Understanding Requirements For Generators
Understanding Requirements For Generators
for Generators
How to apply the requirements of Article 445 in generator installations.
Article 445 contains the electrical installation and other requirements for
generators, including such things as where generators can be installed,
nameplate markings, conductor ampacity, and disconnecting means.
Generators are basically motors that operate in reverse, producing
electricity when rotated, instead of rotating when supplied with electricity.
Article 430, which covers motors, is the longest article in the NEC. Article
445, which covers generators, is one of the shortest. At first, this might not
seem to make sense. But you don’t need to size and protect conductors to a
generator. You do need to size and protect them to a motor.
Related: Top Nine Reasons Generators Fail to Start
Fig. 1. What size conductor is required from a 100A overcurrent protection device on a 20kW, 120/240V single-phase
generator to a 200A service rated transfer switch if the terminals are rated for 75°C conductor sizing?
ADVERTISING
Generators need overload protection, and it’s necessary to properly size the
conductors that come from the generator. But these considerations are
much more straightforward than the equivalent considerations for motors.
Overcurrent protection
The overcurrent protection requirements are not the same for all types of
generators. The NEC recognizes these five types:
The authority having jurisdiction (AHJ) must deem that a generator is vital
to the operation of an electrical system, and the generator should operate to
failure (rather than be protected) to prevent a greater hazard to persons.
Conductor ampacity
When sizing the conductors from the load side of the generator overcurrent
protection device to the transfer switch, size them per Sec. 240.4.
Generators that aren’t a separately derived system [Art. 100] must have the
neutral conductor sized to carry the maximum unbalanced current as
determined by Sec. 220.61, serve as part of the effective ground-fault
current path, and not be smaller than required by Sec. 250.30 (Fig. 2).
Live parts
For generators that operate at more than 50VAC or 60VDC to ground, live
parts shall not be exposed to accidental contact where accessible to
unqualified persons [Sec. 445.14]. One way (among others) to meet this
rule is to locate the generator in a locked room with key card access. That
way, only qualified persons can get near the generator. That not only
protects unqualified persons from your generator, but it also protects your
generator system from unqualified persons.
You should also evaluate the system to determine if guards are necessary
for the protection of attendants. If so, the requirements of Sec. 430.233
apply [445.15]. Basically, suitable insulating mats or platforms shall be
provided so that the attendant can’t readily touch live parts unless standing
on the mat(s) or platform(s).
Bushings
If you have an engine generator set, just assume oil will be present. Use
bushings that are of suitable material, such as polyurethane.
Fig. 3. The disconnecting means requirements for generators are outlined in Sec. 445.18(A).
Disconnecting means and shutdown of the prime mover
Generators must have provisions to shut down the prime mover; shutdown
must comply with all the following [445.18(B)]:
The provisions to shut down the prime mover can satisfy the requirements
of Sec. 445.18(A) where the shutdown is capable of being locked in the open
position per Sec. 110.25.
Generators with greater than a 15kW rating must be provided with an
additional shutdown means located outside the equipment room or
generator and comply with Sec. 445.18(B)(1) and (B)(2).
One objective of Art. 445 is to correctly select the overprotection for the
application. Remember: There are five types of application. Another
objective is to correctly size the conductors that contain the overcurrent
protection; their ampacity can’t be less than 115% of the nameplate current.
A good installation goes beyond those and other Art. 445 requirements. For
example, all wiring is properly labeled, routed, and secured. Additionally,
terminations are properly torqued and labeled. These aren’t just nice
touches; they’re the hallmarks of a job done right