EasergyP5 NRJED313567EN 270519 PDF
EasergyP5 NRJED313567EN 270519 PDF
EasergyP5 NRJED313567EN 270519 PDF
Easergy P5
Catalog 2019
Network protection relays
se.com/easergy
Note: Electrical power systems are dangerous, protection relays are defined and governed
by international standards such as IEC 60255 “Measuring relays and protective equipment”
and IEEE C37.97 “Protective relay applications to power systems buses”. Never attempt to
install or operate protection relays or associated equipment without the necessary
qualifications, training and tools. Exposure to electrical arc-flash incidents can be life
threatening, no situation can ever be deemed fully safe. Standards such as NFPA 70E define
important risk categorization and such standards identify both distance from, and energy of
the arc incident to be important factors. In order to reduce the risk category and improve
safety during arc-flash incidents, functionality is available in Easergy P5 protection relays to:
i) to operate electrical panel from a safer distance via wireless communication, and ii) arc-
flash protection functionality to detect and limit the arc energy by tripping the connected
circuit breaker faster than in a conventional protection scheme.
General Contents
PM107471
Product description 40
Digital experience 62
Services 80
Ordering 84
Selection guide 11
Communication 36
Examples of architectures 36
Redundancy protocols 37
Data exchanged 38
Cyber security 39
Cyber security systems 39
The Easergy P5 is a protection relay for demanding medium-voltage applications. It offers users dedicated features
for industry-leading protection relay functionality to reduce risks, improve reliability, all with advanced connectivity.
Additionally, it can be used with a range of digital tools that make everyday operations simpler for users. The Easergy
P5 is part of the PowerLogic range of power monitoring and control solutions and has been built on more than 100
years of experience in protection relays, including Sepam, MiCOM, and Vamp, renowned for their reliability and
performance.
Best-in-class reliability
Withdrawable design for quicker maintenance
Backup memory function enabling industry-leading 10 minute recovery time!
Condition monitoring for reduced risk of power outage and maximized equipment life
Extended equipment lifetime when used with EcoStruxure Asset Advisor
Advanced cybersecurity
IEC 62443 compliant, the P5 has been designed with an optional
cybersecurity package. This means reduced exposure to cyber threats
and improved operational security. By default, the Easergy P5 includes
important features such as password management, port hardening, and
secured communication compliant to the latest international standards.
Greater connectivity
The protection relay features seven communication protocols. This includes compliance with IEC 61850 ed. 1 and ed. 2,
Modbus (serial/TCP), IEC 60870-5-103, IEC 60870-5-101, Ethernet/IP, and DNP3 (serial/TCP). Additionally, thanks to the P5’s
modular design, communication ports can be added at any time to enable you to upgrade your device in line with future
network evolutions.
As an EcoStruxure-ready solution, the Easergy P5’s digital benefits can be taken even further with best-in-class
monitoring of substation equipment health. For example, when paired with EcoStruxure Asset Advisor
software, users get data for predictive maintenance, which helps them reduce OpEx, speed up processes,
and boost efficiency.
EcoStruxure ready
EcoStruxure™ Architecture
Cloud and/or
On Premise
End to End
Edge Control
Connected Products
Easergy P5 protection relay is based on proven technology concepts and developed in close cooperation with customers,
so it’s built to meet your toughest demands. It’s available in two sizes to best fit your needs:
• The Easergy P5 features a modular design that allows user-defined conventional protection and arc-flash protection solution
• The Easergy P5 embeds latest cybersecurity functionality to prevent intentional miss-use and cyber-attacks.
• The Easergy P5 enables fast replacement with enhanced safety thanks to the withdrawability and the back-up memory that automatically
restore parameters without using any configuration tool.
Easergy products are designed to be user friendly, a feature that is proven in our customer reports day after day. You’ll
benefit from features that include:
• A complete set of protection functions, related to the application
• Arc-flash detection in P5x30 models
• Dedicated circuit breaker control with single-line diagram, push buttons, programmable function key and LEDs, and a customizable alarm
• Multilingual HMI for customized messaging
• Settings tool relay management software for setting parameters, configuring, and network fault simulation
• Both serial and Ethernet communication, including redundancy
• IEC 61850 standard Ed.1 & Ed.2
PM107451
Range overview
DM107110
P5T30
Transformer P5U20
differential
P5G30 Universal
Generator
T U L L F U
G U U U U
M
U U
G
T U L L U M
G
DM107111
DM107112
DM107113
with specific functions to address your needs
in a one-box design, regardless of application.
Voltage P5V20 - -
Feeder P5F30 with directional
Transformer - P5U20 -
Motor P5M30
Characteristics
1/5A CT (x3) (*)
Phase current - 1/5A CT (x3)
or LPCT (x3) (*)
1/5A CT & 1A CT 1/5A CT & 1A CT
Measuring inputs Residual current -
or CSH or CSH
VT (x4) (*)
Voltage VT (x4) -
or LPVT (x4) (*)
Arc-flash sensor inputs - 0 to 6 point sensors
Inputs 4 to 10 4 to 22
Digital
Outputs 3 to 7 + WD 3 to 15 + WD
Inputs - -
Analog
Outputs - -
Temperature sensor input - 0 to 16 (external module) 0 to 16 (external modules)
Front ports USB device and USB host USB device and USB host
Nominal Power Supply 24-250 VDC ; 100-230 VAC 48-250 VDC ; 100-230 VAC
Ambient temperature, in service -40 to 70°C (-40 to 158°F) -40 to 70°C (-40 to 158°F)
Communication
Extension + Backup memory
Serial
Ethernet
2nd Ethernet -
IEC 61850 Ed.1 & Ed.2
IEC 60870-5-103 & 101
DNP3 Ethernet
Protocols DNP3 serial
Modbus Ethernet
Modbus serial
EtherNet IP
Redundancy RSTP
protocols PRP / HSR
Others
6 controlled + 2 monitored objects 6 controlled + 2 monitored
Control
Mimic objects Mimic
Logic (Matrix + Logic Equations)
Cyber security
Draw-out device
102/176/219 mm 152/176/219 mm
Hardware dimensions (H/W/D)
4.01/6.93/8.62 in 6.0/6.93/8.62 in
ANSI Logical
Protection Functions P5V20 P5U20 P5F30 P5M30
code Node
Current protection
Phase overcurrent 50/51 OCPTOC - 3 3 3
Earth/ground fault overcurrent (1) 50N/51N EFPTOC - 5/8 5/8 5/8
Directional phase overcurrent 67 DOCPTOC - - 4 4
Directional earth/ground fault overcurrent 67N DEFPTOC - - 3 3
Transient intermittent/ground fault 67NI IOIOPTEF - - 1 -
Negative sequence overcurrent 46 (I2/I1) NEGPTOC - 1 1 1
Current unbalance, Broken conductor 46BC (I2) UIBCPTOC - 1 1 -
Breaker failure 50BF CBFPPIOC 1 1 1 1
Phase undercurrent 37 UCPTUC - 1 - 1
Switch on to fault (SOTF) SOFT - 1 1 1
Cold load pickup (CPLU) CLP - 1 1 1
Voltage protection
Undervoltage 27 UVPTUV 3 - 3 3
Overvoltage 59 OVPTOV 3 - 3 3
Earth/ground fault overvoltage 59N UOPTOV 3 - 3 3
Frequency protection
Over and/or underfrequency 81 OFUFPTOF 2 - 2 2
Underfrequency 81U UFPTUF 2 - 2 2
Rate of change of frequency 81R DFDTPFRC 2 - 2 -
Thermal protection
Thermal overload 49 THFPTTR - 1 1 1
Temperature monitoring 38/49T RTDGAPC - 16 16 16
Power protection
Wattmetric earth/ground fault 32N EFPDOP - - 2 2
Directional active underpower 37P REVPPDOP - - 2 2
Rotating machine protection
Frequent start inhibition 66 FSTPMRI - 1 - 1
Excessive start time, locked rotor 48/51LR STALPMSS - 1 - 1
Positive sequence undervoltage 27P UVPSPTUV 2 - - 2
Line protection
FLRFLO/
Fault locator 21FL - - 1 -
SCRFLO
Auto-Recloser 79 ARRREC - 1 1 -
Transformer protection
Magnetizing inrush detection 68H2 HAR2PTOC - 1 1 1
Fifth harmonic detection 68H5 HAR5PTOC - 1 1 1
Capacitor protection
Capacitor bank unbalance 51C - 2 2 -
Capacitor overvoltage 59C - 1 1 -
Other protection
Arc-flash detection 50ARC ARCMPIOC - - 8 8
Programmable stages 99 PSGAPC 8 8 8 8
Programmable curves 3 3 3 3
Control, monitoring, supervision
Synchronization check 25 RSYN 1 - 1 -
Lockout relay 86 1 1 1 1
CT supervision 60 CTSGGIO - 1 1 1
VT supervision 60 VTSGGIO 1 - 1 1
LLN0/SP.SG-
Setting groups 4 4 4 4
CB
DM107115
P5F30 P5F30
P5F30 P5F30
• Up to 6 light point sensors to monitor the busbar • Up to 6 light point sensors in each relay
• Transmission of light detection signals via digital I/O or
IEC 61850 GOOSE messages
Zone 1
light detection signal
connected to Device 1. If the arc-flash sensor awakens and simul-
taneously Device 3 sends a current signal, the zone 3.1 is isolated
P5F30
by the outgoing feeder breaker.
DEVICE 3
Zone 1
The arc-flash sensor for zone 3.2 is connected to Device 2 and
operates the same way.
Outgoing protection
• Feeder overcurrent protection
• Feeder overload protection
Feeder protection Overhead line protection Protection of feeders with metering
DM107117
DM107118
DM107119
P5U20 P5F30
P5F30 P5F30
• Feeder earth/ground fault overcurrent • Directional phase and earth/ground fault • Power and energy measurement
overcurrent • Min and max demand values over the last
• Recloser 31 days and 12 months
• Fault locator
Incomer protection
• Busbar overcurrent protection
Incomer protection without voltage monitoring Incomer protection with voltage and frequency monitoring
DM107120
DM107121
DM107123
P5F30
P5F30 P5F30
• Voltage and frequency min and max values • Directional phase overcurrent
• Voltage harmonic values and THD • Directional earth/ground fault overcurrent
• Voltage sags and swells
Voltage monitoring
• Under/over voltage protection
• Earth/ground fault overvoltage
• Under/over frequency protection
DM107124
P5V20
Motor protection
• Motor overcurrent and earth/ground fault overcurrent
• Thermal overload
• Motor start-up supervision
• Motor restart inhibition
Motor protection without voltage monitoring Motor protection with voltage monitoring
DM107125
DM107126
RTD RTD
module module
DM107128
P5U20 P5F30 P5F30
26 26
63 63
49T
RTD
module
P5F30 P5F30
26 26
63 63
49T 49T
• Tank earth/ground leakage protection • Earth/ground fault overcurrent on the secondary side
DM107132
DM107133
P5U30
P5U20 P5F30 P5U20 P5F30
P5F30
• Transformer earth/ground fault overcurrent • Earth/ground fault overcurrent for • Over and undervoltage protection
transformer and back-up protection • Power and energy measurement
• Min and max demand values over the last
31 days and 12 months
P5F30 P5F30
DM107136
DM107137
P5U20 P5F30
P5F30 P5F30
P5U20
Functions Settings
Pick-up setting [xIn] 0.10 to 5.00
Line reactance 0.010 to 10.000 Ohm / km
Earth/ground factor 0.000 to 10.000
Earth/ground factor angle -60° to +60°
Synchro-check - ANSI 25
This function checks the phase-phase voltages on both sides of CB and allows CB closing when the voltage
phase angle, magnitude, frequency differences are all within permitted limits.
• 7 operation modes about no-voltage condition (dead line, dead bus) are provided.
• Synchronous mode is provided, where the frequency difference is less than 0.3Hz.
• Asynchronous mode is provided, where CB close time is compensated.
• Independent settings for voltage phase angle, magnitude, frequency differences.
Functions Settings
Synchronization mode Off, Async, Sync
Voltage check mode DD, DL, LD, DD/DL, DD/LD, DL/LD, DD/DL/LD
CB close time 0.04 to 0.6s
UDEAD limit setting 1% to 120% Un
ULIVE limit setting 1% to 130% Un
Frequency difference 0.01 to 1.0Hz
Voltage difference 1% to 60% Un
Phase angle difference 2º to 90º
Request timeout 0.1 to 600s
Note1: the reset time delay setting is only available for stage 1
(1) Sn = √3 Un In
Functions Settings
Functions Settings
Pick-up setting 0 to 180 °C (32 to 356 °F)
Functions Settings
Basic current setting 0.1In to 4.0In
Factor k 1.0 to 1.5
Heating time constant 1.0 min to 1000 min
Thermal alarm value 50% to 100%
Reserve time thermal alarm 1.0 min to 1000 min
Temperature based mode Current, Ambient
Nominal ambient temperature -40ºC to 300ºC
Max object temperature -40ºC to 300ºC
Alarm object temperature 0ºC to 300ºC
Min object temperature -40ºC to 300ºC
Default object temperature -40ºC to 300ºC
Thermal level initiation 0 to 90%
Functions Settings
Basic current setting 0.1In to 4.0In
Factor k 1.0 to 1.5
Heating Time constant 1.0min to 1000min
Time constant for motor start 1.0min to 1000min
Cooling time constant 1.0min to 1000min
Thermal alarm value 50% to 100%
Reserve time thermal alarm 1.0min to 1000min
Temperature based mode Current, Ambient
Nominal ambient temperature -40ºC to 300ºC
Max object temperature -40ºC to 300ºC
Alarm object temperature 0ºC to 300ºC
Min object temperature -40ºC to 300ºC
Default object temperature -40ºC to 300ºC
Thermal level initiation 0 to 90%
Functions Settings
I>int. On, Off
Io>int. On, Off
GOOSE NI On, Off
Virtual output 1 to 6 On, Off
Arc-flash stage 1 to 8 On, Off
Pick-up setting, I>Int. [xIn] 0.50 to 8.00
Pick-up setting, Io>Int. 0.10 to 5.00
Trip delay [ms] 0 to 255
Hold time [ms] 20 to 2500
Functions Settings
I0 input I0, I0 CSH, I0 calc,
Pick-up setting 0.02 Ino to 10 Ino for measured input with EF CT
0.02 Ino to 10 Ino for measured input with CSH CT
0.05 In to 20 In for calculated I0
Delay curve family DT, IEC, IEEE, IEEE2, RI, Prg1, Prg2, Prg3
IDMT delay type IEC: NI, VI, EI, LTI
IEEE: VI, EI, LTI, LTEI, LTVI, MI, STI, STEI
IEEE2: NI, VI, EI, MI
RI: RI, RXIDG
DT Operation delay 0.03 to 300s
Inv. Time coefficient k 0.05 to 20.0 for IEC, RI curves
0.5 to 20.0 for RXIDG, IEEE and IEEE2 curves
Reset time 0.03 to 100s
Inrush blocking Off, On
SOL Enable Off, On
SOL operation delay 0.03 to 300s
SOL Inv. Time coefficient k 0.05 to 20.0 for IEC, RI curves
0.5 to 20.0 for RXIDG, IEEE and IEEE2 curves
CLP Enable Off, On
CLP pick-up value 0.02In to 20.0In
CLP operation delay 0.03 to 300s
CLP Inv. Time coefficient k 0.05 to 20.0 for IEC, RI curves
0.5 to 20.0 for RXIDG, IEEE and IEEE2 curves
Overvoltage - ANSI 59
This function is applied to detect the abnormal higher system voltage or to check sufficient voltage for voltage
source transfer. This protection works with the maximum phase to phase voltage.
• 3 independent stages with define time are provided.
Lockout - ANSI 86
This function is used to prevent switch onto fault and function is also called latching, can be programmed for
outputs in the OUTPUT MATRIX setting view. Any protection stage start or trip, digital input, logic output, alarm
and GOOSE signal connected to the following outputs can be latched when required.
• Lockout function independently to protection stages in output matrix.
HMI/
SCADA
This architecture allows you to connect HMI/SCADA to a set of Easergy
protection relays using a multi-drop serial communication link with master-slave
communication.
Daisy chain
Serial
link Available protocols: Time synchronisation protocol:
• Modbus RTU • IRIG-B
• IEC 60870-5-101 • Minute pulse
• IEC 60870-5-103
• DNP3
Relay 1 Relay 2 Relay n (n max= 32)
HMI/
SCADA
This architecture allows you to connect a set of Easergy protection relays directly to
an Ethernet network.
Available protocols:
• IEC 61850
• IEC 60870-5-101
Ethernet
Network
• DNP3
• EtherNet/IP
Ethernet Ethernet
switch switch Note: It is possible to mix on the same Ethernet network the IEC 61850 protocol
with any of the 4 other protocols.
This allows you to use the GOOSE messages between relays together with another
protocol for communication to SCADA.
The Easergy P5 relay handles the IEC 61850 station bus, in compliance with
standards IEC 61850-6, 7-1, 7-2, 7-3, 7-4 and 8-1 Ed.1 or Ed.2, according to
configuration.
Panel Ethernet
switch Easergy
HMI Pro
HMI/
SCADA
RSTP (Rapid Spanning Tree Protocol)
DM107141
The principle of RSTP is to virtually cut all links that are not necessary at a given
time, changing the meshed topology into a tree topology.
The main advantage of RSTP is that it is widespread and works on any network
Ethernet Ethernet
switch switch topology. On the other hand, RSTP takes milliseconds or seconds to reconfigure the
network in case of network interruption.
With Easergy P5, the typical reconfiguration time for a loop of 10 relays is 0,050s.
Ethernet Ethernet
switch switch
HMI/
SCADA
Network A Network B
The receiving device is in charge of removing the redundant frame if it is received.
PRP features a 0 ms recovery time in case of failure.
Network Ethernet HSR is similar to PRP but only works on a ring architecture.
switch
Frames are transmitted on the ring in both directions and the receiving device
eliminates redundant frames.
HSR provides a 0 ms recovery time and is an alternative to PRP when network
topology can be restricted to a ring.
PRP & HSR are listed in IEC 62439-3 as part of IEC 61850 standard. They both
provide standardized, interoperable and performing redundant Ethernet solutions.
Easergy P5 Easergy P5 Easergy P5
Historical data
Disturbance records - - - - -
Setting management
Setting group change -
Settings - - - - -
The Methodology described in the IEC 61850-6 standard can be applied with
DM107144
System
.icd file configurator
Easergy relays, in order to build a protection and control system based on this
standard.
.icd file
Schneider Electric web
For each model of Easergy relay, the IED capability file can be downloaded from
the Schneider Electric website.
Easergy
Pro
.scd file
The system description file generated by the system configurator can be
processed by Easergy Pro and the relevant system settings integrated in the
Easergy configuration.
.iid file
When the configuration of an Easergy relay is completed or modified, Easergy
Pro can generate an Instantiated IED Description file to be used by the system
configurator to update the system description.
Third-party Typically, the Radius server implemented with windows server component: NPS +
device Active Directory.
Schneider Electric can also provide an IEC62351-8 compliant Radius server
already configured with authorization. This server allows a fast and reliable solution,
managed by the CAE software. In addition, it’s includes a syslog server.
eSetup
Easergy Pro
DM107150
USB
I1: 0.0A 6 programmable front
I2: 0.0A 3-color LEDs ports
I3: 0.0A
P : 0.0W
Control buttons
V : 0.0V F1 1 Function key
Programmable Logic
AND TIMER
Inputs XOR Output
OR COUNTER
Setting groups:4
Ethernet module - Slot M Slot M Slot M + N
68 Protocols Redundancy RJ45 RJ45 LC LC LC LC
79 99 38
H2/H5 49T
• IEC 61850 protocol:
• Modbus • RSTP OR
• DNP3.0
• Ethernet/IP
SOTF 74 86
OR
Serial module - Slot N Slot N Redundancy
protocols:
Protocols Electrical RJ45 RJ45
CLPU ST • HSR
• Modbus connection:
• DNP3.0
OR • PRP
• RS485
• IEC -101 2/4 wires
48 • IEC -103
37 66 51LR
Extension module - Slot P
RJ45
59C Back-up
memory
RTD1 RTD2 RTD3 RTD4
49 59641
50BF
OR
46 50N
46BC 50G 6I/4O board - Slot C
DI1 DI2 DI3 DI4 DI5 DI6
51N
60
51G DO1 DO2 DO3 DO4 REL51045
De-modulated Modulated
I1 / I2 / I3 Io/I’o IRIG-B IRIG-B
Analog measurement board - Slot A Power Supply - Slot B
Current input DI1 DI2 DI3 DI4
Other types
of control
Circuit-btreaker controls
The Easergy P5V20 offers a complete set of voltage and frequency protections, as well as measurements and recording/monitoring
functions for efficient operation of the power system.
eSetup
Easergy Pro
DM107151
USB
I1: 0.0A 6 programmable front
I2: 0.0A 3-color LEDs ports
I3: 0.0A
P : 0.0W
Control buttons
V : 0.0V F1 Function keys
Programmable Logic
AND TIMER
Inputs XOR Output
OR COUNTER
Setting groups:4
Ethernet module - Slot M Slot M Slot M + N
Protocols Redundancy RJ45 RJ45 LC LC LC LC
99 • IEC 61850 protocol:
• Modbus • RSTP OR
• DNP3.0
• Ethernet/IP
74 86
OR
Serial module - Slot N Slot N Redundancy
protocols:
Protocols Electrical RJ45 RJ45
ST • HSR
• Modbus connection:
• DNP3.0
OR • PRP
• RS485
• IEC -101 2/4 wires
• IEC -103
81
81U
59N
27
27P
25
59
6I/4O board - Slot C
DI1 DI2 DI3 DI4 DI5 DI6
60 REL51045
DO1 DO2 DO3 DO4 De-modulated Modulated
IRIG-B IRIG-B
V / V0 V4
Analog measurement board - Slot A Power Supply - Slot B
Current input Voltage input DI1 DI2 DI3 DI4
Other types
of control
Circuit-btreaker control
The Easergy P5F30 offers a complete set of current and voltage based protections
The Easergy P5F30 is designed for the and measurement, control facilities and recording/monitoring functions for efficient
operation of electrical distribution networks of operation of the power system. It is suitable for application on solidly grounded,
industrial installations and utility substations for impedance grounded, Petersen coil grounded and isolated systems.
all levels of voltages.
eSetup
Easergy Pro
DM107148
USB
I1: 0.0A 10 programmable front
I2: 0.0A 3-color LEDs ports
I3: 0.0A
P : 0.0W
Control buttons
V : 0.0V F1 7 Function keys F7
Setting groups:4
Ethernet module - Slot M Slot M Slot M + N
68 Protocols Redundancy RJ45 RJ45 LC LC LC LC
79 99 38
H2/H5 49T
• IEC 61850 protocol:
• Modbus • RSTP OR
• DNP3.0
• Ethernet/IP
SOTF 74 86
OR
Serial module - Slot N Slot N Redundancy
protocols:
50 Protocols Electrical RJ45 RJ45
CLPU ST • HSR
ARC • Modbus connection:
• DNP3.0
OR • PRP
• RS485
• IEC -101 2/4 wires
• IEC -103
De-modulated Modulated
I1 / I2 / I3 Io/I’o V / V0 V4 IRIG-B IRIG-B
Arc sensor:
Other types
See list of
of control Accessories
REL52801
to REL52810
Circuit-btreaker controls
Arc flash sensors
Depends on the configuration
The Easergy P5M30 is more than a conventional protection relay. It offers numerous
Compact, specially developed and designed additional functions suitable and crucial for a wide range of applications, which
for rotating machine, the Easergy P5M30 relays involve protection, monitoring, diagnosis, fault analysis tools, and maintenance aids.
performs an essential role in many industrial
processes and generations for medium and
large sized rotating machines.
eSetup
Easergy Pro
DM107149
USB
I1: 0.0A 10 programmable front
I2: 0.0A 3-color LEDs ports
I3: 0.0A
P : 0.0W
Control buttons
V : 0.0V F1 7 Function keys F7
Setting groups:4
Ethernet module - Slot M Slot M Slot M + N
68 Protocols Redundancy RJ45 RJ45 LC LC LC LC
99 38
H2/H5 49T
• IEC 61850 protocol:
• Modbus • RSTP OR
• DNP3.0
• Ethernet/IP
SOTF 74 86
OR
Serial module - Slot N Slot N Redundancy
protocols:
50 Protocols Electrical RJ45 RJ45
CLPU ST • HSR
ARC • Modbus connection:
• DNP3.0
OR • PRP
• RS485
• IEC -101 2/4 wires
48 • IEC -103
37 66 51LR
Extension module - Slot P
67 37P RJ45
Back-up
memory
RTD1 RTD2 RTD3 RTD4
49 59641
81
Arc board - Slot E RTD5 RTD6 RTD7 RTD8
81U
DI1 DI2 DI3
50BF Arc 1 Arc 2 Arc 3
A A A
DO1 DO2 DO3
59N
50 RTD1 RTD2 RTD3 RTD4
51 6I/4O board - Slot D
67N 59641
27 DI1 DI2 DI3 DI4 DI5 DI6
RTD5 RTD6 RTD7 RTD8
27P
DO1 DO2 DO3 DO4
OR
46 50N
59
46BC 50G 6I/4O board - Slot C
DI1 DI2 DI3 DI4 DI5 DI6
51N
60 60
51G DO1 DO2 DO3 DO4 REL51045
De-modulated Modulated
I1 / I2 / I3 Io/I’o V / V0 IRIG-B IRIG-B
Analog measurement board - Slot A Power Supply - Slot B
Current input Voltage input DI1 DI2 DI3 DI4
Other types
of control
M
Circuit-btreaker controls
Arc flash sensors
Depends on the configuration
97.5 mm
168mm (6.61 in.)
102 mm (3.84 in.)
DM107165
51,8 mm
167.2 mm 180 mm 158 mm
(2.04 in.)
(6.58 in.) (7.08 in.) (6.22 in.)
4 mm (0.16 in.)
in
5.12 ± 0.2
7.09 ± 0.2
More info on installation accesories page 77
8.07 ± 0.2
205 ± 0.5
8.07 ± 0.2
205 ± 0.5
P5x20 P5x30
152.4 mm 149 mm
224mm (8.82 in.)
DM107168
167.2 mm 180 mm
(6.58 in.) (7.08 in.) 158 mm
103.6 mm (6.22 in.)
(4.08 in.)
F1 F2 F3
F4 F5 F6 F7
4 mm (0.16 in.)
5.12 ± 0.2
7.09 ± 0.2
More info on installation accesories page 77
8.07 ± 0.2
205 ± 0.5
P5x30
Optional modules
PM107312
Draw-out design
PM107326
A B C D E A B C
PM107428
PM107490
Rear communication
modules:
operation
All the data required for a local equipment operation may be displayed on demand:
Working languages
All the texts and messages displayed on the Easergy P5 protection relay are
available in two languages: English plus a local language. Files of different
languages can be downloaded from the Schneider Electric website.
PM107302
KEYS
HOME key: return to the previous menu. To LEDS
return to the first menu item in the main menu,
press the button for at least three seconds On (Green)
INFO push-button for viewing additional
information, entering the password view, and !
adjusting the LCD contrast Alarm (Yellow)
6 customizable
DOWN key: move down in the menu tri-color LEDs
or decrease a numerical value
LEFT key: move backwards in a
parallel menu or select a digit in PORTS
a numerical value
USB mini B
RIGHT key: move forwards in a (Computer)
parallel menu or select a digit in
a numerical value USB A
(USB key)
Switchgear control key (OPEN)
LABELS
PM107315
KEYS
DM107153
LEDS
HOME key: return to the previous menu.
To return to the first menu item in the main
menu, press the button for at least three On (Green)
seconds
INFO push-button for viewing additional Alarm (Yellow)
information, entering the password view,
and adjusting the LCD contrast
Trip (Red)
Reset control key
Maintenance
ENTER key: activate or confirm (Yellow)
a function 10 customizable
UP key: move up in the menu tri-color LEDs
or increase a numerical value
Navigation keys
LABELS
DM107154
L1 L1
L2 L2
L3 L3
S1 A9 S1 A9
1/5 A A10 IL1 1/5 A A10
IL1
S1 A11 S1 A11
A12 IL2 A12
IL2
S1 A13 S1 A13
A14 A14
IL3 IL3
A15 A15
1/5 A A16 Std A16 Std
S1 A17 A17
1A VS 1A A18
A18 VS
S1 S1
L1 L1
DM107155
L2 L2
L3 L3
S1 A9 S1 A9
1/5 A A10 IL1 1/5 A A10 IL1
S1 A11 S1 A11
A12 IL2 A12 IL2
S1 A13 S1 A13
A14 IL3 A14 IL3
A15 A15
A16 20 A A16 20 A
CSH
S1
A17 A17
A18 2A CSH A18 2A
S1
L1
DM107156
L2
L3
RJ45 IL1
RJ45 IL2
RJ45 IL3
A1
CSH 20 A
A2
S1
A3
A4 2A
L1
DM107157
DM107158
L1
L2 L2
L3 L3
A1 A1
A2 V1 A2 V1
A3 A3
A4 V2 A4 V2
A5 A5
A6 V3 A6 V3
A7 A7
A8 V4 A8 V4
L1
L2
L3
A1
A2 VL1
A3
A4 VL2
A5
A6 VL3
A7
A8 V4
L1 V4 = VB-VA
L2
or V4=VA
L3
according to setting
LPVT L1
LPVT hub
connector
LPVT L2
LPVT L3
RJ45 V4
I/Os – slot B
DM107161
DM107162
DI1 1 DI1 1
2 2
3 3
DI2 4 DI2 4
5 5
DI3 DI3
6 6
DI4 7 DI4 7
8 8
DO1 9 DO1 H 9
10 10
S
DO2 DO2
11 11
12 12
13 13
DO3 14 DO3 14
15 15
WD 16 WD 16
17 17
18 18
19 19
20 20
DM107164
DI1 1 DI1 1
2 2
slots C, D, E DI2 3
4
DI2 3
4
DI3 DI3 5
5
6 6
DI4 7 DO1 7
8 8
DI5 DO2
9 9
10 10
DI6 11
11
12 DO3 12
13
DO1 13
14 14
DO2 15 15
L> 16
16
17 17
DO3 L>
18 18
19 19
DO4 L>
20 20
6 DI + 4 DO 3 Arc + 3 DI + 3 DO
DI1 to DI6: universal digital inputs DI1 to DI3: universal digital inputs
DO1 to DO4: signaling relay outputs DO1 and DO2: control relay outputs
DO3: signaling relay outputs
3 point light sensor inputs
Electrical characteristics
Power supply
P5x20 24-250 Vdc; 100-230 Vac
Rated voltage
P5x30 48-250 Vdc; 100-230 Vac
Variation -20% / +20%
P5x20 4.4 W
Typical burden
P5x30 5.2 W
P5x20 5.5 W 8 W
Maximum burden
P5x30 To be completed > 10.5 W
Maximum interruption time 100 ms
Energizing inputs
Rated frequency 50/60 Hz
VT inputs
Rated voltage 200 V
Input impedance > 100 kohms
Voltage withstand, continuous 1.2 rated voltage
LPVT inputs (*)
Rated voltage 3.25 V/ 3
Extended rated voltage 0.25 to 1.5 rated voltage
Input impedance 10 MOhms / 15 pF
Thermal withstand 25 V
Digital inputs
Rated voltage 240 V DC or AC
Switching threshold voltage 10 to 200 V, settable
Current drain 1 to 28 mA, settable (1)
(1) According to configuration
(*) Contact us for availability
Relay outputs
Environmental characteristics
Electromagnetic compatibility Standard Level / Class Value
Emission Tests
Conducted emission CISPR 11 Class A 0.15 to 0.5 MHz: 79 dBµV (quasi peak)
CISPR 22 Class A 0.5 to 30 MHz: 73 dBµV (quasi peak)
IACS E10 0.15 MHz to 0.3 MHz: 80 to 50 dBμV/m
Radiated emission CISPR 22 Class A 30 MHz to 230 MHz: 40 dBµV (quasi peak)
0.3 MHz to 100 MHz: 60 to 54 dBμV/m
IACS E10 100 MHz - 2000 MHz, 54 dBμV/m
except for: 156 MHz - 165 MHz, 24 dBμV/m
In operation
Vibrations IEC 60255-21-1 Class 2 1 Gn, 10 Hz to 200 Hz
GOST 17516.1 0,015 mm peak, 0,5 Hz to 57,6 Hz
1 Gn 57,6 Hz to 150 Hz
IACS E10 13.2 Hz to 100 Hz – acceleration ± 0.7 g
Shocks IEC 60255-21-2 Class 2 10 Gn / 11 ms
Earthquakes IEC 60255-21-3 Class 2 2 Gn horizontal / 1 Gn vertical
De-energized
Vibrations IEC 60255-21-1 Class 2 2 Gn ; 10 Hz - 150 Hz
Shocks IEC 60255-21-2 Class 2 30 Gn / 11 ms
Jolts IEC 60255-21-2 Class 2 20 Gn / 16 ms
In storage
Storage conditions -40°C to +85°C (-40°F to +185°F)
Exposure to cold IEC 60068-2-1 Ab -40°C (-40°F) ; 96 h
Exposure to dry heat IEC 60068-2-2 Bb +85°C (+185°F) ; 96 h
Exposure to damp heat IEC 60068-2-78 Cab 93% RH to 95% RH, 40°C (104°F), 56 days
Corrosive atmosphere
Salt mist IEC 60068-2-52 Kb / 1
2 and 4 gas IEC 60068-2-60 Ke • Method 1;
0,5 ppm ; 1 ppm
• Method 4;
–– 0,071 ppm H2S, 0,26 ppm ,
–– 0,034 ppm , 0,11 ppm
IEC 60721-3-3 3C2 21 days
Standard Value
IEC60255-26 CE marking according to:
IEC60255-27 EMC Directive 2014/30/EU
LV Directive 2014/35/EU
UL508 File E354250, NRGU
ANSI/IEEE C37.90
CAN/CSA C22.2 No.14
Set up software 64
eSetup Easergy Pro 64
eSetup Easergy Pro - during engineering 65
eSetup Easergy Pro - during commissioning 65
eSetup Easergy Pro - during operation 65
Web-HMI 66
Mobile application 67
DM105614b
DM105613b
eSetup eSetup
DM105612b
eSetup
Easergy Pro Easergy Pro
Easergy Pro
Use eSetup Easergy Pro in standalone Connect the PC running eSetup Easergy Connect the PC running eSetup Easergy
mode during engineering to prepare the Pro to the USB port of the Easergy Pro to the Ethernet network during
configuration. protection relay during commissioning to operation to retrieve data from the relays
adjust the settings and test the relay. and update the system.
During engineering
EM106160
• Create the configuration of the Easergy P5 relay: select the appropriate options
and receive the order code
• Set the characteristics of the CTs, VTs, or sensors connected to the relay, and
select the protection functions that will be activated and their settings
• Build a specific logic, if required, using a graphic editor
• Map the digital inputs of the relay and different internal signals to the relevant
functions, LEDs, and digital outputs, using a straightforward matrix format.
• Draw the single-line diagram that will appear on the front display of the relay for
switchgear control and select the measurements that will be displayed. If any,
build the interlocking logic using a matrix format
• For IEC 61850 protocol, configure the data set and the report control blocks that
will be published and select the GOOSE data to which you want to subscribe
• Complete the setting of additional functions (disturbance recorder, event logging
system, clock synchronization, etc.).
During commissioning
EM106163
• Connect to the front panel of one single relay or access several relays by
connecting to Ethernet
• Open the Digital Inputs menu to check the status of inputs. Reverse the polarity
or add a filtering delay if necessary
• Open the Relays menu and force the status change of the output relays in order
to check the wiring.
• Open the Phasor Diagram menu to see in real time the phasor of injected
currents and voltages and the value
• Use virtual injection for testing protection settings and circuit breaker tripping
and for checking LEDs and connected outputs
• Open the Logic or the Matrix menu if the logic needs to be tested. The active
signals appear in a different color and are updated in real time. Changes in the
logic or in the matrix can be made and applied to the relay smoothly.
During operation
EM106166
• Connect to the front panel of a single relay or gain access to several relays by
connecting to Ethernet
• During normal operation, get the most of the metering capabilities of the
Easergy protection relay:
–– Open the different Measurements menus to access the power monitoring
and power quality data.
–– Open the disturbance recorder menu to get a waveform capture or program
the recording of a power trend.
• After a trip, use eSetup Easergy Pro to understand the fault:
–– Check the fault log of the protection that has tripped the circuit breaker
–– Download the disturbance record from the Easergy P5 and display it with a
disturbance recorder evaluation tool, eg. Wavewin.
Free download
EcoStruxure Power Device on:
(1) Wi-Fi is not embedded in Easergy P5, a separate Wi-Fi router connected to an Ethernet port of
the device is required.
Mounting accessories 77
Wiring accessories 78
The Ethernet communication module is inserted in the slot M of the device. It can
be selected as an option when ordering the device or purchased later and installed
on site. It is available in 2 versions for copper wire or fiber optic connection.
It provides RSTP (Rapid Spanning Tree Protocol), which allows fast reconfiguration
of the communication system.
Characteristics
Standard 2 ports: 100 Base FX
Baud rate 100 Mbits/s
Fiber type Multimode glass fiber
Wavelength 1300 nm
Ethernet FO module
Connection LC
DANGER
The Ethernet communication module with HSR and PRP redundancy is inserted in
both slots M and N of the device. It can be selected as an option when ordering the
device or purchased later and installed on site. It requires fiber optic connection.
This module includes a 12VDC input for connection of a back-up power supply:
Ethernet HSR/PRP FO module
when the main power supply of Easergy P5 is switched off, the communication
module is still energized and the communication loop is not interrupted.
Characteristics
Standard 2 ports: 100 Base FX
Baud rate 100 Mbits/s
Fiber type Multimode glass fiber
Wavelength 1300 nm
Connection LC
Burden 0.5 W
DANGER
The Serial line communication module is inserted in the slot N of the device. It can
be selected as an option when ordering the device or purchased later and installed
on site. It is available in 2 versions for RS485 or fiber optic connection.
Characteristics
EIA 2-wire RS485 differential
Standard or EIA 4-wire RS485 differential (selection by
configuration)
Line polarization 12V, internally provided
RS485 serial line module
2x RJ45 – pin-out as follows:
1. RXD0
2. RXD1
Connection
4. TXD1 (D1)
5. TXD0 (D0)
8. Common
Note: the REL 51053 accessory is used for line termination. (To be ordered separately)
Characteristics
Fiber type Multimode glass fiber
Wavelength 820 nm
Connection ST
Fiber optic diameter Max attenuation
50/125 µm 5.6
Maximum attenuation
62.5/125 µm 9.4
(fiber optic + connectors)
Fibre optic serial line module 100/140 µm 14.9
DANGER
Extension module
DM101271
The Extension module is inserted in the slot P of the device. It can be selected as an
option when ordering the device or purchased later and installed on site. It provides:
• connection to the external modules
• automatic back-up of data:
–– active configuration file
Extension module
–– disturbance records
–– motor-startup records (when available)
–– sequence of events records
–– power system maintenance data log
–– maintenance data of circuit-breaker, switches, motor and transformer
(whichever available)
Characteristics
Connection RJ45
Specific cables have the following references:
• 59660: length 0.6m
Type of cable
• 59661: length 2m
• 59662: length 4m
Mechanical characteristics
Assembly Symmetrical DIN rail
1.81
5.67
IRIG-B module
REL51045: IRIG-B module
DM107171
The IRIG-B module is an external module used for accurate time synchronization.
It is connected to the extension module. It can be selected as an option when
ordering the device or purchased later and installed on site. The module provides
both a modulated (MOD INPUT) and an unmodulated input (UNMOD INPUT) and
can automatically detect which input type is used by the user. No configuration of
input type is needed in the Easergy P5 protection relay.
Mechanical characteristics
Assembly Symmetrical DIN rail
The specifically designed CSH120, CSH200 and CSH300 core balance CTs are
for direct residual or earth/ground fault current measurement. The only difference
between them is the diameter.
Due to their low voltage insulation, they can only be used on shielded cables.
4 horizontal
4 mounting
horizontal mounting 4 vertical mounting
4 vertical mounting
holes 6 holes 6 holes 6 holes 6
Sensors description
The sensor is used by an arc-flash protection device (Easergy P5 Advanced) or
system to detect the light coming from the arc-flash incident.
The Easergy P5 Advanced arc-flash sensor is activated by strong light. The
sensor transforms the light information into the current signal, which is used by the
protection device to indicate arc-flash.
Arc-flash sensors
REL52801
REL52802
REL52803
REL52804
REL52805
REL52806
REL52807
REL52808
REL52809
REL52810
Characteristics
Material Plastic
Type Standard Pipe
Weight 1,000 g 1,300 g 1,300 g 300 g 400 g 400 g 1,000 g 1,300 g 300 g 400 g
2.20 lb 2.87 lb 2.87 lb 0.66 lb 0.88 lb 0.88 lb 2.20 lb 2.87 lb 0.66 lb 0.88 lb
Cable length (m) 6 20 20 6 6 6 20 20 6 6
Shielded cable - - - - - -
Halogen free - - - - - - - -
Environment Pollution Degree 2
Operation temperature -25°C (-13°F) to +70°C (+158°F)
Light spectrum sensitive area 400 – 1100 nm
Detection time 1 ms
Light sensitivity 8 000 – 10 000 lux
Loop supervision Yes
To connect the interface in the Easergy P5 Standard devices, use REL52883 cable.
mm 22.2
DM105632
in 0.83 20
14 0.79
0.55
0.39
10
25
1.83
46.4
0.98
8
0.31
4.2
0.17
REL52807 - 52810 dimensions
mm 11 62
Sensitivity area
DM105636
in 2.44
0.43
1 2 The Easergy protection relays are available for flush mounting or rack mounting.
DM104076
1 2 1 2
Easergy protection relays may be flush mounting. Dedicated accessories will help
for an easy and quick installation:
mm
Assemble the cross socks flush (1) 130 ± 0.5
in 180 ± 0.5
DM107199
5.12 ± 0.2
and the case (2) 7.09 ± 0.2
8.07 ± 0.2
205 ± 0.5
8.07 ± 0.2
205 ± 0.5
P5x20 P5x30
REL51052: 30TE Flush mounting accessory
mm
130 ± 0.5
in 180 ± 0.5
5.12 ± 0.2
DM107199
7.09 ± 0.2
8.07 ± 0.2
205 ± 0.5
8.07 ± 0.2
205 ± 0.5
P5x20 P5x30
0.5 to 1.5
DM107172
To facilitate the wiring of the terminals in Slots C, D, E of Easergy P5 protection relay, the user can order the following comb-busbars that are
provided in 50-pieces or 100-pieces packs.
Install
Life Cycle Services
Life cycle services Schneider Electric will help you to install more efficient, more reliable and safer
solutions based on your plans:
DM408843
Install Operate
How do I install and commission?
Schneider Electric helps you maximize your installation uptime and control your
capital expenditures through its services offering:
Operate • Asset operation solutions: Provide the information you need to increase
safety, enhance installation performance, and optimize asset maintenance and
How do I operate and maintain?
investment
• Advantage service plans: Customize service plans that include preventive,
predictive and corrective maintenance
Optimize
How do I optimize? • On-site maintenance services: Deliver extensive knowledge and experience
in electrical distribution maintenance
• Spare parts management: Ensure spare parts availability and optimized
Renew maintenance budget of your spare parts
How do I renew my solution? • Technical training: Build necessary skills and competencies to properly and
safely operate your installations
Optimize
When it comes to your electrical Schneider Electric proposes recommendations for improved safety, availability,
distribution installation, we can reliability and quality:
help you: • MP4 electrical assessment: Define an improvement and risk management
• Increase productivity, reliability, and safety program
• Mitigate risk and limit downtime
• Keep equipment up to date and extend
lifespan Renew
• Cut cost and increase savings We extend the life of your system while providing upgrades and offers to take full
• Improve your return on investment responsibility for the end-of-life processing of old electrical equipment:
CONTACT US! • Retrofit: Keep up to date and improve the performance of electrical
installations
https://www.schneider-electric.com/
• MV product end of life: Recycle and recover outdated equipment with end-of-
en/work/services/field-services/
life services
electrical-distribution/
1999
ECOFITTM 2000 2019 2020 2028 (*)
for your MV Switchboard
MiCOM Px20
• Extend your switchgears lifetime Sepam S20 and S40
• Access asset and energy management with
digitization Easergy P5
• Reduce your environmental impact ECOFIT™ solution
• Enhance your process dependability
• Optimize your maintenance service costs and End of full spare parts
limit your investment Sales End of sales availability
• New ECOFIT™ spare parts availability.
(*) Please consult Schneider electric
ECOFIT™ offers:
Sepam S20 Sepam S40 MiCOM Px20 Easergy P5
20TE or 30TE size 20TE or 30TE size
Case Flush mounting Flush mounting
Flush mounting Flush mounting
Installation Fix Fix Withdrawable case Withdrawable case
Language Multilanguage Multilanguage Multilanguage Multilanguage
IEC 61850 Ed.1 & Ed.2
Modbus serial IEC 60870-5-103 & 101
IEC 61850 Station bus
Kbus IEC 60870-5-101 Ethernet
IEC 60870-5-103 IEC 60870-5-103
Courier DNP3 Ethernet
Communication DNP3 DNP3
IEC60870-5-103 DNP3 serial
Modbus serial Modbus serial
DNP3 Modbus Ethernet
Modbus Ethernet
Modbus serial
EtherNet/IP
24 - 250 Vdc 24 - 250 Vdc 24 - 250 Vdc 24 - 250 Vdc
Power supply
48 - 240 Vac 48 - 240 Vac 48 - 240 Vac 100 - 230 Vac
20TE model: 10 LEDs
Control LED 11 LEDs 11 LEDs 8 LEDs
30TE model: 14 LEDs
Cyber security No No No Yes
Arc-flash No No No 30TE model: 0 to 6 sensors
Back up memory No No No Yes
20TE model: 30TE model: 20TE model:
S20 / S24 / T20 / T24 / B21 S40 / S41 / S42 / S43 / P120 / P121 / P122 /P123
/ B22 / M20 S44 / S50 / S51 / S52 / / P921 / P922 / P923 /
Compatibility with S53 / S54 / T40 / T42 / T50 P721 / P723 / P920
/ T52 / M40 / M41 / G40 30TE model:
P126 / P127 / P225 / P521
/ P220 / P125
Green Premium
TM
Easergy P5 configurator 88
Ready-to-use configuration 89
P5x20 ordering variants 89
P5x30 ordering variants 90
Additional modules ordering variants 91
Accessories ordering variants 92
Tools 93
Easergy P5x20 • Please indicate the Part No. (for example: REL50006) to your
ordering variants Schneider Electric correspondant
• For other variants please contact your Schneider Electric
correspondant
REL50331 P5U20-AABA-BABAH-AAAA 24-250V 3CT 2Io 4DI-4DO RSTP Eth RJ45 + extension + CS Level 0
REL50332 P5U20-AABA-CABAH-AAAA 24-250V 3CT 1CSH 4DI-4DO RSTP Eth RJ45 + extension + CS Level 0
REL50333 P5U20-AABB-BABAH-AAAA 24-250V 3CT 2Io 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0
REL50334 P5U20-AABB-CABAH-AAAA 24-250V 3CT 1CSH 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0
REL50339 P5V20-AABA-DABAH-AAAA 24-250V 4VT 4DI-4DO RSTP Eth RJ45 + extension + CS Level 0
REL50340 P5V20-AABB-DABAH-AAAA 24-250V 4VT 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0
Easergy P5x30 • Please indicate the Part No. (for example: REL50006) to your
ordering variants Schneider Electric correspondant
• For other variants please contact your Schneider Electric
correspondant
REL50402 P5F30-AACB-HAAAA-AAAA 48-250V 3CT 1CSH 4VT 10DI-8DO no comm + no extension + CS Level 0
REL50404 P5F30-BACB-GAAAA-AAAA 48-250V 3CT 2Io 4VT 16DI-12DO no comm + no extension + CS Level 0
REL50405 P5F30-BACB-HAAAA-AAAA 48-250V 3CT 1CSH 4VT 16DI-12DO no comm + no extension + CS Level 0
REL50451 P5F30-AACB-GABAH-AAAA 48-250V 3CT 2Io 4VT 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0
REL50452 P5F30-AACB-HABAH-AAAA 48-250V 3CT 1CSH 4VT 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0
REL50453 P5F30-BACB-GABAH-AAAA 48-250V 3CT 2Io 4VT 16DI-12DO RSTP Eth RJ45 + extension + CS Level 0
REL50454 P5F30-BACB-HABAH-AAAA 48-250V 3CT 1CSH 4VT 16DI-12DO RSTP Eth RJ45 + extension + CS Level 0
REL50408 P5M30-AACB-HAAAA-AAAA 48-250V 3CT 1CSH 4VT 10DI-8DO no comm + no extension + CS Level 0
REL50410 P5M30-BACB-GAAAA-AAAA 48-250V 3CT 2Io 4VT 16DI-12DO no comm + no extension + CS Level 0
REL50411 P5M30-BACB-HAAAA-AAAA 48-250V 3CT 1CSH 4VT 16DI-12DO no comm + no extension + CS Level 0
REL50455 P5M30-AACB-GABAH-AAAA 48-250V 3CT 2Io 4VT 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0
REL50456 P5M30-AACB-HABAH-AAAA 48-250V 3CT 1CSH 4VT 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0
REL50457 P5M30-BACB-GABAH-AAAA 48-250V 3CT 2Io 4VT 16DI-12DO RSTP Eth RJ45 + extension + CS Level 0
REL50458 P5M30-BACB-HABAH-AAAA 48-250V 3CT 1CSH 4VT 16DI-12DO RSTP Eth RJ45 + extension + CS Level 0
Communication modules
REL51038 Ethernet TP module - slot M
External modules
59641 8 temperature sensor module (MET148-2)
Sensors
59635 core balance CT, Ø=120mm (CSH120)
EMS59572 VT adapter
Accessories
Qty. Designation
Mounting accessories
REL51032 20TE flush mounting accessory
Wiring accessories
REL51054 2-pin comb-busbar for I/O - 100 pces
contacts
Training
© 2019 Schneider Electric. All Rights Reserved. Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies.
NRJED313567EN - 27th May 2019