High Impedance Busbar Protection Principles and Calculations
High Impedance Busbar Protection Principles and Calculations
The equivalent circuit of this busbar protection scheme would look like the
following:
That is far too complicated for our purposes. We can combine 52-2 CT, 52-3 CT,
and 52-4 into one CT to simplify the circuit to look like the following:
But we’re going to apply an external fault through two feeders to make it easier
to understand.
Any current flowing through the 52-1 CT (52-1CT IP1) is shown on the left hand
side of our two-feeder equivalent circuit below. The primary current creates a
magnetic field (Ie1, Ze1) that usually uses a small amount of current to inject the
secondary current (IS1) into the CT secondary circuit.
The secondary winding is made from a conductor that has resistance and is
coiled around a core to create inductance. That impedance is shown on the
drawing as ZCT1. The external conductors connecting the CT to the rest of the
circuit also have an impedance that is represented by ZL1.
The 52-2 CT has the same characteristics as the 52-1 CT, which is represented
on the right-hand side of the equivalent circuit. The CTs are connected in parallel
with all polarity marks connected to the same point so that external faults
theoretically cancel each other out, and internal faults combine to create larger
currents during a fault for shorter trip times.
The DC Offset that commonly occurs during faults (You can get more info in
the What is DC Offset? Ask Chris post)
Residual magnetism in the CT (Remanence) from previous faults or improper
testing
A normal CT has a CT ratio (1200:5 in our example), which defines the turns-ratio
(240:1 in our example). 83.33 should be exported When 20,000A flows through
the 240 turns in a properly functioning CT, but:
83.295A is injected out of the CT secondary terminals. (The actual CT ratio may
be slightly higher than the reported 240:1 to compensate for the excitation current
losses.)
When a CT saturates, the magnetic field requires more current than normal to
maintain the current transformation, which means that there is less current
injected into the CT secondary circuit. We’re showing the worst case scenario in
our example where ALL of the primary current is used in the magnetic field, and
zero amps is injected into the CT secondaries.
CT Ratings
A protection class CT is usually defined by its ratio, accuracy, construction, and
burden. We’ve already discussed the CT ratio (1200:5 in our example). If you
look back to the single line drawing, you’ll see that there was another designation
beside the CTs (C200).
The accuracy class in percent (10% if no number appears in front of the letter)
How the CT was constructed using a letter (C = Minimum leakage flux and CT
performance can be calculated)
How can a voltage define the burden, you might ask? All standard protection
class CT ratings are valid between 1 to 20x nominal current. If our CT’s have 5A
nominal secondary currents, they are allowed to be +/-10% accurate between 5
and 100A secondary. If the maximum burden is 200V, we can apply Ohm’s Law
to determine that the maximum impedance connected to the CT secondaries is
2.0Ω (200V / 100A). That’s the standard calculation that ALL CT testers should
know and apply when they are performing their CT tests. Did you?
All protection class CTs also have a saturation curve like the graph below. The
200 in our rating means that if the voltage across the CT’s magnetic field is
greater than 200V, the CT is no longer guaranteed to operate within its 10% error.
200V is greater than 166.66V (our minimum allowable CT saturation voltage), so
the CTs in our example are appropriate for our application.
Start by drawing a horizontal line from 83.33V until you reach the 1200:5 curve.
Determine the excitation current using the log scale on the x-axis (0.035A).
Let’s imagine that we set the relay to 50V. We can calculate how much differential
current will cause the relay to trip under normal conditions using Ohm’s Law. The
87Z is 2000Ω in our example with a 50V setting. That means that 0.025A (50V /
2000Ω) of differential current will cause the relay to trip. This setting might be OK
with class X CTs with specific operating characteristics, but we will probably get
a false trip with normal class C CTs, especially if we have different vintages of
CTs in our high impedance busbar differential circuit.
Most design engineers add a safety factor starting at 1.5x the minimum setting to
account for potential increases in fault current. We will increase the setting by a
factor of two and then round up to 100V. This means that the differential current
caused by CT mismatch (0.05A or 100V/2000Ω) must be twice our previous
setting, or higher, to cause a mis-operation during normal conditions or through-
faults.
We have 20,000A flowing into the 52-1 CT which should equal 83.333A flowing
out of its secondary terminals. However, the CT needs excitation current to create
secondary current. If we use our previously calculated 0.035A for this scenario
(that amount would not technically apply here, but we need to pick something and
I don’t want to do more math for such a small amount of current), 83.295A should
flow out of the CT secondaries.
Since the 52-2 CT has zero amps flowing in the primary windings, zero amps
should flow out of the secondaries. Without a magnetic field however, the 52-2
CT’s secondary winding is just a bunch of coiled wire with a low impedance. The
52-1 CT secondary current will want to flow through the low impedance in the 52-
2 CT secondaries, but once a small amount of current (0.044A from our previous
example) starts flowing in the secondary circuit, a magnetic field will be created
and the CT will try to maintain its turns-ratio. Zero amps of the primary should
equal zero amps on the secondary minus the excitation current. Once the
magnetic field is built, the 52-2 CT secondaries will become an open circuit (like
it does when you perform your saturation and ratio tests) and the remaining
current will flow through the 87Z circuit because it will now have a lower
impedance.
Using Ohm’s Law, 83.251A through 2000Ω should create 166,502V. The MOV
will protect the secondary circuits from damage by limiting the possible voltage to
a number much smaller than 166,502V, but the secondary voltage could rise to
the system voltage without the MOV. Either way, it is extremely unlikely that the
voltage will reach those heights because the CT should start saturating at 200V.
The CT is guaranteed to saturate during an internal fault and will produce a
waveform that looks like this:
Our relay better be able to operate when this waveform appears; so it is often
beneficial to use a single-purpose relay for a high impedance busbar differential
relay scheme to minimize the trip time. Some digital relays need extra time to
measure, apply filters, and analyze the waveform before they can operate, which
may mean that the fault may stay on the system longer than necessary. The
longer a fault stays on the system, the greater potential for system de-
stabilization, which could cause a larger system outage than necessary.
The voltage during an internal fault should always be larger than our setting and
the relay should trip in the shortest time possible.
Conclusion
The dirty little secret about all forms of differential protection is that we know the
relay will trip for all internal faults. When we’re designing and testing differential
schemes, we’re primarily concerned with making sure the relay will NOT trip
during external faults. Did you notice that all of the important calculations above
occurred during external fault scenarios? Have you noticed that most differential
tests try to find the point where the relay will operate during an external fault
(currents 180° apart), instead of applying single source or multiple source fault in
the same direction?
I hope this article helped you better understand high impedance differential
schemes. If you liked it, please share it to help us get noticed, which helps us
continue to produce free content like this.