1 - D2
The terminal D1-D2 must to be connected to a CT sensible to earth currents (64S - on star
connection of the generator, 64T on the earth connection of the transformer case).
26
SEB Divisione Elettronica e Sistemi INSTALLATION
Insertion
27
SEB Divisione Elettronica e Sistemi INSTALLATION
28
SEB Divisione Elettronica e Sistemi INSTALLATION
31
32
33
34
35
24
25
26
27
28
29
R3 R4
When the STANDARD Seb communication protocol is selected, the transmission speed is
automatically selected between 300 to 9600 bauds and the protocol is ASCII-HEX; the
documentation related to the protocol is freely available on request.
When the MODBUS communication protocol is selected, the transmission speed can be
programmed between 300 to 9600 bauds (ref. B3, par. 5.3).
Line H
120 Ohm
Line L
120 Ohm
CONTROLLORE
20
21
22
23
20
21
22
23
20
21
22
23
I / Ithresh I / Ithresh
Ki ∗ K
t= α
+ 0.02s
I
−1
Ithresh
I / Ithresh
30
SEB Divisione Elettronica e Sistemi TECHNICAL CHARACTERISTICS
8 TECHNICAL CHARACTERISTICS
Measuring inputs
Rated phase current (In) 1 A / 5 A programmable
Rated earth current (Ion) 1Ao5A
Thermal withstand continuously 4 In / Ion
Thermal withstand for 1 s 100 In / Ion
Rated frequency 50 / 60 Hz
Primary CT’s current 1 ÷ 18500 A
Digital inputs
Number of inputs 3
External control voltage as Uaux
Typical current (sink) 2 mA
Data transmission
Standard RS485 half duplex
Communication protocol MOD-BUS ASCII
Transmission speed 300 - 9600 baud selectable
Optional fibre optic module
Auxiliary supply
24 ÷ 320 Vdc ± 20%
Range
48 ÷ 230 Vac ± 20%
Frequency (Vac) 47 ÷ 63 Hz
Burdens (min/max) 5 / 10 W
Environmental conditions
Operation -10 / +60 °C
Transport and storage -25 / +80 °C
Relative humidity (without condensation) < 95%
Protection degree for flush mounting IP 52
(optional) (IP 54)
Weight 2.5 kg
31
SEB Divisione Elettronica e Sistemi TABLES
9 TABLES
Table A Thresholds and time delays
Characteristic
curves (IEC-255) A, B, C -- A, B, C --
Characteristic
constant 0.01 ÷ 20.00 s -- 0.01 ÷ 20.00 s --
Resolution 0.01 s 0.01 s
Additional delay 0.00 ÷ 99.99 s 0.00 ÷ 99.99 s 0.00 ÷ 99.99 s 0.00 ÷ 99.99 s
OTHER VALUES
Burden referred to
0.3 VA / phase 0.3 VA / phase
rated value
Drop-off ratio ≥ 0.95
Overshoot time ≤ 30 ms
Output relays Programmable for each threshold
R1, R2, R3, R4 START / TRIP and normally ON / OFF
1
Minimum threshold value 0.005 Ion is available starting with firmware version 2.32; with firmware version
until 2.31, minimum threshold value was 0.01 Ion
2
Resolution 0.005 Ion is available starting with firmware version 2.31; with firmware version until 2.30,
resolution was 0.01 Ion
32