A Platform For For Valodation of FACTS Models
A Platform For For Valodation of FACTS Models
1, JANUARY 2006
III. DETAILED ELECTROMAGNETIC TRANSIENT SIMULATION IV. SMALL SIGNAL STABILITY MODEL
MODEL OF UPFC
A. Generator Model
Because the electromagnetic transient simulation model In the small signal model, the generators with their exciters
represents the system in extreme detail, it provides a means for are represented by the typical fourth-order dynamic model
validating the small signal and other reduced models for the (third-order generator plus a first-order exciter)
network. For this purpose, the system in Fig. 1 is represented
in full, with detailed models for the synchronous machines (1)
(including full representation of sub-transient effects), exciters.
The lines can be represented with distributed parameters or as (2)
486 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 1, JANUARY 2006
(3)
(4)
(5)
The voltage and current relationship for the UPFC are given by
(6) (10)
where
(9)
(14)
where we have the following.
The state-space representation of the complete power system
1) , and are the reference control settings of the can be obtained in the standard format of (15) and (16) by elim-
UPFC, namely, the in-phase injected voltage, quadrature inating and from the differential-algebraic equations
injected voltage, and shunt current, respectively. of the dynamic devices (5), (6) and (11)–(13) and the network
2) , and are the in-phase injected voltage, equations (14).
quadrature injected voltage, and quadrature shunt cur-
rent, respectively.
3) , and are the time constants used to model (15)
the PWM time delay associated with , and . (16)
JIANG et al.: PLATFORM FOR VALIDATION OF FACTS MODELS 487
TABLE I
MODES OF OSCILLATION
TABLE II
PARTICIPATION FACTORS
Fig. 8. Dominant mode of G2 from Prony analysis. Fig. 10. Dominant mode of G4 from Prony analysis.
Fig. 9. Dominant mode of G3 from Prony analysis. Fig. 11. Comparison of sending end real power of small signal model versus
emtp-type model.
ipation factors suggest that this mode is the 1.12-Hz mode. The
TABLE III
mode shape diagrams also suggest similar conclusions. It is evi- PRONY ANALYSIS OF PSCAD WAVEFORMS
dent from these diagrams that the rotor angle of Generator 3 os-
cillates when the 0.75-Hz mode is excited (Fig. 5) and when the
1.12-Hz mode is excited (Fig. 7). On the other hand, Fig. 6 indi-
cates that there is negligible influence on Generator 3 when the
0.85-Hz mode is excited. As the UPFC in line 7–8 primarily af-
fects the power in Generator 3, this suggests that the damping of
the 1.12-Hz mode and/or the 0.75-Hz mode could be improved
with its installation. A more quantitative evaluation of the effec-
tiveness of controllers is presented in Section VI. The frequency
information obtained from the eigen-analysys is verified against equations. The close agreement validates the Small Signal Anal-
the simulation results from a detailed electromagnetic transient ysis model.
simulation model in Section V-B. The electromagnetic simulation can also be used to verify
the modal frequencies, damping and participation factor infor-
B. Validation Using Electromagnetic Transients Simulation mation. Prony Analysis was performed in order to validate the
An electromagnetic transient simulation of the power system small signal model. Results of Prony analysis on the waveforms
with a switching level detailed model of the UPFC was per- from emtp-type simulation of the speed of three machines
formed using PSCAD/EMTDC. The disturbance applied was a , and the sending end power of the transmission
1% increase of the reference setting of the quadrature injected line on which the UPFC is located (line 7–8) are tabulated in
voltage of the UPFC for a period of 100 ms. Figs. 8–11 show Table III. The following observations can be made by com-
the simulated waveforms for the speeds of gener- paring this information with the eigenvalues given in Tables I
ators 2–4 and the sending end power, respectively. Superposed and II, which were obtained from the small signal model.
on the emtp-type simulations are the waveforms obtained from 1) Although the 1.12-Hz mode is presented in all four wave-
time-domain simulation of the linearized Small Signal Analysis forms (Prony analysis estimates in the range 1.11 Hz to
JIANG et al.: PLATFORM FOR VALIDATION OF FACTS MODELS 489
TABLE IV TABLE V
CONTROLLABILITY INDEX EIGENVALUE SENSITIVITY TO FEEDBACK GAIN
VI. DESIGN OF DAMPING CONTROLLER (real power of UPFC sending end) are considered as feedback
The question arises as to whether the UPFC placed in line candidates. The effectiveness of each of these signals is evalu-
7–8 for transmission congestion relief can also be modulated to ated by calculating the eigenvalue sensitivity to feedback gain
damp system oscillations. Ideally one would like to increase the [6]. These sensitivities are given in Table V. As the objective
damping of the poorly damped 0.85- and 1.12-Hz modes. Con- is to move the real part of eigenvalue in order to improve the
trollability analysis performed on the small signal model can de- damping, the sensitivity index with the largest real part identi-
termine if such modes can be damped at all, after which linear fies the most effective feedback signal, which is . However,
control design theory can be used to select the optimal feedback in a practical controller, it is usually desirable to choose a
controller. There are three reference control settings available local signal, hence the second best signal is selected. The
in the UPFC for damping control. These are , and . larger sensitivity of the real part of the eigenvalue with than
The effectiveness of using these inputs can be evaluated by cal- with implies that is the better choice for the controller
culating the controllability indices of the modes [4]. These in- input. Once the feedback structure (i.e., feedback and input) is
dices are easily obtained once the eigenvalues and eigenvectors identified, the gain of the feedback controller can be selected.
of the small signal system are evaluated. The controllability in- Using a feedback gain of 0.3 produces a new set of eigenvalues
dices are given in Table IV. The relatively large magnitude of for the system, with the three poorly damped ones shown in
the indices for the 1.12-Hz mode using inputs and indi- Table VI. Note the slight change in the frequency from 1.12
cate the suitability of using these inputs to improve the damping to 1.10 Hz and the improved damping of this mode from 3.30
of that mode. Very small indices for the 0.85-Hz mode indicate (as in Table I) to 4.35. Time domain simulation of the small
that this mode is not controllable using any of the control inputs signal model with and without feedback as in Fig. 12 shows
of the UPFC. These findings are consistent with the mode shape this additional damping.
based arguments made in Section V-A. Once again, as shown in Fig. 13, detailed emtp-type simu-
Based on the above analysis, an output feedback damping lation produces nearly identical responses to those obtained in
controller is designed to improve the damping of the 1.12-Hz Fig. 12 for the small signal model. Using Prony Analysis on the
mode by modulating either the or input. The feedback detailed simulation waveforms the frequencies and damping are
signal is generated by multiplying the selected output marked determined, as in Table VII. The damping as observed from the
for feedback with a simple proportional gain. The outputs most prominent signal for this mode is improved from 3.74
(real power of generator G1, G2, G3), and to 4.92, which compares well with the theoretical value of 4.35.
490 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 1, JANUARY 2006
TABLE IX
CONFIGURATION OF TRANSMISSION LINE
Fig. 13. Damping effect on the sending end real power. emtp-type model.
TABLE VII
PRONY ANALYSIS OF PSCAD WAVEFORMS: WITH FEEDBACK CONTROL
TABLE XI [4] P. Kundur, Power System Stability and Control. New York: McGraw-
TRANSFORMER DATA (SYSTEM BASE: 100 MVA) Hill, 1994.
[5] S. Limyingcharoen, “Application of Unified Power Flow Controllers in
Power System Stability Enhancement,” Ph.D. dissertation, Dept. Elect.
Electron. Eng., Univ. Auckland, Auckland, New Zealand, Mar. 1999.
[6] F. L. Pagola, I. J. Perez-Arriaga, and G. C. Verghese, “On sensitivities,
residues, and participations: Applications to oscillatory stability analsis
and control,” IEEE Trans. Power Systems, vol. 4, pp. 278–285, 1989.
[7] Transmission Line Reference Book (345 kV and Above), Second ed.
Palo Alto, CA: Elect. Power Res. Inst., 1987, p. 39.
TABLE XII
GENERATOR AND EXCITER DATA
Shan Jiang (S’04) received the B.Sc. and M.Sc. (Eng.) degrees in electrical
engineering from Chongqing University, Chongqing, China, in 1989 and 1993,
respectively. He is currently pursuing the Ph.D. degree with the University of
Manitoba, Winnipeg, MB, Canada.
His research interests are FACTs and power system control.
TABLE XIII
UPFC DATA U. D. Annakkage (M’95–SM’04) received the B.Sc. (Eng.) degree in electrical
engineering from the University of Moratuwa, Moratuwa, Sri Lanka in 1982
and the M.Sc. and Ph.D. degrees from the University of Manchester Institute
of Science and Technology (UMIST), Manchester, U.K., in 1984 and 1987, re-
spectively.
He is presently a Professor with the University of Manitoba, Winipeg, MB,
line geometries for an equivalent- representation, corrected for Canada. His research interests include power system stability and control, secu-
rity assessment and control, operation of restructured power systems, and power
long-line effects (see also Tables XI–XIII). system simulation.
REFERENCES
[1] L. Gyugyi, “Unified power-flow control concept for flexible ac transmis-
sion systems,” in Proc. Inst. Elect. Eng., vol. 139, 1992, pp. 323–331. A. M. Gole (M’82–SM’04) received the B.Tech. degree in electrical engineering
[2] L. Y. Dong, L. Zhang, and M. L. Crow, “A new control strategy for the from the Indian Institute of Technology, Bombay, India, in 1978 and the Ph.D.
unified controller,” in Proc. IEEE PES Winter Meet., vol. 1, Jan. 2002, degree from the University of Manitoba, Winnipeg,MB, Canada, in 1982.
pp. 562–566. He currently holds the NSERC Industrial Research Chair in Power System
[3] I. Papic, P. Zunko, D. Povh, and M. Weinhold, “Basic control of uni- Simulation at the University of Manitoba. His research interests include tran-
fied power flow controller,” IEEE Trans. Power Syst., vol. 12, no. 4, pp. sients simulation and power electronics applications in transmission.
1734–1739, Nov. 1997. Prof. Gole is a Professional Engineer in the Province of Manitoba.