CALCULATION FOR FIRE EXTINGUISHER

A - RATING UNIT OF FIRE


FLOOR FLOOR AREA (M2) REQUIRED TOTAL FIRE RATING (27)A EXTINGUISHER
GROUND
FLOOR 2825.76 0.065 183.67 6.8 7
FIRST
FLOOR 2825.76 0.065 183.67 6.8 7

CALCULATION FOR WATER STORAGE CAPACITY FOR HOSE REEL

WATER STORAGE
FLOOR HOSE REEL REQUIRED (LITRE)
GROUND FLOOR NO. 1 2275
NO. 2 1137.5
FIRST FLOOR NO. 3 1137.5
NO.4 1137.5

TOTAL OF WATER 5687.5


STORAGE
REQUIRED (LITRE)

CALCULATION FOR ZONING FIRE ALARM CONTROL PANEL

ZONING
FLOOR AREA (M2) ZONING AREA NUMBER OF ZONE
REQUIRED

GROUND 1659.72 200 6.44 9


FLOOR

FIRST 1659.72 200 6.44 9


FLOOR
SECOND 1071.593 200 6.44 6
FLOOR
CALCULATION FOR HEAT DETECTOR AT THE GROUND FLOOR

DETECTION RANGE
LENGTH WIDTH AREA HEIGHT OF
ROOM HEAT DETECTOR TOTAL UNIT
(M) (M) (M2) (M) (M2)

HR
DEPARTMENT 2.848 3.3052 9.41 5 100 0.0941 0

CALCULATION FOR SMOKE DETECTOR AT THE GROUND FLOOR

DETECTION RANGE
LENGTH WIDTH AREA HEIGHT OF
ROOM HEAT DETECTOR TOTAL UNIT
(M) (M) (M2) (M) (M2)
ACCOUNT
DEPARMENT 3.9624 3.0486 12.08 5 100 0.1208 1
PANTRY 2.7432 2.5432 7 5 100 0.07 0
LIFT LOBBY 6.21539 9.5104 59.11 5 100 0.5911 1
TOILET MALE 2.4524 2.77 6.79 5 100 0.0679 0

TOILET FEMALE
2.4524 2.117 5.19 5 100 0.0519 0
LOGISTIC 3.6576 2.5432 9.3 5 100 0.093 0
DEPARMENT
GENERAL
OFFICE 1 2.117 2.4224 5.13 5 100 0.0513 0
GENERAL 2.77 2.97 8.23 5 100 0.0823 0
OFFICE 2
PANTRY 2.7432 2.5432 7 5 100 0.07 0
STORE 2.484 4.0672 10.103 5 100 0.101 1
RISER 3.1528 2.4532 8.02 5 100 0.0802 0
SERVER ROOM
3.0486 3.9624 12.08 5 100 0.1208 1
CORRIDOR 6.0974 17.573 107.1 5 100 1.071 1
LOBBY 5.3092 3.4576 18.4 5 100 0.184 1
CALCULATION FOR SMOKE DETECTOR AT THE FIRST FLOOR

DETECTION RANGE
LENGTH WIDTH AREA HEIGHT
ROOM OF HEAT DETECTOR TOTAL UNIT
(M) (M) (M2) (M) (M2)

SURAU MALE 2.477 4.0672 10.1 5 100 0.101 1


SURAU FEMALE 2.5432 2.5432 6.47 5 100 0.0647 0
RISER 3.1528 2.4532 8.02 5 100 0.0802 0
TOILET MALE 2.4524 2.77 6.79 5 100 0.0679 0
TOILET FEMALE 2.4524 2.117 5.19 5 100 0.0519 0

CALCULATION FOR HEAT DETECTOR AT THE FIRST FLOOR

DETECTION RANGE
LENGTH WIDTH AREA HEIGHT
ROOM OF HEAT DETECTOR TOTAL UNIT
(M) (M) (M2) (M) (M2)
MANAGER ROOM 2.848 3.3052 9.41 5 100 0.0941 0
EXEXUTIVE ROOM 3.6576 2.5432 9.3 5 100 0.093 0
MEETING AREA 4.9524 8.5478 42.33 5 100 0.4233 1
LIFT LOBBY 6.21539 9.5104 59.11 5 100 0.5911 1
CORRIDOR 6.0974 17.5728 107.1 5 100 1.071 1
ACCOUNT
DEPARMENT
3.9624 3.0486 12.08 5 100 0.1208 1
CALCULATION FOR SMOKE DETECTOR AT THE FIRST FLOOR

DETECTIO
LENGTH WIDTH AREA HEIGHT NOFRANGE
ROOM HEAT TOTAL UNIT
(M) (M) (M2) (M) DETECTO
R (M2)

CORRIDOR 1 2.891 10.075 29.13 4 100 0.2913 1


CORRIDOR 2 30.45 4.126 125.64 4 100 1.2564 2
CORRIDOR 3 11.916 14.275 170.1 4 100 1.701 2
HOUSE 10 10 100 4 100 1 1

CALCULATION FOR HEAT DETECTOR AT THE FIRST FLOOR

DETECTIO
LENGTH WIDTH AREA HEIGHT NOFRANGE
ROOM HEAT TOTAL UNIT
(M) (M) (M2) (M) DETECTO
R (M2)

HOUSE 10 10 100 4 50 2 2