ACS800 04 Technical Manual 0 55kW To 160kW
ACS800 04 Technical Manual 0 55kW To 160kW
ACS800 04 Technical Manual 0 55kW To 160kW
Hardware Manual
ACS800-04 Drive Modules (0.55 to 160 kW)
ACS800-U4 Drive Modules (0.75 to 200 HP)
ACS800 Single Drive Manuals
• Safety instructions
• Electrical installation planning
• Mechanical and electrical installation
• Motor control and I/O board (RMIO)
• Maintenance
• Technical data
• Dimensional drawings
• Resistor braking
Hardware Manual
3AFE68372984 Rev C EN
EFFECTIVE: 16.2.2007
Safety instructions
Hot surface warning warns of hot surfaces which can cause physical
injury.
Safety instructions
6
WARNING! Ignoring the following instructions can cause physical injury or death, or
damage to the equipment:
• Only qualified electricians are allowed to install and maintain the drive.
• Never work on the drive, the motor cable or the motor when main power is
applied. After switching off the input power, always wait for 5 min to let the
intermediate circuit capacitors discharge before you start working on the drive,
the motor or the motor cable.
Always ensure by measuring with a multimeter (impedance at least 1 Mohm)
that:
1. voltage between drive input phases U1, V1 and W1 and the frame is close to
0V
2. voltage between terminals UDC+ and UDC- and the frame is close to 0 V.
• Do not work on the control cables when power is applied to the drive or to the
external control circuits. Externally supplied control circuits may cause
dangerous voltages inside the drive even when the main power on the drive is
switched off.
• Do not make any insulation or voltage withstand tests on the drive or drive
modules.
• When reconnecting the motor cable, always check that the phase order is
correct.
Note:
• The motor cable terminals on the drive are at a dangerously high voltage when
the input power is on, regardless of whether the motor is running or not.
• The Prevention of Unexpected Start function does not remove the voltage from
the main and auxiliary circuits.
• At installation sites above 2000 m (6562 ft), the terminals of the RMIO board
and optional modules attached to the board do not fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 50178.
Safety instructions
7
Grounding
These instructions are intended for all who are responsible for the grounding of the
drive.
WARNING! Ignoring the following instructions can cause physical injury, death,
increased electromagnetic interference and equipment malfunction:
• Ground the drive, motor and adjoining equipment to ensure personnel safety in
all circumstances, and to reduce electromagnetic emission and interference.
• Do not install a drive with EMC filter option +E202 or +E200 on an ungrounded
power system or a high resistance-grounded (over 30 ohms) power system.
Note:
• Power cable shields are suitable for equipment grounding conductors only
when adequately sized to meet safety regulations.
Safety instructions
8
WARNING! Ignoring the following instructions can cause physical injury or death,
or damage to the equipment:
• The drive is heavy. Do not lift it alone. Place the unit only on its back.
• Make sure that dust from borings and grindings does not enter the drive when
installing. Electrically conductive dust inside the unit may cause damage or
malfunctioning.
WARNING! Ignoring the following instructions can cause damage to the printed
circuit boards:
• Handle the fibre optic cables with care. When unplugging optic cables, always
grab the connector, not the cable itself. Do not touch the ends of the fibres with
bare hands as the fibre is extremely sensitive to dirt. The minimum allowed
bend radius is 35 mm (1.4 in.).
Safety instructions
9
Operation
These warnings are intended for all who plan the operation of the drive or operate
the drive.
WARNING! Ignoring the following instructions can cause physical injury or death,
or damage to the equipment:
• Before adjusting the drive and putting it into service, make sure that the motor
and all driven equipment are suitable for operation throughout the speed range
provided by the drive. The drive can be adjusted to operate the motor at
speeds above and below the speed provided by connecting the motor directly
to the power line.
• Do not control the motor with the disconnecting device (means); instead, use
the control panel keys and , or commands via the I/O board of the drive.
The maximum allowed number of charging cycles of the DC capacitors (i.e.
power-ups by applying power) is five in ten minutes.
Note:
• If an external source for start command is selected and it is ON, the drive (with
Standard / Motion Control Application Program) will start immediately after fault
reset unless the drive is configured for 3-wire (a pulse) start/stop.
• When the control location is not set to Local (L not shown in the status row of
the display), the stop key on the control panel will not stop the drive. To stop
the drive using the control panel, press the LOC/REM key and then the stop
key .
Safety instructions
10
WARNING! Do not work on the drive when the permanent magnet motor is rotating.
Also, when the supply power is switched off and the inverter is stopped, a rotating
permanent magnet motor feeds power to the intermediate circuit of the drive and the
supply connections become live.
Before installation and maintenance work on the drive:
• Stop the motor.
• Ensure that the motor cannot rotate during work. Prevent the start-up of any
drives in the same mechanical group by opening the “prevention of unexpected
start” switch and padlocking it. Make sure that no other system, like hydraulic
crawling drives, are able to rotate the motor directly or through any mechanical
connection like felt, nip, rope, etc.
• Ensure that there is no voltage on the drive power terminals:
Alternative 1) Disconnect the motor from the drive with a safety switch or by other
means. Measure that there is no voltage present on the drive input or output
terminals (U1, V1, W1, U2, V2, W2, UDC+, UDC-).
Alternative 2) Measure that there is no voltage present on the drive input or output
terminals (U1, V1, W1, U2, V2, W2, UDC+, UDC-). Ground the drive output
terminals temporarily by connecting them together as well as to the PE.
Alternative 3) If possible, both of the above.
WARNING! Do not run the motor over the rated speed. Motor overspeed leads to
overvoltage which may damage or explode the capacitors in the intermediate circuit
of the drive.
Controlling a permanent magnet motor is only allowed using the ACS800 Permanent
Magnet Synchronous Motor Drive Application Program, or other application
programs in scalar control mode.
Safety instructions
11
Table of contents
Safety instructions
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Use of warnings and notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mechanical installation and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Printed circuit boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fibre optic cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Permanent magnet motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Start-up and operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table of contents
ACS800-04/U4
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Type code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Main circuit and control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Printed circuit boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Motor control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table of contents
12
Mechanical installation
Unpacking the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Before installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Requirements for the installation site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Flange mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Table of contents
13
Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Checking the insulation of the assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Input cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Motor and motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
IT (ungrounded) systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Power cable connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Connecting the power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Grounding the motor cable shield at the motor end . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Frame sizes R2 to R4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Frame size R5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Frame size R6: Cable lug installation [16 to 70 mm2 (6 to 2/0 AWG) cables] . . . . . . . 64
Power cable protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Frame size R5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Frame size R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Warning sticker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Connecting the control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
360 degrees grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
When the outer surface of the shield is covered with non-conductive material . . . . . . 69
Connecting the shield wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Cabling of I/O and fieldbus modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Pulse encoder module cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Installation of optional modules and PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Fibre optic link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
External +24 V power supply for the RMIO board via terminal X34 . . . . . . . . . . . . . . . . . . . . . . . . 71
Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Connecting +24 V external power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Prevention of Unexpected Start, AGPS board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Table of contents
14
Installation checklist
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
Maintenance
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
Heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
Fan replacement (R2, R3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
Fan replacement (R4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .87
Fan replacement (R5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
Fan replacement (R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
Additional fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
Replacement (R2, R3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
Replacement (R4, R5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
Replacement (R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
Reforming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
Technical data
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91
IEC data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
Temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
Table of contents
15
Altitude derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Cooling characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Cooling requirements for flange mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Mains cable fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
gG fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Dimensions, weights and noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
NEMA data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Input cable fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Cable Entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Input power connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Motor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Degrees of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
AGPS-11C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Applicable standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Compliance with the EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Compliance with the EN 61800-3 (2004) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
First environment (drive of category C2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Second environment (drive of category C3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Second environment (drive of category C4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Machinery Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
“C-tick” marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Compliance with IEC 61800-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
First environment (drive of category C2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Second environment (drive of category C3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Second environment (drive of category C4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Marine type approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
UL/CSA markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
UL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Equipment warranty and liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Product protection in the US . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Dimensional drawings
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Frame size R2 (with optional control panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Frame size R3 (with optional control panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Frame size R4 (with optional control panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Table of contents
16
Resistor braking
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
Availability of brake choppers and resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
How to select the correct drive/chopper/resistor combination . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
Optional brake chopper and resistor(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130
Resistor installation and wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .132
Protection of frame sizes R2 to R5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
Protection of frame size R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134
Brake circuit commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134
Table of contents
17
Compatibility
The manual is compatible with ACS800-04/U4 (frame sizes R2...R6).
Intended audience
This manual is intended for people who plan the installation, install, commission, use
and service the drive. Read the manual before working on the drive. The reader is
expected to know the fundamentals of electricity, wiring, electrical components and
electrical schematic symbols.
This manual is written for readers worldwide. Both SI and imperial units are shown.
Special US instructions for installations within the United States that must be
installed per the National Electrical Code and local codes are marked with (US).
Contents
The chapters of this manual are briefly described below.
Safety instructions give safety instructions for the installation, commissioning,
operation and maintenance of the drive.
About this manual lists the steps in checking the delivery and installing and
commissioning the drive and refers to chapters/sections in this manual and other
manuals for particular tasks.
ACS800-04/U4 describes the drive.
Planning the cabinet assembly guides in planning the installation of a drive module
into a user-defined cabinet.
Mechanical installation instructs how to place and mount the drive.
Planning the electrical installation instructs on the motor and cable selection, the
protections and the cable routing.
Electrical installation shows how to wire the drive.
Motor control and I/O board (RMIO) shows the external control connections to the
I/O board.
Installation checklist contains a list for checking the mechanical and electrical
installation of the drive.
Maintenance contains preventive maintenance instructions.
Technical data contains the technical specifications of the drive, e.g. the ratings,
sizes and technical requirements, provisions for fulfilling the requirements for CE
and other markings and warranty policy.
Dimensional drawings contains the dimensional drawings of the drive.
Resistor braking describes how to select, protect and wire brake choppers and
resistors. The chapter also contains the technical data.
Task See
Identify the frame size of your drive: R2, R3, R4, R5 Technical data: IEC data or NEMA data
or R6.
Unpack and check the units. Mechanical installation: Unpacking the unit
Check that all necessary optional modules and If the converter has been non-operational for
equipment are present and correct. more than one year, the converter DC link
Only intact units may be started up. capacitors need to be reformed. Ask ABB for
instructions.
Check the insulation of the motor and the motor Electrical installation: Checking the insulation of
cable. the assembly
Task See
Connect the power cables. Electrical installation, Motor control and I/O
Connect the control and the auxiliary control cables. board (RMIO), Resistor braking (optional) and
the optional module manual delivered with the
module.
Operating of the drive: start, stop, speed control etc. Appropriate Firmware Manual
Product training
For information on ABB product training, navigate to www.abb.com/drives and select
Drives – Training courses on the right pane.
Frame (size) Size of the frame into which the drive module is assembled. Several
supply modules with different nominal powers may have the same frame
size. The term refers to modules that have a similar mechanical
construction.
To determine the frame size of a drive module, refer to the rating tables in
chapter Technical data.
I/O Input/Output
AGPS Gate driver Power Supply board. An optional board used to implement the
Prevention of Unexpected Start function.
RMIO Motor control and I/O board. The external I/O control signals are
connected to RMIO.
ACS800-04/U4
Layout
The ACS800-04/U4 (frame sizes R2 to R6) is an IP20 drive module for controlling
AC motors. It is to be installed into a cabinet by the customer with wall fastening.
Option slots
Power cable
terminal
Heatsink
PE
Location of the components vary depending on the frame size.
ACS800-04/U4
24
Type code
The type code contains information on the specifications and configuration of the
drive. The first digits from left express the basic configuration (e.g. ACS800-04-
0016-3). The optional selections are given thereafter, separated by + signs (e.g.
+E202). The main selections are described below. Not all selections are available for
all types. For more information, refer to ACS800 Ordering Information
[3AFE64556568 (English)], available on request.
Selection Alternatives
Product series ACS800 product series
Type 04 Drive module. When no options are selected: IP20, no control panel, no
EMC filter, Standard Application Program, brake chopper in frame sizes
R2, R3, and R4 (only 690 V), boards without coating, one set of manuals.
U4 Drive module (USA). When no options are selected: UL open type, no
control panel, no EMC filter, Standard Application Program, brake
chopper in frame sizes R2, R3, and R4 (only 690 V), boards without
coating, one set of manuals.
Size See Technical data: IEC data or NEMA data.
Voltage range 2 208/220/230/240 VAC
(nominal rating in bold) 3 380/400/415 VAC
5 380/400/415/440/460/480/500 VAC
7 525/575/600/690 VAC
+ options
Control panel J400 Control panel CDP312R assembled on the drive module
J414 Control panel holder for frame sizes R2, R3 and R4 (not to be used with
option J400)
Construction C132 Marine drive (coated boards included)
C135 Flange mounting. Flange mounting plate assembled. IP55 for heat sink
side and IP20 for drive front side.
Filter E200 EMC/RFI filter for second environment TN (grounded) system, drive
category C3
E202 EMC/RFI filter for first environment TN (grounded) system, drive category
C2. (Not available for 690 V units.)
E210 EMC/RFI filter for second environment TN/IT (grounded/ungrounded)
system, drive category C3 (frame size R6 only)
Resistor braking D150 Brake chopper. Included as standard in frame sizes R2, R3 and R4 (only
690 V).
Safety Q950 Prevention of Unexpected Start: AGPS board and 3 m connection wire.
Fieldbus K... Refer to ACS800 Ordering Information [3AFE64556568 (English)].
I/O L...
Application program N...
Manual language R...
Specialities P901 Coated boards
P904 Extended warranty
ACS800-04/U4
25
Diagram
This diagram shows the control interfaces and the main circuit of the drive. Location
of terminals vary depending on the drive frame size.
Drive
= ~
Input power
~ = Output power
R- UDC+ UDC-
R+
ACS800-04/U4
26
Operation
This table describes the operation of the main circuit in short.
Component Description
Capacitor bank Energy storage which stabilizes the intermediate circuit DC voltage.
IGBT inverter Converts the DC voltage to AC voltage and vice versa. The motor
operation is controlled by switching the IGBTs.
Motor control
The motor control is based on the Direct Torque Control (DTC) method. Two phase
currents and DC link voltage are measured and used for the control. The third phase
current is measured for earth fault protection.
ACS800-04/U4
27
Note: The installation examples in this manual are provided only to help the installer
in designing the installation. The installation must always be designed and made
according to applicable local laws and regulations. ABB does not assume any
liability whatsoever for any installation which breaches the local laws and/or other
regulations.
Cabinet construction
The cabinet frame must be sturdy enough to carry the weight of the drive
components, control circuitry and other equipment installed in it.
The cabinet must protect the drive module against contact and meet the
requirements for dust and humidity (see chapter Technical data).
Note: Ensure that the modules are properly grounded through their fastening points
to the installation base.
200 [7.9]
300 [12]
Air outlet
Air inlet
Arrange the cooling air flow through the modules so that the requirements given in
chapter Technical data are met:
• cooling air flow
Note: The values in Technical data apply to continuous nominal load. If the load is cyclic or less
than nominal, less cooling air is required.
In IP54 (UL type 12) cabinets, thick filter mats are used to prevent water splashes
from entering the cabinet. This entails the installation of additional cooling
equipment, such as a hot air exhaust fan.
The installation site must be sufficiently ventilated.
Main
Cabinet (side view) air Cabinet (side view)
flow
out
HOT
AREA Air flow out
Main air flow out HOT AREA
Air baffle
Air baffle plate
plates
Main
air
flow
in
Vertical mounting
AC switch fuse
AC fuse bases
AC fuses
Airflow guides
Cool area
Mounting
plates
Modules
Cabinet heaters
Use a cabinet heater if there is a risk of condensation in the cabinet. Although the
primary function of the heater is to keep the air dry, it may also be required for
heating at low temperatures. When placing the heater, follow the instructions
provided by its manufacturer.
Control panel
Cabinet door
4...8 mm
(0.16...0.31 in.)
Control panel footprint
Tightening torque:
1 Nm (0.74 lbf ft) 10 mm (0.39 in.)
EMC requirements
Generally, the fewer and smaller the holes in the cabinet, the better the interference
attenuation. The maximum recommended diameter of a hole in galvanic metal
contact in the covering cabinet structure is 100 mm. Special attention must be paid
to the cooling air inlet and outlet gratings.
The best galvanic connection between the steel panels is achieved by welding them
together as no holes are necessary. If welding is not possible, the seams between
the panels are recommended to be left unpainted and equipped with special
conductive EMC strips to provide adequate galvanic connection. Usually, reliable
strips are made of flexible silicon mass covered with a metal mesh. The non-
tightened touch-contact of the metal surfaces is not sufficient, so a conductive
gasket between the surfaces is required. The maximum recommended distance
between assembly screws is 100 mm.
Sufficient high-frequency grounding network must be constructed in the cabinet to
avoid voltage differences and forming of high-impedance radiator structures. A good
high-frequency grounding is made with short flat copper braids for low inductance.
One-point high-frequency grounding cannot be used due to the long distances inside
the cabinet.
First environment EMC compliance *) of the drive requires 360° high frequency
grounding of the motor cable shields at their entries. The grounding can be
implemented by a knitted wire mesh screening as shown below.
Lead-through plate
Cable
*) First environment EMC compliance is defined in section CE marking in chapter Technical data.
360° high frequency grounding of the control cable shields is recommended at their
entries. The shields can be grounded by means of conductive shielding cushions
pressed against the cable shield from both directions:
Cable
Cable grommet
Mechanical installation
Tear
Mechanical installation
36
Delivery check
Check that there are no signs of damage. Before attempting installation and
operation, check the information on the type designation label of the drive to verify
that the unit is of the correct type. The label includes IEC rating, C-UL US, CSA,
C-tick and CE markings, a type code and a serial number, which allow individual
recognition of each unit. The first digit of the serial number refers to the
manufacturing plant. The next four digits refer to the unit’s manufacturing year and
week, respectively. The remaining digits complete the serial number so that there
are no two units with the same serial number.
The type designation label is attached to the heat sink and the serial number label to
the upper part of the back plate of the unit.
Before installation
Check the installation site according to the requirements below. See Dimensional
drawings for frame details.
Mechanical installation
37
Installation procedure
1. Mark the locations for the four holes. The mounting points are shown in
Dimensional drawings. With frame sizes R2...R5, use the mounting template cut
from the package.
2. Fix the screws or bolts to the marked locations.
3. Position the drive onto the screws on the cabinet wall. Note: Lift the drive by its
chassis (R6: by its lifting holes).
4. Tighten the screws in the cabinet wall securely.
Mechanical installation
38
Flange mounting
The flange mounting plate is factory assembled on the drive. With flange mounting,
the degree of protection is IP55 for the heat sink side and IP20 for the drive front
side. The drive front side must always be housed in a cabinet.
Mechanical installation
39
R6 flange mounting
1
2 Lifting lug
Mounting plate
3
Washer
Screw
Mechanical installation
40
Mechanical installation
41
Example: When the supply voltage is 440 V and the drive is operating in motor
mode only, the maximum peak voltage in the motor terminals can be
approximated as follows: 440 V · 1.35 · 2 = 1190 V. Check that the motor
insulation system withstands this voltage.
Requirements table
The following table shows how to select the motor insulation system and when an optional ABB du/dt
filter, insulated N-end (non-driven end) motor bearings and ABB common mode filters are required. The
motor manufacturer should be consulted regarding the construction of the motor insulation and
additional requirements for explosion-safe (Ex) motors. Failure of the motor to fulfil the following
requirements or improper installation may shorten motor life or damage the motor bearings and voids
the warranty.
Abbreviation Definition
UN nominal voltage of the supply network
ÛLL peak line-to-line voltage at motor terminals which the motor insulation must withstand
PN motor nominal power
du/dt du/dt filter at the output of the drive +E205
CMF common mode filter +E208
N N-end bearing: insulated motor non-driven end bearing
n.a. Motors of this power range are not available as standard units. Consult the motor manufacturer.
voltage (AC line Motor ABB du/dt filter, insulated N-end bearing and ABB common
voltage) insulation mode filter
system PN < 55 kW 55 kW < PN < PN > 200 kW
200 kW
PN < 74 HP 74 HP < PN < PN > 268 HP
268 HP
A Random- UN < 500 V Standard - +N + N + CMF
B wound M3AA, 500 V < U < 600 V Standard + du/dt + du/dt + N + du/dt + N + CMF
N
B M3AP, M3BP
or
Reinforced - +N + N + CMF
600 V < UN < 690 V Reinforced + du/dt + du/dt + N + du/dt + N + CMF
Note 7: Calculating the rise time and the peak line-to-line voltage
The peak line-to-line voltage at the motor terminals generated by the drive as well as the voltage rise
time depend on the cable length. The requirements for the motor insulation system given in the table
are “worst case” requirements covering installations with 30 metre and longer cables. The rise time can
be calculated as follows: t = 0.8 · ÛLL/(du/dt). Read ÛLL and du/dt from the diagrams below. Multiply
the values of the graph by the supply voltage (UN).With resistor braking, the ÛLL and du/dt values are
approximately 20 % higher.
3.0 5.5
ÛLL/UN 5.0
2.5 du/dt
------------- (1/μs)
4.5 UN
2.0 4.0
3.5
1.5
3.0
ÛLL/UN
1.0 2.5
du/dt
------------- (1/μs)
UN 2.0
0.5
1.5
0.0 1.0
100 200 300 100 200 300
Note 8: Sine filters protect the motor insulation system. Therefore, du/dt filter can be replaced with
a sine filter. The peak phase-to-phase voltage with the sine filter is approximately 1.5 × UN.
Note 9: Common mode filter is available as a separate kit (one box including three rings for one cable).
Supply connection
Main contactor
If used, dimension the contactor according to the nominal voltage and current of the
drive. The utilization category (IEC 947-4) is AC-1.
Fuses
See section Thermal overload and short circuit protection.
Thermal overload protection of the drive and the input and motor cables
The drive protects itself and the input and motor cables against thermal overload
when the cables are dimensioned according to the nominal current of the drive. No
additional thermal protection devices are needed.
Protection against short circuit inside the drive or in the supply cable
Protect the input cable and drive against short-circuit according to the following
guide lines.
Circuit diagram Short-circuit
protection
Protect the drive and
Distribution Drive or drive input cable with fuses
board Input cable module or a circuit breaker.
See footnotes 1) and
1) 2).
~ M
~ 3~
2)
~ M
I>
~ 3~
1) Size the fuses according to instructions given in chapter Technical data. The fuses will protect the input
cable in short-circuit situations, restrict drive damage and prevent damage to adjoining equipment in
case of a short-circuit inside the drive.
2) Circuit breakers which have been tested by ABB with the ACS800 can be used. Fuses must be used
with other circuit breakers. Contact your local ABB representative for approved breaker types and
supply network characteristics.
The protective characteristics of circuit breakers depend on the type, construction and settings of the
breakers. There are also limitations pertaining to the short-circuit capacity of the supply network.
WARNING! Due to the inherent operating principle and construction of circuit breakers,
independent of the manufacturer, hot ionized gases may escape from the breaker
enclosure in case of a short-circuit. To ensure safe use, special attention must be paid to
the installation and placement of the breakers. Follow the manufacturer’s instructions.
Note: Circuit breakers must not be used without fuses in the USA.
Note: Pressing the stop key ( ) on the control panel of the drive does not generate
an emergency stop of the motor or separate the drive from dangerous potential.
WARNING! The Prevention of Unexpected Start function does not disconnect the
voltage of the main and auxiliary circuits from the drive. Therefore maintenance work
on electrical parts of the drive or the motor can only be carried out after isolating the
drive system from the main supply.
Note: The Prevention of Unexpected Start function is not intended for stopping the
drive. If a running drive is stopped by using the Prevention of Unexpected Start
function, the drive will cut off the motor supply voltage and the motor will coast to
stop.
General rules
Dimension the mains (input power) and motor cables according to local
regulations:
• The cable must be able to carry the drive load current. See chapter Technical
data for the rated currents.
• The cable must be rated for at least 70°C maximum permissible temperature of
conductor in continuous use. For US, see section Additional US requirements.
• The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
• 600 V AC cable is accepted for up to 500 V AC. 750 V AC cable is accepted for
up to 600 V AC. For 690 V AC rated equipment, the rated voltage between the
conductors of the cable should be minimum 1 kV.
For drive frame size R5 and larger, or motors larger than 30 kW (40 HP),
symmetrical shielded motor cable must be used (figure below). A four-conductor
system can be used up to frame size R4 with up to 30 kW (40 HP) motors, but
shielded symmetrical motor cable is always recommended. The shield(s) of motor
cable(s) must have 360° bonding at both ends.
Note: When continuous metal conduit is employed, shielded cable is not required.
The conduit must have bonding at both ends as with cable shield.
A four-conductor system is allowed for input cabling, but shielded symmetrical cable
is recommended. To operate as a protective conductor, the shield conductivity must
be as follows when the protective conductor is made of the same metal as the phase
conductors:
Cross-sectional area of the phase Minimum cross-sectional area of the corresponding
conductors protective conductor
S (mm2) Sp (mm2)
S < 16 S
16 < S < 35 16
35 < S S/2
Recommended
Symmetrical shielded cable: three phase conductors A separate PE conductor is required if the conductivity
and a concentric or otherwise symmetrically of the cable shield is < 50% of the conductivity of the
constructed PE conductor, and a shield phase conductor.
PE conductor Shield
and shield Shield
PE
PE
PE Shield
A four-conductor system:
three phase conductors
and a protective
conductor.
Not allowed for motor cables Not allowed for motor cables with phase
conductor cross section larger than 10 mm2
[motors > 30 kW (40 HP)].
Cable core
Additional US requirements
Type MC continuous corrugated aluminium armor cable with symmetrical grounds or
shielded power cable must be used for the motor cables if metallic conduit is not
used. For the North American market, 600 V AC cable is accepted for up to
500 V AC. 1000 V AC cable is required above 500 V AC (below 600 V AC). For
drives rated over 100 amperes, the power cables must be rated for 75°C (167°F).
Conduit
Separate parts of a conduit must be coupled together, bridge the joints with a ground
conductor bonded to the conduit on each side of the joint. Bond the conduits also to
the drive enclosure and motor frame. Use separate conduits for input power, motor,
brake resistor, and control wiring. When conduit is employed, type MC continuous
corrugated aluminium armor cable or shielded cable is not required. A dedicated
ground cable is always required.
Note: Do not run motor wiring from more than one drive in the same conduit.
If there are power factor compensation capacitors in parallel with the three phase
input of the drive:
1. Do not connect a high-power capacitor to the power line while the drive is
connected. The connection will cause voltage transients that may trip or even
damage the drive.
2. If capacitor load is increased/decreased step by step when the AC drive is
connected to the power line: Ensure that the connection steps are low enough not
to cause voltage transients that would trip the drive.
3. Check that the power factor compensation unit is suitable for use in systems with
AC drives i.e. harmonic generating loads. In such systems, the compensation unit
should typically be equipped with a blocking reactor or harmonic filter.
WARNING! Never connect the supply power to the drive output terminals U2, V2
and W2. If frequent bypassing is required, employ mechanically connected switches
or contactors. Mains (line) voltage applied to the output can result in permanent
damage to the unit.
RMIO
Relay outputs
Varistor X25
1 RO1
230 V AC 2 RO1
3 RO1
RC filter X26
1 RO2
230 V AC 2 RO2
3 RO2
Diode X27
1 RO3
24 VD C 2 RO3
3 RO3
a b
A double-shielded twisted A single-shielded twisted
pair cable multipair cable
Relay cable
The cable type with braided metallic screen (e.g. ÖLFLEX by LAPPKABEL,
Germany) has been tested and approved by ABB.
WARNING! IEC 60664 requires double or reinforced insulation between live parts
and the surface of accessible parts of electrical equipment which are either non-
conductive or conductive but not connected to the protective earth.
To fulfil this requirement, the connection of a thermistor (and other similar
components) to the digital inputs of the drive can be implemented in three alternate
ways:
1. There is double or reinforced insulation between the thermistor and live parts of
the motor.
2. Circuits connected to all digital and analogue inputs of the drive are protected
against contact and insulated with basic insulation (the same voltage level as the
drive main circuit) from other low voltage circuits.
3. An external thermistor relay is used. The insulation of the relay must be rated for
the same voltage level as the main circuit of the drive. For connection, see
ACS800 Firmware Manual.
WARNING! Protect against direct contact when installing, operating and servicing
the RMIO board wiring and optional modules attached to the board. The Protective
Extra Low Voltage (PELV) requirements stated in EN 50178 are not fulfilled at
altitudes above 2000 m (6562 ft).
Motor cable
Drive
min 300 mm (12 in.)
Power cable
Control cables
230 V 230 V
24 V (120 V) 24 V (120 V)
Not allowed unless the 24 V cable is Lead 24 V and 230 V (120 V) control
insulated for 230 V (120 V) or insulated cables in separate ducts inside the
with an insulation sleeving for cabinet.
230 V (120 V).
Electrical installation
WARNING! The work described in this chapter may only be carried out by a qualified
electrician. Follow the Safety instructions on the first pages of this manual. Ignoring
the safety instructions can cause injury or death.
Make sure that the drive is disconnected from the mains (input power) during
installation. If the drive is already connected to the mains, wait for 5 min after
disconnecting mains power.
Drive
Do not make any voltage tolerance or insulation resistance tests (e.g. hi-pot or
megger) on any part of the drive as testing can damage the drive. Every drive has
been tested for insulation between the main circuit and the chassis (2500 V rms
50 Hz for 1 second) at the factory. Also, there are voltage-limiting circuits inside the
drive which cut down the testing voltage automatically.
Input cable
Check the insulation of the input cable according to local regulations before
connecting it to the drive.
Electrical installation
60
IT (ungrounded) systems
Ensure that the drive is not equipped with optional EMC filter, i.e. type code does not
include selections +E200 or +E202.
However if EMC filters exist, disconnect the EMC filter capacitors of selections
+E202 and +E200 before connecting the drive to an ungrounded system. For
detailed instructions on how to do this, please contact your local ABB distributor.
Electrical installation
61
(PE) PE (PE)
3)
V1 W1
U1
External brake
For alternatives, see
Planning the electrical
resistor (360
degrees grounding
3 ~
installation: Motor
required)
Disconnecting device
(means). L1 L2 L3
Motor cable grounding: Use a separate grounding cable (3) if the conductivity of
the cable shield is < 50% of the conductivity of the phase conductor and there is
no symmetrically constructed grounding conductor in the cable (see Planning the
electrical installation: Selecting the power cables).
360 degrees grounding is required at the cabinet entry in first environment
installations. First environment EMC compliance is defined in chapter Technical
data.
Note: If there is a symmetrically constructed grounding conductor in the motor
cable in addition to the conductive shield, connect the grounding conductor to the
grounding terminal at the drive and motor ends.
Note: Do not use an asymmetrically constructed motor cable. Connecting its
fourth conductor at the motor end increases bearing currents and causes extra
wear.
Electrical installation
62
• Connect the phase conductors of the mains cable to the U1, V1 and W1 terminals
and the phase conductors of the motor cable to the U2, V2 and W2 terminals.
Strip the conductor ends as follows to fit them inside the power cable connection
terminals.
Note: Lead the unstripped cable as close to the terminals as possible. All
unstripped parts must be protected against contact.
Frame size Stripping length
mm in.
R2, R3 10 0.39
R4, R5 16 0.63
R6 28 1.10
Conductive gaskets
or ground the cable by twisting the shield as follows: flattened width > 1/5 · length
b > 1/5 · a
b
a
Electrical installation
63
Frame sizes R2 to R4
U1 V1 W1 UDC+
R- R+ UDC- U2 V2 W2
PE
PE
Frame size R5
UDC+
PE U1 V1 W1 R- R+ UDC- U2 V2 W2 PE
Electrical installation
64
Frame size R6: Cable lug installation [16 to 70 mm2 (6 to 2/0 AWG) cables]
U1 UDC+
U1
U1 V1 W1 R- R+ UDC- U2 V2 W2 Remove the screw terminals.
Fasten the cable lugs to the
remaining bolts with M10
nuts.
PE
Electrical installation
65
Frame size R6: Cable terminal installation [95 to 185 mm2 (3/0 to 350 AWG) cables]
U1 UDC+
U1
U1 V1 W1 R- R+ UDC- U2 V2 W2
1 2
Electrical installation
66
Frame size R6
Cover the power cable terminals as follows:
1. Cut holes for the installed cables into the clear plastic shroud in cable lug
installations.
2. Press the shroud onto the terminals.
Removal of the shroud by lifting up with a screw driver from the corner:
Warning sticker
There are warning stickers in different languages inside the packing box of the drive.
Attach a warning sticker in the language of your choice onto the plastic skeleton
above the power cable terminals.
Electrical installation
67
Terminals
Location of terminals vary depending on the drive frame size.
Frame sizes R2 to R4
The control cable connection terminals are
exposed when the control panel mounting platform
is turned aside by pulling this knob. Be careful, do Detachable connection terminals (pull up)
not use excess force when pulling.
X39 for control panel cable
(control panel is an option)
Optional module 2
DDCS communication
option module 3:
RDCO
4
3
2
1
Relay outputs
Electrical installation
68
Electrical installation
69
Insulation
4
3
2
1
When the outer surface of the shield is covered with non-conductive material
• Strip the cable carefully (do not cut the grounding wire and the shield)
• Turn the shield inside out to expose the conductive surface.
• Wrap the grounding wire around the conductive surface.
• Slide a conductive clamp onto the conductive part.
• Fasten the clamp to the grounding plate with a screw as close as possible to the
terminals where the wires are about to be connected.
Electrical installation
70
Module
As short as possible
Shield
4
3
2
1
As short as
possible
Note1: If the encoder is of
1
2 unisolated type, ground the encoder
3
4 cable at the drive end only. If the
encoder is galvanically isolated
from the motor shaft and the stator
frame, ground the encoder cable
Shield
Electrical installation
71
External +24 V power supply for the RMIO board via terminal X34
This section describes how to connect an external +24 V power supply for the RMIO
board via terminal X34. For the current consumption of the RMIO board, see chapter
Motor control and I/O board (RMIO).
Note: External power is easier to supply to the RMIO board via terminal X23, see
chapter Motor control and I/O board (RMIO).
Parameter settings
In Standard Application Program, set parameter 16.09 CTRL BOARD SUPPLY to
EXTERNAL 24V if the RMIO board is powered from an external supply.
Electrical installation
72
X34
4
4
Electrical installation
73
5 6 7
Electrical installation
74
WARNING! Dangerous voltages can be present on the AGPS board even when the
115...230 V supply is switched off. Follow the Safety instructions on the first pages of
this manual and the instruction in this section when working on the AGPS board.
Make sure that the drive is disconnected from the mains (input power) and the
115...230 V source for the AGPS board is switched off during installation and
maintenance. If the drive is already connected to the mains, wait for 5 min after
disconnecting mains power.
X2
X1
115...230 V
3
Electrical installation
75
Note: Location of the X41 terminal block varies according to the drive frame size.
Note: Maximum cable length between AGPS terminal block X2 and drive terminal
block is restricted to 10 m.
For technical data see section AGPS-11C in chapter Technical data.
Electrical installation
76
The following figure presents the circuit diagram of the Prevention of Unexpected
Start.
3AFE00374994
Electrical installation
77
WARNING! If the RMIO board is supplied from an external power source via
terminal X34, the loose end of the cable removed from the RMIO board terminal
must be secured mechanically to a location where it cannot come into contact with
electrical parts. If the screw terminal plug of the cable is removed, the wire ends
must be individually insulated.
Parameter settings
In Standard Application Program, set parameter 16.09 CTRL BOARD SUPPLY to
EXTERNAL 24V if the RMIO board is powered from an external supply.
Analogue outputs
Two programmable current outputs: 0 (4) to 20 mA, RL < 700 ohm
Resolution 0.1% (10 bit)
Inaccuracy ±1% (Full Scale Range) at 25°C (77°F). Temperature coefficient: ±200 ppm/°C
(±111 ppm/°F) max.
Digital inputs
With Standard Application Program six programmable digital inputs (common ground:
24 VDC, -15% to +20%) and a start interlock input. Group isolated, can be divided in
two isolated groups (see Isolation and grounding diagram below).
Thermistor input: 5 mA, < 1.5 kohm “1” (normal temperature), > 4 kohm “0”
(high temperature), open circuit “0” (high temperature).
Internal supply for digital inputs (+24 VDC): short circuit proof. An external 24 VDC
supply can be used instead of the internal supply.
Isolation test voltage 500 VAC, 1 min
Logical thresholds < 8 VDC “0”, > 12 VDC “1”
Input current DI1 to DI 5: 10 mA, DI6: 5 mA
Filtering time constant 1 ms
Relay outputs
Three programmable relay outputs
Switching capacity 8 A at 24 VDC or 250 VAC, 0.4 A at 120 VDC
Minimum continuous current 5 mA rms at 24 VDC
Maximum continuous current 2 A rms
Contact material Silver Cadmium Oxide (AgCdO)
Isolation test voltage 4 kVAC, 1 minute
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 50178 provided that the external circuits connected to the terminals also
fulfil the requirements and the installation site is below 2000 m (6562 ft). Above 2000 m (6562 ft), see page 57.
9 AO1+
10 AO1-
11 AO2+
12 AO2-
X22
1 DI1
2 DI2
3 DI3
4 DI4 Jumper J1 settings:
9 DGND1
Installation checklist
Checklist
Check the mechanical and electrical installation of the drive before start-up. Go
through the checklist below together with another person. Read the Safety
instructions on the first pages of this manual before you work on the unit.
Check
MECHANICAL INSTALLATION
The ambient operating conditions are allowed. (See Mechanical installation, Technical data:
IEC data or NEMA data, Ambient conditions.)
The unit is fixed properly into the cabinet. (See Planning the cabinet assembly and
Mechanical installation.)
The cooling air will flow freely.
The motor and the driven equipment are ready for start. (See Planning the electrical
installation: Motor selection and compatibility, Technical data: Motor connection.)
ELECTRICAL INSTALLATION (See Planning the electrical installation, Electrical installation.)
Drive does not include the EMC filter option (+E202, +E200) or the +E202 and +E200 EMC
filter capacitors are disconnected if the drive is connected to an IT (ungrounded) system.
The capacitors are reformed if stored over one year (refer to ACS600/800 Capacitor
Reforming Guide [3AFE64059629 (English)].
The drive is grounded properly.
The mains (input power) voltage matches the drive nominal input voltage.
The mains (input power) connections at U1, V1 and W1 and their tightening torques are OK.
Appropriate mains (input power) fuses and disconnector are installed.
The motor connections at U2, V2 and W2 and their tightening torques are OK.
The motor cable is routed away from other cables.
There are no power factor compensation capacitors in the motor cable.
The external control connections inside the drive are OK.
There are no tools, foreign objects or dust from drilling inside the drive.
Mains (input power) voltage cannot be applied to the output of the drive (with bypass
connection).
Motor connection box and other covers are in place.
Installation checklist
84
Check
Modules with prevention of unexpected start option only (AGPS board): The prevention of
unexpected start circuit is completed.
Installation checklist
85
Maintenance
Safety
WARNING! Read the Safety instructions on the first pages of this manual before
performing any maintenance on the equipment. Ignoring the safety instructions can
cause injury or death.
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Heatsink
The heatsink fins pick up dust from the cooling air. The drive runs into
overtemperature warnings and faults if the heatsink is not clean. In a “normal”
environment (not dusty, not clean) the heatsink should be checked annually, in a
dusty environment more often.
Clean the heatsink as follows (when necessary):
1. Remove the cooling fan (see section Fan).
2. Blow clean compressed air (not humid) from bottom to top and simultaneously
use a vacuum cleaner at the air outlet to trap the dust. Note: If there is a risk of
the dust entering adjoining equipment, perform the cleaning in another room.
3. Replace the cooling fan.
Maintenance
86
Fan
The cooling fan lifespan of the drive is about 50 000 operating hours. The actual
lifespan depends on the drive usage and ambient temperature. See the appropriate
ACS800 Firmware Manual for an actual signal which indicates the hours of usage of
the fan. For resetting the running time signal after a fan replacement, please contact
ABB.
Fan failure can be predicted by the increasing noise from fan bearings and the
gradual rise in the heatsink temperature in spite of heatsink cleaning. If the drive is
operated in a critical part of a process, fan replacement is recommended once these
symptoms start appearing. Replacement fans are available from ABB. Do not use
other than ABB specified spare parts.
Bottom view
Maintenance
87
1 1 Bottom view
2
3
View from above fan
plate pulled out
4 4
4 4
Maintenance
88
4 4 2
Maintenance
89
Bottom view
Additional fan
In ACS800-04/U4 (R2...R6) units there is an additional fan in all types except in
-0001-2, -0002-2, -0003-2, -0003-3, -0004-3, -0005-3, -0004-5, -0005-5 and
-0006-5.
Maintenance
90
Replacement (R6)
To remove the fan, release the retaining clips by pulling the back edge (1) of the fan
upwards. Disconnect the cable (2, detachable terminal). Install the new fan in
reverse order.
Rotation direction
Capacitors
The drive intermediate circuit employs several electrolytic capacitors. Their lifespan
is from 45 000 to 90 000 hours depending on drive loading and ambient
temperature. Capacitor life can be prolonged by lowering the ambient temperature.
It is not possible to predict a capacitor failure. Capacitor failure is usually followed by
a mains fuse failure or a fault trip. Contact ABB if capacitor failure is suspected.
Replacements for frame size R4 and up are available from ABB. Do not use other
than ABB specified spare parts.
Reforming
Reform (re-age) spare part capacitors once a year according to ACS600/800
Capacitor Reforming Guide [3AFE64059629 (English)].
LEDs
This table describes LEDs of the drive.
Maintenance
91
Technical data
IEC data
Ratings
The IEC ratings for the ACS800-04 with 50 Hz and 60 Hz supplies are given below.
The symbols are described below the table.
ACS800-04 size Nominal No-overload Light-overload Heavy-duty use Frame Air Heat
ratings use use size flow dissipation
Icont.max Imax Pcont.max I2N PN I2hd Phd
A kW
A A kW A kW m3/h W
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0001-2 5.1 6.5 1.1 4.7 0.75 3.4 0.55 R2 35 100
-0002-2 6.5 8.2 1.5 6.0 1.1 4.3 0.75 R2 35 100
-0003-2 8.5 10.8 1.5 7.7 1.5 5.7 1.1 R2 35 100
-0004-2 10.9 13.8 2.2 10.2 2.2 7.5 1.5 R2 35 120
-0005-2 13.9 17.6 3 12.7 3 9.3 2.2 R2 35 140
-0006-2 19 24 4 18 4 14 3 R3 69 160
-0009-2 25 32 5.5 24 5,5 19 4 R3 69 200
-0011-2 34 46 7.5 31 7.5 23 5.5 R3 69 250
-0016-2 44 62 11 42 11 32 7.5 R4 103 340
-0020-2 55 72 15 50 11 37 7.5 R4 103 440
-0025-2 72 86 18.5 69 18.5 49 11 R5 250 530
-0030-2 86 112 22 80 22 60 15 R5 250 610
-0040-2 103 138 30 94 22 69 18.5 R5 250 810
-0050-2 141 164 37 132 37 97 30 R6 405 1190
-0060-2 166 202 45 155 45 115 30 R6 405 1190
-0070-2 202 282 55 184 55 141 37 R6 405 1440
Technical data
92
ACS800-04 size Nominal No-overload Light-overload Heavy-duty use Frame Air Heat
ratings use use size flow dissipation
Icont.max Imax Pcont.max I2N PN I2hd Phd
A kW
A A kW A kW m3/h W
Three-phase supply voltage 380 V, 400 V or 415 V
-0003-3 5.1 6.5 1.5 4.7 1.5 3.4 1.1 R2 35 100
-0004-3 6.5 8.2 2.2 5.9 2.2 4.3 1.5 R2 35 120
-0005-3 8.5 10.8 3 7.7 3 5.7 2.2 R2 35 140
-0006-3 10.9 13.8 4 10.2 4 7.5 3 R2 35 160
-0009-3 13.9 17.6 5.5 12.7 5.5 9.3 4 R2 35 200
-0011-3 19 24 7.5 18 7.5 14 5.5 R3 69 250
-0016-3 25 32 11 24 11 19 7.5 R3 69 340
-0020-3 34 46 15 31 15 23 11 R3 69 440
-0023-3 40 46 22 39 18.5 28 15 R3 69 520
-0025-3 44 62 22 41 18.5 32 15 R4 103 530
-0030-3 55 72 30 50 22 37 18.5 R4 103 610
-0035-3 59 72 30 57 30 41 22 R4 103 660
-0040-3 72 86 37 69 30 49 22 R5 168 810
-0050-3 86 112 45 80 37 60 30 R5 168 990
-0060-3 103 138 55 100 55 69 37 R5 168 1190
-0070-3 141 164 75 132 55 97 45 R6 405 1440
-0100-3 166 202 90 155 75 115 55 R6 405 1940
-0120-3 202 282 110 184 90 141 75 R6 405 2310
-0135-3 225 326 110 220 110 163 90 R6 405 2810
-0165-3 260 326 132 254 132 215 110 R6 405 3260
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0004-5 4.9 6.5 2.2 4.5 2.2 3.4 1.5 R2 35 120
-0005-5 6.2 8.2 3 5.6 3 4.2 2.2 R2 35 140
-0006-5 8.1 10.8 4 7.7 4 5.6 3 R2 35 160
-0009-5 10.5 13.8 5.5 10 5.5 7.5 4 R2 35 200
-0011-5 13.2 17.6 7.5 12 7.5 9.2 5.5 R2 35 250
-0016-5 19 24 11 18 11 13 7.5 R3 69 340
-0020-5 25 32 15 23 15 18 11 R3 69 440
-0025-5 34 46 18.5 31 18.5 23 15 R3 69 530
-0028-5 38 46 22 37 22 27 18.5 R3 69 590
-0030-5 42 62 22 39 22 32 18.5 R4 103 610
-0040-5 48 72 30 44 30 36 22 R4 103 810
-0045-5 56 72 37 54 37 39 22 R4 103 950
-0050-5 65 86 37 61 37 50 30 R5 168 990
-0060-5 79 112 45 75 45 60 37 R5 168 1190
-0070-5 96 138 55 88 55 69 45 R5 168 1440
-0100-5 124 164 75 115 75 88 55 R6 405 1940
-0120-5 157 202 90 145 90 113 75 R6 405 2310
-0140-5 180 282 110 163 110 141 90 R6 405 2810
-0165-5 225 326 132 220 132 163 110 R6 405 3260
-0205-5 260 326 160 254 160 215 132 R6 405 3800
Technical data
93
ACS800-04 size Nominal No-overload Light-overload Heavy-duty use Frame Air Heat
ratings use use size flow dissipation
Icont.max Imax Pcont.max I2N PN I2hd Phd
A kW
A A kW A kW m3/h W
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0011-7 13 14 11 11.5 7.5 8.5 5.5 R4 103 300
-0016-7 17 19 15 15 11 11 7.5 R4 103 340
-0020-7 22 28 18.5 20 15 15 11 R4 103 440
-0025-7 25 38 22 23 18.5 19 15 R4 103 530
-0030-7 33 44 30 30 22 22 18.5 R4 103 610
-0040-7 36 54 30 34 30 27 22 R4 103 690
-0050-7 51 68 45 46 37 34 30 R5 250 840
-0060-7 57 84 55 52 45 42 37 R5 250 1010
-0070-7 79 104 75 73 55 54 45 R6 405 1220
-0100-7 93 124 90 86 75 62 55 R6 405 1650
-0120-7 113 172 110 108 90 86 75 R6 405 1960
-0145-7 134 190 132 125 110 95 90 R6 405 2660
-0175-7 166 245 160 155 132 131 110 R6 405 3470
-0205-7 190 245 160 180 160 147 132 R6 405 4180
PDM code: 00096931-J
Symbols
Nominal ratings
Icont.max continuous rms output current. No overload capability at 40°C.
Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
Typical ratings:
No-overload use
Pcont.max typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
230 V, 400 V, 500 V or 690 V.
Light-overload use (10% overload capability)
I2N continuous rms current. 10% overload is allowed for one minute every 5 minutes.
PN typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
230 V, 400 V, 500 V or 690 V.
Heavy-duty use (50% overload capability)
I2hd continuous rms current. 50% overload is allowed for one minute every 5 minutes.
Phd typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
230 V, 400 V, 500 V or 690 V.
Sizing
The current ratings are the same regardless of the supply voltage within one voltage range. To achieve
the rated motor power given in the table, the rated current of the drive must be higher than or equal to
the rated motor current.
Note 1: The maximum allowed motor shaft power is limited to 1.5 · Phd, 1.1 · PN or Pcont.max (whichever
value is greatest). If the limit is exceeded, motor torque and current are automatically restricted. The
function protects the input bridge of the drive against overload. If the condition exists for 5 minutes, the
limit is set to Pcont.max.
Note 2: The ratings apply in ambient temperature of 40°C (104°F). In lower temperatures the ratings
are higher (except Imax).
Note 3: Use the DriveSize PC tool for a more accurate dimensioning if the ambient temperature is
below 40°C (104°F) or the drive is loaded cyclically.
Technical data
94
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres
(3300 ft), or if the ambient temperature exceeds 40°C (104°F).
Temperature derating
In the temperature range +40°C (+104°F) to +50°C (+122°F) the rated output current is decreased by
1% for every additional 1°C (1.8°F). The output current is calculated by multiplying the current given in
the rating table by the derating factor.
Example If the ambient temperature is 50°C (+122°F), the derating factor is 100% - 1 % · 10°C =
90% or 0.90. The output current is then 0.90 · I or 0.90 · I . °C
2N 2hd
Altitude derating
In altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the derating is 1% for every 100 m
(328 ft). For a more accurate derating, use the DriveSize PC tool.
Cooling characteristics
ACS800-04 Minimum effective area of air inlet Minimum effective area of air outlet
frame size cm2 cm2
IP22 cabinet IP54 cabinet IP22 cabinet IP54 cabinet
R2 125 250 200 400
R3 250 500 400 800
R4 375 750 600 1200
R5 500 1000 800 1600
R6 1000 2000 1600 3200
ACS800-04 Air flow: drive front side Air flow: heat sink side
frame size m3/h m3/h
R2 18 35
R3 30 69
R4 30 103
R5 30 168
R6 30 405
Technical data
95
Technical data
96
Technical data
97
Technical data
98
Cable types
The table below gives copper and aluminium cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30°C, PVC insulation, surface temperature 70°C (EN 60204-1 and
IEC 60364-5-2/2001). For other conditions, size the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
Copper cables with concentric Aluminium cables with concentric
copper shield copper shield
Max. load current Cable type Max. load current Cable type
A mm2 A mm2
14 3x1.5 61 3x25
20 3x2.5 75 3x35
27 3x4 91 3x50
34 3x6 117 3x70
47 3x10 143 3x95
62 3x16 165 3x120
79 3x25 191 3x150
98 3x35 218 3x185
119 3x50 257 3x240
153 3x70 274 3 x (3x50)
186 3x95 285 2 x (3x95)
215 3x120
249 3x150
284 3x185
PDM code: 00096931
Technical data
99
Cable entries
Brake resistor, mains and motor cable terminal sizes (per phase) and tightening
torques are given below.
Frame U1, V1, W1, U2, V2, W2, R+, R- Earthing PE
size Maximum wire size Tightening torque Maximum wire size Tightening torque
mm2 Nm mm2 Nm
R2 up to 16 * 1.2...1.5 up to 10 1.5
R3 up to 16 * 1.2...1.5 up to 10 1.5
R4 up to 25 2…4 up to 16 3.0
R5 6...70 15 6...70 15
R6 95...185 ** 20...40 95 8
Technical data
100
NEMA data
Ratings
The NEMA ratings for the ACS800-U4 with 60 Hz supplies are given below. The
symbols are described below the table. For sizing, derating and 50 Hz supplies, see
section IEC data.
ACS800-U4 size Imax Normal use Heavy-duty use Frame Air flow Heat
size dissipation
I2N PN I2hd Phd
A A HP A HP ft3/min BTU/Hr
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0002-2 8.2 6.6 1.5 4.6 1 R2 21 350
-0003-2 10.8 8.1 2 6.6 1.5 R2 21 350
-0004-2 13.8 11 3 7.5 2 R2 21 410
-0006-2 24 21 5 13 3 R3 41 550
-0009-2 32 27 7.5 17 5 R3 41 680
-0011-2 46 34 10 25 7.5 R3 41 850
-0016-2 62 42 15 31 10 R4 61 1150
-0020-2 72 54 20 * 42 15 ** R4 61 1490
-0025-2 86 69 25 54 20 ** R5 147 1790
-0030-2 112 80 30 68 25 ** R5 147 2090
-0040-2 138 104 40 * 80 30 ** R5 147 2770
-0050-2 164 132 50 104 40 R6 238 3370
-0060-2 202 157 60 130 50 ** R6 238 4050
-0070-2 282 192 75 154 60 ** R6 238 4910
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V or 480 V
-0004-5 6.5 4.9 3 3.4 2 R2 21 410
-0005-5 8.2 6.2 3 4.2 2 R2 21 480
-0006-5 10.8 8.1 5 5.6 3 R2 21 550
-0009-5 13.8 11 7.5 8.1 5 R2 21 690
-0011-5 17.6 14 10 11 7.5 R2 21 860
-0016-5 24 21 15 15 10 R3 41 1150
-0020-5 32 27 20 21 15 R3 41 1490
-0025-5 46 34 25 27 20 R3 41 1790
-0030-5 62 42 30 34 25 R4 61 2090
-0045-5 72 54 40 39 30 R4 61 2770
-0050-5 86 65 50 52 40 R5 147 3370
-0060-5 112 79 60 65 50 R5 147 4050
-0070-5 138 96 75 77 60 R5 147 4910
-0100-5 164 124 100 96 75 R6 238 6610
-0120-5 202 157 125 124 100 R6 238 7890
-0140-5 282 180 150 156 125 R6 238 9600
-0205-5 326 254 200 215 150 R6 238 12980
Three-phase supply voltage 525 V, 575 V or 600 V
-0011-7 14 11.5 10 8.5 7.5 R4 61 1050
-0016-7 19 15 10 11 10 R4 61 1200
-0020-7 28 20 15/20*** 15 15** R4 61 1550
-0025-7 38 23 20 20 20** R4 61 1850
-0030-7 44 30 25/30*** 25 25** R4 61 2100
-0040-7 54 34 30 30 30** R4 61 2400
-0050-7 68 46 40 40 40** R5 147 2900
-0060-7 84 52 50 42 40 R5 147 3450
-0070-7 104 73 60 54 50 R6 238 4200
-0100-7 124 86 75 62 60 R6 238 5650
-0120-7 172 108 100 86 75 R6 238 6700
-0145-7 190 125 125 99 100 R6 238 9100
Technical data
101
ACS800-U4 size Imax Normal use Heavy-duty use Frame Air flow Heat
size dissipation
I2N PN I2hd Phd
A A HP A HP ft3/min BTU/Hr
-0175-7 245 155 150 131 125 R6 238 11900
-0205-7 245 192 200 147 150 R6 238 14300
PDM code: 00096931-J
*
Overload may be limited to 5% at high speeds (> 90% speed) by the internal power limit of the drive.
The limitation also depends on motor characteristics and network voltage.
**
Overload may be limited to 40% at high speeds (> 90% speed) by the internal power limit of the
drive. The limitation also depends on motor characteristics and network voltage.
*** Higher rating is available with special 4-pole high-efficiency NEMA motor.
Symbols
Nominal ratings
Imax maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
Normal use (10% overload capability)
I2N continuous rms current. 10% overload is typically allowed for one minute every 5 minutes.
PN typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V,
460 V or 575 V).
Heavy-duty use (50% overload capability)
I2hd continuous rms current. 50% overload is typically allowed for one minute every 5 minutes.
Phd typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V,
460 V or 575 V).
Note 1: The ratings apply in ambient temperature of 40°C (104°F). In lower temperatures the ratings
are higher (except Imax).
Technical data
102
Technical data
103
Cable types
Cable sizing is based on NEC Table 310-16 for copper wires, 75°C (167°F) wire insulation at 40°C
(104°F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or
earth (directly buried). For other conditions, dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
Technical data
104
Cable Entries
Brake resistor, input and motor cable (per phase) terminal sizes and tightening
torques are given below.
Frame U1, V1, W1, U2, V2, W2, R+, R- Earthing PE
size Maximum wire size Tightening torque Maximum wire size Tightening torque
AWG lbf ft AWG lbf ft
R2 up to 6 * 0.9…1.1 up to 8 1.1
R3 up to 6 * 0.9...1.1 up to 8 1.1
R4 up to 4 1.5…3.0 up to 5 2.2
R5 10...2/0 11.1 10...2/0 11.1
R6 3/0...350 MCM ** 14.8...29.5 4/0 5.9
Technical data
105
Motor connection
Voltage (U2) 0 to U1, 3-phase symmetrical, Umax at the field weakening point
Frequency DTC mode: 0 to 3.2 · fFWP. Maximum frequency 300 Hz.
UNmains
fFWP = · fNmotor
UNmotor
fFWP: frequency at field weakening point; UNmains: mains (input power) voltage;
UNmotor: rated motor voltage; fNmotor: rated motor frequency
Frequency resolution 0.01 Hz
Current See section IEC data.
Power limit 1.5 · Phd, 1.1 · PN or Pcont.max (whichever value is greatest)
Field weakening point 8 to 300 Hz
Switching frequency 3 kHz (average). In 690 V units 2 kHz (average).
Maximum recommended Sizing method Max. motor cable length
motor cable length DTC control Scalar control
according to I2N and I2hd R2 to R3: 100 m (328 ft) R2: 150 m (492 ft)
according to Icont.max at R4 to R6: 300 m (984 ft) R3 to R6: 300 m (984 ft)
ambient temperatures below
30°C (86°F)
according to Icont.max at R2: 50 m (164 ft) Note: This applies to units with EMC filter
ambient temperatures above also.
30°C (86°F) R3 and R4: 100 m (328 ft)
R5 and R6: 150 m (492 ft)
Note: With cables longer than 100 m (328 ft), the EMC Directive requirements may not be
fulfilled. See section CE marking.
Efficiency
Approximately 98% at nominal power level
Cooling
Method Internal fan, flow direction from bottom to top.
Free space around the unit See chapter Mechanical installation.
Degrees of protection
IP20 (UL open type). See chapter Planning the cabinet assembly.
Technical data
106
AGPS-11C
Nominal input voltage 115...230 VAC ±10%
Nominal input current 0.1 A (230 V) / 0.2 A (115 V)
Nominal frequency 50/60 Hz
Max. external fuse 16 A
X1 terminal sizes 3 x 2.5 mm2
Output voltage 15 VDC ±0.5 V
Nominal output current 0.4 A
X2 terminal block type JST B4P-VH
Ambient temperature 0...50°C
Relative humidity Max. 90%, no condensation allowed
Dimensions (with enclosure) 167 x 128 x 52 mm (Height x Width x Depth)
Weight (with enclosure) 0.75 kg
Approvals C-UL, US listed
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Operation Storage Transportation
installed for stationary use in the protective package in the protective package
Installation site altitude 0 to 4000 m (13123 ft) above - -
sea level [above 1000 m
(3281 ft), see section
Derating]
Air temperature -15 to +50°C (5 to 122°F). No -40 to +70°C (-40 to +158°F) -40 to +70°C (-40 to +158°F)
frost allowed. See section
Derating.
Relative humidity 5 to 95% Max. 95% Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels No conductive dust allowed.
(IEC 60721-3-3, IEC 60721-3- Boards without coating: Boards without coating: Boards without coating:
2, IEC 60721-3-1) Chemical gases: Class 3C1 Chemical gases: Class 1C2 Chemical gases: Class 2C2
Solid particles: Class 3S2 Solid particles: Class 1S3 Solid particles: Class 2S2
Boards with coating: Boards with coating: Boards with coating:
Chemical gases: Class 3C2 Chemical gases: Class 1C2 Chemical gases: Class 2C2
Solid particles: Class 3S2 Solid particles: Class 1S3 Solid particles: Class 2S2
Atmospheric pressure 70 to 106 kPa 70 to 106 kPa 60 to 106 kPa
0.7 to 1.05 atmospheres 0.7 to 1.05 atmospheres 0.6 to 1.05 atmospheres
Vibration (IEC 60068-2)* Max. 1 mm (0.04 in.) Max. 1 mm (0.04 in.) Max. 3.5 mm (0.14 in.)
(5 to 13.2 Hz), (5 to 13.2 Hz), (2 to 9 Hz),
max. 7 m/s2 (23 ft/s2) max. 7 m/s2 (23 ft/s2) max. 15 m/s2 (49 ft/s2)
(13.2 to 100 Hz) sinusoidal (13.2 to 100 Hz) sinusoidal (9 to 200 Hz) sinusoidal
Shock (IEC 60068-2-29) Not allowed Max. 100 m/s2 (330 ft./s2), Max. 100 m/s2 (330 ft./s2),
11 ms 11 ms
Free fall Not allowed 250 mm (10 in.) for weight 250 mm (10 in.) for weight
under 100 kg (220 lb) under 100 kg (220 lb)
100 mm (4 in.) for weight 100 mm (4 in.) for weight
over 100 kg (220 lb) over 100 kg (220 lb)
2. For higher vibration use the
*Note: For frame sizes R2 to R4 with panel option maximum allowed vibration is 3 m/s
RPMP kit. See Control Panel Mounting Platform Kit (RPMP) Installation Guide [3AFE64677560 (English)].
Technical data
107
Materials
Drive enclosure • PC/ABS 2.5 mm, colour NCS 1502-Y (RAL 90021 / PMS 420 C)
• hot-dip zinc coated steel sheet 1.5 to 2 mm, thickness of coating 100 micrometres
• cast aluminium AlSi (R2 and R3)
• extruded aluminium AlSi (R4 to R6)
Package Corrugated cardboard (frames R2 to R5 and option modules), plywood and wood (frame
size R6), expanded polystyrene. Plastic covering of the package: PE-LD, bands PP or
steel.
Disposal The drive contains raw materials that should be recycled to preserve energy and natural
resources. The package materials are environmentally compatible and recyclable. All
metal parts can be recycled. The plastic parts can either be recycled or burned under
controlled circumstances, according to local regulations. Most recyclable parts are marked
with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit
boards can be landfilled. The DC capacitors (C1-1 to C1-x) contain electrolyte and the
printed circuit boards contain lead, both of which are classified as hazardous waste within
the EU. They must be removed and handled according to local regulations.
For further information on environmental aspects and more detailed recycling instructions,
please contact your local ABB distributor.
Applicable standards
The drive complies with the following standards. The compliance with the European Low
Voltage Directive is verified according to standards EN 50178 and EN 60204-1.
• EN 50178 (1997) Electronic equipment for use in power installations
• EN 60204-1 (1997) Safety of machinery. Electrical equipment of machines. Part 1: General requirements.
Provisions for compliance: The final assembler of the machine is responsible for installing
- an emergency-stop device
- a supply disconnecting device
- the ACS800-04/U4 into a cabinet.
• EN 60529: 1991 Degrees of protection provided by enclosures (IP code)
(IEC 60529)
• IEC 60664-1 (1992) Insulation coordination for equipment within low-voltage systems. Part 1: Principles,
requirements and tests.
• EN 61800-3 (2004) Adjustable speed electrical power drive systems. Part 3: EMC requirements and specific
test methods
• UL 508C UL Standard for Safety, Power Conversion Equipment, second edition
• NEMA 250 (2003) Enclosures for Electrical Equipment (1000 Volts Maximum)
• CSA C22.2 No. 14-95 Industrial control equipment
Technical data
108
CE marking
A CE mark is attached to the drive to verify that the unit follows the provisions of the European Low
Voltage and EMC Directives (Directive 73/23/EEC, as amended by 93/68/EEC and Directive 89/336/
EEC, as amended by 93/68/EEC).
Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to
operate without problems within an electromagnetic environment. Likewise, the equipment must not
disturb or interfere with any other product or system within its locality.
First environment includes establishments connected to a low-voltage network which supplies buildings
used for domestic purposes.
Second environment includes establishments connected to a network not supplying domestic premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed and
commissioned only by a professional when used in the first environment. Note: A professional is
a person or organisation having necessary skills in installing and/or commissioning power drive
systems, including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in the second
environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current equal to or above
400 A, or intended for use in complex systems in the second environment.
Technical data
109
Neighbouring network
Static screen
Point of measurement
Equipment Equipment
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available
from the local ABB representative.
3. The motor and control cables are selected as specified in the Hardware Manual.
4. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such
a network.
Machinery Directive
The drive complies with the European Union Machinery Directive (98/37/EC) requirements for an
equipment intended to be incorporated into machinery.
Technical data
110
“C-tick” marking
“C-tick” marking is required in Australia and New Zealand. A “C-tick” mark is attached to each drive in
order to verify compliance with the relevant standard (IEC 61800-3 (2004) – Adjustable speed electrical
power drive systems. Part 3: EMC requirements and specific test methods), mandated by the
Trans-Tasman Electromagnetic Compatibility Scheme.
Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to
operate without problems within an electromagnetic environment. Likewise, the equipment must not
disturb or interfere with any other product or system within its locality.
The Trans-Tasman Electromagnetic Compatibility Scheme (EMCS) was introduced by the Australian
Communication Authority (ACA) and the Radio Spectrum Management Group (RSM) of the New
Zealand Ministry of Economic Development (NZMED) in November 2001. The aim of the scheme is to
protect the radiofrequency spectrum by introducing technical limits for emission from electrical/
electronic products.
First environment includes establishments connected to a low-voltage network which supplies buildings
used for domestic purposes.
Second environment includes establishments connected to a network not supplying domestic premises.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed and
commissioned only by a professional when used in the first environment. Note: A professional is
a person or organisation having necessary skills in installing and/or commissioning power drive
systems, including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in the second
environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current equal to or above
400 A, or intended for use in complex systems in the second environment.
Technical data
111
Neighbouring network
Static screen
Point of measurement
Equipment Equipment
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available
from the local ABB representative.
3. The motor and control cables are selected as specified in the Hardware Manual.
4. The drive is installed according to the instructions given in the Hardware Manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public network which
supplies domestic premises. Radio frequency interference is expected if the drive is used on such
a network.
Technical data
112
UL/CSA markings
The ACS800-04 and ACS800-U4 are C-UL US listed and CSA marked.
UL
The drive is suitable for use on a circuit capable of delivering not more than 65 kA rms symmetrical
amperes at the drive nominal voltage (600 V maximum for 690 V units).
The drive provides overload protection in accordance with the National Electrical Code (US). See
ACS800 Firmware Manual for setting. Default setting is off, must be activated at start-up.
The drives are to be used in a heated indoor controlled environment. See section Ambient conditions
for specific limits.
Brake chopper - ABB has brake choppers that, when applied with appropriately sized brake resistors,
will allow the drive to dissipate regenerative energy (normally associated with quickly decelerating
a motor). Proper application of the brake chopper is defined in chapter Resistor braking. This can be
applied to a single drive or multiple drives with DC bus connected to allow a sharing of regenerative
energy.
Technical data
113
Technical data
114
Technical data
115
Dimensional drawings
Dimensional drawings
116
3AFE68347432
Dimensional drawings
117
3AFE68360544
Dimensional drawings
118
3AFE68364655
Dimensional drawings
119
3AFE68365741
Dimensional drawings
120
3AFE68365945
Dimensional drawings
121
Lifting lug
7 [0.276]
H
D
Frame size H W D
mm [in.] mm [in.] mm [in.]
R2 476.5 [18.76] 235.5 [9.27] 25 [0.984]
R3 530.5 [20.89] 245.5 [9.67] 25 [0.984]
R4 595.95 [23.46] 373.6 [14.71] 25 [0.984]
R5 700 [27.56] 398.8 [15.70] 25 [0.984]
R6 786 [30.94] 433.4 [17.06] 25 [0.984]
Dimensional drawings
122
[5.51]
[0.276]
[15.16]
22
[0.866] [7.54]
[5.51]
[2.17]
98.25
[3.87]
[0
.7
87
]
3AFE68361001
[6.69]
Dimensional drawings
123
[7.09]
[0.394]
[6.30]
[17.32]
[0.276]
[6.30]
22
105.25
[2.36]
[4.14]
[0.866] [7.93]
3AFE68370418
Dimensional drawings
124
86.8
[3.42]
142.95
[5.63]
[12.40]
21
[4.96]
[0.827]
[0.276]
[11.81]
[20.08]
[6.53]
[1.30]
[5.23]
[3.94]
[6.02]
]
153
87
3AFE68375371
.7
[0
Dimensional drawings
125
[4.33] [13.39]
[14.33]
[8.66]
[0.276]
[24.57]
[8.66]
[0.866]
[4.33]
[3.15]
[5.12]
130
3AFE68371619
]
87
.7
119.4
[0
[4.70]
Dimensional drawings
126
[8.66]
[0
.7
87
]
[0.709]
18
[4.84]
16.7
[15.75] [0.657]
[6.61]
[0.276]
[6.61]
[28.35]
[6.61]
[3.94]
[0.787]
[4.84]
3AFE68367280
]
100
87
116.7
.7
[4.59] [3.94]
[0
Dimensional drawings
127
AGPS board
3AFE68293898
Dimensional drawings
128
Dimensional drawings
129
Resistor braking
3. Check the resistor selection. The energy generated by the motor during a 400
second period must not exceed the resistor heat dissipation capacity ER.
If the ER value is not sufficient, it is possible to use a four-resistor assembly in which two standard
resistors are connected in parallel, two in series. The ER value of the four-resistor assembly is four
times the value specified for the standard resistor.
Resistor braking
130
Note: A resistor other than the standard resistor can be used provided that:
• its resistance is not lower than the resistance of the standard resistor.
• the resistance does not restrict the braking capacity needed, i.e.
2
UDC
Pmax <
R
where
Pmax maximum power generated by the motor during braking
UDC voltage over the resistor during braking, e.g.
1.35 · 1.2 · 415 VDC (when supply voltage is 380 to 415 VAC),
1.35 · 1.2 · 500 VDC. (when supply voltage is 440 to 500 VAC) or
1.35 · 1.2 · 690 VDC (when supply voltage is 525 to 690 VAC).
R resistor resistance (ohm)
• the heat dissipation capacity (ER) is sufficient for the application (see step 3
above).
WARNING! Never use a brake resistor with a resistance below the value specified
for the particular drive / brake chopper / resistor combination. The drive and the
chopper are not able to handle the overcurrent caused by the low resistance.
Resistor braking
131
Resistor braking
132
PbrcontThe drive and the chopper will withstand this continuous braking power. The braking is considered continuous if the
braking time exceeds 30 s.
Note: The braking energy transmitted to the specified resistor(s) in 400 seconds may not exceed ER.
R Resistance value for the listed resistor assembly. Note: This is also the minimum allowed resistance for the braking
resistor.
ER Short energy pulse that the resistor assembly withstands every 400 seconds. This energy will heat the resistor
element from 40°C (104°F) to the maximum allowable temperature.
PRcont Continuous power (heat) dissipation of the resistor when placed correctly. Energy ER dissipates in 400 seconds.
1)
22 kW with standard 22 ohm resistor and 33 kW with 32…37 ohm resistor
All braking resistors must be installed outside the converter module. The SACE braking resistors are built in an IP21 metal
housing. The SAFUR braking resistors are built in an IP00 metal frame. Note: The SACE and SAFUR resistors are not UL
listed.
WARNING! The materials near the brake resistor must be non-flammable. The
surface temperature of the resistor is high. Air flowing from the resistor is of
hundreds of degrees Celsius. Protect the resistor against contact.
Use the cable type used for drive input cabling (see to chapter Technical data) to
ensure the input fuses will also protect the resistor cable. Alternatively, two-
conductor shielded cable with the same cross-sectional area can be used. The
maximum length of the resistor cable(s) is 10 m (33 ft). For the connections, see the
power connection diagram of the drive.
Resistor braking
133
L1 L2 L3
1
OFF
Fuses 2
1 3 5 13 3
ON
2 4 6 14 4
ACS800
U1 V1 W1
Θ Thermal switch (stand-
ard in ABB resistors)
K1
Resistor braking
134
For other application programs, the thermal switch may be wired to a different digital
input. Programming of the input to trip the drive by “EXTERNAL FAULT” may be
needed. See the appropriate Firmware Manual.
WARNING! If the drive is equipped with a brake chopper but the chopper is not
enabled by parameter setting, the brake resistor must be disconnected because the
protection against resistor overheating is then not in use.
For settings of other application programs, see the appropriate Firmware Manual.
Resistor braking
3AFE68372984 Rev C EN
EFFECTIVE: 16.2.2007