EasergyP5 NRJED313567EN 270519 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 94

Powerlogic

Easergy P5

Catalog 2019
Network protection relays

se.com/easergy
Note: Electrical power systems are dangerous, protection relays are defined and governed
by international standards such as IEC 60255 “Measuring relays and protective equipment”
and IEEE C37.97 “Protective relay applications to power systems buses”. Never attempt to
install or operate protection relays or associated equipment without the necessary
qualifications, training and tools. Exposure to electrical arc-flash incidents can be life
threatening, no situation can ever be deemed fully safe. Standards such as NFPA 70E define
important risk categorization and such standards identify both distance from, and energy of
the arc incident to be important factors. In order to reduce the risk category and improve
safety during arc-flash incidents, functionality is available in Easergy P5 protection relays to:
i) to operate electrical panel from a safer distance via wireless communication, and ii) arc-
flash protection functionality to detect and limit the arc energy by tripping the connected
circuit breaker faster than in a conventional protection scheme.
General Contents
PM107471

Easergy P5 Range description 4

Product description 40

Digital experience 62

Additional modules and accessories 68

Services 80

Ordering 84

schneider-electric.com Easergy P5 Catalog | 3


Easergy P5
Range description

4 | Easergy P5 Catalog schneider-electric.com


Easergy P5
Range description
Overview 10

Selection guide 11

Selection guide by functionality 12

Selection guide by application 14


Arc-flash application 14
Feeder / Incomer application 15
Motor application 16
Transformer application 17
Capacitor application 19

Functions and description 20

Communication 36
Examples of architectures 36
Redundancy protocols 37
Data exchanged 38

Cyber security 39
Cyber security systems 39

schneider-electric.com Easergy P5 Catalog | 5


The Easergy P5 at a glance

The Easergy P5 is a protection relay for demanding medium-voltage applications. It offers users dedicated features
for industry-leading protection relay functionality to reduce risks, improve reliability, all with advanced connectivity.
Additionally, it can be used with a range of digital tools that make everyday operations simpler for users. The Easergy
P5 is part of the PowerLogic range of power monitoring and control solutions and has been built on more than 100
years of experience in protection relays, including Sepam, MiCOM, and Vamp, renowned for their reliability and
performance.

Industry-leading protection functions


Built-in arc-flash protection functions (optional)
Nearby control with a mobile application
Latest cybersecurity built in, with IEC 62443 compliance and Achilles certification

Best-in-class reliability
Withdrawable design for quicker maintenance
Backup memory function enabling industry-leading 10 minute recovery time!
Condition monitoring for reduced risk of power outage and maximized equipment life
Extended equipment lifetime when used with EcoStruxure Asset Advisor

Maximized everyday simplicity


Easier operation with digital tools including the EcoStruxure Power Device app
Powerful communication with plug and play ports and seven protocols supported
Scalable hardware making it easy to upgrade as your applications evolve

6 | Easergy P5 Catalog schneider-electric.com 6


Enjoy a package of sought-after
features in one device

The Easergy P5 presents a major step forward for protection relays,


bringing a number of best-in-class features together in one device.

Built-in arc-flash protection functions


Arc-flashs will always exist when switching or during unexpected conditions.
Arc-flash protection functions detect if an arc-flash exists, and take action
within milliseconds to isolate the connected circuit breaker, meaning that
arc-flash energy should not grow and cause unexpected outages or risks.

Advanced cybersecurity
IEC 62443 compliant, the P5 has been designed with an optional
cybersecurity package. This means reduced exposure to cyber threats
and improved operational security. By default, the Easergy P5 includes
important features such as password management, port hardening, and
secured communication compliant to the latest international standards.

Intuitive withdrawable design


With a handle built in as part of the design, the P5 can be quickly
disconnected or exchanged to speed up maintenance. Wiring, data,
communication, and settings (including backup) can be stored with the
panel and will be there when the relay is reconnected.

Improved recovery time


When maintenance or testing is required, Easergy P5 helps dramatically decrease your outage recovery time. The backup
memory can automatically restore settings, you can continue your operations in as little as 10 minutes.*
*Result of mean time to repair (MTTR) calculation conducted by Schneider Electric

Greater connectivity
The protection relay features seven communication protocols. This includes compliance with IEC 61850 ed. 1 and ed. 2,
Modbus (serial/TCP), IEC 60870-5-103, IEC 60870-5-101, Ethernet/IP, and DNP3 (serial/TCP). Additionally, thanks to the P5’s
modular design, communication ports can be added at any time to enable you to upgrade your device in line with future
network evolutions.

schneider-electric.com Easergy P5 Catalog | 7


Make everyday operations
easier with digital tools
The Easergy P5’s industry leading protection features are complemented by a comprehensive set of tools
available on mobile devices such as smartphones or tablets, and desktop computers. This means you get
simpler installation, configuration, and maintenance, enabling you to save time and money. Nearby control
and monitoring allows users to fully operate the device via wireless communication, from a safer distance.

Digital tools for the Easergy P5 include:


The EcoStruxure Power Build – Medium Voltage online ordering tool for quicker and easier ordering
The eSetup Easergy Pro software with virtual injection testing
An embedded web server, allowing easy and fast settings changes
The EcoStruxure™ Power Device app for simpler and safer operation and maintenance
The mySchneider app, a simple way to access support and product data just by flashing the QR code
on the device

As an EcoStruxure-ready solution, the Easergy P5’s digital benefits can be taken even further with best-in-class
monitoring of substation equipment health. For example, when paired with EcoStruxure Asset Advisor
software, users get data for predictive maintenance, which helps them reduce OpEx, speed up processes,
and boost efficiency.

8 | Easergy P5 Catalog schneider-electric.com


Take the Easergy P5 further
with EcoStruxure
450 000
EcoStruxure, Schneider Electric’s IoT-enabled, open and interoperable
architecture and platform, brings together Connected Products, Edge
Control, and Apps, Analytics & Services. EcoStruxure connected products
EcoStruxure systems deployed since
deliver enhanced value around safety, reliability, efficiency, sustainability, 2007 with the support of our 9,000
and connectivity. system integrators

EcoStruxure ready

Efficient asset management 24/7 connectivity Enhanced safety


Boost your efficiency and Make better informed decisions Advanced features designed-in
reduce downtime using with real-time data that’s based on well-known designs,
predictive maintenance tools available everywhere, anytime experience and technology

EcoStruxure™ Architecture

Building Data Center Industry Infrastructure

Apps, Analytics & Services


Cybersecurity

Cloud and/or
On Premise
End to End

Edge Control

Connected Products

EcoStruxure EcoStruxure EcoStruxure EcoStruxure EcoStruxure EcoStruxure


Power Building IT Machine Plant Grid

schneider-electric.com Easergy P5 Catalog | 9


Easergy P5 Overview
Range description

Easergy P5 protection relay is based on proven technology concepts and developed in close cooperation with customers,
so it’s built to meet your toughest demands. It’s available in two sizes to best fit your needs:
• The Easergy P5 features a modular design that allows user-defined conventional protection and arc-flash protection solution
• The Easergy P5 embeds latest cybersecurity functionality to prevent intentional miss-use and cyber-attacks.
• The Easergy P5 enables fast replacement with enhanced safety thanks to the withdrawability and the back-up memory that automatically
restore parameters without using any configuration tool.

Easergy products are designed to be user friendly, a feature that is proven in our customer reports day after day. You’ll
benefit from features that include:
• A complete set of protection functions, related to the application
• Arc-flash detection in P5x30 models
• Dedicated circuit breaker control with single-line diagram, push buttons, programmable function key and LEDs, and a customizable alarm
• Multilingual HMI for customized messaging
• Settings tool relay management software for setting parameters, configuring, and network fault simulation
• Both serial and Ethernet communication, including redundancy
• IEC 61850 standard Ed.1 & Ed.2

Easergy P5 is a family of digital protection relays for distribution


networks dedicated to:
• Critical buildings and Industry: • Large sites:
–– Healthcare –– Oil and Gas
–– Transportation –– Mining
–– Industrial buildings –– Mineral and Metals
PM107437

PM107451

–– Data Center –– Water


• Utilities - Energy distribution

Range overview
DM107110

P5U20 P5L30 P5F30 P5M30


Universal Directional & Line diff. Feeder Motor

P5T30
Transformer P5U20
differential
P5G30 Universal
Generator

T U L L F U
G U U U U
M

U U
G

T U L L U M
G

10 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Selection guide
Range description

Easergy P5x20 Easergy P5x30

Easergy P5 contains two main devices, each

DM107111

DM107112

DM107113
with specific functions to address your needs
in a one-box design, regardless of application.

Voltage P5V20 - -
Feeder P5F30 with directional
Transformer - P5U20 -
Motor P5M30
Characteristics
1/5A CT (x3) (*)
Phase current - 1/5A CT (x3)
or LPCT (x3) (*)
1/5A CT & 1A CT 1/5A CT & 1A CT
Measuring inputs Residual current -
or CSH or CSH
VT (x4) (*)
Voltage VT (x4) -
or LPVT (x4) (*)
Arc-flash sensor inputs - 0 to 6 point sensors
Inputs 4 to 10 4 to 22
Digital
Outputs 3 to 7 + WD 3 to 15 + WD
Inputs - -
Analog
Outputs - -
Temperature sensor input - 0 to 16 (external module) 0 to 16 (external modules)
Front ports USB device and USB host USB device and USB host
Nominal Power Supply 24-250 VDC ; 100-230 VAC 48-250 VDC ; 100-230 VAC
Ambient temperature, in service -40 to 70°C (-40 to 158°F) -40 to 70°C (-40 to 158°F)
Communication
Extension + Backup memory
Serial
Ethernet
2nd Ethernet -
IEC 61850 Ed.1 & Ed.2
IEC 60870-5-103 & 101
DNP3 Ethernet
Protocols DNP3 serial
Modbus Ethernet
Modbus serial
EtherNet IP
Redundancy RSTP
protocols PRP / HSR
Others
6 controlled + 2 monitored objects 6 controlled + 2 monitored
Control
Mimic objects Mimic
Logic (Matrix + Logic Equations)
Cyber security
Draw-out device
102/176/219 mm 152/176/219 mm
Hardware dimensions (H/W/D)
4.01/6.93/8.62 in 6.0/6.93/8.62 in

(*) Contact us for availability

schneider-electric.com Easergy P5 Catalog | 11


Easergy P5 Selection guide by
Range description functionality

ANSI Logical
Protection Functions P5V20 P5U20 P5F30 P5M30
code Node
Current protection
Phase overcurrent 50/51 OCPTOC - 3 3 3
Earth/ground fault overcurrent (1) 50N/51N EFPTOC - 5/8 5/8 5/8
Directional phase overcurrent 67 DOCPTOC - - 4 4
Directional earth/ground fault overcurrent 67N DEFPTOC - - 3 3
Transient intermittent/ground fault 67NI IOIOPTEF - - 1 -
Negative sequence overcurrent 46 (I2/I1) NEGPTOC - 1 1 1
Current unbalance, Broken conductor 46BC (I2) UIBCPTOC - 1 1 -
Breaker failure 50BF CBFPPIOC 1 1 1 1
Phase undercurrent 37 UCPTUC - 1 - 1
Switch on to fault (SOTF) SOFT - 1 1 1
Cold load pickup (CPLU) CLP - 1 1 1
Voltage protection
Undervoltage 27 UVPTUV 3 - 3 3
Overvoltage 59 OVPTOV 3 - 3 3
Earth/ground fault overvoltage 59N UOPTOV 3 - 3 3
Frequency protection
Over and/or underfrequency 81 OFUFPTOF 2 - 2 2
Underfrequency 81U UFPTUF 2 - 2 2
Rate of change of frequency 81R DFDTPFRC 2 - 2 -
Thermal protection
Thermal overload 49 THFPTTR - 1 1 1
Temperature monitoring 38/49T RTDGAPC - 16 16 16
Power protection
Wattmetric earth/ground fault 32N EFPDOP - - 2 2
Directional active underpower 37P REVPPDOP - - 2 2
Rotating machine protection
Frequent start inhibition 66 FSTPMRI - 1 - 1
Excessive start time, locked rotor 48/51LR STALPMSS - 1 - 1
Positive sequence undervoltage 27P UVPSPTUV 2 - - 2
Line protection
FLRFLO/
Fault locator 21FL - - 1 -
SCRFLO
Auto-Recloser 79 ARRREC - 1 1 -
Transformer protection
Magnetizing inrush detection 68H2 HAR2PTOC - 1 1 1
Fifth harmonic detection 68H5 HAR5PTOC - 1 1 1
Capacitor protection
Capacitor bank unbalance 51C - 2 2 -
Capacitor overvoltage 59C - 1 1 -
Other protection
Arc-flash detection 50ARC ARCMPIOC - - 8 8
Programmable stages 99 PSGAPC 8 8 8 8
Programmable curves 3 3 3 3
Control, monitoring, supervision
Synchronization check 25 RSYN 1 - 1 -
Lockout relay 86 1 1 1 1
CT supervision 60 CTSGGIO - 1 1 1
VT supervision 60 VTSGGIO 1 - 1 1
LLN0/SP.SG-
Setting groups 4 4 4 4
CB

12 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Selection guide by
Range description functionality

Control functions P5V20 P5U20 P5F30 P5M30


Switchgear control and monitoring 6 6 6 6
Switchgear monitoring only 2 2 2 2
Programmable switchgear interlocking
Local control on single-line diagram
Local control with O/I keys
Local/remote function
Function keys 1 1 7 7
Custom logic (logic equations)
Control with Smart App

Measurement functions P5V20 P5U20 P5F30 P5M30


RMS current values
RMS voltage values
RMS active, reactive and apparent power
Frequency
Fundamental frequency current values
Fundamental frequency voltage values
Fundamental frequency active, reactive and apparent power values
Power factor
Energy values active and reactive
Demand values: phase currents
Demand values: active, reactive, apparent power and power factor
Maximum demand values: phase currents
Minimum and maximum demand values: RMS phase currents
Minimum and maximum demand values:
active, reactive, apparent power and power factor
Maximum demand values over the last 31 days and 12 months:
active, reactive, apparent power
Minimum demand values over the last 31 days and 12 months:
active, reactive power
Maximum and minimum values: currents
Maximum and minimum values: voltages
Maximum and minimum: frequency
Maximum and minimum:
active, reactive, apparent power and power factor
Harmonic values of phase current and THD
Harmonic values of voltage and THD
Voltage sags and swells

Logs and records P5V20 P5U20 P5F30 P5M30


Sequence of event record
Disturbance record
Tripping context record
Relay maintenance data log
Security data log

Monitoring functions ANSI code P5V20 P5U20 P5F30 P5M30


Trip circuit supervision 74 1 1 1 1
Circuit breaker monitoring 1 1 1 1
Relay monitoring

schneider-electric.com Easergy P5 Catalog | 13


Easergy P5 Selection guide by application
Range description Arc-flash application

Busbar arc-flash protection


• Arc-flash protection, activated by overcurrent and light signals, or light signals alone
Centralized busbar arc-flash protection De-centralized busbar arc-flash protection
DM107114

DM107115
P5F30 P5F30

P5F30 P5F30

• Up to 6 light point sensors to monitor the busbar • Up to 6 light point sensors in each relay
• Transmission of light detection signals via digital I/O or
IEC 61850 GOOSE messages

Zone arc-flash protection


• Up to 8 arc-flash protection stages in each relay
• Transmission of signals via digital I/O or IEC 61850 GOOSE messages

In this application example, the arc-flash sensor for zone 3.1 is


DM107116

Zone 1
light detection signal
connected to Device 1. If the arc-flash sensor awakens and simul-
taneously Device 3 sends a current signal, the zone 3.1 is isolated
P5F30
by the outgoing feeder breaker.
DEVICE 3

Zone 1
The arc-flash sensor for zone 3.2 is connected to Device 2 and
operates the same way.

The arc-flash sensors for zone 2 are connected to Device 1, 2, or 3.


Zone 2
If a sensor awakens in zone 3, the light-only signal is transferred to
Device 3, which then trips the main circuit breaker.
P5F30 P5F30
DEVICE 1 DEVICE 2 An eventual arc-flash fault in zone 1 does not necessarily activate
the current element in Device 3. However, arc-flash detection can be
Zone 3.1 Zone 3.2 achieved by using the light-only principle. If an arc-flash occurs in
cable termination, zone 1, an inter-trip signal is sent by Device 3 to
the upstream circuit breaker.

14 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Selection guide by application
Range description Feeder / Incomer application

Outgoing protection
• Feeder overcurrent protection
• Feeder overload protection
Feeder protection Overhead line protection Protection of feeders with metering
DM107117

DM107118

DM107119
P5U20 P5F30
P5F30 P5F30

• Feeder earth/ground fault overcurrent • Directional phase and earth/ground fault • Power and energy measurement
overcurrent • Min and max demand values over the last
• Recloser 31 days and 12 months
• Fault locator

Incomer protection
• Busbar overcurrent protection
Incomer protection without voltage monitoring Incomer protection with voltage and frequency monitoring
DM107120

DM107121

P5U20 P5F30 P5F30

• Earth/ground fault overcurrent • Under/over voltage


• Frequency, rate of change of frequency
Incomer protection with power quality monitoring Parallel incomer protection
DM107122

DM107123

P5F30

P5F30 P5F30

• Voltage and frequency min and max values • Directional phase overcurrent
• Voltage harmonic values and THD • Directional earth/ground fault overcurrent
• Voltage sags and swells

schneider-electric.com Easergy P5 Catalog | 15


Easergy P5 Selection guide by application
Range description Feeder / Incomer application

Voltage monitoring
• Under/over voltage protection
• Earth/ground fault overvoltage
• Under/over frequency protection

DM107124
P5V20

• Load-shedding-specific function: rate of change of frequency

Selection guide by application


Motor application

Motor protection
• Motor overcurrent and earth/ground fault overcurrent
• Thermal overload
• Motor start-up supervision
• Motor restart inhibition
Motor protection without voltage monitoring Motor protection with voltage monitoring
DM107125

DM107126

P5U20 P5M30 P5M30

RTD RTD
module module

• Temperature measurement (stator, bearings) • Undervoltage protection

16 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Selection guide by application
Range description Transformer application

Transformer feeder protection


• Transformer overcurrent and earth/ground fault overcurrent protection
• Thermal overload protection
• External trip from thermostat/Buchholz
Transformer feeder protection without voltage monitoring Transformer feeder protection with voltage monitoring
DM107127

DM107128
P5U20 P5F30 P5F30

26 26
63 63
49T

RTD
module

• Temperature measurement (ambient, oil) • Over and undervoltage protection

Transformer feeder protection with additional current measurement


DM107130
DM107129

P5F30 P5F30

26 26
63 63
49T 49T

• Tank earth/ground leakage protection • Earth/ground fault overcurrent on the secondary side

schneider-electric.com Easergy P5 Catalog | 17


Easergy P5 Selection guide by application
Range description Transformer application

Transformer incomer protection


• Busbar overcurrent protection
• Inter-trip from primary CB protection
Transformer incomer protection without voltage monitoring Transformer feeder protection with
voltage monitoring
DM107131

DM107132

DM107133
P5U30
P5U20 P5F30 P5U20 P5F30
P5F30

• Transformer earth/ground fault overcurrent • Earth/ground fault overcurrent for • Over and undervoltage protection
transformer and back-up protection • Power and energy measurement
• Min and max demand values over the last
31 days and 12 months

Parallel transformer incomer protection


DM107134

P5F30 P5F30

• Directional phase overcurrent

18 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Selection guide by application
Range description Capacitor application

Capacitor bank protection


• Capacitor bank overcurrent and earth/ground fault protection
• Capacitor bank overload protection
Capacitor bank protection without Capacitor bank protection with voltage Protection of harmonic filters
voltage monitoring monitoring
DM107135

DM107136

DM107137
P5U20 P5F30
P5F30 P5F30

P5U20

• Capacitor overvoltage protection, based on • Capacitor bank unbalance • Overvoltage


current measurement and harmonics • Overvoltage • Capacitor bank unbalance
• Current harmonic values and THD • Current and voltage harmonic values • Capacitor overvoltage protection, based
and THD on current measurement and harmonics
• Current harmonic values and THD

schneider-electric.com Easergy P5 Catalog | 19


Easergy P5 Functions and description
Range description

Fault locator - ANSI 21FL


The function can be used to locate a short-circuit fault and an earth/ground fault in radially operated networks.
The fault location is given as in reactance (ohms) and kilometers or miles. The fault value can then be exported,
for example, with an event to a Distribution Management System (DMS). The system can then localize the fault. If
a DMS is not available, the distance to the fault is displayed as kilometers and as a reactance value.

Functions Settings
Pick-up setting [xIn] 0.10 to 5.00
Line reactance 0.010 to 10.000 Ohm / km
Earth/ground factor 0.000 to 10.000
Earth/ground factor angle -60° to +60°

Synchro-check - ANSI 25
This function checks the phase-phase voltages on both sides of CB and allows CB closing when the voltage
phase angle, magnitude, frequency differences are all within permitted limits.
• 7 operation modes about no-voltage condition (dead line, dead bus) are provided.
• Synchronous mode is provided, where the frequency difference is less than 0.3Hz.
• Asynchronous mode is provided, where CB close time is compensated.
• Independent settings for voltage phase angle, magnitude, frequency differences.

Functions Settings
Synchronization mode Off, Async, Sync
Voltage check mode DD, DL, LD, DD/DL, DD/LD, DL/LD, DD/DL/LD
CB close time 0.04 to 0.6s
UDEAD limit setting 1% to 120% Un
ULIVE limit setting 1% to 130% Un
Frequency difference 0.01 to 1.0Hz
Voltage difference 1% to 60% Un
Phase angle difference 2º to 90º
Request timeout 0.1 to 600s

Under voltage - ANSI 27


This function is applied to detect the abnormal system voltage decrease to trigger the automatic load shedding
or voltage source transfer or trip out the motor loads to avoid motor stall. This protection works with the minimum
phase to phase voltage.
• 3 independent stages with define time are provided.
• Low voltage self-blocking will operate when the maximum phase to phase voltage is less than 10%Un.

Functions Settings Time delay


Under voltage Off, Async, Sync
Trip: 0.04 to 300 s
Pick-up setting 20% to 120% Un
Reset1: 0.3 to 300 s
Reset ratio 0.1% to 20%

Note1: the reset time delay setting is only available for stage 1

20 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Functions and description
Range description

Positive sequence under voltage - ANSI 27P


This function is applied to detect the insufficient or unbalanced system voltage and detect the reverse rotation.
• 2 independent stages with define time are provided.
• Low voltage self-blocking will operate when the positive sequence voltage is less than 10% Un.

Functions Settings Time delays


Pick-up setting 20% to 120% Un 0.08 to 300 s
Low voltage self-blocking 2% to 100% Un

Directional power - ANSI 32


This function can be used as underpower protection (e.g. loss of load of a motor) or as reverse power protection
(e.g. power generation by a motor if supply is disconnected). It starts if measured active power drops below the
set threshold and operates with definite time delay.
• 2 independent stages
• Undervoltage blocking if maximum voltage is less than 5% Un.

Functions Settings Time delay


Pick-up setting -200% to 200% Sn (1)
0.3 to 300.0 s

(1) Sn = √3 Un In

Wattmetric earth/ground fault - ANSI 32N


This function detects single phase to earth/ground faults in Petersen coil compensated power systems. It
operates on active residual power. Using memory mode allows also operation on intermittent earth/ground faults.
• Neutral displacement voltage U0> element to enable function.
• Settable forward/reverse direction.
• Operating characteristic with settable minimum active power and sector angles.
• Dedicated blocking input.
• Dedicated input to bypass operate time delay.

Functions Settings Time delay


Direction mode Direction mode
Pick-up setting I0U0> Pick-up setting I0U0> 0.05 to 300.00 s
U0> setting U0> setting
Sector angle setting Sector angle setting
Memory mode Memory mode
Memory U0> Memory U0> Mem. hold time: 0.05 to 10.00 s
Mem. oper. Time: 0.00 to 100.00 s
SOL operation SOL operation
SOL operation delay SOL operation delay 0.05 to 300.00 s

schneider-electric.com Easergy P5 Catalog | 21


Easergy P5 Functions and description
Range description

Phase undercurrent - ANSI 37


This function is typically used to detect defects in motor drives based on loss of load detection because of
significant drop of current. It measures the fundamental component of the phase currents.
• One stage.
• Low-current blocking if maximum current is less than 15% In.

Functions Settings

Temperature monitoring - ANSI 38


This function is used to detect abnormal heat rise by directly measuring the temperature inside equipment
(transformer, motors, generators, …) with RTD sensors.
• Two independent set points: alarm and tripping.
• Inbuilt RTD supervision (shorting, open loop).

Functions Settings
Pick-up setting 0 to 180 °C (32 to 356 °F)

Unbalance overcurrent - ANSI 46


This function provides greater sensitivity to detect phase to phase faults at the end of long lines or behind
transformer. It can also be used for machine protection (against temperature rise caused by unbalance power
supply, phase inversion, or loss of phase).
• One stage.
• DT or IDMT operating time.

Functions Settings Time delay


Pick-up setting 0.02 to 5.00 In 0.07 to 300.00 s
Delay curve family IEC, IEEE, IEEE2,RI, programmable (prg.)
Delay type IEC: NI, VI, EI, LTI, Parameters
IEEE: VI, EI, LTI, LTEI, LTVI, MI, STI, STEI, Parameters
IEEE2: NI, VI, EI, MI, Parameters
RI: RI, RXIDG
Prg.: configurable using constant A, B, C, D, E
in delay function
Inv. time coefficient k 0.05 to 20.0 for IEC and RI
0.50 to 20.0 for RXIDG, IEEE and IEEE2

22 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Functions and description
Range description

Unbalance overcurrent, broken conductor - ANSI 46BC


This function is applied to detect the broken conductor condition, based on the ratio between the negative
sequence current and the positive sequence current.
• 1 stage with define time is provided.
• Low voltage self-blocking will operate when the positive sequence voltage is less than 10%Un

Functions Settings Time delay


Pick-up setting I2/I1 > 2% to 70% 0.07 to 300s

Excessive start time - ANSI 48


Protection of motors against overheating caused by motor excessive start time due to heavy motor load or too
low voltage.
• Motor start detection is based on “Current” or “CB Position” or “Both”.
• Operation with definite time delay or inverse time delay.

Functions Settings Time delay


Motor start detection current 1.3 to 10.0In
CB position detection mode CBPos, Current, CBPos&Cur
Delay type DT, INV
Motor start time 1 to 300.0s

schneider-electric.com Easergy P5 Catalog | 23


Easergy P5 Functions and description
Range description

Thermal overload protection for feeder - ANSI 49F


This function is applied to detect conditions where thermal damage may be caused by overloads on cables. The
thermal capacity is calculated by the thermal replica according to IEC60255-149. The equivalent current for the
thermal replica is the maximum RMS current of 3 phases.
• Independent settable alarm stage and trip stage are provided.
• Current based setting mode and temperature based setting mode are provided.
• Temperature sensor can be applied for ambient temperature under temperature based mode.
• A digital input can be applied to inhibit the thermal overload protection.

Functions Settings
Basic current setting 0.1In to 4.0In
Factor k 1.0 to 1.5
Heating time constant 1.0 min to 1000 min
Thermal alarm value 50% to 100%
Reserve time thermal alarm 1.0 min to 1000 min
Temperature based mode Current, Ambient
Nominal ambient temperature -40ºC to 300ºC
Max object temperature -40ºC to 300ºC
Alarm object temperature 0ºC to 300ºC
Min object temperature -40ºC to 300ºC
Default object temperature -40ºC to 300ºC
Thermal level initiation 0 to 90%

24 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Functions and description
Range description

Thermal overload protection for motor - ANSI 49M


This function is applied to detect conditions where thermal damage may be caused by overloads on cables. The
thermal capacity is calculated by the thermal replica according to IEC60255-149. The equivalent current for the
thermal replica considers the maximum RMS current of 3 phases and the negative phase sequence current with
a settable weighting coefficient.
• Independent settable alarm stage and trip stage are provided.
• Heating time constant and cooling time constant are provided.
• Current based setting mode and temperature based setting mode are provided.
• Temperature sensor can be applied for ambient temperature under temperature based mode.
• A digital input can be applied to inhibit the thermal overload protection.

Functions Settings
Basic current setting 0.1In to 4.0In
Factor k 1.0 to 1.5
Heating Time constant 1.0min to 1000min
Time constant for motor start 1.0min to 1000min
Cooling time constant 1.0min to 1000min
Thermal alarm value 50% to 100%
Reserve time thermal alarm 1.0min to 1000min
Temperature based mode Current, Ambient
Nominal ambient temperature -40ºC to 300ºC
Max object temperature -40ºC to 300ºC
Alarm object temperature 0ºC to 300ºC
Min object temperature -40ºC to 300ºC
Default object temperature -40ºC to 300ºC
Thermal level initiation 0 to 90%

schneider-electric.com Easergy P5 Catalog | 25


Easergy P5 Functions and description
Range description

Arc-flash - ANSI 50ARC


This function is used to detect and minimize the effects of an internal arcing fault by using e.g. circuit breaker
(CB) to mitigate the fault.
• Eight independent arc-flash stages
• GOOSE communication
• 3 to 6 arc-flash sensors available.

Functions Settings
I>int. On, Off
Io>int. On, Off
GOOSE NI On, Off
Virtual output 1 to 6 On, Off
Arc-flash stage 1 to 8 On, Off
Pick-up setting, I>Int. [xIn] 0.50 to 8.00
Pick-up setting, Io>Int. 0.10 to 5.00
Trip delay [ms] 0 to 255
Hold time [ms] 20 to 2500

Breaker failure - ANSI 50BF


The circuit breaker failure function (CBF) can be used to operate any upstream circuit breaker (CB) if the
programmed output matrix signals, selected to control the main breaker, have not disappeared within a given
time after the initial command.
• Two circuit breaker controls.

Functions Settings Time delay


Pick-up setting [xIn] 0.02 to 4.00
Pick-up setting [xIn] 0.05 to 4.00 Io< for CHS
0.02 to 4.00 Io< for CT
0.002 to 4.00 Io< for VSEF
Time 1,2 operation delay 0.02 to 50 s

Switch onto fault (SOTF) - ANSI 50HS


This function is applied to provide the fast trip based on the instantaneous overcurrent protection, out when the
CB is closed against a faulty line.
• 1 stage instantaneous overcurrent is provided.
• CB Open/Dead line detection is based on the low current threshold 0.02In or digital input.
• SOFT active duration after CB closure is settable.

Functions Settings Time delay


Pick-up setting 1.0 to 40.0In
Dead line detection delay 0 to 60.0s
SOFT active time 0.1 to 60.0s

26 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Functions and description
Range description

Phase overcurrent I> or I>> or I>>> - ANSI 50/51


These functions can be used against short circuit faults and heavy overloads. The overcurrent function measures
the fundamental frequency component of the phase currents. The protection is sensitive to the highest of the
three phase currents. Whenever this value exceeds the user’s start setting of a particular stage, this stage starts
and a start signal is issued. If the fault situation remains on longer than the operation delay setting, a trip signal
is issued.
• Overcurrent protection sensitive to the highest phase current measured
• Three independent stages
• Four setting groups on each.

I> Functions Settings


Pick-up setting [xIn] 0.05 to 20.00
Delay curve family DT, IEC, IEEE, IEEE2, RI, Prg1, Prg2, Prg3
Delay type DT, NI, VI, EI, LTI, LTEI,
LTVI, MI, STI, STEI, RI,
RXIDG, Parameters, -
Operation delay [s] 0.03 to 300.00
Inv. time coefficient 0.05 to 20.00
Reset time [s] 0.03 to 100.00

I>> Functions Settings


Pick-up setting [xIn] 0.10 to 20.00
Delay curve family DT, IEC, IEEE, IEEE2, RI, Prg1, Prg2, Prg3
Delay type DT, NI, VI, EI, LTI, LTEI,
LTVI, MI, STI, STEI, RI,
RXIDG, Parameters, -
Operation delay [s] 0.03 to 300.00

I>>> Functions Settings


Pick-up setting [xIn] 0.10 to 40.00
Operation delay [s] 0.03 to 300.00

schneider-electric.com Easergy P5 Catalog | 27


Easergy P5 Functions and description
Range description

Earth/ground fault overcurrent - ANSI 50N/51N


Earth/ground fault protection is based on the measured residual current from 1A/5A standard CT or CSH CT.
Alternatively, it can also apply the calculated residual current.
• 2 independent stages with definite time or IDMT or customized curves. Another 3 stages with definite time
• 18 IDMT curves include IEEE, IEEE2, IEC, RI standardized IDMT curves and 3 customized curves.
• Inrush blocking, Cold load pick-up, Selective overcurrent logic are settable in the first 4 stages.

Functions Settings
I0 input I0, I0 CSH, I0 calc,
Pick-up setting 0.02 Ino to 10 Ino for measured input with EF CT
0.02 Ino to 10 Ino for measured input with CSH CT
0.05 In to 20 In for calculated I0
Delay curve family DT, IEC, IEEE, IEEE2, RI, Prg1, Prg2, Prg3
IDMT delay type IEC: NI, VI, EI, LTI
IEEE: VI, EI, LTI, LTEI, LTVI, MI, STI, STEI
IEEE2: NI, VI, EI, MI
RI: RI, RXIDG
DT Operation delay 0.03 to 300s
Inv. Time coefficient k 0.05 to 20.0 for IEC, RI curves
0.5 to 20.0 for RXIDG, IEEE and IEEE2 curves
Reset time 0.03 to 100s
Inrush blocking Off, On
SOL Enable Off, On
SOL operation delay 0.03 to 300s
SOL Inv. Time coefficient k 0.05 to 20.0 for IEC, RI curves
0.5 to 20.0 for RXIDG, IEEE and IEEE2 curves
CLP Enable Off, On
CLP pick-up value 0.02In to 20.0In
CLP operation delay 0.03 to 300s
CLP Inv. Time coefficient k 0.05 to 20.0 for IEC, RI curves
0.5 to 20.0 for RXIDG, IEEE and IEEE2 curves

28 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Functions and description
Range description

Capacitor bank unbalance - ANSI 51C


This function is used in double-wye-connected capacitor banks. The unbalance current is measured with a
dedicated current transformer (like 5A/5A) between two starpoints of the bank.
• Standard earth/ground fault CT
• CHS core balance CT.

Functions Settings Time delay


Pick-up setting [pu] 0.02 to 10.00
Operation delay [s] 0.03 to 300 DT

Locked rotor - ANSI 51LR


Protection of motors against overheating caused by motor rotor jam due to heavy motor load or a mechanical
failure after the normal start.
• Operation with definite time delay or inverse time delay.
• Automatically blocked when the motor is starting.

Functions Settings Time delay


Pick-up setting 10% to 100.0%Istart
Delay type DT, INV
Operation delay 1 to 300.0s

Overvoltage - ANSI 59
This function is applied to detect the abnormal higher system voltage or to check sufficient voltage for voltage
source transfer. This protection works with the maximum phase to phase voltage.
• 3 independent stages with define time are provided.

Functions Settings Time delays


Pick-up setting 50% to 150% Un Trip: 0.04 to 300s
Reset1: 0.03 to 300s
Reset ratio 0.1% to 20%

schneider-electric.com Easergy P5 Catalog | 29


Easergy P5 Functions and description
Range description

Capacitor overvoltage - ANSI 59C


This function calculates the voltages of a three-phase Y-connected capacitor bank using the measured currents
of the capacitors. No voltage measurements are needed.
Especially in filter applications, there are harmonics and depending on the phase angles, the harmonics can
increase the peak voltage. This protection function calculates the worst-case overvoltage in per-unit values using
Equation 7.10 according to IEC 60871-1 standard. Harmonics up to 15th are taken into account.
• 3 independent stages with define time.

Functions Settings Time delays


Pick-up setting UC> 0.10 to 2.50 UCLN 1.0 to 30.0 s
Rated L-N voltage UCLN 100 to 260000 V
Capacitance per phase 1.00 to 650.00 μF

Neutral voltage displacement - ANSI 59N


This function is used for general earth/ground fault detection and for (un)selective backup protection. It
measures the fundamental component of the neutral displacement voltage.
• 3 stages with DT operating time
• Attenuation of the third harmonic by more than 60 dB
• Faster high-set stage U0>>>.

Functions Settings Time delays


Pick-up setting 2% to 120% Un0 0.04 to 300.00 s

Motor restart inhibition - ANSI 66


This function prevents too frequent motor starts according to the definitions of the motor manufacturer, because
every motor start heats it up considerably because the initial currents are significantly above the rated current.
• Settable number of starts per hour
• Settable minimum time between consecutive starts

Functions Settings Time delay


Time from motor start 0 min, 120 min
Max. hot starts / hour 1 to 20
Max. cold starts / hour 1 to 20
Min. time between starts 0.0 to 100.0 min

30 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Functions and description
Range description

Directional phase overcurrent - ANSI 67


This function provides directional short circuit protection.
• 4 independent stages, all with DT, 2 alternatively with IDMT operating time
• Settable directionality
• Directional voltage memory (3.2 s)
• Cold Load Pickup (CLP) and inrush current handling
• Selective Overcurrent Logic (SOL).

Functions Settings Time delay


Pick-up setting IΦ> DT: 0.10 to 20.00 In DT: 0.04 to 300.00 s
IDMT: 0.10 to 5.00 In
Delay curve family IEC, IEEE, IEEE2, RI, programmable (prg.)
Delay type IEC: NI, VI, EI, LTI, Parameters
IEEE: VI, EI, LTI, LTEI, LTVI, MI, STI, STEI, Parameters
IEEE2: NI, VI, EI, MI, Parameters
RI: RI, RXIDG
Prg.: configurable using constant A, B, C, D, E
in delay function
Inv. time coefficient k 0.05 to 20.0 for IEC and RI
0.50 to 20.0 for RXIDG, IEEE and IEEE2
Release delay 0.03 to 100 s
Direction mode Directional, Undirrectional, Directional + Backup
Angle offset -180° to +179°
Inrush stabilization Enable / Disable
SOL (Sel. O/C Logic) Enable / Disable
SOL operat. Delay DT: 0.04 to 300.00 s
SOL Inv. time coeff. k 0.05 to 20.0 for IEC and RI
0.50 to 20.0 for RXIDG, IEEE and IEEE2
CLP (Cold Load pickup) Enable / Disable
CLP Pick-up setting I> DT: 0.10 to 20.00 In
IDMT:0.10 to 5.00 In
CLP operation delay DT: 0.04 to 300.00 s
CLP Inv. time coeff. k 0.05 to 20.0 for IEC and RI
0.50 to 20.0 for RXIDG, IEEE and IEEE2

Note: IDMT characteristic for stages IΦ> and IΦ>> only

schneider-electric.com Easergy P5 Catalog | 31


Easergy P5 Functions and description
Range description

Directional earth/ground fault overcurrent - ANSI 67N


This function provides selective and sensitive earth/ground fault protection for various network
earthing systems.
• Residual current and voltage can be either measured or internally calculated
• 3 independent stages with DT operating time
• Settable directionality
• Directional voltage memory (3.2 s).

Functions Settings Time delay


I0 input I0, I0Calc, I0’
Pick-up setting Io> DT: 0.002 to 20.00 In0 DT: 0.04 to 300.00 s
IDMT: 0.10 to 5.00 In
Delay curve family IEC, IEEE, IEEE2, RI, programmable (prg.)
Delay type IEC: NI, VI, EI, LTI, Parameters
IEEE: VI, EI, LTI, LTEI, LTVI, MI, STI, STEI, Parameters
IEEE2:NI, VI, EI, MI, Parameters
RI: RI, RXIDG
Prg.: configurable using constant A, B, C, D, E
in delay function
Inv. time coefficient k 0.05 to 20.0 for IEC and RI
0.50 to 20.0 for RXIDG, IEEE and IEEE2
Residual voltage U0 1% to 50% Un0
Direction mode ResCap, Sector, Undir
Angle offset -180 – +179°
Note: IDMT characteristic for stages I0> only

Transient intermittent earth/ground fault - ANSI 67NI


This function detects short transient intermittent phase to earth/ground faults in compensated networks, which
cannot be correctly recognized by steady-state directional earth/ground fault functions using the fundamental
frequency components only.
• Neutral displacement voltage U0> element to enable function
• Settable forward/reverse direction
• Dedicated blocking input to coordinate with AR.

Functions Settings Time delay


I0 input I0, I0'
Direction mode Forward; Reverse
Min. number of peaks 1 to 20
U0> setting 1% to 60% Un0
Operate time 0.02 to 300.00 s
Memory hold time 0.01 to 300.00 s
Reset delay 0.06 to 300.00 s

32 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Functions and description
Range description

2nd harmonic (H2) detection - ANSI 68H2


This function detects inrush current flows that occur when transformers or machines are energized. It may be
used to stabilize protection functions (e.g. phase overcurrent, earth/ground fault overcurrent, …) or even to issue
a trip if the inrush condition persists too long.
• Based on proven I2/I1 measurement
• Measurement per phase.

Functions Settings Time delays


Pick-up setting If2> 10% to 100% 0.03 to 300.00 s

5th harmonic (H5) detection - ANSI 68H5


This function detects 5th harmonic current flows that occur during overexcitation of transformers. It may be used
to stabilize protection functions or even to trip if the condition persists too long.
• Based on proven I5/I1 measurement.
• Measurement per phase.

Functions Settings Time delay


Pick-up setting If5> 10% to 100% 0.03 to 300.00 s

Auto-recloser function - ANSI 79


This function detects 5th harmonic current flows that occur during overexcitation of transformers. It may be used
to stabilize protection functions or even to issue a trip if the condition persists too long.
• 5 shots.
• Control of 2 CBs.
• Control via binary or virtual inputs.

Function Settings Time delay


Enable Auto-Recloser On; Off
also via digital input (DI), virtual input (VI), virtual
output (VO) or function key
Breaker 1 object Obj1 to Obj6
Breaker 2 object Obj1 to Obj6
Auto CB selection Disable; Enable
Input for selecting CB2 via DI, VI, VO or function key
Reclaim time 0.02 to 3000.00 s
Block by external synchro. check via DI, VI, VO or function key
Shot specific reclaim time On; Off
AR info for mimic display On; Off
Settings per shot Dead time 0.01 to 1200.00 s
Discrimination time 0.02 to 300.00 s
Additional setting 1 shot
st
Start delay 0.02 to 300.00 s

schneider-electric.com Easergy P5 Catalog | 33


Easergy P5 Functions and description
Range description

Over frequency - ANSI 81O


Protection of motors against overheating caused by motor excessive start time due to heavy motor load or too
low voltage.
• 2 independent stages with define time are provided.
• Under voltage self-blocking will operate when the maximum phase to phase voltage is less than the voltage
setting.

Functions Settings Time delay


Pick-up setting 40 to 70 Hz Trip: 0.1 to 300 s
Low voltage blocking 30% to 100% Un

Rate of change of frequency - ANSI 81R


This function is applied to detect the rate of change of system frequency, for fast load shedding or fast
disconnection of islanded generators under loss of main condition.
• 2 independent stages with define time are provided.
• Direction of the frequency change is settable.
• Under voltage self-blocking will operate when the maximum phase to phase voltage is less than the voltage
setting.

Functions Settings Time delay


Direction of change Negative, Positive, Either
Pick-up setting 0.1 to 10 Hz/s Trip: 0.05 to 10 s
Low voltage blocking 30% to 100% Un

Under frequency - ANSI 81U


This function is applied to detect the abnormal lower system frequency, to trigger load shedding, or indicate the
loss of main grid.
• 4 independent stages with define time are provided.
• Under voltage self-blocking will operate when the maximum phase to phase voltage is less than the voltage
setting.

Functions Settings Time delay


Pick-up setting 40 to 64 Hz Trip: 0.1 to 300 s
Low voltage blocking 30% to 100% Un

34 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Functions and description
Range description

Lockout - ANSI 86
This function is used to prevent switch onto fault and function is also called latching, can be programmed for
outputs in the OUTPUT MATRIX setting view. Any protection stage start or trip, digital input, logic output, alarm
and GOOSE signal connected to the following outputs can be latched when required.
• Lockout function independently to protection stages in output matrix.

Functions Settings Time delay


Pick-up setting 40 to 70 Hz Trip: 0.1 to 300 s
Low voltage blocking 30% to 100% Un

Programmable stages - ANSI 99


For special applications the user can built own detection stages by selecting the supervised signal and the
comparison mode.
• 8 independent stages, all with DT, 2 alternatively with IDMT operating time
• Priority selection for fast operation needs
• Multiple coupling and comparing conditions.

Functions Settings Time delay


Pick-up setting
Operation time 0.08 to 300 Instant overcurrent

schneider-electric.com Easergy P5 Catalog | 35


Easergy P5 Communication
Range description Examples of architectures

Connection to SCADA using serial line


DM107138

HMI/
SCADA
This architecture allows you to connect HMI/SCADA to a set of Easergy
protection relays using a multi-drop serial communication link with master-slave
communication.
Daisy chain
Serial
link Available protocols: Time synchronisation protocol:
• Modbus RTU • IRIG-B
• IEC 60870-5-101 • Minute pulse
• IEC 60870-5-103
• DNP3
Relay 1 Relay 2 Relay n (n max= 32)

Connection to SCADA using Ethernet


DM107139

HMI/
SCADA
This architecture allows you to connect a set of Easergy protection relays directly to
an Ethernet network.

Available protocols:
• IEC 61850
• IEC 60870-5-101
Ethernet
Network
• DNP3
• EtherNet/IP
Ethernet Ethernet
switch switch Note: It is possible to mix on the same Ethernet network the IEC 61850 protocol
with any of the 4 other protocols.

This allows you to use the GOOSE messages between relays together with another
protocol for communication to SCADA.

It is also possible to connect an Easergy relay to 2 different control systems, using


Sub- the same Ethernet communication port and IEC 61850 protocol for one of them and
Network any available protocol for the other one.

The Easergy P5 relay handles the IEC 61850 station bus, in compliance with
standards IEC 61850-6, 7-1, 7-2, 7-3, 7-4 and 8-1 Ed.1 or Ed.2, according to
configuration.

Other available Ethernet protocols:


• FTP for file transfer
• SNTP for time synchronization
• HTTPS for web server

Switchboard internal network


DM107140

Panel Ethernet
switch Easergy
HMI Pro

This architecture allows fast GOOSE communication between Easergy protection


relays of the switchboard, thus avoiding costly wiring. Typical uses are logic
Ethernet
discrimination, load shedding, etc.
In addition, a panel HMI featuring a web browser can be used to monitor and
GOOSE
messages
GOOSE
messages control the entire switchboard.
A spare connection on the panel Ethernet switch can also be provided for
connecting the Easergy Pro.
On Easergy P5x30 models, 2 independent Ethernet communication modules
are available. This allows to implement the switchboard internal network and the
communication to SCADA on two separate Ethernet networks.

36 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Communication
Range description Redundancy protocols

HMI/
SCADA
RSTP (Rapid Spanning Tree Protocol)
DM107141

The principle of RSTP is to virtually cut all links that are not necessary at a given
time, changing the meshed topology into a tree topology.
The main advantage of RSTP is that it is widespread and works on any network
Ethernet Ethernet
switch switch topology. On the other hand, RSTP takes milliseconds or seconds to reconfigure the
network in case of network interruption.
With Easergy P5, the typical reconfiguration time for a loop of 10 relays is 0,050s.

Ethernet Ethernet
switch switch

PRP (Parallel Redundancy Protocol)


DM107142

HMI/
SCADA

The principle of PRP is to transmit frames in parallel on two independent network


infrastructures: A and B.

Network A Network B
The receiving device is in charge of removing the redundant frame if it is received.
PRP features a 0 ms recovery time in case of failure.

HSR (High-availability Seamless Redundancy)


DM107143

Network Ethernet HSR is similar to PRP but only works on a ring architecture.
switch
Frames are transmitted on the ring in both directions and the receiving device
eliminates redundant frames.
HSR provides a 0 ms recovery time and is an alternative to PRP when network
topology can be restricted to a ring.
PRP & HSR are listed in IEC 62439-3 as part of IEC 61850 standard. They both
provide standardized, interoperable and performing redundant Ethernet solutions.
Easergy P5 Easergy P5 Easergy P5

schneider-electric.com Easergy P5 Catalog | 37


Easergy P5 Communication
Range description Data exchanged

Data exchanged with SCADA

Ports Ethernet Serial or Ethernet Serial


IEC 60870- IEC 60870-
Protocol IEC 61850 Ethernet/IP FTP DNP3 Modbus
5-103 5-101

Real time data


Measurement -
Alarms and status -
Controls -
Time-stamped events -

Historical data
Disturbance records - - - - -

Sequence of event record files - - - - - -

Setting management
Setting group change -
Settings - - - - -

Data exchanged according to IEC 61850

The Methodology described in the IEC 61850-6 standard can be applied with
DM107144

System
.icd file configurator
Easergy relays, in order to build a protection and control system based on this
standard.

Safe Repository and

.icd file
Schneider Electric web

.scd file .iid file

For each model of Easergy relay, the IED capability file can be downloaded from
the Schneider Electric website.

Easergy
Pro
.scd file
The system description file generated by the system configurator can be
processed by Easergy Pro and the relevant system settings integrated in the
Easergy configuration.

.iid file
When the configuration of an Easergy relay is completed or modified, Easergy
Pro can generate an Instantiated IED Description file to be used by the system
configurator to update the system description.

38 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Cyber security
Range description Cyber security systems

Cyber security features implemented in


Common features of basic and advanced
Easergy P5 help to mitigate cyber threats.
packages
Easergy P5 can be ordered, either with: • Secured communication between Easergy P5 and associated tools,
- Cyber security basics or • Protection of the hardware and logical communication ports,
- Cyber security advanced. • Password based user’s authentication,
• Role Based Access Control authorization management,
• Secured log storage
DM107145

• Compliant to NERC CIP and BDEW requirements.


CAE tool

Extra features provided by advanced


Security logs Security configuration
package
Security
logs With advanced package, Easergy P5 take benefit of “EcoStruxure Cybersecurity
request Admin Expert” (CAE), a windows-based tool that allows a central management of
Security configuration and access to security logs of each Easergy P5 connected
to the substation network.
Security configuration P5 includes:
• Roles and permissions: Role Base Access Control (RBAC),
• Users with associated roles,
• Security policy, for example password complexity or password strategy,
• Rules for security logs, choose between various standard,
DM107146

With Level1 option, Easergy P5 become part of a cyber security management


system consisting of servers for security logs, authentication and authorization,
using standard network protocols.
Syslog server
Easergy P5 can send security logs to any standard syslog server. Two use-cases
are available for authentication and authorization features:
• local
• centralized.
Security logs in
Syslog format Advanced - Local Authentication and Authorization
In this usecase, local authentication and authorization don’t rely on any external
servers. Security configuration is stored locally in each Easergy P5. Users
authentication and authorization using associated role are performed locally
(RBAC). CAE is used to update globally the security configuration of all the
Easergy P5 located inside the substation, so that users, associated passwords, and
other parameters are consistent on all devices.

Advanced - Centralized Authentication and Authorization


DM107147

RADIUS server Tools


In this usecase, centralized authentication and authorization relies on one or two
RADUIS server, with IEC62351-8 extension.
Authentication
This allowed to use Unified Account management system shared across
result + role
RADIUS protocol
heterogenous solutions. The same credentials are used at front panel of each
Easergy P5, at tools and also at third party devices.
Authentication Secured
+ role request communication Radius server is in charge of authenticating users and providing associated
role. Then Easergy P5 allows access based on this role and the internal security
configuration (RBAC).

Third-party Typically, the Radius server implemented with windows server component: NPS +
device Active Directory.
Schneider Electric can also provide an IEC62351-8 compliant Radius server
already configured with authorization. This server allows a fast and reliable solution,
managed by the CAE software. In addition, it’s includes a syslog server.

schneider-electric.com Easergy P5 Catalog | 39


Easergy P5
Product description

40 | Easergy P5 Catalog schneider-electric.com


Easergy P5
Product description
Functional view 38
P5U20 - Universal application 42
P5V20 - Voltage application 43
P5F30 - Feeder application 44
P5M30 - Motor application 45

Base unit description 46


P5x20 - dimensions and weight 46
P5x30 - dimensions and weight 43
Hardware specification 48
Rear panel description 49
Front panel description 50
P5x20 - Front panel description 51
P5x30 - Front panel description 52
Connection diagrams 53
Technical characteristics 56

schneider-electric.com Easergy P5 Catalog | 41


Easergy P5 Functional view
Product description P5U20 - Universal application

The Easergy P5U20 offers a complete set of current-based protections and


The Easergy P5U20 is used for feeder, motor, or measurement, control facilities and recording/monitoring functions for efficient
distribution transformer protection. operation of the power system.

eSetup
Easergy Pro
DM107150

HMI interface ON REL59700


Mimic Diagram

USB
I1: 0.0A 6 programmable front
I2: 0.0A 3-color LEDs ports
I3: 0.0A
P : 0.0W
Control buttons
V : 0.0V F1 1 Function key

Programmable Logic
AND TIMER
Inputs XOR Output

OR COUNTER

Setting groups:4
Ethernet module - Slot M Slot M Slot M + N
68 Protocols Redundancy RJ45 RJ45 LC LC LC LC
79 99 38
H2/H5 49T
• IEC 61850 protocol:
• Modbus • RSTP OR
• DNP3.0
• Ethernet/IP
SOTF 74 86
OR
Serial module - Slot N Slot N Redundancy
protocols:
Protocols Electrical RJ45 RJ45
CLPU ST • HSR
• Modbus connection:
• DNP3.0
OR • PRP
• RS485
• IEC -101 2/4 wires
48 • IEC -103
37 66 51LR
Extension module - Slot P
RJ45
59C Back-up
memory
RTD1 RTD2 RTD3 RTD4
49 59641

RTD5 RTD6 RTD7 RTD8

50BF

50 RTD1 RTD2 RTD3 RTD4


51
59641

RTD5 RTD6 RTD7 RTD8


51C

OR
46 50N
46BC 50G 6I/4O board - Slot C
DI1 DI2 DI3 DI4 DI5 DI6
51N
60
51G DO1 DO2 DO3 DO4 REL51045

De-modulated Modulated
I1 / I2 / I3 Io/I’o IRIG-B IRIG-B
Analog measurement board - Slot A Power Supply - Slot B
Current input DI1 DI2 DI3 DI4

I1 I2 I3 Io I’o DO1 DO2 DO3 SF

Other types
of control

Circuit-btreaker controls

Depends on the configuration

42 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Functional view
Product description P5V20 - Voltage application

The Easergy P5V20 offers a complete set of voltage and frequency protections, as well as measurements and recording/monitoring
functions for efficient operation of the power system.

In addition it can be used for the control of switchgear.

eSetup
Easergy Pro
DM107151

HMI interface ON REL59700


Mimic Diagram

USB
I1: 0.0A 6 programmable front
I2: 0.0A 3-color LEDs ports
I3: 0.0A
P : 0.0W
Control buttons
V : 0.0V F1 Function keys

Programmable Logic
AND TIMER
Inputs XOR Output

OR COUNTER

Setting groups:4
Ethernet module - Slot M Slot M Slot M + N
Protocols Redundancy RJ45 RJ45 LC LC LC LC
99 • IEC 61850 protocol:
• Modbus • RSTP OR
• DNP3.0
• Ethernet/IP
74 86
OR
Serial module - Slot N Slot N Redundancy
protocols:
Protocols Electrical RJ45 RJ45
ST • HSR
• Modbus connection:
• DNP3.0
OR • PRP
• RS485
• IEC -101 2/4 wires
• IEC -103

Extension module - Slot P


RJ45
Back-up
memory
81R

81
81U

59N

27
27P

25

59
6I/4O board - Slot C
DI1 DI2 DI3 DI4 DI5 DI6
60 REL51045
DO1 DO2 DO3 DO4 De-modulated Modulated
IRIG-B IRIG-B
V / V0 V4
Analog measurement board - Slot A Power Supply - Slot B
Current input Voltage input DI1 DI2 DI3 DI4

I1 I2 I3 Io I’o V1 V2 V3 Vo DO1 DO2 DO3 SF

Other types
of control

Circuit-btreaker control

schneider-electric.com Easergy P5 Catalog | 43


Easergy P5 Functional view
Product description P5F30 - Feeder application

The Easergy P5F30 offers a complete set of current and voltage based protections
The Easergy P5F30 is designed for the and measurement, control facilities and recording/monitoring functions for efficient
operation of electrical distribution networks of operation of the power system. It is suitable for application on solidly grounded,
industrial installations and utility substations for impedance grounded, Petersen coil grounded and isolated systems.
all levels of voltages.

eSetup
Easergy Pro
DM107148

HMI interface ON REL59700


Mimic Diagram

USB
I1: 0.0A 10 programmable front
I2: 0.0A 3-color LEDs ports
I3: 0.0A
P : 0.0W
Control buttons
V : 0.0V F1 7 Function keys F7

Programmable Logic Ethernet module - Slot L


AND TIMER
Protocols Redundancy RJ45 RJ45
Inputs XOR Output • IEC 61850 protocol:
• Modbus • RSTP
OR COUNTER • DNP3.0
• Ethernet/IP

Setting groups:4
Ethernet module - Slot M Slot M Slot M + N
68 Protocols Redundancy RJ45 RJ45 LC LC LC LC
79 99 38
H2/H5 49T
• IEC 61850 protocol:
• Modbus • RSTP OR
• DNP3.0
• Ethernet/IP
SOTF 74 86
OR
Serial module - Slot N Slot N Redundancy
protocols:
50 Protocols Electrical RJ45 RJ45
CLPU ST • HSR
ARC • Modbus connection:
• DNP3.0
OR • PRP
• RS485
• IEC -101 2/4 wires
• IEC -103

Extension module - Slot P


67 21FL 37P RJ45
Back-up
memory
81R RTD1 RTD2 RTD3 RTD4
49 59641
81
Arc board - Slot E RTD5 RTD6 RTD7 RTD8
81U
DI1 DI2 DI3
50BF Arc 1 Arc 2 Arc 3
67NI 32N A A A
DO1 DO2 DO3
59N
50 RTD1 RTD2 RTD3 RTD4
51 Arc board - Slot D
67N 59641
DI1 DI2 DI3
Arc 1 Arc 2 Arc 3 RTD5 RTD6 RTD7 RTD8
51C 27
A A A
DO1 DO2 DO3
25 OR
46 50N
59
46BC 50G 6I/4O board - Slot C
DI1 DI2 DI3 DI4 DI5 DI6
51N
60 60
51G DO1 DO2 DO3 DO4 REL51045

De-modulated Modulated
I1 / I2 / I3 Io/I’o V / V0 V4 IRIG-B IRIG-B

Analog measurement board - Slot A Power Supply - Slot B


Current input Voltage input DI1 DI2 DI3 DI4

I1 I2 I3 Io I’o V1 V2 V3 Vo DO1 DO2 DO3 SF

Arc sensor:
Other types
See list of
of control Accessories
REL52801
to REL52810

Circuit-btreaker controls
Arc flash sensors
Depends on the configuration

44 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Functional view
Product description P5M30 - Motor application

The Easergy P5M30 is more than a conventional protection relay. It offers numerous
Compact, specially developed and designed additional functions suitable and crucial for a wide range of applications, which
for rotating machine, the Easergy P5M30 relays involve protection, monitoring, diagnosis, fault analysis tools, and maintenance aids.
performs an essential role in many industrial
processes and generations for medium and
large sized rotating machines.

eSetup
Easergy Pro
DM107149

HMI interface ON REL59700


Mimic Diagram

USB
I1: 0.0A 10 programmable front
I2: 0.0A 3-color LEDs ports
I3: 0.0A
P : 0.0W
Control buttons
V : 0.0V F1 7 Function keys F7

Programmable Logic Ethernet module - Slot L


AND TIMER
Protocols Redundancy RJ45 RJ45
Inputs XOR Output • IEC 61850 protocol:
• Modbus • RSTP
OR COUNTER • DNP3.0
• Ethernet/IP

Setting groups:4
Ethernet module - Slot M Slot M Slot M + N
68 Protocols Redundancy RJ45 RJ45 LC LC LC LC
99 38
H2/H5 49T
• IEC 61850 protocol:
• Modbus • RSTP OR
• DNP3.0
• Ethernet/IP
SOTF 74 86
OR
Serial module - Slot N Slot N Redundancy
protocols:
50 Protocols Electrical RJ45 RJ45
CLPU ST • HSR
ARC • Modbus connection:
• DNP3.0
OR • PRP
• RS485
• IEC -101 2/4 wires
48 • IEC -103
37 66 51LR
Extension module - Slot P
67 37P RJ45
Back-up
memory
RTD1 RTD2 RTD3 RTD4
49 59641
81
Arc board - Slot E RTD5 RTD6 RTD7 RTD8
81U
DI1 DI2 DI3
50BF Arc 1 Arc 2 Arc 3
A A A
DO1 DO2 DO3
59N
50 RTD1 RTD2 RTD3 RTD4
51 6I/4O board - Slot D
67N 59641
27 DI1 DI2 DI3 DI4 DI5 DI6
RTD5 RTD6 RTD7 RTD8
27P
DO1 DO2 DO3 DO4
OR
46 50N
59
46BC 50G 6I/4O board - Slot C
DI1 DI2 DI3 DI4 DI5 DI6
51N
60 60
51G DO1 DO2 DO3 DO4 REL51045

De-modulated Modulated
I1 / I2 / I3 Io/I’o V / V0 IRIG-B IRIG-B
Analog measurement board - Slot A Power Supply - Slot B
Current input Voltage input DI1 DI2 DI3 DI4

I1 I2 I3 Io I’o V1 V2 V3 Vo DO1 DO2 DO3 SF

Other types
of control

M
Circuit-btreaker controls
Arc flash sensors
Depends on the configuration

schneider-electric.com Easergy P5 Catalog | 45


Easergy P5 Base unit description
Product description P5x20 - Dimensions and weight

4U - 20TE standard box Dimensions mm in.


Height 180 7.08
Width 102 4.01
Depth 224 8.82
Weight kg lbs
Weight 2.5 to 3.5 5.5 to 7.7

224mm (8.82 in.)

97.5 mm
168mm (6.61 in.)
102 mm (3.84 in.)
DM107165

(4.01 in.) 148 mm (5.83 in.)

51,8 mm
167.2 mm 180 mm 158 mm
(2.04 in.)
(6.58 in.) (7.08 in.) (6.22 in.)

4 mm (0.16 in.)

Flush mounting installation Cut-out dimensions mm in.


Height 205 8.07
mm
130 ± 0.5 Width 130 5.12
180 ± 0.5
DM107199

in
5.12 ± 0.2
7.09 ± 0.2
More info on installation accesories page 77
8.07 ± 0.2
205 ± 0.5

8.07 ± 0.2
205 ± 0.5

P5x20 P5x30

46 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Base unit description
Product description P5x30 - Dimensions and weight

4U - 30TE standard box Dimensions mm in.


Height 180 7.08
Width 152.4 6
Depth 224 8.82
Weight kg lbs
Weight 2.5 to 3.5 5.5 to 7.7

152.4 mm 149 mm
224mm (8.82 in.)
DM107168

(6 in.) (5.87 in.)


168mm (6.61 in.)

148 mm (5.83 in.)

167.2 mm 180 mm
(6.58 in.) (7.08 in.) 158 mm
103.6 mm (6.22 in.)
(4.08 in.)

F1 F2 F3

F4 F5 F6 F7

4 mm (0.16 in.)

Flush mounting installation Cut-out dimensions mm in.


Height 205 8.07
130 ± 0.5 Width 180 7.09
180 ± 0.5
DM107199

5.12 ± 0.2
7.09 ± 0.2
More info on installation accesories page 77
8.07 ± 0.2
205 ± 0.5

P5x30

schneider-electric.com Easergy P5 Catalog | 47


Easergy P5 Base unit description
Product description Hardware specification

Optional modules
PM107312

Option in slots A, B, C, D, E must be selected when ordering the device (measuring


inputs, power supply and input/output optional boards).
Communication modules in slots L, M, N, P can be ordered separately and added
on site, when more communication capabilities are required.
External modules are available for RTD inputs and for IRIG-B time synchronization.

Draw-out design
PM107326

Easergy P5 protection relays can be drawn-out, offering faster and easier


maintenance with less risk:
1. Its removable parts (including the I/O board, CPU board and power supply) can
be easily replaced.
2. Thanks to the backup memory included in the extension module (option),
configuration and log records are automatically reloaded, allowing quick relay
restart without additional configuration. No recommissioning is necessary.
3. The CT and VT inputs are isolated when the device is withdrawn.

48 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Base unit description
Product description Rear panel description

A B C D E A B C

PM107428

PM107490
Rear communication
modules:

Dual port copper (RJ45)


ETH
or optical fibre
(multimode glass fiber)
Ethernet module

RS485 or optical fibre


SRL
serial communication
module

Extension port for


EXT !
connection with external
modules
M N P L M N P

Easergy P5x20 Easergy P5x30


3 phase CT + 2 residual CT 3 phase CT + 2 residual CT + 4 VT
Slot A CT/VT inputs or: 3 phase CT + 1 residual CSH or: 3 phase CT + 1 residual CSH + 4 VT
or: 4 VT or: 3 phase LPCT + 1 residual CSH +4 LPVT (*)
Power supply
Slot B 24 to 250 V supply + 4 DI + 3 DO + WD 48 to 250 V supply + 4 DI + 3 DO + WD
and digital I/O
Slot C (option) Additional I/O 6 DI + 4 DO 6 DI + 4 DO
6 DI + 4 DO
Slot D (option) Additional I/O
or: 3 Arc + 3 DI + 3 DO
6 DI + 4 DO
Slot E (option) Additional I/O
or: 3 Arc + 3 DI + 3 DO
Slot P (option) Extension port Extension module Extension module
RS485 serial line module RS485 serial line module
Slot N (option) Serial port
or: Fiber optic serial line module or: Fiber optic serial line module
Ethernet TP module with RSTP Ethernet TP module with RSTP
Slot M (option) Ethernet port
or: Ethernet FO module with RSTP or: Ethernet FO module with RSTP
Slots M&N Ethernet port
Ethernet FO module with HSR/PRP Ethernet FO module with HSR/PRP
(option): with HSR/PRP

Slot L (option) Ethernet port Second Ethernet TP module with RSTP

(*) Contact us for availability

schneider-electric.com Easergy P5 Catalog | 49


Easergy P5 Base unit description
Product description Front panel description

Comprehensive data for fast and easy


DM107197

operation
All the data required for a local equipment operation may be displayed on demand:

• Display the single-line diagram and freely assignable analog values

• Display of all measurements

• Display of operation and alarm messages

• Display and setting of all parameters


Home page of easy navigation
• Entry of password to protect parameter and protection settings
DM107196

Ergonomic data presentation


• 480 x 272 colour LCD screen (P5x30 models) or 192 x 96 LCD screen (P5x20
models) to display any character or symbol

• Dedicated keys for operation:


–– Control buttons (O/I) to operate the circuit breaker and other controllable
objects
–– Reset button (R) to clear the alarms and reset the lockout function
Single-line diagram for easy operation –– Local / Remote button
• Programmable function keys (7 on P5x30 models, 1 on P5x20 models)

• Dedicated LEDs for signalling:


–– Power on
–– Relay maintenance
–– Trip
–– Alarm

• Tri-color programmable LEDs (10 on P5x30 models, 6 on P5x20 models)

Working languages
All the texts and messages displayed on the Easergy P5 protection relay are
available in two languages: English plus a local language. Files of different
languages can be downloaded from the Schneider Electric website.

50 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Base unit description
Product description P5x20 - Front panel description

PM107302
KEYS
HOME key: return to the previous menu. To LEDS
return to the first menu item in the main menu,
press the button for at least three seconds On (Green)
INFO push-button for viewing additional
information, entering the password view, and !
adjusting the LCD contrast Alarm (Yellow)

Reset control key


Trip (Red)
ENTER key: activate or confirm
a function Maintenance
UP key: move up in the menu (Yellow)
or increase a numerical value
Navigation keys

6 customizable
DOWN key: move down in the menu tri-color LEDs
or decrease a numerical value
LEFT key: move backwards in a
parallel menu or select a digit in PORTS
a numerical value
USB mini B
RIGHT key: move forwards in a (Computer)
parallel menu or select a digit in
a numerical value USB A
(USB key)
Switchgear control key (OPEN)

Switchgear control key (CLOSE) SEAL (open)

Local/remote control key

F1 Customizable function key


PM107301

LABELS

Customizable LED labels

Customizable Bay label


SEAL (closed)

schneider-electric.com Easergy P5 Catalog | 51


Easergy P5 Base unit description
Product description P5x30 - Front panel description

PM107315
KEYS

DM107153
LEDS
HOME key: return to the previous menu.
To return to the first menu item in the main
menu, press the button for at least three On (Green)
seconds
INFO push-button for viewing additional Alarm (Yellow)
information, entering the password view,
and adjusting the LCD contrast
Trip (Red)
Reset control key
Maintenance
ENTER key: activate or confirm (Yellow)
a function 10 customizable
UP key: move up in the menu tri-color LEDs
or increase a numerical value
Navigation keys

DOWN key: move down in the


menu or decrease a numerical value PORTS
LEFT key: move backwards in a USB mini B
parallel menu or select a digit (Computer)
in a numerical value
USB A
RIGHT key: move forwards in a (USB key)
parallel menu or select a digit
in a numerical value

Switchgear control key (OPEN)


SEAL (open)
Switchgear control key (CLOSE)

Local/remote control key

F1 Customizable function keys


PM107314

LABELS

Customizable LED labels

Customizable Bay label


SEAL (closed)

52 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Base unit description
Product description Connection diagrams

CT and LPCT connection – slot A

Version with 3 phase CT + 2 residual CT inputs

DM107154
L1 L1
L2 L2
L3 L3

S1 A9 S1 A9
1/5 A A10 IL1 1/5 A A10
IL1
S1 A11 S1 A11
A12 IL2 A12
IL2
S1 A13 S1 A13
A14 A14
IL3 IL3
A15 A15
1/5 A A16 Std A16 Std
S1 A17 A17
1A VS 1A A18
A18 VS
S1 S1

Version with 3 phase CT + 1 CSH inputs

L1 L1
DM107155

L2 L2
L3 L3

S1 A9 S1 A9
1/5 A A10 IL1 1/5 A A10 IL1
S1 A11 S1 A11
A12 IL2 A12 IL2
S1 A13 S1 A13
A14 IL3 A14 IL3
A15 A15
A16 20 A A16 20 A
CSH
S1
A17 A17
A18 2A CSH A18 2A
S1

Version with 3 phase LPCT + 1 CSH inputs (*)

L1
DM107156

L2
L3

RJ45 IL1

RJ45 IL2

RJ45 IL3

A1
CSH 20 A
A2
S1
A3
A4 2A

(*) Contact us for availability

schneider-electric.com Easergy P5 Catalog | 53


Easergy P5 Base unit description
Product description Connection diagrams

VT and LPVT connection – slot A

Version with 4 VT inputs

3 phase-to-neutral voltages 2 phase-to-phase voltages + 1 residual voltage


and 1 residual voltage + 1 additional phase-to-phase voltage

L1
DM107157

DM107158
L1
L2 L2
L3 L3

A1 A1
A2 V1 A2 V1

A3 A3
A4 V2 A4 V2
A5 A5
A6 V3 A6 V3
A7 A7
A8 V4 A8 V4

3 phase-to-neutral voltages + 1 additional phase-to-phase voltage


DM107159

L1
L2
L3

A1
A2 VL1
A3
A4 VL2
A5
A6 VL3
A7
A8 V4

Version with 4 LPVT inputs (*)


DM107160

L1 V4 = VB-VA
L2
or V4=VA
L3
according to setting
LPVT L1
LPVT hub
connector

LPVT L2

LPVT L3

RJ45 VL1, VL2, VL3


LPVT hub
connector

RJ45 V4

(*) Contact us for availability

54 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Base unit description
Product description Connection diagrams

Power supply and digital P5U20 – P5V20 P5F30 – P5M30

I/Os – slot B

DM107161

DM107162
DI1 1 DI1 1
2 2
3 3
DI2 4 DI2 4
5 5
DI3 DI3
6 6
DI4 7 DI4 7
8 8
DO1 9 DO1 H 9
10 10
S

DO2 DO2
11 11
12 12
13 13
DO3 14 DO3 14
15 15
WD 16 WD 16
17 17
18 18
19 19
20 20

24 to 250 V supply + 4 DI + 3 DO + WD 48 to 250 V supply + 4 DI + 3 DO + WD


DI1 to DI4: universal digital inputs DI1 to DI4: universal digital inputs
DO1, DO2 and DO3: DO1: high-speed/high-break output
control relay outputs DO2 and DO3: control relay outputs
WD: signaling relay output - watchdog WD: signaling relay output - watchdog

Additional digital I/Os P5U20 – P5V20 – P5F30 – P5M30 P5F30 – P5M30

and arc-sensors inputs –


DM107163

DM107164

DI1 1 DI1 1
2 2
slots C, D, E DI2 3
4
DI2 3
4
DI3 DI3 5
5
6 6
DI4 7 DO1 7
8 8
DI5 DO2
9 9
10 10
DI6 11
11
12 DO3 12
13
DO1 13
14 14
DO2 15 15
L> 16
16
17 17
DO3 L>
18 18
19 19
DO4 L>
20 20

6 DI + 4 DO 3 Arc + 3 DI + 3 DO
DI1 to DI6: universal digital inputs DI1 to DI3: universal digital inputs
DO1 to DO4: signaling relay outputs DO1 and DO2: control relay outputs
DO3: signaling relay outputs
3 point light sensor inputs

schneider-electric.com Easergy P5 Catalog | 55


Easergy P5 Base unit description
Product description Technical characteristics

Electrical characteristics
Power supply
P5x20 24-250 Vdc; 100-230 Vac
Rated voltage
P5x30 48-250 Vdc; 100-230 Vac
Variation -20% / +20%
P5x20 4.4 W
Typical burden
P5x30 5.2 W
P5x20 5.5 W 8 W
Maximum burden
P5x30 To be completed > 10.5 W
Maximum interruption time 100 ms
Energizing inputs
Rated frequency 50/60 Hz

Phase CT and standard earth/ground fault CT inputs


Rated current 1A/5A
Input impedance < 0.02 Ohm
Thermal withstand, continuous 20 A
Thermal withstand, 1 s 500 A

Very sensitive earth/ground fault CT input


Rated current 1A
Input impedance < 0.02 ohm
Thermal withstand, continuous 4A
Thermal withstand, 1 s 100 A

CSH input (for 470/1 dedicated sensors)


Rated current 2 A / 20 A (primary value)
Input impedance < 0.02 ohm
Thermal withstand, continuous 300 A (primary value)
Thermal withstand, 1 s 20 kA (primary value)

LPCT inputs (*)


Rated voltage 22.5 mV
Extended rated voltage 0.25 to 31.5 rated voltage
Input impedance 2 MOhms / 500 pF
Thermal withstand 60 V

VT inputs
Rated voltage 200 V
Input impedance > 100 kohms
Voltage withstand, continuous 1.2 rated voltage
LPVT inputs (*)
Rated voltage 3.25 V/ 3
Extended rated voltage 0.25 to 1.5 rated voltage
Input impedance 10 MOhms / 15 pF
Thermal withstand 25 V
Digital inputs
Rated voltage 240 V DC or AC
Switching threshold voltage 10 to 200 V, settable
Current drain 1 to 28 mA, settable (1)
(1) According to configuration
(*) Contact us for availability

56 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Base unit description
Product description Technical characteristics

Relay outputs

Control relay outputs


Rated voltage 240 V DC or AC
Continuous current 8A
Making current 30 A, 200 ms
Breaking capacity (L/R<40ms) 50W (24 to 127V) / 30W (240V) (2)

Signaling relay output


Rated voltage 240V DC or AC
Continuous current 2A
Breaking capacity (L/R<20ms) 2A (24V) / 1A (48V) / 0.2A (127V) / 0.1A
(240V)

High-speed and high-break output


Rated voltage 240 V DC or AC
Continuous current 10 A
Making current 30 A, 200 ms
Breaking capacity (L/R < 40 ms) 10 A (24 to 240 V)
Closing / opening time 1 ms / 200 ms
(1) With a limitation according to the rated voltage of the circuit
(2) 50W @ 24V with additional customer protection (RC or zener diode)

schneider-electric.com Easergy P5 Catalog | 57


Easergy P5 Base unit description
Product description Technical characteristics

Environmental characteristics
Electromagnetic compatibility Standard Level / Class Value

Emission Tests
Conducted emission CISPR 11 Class A 0.15 to 0.5 MHz: 79 dBµV (quasi peak)
CISPR 22 Class A 0.5 to 30 MHz: 73 dBµV (quasi peak)
IACS E10 0.15 MHz to 0.3 MHz: 80 to 50 dBμV/m
Radiated emission CISPR 22 Class A 30 MHz to 230 MHz: 40 dBµV (quasi peak)
0.3 MHz to 100 MHz: 60 to 54 dBμV/m
IACS E10 100 MHz - 2000 MHz, 54 dBμV/m
except for: 156 MHz - 165 MHz, 24 dBμV/m

Immunity tests – radiated disturbances


Electrostatic discharge IEC 61000-4-2
ANSI C37.90.3 Class 4 15 kV air / 8kV contact
Radiated electromagnetic energy IEC 61000-4-3 Level 3 10 V/m, 80 MHz to 2.7 GHz, 80% AM (1 KHz)
ANSI C37.90.2 20 V/m, 80 MHz to 1 GHz, 80% AM (1 KHz)
GOST 32137 10 V/m, 80 MHz to 1 GHz, 80% AM (1 KHz) and pulse 200
Hz
GOST 30804.4.3 30 V/m, 800 to 960 MHz & 1.4 to 2 GHz
IACS E10 10 V/m, 80 MHz to 1 GHz
Magnetic fields at power frequency IEC 61000-4-8 Level 5 100 A/m continuous, 1000 A/m, 3s
Pulse magnetic fields IEC 61000-4-9 Level 5 1000 A/m
Oscillatory magnetic fields IEC 61000-4-10 Level 5 100 A/m, 100 kHz and 1 MHz, 2s

Immunity tests – conducted disturbances


Radio frequency disturbances IEC 61000-4-6 Level 3 10 V CM, 0.15 MHz to 80 MHz
Slow damped oscillatory waves IEC 61000-4-18 Level 3 2.5 kV CM, 1 kV DM, 100 kHz & 1 MHz
ANSI C37.90.1 2.5 kV, 1 MHz, CM and TM
IEC 61000-4-12 2 kV CM, 1 kV DM, 100 kHz
GOST30804.4.12 Source impedance: 12 Ω
Fast damped oscillatory waves IEC 61000-4-18 Level 3 2 kV CM, 3MHz, 10MHz, 30MHz
Conducted disturbances 0 to 150 kHz IEC 61000-4-16 Level 4 300 V CM, 150 V DM, 0 to 150 kHz
30 V, continuous at power frequency
Electrical fast transient or burst IEC 61000-4-4 Level 4 4 kV CM, 5 kHz and 100 kHz
ANSI C37.90.1 4 kV, 5 kHz CM and TM
IACS E10 2 kV power supply, 1 kV digital I/Os, 5min
Surge IEC 61000-4-5 Level 4 4 kV CM, 2 kV DM / communication ports: 2 kV CM, 1 kV
DM

58 | Easergy P5 Catalog schneider-electric.com


Easergy P5 Base unit description
Product description Technical characteristics

Electromagnetic compatibility Standard Level / Class Value

Disturbances on the power supply


Voltage dips IEC 61000-4-11 0%, 5/6 cycles min
40%, 10/12 cycles
70%, 25/30 cycles
IEC 61000-4-29 0%, 100 ms min
40%, 200 ms
70%, 500 ms
Interruption IEC 61000-4-11 0%, 250/300 cycles
IEC 61000-4-29 0%, 5 s
Voltage variations IEC 61000-4-14 Class 3 ±12 % Un
Frequency variations IEC 61000-4-28 Level 4 ±15 % of frequency variation
Ripples IEC 61000-4-17 15%, 100 Hz to 120 Hz
Gradual shutdown IEC 61000-4-27
Reverse of DC power supply IEC 61000-4-27
AM : Amplitude Modulation / CM : Common Mode / DM : Differential Mode / TM : Transversal Mode

Mechanical robustness Standard Level / Class Value

In operation
Vibrations IEC 60255-21-1 Class 2 1 Gn, 10 Hz to 200 Hz
GOST 17516.1 0,015 mm peak, 0,5 Hz to 57,6 Hz
1 Gn 57,6 Hz to 150 Hz
IACS E10 13.2 Hz to 100 Hz – acceleration ± 0.7 g
Shocks IEC 60255-21-2 Class 2 10 Gn / 11 ms
Earthquakes IEC 60255-21-3 Class 2 2 Gn horizontal / 1 Gn vertical

De-energized
Vibrations IEC 60255-21-1 Class 2 2 Gn ; 10 Hz - 150 Hz
Shocks IEC 60255-21-2 Class 2 30 Gn / 11 ms
Jolts IEC 60255-21-2 Class 2 20 Gn / 16 ms

schneider-electric.com Easergy P5 Catalog | 59


Easergy P5 Base unit description
Product description Technical characteristics

Climatic withstand Standard Level / Class Value

In operation - Operating condition: -40°C to +70°C (-40°F to +158°F)


Operating conditions -40°C to +70°C (-40°F to +158°F)
Exposure to cold IEC 60068-2-1 Ad -40°C (-40°F) ; 96 h
Exposure to dry heat IEC 60068-2-2 Bd +70°C (+158°F), 96 h
+85°C (+185°F), 16 h
Exposure to damp heat IEC 60068-2-78 Cab 93% RH without condensation, 40°C
(104°F), 56 days
IEC 60068-2-30 Db 93-95% RH, 25°C to 55°C (77°F to 131°F),
6 cycles (12 + 12 hours)
Temperature variation IEC 60068-2-14 Nc -40°C to +70°C (-40°F to +158°F)
10°C/mn (18°F/mn)

In storage
Storage conditions -40°C to +85°C (-40°F to +185°F)
Exposure to cold IEC 60068-2-1 Ab -40°C (-40°F) ; 96 h
Exposure to dry heat IEC 60068-2-2 Bb +85°C (+185°F) ; 96 h
Exposure to damp heat IEC 60068-2-78 Cab 93% RH to 95% RH, 40°C (104°F), 56 days

Corrosive atmosphere
Salt mist IEC 60068-2-52 Kb / 1
2 and 4 gas IEC 60068-2-60 Ke • Method 1;
0,5 ppm ; 1 ppm
• Method 4;
–– 0,071 ppm H2S, 0,26 ppm ,
–– 0,034 ppm , 0,11 ppm
IEC 60721-3-3 3C2 21 days

Climatic withstand Standard Value


General safety IEC 60255-27
Creepage distances and IEC 60255-27 Pollution degree 2
clearances overvoltage category III
High voltage withstand IEC 60255-27 2 kV rms, 1mn
1 kV rms, 1mn across opened
contacts
ANSI C37.90 1.5 kV rms 1 mn across opened
contacts of control relays
Impulse voltage withstand IEC 60255-27 5 kV, 1.2 μs/50 μs
Insulation IEC 60255-27 Insulation resistance > 100 MΩ at 500
Vdc

Marking and homologations

Standard Value
IEC60255-26 CE marking according to:
IEC60255-27 EMC Directive 2014/30/EU
LV Directive 2014/35/EU
UL508 File E354250, NRGU
ANSI/IEEE C37.90
CAN/CSA C22.2 No.14

60 | Easergy P5 Catalog schneider-electric.com


Notes

schneider-electric.com Easergy P5 Catalog | 61


Digital experience

62 | Easergy P5 Catalog schneider-electric.com


Digital experience

Set up software 64
eSetup Easergy Pro 64
eSetup Easergy Pro - during engineering 65
eSetup Easergy Pro - during commissioning 65
eSetup Easergy Pro - during operation 65

Web-HMI 66

Mobile application 67

schneider-electric.com Easergy P5 Catalog | 63


Digital experience Set up software
eSetup Easergy Pro

Minimum requirements for running At each step of the digital life


eSetup Easergy Pro:
eSetup Easergy Pro offers full facilities to set up Easergy relays. Intuitive and
• Windows 7 or higher simple, eSetup Easergy Pro is a user-oriented interface to assist you during the
engineering, commissioning and operation of Easergy protection relays.
• 512 MB RAM
ts streamlined workflow and graphical representations has been designed to
• 50 MB Disk space
smooth your configuration process.
The software is available for download on the Schneider Electric website.

DM105614b
DM105613b

eSetup eSetup
DM105612b

eSetup
Easergy Pro Easergy Pro
Easergy Pro

Use eSetup Easergy Pro in standalone Connect the PC running eSetup Easergy Connect the PC running eSetup Easergy
mode during engineering to prepare the Pro to the USB port of the Easergy Pro to the Ethernet network during
configuration. protection relay during commissioning to operation to retrieve data from the relays
adjust the settings and test the relay. and update the system.

For connection to Easergy P5, use the


REL52822 connection cord

64 | Easergy P5 Catalog schneider-electric.com


Digital experience Set up software
eSetup Easergy Pro

During engineering
EM106160

• Create the configuration of the Easergy P5 relay: select the appropriate options
and receive the order code
• Set the characteristics of the CTs, VTs, or sensors connected to the relay, and
select the protection functions that will be activated and their settings
• Build a specific logic, if required, using a graphic editor
• Map the digital inputs of the relay and different internal signals to the relevant
functions, LEDs, and digital outputs, using a straightforward matrix format.
• Draw the single-line diagram that will appear on the front display of the relay for
switchgear control and select the measurements that will be displayed. If any,
build the interlocking logic using a matrix format
• For IEC 61850 protocol, configure the data set and the report control blocks that
will be published and select the GOOSE data to which you want to subscribe
• Complete the setting of additional functions (disturbance recorder, event logging
system, clock synchronization, etc.).

During commissioning
EM106163

• Connect to the front panel of one single relay or access several relays by
connecting to Ethernet
• Open the Digital Inputs menu to check the status of inputs. Reverse the polarity
or add a filtering delay if necessary
• Open the Relays menu and force the status change of the output relays in order
to check the wiring.
• Open the Phasor Diagram menu to see in real time the phasor of injected
currents and voltages and the value
• Use virtual injection for testing protection settings and circuit breaker tripping
and for checking LEDs and connected outputs
• Open the Logic or the Matrix menu if the logic needs to be tested. The active
signals appear in a different color and are updated in real time. Changes in the
logic or in the matrix can be made and applied to the relay smoothly.

During operation
EM106166

• Connect to the front panel of a single relay or gain access to several relays by
connecting to Ethernet
• During normal operation, get the most of the metering capabilities of the
Easergy protection relay:
–– Open the different Measurements menus to access the power monitoring
and power quality data.
–– Open the disturbance recorder menu to get a waveform capture or program
the recording of a power trend.
• After a trip, use eSetup Easergy Pro to understand the fault:
–– Check the fault log of the protection that has tripped the circuit breaker
–– Download the disturbance record from the Easergy P5 and display it with a
disturbance recorder evaluation tool, eg. Wavewin.

schneider-electric.com Easergy P5 Catalog | 65


Digital experience Web-HMI
Description

Boost operational efficiency with the


Enhance operational
embedded web-HMI
efficiency
• Direct access to protection and Quickly and conveniently configure, monitor, and operate your Easergy P5
communication settings protection relay with our web-HMI. The web-HMI, accessible online via IP address
• Control and monitoring of circuit breakers of the relay, doesn’t require you to install specific computer software - simply use
and switches your web browser to connect to the device. You only need to enable the web server
service during the initial configuration of Easergy P5 with eSetup Easergy Pro. The
• Mirror HMI function
web-HMI is based on the same page design as eSetup Easergy Pro, making it easy
• Direct access to measurements including to use!
the graphic phasors
• Device diagnosis
• MATRIX status
• Access to logs and other information

66 | Easergy P5 Catalog schneider-electric.com


Digital experience Mobile application
Description

EcoStruxureTM Power Device app


Within the palm of your hand you can be connected to your Schneider Electric:
• Masterpact MTZ air circuit breaker
• TeSys GV4 motor circuit breaker
• Easergy P5 protection relays
• ... and more!
EcoStruxure Power Device app is a single mobile application with necessary
information and capabilities to operate and efficiently maintain devices in the
EcoStruxure architecture.
This app can be installed on your IOS and Android smartphone. The protection
devices can be identified on the app by simply scanning their QR codes.
Wireless communication is possible via by WIFI, Bluetooth, NFC technologies
for operation and monitoring within the proximity of the devices. Get real time
notifications about the electrical installation: load levels, health status, warnings and
alarms, protection settings…and more!

Free download
EcoStruxure Power Device on:

(1) Wi-Fi is not embedded in Easergy P5, a separate Wi-Fi router connected to an Ethernet port of
the device is required.

schneider-electric.com Easergy P5 Catalog | 67


Additional Modules
and Accessories

68 | Easergy P5 Catalog schneider-electric.com


Additional Modules
and Accessories
Communication accessories 70
Modules 70
Sensors 75

Mounting accessories 77

Wiring accessories 78

schneider-electric.com Easergy P5 Catalog | 69


Additional Modules Communication accessories
and Accessories
Modules

Ethernet communication module with


RSTP redundancy
REL51038: Ethernet TP module
DM101268

The Ethernet communication module is inserted in the slot M of the device. It can
be selected as an option when ordering the device or purchased later and installed
on site. It is available in 2 versions for copper wire or fiber optic connection.

It provides RSTP (Rapid Spanning Tree Protocol), which allows fast reconfiguration
of the communication system.

Ethernet TP module Characteristics


Standard 2 ports: 10/100 Base TX
Baud rate 10 or 100 Mbits/s
Type of cable Standard Ethernet CAT 5
Connection RJ45
DM101267

REL51039: Ethernet FO module

Characteristics
Standard 2 ports: 100 Base FX
Baud rate 100 Mbits/s
Fiber type Multimode glass fiber
Wavelength 1300 nm
Ethernet FO module
Connection LC

Maximum attenuation Fiber optic diameter Max attenuation


(fiber optic + connectors) 50/125 or 62.5/125 µm 14 dB

DANGER

HAZARD OF DAMAGE TO THE EYES

Never look into the end of a fiber optic or


connectors of the module
Failure to follow these instructions will result in
death or serious injury.

70 | Easergy P5 Catalog schneider-electric.com


Additional Modules Communication accessories
and Accessories
Modules

Ethernet communication module with


HSR and PRP redundancy
REL51033: Ethernet HSR/PRP FO module
DM101266

The Ethernet communication module with HSR and PRP redundancy is inserted in
both slots M and N of the device. It can be selected as an option when ordering the
device or purchased later and installed on site. It requires fiber optic connection.

It provides PRP (Parallel Redundancy Protocol) and HSR (High-availability


Seamless Redundancy) – selectable by configuration, which allow instantaneous
reconfiguration of the communication system without communication packet loss.

This module includes a 12VDC input for connection of a back-up power supply:
Ethernet HSR/PRP FO module
when the main power supply of Easergy P5 is switched off, the communication
module is still energized and the communication loop is not interrupted.

Characteristics
Standard 2 ports: 100 Base FX
Baud rate 100 Mbits/s
Fiber type Multimode glass fiber
Wavelength 1300 nm
Connection LC

Maximum attenuation Fiber optic diameter Max attenuation


(fiber optic + connectors) 50/125 or 62.5/125 µm 14 dB

Back-up power supply input


Rated voltage 12VDC ±20%

Burden 0.5 W

Dielectric withstand 500V, 50Hz, 1mn

DANGER

HAZARD OF DAMAGE TO THE EYES

Never look into the end of a fiber optic or


connectors of the module
Failure to follow these instructions will result in
death or serious injury.

schneider-electric.com Easergy P5 Catalog | 71


Additional Modules Communication accessories
and Accessories
Modules

Serial line communication module


REL51036: RS485 serial line module
DM101269

The Serial line communication module is inserted in the slot N of the device. It can
be selected as an option when ordering the device or purchased later and installed
on site. It is available in 2 versions for RS485 or fiber optic connection.

Characteristics
EIA 2-wire RS485 differential
Standard or EIA 4-wire RS485 differential (selection by
configuration)
Line polarization 12V, internally provided
RS485 serial line module
2x RJ45 – pin-out as follows:
1. RXD0
2. RXD1
Connection
4. TXD1 (D1)
5. TXD0 (D0)
8. Common
Note: the REL 51053 accessory is used for line termination. (To be ordered separately)

REL51040: Fiber optic serial line module


DM101270

Characteristics
Fiber type Multimode glass fiber
Wavelength 820 nm
Connection ST
Fiber optic diameter Max attenuation

50/125 µm 5.6
Maximum attenuation
62.5/125 µm 9.4
(fiber optic + connectors)
Fibre optic serial line module 100/140 µm 14.9

200 (HCS) µm 19.2

DANGER

HAZARD OF DAMAGE TO THE EYES

Never look into the end of a fiber optic or


connectors of the module
Failure to follow these instructions will result in
death or serious injury.

72 | Easergy P5 Catalog schneider-electric.com


Additional Modules Communication accessories
and Accessories
Modules

Extension module
DM101271

REL51034: Extension module

The Extension module is inserted in the slot P of the device. It can be selected as an
option when ordering the device or purchased later and installed on site. It provides:
• connection to the external modules
• automatic back-up of data:
–– active configuration file
Extension module
–– disturbance records
–– motor-startup records (when available)
–– sequence of events records
–– power system maintenance data log
–– maintenance data of circuit-breaker, switches, motor and transformer
(whichever available)

Characteristics
Connection RJ45
Specific cables have the following references:
• 59660: length 0.6m
Type of cable
• 59661: length 2m
• 59662: length 4m

schneider-electric.com Easergy P5 Catalog | 73


Additional Modules Communication accessories
and Accessories
Modules

Temperature sensor module


PE88063

59641: Temperature sensor module

The Temperature sensor module is an external module used for temperature


measurement with Resistance Temperature Detectors (RTDs). It is connected to the
extension module. It can be selected as an option when ordering the device or
purchased later and installed on site. It provides 8 RTD inputs.
It does not require any auxiliary supply connection.
DE88205

Mechanical characteristics
Assembly Symmetrical DIN rail

3.46 RTD input


Connection Screw-type terminals
Type of cable Shielded cable
Type of RTD Pt100, Ni100, Ni120
Current injected in the RTD 4 mA

1.81
5.67

IRIG-B module
REL51045: IRIG-B module
DM107171

The IRIG-B module is an external module used for accurate time synchronization.
It is connected to the extension module. It can be selected as an option when
ordering the device or purchased later and installed on site. The module provides
both a modulated (MOD INPUT) and an unmodulated input (UNMOD INPUT) and
can automatically detect which input type is used by the user. No configuration of
input type is needed in the Easergy P5 protection relay.

It does not require any auxiliary supply connection.

Mechanical characteristics
Assembly Symmetrical DIN rail

Modulated IRIG-B input


Connection BNC socket
Type of cable 50 ohm coaxial
Time code format B124, B125 (1)
Input signal level 200mV to 20V

Demodulated IRIG-B input


Connection Screw-type terminals
Type of cable Twisted pair
Time code format B004, B005 (1)
Input signal level TTL
(1) according to standard 200-04

74 | Easergy P5 Catalog schneider-electric.com


Additional Modules Communication accessories
and Accessories
Sensors

CSH core-balance current transformers


DE88206

The specifically designed CSH120, CSH200 and CSH300 core balance CTs are
for direct residual or earth/ground fault current measurement. The only difference
between them is the diameter.

Due to their low voltage insulation, they can only be used on shielded cables.

Core balance CT 59635: CSH120 59636: CSH200 59637: CSH300


Inner diameter 120 mm (4.7 in) 200 mm (7.9 in) 300 mm (11.8 in)
Weight 0.6 kg (1.32 lb) 1.4 kg (3.09 lb)
Transformation ratio 1/470
Maximum
20 kA - 1 s
permissible current

CSH120, CSH200 and CSH300 core balance CTs.


Dimensions
DE88396

4 horizontal
4 mounting
horizontal mounting 4 vertical mounting
4 vertical mounting
holes 6 holes 6 holes 6 holes 6

59635: CSH120 59636: CSH200 59637: CSH300


mm in. mm in. mm in.
A 120 4.75 196 7.72 291 11.46
B 164 6.46 256 10.1 360 14.17
D 44 1.73 46 1.81
E 190 7.48 274 10.8 390 15.35
F 80 3.14 120 4.72 120 4.72
H 40 1.57 60 2.36 60 2.36
J 166 6.54 254 10 369 14.53
K 65 2.56 104 4.09
L 35 1.38 37 1.46

schneider-electric.com Easergy P5 Catalog | 75


Additional modules Arc-flash sensors
and accessories
For Easergy P5x30 only

Sensors description
The sensor is used by an arc-flash protection device (Easergy P5 Advanced) or
system to detect the light coming from the arc-flash incident.
The Easergy P5 Advanced arc-flash sensor is activated by strong light. The
sensor transforms the light information into the current signal, which is used by the
protection device to indicate arc-flash.

Arc-flash sensors
REL52801

REL52802

REL52803

REL52804

REL52805

REL52806

REL52807

REL52808

REL52809

REL52810
Characteristics

Material Plastic
Type Standard Pipe
Weight 1,000 g 1,300 g 1,300 g 300 g 400 g 400 g 1,000 g 1,300 g 300 g 400 g
2.20 lb 2.87 lb 2.87 lb 0.66 lb 0.88 lb 0.88 lb 2.20 lb 2.87 lb 0.66 lb 0.88 lb
Cable length (m) 6 20 20 6 6 6 20 20 6 6
Shielded cable - - - - - -
Halogen free - - - - - - - -
Environment Pollution Degree 2
Operation temperature -25°C (-13°F) to +70°C (+158°F)
Light spectrum sensitive area 400 – 1100 nm
Detection time 1 ms
Light sensitivity 8 000 – 10 000 lux
Loop supervision Yes
To connect the interface in the Easergy P5 Standard devices, use REL52883 cable.

REL52801 - 52806 dimensions


DM105635

mm 22.2
DM105632

in 0.83 20
14 0.79
0.55
0.39
10

25
1.83
46.4

0.98

8
0.31
4.2
0.17
REL52807 - 52810 dimensions
mm 11 62
Sensitivity area
DM105636

in 2.44
0.43

Arc-flash sensor: Pipe type

76 | Easergy P5 Catalog schneider-electric.com


Additional Modules Mounting accessories
and Accessories

1 2 The Easergy protection relays are available for flush mounting or rack mounting.
DM104076

Rack mounting accessories


Rack mounting frames have been designed to have dimensions in accordance with
IEC60297 and are supplied ready-to-use. On a standard 483mm (19”) rack system,
this enables combinations up to four Easergy P52 units. If the full 80TE space is not
used, blanking plates (10TE, 20TE and 30TE) are also available.

REL51021: 19 inch rack mounting accessory


Assemble the case (2) and the rack frame (1)
This reference can be used with all Easergy P5x20 and P5x30 relays..

Flush mounting accessories


DM107198

1 2 1 2

Easergy protection relays may be flush mounting. Dedicated accessories will help
for an easy and quick installation:

REL51032: 20TE Flush mounting accessory

This reference can be used with all Easergy P5x20 relays..


F0270

mm
Assemble the cross socks flush (1) 130 ± 0.5
in 180 ± 0.5
DM107199

5.12 ± 0.2
and the case (2) 7.09 ± 0.2
8.07 ± 0.2
205 ± 0.5

8.07 ± 0.2
205 ± 0.5

P5x20 P5x30
REL51052: 30TE Flush mounting accessory

This reference can be used with all Easergy P5x30 relays..

mm
130 ± 0.5
in 180 ± 0.5
5.12 ± 0.2
DM107199

7.09 ± 0.2
8.07 ± 0.2
205 ± 0.5

8.07 ± 0.2
205 ± 0.5

P5x20 P5x30

schneider-electric.com Easergy P5 Catalog | 77


Additional Modules Wiring accessories
and Accessories

90° Ring wiring Commercial reference Wire section Description

REL51059 Ring lug terminal


F0191

0.5 to 1.5
DM107172

(AWG 20 ... 16) 3.68 mm (0.14 in.)


Color: RED

REL51060 1.5 to 2.5 Ring lug terminal


(AWG 16 ... 14) 4.45 mm (0.18 in.)
Color: BLUE

REL51061 2.5 to 6 Ring lug terminal


(AWG 14 ... 10) 6.35 mm (0.25 in.)
Color: YELLOW

Comb-busbars for wiring at slots C, D, E Commercial reference Quantity pack Description

To facilitate the wiring of the terminals in Slots C, D, E of Easergy P5 protection relay, the user can order the following comb-busbars that are
provided in 50-pieces or 100-pieces packs.

REL51054 100 pcs. 2-pin comb-busbar


DM107173

REL51055 100 pcs. 3-pin comb-busbar


DM107174

REL51056 50 pcs. 4-pin comb-busbar


DM107175

REL51057 50 pcs. 5-pin comb-busbar


DM107176

REL51058 50 pcs. 6-pin comb-busbar


DM107177

78 | Easergy P5 Catalog schneider-electric.com


Notes

schneider-electric.com Easergy P5 Catalog | 79


Services

80 | Easergy P5 Catalog schneider-electric.com


Services

Greater peace of mind throughout


82
your installation lifecycle

On-site condition maintenance


83
with ProDiag MV Relay

Achieve higher sustainability


84
with ECOFIT™ solutions

The most eco-friendly products


85
in the industry

schneider-electric.com Easergy P5 Catalog | 81


Services Greater peace of mind
throughout your installation
lifecycle

How can you cut costs and improve Plan


performance at the same time? Schneider Electric helps you plan the full design and execution of your solution,
looking at how to make your process more dependable and optimize time:
When it comes to your electrical
distribution infrastructure, the answer • Technical feasibility studies: Design solution in your environment
is straightforward: get professional • Preliminary design: Accelerate turnaround time to reach a final solution
expertise. design

Install
Life Cycle Services
Life cycle services Schneider Electric will help you to install more efficient, more reliable and safer
solutions based on your plans:
DM408843

• Project management: Complete your projects on time and within budget


Plan
• Commissioning: Ensure your actual performance versus design, through on-
What are my options?
site testing and commissioning, and tools and procedures

Install Operate
How do I install and commission?
Schneider Electric helps you maximize your installation uptime and control your
capital expenditures through its services offering:

Operate • Asset operation solutions: Provide the information you need to increase
safety, enhance installation performance, and optimize asset maintenance and
How do I operate and maintain?
investment
• Advantage service plans: Customize service plans that include preventive,
predictive and corrective maintenance
Optimize
How do I optimize? • On-site maintenance services: Deliver extensive knowledge and experience
in electrical distribution maintenance
• Spare parts management: Ensure spare parts availability and optimized
Renew maintenance budget of your spare parts
How do I renew my solution? • Technical training: Build necessary skills and competencies to properly and
safely operate your installations

Optimize
When it comes to your electrical Schneider Electric proposes recommendations for improved safety, availability,
distribution installation, we can reliability and quality:
help you: • MP4 electrical assessment: Define an improvement and risk management
• Increase productivity, reliability, and safety program
• Mitigate risk and limit downtime
• Keep equipment up to date and extend
lifespan Renew
• Cut cost and increase savings We extend the life of your system while providing upgrades and offers to take full
• Improve your return on investment responsibility for the end-of-life processing of old electrical equipment:

CONTACT US! • Retrofit: Keep up to date and improve the performance of electrical
installations
https://www.schneider-electric.com/
• MV product end of life: Recycle and recover outdated equipment with end-of-
en/work/services/field-services/
life services
electrical-distribution/

82 | Easergy P5 Catalog schneider-electric.com


Services On-site condition maintenance
with ProDiag MV Relay
DM107178

Why carry out diagnostics?


Business competitiveness depends strongly on productivity, and productivity
means uptime. On-site condition maintenance, with regular diagnostics, provides a
long-term solution to avoid downtime.

Why perform Easergy relay diagnostics with Schneider Electric?


Schneider Electric offers a complete range of maintenance services to provide
you with the necessary level of maintenance for your Easergy devices. Having
Schneider Electric at your side means our highly qualified personal can perform the
right maintenance, while complying with manufacturer procedures and international
services.

Diagnosing protection relay tripping


capability
The ProDiag MV Relay diagnostic solution should be used on MV protection relays
that have not received any diagnostics within the last four years.
ProDiag MV Relay: Included in
This diagnostic checks the protection relay’s conformity against the original
the extended 10-year warranty* product specifications to ensure that they meet their goals of:
• Reducing risks by isolating hazardous segments of the network where an
The Easergy P5 extended 10-year warranty electrical fault has been detected
applies under the following conditions: • Maintaining high energy availability to avoid a total power outage and costly
• The product is registered within 18 downtime
months. Simply use the “My Schneider” • Maximizing uptime by performing in-depth analysis and de-energizing
app to scan the QR code found on the equipment only when absolutely necessary
front of your Easergy P5
ProDiag MV Relay’s unique features:
• The ProDiag MV Relay diagnostic is
• Automatic download of all protection relay settings through drivers in the
performed every FOUR YEARS (when ProDiag MV Relay manager
Easergy P5 is used under normal
• Easy verification of modifications made to protection settings since the last
operating conditions)
visit
• Any replaced or repaired products • Easy verification of MV Relay original technical specifications
have the latest hardware and firmware
versions, and are functionally compliant
EM100201

with the original product

* Standard warranty 2 years.


Please check with your local Schneider Electric
representative for extended warranty availability and
conditions.

schneider-electric.com Easergy P5 Catalog | 83


Services Achieve higher sustainability
with ECOFIT™ solutions

Modernizing and upgrading your medium voltage switchgear


doesn’t need to mean your existing infrastructure is destructed.

Schneider Electric retrofit solutions, combined with proper


switchgear maintenance helps you to improve the reliability of
your installation while achieving higher sustainable performance
with ECOFIT™ - a Green Premium™ service.

A true extended life time with ECOFIT™

1999
ECOFITTM 2000 2019 2020 2028 (*)
for your MV Switchboard
MiCOM Px20
• Extend your switchgears lifetime Sepam S20 and S40
• Access asset and energy management with
digitization Easergy P5
• Reduce your environmental impact ECOFIT™ solution
• Enhance your process dependability
• Optimize your maintenance service costs and End of full spare parts
limit your investment Sales End of sales availability
• New ECOFIT™ spare parts availability.
(*) Please consult Schneider electric

ECOFIT™ offers:
Sepam S20 Sepam S40 MiCOM Px20 Easergy P5
20TE or 30TE size 20TE or 30TE size
Case Flush mounting Flush mounting
Flush mounting Flush mounting
Installation Fix Fix Withdrawable case Withdrawable case
Language Multilanguage Multilanguage Multilanguage Multilanguage
IEC 61850 Ed.1 & Ed.2
Modbus serial IEC 60870-5-103 & 101
IEC 61850 Station bus
Kbus IEC 60870-5-101 Ethernet
IEC 60870-5-103 IEC 60870-5-103
Courier DNP3 Ethernet
Communication DNP3 DNP3
IEC60870-5-103 DNP3 serial
Modbus serial Modbus serial
DNP3 Modbus Ethernet
Modbus Ethernet
Modbus serial
EtherNet/IP
24 - 250 Vdc 24 - 250 Vdc 24 - 250 Vdc 24 - 250 Vdc
Power supply
48 - 240 Vac 48 - 240 Vac 48 - 240 Vac 100 - 230 Vac
20TE model: 10 LEDs
Control LED 11 LEDs 11 LEDs 8 LEDs
30TE model: 14 LEDs
Cyber security No No No Yes
Arc-flash No No No 30TE model: 0 to 6 sensors
Back up memory No No No Yes
20TE model: 30TE model: 20TE model:
S20 / S24 / T20 / T24 / B21 S40 / S41 / S42 / S43 / P120 / P121 / P122 /P123
/ B22 / M20 S44 / S50 / S51 / S52 / / P921 / P922 / P923 /
Compatibility with S53 / S54 / T40 / T42 / T50 P721 / P723 / P920
/ T52 / M40 / M41 / G40 30TE model:
P126 / P127 / P225 / P521
/ P220 / P125

84 | Easergy P5 Catalog schneider-electric.com


Services Environmental information with
Green PremiumTM ecolabel

Green Premium
TM

An industry leading portfolio of offers delivering sustainable value

The Green Premium program stands for our commitment to


deliver customer valued sustainable performance. It has been
upgraded with recognized environmental claims and extended to
cover all offers including Products, Services and Solutions.

CO2 and P&L impact through… Resource Performance


More than 75% of our product Green Premium brings improved resource efficiency throughout an asset’s
sales offer superior transparency lifecycle. This includes efficient use of energy and natural resources, along
on the material content, regulatory with the minimization of CO2 emissions.
information and environmental impact
of our products: Cost of ownership optimization through… Circular Performance
We’re helping our customers optimize the total cost of ownership of their
• RoHS compliance assets. To do this, we provide IoT-enabled solutions, as well as upgrade,
• REACh substance information repair, retrofit, and remanufacture services.
• Industry leading # of PEP’s*
• Circularity instructions Peace of mind through… Well-being Performance
Green Premium products are RoHS and REACh compliant. We’re going
beyond regulatory compliance with step-by-step substitution of certain
materials and substances from our products.

Improved sales through… Differentiation


Green Premium delivers strong value propositions through third-party
labels and services. By collaborating with third-party organizations we can
Discover what we support our customers in meeting their sustainability goals such as green
mean by green building certifications.
Check your products!

*PEP: Product Environmental Profile (i.e. Environmental Product Declaration)

schneider-electric.com Easergy P5 Catalog | 85


Ordering

86 | Easergy P5 Catalog schneider-electric.com


Ordering

Easergy P5 configurator 88

Ready-to-use configuration 89
P5x20 ordering variants 89
P5x30 ordering variants 90
Additional modules ordering variants 91
Accessories ordering variants 92

Tools 93

schneider-electric.com Easergy P5 Catalog | 87


Ordering Easergy P5 configurator
Selecting product

Fast and Simple


Easergy P5 CONFIGURATOR:
The unique web tool to quickly and See more on:
easily configure your Easergy P5. • schneider-electric.com/easergy-p5
Or clic directly on : help me choose tool
EM100202

88 | Easergy P5 Catalog schneider-electric.com


Ordering Ready-to-use configuration
P5x20 ordering variants

Easergy P5x20 • Please indicate the Part No. (for example: REL50006) to your
ordering variants Schneider Electric correspondant
• For other variants please contact your Schneider Electric
correspondant

The order forms can be used to define Easergy P5 accessories.

Part No. Qty. Designation

Easergy P5U20 Current relay


REL50301 P5U20-AABA-BAAAA-AAAA 24-250V 3CT 2Io 4DI-4DO no comm + no extension + CS Level 0

REL50302 P5U20-AABA-CAAAA-AAAA 24-250V 3CT 1CSH 4DI-4DO no comm + no extension + CS Level 0

REL50303 P5U20-AABB-BAAAA-AAAA 24-250V 3CT 2Io 10DI-8DO no comm + no extension + CS Level 0

REL50304 P5U20-AABB-CAAAA-AAAA 24-250V 3CT 1CSH 10DI-8DO no comm + no extension + CS Level 0

REL50331 P5U20-AABA-BABAH-AAAA 24-250V 3CT 2Io 4DI-4DO RSTP Eth RJ45 + extension + CS Level 0

REL50332 P5U20-AABA-CABAH-AAAA 24-250V 3CT 1CSH 4DI-4DO RSTP Eth RJ45 + extension + CS Level 0

REL50333 P5U20-AABB-BABAH-AAAA 24-250V 3CT 2Io 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0

REL50334 P5U20-AABB-CABAH-AAAA 24-250V 3CT 1CSH 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0

Easergy P5V20 Voltage relay


REL50305 P5V20-AABA-DAAAA-AAAA 24-250V 4VT 4DI-4DO no comm + no extension + CS Level 0

REL50306 P5V20-AABB-DAAAA-AAAA 24-250V 4VT 10DI-8DO no comm + no extension + CS Level 0

REL50339 P5V20-AABA-DABAH-AAAA 24-250V 4VT 4DI-4DO RSTP Eth RJ45 + extension + CS Level 0

REL50340 P5V20-AABB-DABAH-AAAA 24-250V 4VT 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0

schneider-electric.com Easergy P5 Catalog | 89


Ordering Ready-to-use configuration
P5x30 ordering variants

Easergy P5x30 • Please indicate the Part No. (for example: REL50006) to your
ordering variants Schneider Electric correspondant
• For other variants please contact your Schneider Electric
correspondant

The order forms can be used to define Easergy P5 accessories.

Part No. Qty. Designation

Easergy P5F30 Feeder protection relay


REL50401 P5F30-AACB-GAAAA-AAAA 48-250V 3CT 2Io 4VT 10DI-8DO no comm + no extension + CS Level 0

REL50402 P5F30-AACB-HAAAA-AAAA 48-250V 3CT 1CSH 4VT 10DI-8DO no comm + no extension + CS Level 0

REL50404 P5F30-BACB-GAAAA-AAAA 48-250V 3CT 2Io 4VT 16DI-12DO no comm + no extension + CS Level 0

REL50405 P5F30-BACB-HAAAA-AAAA 48-250V 3CT 1CSH 4VT 16DI-12DO no comm + no extension + CS Level 0

REL50451 P5F30-AACB-GABAH-AAAA 48-250V 3CT 2Io 4VT 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0

REL50452 P5F30-AACB-HABAH-AAAA 48-250V 3CT 1CSH 4VT 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0

REL50453 P5F30-BACB-GABAH-AAAA 48-250V 3CT 2Io 4VT 16DI-12DO RSTP Eth RJ45 + extension + CS Level 0

REL50454 P5F30-BACB-HABAH-AAAA 48-250V 3CT 1CSH 4VT 16DI-12DO RSTP Eth RJ45 + extension + CS Level 0

Easergy P5M30 Motor protection relay


REL50407 P5M30-AACB-GAAAA-AAAA 48-250V 3CT 2Io 4VT 10DI-8DO no comm + no extension + CS Level 0

REL50408 P5M30-AACB-HAAAA-AAAA 48-250V 3CT 1CSH 4VT 10DI-8DO no comm + no extension + CS Level 0

REL50410 P5M30-BACB-GAAAA-AAAA 48-250V 3CT 2Io 4VT 16DI-12DO no comm + no extension + CS Level 0

REL50411 P5M30-BACB-HAAAA-AAAA 48-250V 3CT 1CSH 4VT 16DI-12DO no comm + no extension + CS Level 0

REL50455 P5M30-AACB-GABAH-AAAA 48-250V 3CT 2Io 4VT 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0

REL50456 P5M30-AACB-HABAH-AAAA 48-250V 3CT 1CSH 4VT 10DI-8DO RSTP Eth RJ45 + extension + CS Level 0

REL50457 P5M30-BACB-GABAH-AAAA 48-250V 3CT 2Io 4VT 16DI-12DO RSTP Eth RJ45 + extension + CS Level 0

REL50458 P5M30-BACB-HABAH-AAAA 48-250V 3CT 1CSH 4VT 16DI-12DO RSTP Eth RJ45 + extension + CS Level 0

90 | Easergy P5 Catalog schneider-electric.com


Ordering Ready-to-use configuration
Additional modules ordering variants

Additional modules Qty. Designation

Communication modules
REL51038 Ethernet TP module - slot M

REL51039 Ethernet FO module - slot M

REL51042 Ethernet TP module - slot L

REL51033 Ethernet HSR/PRP FO module - slots MN

REL51036 RS485 serial line module - slot N

VW3A8306RC RS485 line termination accessory

REL51040 Fiber optic serial line module - slot N

REL51034 Extension module - slot P

External modules
59641 8 temperature sensor module (MET148-2)

REL51045 IRIG-B module

59660 0.6m remote module connection cord

59661 2m remote module connection cord

59662 4m remote module connection cord

Sensors
59635 core balance CT, Ø=120mm (CSH120)

59636 core balance CT, Ø=200mm (CSH200)

EMS59572 VT adapter

REL52801 Arc-flash accessory VA1DA-20 Arc-flash sensor 20m

Arc-flash accessory VA1DA-20S-HF Arc-flash sensor


REL52802
20m shielded halogen free
Arc-flash accessory VA1DA-20S Arc-flash sensor 20m
REL52803
shielded
Arc-flash accessory VA1DA-6 Arc-flash sensor 6m
REL52804
connect cable
Arc-flash accessory VA1DA-6S-HF Arc-flash sensor 6m
REL52805
shielded halogen free
Arc-flash accessory VA1DA-6S Arc-flash sensor 6m
REL52806
shielded
Arc-flash accessory VA1EH-20 Arc-flash sensor 20m
REL52807
pipe sensor
Arc-flash accessory VA1EH-20S Arc-flash sensor 20m
REL52808
pipe sensor shielded
Arc-flash accessory VA1EH-6 Arc-flash sensor 6m pipe
REL52809
sensor
Arc-flash accessory VA1EH-6S Arc-flash sensor 6m pipe
REL52810
sensor shielded

schneider-electric.com Easergy P5 Catalog | 91


Ordering Ready-to-use configuration
Accessories ordering variants

Accessories
Qty. Designation

Mounting accessories
REL51032 20TE flush mounting accessory

REL51052 30TE flush mounting accessory

REL51021 19inch rack mounting accessory

REL51018 30TE blanking plate for rack mounting

REL51019 20TE blanking plate for rack mounting

REL51020 10TE blanking plate for rack mounting

Wiring accessories
REL51054 2-pin comb-busbar for I/O - 100 pces

REL51055 3-pin comb-busbar for I/O - 100 pces

REL51056 4-pin comb-busbar for I/O - 50 pces

REL51057 5-pin comb-busbar for I/O - 50 pces

REL51058 6-pin comb-busbar for I/O - 50 pces

REL51059 90° ring wiring terminal red - 250 p

REL51060 90° ring wiring terminal blue - 250 p

REL51061 90° ring wiring terminal yellow - 250 p

Easergy Pro connection cable


59700 PC cord USB

92 | Easergy P5 Catalog schneider-electric.com


TOOLS
Web selector

This site allows you to access the


This international web site allows you to access all the Schneider Electric products in just
Schneider Electric solutions and product information via: two clicks via a comprehensive
range of datasheets, with direct links
• Comprehensive descriptions
to:
• Range datasheets
• Complete libraries: technical
• A download area documents, catalogs, FAQs,
• Product selectors brochures
You can also access information dedicated to your • Selection guides from the e-catalog
business and contact your Schneider Electric country • Product discovery sites and their
support. animations
You will also find illustrated
overviews, news to which you can
subscribe, and a list of country
PM103687

contacts

Training

Training allows you to acquire the


expertise (installation design, work
with power on, etc.) to increase
efficiency and improve customer
service.
The training catalog includes
beginner’s courses in electrical
distribution, knowledge of MV and
LV switchgear, operation and
maintenance of installations, and
design of LV installations to give a
few examples.

schneider-electric.com Easergy P5 Catalog | 93


Green PremiumTM ecolabel product -
Sustainable performance, by design

Schneider Electric Industries SAS


35, rue Joseph Monier - CS 30323
F92506 Rueil-Malmaison Cedex

© 2019 Schneider Electric. All Rights Reserved. Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies.
NRJED313567EN - 27th May 2019

You might also like