3500 - 22m Tdi Module
3500 - 22m Tdi Module
Product Datasheet
Bently Nevada* Asset Condition Monitoring
Description
The 3500/22M Transient Data Interface (TDI) is the interface
between the 3500 monitoring system and compatible
software (System 1* Condition Monitoring and Diagnostic
software and 3500 System Configuration software). The TDI
combines the function of a 3500/20 Rack Interface Module
(RIM) with the data collection capability of a communication
processor such as TDXnet.
Page 1 of 9
Specifications same function as “Rack Reset” contact
on I/O module
Inputs Address Used to set the rack address: 127
switch possible addresses
Power
Used to place 3500 rack in either “RUN”
Consumption 10.5 Watts mode or “PROGRAM” mode. RUN mode
Data allows for normal operation of the rack
and locks out configuration changes.
Front Panel USB-B PROGRAM mode allows for normal
10Base-T/ 100Base- 10Base-T or 100Base-TX operation of the rack and also allows for
TX I/O Ethernet, autosensing local or remote rack configuration. The
Configuration key can be removed from the rack in
100Base-FX I/O 100Base-FX Fiber-Optic Ethernet
Keylock either position, allowing the switch to
remain in either the RUN or PROGRAM
Outputs position. Locking the switch in the RUN
position allows you to restrict
Front Panel LEDs unauthorized rack reconfiguration.
Indicates when the 3500/22M is Locking the switch in PROGRAM
OK LED
operating properly position allows remote reconfiguration of
Indicates when the 3500/22M is a rack at any time.
TX/RX LED communicating with the other modules in
the rack
Indicates when the 3500 rack is in Trip
TM LED
Multiply mode
CONFIG OK Indicates that the 3500 rack has a valid
LED configuration
I/O Module OK Relay
Indicates when the 3500 rack is
operating normally or when a fault has
been detected within the rack. User can
Function select either an “OPEN” or “CLOSED”
contact to annunciate a NOT OK
condition. This relay always operates as
“Normally Energized”.
Standard OK Relay is rated to 5A @ 24
Vdc/120 Vac, 120 Watts/600 VA
Ratings Switched Power (maximum)
Controls
Front Panel
Rack reset Clears latched alarms and Timed OK
button Channel Defeat in the rack. Performs
Page 2 of 9
I/O Module System Contacts Startup/Coastdown Data
l Supports multiple events per revolution speed o 256 samples/rev for 8 revolutions
o 128 samples/rev for 16 revolutions
inputs up to 20 kHz
o 64 samples/rev for 32 revolutions
Page 3 of 9
o 32 samples/rev for 64 revolutions RJ-45 (telephone jack style) for
o 16 samples/rev for 128 revolutions
Connection 10Base-T/100Base-TX Ethernet
l Asynchronous data sampled to support an 800-line
cabling
spectrum at the following frequency spans:
o 10 Hz Cable Length 100 metres (328 feet) maximum
o 20 Hz
100 Base-FX Ethernet I/O
o 50 Hz
o 100 Hz Ethernet, 100Base-FX Fiber Optic, full
o 200 Hz Communications duplex multimode. Conforms to
o 500 Hz IEEE802.3u
o 1000 Hz
o 2000 Hz
Protocol BN Host Protocol and BN TDI Protocol
o 5000 Hz
Supported using Ethernet TCP/IP
o 10 kHz MT-RJ Male Fiber Optic connector for
o 20 kHz
Connection
100 Base-FX cabling
o 30 kHz
2000 metres (6560 feet) maximum,
l Asynchronous data is anti-alias filtered Cable Length
l Channel Pairs for providing Orbit or synchronous full multimode fiber optic cable
spectrum presentations can be split among multiple The 3500/22M has a MT-RJ Male connector on the unit for
monitors. For asynchronous full spectrums the Fiber Optic 100 Base-FX cabling therefore you MUST use a
channels must be within a monitor channel pair (30 MT-RJ Female connector on the fiber optic cable to ensure
kHz frequency span data will not be phase proper connectivity.
correlated between channel pairs)
Environmental Limits
Communications
TDI Module, 10Base-T/ 100Base-TX I/O, and
Protocols 100Base-FX I/O
Communication with 3500 Operating
-30 °C to +65 °C (-22 °F to +149 °F)
BN Host Configuration Software, 3500 Data Temperature
Protocol Acquisition Software, and 3500 Display
Storage
Software -40 °C to +85 °C (-40 °F to +185 °F)
Temperature
Communication with System 1*
Humidity 95%, non-condensing
BN TDI Protocol Condition Monitoring and Diagnostic
Software Battery Life
Front Panel Powered TDI 38 years @ 50 °C (122 °F)
Communications USB-B Unpowered TDI 12 years @ 50 °C (122 °F)
Protocol
BN Host Protocol
Supported
115.2 kbaud maximum
Baud Rate
(auto-baud capable)
USB Cable Length: 5 meters (16.4 ft)
Cable Length maximum. A 3 meter (9.8 ft) cable is
included with the 3500 rack
Connector USB-B
10Base-T / 100Base-TX Ethernet I/O
Ethernet, 10Base-T and 100Base TX.
Communications
Conforms to IEEE802.3
Protocol BN Host Protocol and BN TDI Protocol
Supported using Ethernet TCP/IP
Page 4 of 9
Compliance and Certifications
Note: This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This
Physical
device may not cause harmful interference, and (2) This
device must accept any interference received, including
TDI Module
interference that may cause undesired operation. Dimensions
241.3 mm x 24.4 mm x 241.8 mm (9.50
(Height x Width
EMC in x 0.96 in x 9.52 in)
x Depth)
EN 61000-6-2 Immunity for Industrial Weight 0.91 kg (2.0 lbs)
Environments
Standards I/O Modules
EN 61000-6-4 Emissions for Industrial Dimensions
Environments 241.3 mm x 24.4 mm x 99.1 mm (9.50
(Height x Width
in x 0.96 in x 3.90 in)
European x Depth)
Community EMC Directive 2014/30/EU Weight 0.20 kg (0.44 lbs)
Directives
Rack Space Requirements
Electrical Safety
TDI Module 1 full-height front slot
Standards EN 61010-1
I/O Modules 1 full-height rear slot
European
Community LV Directive 2014/35/EU
Directives
Class I, Zone 2
AEx nC IIC T4 Gc
Class I, Division 2
Groups A, B, C and D
T4 @ Ta = -20 °C ≤ Ta ≤ +65 °C
(-4 °F ≤ Ta ≤ +149 °F)
per drawing 149243
ATEX/IECEx (Approval Option -02
II 3 G
Ex nA nC ic IIC T4 Gc
Page 5 of 9
are channels that collect waveform data due
Ordering Information either to a software command or to an alarm
For the detailed listing of country and product specific event, and therefore support current values,
approvals, refer to the Approvals Quick Reference Guide, scheduled waveform capture, and alarm data
document 108M1756, at www.GEmeasurement.com. capture. Transient points provide all the function
of a Steady-State point with the additional
Product Options and Part Numbers
capability of waveform collection due to
3500/22M TDI Module and I/O parameter variations such as machine speed.
Page 6 of 9
Fiber Optic Cable termination, 6-position, green
Spares
CAUTION
288055-01
Upgrade advisory.
Standard Transient Data Interface If the RIM I/O is left in the rack
Module with USB cable when installing a new TDI, it will
damage the TDI.
100M2833
Please perform the upgrade in this
10 foot A to B USB cable order:
1)Remove RIM
146031-01 2)Remove RIM I/O
3) Insert TDI I/O
10Base-T/100Base-TX I/O Module 4) Insert TDI.
146031-02
Network Requirements
100Base-FX (Fiber Optic) I/O Module
For complete information on network
161580-01 requirements, refer to the 3500 Hardening Guide
[106M9733]. This document can be requested at
3500/22M TDI Operation and bntechsupport.com.
Maintenance Manual
164466-01
Network Accessories Datasheet
00580441
Connector header, internal
termination, 3-position, green
00580436
Connector header, internal
Page 7 of 9
Graphs and Figures
1: Main Module
2: 10 Base-T/100 Base TX (copper) Ethernet I/O Module
3: 100 Base-FX (fiber optic) Ethernet I/O Module
4: LEDs indicate operating status of the module
5: Hardware Switches
6: USB Configuration Port for configuring or retrieving machinery data
7: OK Relay indicates the OK status of the overall rack
8: Signal Common external grounding terminal
9: RJ-45 Ethernet Port for configuration and data collection
10: System Contacts
11: Fiber Optic Ethernet Port for configuration and data collection
Page 8 of 9
Copyright 2002 - 2018 Baker Hughes, a GE company, LLC ("BHGE") All rights reserved.
* Denotes a trademark of Bently Nevada, LLC, a wholly owned subsidiary of Baker Hughes, a GE
company.
All product and company names are trademarks of their respective holders.
Use of the trademarks does not imply any affiliation with or endorsement by the respective holders.
The information contained in this document is subject to change without prior notice.
1631 Bently Parkway South, Minden, Nevada USA 89423
Phone: 1-775.782.3611 www.GEmeasurement.com
Page 9 of 9