0% found this document useful (0 votes)
622 views55 pages

Electrical Load Schedule

This document provides details of the connected electrical loads and maximum demand for a proposed commercial and residential building project in Dubai. It summarizes the key electrical details including the main incomer rating of 2500 amps, total connected load of 1314.14 kW, and maximum demand load of 1051.31 kW taking 80% diversity into account. Circuit breaker ratings and cable sizes are specified for the main LV panel and various sub-distribution boards supplying different areas of the building.

Uploaded by

Lucky Malihan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
622 views55 pages

Electrical Load Schedule

This document provides details of the connected electrical loads and maximum demand for a proposed commercial and residential building project in Dubai. It summarizes the key electrical details including the main incomer rating of 2500 amps, total connected load of 1314.14 kW, and maximum demand load of 1051.31 kW taking 80% diversity into account. Circuit breaker ratings and cable sizes are specified for the main LV panel and various sub-distribution boards supplying different areas of the building.

Uploaded by

Lucky Malihan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 55

PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX.

DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI PLANNED COMPLETION DATE: 2016
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
MAIN SUMMARY CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: LV ROOM - GROUND

CIRCUIT FEEDER RATING - AMPS Fault Duty PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
DB NO. kA 1C, R-PH kW Y-PH B-PH TOTAL 1-PH (1) 3-PH (2) 3-PH (3) CT (4)
mm2 kW kW kW
F/S MCCB SWA/ PVC 2/4X1C
ISO ACB mm2
SP TP MCB REMARKS
INCOMER BY DEWA

OUTGOING
LV PANEL 4P 2500 SET AT 0.8 65 XLPE BY DEWA 2x1Cx150 438.63 431.00 422.52 1314.14 90 1 2400/5A CT

NOTE(S): 1 ALL TRANSFORMERS SHALL HAVE LV INTEGRAL METERING AT LV SIDE


2 ALL TENANT METERS ARE DEWA SUBMETERS TO THE MAIN LV INTEGRAL METER

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 438.6 431.0 422.5 1314.1 90 1

MAX. DEMAND LOAD (3 PH) 1051.31 kW TOTAL CONNECTED LOAD (3 PH) 1314.14 kW

CT-METER LOAD (3PH) ……………kW


Type of Meter (Rating of Incomer): (1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A
(1 Phase) (3 Phase)
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: LV PANEL CLIENT: SARHANK KADER
PLOT NO. JVC14VMRA002
FED FROM: TRANSFORMER CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: LV ROOM - GROUND

CIRCUIT FEEDER DB RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering REMARKS
NO. 1C,
R-PH Y-PH B-PH TOTAL KW DEMAND MAXIMAM 1-PH (1) 3-PH (2) CT (4)
mm2
kW kW kW FACTOR DEMAND
F/S MCCB SWA/ PVC 2/4X1C 2/3/4C mm2
LOAD Kw
mm2
SP TP ISO ACB MCB
INCOMER-1 4P 2500 SET AT 0.8 65 XLPE BY DEWA 1 2400/5A CT METER

2x1Cx150 438.63 431.00 422.52 1314.14


INCOMER-2 4P 2500 SET AT 0.8 65 XLPE MOB. GEN. PROVISION E&M
INTERLOCKED
OUTGOING

SMDB-LL X 500 50 XLPE 2x4Cx150 2Cx70 71.20 75.73 74.43 221.37 0.80 177.10

ESMDB-LL X 200 50 FIRE RATED 4Cx95 1Cx50 32.97 31.39 31.19 95.55 0.80 76.44 WITH ATS TO GEN

SMDB-RETAIL X 80 50 XLPE 4Cx35 1Cx16 11.80 11.80 11.80 35.40 0.80 28.32 3

SMDB-GF X 125 50 XLPE 4Cx50 1Cx25 19.42 16.66 16.71 52.79 0.80 42.23 5

SMDB-1F X 350 50 XLPE 4Cx240 1Cx120 55.81 55.07 52.40 163.28 0.80 130.62 17

SMDB-2F X 350 50 XLPE 4Cx240 1Cx120 55.81 55.07 52.40 163.28 0.80 130.62 17

SMDB-3F X 350 50 XLPE 4Cx240 1Cx120 55.81 55.07 52.40 163.28 0.80 130.62 17

SMDB-4F X 350 50 XLPE 4Cx240 1Cx120 51.11 48.25 49.56 148.93 0.80 119.14 16

SMDB-5F X 350 50 XLPE 4Cx240 1Cx120 53.69 51.95 51.62 157.26 0.80 125.81 15

DB-SS X 32 50 XLPE 2Cx10 1Cx10 1.00 1.00 0.80 0.80

FIRE PUMP X 250 50 FIRE RATED 4Cx150 1Cx70 30.00 30.00 30.00 112.00 0.80 89.60 ELS+ALARM IN CP

CAPACITOR BANK X 1000 50 XLPE 3x4Cx240 3x1Cx120 400KVAR-


MULTISTEP

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 438.63 431.00 422.52 1314.14 90 1
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 1051.31 kW TOTAL CONNECTED LOAD (3 PH) 1314.14 kW

CT-METER LOAD (3PH) ……………kW


Type of Meter (Rating of Incomer): (1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A
(1 Ph ) (3 Ph )
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF:
SMDB-LL CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV ROOM

CIRCUIT FEEDER DB RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
NO. 1C,
R-PH Y-PH B-PH TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)
mm² kW kW kW
F/S MCCB SWA/ PVC 2/4X1C 2/3/4C mm²
ISO ACB mm²
SP TP MCB REMARKS

INCOMER X 500 (N/A) XLPE 2x4Cx150 2Cx70 32.97 31.39 31.19 95.55 0
OUTGOING
ESMDB-MECH@BF X 80 25 XLPE 4Cx25 1Cx16 8.30 8.30 8.30 24.90

EDB-LL1@B1 X 32 25 XLPE 4Cx10 1Cx10 3.53 1.55 1.60 6.68

ESMDB-MTR X 32 25 XLPE 4Cx10 1Cx10 3.00 3.00 3.00 9.00

CENTRAL BATTERY X 32 25 XLPE 4Cx10 1Cx10 1.50 1.50 1.50 4.50

EDB-LL2@GF X 32 25 XLPE 4Cx10 1Cx10 1.90 2.30 1.50 5.70

DB-LL3@1F X 32 25 XLPE 4Cx10 1Cx10 1.14 1.14 1.14 3.42

DB-LL4@4F 32 25 XLPE 4Cx10 1Cx10 1.20 1.20 1.75 4.15

ESMDB-MECH@RF X 80 25 XLPE 4Cx25 1Cx16 12.40 12.40 12.40 37.20

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 32.97 31.39 31.19 95.55 0
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 76.44 kW TOTAL CONNECTED LOAD (3 PH) 95.55 kW

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) U t 60A (2) U t 100A (3) 125 160A (4) LV CT / A
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: ESMDB-MECH@BF CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: BASEMENT FLOOR ELECTRICAL ROOM

CIRCUIT FEEDER DB RATING - AMPS Fault Duty kA PVC XLPE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
NO. 1C,
R-PH Y-PH B-PH TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)
mm² kW kW kW
F/S MCCB SWA/ PVC 2/3/4C mm²
SP TP ISO ACB MCB REMARKS
INCOMER X 63 (N/A) FIRE RATED 4Cx25 1Cx16 8.30 8.30 8.30 24.90 0

OUTGOING
JOCKEY PUMP X 32 25 FIRE RATED 4Cx6 1Cx6 1.00 1.00 1.00 3.00 100mA ELS+ALARM

SUMP PUMP-1 (D) X 32 25 XLPE 4Cx6 1Cx6 0.70 0.70 0.70 2.10 100mA ELS+ALARM

SUMP PUMP-1 (S/BY) X 32 25 XLPE 4Cx6 1Cx6 100mA ELS+ALARM

SUMP PUMP-2 (D) X 32 25 XLPE 4Cx6 1Cx6 0.70 0.70 0.70 2.10 100mA ELS+ALARM

SUMP PUMP-2 (S/BY) X 32 25 XLPE 4Cx6 1Cx6 100mA ELS+ALARM

TRANSFER PUMP (D) X 32 25 XLPE 4Cx6 1Cx6 1.50 1.50 1.50 4.50 100mA ELS+ALARM

TRANSFER PUMP (S/BY) X 32 25 XLPE 4Cx6 1Cx6 100mA ELS+ALARM

EXAF-1 X 32 25 FIRE RATED 4Cx10 1Cx10 2.20 2.20 2.20 6.60 DUAL SPEED STARTER+300mA ELCB

EXAF-2 X 32 25 FIRE RATED 4Cx10 1Cx10 2.20 2.20 2.20 6.60 DUAL SPEED STARTER+300mA ELCB

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 8.30 8.30 8.30 24.90 0
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 19.92 kW TOTAL CONNECTED LOAD (3 PH) 24.90 kW

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) U t 60A (2) U t 100A (3) 125 160A (4) LV CT / A
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
DB REF: SMDB-LL CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV ROOM

CIRCUIT FEEDER RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
DB NO. 1C, R-PH Y-PH B-PH TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)
mm² kW kW kW
F/S MCCB SWA/ PVC 2/4X1C 2/3/4C mm²
ISO ACB mm²
SP TP MCB REMARKS

INCOMER X 500 (N/A) XLPE 2x4Cx150 2Cx70 71.20 75.73 74.43 221.37 0
OUTGOING
DB-LL1@BF X 40 25 XLPE 4Cx16 1Cx16 2.04 3.45 2.15 7.64 BF

DB-LL2@GF X 63 25 XLPE 4Cx25 1Cx16 6.19 6.33 6.25 18.77 GF

DB-LL3@1F X 80 25 XLPE 4Cx35 1Cx16 12.32 11.59 11.92 35.83 1,2 & 3

DB-LL4@4F X 80 25 XLPE 4Cx35 1Cx16 5.08 4.63 4.38 14.09 4,5 & RF

SMDB- X 300 35 XLPE 4Cx185 1Cx95 45.57 49.73 49.73 145.04


MECH@RF

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 71.20 75.73 74.43 221.37 0
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 177.10 kW TOTAL CONNECTED LOAD (3 PH) 221.37 kW

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
( ) ( ) ( ) ( ) C /
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: SMDB-RETAIL
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV ROOM

CIRCUIT FEEDER RATING - AMPS PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
DB NO. 1C,
R-PH Y-PH B-PH TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)
mm² kW kW kW
F/S MCCB SWA/ PVC 2/4X1C 2/3/4C mm²
ISO ACB mm²
SP TP MCB REMARKS
INCOMER X 80 (N/A) XLPE 4Cx35 1Cx16 11.80 11.80 11.80 35.40 3

OUTGOING

DB-RETAIL 01 X 40 XLPE 4Cx16 1Cx16 3.40 3.40 3.40 10.20 1 65m²

DB-RETAIL 02 X 40 XLPE 4Cx16 1Cx16 3.40 3.40 3.40 10.20 1 65m²

DB-RETAIL 03 X 40 XLPE 4Cx16 1Cx16 5.00 5.00 5.00 15.00 1 102m²

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. 11.80 11.80 11.80 35.40 3


SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 28.32 kW TOTAL CONNECTED LOAD (3 PH) 35.40 kW

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) U t 60A (2) U t 100A (3) 125 160A (4) LV CT / A
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: SMDB-GF CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV ROOM

CIRCUIT FEEDER DB RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
NO. 1C,
R-PH Y-PH B-PH TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)
mm² kW kW kW REMARKS
F/S MCCB SWA/ PVC 2/4X1C 2/3/4C mm²
ISO ACB mm²
SP TP MCB
INCOMER X 125 (N/A) XLPE 4Cx50 1Cx25 19.42 16.66 16.71 52.79 5

OUTGOING

DB-F/GF01 X 40 25 XLPE 4Cx10 1Cx10 3.75 3.51 3.96 11.22 1

DB-F/GF02 X 40 25 XLPE 4Cx10 1Cx10 4.11 3.75 3.38 11.24 1

DB-F/GF03 X 40 25 XLPE 4Cx10 1Cx10 3.75 3.58 3.91 11.24 1

DB-F/GF04 X 40 25 XLPE 4Cx10 1Cx10 3.55 4.11 3.58 11.24 1

DB-F/GF05 X 40 25 XLPE 4Cx16 1Cx16 5.19 5.07 5.24 15.51 1

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 19.42 16.66 16.71 52.79 5
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 70% DIVERSITY 36.95 kW TOTAL CONNECTED LOAD (3 PH) 52.79 kW

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) U t 60A (2) U t 100A (3) 125 160A (4) LV CT / A
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: SMDB-1F TYPICAL FOR CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL SMDB-2F & 3F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: TYPICAL FLOOR EL ROOM

RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
1C,
R-PH Y-PH B-PH TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)
CIRCUIT F/S MCCB SWA/ PVC 2/4X1C mm²
2/3/4C mm² kW kW kW
FEEDER DB NO. SP TP ISO ACB MCB mm² REMARKS
INCOMER X 350 (N/A) XLPE 4Cx240 1Cx120 55.81 55.07 52.40 163.28 17

OUTGOING
DB-F101 X 40 25 XLPE 4Cx10 1Cx10 2.85 3.41 2.81 9.07 1
DB-F102 X 40 25 XLPE 4Cx10 1Cx10 2.85 3.41 2.81 9.07 1
DB-F103 X 40 25 XLPE 4Cx10 1Cx10 2.85 3.41 2.81 9.07 1
DB-F104 X 40 25 XLPE 4Cx10 1Cx10 2.85 3.41 2.81 9.07 1
DB-F105 X 40 25 XLPE 4Cx10 1Cx10 3.65 4.13 3.58 11.36 1
DB-F106 X 40 25 XLPE 4Cx10 1Cx10 2.85 3.41 2.81 9.07 1
DB-F107 X 40 25 XLPE 4Cx16 1Cx16 3.51 2.85 2.90 9.26 1
DB-F108 X 40 25 XLPE 4Cx10 1Cx10 3.05 2.61 3.41 9.07 1
DB-F109 X 40 25 XLPE 4Cx10 1Cx10 3.05 2.61 3.41 9.07 1
DB-F110 X 40 25 XLPE 4Cx10 1Cx10 3.05 2.61 3.41 9.07 1
DB-F111 X 40 25 XLPE 4Cx10 1Cx10 3.75 3.58 3.91 11.24 1
DB-F112 X 40 25 XLPE 4Cx10 1Cx10 3.75 3.58 3.91 11.24 1
DB-F113 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61 9.07 1
DB-F114 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61 9.07 1
DB-F115 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61 9.07 1
DB-F116 X 40 25 XLPE 4Cx10 1Cx10 4.11 3.75 3.38 11.24 1
DB-F117 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.15 2.61 9.17 1

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 55.81 55.07 52.40 163.28 17
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 70% DIVERSITY 114.30 kW TOTAL CONNECTED LOAD (3 PH) 163.28 kW

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A
(1 Phase) (3 Phase)
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: SMDB-4F CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 4th FLOOR EL ROOM

CIRCUIT FEEDER RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
DB NO. 1C, R-PH Y-PH B-PH TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)
mm² kW kW kW
F/S MCCB SWA/ PVC 2/4X1C 2/3/4C mm²
ISO ACB mm²
SP TP MCB REMARKS
INCOMER X 350 (N/A) XLPE 4Cx240 1Cx120 51.11 48.25 49.56 148.93 16

OUTGOING
DB-F401 X 40 25 XLPE 4Cx10 1Cx10 2.80 3.41 2.79 9.00 1
DB-F402 X 40 25 XLPE 4Cx10 1Cx10 2.80 3.41 2.79 9.00 1
DB-F403 X 40 25 XLPE 4Cx10 1Cx10 3.05 2.28 3.74 9.07 1
DB-F404 X 40 25 XLPE 4Cx10 1Cx10 2.80 3.41 2.79 9.00 1
DB-F405 X 40 25 XLPE 4Cx10 1Cx10 3.75 3.38 4.11 11.24 1
DB-F406 X 40 25 XLPE 4Cx10 1Cx10 2.80 3.41 2.79 9.00 1
DB-F407 X 40 25 XLPE 4Cx16 1Cx16 4.21 3.44 3.51 11.17 1
DB-F408 X 40 25 XLPE 4Cx10 1Cx10 3.05 2.28 3.74 9.07 1
DB-F409 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61 9.07 1
DB-F410 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61 9.07 1
DB-F411 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61 9.07 1
DB-F412 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61 9.07 1
DB-F413 X 40 25 XLPE 4Cx10 1Cx10 2.80 3.41 2.79 9.00 1
DB-F414 X 40 25 XLPE 4Cx10 1Cx10 3.00 2.26 3.74 9.00 1
DB-F415 X 40 25 XLPE 4Cx10 1Cx10 3.00 2.26 3.74 9.00 1
DB-F416 X 40 25 XLPE 4Cx10 1Cx10 3.41 3.10 2.59 9.10 1

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 51.11 48.25 49.56 148.93 16
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 119.14 kW TOTAL CONNECTED LOAD (3 PH) 148.93 kW

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A
(1 Phase) (3 Phase)
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: SMDB-5F
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 5th FLOOR EL ROOM

CIRCUIT FEEDER RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
DB NO. 1C, R-PH Y-PH B-PH TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)
mm² kW kW kW
F/S SWA/ PVC 2/4X1C 2/3/4C mm²
ISO mm²
SP TP MCB REMARKS
INCOMER X 350 (N/A) XLPE 4Cx240 1Cx120 53.69 51.95 51.62 157.26 15

OUTGOING
DB-F501 X 25 XLPE 4Cx10 1Cx10 2.80 3.41 2.79 9.00 1
DB-F502 X 25 XLPE 4Cx10 1Cx10 2.80 3.41 2.79 9.00 1
DB-F503 X 25 XLPE 4Cx10 1Cx10 3.75 3.38 4.11 11.24 1
DB-F504 X 25 XLPE 4Cx10 1Cx10 2.80 3.41 2.79 9.00 1
DB-F505 X 25 XLPE 4Cx16 1Cx16 3.85 3.50 3.74 11.09 1
DB-F506 X 25 XLPE 4Cx10 1Cx10 3.05 2.61 3.41 9.07 1
DB-F507 X 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61 9.07 1
DB-F508 X 25 XLPE 4Cx10 1Cx10 4.11 3.75 3.38 11.24 1
DB-F509 X 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61 9.07 1
DB-F510 X 25 XLPE 4Cx10 1Cx10 3.41 3.05 2.61 9.07 1
DB-F511 X 25 XLPE 4Cx10 1Cx10 2.80 3.41 2.79 9.00 1
DB-F512 X 25 XLPE 4Cx10 1Cx10 3.00 2.59 3.41 9.00 1
DB-F513 X 25 XLPE 4Cx10 1Cx10 3.00 2.59 3.41 9.00 1
DB-F514 X 25 XLPE 4Cx10 1Cx10 3.10 2.26 3.74 9.10 1
DB-GYM X 25 XLPE 4Cx25 1Cx16 8.40 8.48 7.43 24.31 1

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 53.69 51.95 51.62 157.26 15
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 125.81 kW TOTAL CONNECTED LOAD (3 PH) 157.26 kW

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A
(1 Phase) (3 Phase)
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI CLIENT: SARHANK KADER
PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: ROOF FLOOR ELECTRICAL ROOM
DB REF: SMDB-MECH@RF

CIRCUIT FEEDER RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
DB NO. 1C,
R-PH Y-PH B-PH TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)
mm² kW kW kW
F/S MCCB SWA/ PVC 2/4X1C 2/3/4C mm²
ISO ACB mm²
SP TP MCB REMARKS
INCOMER X 300 (N/A) XLPE 4Cx185 1Cx95 45.57 49.73 49.73 145.04 0

OUTGOING
FAHU-01 X 80 25 XLPE 4Cx25 1Cx16 10.07 10.07 10.07 30.22 300mA ELCB+Y/D STARTER IN CP

CU/FAHU-01-CP X 250 35 XLPE 4Cx150 1Cx70 31.20 31.20 31.20 93.60 300mA ELCB+UVR+ART+CONTACTOR IN CP

BOOSTER PUMP X 20 25 XLPE 4Cx6 1Cx6 0.50 0.50 0.50 1.50 100mA ELCB
(D)
BOOSTER PUMP X 20 25 XLPE 4Cx6 1Cx6 100mA ELCB
(D) - STBY

GEF X 20 25 XLPE 4Cx6 1Cx6 0.40 0.40 0.40 1.20 300mA ELCB
SW POOL EQPT X 40 25 XLPE 4Cx16 1Cx16 3.40 3.40 3.40 10.20

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 45.57 49.73 49.73 145.04 0
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 116.03 kW TOTAL CONNECTED LOAD (3 PH) 145.04 kW

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A
(1 Phase) (3 Phase)
PROJECT: B+G+5 COM & RES BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: ROOF FLOOR ELECTRICAL ROOM
DB REF: ESMDB-MECH@RF
CIRCUIT FEEDER RATING - AMPS Fault Duty kA PVC XLPE CABLE SIZE ECC SIZE CONNECTED LOAD - kW Proposed kWh Metering
DB NO. 1C,
R-PH Y-PH B-PH TOTAL KW 1-PH (1) 3-PH (2) 3-PH (3) CT (4)
mm² kW kW kW
F/S MCCB SWA/ PVC 2/4X1C 2/3/4C mm²
ISO ACB mm²
SP TP MCB REMARKS
INCOMER X 80 (N/A) XLPE 4Cx35 1Cx16 12.40 12.40 12.40 37.20 0
OUTGOING
SEF X 32 25 FIRE RATED 4Cx6 1Cx6 1.50 1.50 1.50 4.50 300mA ELS+ALARM
MAF X 32 25 FIRE RATED 4Cx6 1Cx6 1.50 1.50 1.50 4.50 300mA ELS+ALARM
LIFT-1 X 40 25 XLPE 4Cx16 1Cx16 3.35 3.35 3.35 10.05 300mA ELCB
LIFT-2 X 40 25 XLPE 4Cx16 1Cx16 3.35 3.35 3.35 10.05 300mA ELCB
LIFT CONTROL X 25 25 XLPE 4Cx6 1Cx6 0.70 0.70 0.70 2.10

GSM X 32 25 XLPE 4Cx6 1Cx6 2.00 2.00 2.00 6.00

NOTE(S): 1 ALL MCCB's BEFORE TARIFF METERING SHALL HAVE PADLOCKING FACILITY AT ITS 'OFF' POSITION

MDB CONNECTED TO : DEWA LV DB-TRANSF. TOTAL CONNECTED LOAD PER PHASE 12.40 12.40 12.40 37.20 0
SMDB CONNECTED TO : MDB…………………

MAX. DEMAND LOAD (3 PH) AT 80% DIVERSITY 29.76 kW TOTAL CONNECTED LOAD (3 PH) 37.20 kW

PROVIDE CT-METER LOAD (3PH) ……………kW


CONTRACTOR :………………………………………………………. TEL:………………
(1) Upto 60A (2) Upto 100A (3) 125-160A (4) LV CT ……/…..A
(1 Phase) (3 Phase)
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: DB-SS
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: LV PANEL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: ELECTRICAL SUB-STATION

MCB CCT ECC Load Per Circuit WATT


RTG IN Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF Size Size
SL NO CIR NO Amps ROOM/ AREA
INCOMER ELCB mm2 mm2 LTG EX. 13A SH W/H W/M KIT HD CCU FCU CU
Fan S/O S/O WATT UNIT R Y B REMARKS
40A,4P 1 C1 10 2.5 2.5 SUBSTATION 6 100 600
100mA ELCB-
2 C2 SPACE
1
3 C3 SPACE
40A,4P 4 C4 20 4.0 4.0 SUBSTATION 2 200 400
30mA ELCB-
2 5 C5 SPACE
6 C6 SPACE
32A SPN ISOL

SUB TOTAL 1,000 0 0

CABLE SIZE: 2C, 10 mm ² XLPE/SWA/PVC/CU + TOTAL 1.00 kW


PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: DB-LL1@BF CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: BASEMENT FLOOR ELECTRICAL ROOM

MCB CCT ECC Load Per Circuit WATT


RTG IN Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF
SL NO CIR NO Amps Size Size ROOM/ AREA
INCOMER ELCB
mm2 mm2 LTG EX. 13A SH W/H W/M KIT HD CCU FCU CU
Fan S/O S/O WATT UNIT R Y B REMARKS
R1 10 2.5 2.5 PARKING(1-14 & 27-45)+FAN RM 8 50 400
1
Y1 10 2.5 2.5 PARKING(15-72) 8 50 400
2
40A,4P B1 10 2.5 2.5 DRIVEWAY+RAMP(GF-BF) 12 50 600
3
100mA ELCB-
R2 10 2.5 2.5 STAIR-01 (BF-RF) 13 50 650
1 4
5 Y2 10 2.5 2.5 LIFT SHAFT (BF-RF) 7 20 140
B2 SPACE
6
R3 10 2.5 2.5 DRIVEWAY+RAMP(BF-GF) 14 50 700
40A,4P 7
100mA ELCB- 8 Y3 SPACE
2 STAIR-02 (UG-RF)
9 B3 10 2.5 2.5 15 50 750

10 R4 20 4.0 4.0 LIFT SHAFT+PARKING 4 200 800


40A,4P
30mA ELCB- Y4 SPACE
11
40A TPN ISOL

3 PARKING
12 B4 20 4.0 4.0 3 200 600
R5 SPACE
40A,4P 13
100mA ELCB- 14 Y5 32 6.0 6.0 LIFT LOBBY CU (B1-01) 1 2400 2,400 UVR+ART+CONT
4 LIFT LOBBY FCU (B1-01)
15 B5 20 4.0 4.0 1 170 170

SUB TOTAL 2,550 2,940 2,120


CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,
16mm² PVC/CU GY ECC
TOTAL 7.61
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: DB-LL2@GF CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV RM PAGES: 1/2

MCB CCT ECC Load Per Circuit WATT


RTG IN Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF Amps Size Size
SL NO CIR NO mm2 mm2 ROOM/ AREA REMARKS
INCOMER ELCB
LTG EX. 13A SH W/H W/M KIT HD CCU FCU CU
Fan S/O S/O
WATT UNIT R Y B
1 R1 10 2.5 2.5 CORRIDOR-GF 6 20 120
2 Y1 10 2.5 2.5 FOOT PATH+STAIR LOBBY+WM 7 50 350
40A,4P 3 B1 10 2.5 2.5 ENT+LIFT LOBBY+RETAIL CORR 15 20 300
100mA ELCB-
1 4 R2 10 2.5 2.5 SERV RMS+TOILETS+PASSAGE 1/14 20/50 720
5 Y2 10 2.5 2.5 PARKING-GF 5 50 250
6 B2 10 2.5 2.5 LV RM+GEN RM 8 50 400

40A,4P 7 R3 10 2.5 2.5 MAIN ENT+RETAIL ENT 7 20 140


100mA ELCB- 8 Y3 SPACE
2
9 B3 10 2.5 2.5 DRIVEWAY-GF 7 50 350
10 R4 20 4.0 4.0 SERV RMS+RETAIL CORR 3 200 600
11 Y4 20 4.0 4.0 CORRIDOR+ENT 4 200 800
63A TPN ISOL

40A,4P 12 B4 20 4.0 4.0 PARKING-GF 3 200 600


30mA ELCB-3 13 R5 SPACE
14 Y5 20 4.0 4.0 DISABLED TOILET WH 1 1200 1200
15 B5 20 4.0 4.0 LV RM+GEN RM 2 200 400

40A,4P 16 R6 1,200
100mA ELCB- 17 Y6 20 4.0 4.0 ENT LOBBY CU (GF-09) 1 3600 1,200 UVR+ART+CONT
5
18 B6 1200

40A,4P 19 R7 20 4.0 4.0 CORRIDOR FCU (GF-10) 1 400 400


100mA ELCB- 20 Y7 20 4.0 4.0 ENT LOBBY FCU (GF-09) 1 330 330
6
21 B7 SPACE

40A,4P 22 R8 32 6.0 6.0 GARBAGE RM CU (GF-11) 1 2200 2,200 UVR+ART+CONT


100mA ELCB- 23 Y8 SPACE
7
24 B8 20 4.0 4.0 GARBAGE RM FCU (GF-11) 1 100 100
SUB TOTAL 5,380 4,130 3,350
CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,
16mm² PVC/CU GY ECC
TOTAL 12.86
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF: DB-LL2@GF CLIENT:
SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV RM PAGES: 1/2

MCB CCT ECC Load Per Circuit WATT


RTG IN Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF
SL NO CIR NO Amps Size Size ROOM/ AREA REMARKS
INCOMER ELCB
mm2 mm2 LTG EX. 13A SH W/H W/M ISO CCU FCU CU
Fan S/O S/O WATT UNIT R Y B

40A,4P 25 R9 20 4.0 4.0 TEL RM FCU (GF-13) 1 140 140


100mA ELCB- 26 Y9 20 4.0 4.0 TEL RM CU (GF-13) 1 1700 1700 UVR+ART+CONT
8
27 B9 SPACE

40A,4P 28 R10 20 4.0 4.0 LV RM FCU (GF-14) 1 170 170


100mA ELCB- 29 Y10 SPACE
9
30 B10 20 4.0 4.0 LV RM CU (GF-14) 1 2400 2400 UVR+ART+CONT

40A,4P R11 500


20 4.0 1.0
100mA ELCB- 31 Y11 GARBAGE COMPACTOR 1 1500 500 TPN ISOL
A TP X 4.0 X 4.0
10
B11 500

40A,4P R12 1900


63A TPN ISOL

100mA ELCB- 32 Y12 20 4 4 CORRIDOR CU (GF-10) 1 5700 1900 UVR+ART+CONT


11
B12 1900

SUB TOTAL 6,190 6,330 6,250


CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,
16mm² PVC/CU GY ECC
TOTAL 18.77
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 1st FLOOR ELECTRICAL ROOM PAGES: 1/2
DB REF: DB-LL3@1F
MCB CCT ECC Load Per Circuit WATT
RTG IN Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF Amps Size Size
SL NO CIR NO ROOM/ AREA REMARKS
INCOMER ELCB mm2 mm2 LTG EX. 13A SH W/H W/M KIT HD CCU FCU CU
Fan S/O S/O
WATT UNIT R Y B
1 R1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-1F 17 20 340
2 Y1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-2F 17 20 340
40A,4P 3 B1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-3F 17 20 340
100mA ELCB-
1 4 R2 10 2.5 2.5 SERVICE RMS+STAIR LOBBY-1F 11 50 550
5 Y2 10 2.5 2.5 SERVICE RMS+STAIR LOBBY-2F 11 50 550
6 B2 10 2.5 2.5 SERVICE RMS+STAIR LOBBY-3F 11 50 550

40A,4P 7 R3 20 4.0 4.0 CORR+STORE+TEL RM-1F 5 200 1,000 RING


30mA ELCB- 8 Y3 20 4.0 4.0 CORR+STORE+TEL RM-2F 5 200 1,000 RING
2
9 B3 20 4.0 4.0 CORR+STORE+TEL RM-3F 5 200 1,000 RING

40A,4P 10 R4 20 4.0 4.0 CORRIDOR FCU (F-18)-1F 1 330 330


100mA ELCB- 11 Y4 SPACE
80A TPN ISOL

3
12 B4 20 4.0 4.0 CORRIDOR FCU (SE-18)-2F 1 330 330

40A,4P 13 R5 20 4.0 4.0 CORRIDOR FCU (F-19)-1F 1 400 400


100mA ELCB- 14 Y5 20 4.0 4.0 CORRIDOR FCU (SE-19)-2F 1 400 400
4
15 B5 SPACE

40A,4P 16 R6 1,200
100mA ELCB- 17 Y6 20 4.0 4.0 CORRIDOR CU (SE-18)-2F 1 3600 1200 UVR+ART+CONT
5
18 B6 1200

40A,4P 19 R7 1,900
100mA ELCB- 20 Y7 20 4.0 4.0 CORRIDOR CU (SE-19)-2F 1 5700 1900 UVR+ART+CONT
6
21 B7 1900

40A,4P 22 R8 20 4.0 4.0 CORRIDOR FCU (TH-19)-3F 1 400 400


100mA ELCB- 23 Y8 SPACE
7
24 B8 20 4.0 4.0 CORRIDOR FCU (TH-18)-3F 1 400 400
SUB TOTAL 6,120 5,390 5,720
CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,
16mm² PVC/CU GY ECC
TOTAL 17.23
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 1st FLOOR ELECTRICAL ROOM PAGES: 2/2
DB REF: DB-LL3@1F
MCB CCT ECC Load Per Circuit WATT
RTG IN Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF
SL NO CIR NO Amps Size Size ROOM/ AREA
INCOMER ELCB LTG EX. 13A SH W/H W/M KIT HD CCU FCU CU
mm2 mm2
Fan S/O S/O WATT UNIT R Y B REMARKS
25 R9 1,900
40A,4P
100mA ELCB- 26 Y9 20 4.0 4.0 CORRIDOR CU (TH-19)-3F 1 5700 1900 UVR+ART+CONT
8 27 B9 1900
28 R10 1,900
40A,4P
100mA ELCB- 29 Y10 20 4.0 4.0 CORRIDOR CU (TH-18)-3F 1 5700 1900 UVR+ART+CONT
9 30 B10 1900
31 R11 1,200
40A,4P
100mA ELCB- 32 Y11 20 4.0 4.0 CORRIDOR CU (F-18)-1F 1 3600 1200 UVR+ART+CONT
10 33 B11 1200
34 R12 1,200
40A,4P
100mA ELCB- 35 Y12 20 4.0 4.0 CORRIDOR CU (F-19)-1F 1 3600 1200 UVR+ART+CONT
80A TPN ISOL

11 36 B12 1200

SUB TOTAL 12,320 11,590 11,920


CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,
16mm² PVC/CU GY ECC
TOTAL 35.83
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI CLIENT: SARHANK KADER

PLOT NO. JVC14VMRA002

FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 4th FLOOR ELECTRICALPAGES:
ROOM 1/2 DB REF: DB-LL4@4F

MCB CCT ECC Load Per CircuitWATT

RTG IN Wire Wire CONNECTED LOADS/POINTS


RATING OF Amps Size Size
RATING OF INCOMER SL NO CIR NO ROOM/ AREA WATT UNIT REMARKS
ELCB R Y B
mm2 mm2 LTG EX FAN 13A SH W/M IND SKT KIT HD ISOL FCU CU

S/O S/O

1 R1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-4F 15 20 300

2 Y1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-5F 14 20 280


40A,4P
3 B1 10 2.5 2.5 ROOF 7 50 350
100mA ELCB-
4 R2 10 2.5 2.5 SERVICE RMS-4F 5 50 250
1

5 Y2 10 2.5 2.5 SERVICE RMS-5F 4 50 200

6 B2 10 2.5 2.5 ROOF 10 50 500

40A,4P 7 R3 10 2.5 2.5 EL RM+LIFT LOBBY+ROOF 6 50 300

100mA ELCB- 8 Y3 10 2.5 2.5 GSM RM+ROOF 7 50 350


2
9 B3 SPACE

10 R4 20 4.0 4.0 CORR+TEL RM-4F 4 200 800

11 Y4 20 4.0 4.0 CORR+TEL RM-5F 4 200 800


80A TPN ISOL

40A,4P 12 B4 20 4.0 4.0 ROOF 2 200 400

30mA ELCB-3 13 R5 20 4.0 4.0 SIGNAGE 1 700 700 SPN ISOL

14 Y5 20 4.0 4.0 ROOF 3 600

15 B5 20 4.0 4.0 ROOF 2 400

40A,4P 16 R6 20 4.0 4.0 CORRIDOR FCU (4F-17)-4F 1 330 330

100mA ELCB- 17 Y6 SPACE


4
18 B6 20 4.0 4.0 CORRIDOR FCU (4F-18)-4F 1 330 330

40A,4P 19 R7 1200

100mA ELCB- 20 Y7 20 1.0 4.0 CORRIDOR CU (4F-18)-4F 1 3600 1,200 UVR+ART+CONT

5
21 B7 1,200

40A,4P 22 R8 1200

100mA ELCB- 23 Y8 20 1.0 4.0 CORRIDOR CU (5F-17)-5F 1 3600 1,200 UVR+ART+CONT

6
24 B8 1,200

SUB TOTAL 5,080 4,630 4,380

CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,


TOTAL 14.09
16mm ² PVC/CU GY ECC
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI CLIENT: SARHANK KADER

PLOT NO. JVC14VMRA002

FED FROM: SMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 4th FLOOR ELECTRICALPAGES:
ROOM 2/2 DB REF: DB-LL4@4F

MCB CCT ECC Load Per CircuitWATT

RTG IN Wire Wire CONNECTED LOADS/POINTS


RATING OF
RATING OF INCOMER SL NO CIR NO Amps Size Size ROOM/ AREA WATT UNIT REMARKS
ELCB
mm2 mm2 LTG EX FAN 13A SH W/M IND SKT KIT HD ISOL FCU CU

S/O S/O R Y B

25 R9 SPACE
40A,4P

100mA ELCB- 26 Y9 20 4.0 4.0 CORRIDOR FCU (5F-18)-5F 1 400 400

7 27 B9 20 4.0 4.0 CORRIDOR FCU (5F-17)-5F 1 400 400

28 R10 20 4.0 1.0 400

A TP X 4.0 X 4.0
29 Y10 CLEANING CRADLE-1 1 1200 400 TP IND SKT
40A,4P
30 B10 400
100mA ELCB-
31 R11 20 4.0 1.0 400
8
A TP X 4.0 X 4.0
32 Y11 CLEANING CRADLE-2 1 1200 400 TP IND SKT

33 B11 400

34 R12 20 4.0 1.0 400

A TP X 4.0 X 4.0
35 Y12 CLEANING CRADLE-3 1 1200 400 TP IND SKT
80A TPN ISOL

40A,4P
36 B12 400
100mA ELCB-
37 R13 20 4.0 1.0 400
9
A TP X 4.0 X 4.0
38 Y13 CLEANING CRADLE-4 1 1200 400 TP IND SKT

39 B13 400

40 R14 20 4.0 1.0 1200


40A,4P
A TP X 4.0 X 4.0
100mA ELCB- 41 Y14 CORRIDOR CU (4F-17)-4F 1 3600 1,200 UVR+ART+CONT

10 42 B14 1,200

43 R15 20 4.0 1.0 1900


40A,4P
A TP X 4.0 X 4.0
100mA ELCB- 44 Y15 CORRIDOR CU (5F-18)-5F 1 5700 1,900 UVR+ART+CONT

11 45 B15 1,900

SUB TOTAL 9,780 9,730 9,480

CABLE SIZE: 4C, 25 mm² XLPE/SWA/PVC/CU +1C,

16mm ² PVC/CU GY ECC


TOTAL 28.99
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: BASEMENT FLOOR ELECTRICAL ROOM
DB REF: EDB-LL1@BF

MCB CCT ECC Load Per Circuit WATT


RTG Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR IN Size Size
ROOM/ AREA
INCOMER ELCB NO NO Amps mm² mm²
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
Fan S/O S/O HD WATT UNIT R Y B REMARKS
1 R1 10 2.5 2.5 EL RM+PARKING(15-72) 9 50 450
2 Y1 10 2.5 2.5 DRIVEWAY+RAMP(GF-BF) 13 50 650
40A,4P
3 B1 10 2.5 2.5 PARKING(1-14 & 27-45) 6 50 300
100mA
4 R2 10 2.5 2.5 LIFT LOBBY 4 20 80
ELCB-1
5 Y2 10 2.5 2.5 UG PUMP RM 4 50 200
6 B2 10 2.5 2.5 DRIVEWAY+RAMP(BF-GF) 12 50 600
7 R3 SPACE
8 Y3 20 4.0 4.0 UG PUMP RM 2 200 400
40A,4P
9 B3 20 4.0 4.0 EL RM+LIFT LOBBY+FAN RM 3 200 600
30mA ELCB-
10 R4 20 4.0 4.0 CCTV CAMERA (2NOS.) 2 100 200
2
40A TPN ISOL

11 Y4 20 4.0 4.0 CCTV CAMERA 1 100 100


12 B4 20 4.0 4.0 CCTV CAMERA 1 100 100
40A,4P 13 R5 20 4.0 4.0 UG PUMP RM CU (B2-01) 1 2800 2800 UVR+ART+CONT
100mA 14 Y5 20 4.0 4.0 UG PUMP RM FCU (B2-01) 1 200 200
ELCB-3 15 B5 SPACE

SUB TOTAL 3,530 1,550 1,600


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 6.68
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GROUND FLOOR LV ROOM
DB REF: EDB-LL2@GF

MCB CCT ECC Load Per Circuit WATT


RTG Wire Wire
CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR IN Size Size
Amps ROOM/ AREA
INCOMER ELCB NO NO mm² mm²
LTG EX. 13A SH W/H W/M KIT ISOL FCU CU
Fan S/O S/O HD
WATT UNIT R Y B REMARKS
1 R1 10 2.5 2.5 PARKING-GF 4 50 200
2 Y1 10 2.5 2.5 CORRIDOR-GF 5 50 250
40A,4P
3 B1 10 2.5 2.5 DRIVEWAY-GF 7 50 350
100mA
4 R2 SPACE
ELCB-1
5 Y2 10 2.5 2.5 ENT+LIFT LOBBY+RETAIL CORR 11 50 550
6 B2 SPACE
40A,4P 7 R3 20 4.0 4.0 ENTRY GATE BARRIER 1 500 500 SPN ISOL
100mA 8 Y3 SPACE
ELCB-2 9 B3 20 4.0 4.0 EXIT GATE BARRIER 1 500 500 SPN ISOL
10 R4 20 4.0 4.0 CCTV CAMERA (2NOS.) 2 100 200
CCTV CAMERA (3NOS.)
40A TPN ISOL

11 Y4 20 4.0 4.0 3 100 300


40A,4P
12 B4 20 4.0 4.0 CCTV CAMERA (2NOS.) 2 100 200
100mA @H/L
13 R5 SPACE
ELCB-3
14 Y5 SPACE
15 B5 20 4.0 4.0 CCTV CAMERA (3NOS.) 3 100 300
16 R6 20 4.0 4.0 CORRIDOR+RECP-GF 1/2 200/400 1,000 RING
17 Y6 20 4.0 4.0 MFACP 1 400 400 MFACP
40A,4P
18 B6 20 4.0 4.0 RECEPTION 12U CABINET 1 200 200 12U CAB
30mA ELCB-
19 R7 SPACE
4
20 Y7 20 4.0 4.0 MAIN TEL RM 2 400 800
21 B7 SPACE

SUB TOTAL 1,900 2,300 1,550


CABLE SIZE: 4C, 10 mm² XLPE/SWA/PVC/CU + TOTAL 5.75 kW
1C, 10 mm² PVC/CU GY ECC
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 1st FLOOR ELECTRICAL ROOM
DB REF: EDB-LL3@1F

MCB CCT ECC Load Per Circuit WATT


RTG Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR IN Size Size
Amps mm2 mm2 ROOM/ AREA
INCOMER ELCB NO NO
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
Fan S/O S/O HD
WATT UNIT R Y B REMARKS
40A,4P 1 R1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-1F 17 20 340
100mA 2 Y1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-2F 17 20 340
ELCB-1 3 B1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-3F 17 20 340
40A,4P 4 R2 20 4.0 4.0 CCTV CAMERA (3NOS.)-1F 3 100 300
100mA 5 Y2 20 4.0 4.0 CCTV CAMERA (3NOS.)-2F 3 100 300 @H/L
ELCB-2 6 B2 20 4.0 4.0 CCTV CAMERA (3NOS.)-3F 3 100 300
7 R3 20 4.0 4.0 MOTORIZED DAMPER-1F 1 50 50
8 Y3 20 4.0 4.0 MOTORIZED DAMPER-2F 1 50 50
40A,4P
9 B3 20 4.0 4.0 MOTORIZED DAMPER-3F 1 50 50
100mA @H/L
10 R4 20 4.0 4.0 MOTORIZED DAMPER-1F 1 50 50
ELCB-3
MOTORIZED DAMPER-2F
40A TPN ISOL

11 Y4 20 4.0 4.0 1 50 50
12 B4 20 4.0 4.0 MOTORIZED DAMPER-3F 1 50 50
40A,4P 13 R5 20 4.0 4.0 EL RM-1F 1 400 400
30mA ELCB- 14 Y5 20 4.0 4.0 EL RM-2F 1 400 400
4 15 B5 20 4.0 4.0 EL RM-3F 1 400 400

SUB TOTAL 1,140 1,140 1,140


CABLE SIZE: 4C, 10 mm² XLPE/SWA/PVC/CU + TOTAL 3.42 kW
1C, 10 mm² PVC/CU GY ECC
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: ESMDB-LL CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: 4th FLOOR ELECTRICAL ROOM
DB REF: EDB-LL4@4F

MCB CCT ECC Load Per Circuit WATT


RTG Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR IN Size Size
ROOM/ AREA
INCOMER ELCB NO NO Amps mm2 mm2 LTG EX. 13A SH W/H W/M KIT CCU FCU CU
Fan S/O S/O HD
WATT UNIT R Y B REMARKS
40A,4P 1 R1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-4F 16 20 320
100mA 2 Y1 10 2.5 2.5 CORRIDOR+LIFT LOBBY-5F 15 20 320
ELCB-1 3 B1 10 2.5 2.5 ROOF 7 50 350
4 R2 20 4.0 4.0 CCTV CAMERA (3NOS.)-4F 3 100 300
5 Y2 20 4.0 4.0 CCTV CAMERA (3NOS.)-5F 3 100 300
40A,4P
6 B2 20 4.0 4.0 CCTV CAMERA (1NO.)-RF 1 100 100
100mA @H/L
7 R3 20 4.0 4.0 CCTV CAMERA (1NO.)-RF 1 100 100
ELCB-2
8 Y3 20 4.0 4.0 CCTV CAMERA (1NO.)-RF 1 100 100
9 B3 SPACE
10 R4 20 4.0 4.0 MOTORIZED DAMPER-4F 1 50 50
MOTORIZED DAMPER-5F
40A TPN ISOL

11 Y4 20 4.0 4.0 1 50 50
40A,4P
12 B4 20 4.0 4.0 MOTORIZED DAMPER-RF 1 50 50
100mA @H/L
13 R5 20 4.0 4.0 MOTORIZED DAMPER-4F 1 50 50
ELCB-3
14 Y5 20 4.0 4.0 MOTORIZED DAMPER-5F 1 50 50
15 B5 20 4.0 4.0 MOTORIZED DAMPER-RF 1 50 50
16 R6 20 4.0 4.0 EL RM-4F 1 400 400
17 Y6 20 4.0 4.0 EL RM-5F 1 400 400
40A,4P
18 B6 20 4.0 4.0 EL RM-RF 1 400 400
30mA ELCB-
19 R7 SPACE
4
20 Y7 SPACE
21 B7 20 4.0 4.0 GSM RM-RF 2 400 800

SUB TOTAL 1,220 1,220 1,750


CABLE SIZE: 4C, 10 mm² XLPE/SWA/PVC/CU + TOTAL 4.19 kW
1C, 10 mm² PVC/CU GY ECC
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-GF CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F/GF01 1BHK

MCB CCT ECC Load Per Circuit WATT


RTG Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR IN Size Size
Amps mm2 mm2 ROOM/ AREA
INCOMER ELCB NO NO
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
Fan S/O S/O HD
WATT UNIT R Y B REMARKS
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 50/100 250
100mA 2 Y1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2 20/100 260
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 BED RM 3 200 600
40A,4P
6 B2 20 4.0 4.0 LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 SPACE
2
8 Y3 20 4.0 4.0 12U CABINET 1 200 200
9 B3 20 4.0 4.0 LAUNDRY 1 1000 1,000
40A,4P 10 R4 20 4.0 4.0 BATH WH 1 1200 1200
30mA ELCB- PANTRY (FRIDGE)
40A TPN ISOL

11 Y4 20 4.0 4.0 1 200 200


3 12 B4 SPACE
40A,4P 13 R5 SPACE
100mA 14 Y5 20 4.0 4.0 PANTRY FCU 1 400 400
ELCB-4 15 B5 SPACE
40A,4P 16 R6 1900
100mA 17 Y6 20 4.0 4.0 CU 1 5700 1900 UVR+ART+CONT
ELCB-5 18 B6 1900

SUB TOTAL 3,750 3,510 3,960


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 11.22
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-GF CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F/GF02 1BHK

MCB CCT ECC Load Per Circuit WATT


RTG Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR IN Size Size
Amps mm2 mm2 ROOM/ AREA
INCOMER ELCB NO NO
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
Fan S/O S/O HD
WATT UNIT R Y B REMARKS
40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
100mA 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
4 R2 20 4.0 4.0 BED RM 3 200 600
5 Y2 20 4.0 4.0 PANTRY 2 200 400
40A,4P
6 B2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 12U CABINET 1 200 200
2
8 Y3 20 4.0 4.0 LAUNDRY 1 1000 1,000
9 B3 SPACE
40A,4P 10 R4 20 4.0 4.0 BATH WH 1 1200 1,200
30mA ELCB- PANTRY (FRIDGE)
40A TPN ISOL

11 Y4 20 4.0 4.0 1 200 200


3 12 B4 SPACE
40A,4P 13 R5 1900
100mA 14 Y5 20 4.0 4.0 CU 1 5700 1900 UVR+ART+CONT
ELCB-4 15 B5 1900
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 400 400

SUB TOTAL 4,110 3,750 3,380


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-GF CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F/GF031BHK

MCB CCT ECC Load Per Circuit WATT


RTG Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR IN Size Size
ROOM/ AREA
INCOMER ELCB NO NO Amps mm2 mm2 LTG EX. 13A SH W/H W/M KIT CCU FCU CU
Fan S/O S/O HD
WATT UNIT R Y B REMARKS
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
100mA 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
ELCB-1 3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
40A,4P
6 B2
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1,000
2
8 Y3 20 4.0 4.0 BED RM 3 200 600
9 B3 20 4.0 4.0 12U CABINET 1 200 200
40A,4P 10 R4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
30mA ELCB- SPACE
40A TPN ISOL

11 Y4
3 12 B4 20 4.0 4.0 BATH WH 1 1200 1,200
40A,4P 13 R5 1900
100mA 14 Y5 20 4.0 4.0 CU 1 5700 1900 UVR+ART+CONT
ELCB-4 15 B5 1900
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 400 400

SUB TOTAL 3,750 3,580 3,910


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-GF CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F/GF04 1BHK

MCB CCT ECC Load Per Circuit WATT


RTG Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR IN Size Size
ROOM/ AREA
INCOMER ELCB NO NO Amps mm2 mm2
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
Fan S/O S/O HD
WATT UNIT R Y B REMARKS
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
100mA 2 Y1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 BED RM 3 200 600
40A,4P
6 B2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1000
2
8 Y3 20 4.0 4.0 12U CABINET 1 200 200
9 B3 SPACE
40A,4P 10 R4 SPACE
30mA ELCB- BATH WH
40A TPN ISOL

11 Y4 20 4.0 4.0 1 1200 1,200


3 12 B4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A,4P 13 R5 1900
100mA 14 Y5 20 4.0 4.0 CU 1 5700 1900 UVR+ART+CONT
ELCB-4 15 B5 1900
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 400 400

SUB TOTAL 3,550 4,110 3,580


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-GF CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F/GF05 2BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size CONNECTED LOADS/POINTS
Amps mm2 mm2 LTG EX. 13A SH W/H W/M KIT CCU FCU CU
RATING OF RATING OF SL CIR
Fan S/O S/O HD
INCOMER ELCB NO NO ROOM/ AREA WATT UNIT R Y B REMARKS
1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
2 Y1 10 2.5 2.5 BED RM1+BATH 2/1/1 1 20/50/100 210
40A,4P
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/3 20/100 380
100mA
4 R2 10 2.5 2.5 BED RM2+BATH 2/1/1 1 20/50/100 210
ELCB-1
5 Y2 SPACE
6 B2 SPACE
7 R3 20 4.0 4.0 PANTRY 2 200 400
8 Y3 20 4.0 4.0 BED RM1 3 200 600
40A,4P
9 B3 20 4.0 4.0 LIV/DIN 2/1 200/400 800
30mA ELCB-
10 R4 20 4.0 4.0 BED RM2 3 200 600
2
BATH1 WH
40A TPN ISOL

11 Y4 20 4.0 4.0 1 1200 1,200


12 B4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A,4P 13 R5 20 4.0 4.0 BATH2 WH 1 1200 1,200
30mA ELCB- 14 Y5 20 4.0 4.0 12U CABINET 1 200 200
3 15 B5 20 4.0 4.0 LAUNDRY 1 1000 1,000
16 R6 SPACE
17 Y6 20 4.0 4.0 PANTRY FCU-1 1 330 330
40A,4P
18 B6 20 4.0 4.0 FCU-2 1 330 330
100mA
19 R7 1,267
ELCB-4
20 Y7 20 4.0 4.0 CU 1 3800 1,267 UVR+ART+CONT
21 B7 1,267
40A,4P 22 R8 1,267
100mA 23 Y8 20 4.0 4.0 CU 1 3800 1,267 UVR+ART+CONT
ELCB-5 24 B8 1,267
SUB TOTAL 5,193 5,073 5,243
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 15.51
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(101,102,103,104 & 106)1BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size CONNECTED LOADS/POINTS
Amps mm2 mm2
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
RATING OF RATING OF SL CIR
Fan S/O S/O HD
INCOMER ELCB NO NO ROOM/ AREA WATT UNIT R Y B REMARKS
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
100mA 2 Y1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 BED RM 3 200 600
40A,4P
6 B2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1000
2
8 Y3 20 4.0 4.0 12U CABINET 1 200 200
9 B3 SPACE
40A,4P 10 R4 SPACE
30mA ELCB- 11 BATH WH
40A TPN ISOL

Y4 20 4.0 4.0 1 1200 1,200


3 12 B4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 330 330

SUB TOTAL 2,850 3,410 2,810


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI 1BHK
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F105

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size
CONNECTED LOADS/POINTS
Amps mm2 mm2
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
RATING OF RATING OF SL CIR
Fan S/O S/O HD
INCOMER ELCB NO NO ROOM/ AREA WATT UNIT R Y B REMARKS
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/2 1 20/50/100 350
100mA 2 Y1 10 2.5 2.5 BED RM+BATH 3/1/1 1 20/50/100 230
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 BED RM 3 200 600
40A,4P
6 B2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1000
2
8 Y3 20 4.0 4.0 12U CABINET 1 200 200
9 B3 SPACE
40A,4P 10 R4 SPACE
30mA ELCB- 11 BATH WH
40A TPN ISOL

Y4 20 4.0 4.0 1 1200 1,200


3 12 B4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A,4P 13 R5 1900
100mA 14 Y5 20 4.0 4.0 CU 1 5700 1900 UVR+ART+CONT
ELCB-4 15 B5 1900
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 400 400

SUB TOTAL 3,650 4,130 3,580


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 11.36
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB- F107 1BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size CONNECTED LOADS/POINTS
Amps mm2 mm2 LTG EX. 13A SH W/H W/M KIT CCU FCU CU
RATING OF RATING OF SL CIR Fan S/O S/O HD
INCOMER ELCB NO NO ROOM/ AREA WATT UNIT R Y B REMARKS
40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
100mA 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 5/2 20/100 300
4 R2 20 4.0 4.0 BED RM 3 200 600
5 Y2 20 4.0 4.0 PANTRY 2 200 400
40A,4P
6 B2 20 4.0 4.0 PASSAGE+LIV/DIN 3/1 200/400 1,000 RING
30mA ELCB-
7 R3 SPACE
2
8 Y3 20 4.0 4.0 LAUNDRY 1 1000 1,000
9 B3 20 4.0 4.0 12U CABINET 1 200 200
40A,4P 10 R4 20 4.0 4.0 BATH WH 1 1200 1,200
30mA ELCB- 11 SPACE
40A TPN ISOL

Y4
3 12 B4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
13 R5 20 4.0 4.0 BED BATH FCU 1 300 300
14 Y5 SPACE
40A,4P
15 B5 SPACE
100mA
16 R6 1200
ELCB-4
17 Y6 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
18 B6 1200

SUB TOTAL 3,510 2,850 2,900


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.26
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF:
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB-F(108,109 & 110) 1BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size
Amps mm2 mm2 CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B REMARKS
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
100mA 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
ELCB-1 3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
40A,4P
6 B2 20 4.0 4.0 BED RM 3 200 600
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1,000
2
8 Y3 SPACE
9 B3 20 4.0 4.0 12U CABINET 1 200 200
40A,4P 10 R4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
30mA ELCB- 11 SPACE
40A TPN ISOL

Y4
3 12 B4 20 4.0 4.0 BATH WH 1 1200 1,200
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 20 4.0 4.0 PANTRY FCU 1 330 330
ELCB-5 18 B6

SUB TOTAL 3,050 2,610 3,410


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI DB REF:
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB-F(111 & 112) 1BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size
Amps mm2 mm2 CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B REMARKS
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
100mA 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
ELCB-1 3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
40A,4P
6 B2 SPACE
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1,000
2
8 Y3 20 4.0 4.0 BED RM 3 200 600
9 B3 20 4.0 4.0 12U CABINET 1 200 200
40A,4P 10 R4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
30mA ELCB- 11 SPACE
40A TPN ISOL

Y4
3 12 B4 20 4.0 4.0 BATH WH 1 1200 1,200
40A,4P 13 R5 1900
100mA 14 Y5 20 4.0 4.0 CU 1 5700 1900 UVR+ART+CONT
ELCB-4 15 B5 1900
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 400 400

SUB TOTAL 3,750 3,580 3,910


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(113,114,115) BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size
Amps mm2 mm2 CONNECTED LOADS/POINTS REMARKS
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
RATING OF RATING OF SL CIR Fan S/O S/O HD
INCOMER ELCB NO NO ROOM/ AREA WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
100mA 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
4 R2 20 4.0 4.0 BED RM 3 200 600
5 Y2 20 4.0 4.0 PANTRY 2 200 400
40A,4P
6 B2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 12U CABINET 1 200 200
2
8 Y3 20 4.0 4.0 LAUNDRY 1 1000 1,000
9 B3 SPACE
40A,4P 10 R4 20 4.0 4.0 BATH WH 1 1200 1,200
30mA ELCB- 11 PANTRY (FRIDGE)
40A TPN ISOL

Y4 20 4.0 4.0 1 200 200


3 12 B4 SPACE
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 330 330

SUB TOTAL 3,410 3,050 2,610


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(116) BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size
Amps mm2 mm2 CONNECTED LOADS/POINTS REMARKS
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
RATING OF RATING OF SL CIR Fan S/O S/O HD
INCOMER ELCB NO NO ROOM/ AREA WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
100mA 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
4 R2 20 4.0 4.0 BED RM 3 200 600
5 Y2 20 4.0 4.0 PANTRY 2 200 400
40A,4P
6 B2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 12U CABINET 1 200 200
2
8 Y3 20 4.0 4.0 LAUNDRY 1 1000 1,000
9 B3 SPACE
40A,4P 10 R4 20 4.0 4.0 BATH WH 1 1200 1,200
30mA ELCB- 11 PANTRY (FRIDGE)
40A TPN ISOL

Y4 20 4.0 4.0 1 200 200


3 12 B4 SPACE
40A,4P 13 R5 1900
100mA 14 Y5 20 4.0 4.0 CU 1 5700 1900 UVR+ART+CONT
ELCB-4 15 B5 1900
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 400 400

SUB TOTAL 4,110 3,750 3,380


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-1F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F117 1BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire
IN Size Size WATT
Amps mm2 mm2 REMARKS
CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
100mA 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/2 1 20/50/100 350
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
4 R2 20 4.0 4.0 BED RM 3 200 600
5 Y2 20 4.0 4.0 PANTRY 2 200 400
40A,4P
6 B2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 12U CABINET 1 200 200
2
8 Y3 20 4.0 4.0 LAUNDRY 1 1000 1,000
9 B3 SPACE
40A,4P 10 R4 20 4.0 4.0 BATH WH 1 1200 1,200
30mA ELCB- 11 PANTRY (FRIDGE)
40A TPN ISOL

Y4 20 4.0 4.0 1 200 200


3 12 B4 SPACE
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 330 330

SUB TOTAL 3,410 3,150 2,610


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.17
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(401,402,404,406 & 413) 1BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size
REMARKS
Amps mm2 mm2 CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 PANTRY 1 1 100 200
100mA 2 Y1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2 20/100 260
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 BED RM 3 200 600
40A,4P
6 B2 20 4.0 4.0 LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1000
2
8 Y3 20 4.0 4.0 12U CABINET 1 200 200
9 B3 SPACE
40A,4P 10 R4 SPACE
30mA ELCB- 11 BATH WH
40A TPN ISOL

Y4 20 4.0 4.0 1 1200 1,200


3 12 B4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 330 330

SUB TOTAL 2,800 3,410 2,790


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.00
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(403 & 408)1BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size
REMARKS
Amps mm2 mm2 CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
100mA 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
ELCB-1 3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
40A,4P
6 B2 20 4.0 4.0 BED RM 3 200 600
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1,000
2
8 Y3 SPACE
9 B3 20 4.0 4.0 12U CABINET 1 200 200
40A,4P 10 R4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
30mA ELCB- 11 SPACE
40A TPN ISOL

Y4
3 12 B4 20 4.0 4.0 BATH WH 1 1200 1,200
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 330 330

SUB TOTAL 3,050 2,280 3,740


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(405)1BHK
MCB CCT ECC Load Per Circuit
RTG Wire Wire
IN Size Size
WATT REMARKS
Amps mm2 mm2 CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
100mA
2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
ELCB-1
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
40A,4P
6 B2 20 4.0 4.0 BED RM 3 200 600
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1,000
2
8 Y3 SPACE
9 B3 20 4.0 4.0 12U CABINET 1 200 200
40A,4P 10 R4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A TPN ISOL

30mA ELCB- 11 Y4 SPACE


3 12 B4 20 4.0 4.0 BATH WH 1 1200 1,200
40A,4P 13 R5 1900
100mA 14 Y5 20 4.0 4.0 CU 1 5700 1900 UVR+ART+CONT
ELCB-4 15 B5 1900
40A,4P 16 R6 SPACE
100mA 17 Y6 20 4.0 4.0 PANTRY FCU 1 400 400
ELCB-5 18 B6 SPACE

SUB TOTAL 3,750 3,380 4,110


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F407 2BHK
MCB CCT ECC Load Per Circuit
RTG Wire Wire
WATT
IN Size Size CONNECTED LOADS/POINTS REMARKS
Amps mm2 mm2
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
1 R1 10 2.5 2.5 PANTRY 1 1 100 200

40A,4P 2 Y1 10 2.5 2.5 BED RM1+BATH 2/1/1 1 20/50/100 210


100mA 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
ELCB-1 4 R2 10 2.5 2.5 BED RM2+BATH+BALCONY 4/1/1 1 20/50/100 250
5 Y2 SPACE
6 B2 SPACE
7 R3 20 4.0 4.0 PANTRY 2 200 400
8 Y3 20 4.0 4.0 BED RM1 3 200 600
40A,4P
9 B3 20 4.0 4.0 LIV/DIN 2/1 200/400 800
30mA ELCB-
10 R4 20 4.0 4.0 BATH2 WH 1 1200 1,200
2
40A TPN ISOL

11 Y4 20 4.0 4.0 BATH1 WH 1 1200 1,200


12 B4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A,4P 13 R5 20 4.0 4.0 BED RM2 3 200 600
30mA ELCB- 14 Y5 20 4.0 4.0 12U CABINET 1 200 200
3 15 B5 20 4.0 4.0 LAUNDRY 1 1000 1,000
16 R6 20 4.0 4.0 BED RM2 BATH FCU 1 330 330
17 Y6 SPACE
40A,4P
18 B6 SPACE
100mA
19 R7 1233
ELCB-4
20 Y7 20 4.0 4.0 CU 1 3700 1233 UVR+ART+CONT
21 B7 1233

SUB TOTAL 4,213 3,443 3,513


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 11.17
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(409,410,411 & 412) 1BHK
MCB CCT ECC Load Per Circuit
RTG Wire Wire
WATT
IN Size Size
REMARKS
Amps mm2 mm2 CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
100mA
2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
ELCB-1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
4 R2 20 4.0 4.0 BED RM 3 200 600
5 Y2 20 4.0 4.0 PANTRY 2 200 400
40A,4P
6 B2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 12U CABINET 1 200 200
2
8 Y3 20 4.0 4.0 LAUNDRY 1 1000 1,000
9 B3 SPACE
40A,4P 10 R4 20 4.0 4.0 BATH WH 1 1200 1,200
40A TPN ISOL

30mA ELCB- 11 Y4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200


3 12 B4 SPACE
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 330 330

SUB TOTAL 3,410 3,050 2,610


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(414 & 415)1BHK
MCB CCT ECC Load Per Circuit
RTG Wire Wire
WATT
IN Size Size
Amps mm2 mm2 CONNECTED LOADS/POINTS REMARKS

RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 PANTRY 1 1 100 200
100mA
2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2 20/100 260
ELCB-1
3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 LIV/DIN 2/1 200/400 800
40A,4P
6 B2 20 4.0 4.0 BED RM 3 200 600
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1,000
2
8 Y3 SPACE
9 B3 20 4.0 4.0 12U CABINET 1 200 200
40A,4P 10 R4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A TPN ISOL

30mA ELCB- 11 Y4 SPACE


3 12 B4 20 4.0 4.0 BATH WH 1 1200 1,200
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 330 330

SUB TOTAL 3,000 2,260 3,740


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
TOTAL 9.00
PVC/CU GY ECC
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-4F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F416
MCB CCT ECC Load Per Circuit
RTG Wire Wire WATT
IN Size Size
CONNECTED LOADS/POINTS REMARKS
Amps mm2 mm2
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
100mA
2 Y1 10 2.5 2.5 PANTRY 2 1 100 300
ELCB-1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2 20/100 260
4 R2 20 4.0 4.0 BED RM 3 200 600
5 Y2 20 4.0 4.0 PANTRY 2 200 400
40A,4P
6 B2 20 4.0 4.0 LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 12U CABINET 1 200 200
2
8 Y3 20 4.0 4.0 LAUNDRY 1 1000 1,000
9 B3 SPACE
40A,4P 10 R4 20 4.0 4.0 BATH WH 1 1200 1,200
40A TPN ISOL

30mA ELCB- 11 Y4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200


3 12 B4 SPACE
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 330 330

SUB TOTAL 3,410 3,100 2,590


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.10
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(501,502,504 & 511) 1BHK
MCB CCT ECC Load Per Circuit
RTG Wire Wire WATT
IN Size Size
CONNECTED LOADS/POINTS REMARKS
Amps mm2 mm2
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 PANTRY 1 1 100 200
100mA
2 Y1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
ELCB-1
3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2 20/100 260
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 BED RM 3 200 600
40A,4P
6 B2 20 4.0 4.0 LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1000
2
8 Y3 20 4.0 4.0 12U CABINET 1 200 200
9 B3 SPACE
40A,4P 10 R4 SPACE
40A TPN ISOL

30mA ELCB- 11 Y4 20 4.0 4.0 BATH WH 1 1200 1,200


3 12 B4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 330 330

SUB TOTAL 2,800 3,410 2,790


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.00
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(503)1BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size
Amps mm2 mm2 CONNECTED LOADS/POINTS REMARKS
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
RATING OF RATING OF SL CIR
Fan S/O S/O HD
INCOMER ELCB NO NO ROOM/ AREA WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
100mA 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
ELCB-1 BED RM+BATH
3 B1 10 2.5 2.5 2/1/1 1 20/50/100 210
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
40A,4P
6 B2 20 4.0 4.0 BED RM 3 200 600
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1,000
2
8 Y3 SPACE
9 B3 20 4.0 4.0 12U CABINET 1 200 200
40A,4P 10 R4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A TPN ISOL

30mA ELCB- 11 Y4 SPACE


3 12 B4 20 4.0 4.0 BATH WH 1 1200 1,200
40A,4P 13 R5 1900
100mA 14 Y5 20 4.0 4.0 CU 1 5700 1900 UVR+ART+CONT
ELCB-4 15 B5 1900
40A,4P 16 R6 SPACE
100mA 17 Y6 20 4.0 4.0 PANTRY FCU 1 400 400
ELCB-5 18 B6 SPACE

SUB TOTAL 3,750 3,380 4,110


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(506)1BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size
Amps mm2 mm2 CONNECTED LOADS/POINTS REMARKS
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
RATING OF RATING OF SL CIR
Fan S/O S/O HD
INCOMER ELCB NO NO ROOM/ AREA WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
100mA 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
ELCB-1 BED RM+BATH
3 B1 10 2.5 2.5 2/1/1 1 20/50/100 210
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
40A,4P
6 B2 20 4.0 4.0 BED RM 3 200 600
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1,000
2
8 Y3 SPACE
9 B3 20 4.0 4.0 12U CABINET 1 200 200
40A,4P 10 R4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A TPN ISOL

30mA ELCB- 11 Y4 SPACE


3 12 B4 20 4.0 4.0 BATH WH 1 1200 1,200
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 20 4.0 4.0 PANTRY FCU 1 330 330
ELCB-5 18 B6 SPACE

SUB TOTAL 3,050 2,610 3,410


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(506)1BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size
Amps mm2 mm2 CONNECTED LOADS/POINTS REMARKS
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
RATING OF RATING OF SL CIR
Fan S/O S/O HD
INCOMER ELCB NO NO ROOM/ AREA WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
100mA 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
ELCB-1 BED RM+BATH
3 B1 10 2.5 2.5 2/1/1 1 20/50/100 210
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
40A,4P
6 B2 20 4.0 4.0 BED RM 3 200 600
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1,000
2
8 Y3 SPACE
9 B3 20 4.0 4.0 12U CABINET 1 200 200
40A,4P 10 R4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
40A TPN ISOL

30mA ELCB- 11 Y4 SPACE


3 12 B4 20 4.0 4.0 BATH WH 1 1200 1,200
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 20 4.0 4.0 PANTRY FCU 1 330 330
ELCB-5 18 B6 SPACE

SUB TOTAL 3,050 2,610 3,410


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F505 2BHK

MCB CCT ECC Load Per Circuit


RTG Wire Wire WATT
IN Size Size
Amps mm2 mm2 REMARKS
CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
1 R1 10 2.5 2.5 PANTRY 1 1 100 200

40A,4P 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 5/2 20/100 300


100mA 3 B1 10 2.5 2.5 BED RM1+BATH 2/1/1 1 20/50/100 210
ELCB-1 4 R2 10 2.5 2.5 BED RM2+BATH+BALCONY 4/1/1 1 20/50/100 250
5 Y2 SPACE
6 B2 SPACE
7 R3 20 4.0 4.0 PANTRY 2 200 400
8 Y3 20 4.0 4.0 LIV/DIN 2/1 200/400 800
40A,4P
9 B3 20 4.0 4.0 BED RM1 3 200 600
30mA ELCB-
10 R4 20 4.0 4.0 BATH2 WH 1 1200 1,200
2
40A TPN ISOL

11 Y4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200


12 B4 20 4.0 4.0 BATH1 WH 1 1200 1,200
40A,4P 13 R5 20 4.0 4.0 BED RM2 3 200 600
30mA ELCB- 14 Y5 20 4.0 4.0 LAUNDRY 1 1000 1,000
3 15 B5 20 4.0 4.0 12U CABINET 1 200 200
16 R6 SPACE
17 Y6 SPACE
40A,4P
18 B6 20 4.0 4.0 BED RM2 BATH FCU 1 330 330
100mA
19 R7 1200
ELCB-4
20 Y7 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
21 B7 1200

SUB TOTAL 3,850 3,500 3,740


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
TOTAL 11.09
PVC/CU GY ECC
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(507,509 & 510)1BHK
MCB CCT ECC Load Per Circuit
RTG Wire Wire WATT
IN Size Size
CONNECTED LOADS/POINTS REMARKS
Amps mm2 mm2
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
100mA 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
4 R2 20 4.0 4.0 BED RM 3 200 600
5 Y2 20 4.0 4.0 PANTRY 2 200 400
40A,4P
6 B2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 12U CABINET 1 200 200
2
8 Y3 20 4.0 4.0 LAUNDRY 1 1000 1,000
9 B3 SPACE
40A,4P 10 R4 20 4.0 4.0 BATH WH 1 1200 1,200
30mA ELCB- 11 PANTRY (FRIDGE)
40A TPN ISOL

Y4 20 4.0 4.0 1 200 200


3 12 B4 SPACE
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 330 330

SUB TOTAL 3,410 3,050 2,610


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.07
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(508)1BHK
MCB CCT ECC Load Per Circuit
RTG Wire Wire
IN Size Size WATT
Amps mm2 CONNECTED LOADS/POINTS REMARKS
mm2
RATING OF RATING OF SL CIR LTG EX. 13A SH W/H W/M KIT CCU FCU CU
INCOMER ELCB NO NO ROOM/ AREA Fan S/O S/O HD WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
100mA 2 Y1 10 2.5 2.5 PANTRY+TOILET 1/1 1 20/50/100 250
ELCB-1 3 B1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 4/2 20/100 280
4 R2 20 4.0 4.0 BED RM 3 200 600
5 Y2 20 4.0 4.0 PANTRY 2 200 400
40A,4P
6 B2 20 4.0 4.0 PASSAGE+LIV/DIN 2/1 200/400 800
30mA ELCB-
7 R3 20 4.0 4.0 12U CABINET 1 200 200
2
8 Y3 20 4.0 4.0 LAUNDRY 1 1000 1,000
9 B3 SPACE
40A,4P 10 R4 20 4.0 4.0 BATH WH 1 1200 1,200
30mA ELCB- 11 PANTRY (FRIDGE)
40A TPN ISOL

Y4 20 4.0 4.0 1 200 200


3 12 B4 SPACE
40A,4P 13 R5 1900
100mA 14 Y5 20 4.0 4.0 CU 1 5700 1900 UVR+ART+CONT
ELCB-4 15 B5 1900
40A,4P 16 R6 SPACE
100mA 17 Y6 SPACE
ELCB-5 18 B6 20 4.0 4.0 PANTRY FCU 1 400 400

SUB TOTAL 4,110 3,750 3,380


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 11.24
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F(512 & 513)1BHK

MCB CCT ECC Load Per Circuit WATT


RTG Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR IN Size Size
ROOM/ AREA REMARKS
INCOMER ELCB NO NO Amps mm2 mm2
LTG EX. 13A SH W/H W/M KIT CCU FCU CU
Fan S/O S/O HD WATT UNIT R Y B
40A,4P 1 R1 10 2.5 2.5 PANTRY 1 1 100 200
100mA 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2 20/100 260
ELCB-1 3 B1 10 2.5 2.5 BED RM+BATH 2/1/1 1 20/50/100 210
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 LIV/DIN 2/1 200/400 800
40A,4P
6 B2 20 4.0 4.0 BED RM 3 200 600
30mA ELCB-
7 R3 20 4.0 4.0 LAUNDRY 1 1000 1,000
2
8 Y3 SPACE
9 B3 20 4.0 4.0 12U CABINET 1 200 200
40A,4P 10 R4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200
30mA ELCB- SPACE
40A TPN ISOL

11 Y4
3 12 B4 20 4.0 4.0 BATH WH 1 1200 1,200
40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4 15 B5 1200
40A,4P 16 R6 SPACE
100mA 17 Y6 20 4.0 4.0 PANTRY FCU 1 330 330
ELCB-5 18 B6 SPACE

SUB TOTAL 3,000 2,590 3,410


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.00
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: APARTMENT ENTRANCE
DB REF: DB-F514 1BHK

MCB CCT ECC Load Per Circuit WATT


RTG Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR
IN Size Size ROOM/ AREA REMARKS
INCOMER ELCB NO NO
Amps mm2 mm2 LTG EX. 13A SH W/H W/M KIT CCU FCU CU
Fan S/O S/O HD WATT UNIT R Y B

40A,4P 1 R1 10 2.5 2.5 PANTRY 2 1 100 300


100mA 2 Y1 10 2.5 2.5 PASSAGE+LIV/DIN+BALCONY 3/2 20/100 260
ELCB-1 BED RM+BATH
3 B1 10 2.5 2.5 2/1/1 1 20/50/100 210
4 R2 20 4.0 4.0 PANTRY 2 200 400
5 Y2 20 4.0 4.0 LIV/DIN 2/1 200/400 800
40A,4P 6 B2 20 4.0 4.0 BED RM 3 200 600
30mA ELCB-
2 7 R3 20 4.0 4.0 LAUNDRY 1 1000 1,000
8 Y3 SPACE
9 B3 20 4.0 4.0 12U CABINET 1 200 200

40A,4P 10 R4 20 4.0 4.0 PANTRY (FRIDGE) 1 200 200


30mA ELCB- 11 Y4 SPACE
40A TPN ISOL

3 BATH WH
12 B4 20 4.0 4.0 1 1200 1,200

40A,4P 13 R5 1200
100mA 14 Y5 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4
15 B5 1200

40A,4P 16 R6 SPACE
100mA 17 Y6 20 4.0 4.0 PANTRY FCU 1 330
ELCB-5 SPACE
18 B6 330

SUB TOTAL 3,100 2,260 3,740


CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 9.10
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GYM ENTRANCE
DB REF: DB-GYM
MCB CCT ECC Load Per Circuit WATT
RTG Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR
IN Size Size ROOM/ AREA REMARKS
INCOMER ELCB NO NO
Amps mm2 mm2 LTG EX. 13A SH W/H W/M KIT ISOL FCU CU
Fan S/O S/O HD WATT UNIT R Y B
1 R1 10 2.5 2.5 GYM+BALCONY 2/8 50/100 900
2 Y1 10 2.5 2.5 FEM CHANGING+SHOWER 13 50 650
3 B1 10 2.5 2.5 GYM 8 100 800
40A,4P
100mA 4 R2 SPACE
ELCB-1
M CHANGING+SHOWER+PLANT
5 Y2 10 2.5 2.5 16 50 800
RM

6 B2 SPACE
7 R3 20 4.0 4.0 GYM 3 400 1,200 RING
8 Y3 20 4.0 4.0 MALE+FEMALE CHANGING 2 200 400
40A,4P 9 B3 SPACE
30mA ELCB-
2 10 R4 20 4.0 4.0 MALE SHWR WH 1 1200 1,200
63A TPN ISOL

11 Y4 20 4.0 4.0 FEMALE SHWR WH 1 1200 1,200


12 B4 20 4.0 4.0 GYM 3 400 1,200 RING

40A,4P 13 R5 SPACE
100mA 14 Y5 20 4.0 4.0 GYM FCU (5F-15) 1 330 330
ELCB-3 GYM FCU (5F-16)
15 B5 20 4.0 4.0 1 330 330

40A,4P 16 R6 1200
100mA 17 Y6 20 4.0 4.0 CU 1 3600 1200 UVR+ART+CONT
ELCB-4
18 B6 1200
19 R7 1,350
32 4.0 1.0
20 Y7 SAUNA-MALE 1 4050 1,350 TPN ISOL
A TP X 6.0 X 6.0
40A,4P 21 B7 1,350
100mA
ELCB-5 22 R8 1,350
32 4.0 1.0
23 Y8 SAUNA-FEMALE 1 4050 1,350 TPN ISOL
A TP X 6.0 X 6.0
24 B8 1,350
SUB TOTAL 7,200 7,280 6,230
CABLE SIZE: 4C,10 mm² XLPE/SWA/PVC/CU + 1C, 10mm²
PVC/CU GY ECC TOTAL 20.71
PROJECT: B+G+5 RESIDENTIAL BUILDING DETAILS OF CONNECTED LOAD / MAX. DEMAND AREA: JUMEIRAH VILLAGE CIRCLE, DUBAI
CLIENT: SARHANK KADER PLOT NO. JVC14VMRA002
FED FROM: SMDB-5F CONSULTANT: ARIF & BINTOAK CONSULTING ENGINEERS LOCATION: GYM ENTRANCE
DB REF: DB-GYM
MCB CCT ECC Load Per Circuit WATT
RTG Wire Wire CONNECTED LOADS/POINTS
RATING OF RATING OF SL CIR
IN Size Size ROOM/ AREA REMARKS
INCOMER ELCB NO NO
Amps mm2 mm2 LTG EX. 13A SH W/H W/M KIT ISOL FCU CU
Fan S/O S/O HD WATT UNIT R Y B

40A,4P 25 R9 1200
100mA 26 Y9 20 4.0 4.0 GYM CU (5F-15) 1 3600 1200 UVR+ART+CONT
ELCB-6
27 B9 1200
63A TPN ISOL

SUB TOTAL 8,400 8,480 7,430


CABLE SIZE: 4C,16 mm² XLPE/SWA/PVC/CU + 1C, 16mm²
TOTAL 24.31
PVC/CU GY ECC