2012 Product Catalog
2012 Product Catalog
Copyright
Copyright © NR 2012.01. All rights reserved
We reserve all rights to this document and to the information contained herein. Improper use
in particular reproduction and dissemination to third parties is strictly forbidden except where
expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections
will be included in future editions. If the user nevertheless detects any errors, he is
appreciated any suggested correction or improvement.
Manufacturer:
NR ELECTRIC CO., LTD.
69 Suyuan Avenue, Jiangning, Nanjing 211102, China
Tel: +86 25 8717 8888
Fax: +86 25 8717 8999
www.nrelect.com
E-mail: [email protected]
[email protected]
COMPANY PROFILE 6
Solutions for Integrated Secondary System ...................................... RCS-9647 Reactor Management Relay ............................................ 160
16
PCS-9656 Arc Protection System ..................................................... 277 PCS-994 Frequency & Voltage Controller ........................................ 345
AUTOMATION 337
SMART SUBSTATION SOLUTION 279
MEASUREMENT & RECORDING 353
PCS-221 Merging Unit ..................................................................... 279
PCS-996A Phasor Measurement Unit .............................................. 353
PCS-222 Circuit Breaker Controller ................................................. 282
PCS-9013 DFR Management System .............................................. 358
PCS-223 CB Online Monitoring Unit ................................................ 285
PCS-996R Disturbance Fault Recordor ............................................ 359
PCS-9250-EGI/EAI Electronic CT/VT .............................................. 286
PCS-996S Disturbance Fault Recordor ........................................... 363
PCS-9250-OAI Optic Current Transformer ...................................... 289
PCS-986 Disturbance Fault Recordor ............................................... 367
PCS-9881/9882 Ethernet Switch ..................................................... 309 PCS-9550 HVDC Control & Protection System ................................. 375
RCS-9785C/D GPS Synchronization Clock ..................................... 312 PCS-9250 DC Electronic CT/VT ....................................................... 378
COMMUNICATIONS 380
POWER PLANT AUTOMATION SYSTEM 318 MUX-2M/MUX-64 Interface Unit ...................................................... 380
PCS-9100 Distribution Control System for Thermal Control (DCS) ... 318 PCS-912/913 Power Line Carrier Transceiver .................................. 382
PCS-9700 Electrical Control System for Motor Control (ECS) .......... 320
PCS-9700 Network Control System for Power Station (NCS) ........... 321
PCS-9575 Static Frequency Converter (SFC) ................................... 324 CJX/CZX-12R/CZX-22R Interposing Relay Set ............................... 385
PCS-9580 Static Var Compensator (SVC) ........................................ 325 Installation Instruction ....................................................................... 395
PCS-9570 Fixed Series Compensator (FSC) .................................... 330 SOFTWARE KIT 396
PCS-Explorer ...................................................................................... 396
PCS-9563 PV Grid-Interconnection system ...................................... 331 SCL Configuratiom Software Kit ....................................................... 402
Solutions
for Power Grid
With innovative technologies and years of operational faults within a sub-cycle time and is immunity to power swing,
experiences, NR offers practical solutions for power grid all heavy load and weak-infeed, and is capable to detect high
over the world, including engineered packages and turnkey resistance faults. During power swing, the Power Swing
solutions for new constructed and referbishment projects. The Blocking Logic can properly block distance elements, keep
scope ranges from transmission to distribution substations and stable to an external and quickly clear an internal fault.
systems from 10 kV to 1000 kV.
The PCS/RCS-9700 is an innovative automation solution for
substations, generations and industrials with many advanced
Transmission technologies and patents. It integrates the application of
NR protective relays are designed based on Deviation of Power protection, control, Ethernet, IT and communication technology
Frequency Component (DPFC) and power swing blocking based on international standard. The PCS/RCS-9700 adopts
principles which have successfully brought in a combination layered distributed architecture with bay-oriented and object-
of quick reaction time and reliability, thereby meeting the oriented structure to build a more reliable and easier system for
requirements of power system safety and stability. The unique the future extension and maintenance.
DPFC incremental-quantity distance element can clear internal
With proven technologies and abundant operating experiences, - Generator & Generator-Transformer Unit
NR is dedicated to working on the protection and automation The microprocessor based generator-transformer unit protection
solutions for power plants with unit capacity up to 1000MW. provides comprehensive protection, control and monitoring
The scope ranges from conventional to renewable based power for small to large generators, generator-transformer units,
generation, covering thermal power plants, nuclear power plants, transformers, excitation transformers and exciters. Transformer
hydro power plants, wind power plants and solar power plants. auxiliary relays are provided to provide the mechanical signals
NR's innovative total solutuions and products help optimize such as thermal, gas, oil temperature, winding temperature,
performance, improve reliability, enhance efficiency and minimize pressure, oil level and so on.
environmental impact throughout the plant life cycle.
- Generating Station
Protection, Control & Monitoring NR offers PCS/RCS-900 series high integrated protection and
NR provides cost-effective solutions for the protection, control control devices to generating station in power plants to maintain
and monitoring of power plant assets, including electrical the best quality of service available and communication
protection and field excitation control for generators, mechanism capabilities.
protection for transformers and thermal control for rotors.
The rapid developed indutrial plants requires flexible, ease to to feeders, capacitor banks, reactors and motors in 380V power
use and high efficiency solutions with ability to withstand severe system of industrial enterprises. The PCS-9700M automation
environment. From reliable power generation to automation and system consists of 6kV/600V explosion-proof bay control unit,
remote monitoring, NR can help meet power demands, improve explosion-proof communication gateway, Ethernet switch,
power efficiency and protect plant assets, to achieve critical subsurface video monitoring system, ground monitoring master
demands and high operational efficiency. station and EMS for coal mine shaft.
Transportation
- Electrified Railway
NR’s PCS-9680 series devices feature the integration of
protection, monitoring and disturbance recording functions in
one rack, providing safeguard and guarantee of economical
operation for the entire electrified railway system. The PCS-
9680 series covers transformer protection, feeder protection,
capacitor protection and automatic transfer device. It introduces
harmonics blocking and self-adapting harmonics restraint Commercial Buildings
functions to solve the impact and harmonics caused by loads in NR’s power protection, process control and automation products
electric traction feeding system. can guarantee the uninterrupted supply during a power outage
for different mission-critical applications. NR’s customized
system solutions and complete products series provide highly
reliable safeguarding of business and public entities and have
been well proven in many world famous projects, such as 2008
Beijing Olympic Stadiums and 2010 World Expo in Shanghai.
- Metro Railway
As an important part of metro power supply system, the safe
operation of 110kV/35kV substation will affect the stability of
the entire metro system. The RCS-9600CS series are well
proven products that can provide protection and monitoring for
transmission line, feeders, and transformers in the 110kV/35kV
substation. The RCS-9700 substation automation system Electronics
integrates the protection, control, Ethernet and communication NR can provide reliable power protection, communications and
technology, enabling the implementation of unattended management systems to ensure the uninterrupted power supply
operation for 110kV/35kV metro substation. for electronic manufacturers. NR’s innovative protection devices
and fast transfer devices can quickly detect faults and trip the
faulty line to prevent severe disaster. The fast transfer devices
In station level, it integrates protection, control, monitoring, metering, recording and communication in substation.
In network level, it provides Energy Management System (EMS), Distributed Management System (DMS), Tele-
Meter Reading (TMR), Power Stability Control System (PSCS), Wide Area Measurement System (WAMS),
Disturbance Management System, Relay Management System and CCTV Management System. In addition, the
communication infrastructures between substations and
dispatching center are integrated in the system. Inside the
dispatching center and substations, the LAN is used for the
internal communication. WAN and/or SDH/SONET networks
are adopted for the inter-station communications according
to the specific application.
NR’s is dedicated to providing diverse protection & control products with well-proven
technologies that has been widely used in thousands of projects worldwide. The
protection & control solution covers all primary assets, including generator, transformer,
transmission line, busbar, circuit breaker, reactor, capacitor, motor and beyond.
In the hardware platform, the innovative two-out-of-two logic is adopted to avoid the
mal-operation due to the failure of any component. Dependability and security are
obtained via the redundant scheme and the unique two-out-of-two logic. As well, NR has
a good understanding of protection theory and created many innovative technologies
or patents to improve the protection performances. The protection principle based on
Deviation of Power Frequency Component (DPFC) was firstly introduced by NR that it
can clear the short-circuit fault in an extreme short time. According to the field records,
the fast distance protection using DPFC operated in 3ms for the close-in fault of a
500kV transmission line. The unique power swing blocking logic can properly supervise
the distance protection as well as correctly trip the internal fault during power swing via
the independent detector element for the fault with power swing. In busbar protection,
the patented weighted anti-saturation algorithm is integrated in the current differential
protection to keep security to external fault and quickly clear internal fault during CT
saturation. The transformer protection adopts adaptive-blocking and cross-blocking
methods for inrush current to improve the performance.
With the development of information technology, the communication is extended to the switchyard
and the substation is evolving from Substation Automation System (SAS) to Smart Substation
Solution, becoming an important part of Smart Grid.
NR provides a complete smart substation solution for power grid customers with leading
technologies on Electronic and Optical CT/VT, Merging Unit and Circuit Breaker Controller. NR’s
Smart Substation Solution consists of process bus and station bus. The process bus employs
IEC 61850-9-2 Sampling Value, IEC 61850-8-1 GOOSE for time-critical message and IEEE 1588,
supporting flexible network topologies including Point-to-Point optical communication and Double-
Star Ethernet. The station bus employs IEC 61850-8-1 MMS, GOOSE message and SNTP. It
supports Double-Star Ethernet and Single- or Double- Ring Ethernet.
Substation automation system is a mature method to manage substations and optimize the power
operation performance. Automation system is provided for assets management in substation,
power system status monitoring, remote/local control, fault analysis & evaluation, operators’
authorization, history data statistic & analysis and communication to load dispatching center. It
manages utility assets, monitors operation states and measures load profile. All the information is
collected and visually displayed in the control room. Operators can execute the remote control and
interlocking via the workstation.
NR provides the integrated automation solution for new substation or retrofit substation, covering
consulting, design, supply, installation, training, commissioning & trial operation. The solution is
totally complied with IEC 61850 over double-star LAN or ring LAN. NR has set up its own IEC
61850 Level B Laboratory which can help check the compliance with IEC 61850. As well, NR’s
IEDs has certified by KEMA for the IEC 61850 conformance. NR supplies the complete products
for substation automation system, including Bay Control Unit, Protective Relay, Fault Recorder,
PMU, Protocol Converter, Gateway, GPS Receiver, Gigabit Switch and HMI Software. NR can
also integrate the metering and CCTV into the automation system.
In NR’s solution, the redundant scheme is comprehensively considered, such as redundant server
& database, redundant network, redundant gateway, redundant GPS receiver and redundant
protocol converter. Standby system will be automatically switched to active state during the hot
system failure in a very short time.
Energy Management
Energy Management System (EMS) and Distribution Management System (DMS) monitor,
manage and optimize the energy generation, transmission, distribution and consumption to help
the utility or industrial customers to maximize efficiency and minimize cost. It supervises the whole
power network and produces the accurate control strategy to realize the energy optimization.
NR’s Energy Management System provides the versatile interfaces and protocols for connection
with RTU or Gateway in substations, such as IEC 61870-5-101, IEC 61870-5-104, DNP 3.0. The
redundant scheme of server, database and communication is adopted to improve the reliability. It
fully complies with IEC 61970 standard, providing a unified data platform based on CIM (Common
Information Model).
NR’s EMS solution provides diverse functions that are tailored according to the specific project
requirements. It provides the Supervisory Control and Data Acquisition (SCADA), Automatic
Generation Control (AGC), versatile Power Application Software (PAS), Dispatcher Training
Simulator (DTS), Wide Area Measurement System (WAMS) and Tele-Meter Reading (TMR).
Because all the data acquired from the substations is stored in the unified database with
standardized access interfaces, the application function is easily expandable to meet the specific
application.
Blackouts will cause serious impacts to the modern society from economy to life, particularly critical to the important
institutes, such as hospital, underground mine, gas station, sewage treatment plants, etc.
NR provides the well-proven three-defense-line solution to improve the power system stability and significantly
reduce the blackouts. The first defense line means the reliable and high-speed relays that can clear the faults
correctly and fast, especially the reasonable actions during system oscillation, unstable frequency and unstable
voltage.
The unique second defense line is the innovative Power Stability Control System (PSCS) that provides the system-
level solution for the whole power grid. Different from other System Protection Schemes (SPS), the PSCS is based
on instability prediction instead of instability measurement. Before the installation, the tactic table is pre-determined
and simulated according to the previous stability study and strategy analysis. After installation, PSCS acquires all
the necessary real-time data from the substations or power plants and seeks the appropriate remedy actions in the
tactic table to pull the power system back to stability state BEFORE the system goes into instability state. Other SPS
only detects the system parameters and take actions AFTER the system enters instability state.
The third defense line is the out-of-step controller and frequency/voltage controller. These controllers detect the
system parameters and take actions to prevent the expansion of instability. Generally a basic requirement for
these controllers is that they should not operate during short-circuit fault which would be cleared by the protective
relays. Vice versa, the relay should not operate during system instability and leave it for the controllers to take
measurement.
The after-disturbance analysis is important to discover the potential problems in power system and help customers
enhance the system reliability. Generally the disturbance recording function using the dedicated Disturbance &
Fault Record (DFR) or integrated in the protective relay is applied in the substations and power plants to collect the
disturbance data.
NR provides the dedicated DFR to record the disturbance information including analog and
digital quantities to help verify the proper operation of protection & control devices and analyze
the potential problem in power system. To enhance the analysis capability, NR provides the
DFR management system based on the system-level data for the regional network and wide
area network. It connects with the DFRs in all substations and collects the disturbance data of
the whole power network. Engineers can analysis the disturbance cases using the data of the
complete network. The disturbance management system adopts IEC61850, FTP and IEC60870-5-
103 based on SDH/SONET or WAN.
Phasor Measurement Unit (PMU) installed in the substations measures and sends the phasor to
the remote control center. The operator could visually view the synchronized phasors of the whole
power grid via the Wide Area Measurement System (WAMS), as well it could help the operators
make a correct decision to take remedy actions for power stability.
NR provides the complete solution of WAMS including the PMU and PDC (Phasor Data
Concentrator). The WAMS software package installed in the dispatching center collects all the
pahsor data from PMU and PDC in all substations and shows all the synchronized phasors to
operators. The PMUs and PDCs communicate with the dispatching center via SDH/SONET or
WAN.
Reactive power is necessary to power system and plenty of power components can generate
or absorb reactive power. The balance of reactive power is an important issue since it is relative
to the system voltage. Generally the reactive power should be locally compensated to avoid the
transmission in power network so as to reduce losses.
The installation points of SVC in the network will be determined based on the system study.
SVC at the suitable points will increase transfer capability, maintain voltage profile, reduce
voltage fluctuation and enhance voltage stability. As well, the SVC will help suppress the power
oscillations via voltage amplitude modulation.
NR provides Static VAR Compensator (SVC) solution to smoothly adjust reactive power in the
power grid or industrial to achieve the stable voltage profile. It is composed of thyristors, reactors,
capacitor banks and control system. Versatile technologies are integrated in NR’s SVC solution,
including Thyristor-Controlled Reactor (TCR), Thyristor-Switched Capacitor (TSC), Breaker-
Switched Capacitor (BSC) or Fixed Capacitor (FC).
Flexible schemes are designed to meet the specific
project requirement, including TCR and TSC, TCR and
BSC or TCR and FC.
To obtain a stable voltage conditions, the produced reactive power must be compensated. The most advanced solution to compensate the
reactive power is using high performance Insulated Gate Bipolar Transistor (IGBT) to provide fast and variable reactive power to the grid.
The STATCOM can be considered as an advanced static VAR compensator (Advanced SVC).
NR provides the Static Synchronous Compensator (STATCOM) based on Voltage-Sourced-Converter (VSC) for reactive power regulating
used on flexible AC transmission, renewable energy generation, heavy loads centers and industrial fields. It helps utilities and industrial
customers gain economical benefits through solving voltage unbalance and distortion, restraining system overvoltage, supplying damped
oscillations and improving power factor.
• Faster response
The output of STATCOM range from rated capacitive reactive power to rated inductive reactive power with a very short time delay.
• Better results
STATCOM can compensate reactive power, harmonic and unbalance
of load, while SVC only compensates the reactive power.
• Fewer harmonic
Compared to SVC, STATCOM generates fewer harmonic and also
has active filter function.
De-Icer
Heavy ice covering on transmission lines may cause tower collapse, break transmission lines and destroy
power grid integrality, generating serious damages to power system, or even large-scale regional outage.
NR develops the innovative De-Icer system to help customer solve the dangerous problem caused by
serious climate. NR provides the fixed De-Icer and relocatable De-Icer to meet the different applications.
And during the normal state, the De-Icer could be used as SVC to compensate the reactive power in the
power grid. It could be switched into the de-Icing state according to the field requirement.
De-Icer adopts thyristor rectifier converting AC current into DC current and injects the DC current into the
conductors, and then realizes de-icing with the heat produced by DC current crossing the line resistance.
When de-icing a transmission line, the line should be out of service and the 3-phase conductor should be
connected with the De-Icer. At the opposite substation, the 3-phase conductor shall be short-circuited. The
DC current will be injected into the conductor via Phase Selecting Switches (PSS) integrated in De-Icer.
The controller of De-Icer controls the DC current via adjusting triggering angle of thyristor.
To protect our environment, human beings should put more emphasis on the renewable energy. Compared to traditional
energy, renewable energy comes from natural resources such as sunlight, wind and geothermal heat, which are naturally
replenished and has minimum impact on environment. Nowadays renewable power generators are spreading across
many countries, providing a significant share of electricity in some areas. NR provides the innovative technologies for the
grid interconnection of renewable energy, including wind energy converter and photovoltaic (PV) inverter.
mode, including pulse mode control for low frequency, load to inject the exciting current into rotor to estabilish the magnetic
commutation control for high frequency and excitation current field. The excitation system need to maintain the generator
control. voltage level and is required to act on power system static and
transient conditions.
Modern HVDC power transmission asks for high efficient solution featuring
true reliability and flexibility. For this reason, NR is continuously improving
the solution to HVDC control and protection based on years’ of practical
experiences and the most leading-edge technologies. The outstanding
solution includes the control and protection for conventional HVDC
transmission through overhead lines or submarine cables, back-to-back
HVDC transmission and Voltage Source Converter (VSC) based HVDC
transmission.
Figure 1. Bulk electricity transmission over long distance lines transformer. The control and protection system
is built in redundant structure to ensure the
operation of HVDC system is immune to any
single failure.
VSC-Based HVDC
DC Electronic CT/VT
Engineering Services
Consulting Service
NR's experienced engineering service teams provide a wealth of telecome consulting and on-site
commissioning for end users all over the world. Customers also can contact NR by hotline or by visiting
official website. NR is always dedicated in training professional engineers and technicians to serve
customers better. We believe that their abundant on-site experiences and expert skills will help users to
solve any emergencies and potential problems.
The dedicated services group offers a wide range of professional consultancy services to customers,
including:
• On-site commissioning
• Software maintenance
NR's regional engineering teams are always working in close cooperation with end users to reduce
commissioning time and cost. This service enables customers to work with our factory-trained technical staffs
on-site to support testing and commissioning efforts and provide hands-on training for your personnel.
Engineering Design
NR engineers design protection and automation scheme for transmission, distribution and generation systems,
and offer unique engineering design on power quality control and system study. The service includes system
settings calculation, complete design and drawing packages and Engineering studies. It enables NR to
promote awareness of detailed system situations of each specific case and to customize system solutions to fit
customers' demands.
The engineering design on power quality focuses on stabilizing weak systems and improving dynamic voltage
control in industrial system. NR's professional engineers will help users to perform system analysis and
valve design. Engineering design on system study is an essential step of power stability control. NR's expert
engineers are involved in the system analysis including studies on system structure, power flows, generation
and consumption, ect., to draw up the offline tactic table for power stability control.
NR Training Program
NR Training Center
NR has founded a training center with the samples of all products to provide professional training
for domestic and oversea customers. At NR's advanced training center, we offer regularly scheduled
courses containing theoretical courses and hands-on interactions using relays & meters, relay test tools,
automation softwares, communication equipments and personal computers.
The key to the successful training program is qualified and expert instructors. At NR training center, a
group of well trained instructors with years of practical experience in the protection industry is dedicated
to bringing high quality technical topics in different languages, including English, Russan, French and
Spainish.
On-site Training
To maximize customers' benefits from our training, NR offers the option of conducting training courses
at users' facility. These on-site courses can be tailored based on the specific engineering project and
requirements. All the necessary testers and literature will be provided on-site for operation practice.
RCS-902
PCS-902
RCS-931
RCS-901
RCS-941
RCS-943
RCS-922
RCS-924
RCS-925
PCS-931
PCS-924
Functional
Function
Code
• DPFC distance protection. (21D) Mho and quadrilateral characteristics are provided for
Innovative Deviation of Power Frequency Component both phase and ground distance protections. It provides
distance protection can quickly clear faults and is immune to the interfaces for station bus and process bus respectively
the load current, weak-infeed and power swing. and supports IEC 61850-8-1 MMS, GOOSE, IEC 61850-9-
2 Sampling Value. It provides the RJ-45 faceplate port for
• Four zones of phase-to-phase distance protection. (21P) testing and setting to make commissioning and maintenance
Four zones of phase-to-phase distance protection integrates easier.
the memorized positive sequence voltage polarization,
direction characteristic, load blinder and unique low-voltage
distance element. The fourth zone can be set as the reverse
directional protection.
Overcurrent protection can be supervised by voltage element
and directional element. IDMT curves complied with IEC and
• Four zones of phase-to-ground distance protection. (21G)
ANSI standard are available for selection.
Four zones of phase-to-ground distance protection integrates
the memorized positive sequence voltage polarization,
• Four stages of directional zero sequence overcurrent
reactance characteristic, direction characteristic, load blinder
protection. (67N, 50/51N)
and unique low-voltage distance element. The fourth zone is
Zero sequence overcurrent protection can be supervised
the reverse directional protection.
by voltage element and directional element. IDMT curves
complied with IEC and ANSI standard are present for
• Four stages of directional phase overcurrent protection. (67P,
selection.
50/51P)
• Thermal overload protection. (49) • The typical pickup time is 10 ms for a close-in fault, 15 ms
The output of thermal overload protection can be set to for a fault in the middle of a line, 25 ms for a remote fault.
tripping or alarm. • The relay is based on NR’s well established and proven
UAPC hardware platform with multi-processor architecture.
• Synchronism check. (25) The multi CPU technology supports parallel operating
Synchronism check and dead bus or dead line check are simultaneously.
both provided for auto-reclosing.
• The binary output can be used to initiate the power line
• Auto-reclosing (single and/or three-pole for one or two carrier transceiver or other signal channel, and the optical
breakers). (79) fiber is optional instead of carriers to realize the pilot
Single/three pole auto-reclosing is applicable to one or two scheme.
breakers. Priority logic is integrated for use on one-and-a- • The sensitive DPFC distance protection is integrated to
half breaker arrangement and ring breaker arrangement. target on the quick clearance of internal fault without being
affected by power swing.
• Voltage and current drift auto adjustment.
The relay continually and automatically traces the voltage • Phase-ground distance protection is provided with zero-
and current drifts and adjusts the zero point to the normal sequence compensation.
value. • The patented adaptive floating threshold is insensitive to
system imbalance and disturbance. The measuring element
• Frequency tracking. can achieve high security and high speed simultaneously.
Frequency tracking is provided to accommodate the
frequency shift in power system. • The unique built-in power swing blocking logic can properly
supervise the distance protection during a power swing. The
power swing blocking logic can prevent mal-operation for
Monitoring and Metering an external fault and quickly clear the internal fault during a
• CT failure supervision. power swing.
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<30W (for conventional substation application)
Quiescent condition
<35W (for smart substation application)
Burden
<35W (for conventional substation application)
Operating condition
<40W (for smart substation application)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 200In
for half a cycle 250In
Burden <0.2VA/phase < 0.25VA/phase
Analog Voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V 200V (Broken delta for residual voltage)
linear to 1~170V 1~233V
continuously 200V 220V
Thermal withstand capability 10s 260V 380V
1s 300V 420V
Burden < 0.20VA/phase @Un < 0.8VA/phase@Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Housing color Silver grey
Protection class: IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
Type Test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Technical data
Power Supply
Rated Voltage (Un) 24 Vdc, 30 Vdc, 48 Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 25 W
Burden
Operating condition < 55 W
Backup battery type ML2032, 3V, 65mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class per IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800bps~57600bps
Transmission distance < 1000m@4800bps
RS-485 (EIA) Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type ST
Baud rate 4800bps~57600bps
Transmission standard 100Base-FX,
Transmission distance <1500m
RS-485 (EIA) Optical(Optional)
Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
IEC61000-4-8:2001, Class V
Power frequency magnetic field immunity 100A/m continuous
1000A/m for 1-3s
IEC61000-4-9:2001, Class V
Pulse magnetic field immunity 6.4/16 us
1000A/m for 3s
IEC61000-4-10:2001, Class V
Damped oscillatory magnetic field immunity
100kHz & 1MHz – 100A/m
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
• DPFC differential protection. (87) • Four zones of phase-to-ground distance protection. (21G)
Four zones of phase-to-ground distance protection inte-
grates the memorized positive sequence voltage polariza-
tion, reactance characteristic, direction characteristic, load
blinder and unique low-voltage distance element. The fourth
zone is the reversal directional protection. Mho and quadri-
lateral characteristics are provided for selection.
• Breaker failure protection for one or two breakers (50BF) • Voltage and current drift auto adjustment.
Breaker failure protection can be applied to one breaker and The relay continually and automatically traces the voltage
two breakers. and current drifts and adjusts the zero point to the normal
value.
• Two stages of under voltage protection and two stages of
over voltage protection (27/59) • Frequency tracking.
Under/over phase voltage protection and under/over (positive Frequency tracking is provided to accommodate the fre-
sequence, negative sequence or zero sequence) voltage quency shift in power system.
protection are provided.
• Out-of-step tripping (78) • Six or Eight 100Base-FX ports with IEC 61850-9-2 Sampling
The out-of-step status is detected in the relay and it can be Value and GOOSE for time-critical message
used to trip the transmission line. • One RS-485 rear port for clock synchronization
• One RS-232 rear port for printer
• Unique power swing blocking logic. (68)
• One faceplate RJ45 port for testing and setting
The power swing blocking logic can prevent mal-operation
during external fault a power swing and clear the internal • Clock synchronization via Pulse-Per-Second, IRIG-B and
fault in power swing. SNTP
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<30W (for conventional substation application)
Quiescent condition
<35W (for smart substation application)
Burden
<35W (for conventional substation application)
Operating condition
<40W (for smart substation application)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 200In
for half a cycle 250In
Burden <0.2VA/phase < 0.25VA/phase
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Housing color Silver grey
Protection class: IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type Test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
• Stages of directional zero sequence overcurrent protection. • Total 1280 SOE, including tripping , alarm, binary input
(67N, 50/51N) change and human operation reports.
• Breaker failure protection. (50BF) • High resolution oscillography of last 24 oscillograms. (Com-
patible with COMTRADE format)
• Two stages of under voltage protection and two stages of
over voltage protection. (27/59)
• Four stages of frequency protection (81)
Communications
• Stub protection for T-Zone in 3/2 breaker and ring breaker • 1 or 2 communication channels with dedicated fiber or multi-
application (50S) plexer fiber for protection
Technical data
Power Supply
Rated Voltage (Un) 24 Vdc, 30 Vdc, 48 Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 25 W
Burden
Operating condition < 55 W
Backup battery type ML2032, 3V, 65mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
Thermal continuously 120 V 120 V 200V
withstand 10s 200 V 200 V 350V
capability 1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class per IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800bps~57600bps
RS-485 (EIA) Electrical Transmission distance < 1000m@4800bps
Maximal capacity 32
Twisted Pair Screened twisted pair cable
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
• CT failure supervision.
• VT failure supervision.
• Synchro-check voltage failure supervision.
• Tripping circuit supervision.
• Fault Recorder.
• Fault Locator.
• 64 tripping reports, 64 alarm reports and 64 binary input
status change reports.
• High resolution oscillography of last 24 oscillograms.
Functions (Compatible with COMTRADE format)
Communications
• Pilot DPFC (Deviation Power Frequency Variation
Component) directional comparison line protection. (85) • Pilot communication schemes (PUTT, POTT, WI) with fiber,
• Pilot zero sequence directional comparison protection. (DEF) carrier or other channels.
• DPFC distance protection. (21D) • 2 optional Ethernet ports with IEC 61850 or IEC 60870-5-
103 over TCP/IP
• Phase-to-phase distance protection. (21P)
• 2 RS-485 communication rear ports conform to IEC 60870-
• Phase-to-ground distance protection. (21G)
5-103 protocol
• Directional phase overcurrent protection. (67P)
• 1 RS-485 communication rear ports for clock synchronization
• Phase overcurrent protection. (50/51P)
• 1 RS-232 communication rear ports or RS-485 for printer
• Directional zero sequence overcurrent protection. (67N)
• 1 RS-232 communication faceplate port for testing and
• Zero sequence overcurrent protection. (50/51N) setting
• Under/Over voltage protection. (27/59) • GPS clock.
• Time overcurrent protection during VT failure. (51P VT)
• Time zero sequence protection during VT failure. (51N VT)
• Switch-onto-fault (SOTF) logic. Features
• Power swing blocking (68)
• The typical operating time is 10 ms for a close-in fault, 15 ms
• Fault detection element under pole discrepancy condition
for a fault in the middle of the line, 25 ms for a remote fault.
• Overload alarm function.
• The protection principles of DPFC directional comparison
• Synchronism check. (25)
element and DPFC distance element are applied in the relay.
• Auto-reclosing (single-pole and three-pole). (79) It can significantly reduce the pickup time and clear the fault
• Voltage and current drift auto adjustment. fast. The DPFC directional pilot scheme is sensitive which
• Self diagnostict. makes the system reliable. The system adopting this pilot
Technical data
Power Supply
Rated Voltage (Un) 24 Vdc, 30 Vdc, 48 Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 25 W
Burden
Operating condition < 55 W
Backup battery type ML2032, 3V, 65mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
Thermal continuously 120 V 120 V 200V
withstand 10s 200 V 200 V 350V
capability 1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class: IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800bps~57600bps
Transmission distance < 1000m@4800bps
RS-485 (EIA) Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type ST
Baud rate 4800bps~57600bps
Transmission standard 100Base-FX,
Transmission distance <1500m
RS-485 (EIA) Optical(Optional)
Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type RJ-45
Transmission rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Ethernet Safety level Isolation to ELV level
Port number 2
Connector type SC
Transmission Rate 100Mbits/s
Optical(optional)
Transmission standard 100Base-FX
Transmission distance < 1500m
Optical Fiber Type Multi-mode or single-mode
Type test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
IEC61000-4-8:2001, Class V
Power frequency magnetic field immunity 100A/m continuous
1000A/m for 1-3s
IEC61000-4-9:2001, Class V
Pulse magnetic field immunity 6.4/16 us
1000A/m for 3s
IEC61000-4-10:2001, Class V
Damped oscillatory magnetic field immunity
100kHz & 1MHz – 100A/m
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Technical data
Power Supply
Rated Voltage (Un) 24 Vdc, 30 Vdc, 48 Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 25 W
Burden
Operating condition < 55 W
Backup battery type ML2032, 3V, 65mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
Thermal continuously 120 V 120 V 200V
withstand 10s 200 V 200 V 350V
capability 1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Read more on the web
www.nrelect.com read more on www.nrelect.com 63
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class: IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800bps~57600bps
Transmission distance < 1000m@4800bps
RS-485 (EIA) Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type ST
Baud rate 4800bps~57600bps
Transmission standard 100Base-FX,
Transmission distance <1500m
RS-485 (EIA) Optical(Optional)
Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type RJ-45
Transmission rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Ethernet Safety level Isolation to ELV level
Port number 2
Connector type SC
Transmission Rate 100Mbits/s
Optical(optional)
Transmission standard 100Base-FX
Transmission distance < 1500m
Optical Fiber Type Multi-mode or single-mode
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
IEC61000-4-8:2001, Class V
Power frequency magnetic field immunity 100A/m continuous
1000A/m for 1-3s
IEC61000-4-9:2001, Class V
Pulse magnetic field immunity 6.4/16 us
1000A/m for 3s
IEC61000-4-10:2001, Class V
Damped oscillatory magnetic field immunity
100kHz & 1MHz – 100A/m
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Communications
Functions
• High-speed optical fiber channel for protection data ex-
Protection and Control changing.
• Phase current differential protection (87P) • 2 optional Ethernet ports with IEC 61850 protocol
• Zero sequence current differential protection (87N) • 2 RS-485 communication rear ports with IEC 60870-5-103
protocol.
• DPFC (Deviation Power Frequency Component) differential
protection (87D) • 1 RS-485 communication rear ports for clock synchroniza-
tion.
• Phase-phase distance protection (21P)
• 1 RS-232 communication rear ports or RS-485 for printer.
• Phase-ground distance protection (21G)
• 1 RS-232 communication faceplate port for testing and set-
• Four-stage directional phase overcurrent protection (67P,
ting.
50P, 51P)
• Four-stage directional zero sequence overcurrent protection
(67N, 50N, 51N)
• Power swing blocking function (68) Features
• Overload alarm function (49)
• Circuit breaker monitoring • The relay integrates AC voltage auto-switching module. In
the double-busbar scheme, when the transmission line is
• Voltage and current drift auto regulation
switched between the two busbars, the AC voltage inputs of
• Synchro-checking (25) the relay will be auto-switched according to the actual bus-
• Auto-reclosing (three-pole) function (79) bar VT based on the states of isolators.
• Monitoring and Metering • The patented adaptive floating threshold method is adopted,
which is insensitive to system unbalance and disturbance.
Technical data
Power Supply
Rated Voltage (Un) 24 Vdc, 30 Vdc, 48 Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 25 W
Burden
Operating condition < 55 W
Backup battery type ML2032, 3V, 65mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
Thermal continuously 120 V 120 V 200V
withstand 10s 200 V 200 V 350V
capability 1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Protection class: IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800bps~57600bps
Transmission distance < 1000m@4800bps
RS-485 (EIA) Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type ST
Baud rate 4800bps~57600bps
Transmission standard 100Base-FX,
Transmission distance <1500m
RS-485 (EIA) Optical(Optional)
Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type RJ-45
Transmission rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Ethernet
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2
Optical(optional) Connector type SC
Transmission Rate 100Mbits/s
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
IEC61000-4-8:2001, Class V
Power frequency magnetic field immunity 100A/m continuous
1000A/m for 1-3s
IEC61000-4-9:2001, Class V
Pulse magnetic field immunity 6.4/16 us
1000A/m for 3s
IEC61000-4-10:2001, Class V
Damped oscillatory magnetic field immunity
100kHz & 1MHz – 100A/m
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Functions
Protection and Control
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<30W (for conventional substation application)
Quiescent condition
<35W (for smart substation application)
Burden
<35W (for conventional substation application)
Operating condition
<40W (for smart substation application)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 200In
for half a cycle 250In
Burden <0.2VA/phase < 0.25VA/phase
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Housing color Silver grey
Protection class: IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type Test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
• Rear communication ports: Ethernet with IEC 61850 or 2 • The relay provides GPS clock synchronization, including
RS-485 with IEC 60870-5-103 protocol, 1 RS-485 with clock message, second pulse, minute pulse and IRIG-B
synchronization, 1 RS-232 or RS-485 with printer. synchronization.
• Front communication port: 1 RS-232 for testing and setting. • The format of event report is compatible with international
COMTRADE file.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class; IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Features
• The patented adaptive floating threshold method is adopted,
which is insensitive to system unbalance and disturbance.
The measuring element can get both high security and high
speed simultaneously.
Functions and the other for protection and its logic. Tripping outputs
are supervised by the fault detector to prevent any mal-
• Current differential protection. (87) operation.
• Two-stage overcurrent protection for energizing a bus or a • The connector type can be selected as plug in/out terminal
line (50E) connector or crimp terminal connector. The unique plug in/
• CT failure open detection logic. out terminal connectors from the relay rear panel to the ter-
minal blocks on the rack or cabinet makes the on-site com-
• Tripping circuit supervision.
missioning and replacement much easier than the traditional
• Current drift auto adjustment. screw terminals when you do the commissioning.
• Self diagnostic.
• On the premise of 24 samples per cycle, all data measure-
• Fault Recorder. ment, calculation and logic discrimination can be done within
• GPS clock synchronization. one sampling period. The event recording and protection
• 64 tripping reports, 64 alarm reports and 64 binary input sta- logic calculation are completed simultaneously.
tus change reports. • The relay provides GPS clock synchronization, including
• High resolution oscillography of last 24 oscillograms. (Com- message, second pulse, minute pulse and IRIG-B synchro-
patible with international COMTRADE format) nization.
• Rear communication ports: Ethernet with IEC 61850 or 2 • The format of event report is compatible with international
RS-485 with IEC 60870-5-103 protocol, 1 RS-485 with clock COMTRADE file.
synchronization, 1 RS-232 or RS-485 with printer.
• The relay is compatible with multiple protocols- IEC61850
• Front communication port: 1 RS-232 for testing and setting.
and IEC 60870-5-103. It provides networking interface such
as RS485, RS232 and Ethernet port.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class; IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Communications
Functions
• 2 RS-485 communication rear ports conform to IEC 60870-5-
Protection and Control 103 protocol
• Overvoltage protection (59) • 1 RS-485 communication rear ports for clock synchronization
• Direct transfer trip (DTT) • 1 RS-232 or RS-485 (can be set by jumper) communication
• Overvoltage element with compensation rear ports for printer
• Undervoltage element with compensation • 1 RS-232 communication faceplate port for testing and
• DPFC overcurrent element setting
• Zero-sequence and negative sequence overcurrent element • 2 optional Ethernet ports, IEC 61850, or IEC 60870-5-103
over TCP/IP
• Undercurrent element
• Low power factor element
• Low active power element
Features
Monitoring and Metering • High compensation accuracy since the influence of distributed
capacitance on protective device is considered adequately
• Voltage and current drift auto regulation
in overvoltage with compensation and undervoltage with
• Self diagnostic compensation.
• Circuit breaker supervision
• The RCS-925 can provide completed local auxiliary criterion
• Event Recorder including 128 binary input change reports, which can reflect all fault types so as to improve the reliability
128 miscellaneous reports and of transfer trip.
• 128 self-supervision reports. • The self-adaptive floating threshold only reflects the deviation
• Disturbance recorder including 128 fault reports, and 24 of power frequency component and thus can defend system
oscillograms (The file format of disturbance recorder is unbalance and system disturbance.
compatible with international COMTRADE file.) • The connector type can be selected as plug in/out terminal
• GPS clock synchronization - second pulse, minute pulse, RS- connector or crimp terminal connector. The unique plug in/
Technical data
Power Supply
Rated Voltage (Un) 24 Vdc, 30 Vdc, 48 Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 25 W
Burden
Operating condition < 55 W
Backup battery type ML2032, 3V, 65mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
Thermal continuously 120 V 120 V 200V
withstand 10s 200 V 200 V 350V
capability 1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class: IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800bps~57600bps
Transmission distance < 1000m@4800bps
RS-485 (EIA) Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type ST
Baud rate 4800bps~57600bps
Transmission standard 100Base-FX,
Transmission distance <1500m
RS-485 (EIA) Optical(Optional)
Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type RJ-45
Transmission rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2
Connector type SC
Ethernet
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Transmission distance < 1500m
Optical(optional) Optical Fiber Type Multi-mode or single-mode
853/1310nm for multi-mode
Wavelength
1310/1550nm for single-mode
Fiber size 62.5/125μm (core DIA/claddingDIA)
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Rear interface connecting local HMI with personal computer via RCSPC software
Port number 1
Local HMI communication
Application
Download program of protection relay
RS-232 (EIA)
Baud rate 4800bps~57600bps
Connector type 9 pin D-type female connector
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
IEC61000-4-8:2001, Class V
Power frequency magnetic field immunity 100A/m continuous
1000A/m for 1-3s
IEC61000-4-9:2001, Class V
Pulse magnetic field immunity 6.4/16 us
1000A/m for 3s
IEC61000-4-10:2001, Class V
Damped oscillatory magnetic field immunity
100kHz & 1MHz – 100A/m
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Function Index
RCS-915AB
RCS-915CD
RCS-915AS
PCS-915IC
PCS-915ID
RCS-915E
RCS-9628
Functional
Function
Code
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<25W (4U)
Quiescent condition
<45W (8U)
Burden
<35W (4U)
Operating condition
<60W (8U)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 100In
for half a cycle 250In
Burden <0.15VA/phase < 0.25VA/phase
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 48V 110V 125V 220V 250V
Rated current 1.2mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 55%~70% of rated voltage
Dropout voltage <55% of rated voltage
Maximum permissive voltage 120% of rated voltage
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
482.6mm×177mm×291mm(4U),
Enclosure dimensions (W×H×D)
482.6mm×354.8mm×285mm (8U)
Mounting Flush mounted
450mm×179mm(4U), M6 screw
Trepanning dimensions (W×H)
450mm×356.8mm(8U), M6 screw
Housing color Silver grey
Protection class: IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
and is immune to load current variation. Pole discrepancy detection element is used to protect pole
position disagreement
- Voltage control element
The voltage could be selected to use phase voltage, residual - Switch-onto-fault protection (50SOTF)
voltage and/or negative sequence voltage. Switch-onto-fault logic of bus coupler/section is used for bus
energizing.
- CT saturation inhibit
Two principles for CT saturation detection are provided: patented - Overcurrent protection (50/51)
adaptive weighted anti-saturation algorithm and harmonics. It Phase and neutral overcurrent protection with time delay are
keeps the current differential protection stable to external fault both provided.
and quickly clears internal fault and external-to-internal evolving • Feeder protection
fault during CT saturation. - Breaker failure protection (50BF)
- Check zone and discrimination zone It can be supervised by voltage control element. Re-tripping,
Check zone differential element and discrimination zone bus coupler/bus section tripping and bay breaker tripping are
differential element are both provided to enhance the reliability. executed sequentially.
- Dead zone protection (50DZ)
• Bus coupler/section protection It is provided to clear the dead zone fault between CT and
- Breaker failure protection (50BF) breaker for all feeder bays.
It can be supervised by voltage control element. Re-tripping, bus - Pole disagreement protection (62PD)
coupler/bus section tripping and bay breaker tripping are issued Pole discrepancy detection element is used to protect pole
sequentially. position disagreement
• Event recorder including 1024 disturbance records, 1024 • The relay provides isolator monitoring function responding to
binary events, 1024 supervision events and 1024 operating both normally open and normally closed auxiliary contacts.
logs
• Traditional harmonics and patented adaptive weighted anti-
• Disturbance recorder including 64 disturbance records saturation algorithm are provided for CT saturation detection.
with waveforms (The file format of disturbance recorder is
compatible with international COMTRADE file.) • DPFC differential protection is integrated to coordinate with
percentage restraint phase current differential protection and
• Fault Recorder
improve the sensitivity and tripping speed.
• One RS-485 rear port for clock synchronization • The relay is compatible with IEC 61850-8-1 MMS, GOOSE
• One RS-232 rear port for printer and IEC 61850-9-2 Sampling Value and provides the
independent interfaces for station bus and process bus
• One faceplate RJ45 port for testing and setting
respectively.
• Clock synchronization via Pulse-Per-Second, IRIG-B and
SNTP
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
Quiescent condition <25W (4U)
Burden
Operating condition <35W (4U)
Analog Voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V
linear to 1~170V
continuously 200V
Thermal withstand capability 10s 260V
1s 300V
Burden < 0.20VA/phase @Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 48V 110V 125V 220V 250V
Rated current 1.2mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 55%~70% of rated voltage
Dropout voltage <55% of rated voltage
Maximum permissive voltage 120% of rated voltage
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
Burden 300mW 240mW
Making capacity 2000VA 3040VA
6A@3s 10A@3s
Short duration current
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177mm×291mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450mm×179mm(4U), M6 screw
Housing color Silver grey
Protection class: IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Functions
Features
• Busbar differential protection. (87B)
- Steady-state percentage differential protection • The RCS-915 provides less than 20ms typical trip time for
- DPFC percentage differential protection busbar differential protection.
• Bus coupler/section protection.
• The CPU system adopts parallel calculation.
- SOTF protection (50)
- Dead zone protection (51/62EF) • Independent fault detector element is equipped.
- Breaker failure protection (50BF)
- Overcurrent protection (51P/51N)
• The device integrates high sensitive percentage differential
- Pole discrepancy protection (51/62PD)
protection.
• Feeder protection. • It is matching to different CT ratios and settable CT
- Breaker failure protection (50BF) adjustment coefficient.
- End fault protection (51/62EF)
- Pole discrepancy protection (51/62PD) • Busbar differential element can be supervised by voltage
- Transfer trip (TT)
elements.
• CT circuit failure supervision. • The sensitive and high-speed DFPC current differential
element is integrated in the relay.
• VT circuit failure supervisionCT failure detection logic.
• Disconnected position alarm. • A fully-fledged adaptive weighted anti-saturation algorithm.
• Busbar voltage switching. • The breaker failure protection of all feeders, bus coupler and
• Receiving PPS (pulse per second) and PPM (pulse per bus section is integrated in the RCS-915 relay.
minute) via external contact
• Various GPS clock synchronizations are provided: second/
• Receiving PPS, PPM and IRIG-B signal via RS-485 minute pulse via binary input or RS-485, message via
• Receiving time synchronization message from substation communication ports and IRIG-B synchronization.
automation system
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1min
Making Capacity >1000W at L/R=40ms
Continuous carry 5A 8A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 4ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×353.6×285 (unit: mm)
Trepanning dimensions (W×H) 450×355 (unit: mm) M6 screw
Mounting Flush mounted
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~38400bps
Transmission distance < 1000m@4800bps
Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
RS-485 (EIA) Connector type ST
Baud rate 4800 ~ 38400bps
Transmission standard 100Base-FX,
Optical Transmission distance <1500m
(Optional) Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Rear interface connecting local HMI with personal computer via RCSPC software
Port number 1
Local human-machine communication
Application
Download program of protection relay
RS-232 (EIA)
Baud rate 4800 ~ 9600bps
Connector type 9 pin D-type female connector
Safety level Isolation to ELV level
Interfaces connecting a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
- Mechanical tests
- Electrical tests
- Environmental tests
Auxiliary Testing
• Virtual SOE records generation
• Virtual measurement values generation
• Virtual tripping reports generation
• Virtual fault wave records generation
Features
• On the premise of 24 samples per cycle, all data
measurement, calculation and logic discrimination can be
Functions finished within one sampling period. The event recording and
protection logic calculation can be finished simultaneously.
Protection and control • Definite time overvoltage protection and residual overvoltage
• Undervoltage protection. (27) protection are both provided.
• Overvoltage protection. (59)
• Negative sequence overvoltage element is provided in this
• Residual overvoltage protection (59N) relay.
• Negative sequence overvoltage element (47)
• The relay constantly measures and calculates a large
• Mechanical protection (MR) amount of analog quantities, such as phase-to-phase
• Voltage drift automatic adjustment voltage, phase voltage, neutral voltage and system
frequency.
• Self supervision
• Voltage transformer supervision (VTS) • Multiple GPS clock synchronization, including message,
pulse per second, and IRIG-B synchronization.
Management and Mertering • The relay is equipped with two EIA RS-485 standardized
• Tripping circuit supervision interfaces and two Ethernet interfaces. Two optional Ethernet
interfaces are provided: electrical or optical.
• Remote control and measurements.
• 64 Trip records • The relay can communicate with SAS or RTU using
IEC60870-5-103 or modbus.
• 64 Operating alarm records
• 64 Self-check alarm records • Perfect fault and disturbance record function: 64 latest fault
reports, 8 latest fault waves(up to 15s), 64 user operating
• 64 User operating records
records, and 256 records of time tagged sequence of event
• 8 Disturbance records can be recorded.
• 256 SOE records, latest records of following elements
state changing: operating abnormality alarm elements, self-
AC Voltage Inputs
Standard Per IEC 60255-6, 1988
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs:
Rated Voltage 110VDC 220VDC 125VDC 250VDC
Pickup voltage 77VDC 154VDC 87.5VDC 175VDC
Dropout voltage 60.5VDC 121VDC 68.8VDC 137.5VDC
Maximum permitted voltage 150V 300V 150V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000Vac rms for 1min
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
DC Output
Output range 4 ~ 20mA
Max load resistance 500ohm
Max output voltage 10V
Atmospheric Environment
Standard IEC60255-6:1988
Operating temperature range -25 °C ~ +55 °C
Transport and storage temperature range -40 °C ~ +70 °C
Permissible humidity 5% ~ 95%, condensation not permissible
Mechanical Specifications
Enclosure dimensions (W×H×D) 142.4×266.0×203.0 (unit: mm)
Trepanning dimensions (W×H) 154×268.0 (unit: mm), M5 screw
Mounting Way Flush mounted
Communication Interfaces:
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Ethernet
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2
Optical Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Fiber Type Multi-mode
Wavelength 1300nm
Ethernet Optical
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces for communicating with a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
Type test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2007 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz /450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2008 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:1974, 16 hours at +55°C
Dry cold test IEC60068-2-1:1990, 16 hours at -25°C
IEC60068-2-30:1980, two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Function Index
RCS-9621
RCS-9661
RCS-9671
RCS-9679
RCS-9681
RCS-9622
RCS-9624
PCS-9671
RCS-978
RCS-974
PCS-978
PCS-974
Functional
Function
Code
• Inter-turn fault protection. (32G/21G) • Phase-to-phase impedance protection for HV and MV side.
Inter-turn protection consists of zero-sequence power (21P)
directional element and zero-sequence impedance element. Users have options to select the forward direction or
backward direction by logic setting, and power swing
• Overexciation protection. (24) blocking logic is integrated to improve the safe operation.
Overexcitation protection based on the ratio of voltage and
frequency is provided. • Phase-to-ground impedance protection for HV and MV side.
(21G)
Users have options to select the forward direction or
• Underfrequency and overfrequency protection. (81U/81O)
backward direction by logic setting, and power swing
Under frequency protection with df/dt blocking and over
blocking logic is integrated to improve safe operation.
frequency protection are both provided. The frequency is
derived from positive-sequence voltage.
• Power swing blocking. (68)
The unique power swing blocking logic is integrated to
• Mechanical protection. (MR)
improve the safe operation of impedance protection.
Under frequency protection with df/dt blocking and over
frequency protection are both provided. The frequency
• Voltage and current drift auto adjustment.
is derived from positive-sequence voltage. Up to eight
The relay continually and automatically traces the voltage
channels of mechanical protection are provided for tank.
and current drifts and adjusts the zero point to the normal
value.
• Four stage phase overcurrent protection (50P/51P/67P)
Overcurrent protection can be supervised by voltage
• Frequency tracking.
element, harmonic element and directional element. IDMT
Frequency tracking is provided to accommodate the
curves complied with IEC and ANSI are provided for
frequency shift in power system.
selection. Up to four overcurrent protections are provided.
• Four stage zero sequence overcurrent protection for each Monitoring and Metering
side. (50N/51N/67N) • CT saturation detection.
Overcurrent protection can be supervised by voltage
• Inrush current detection.
element, harmonic element and directional element. IDMT
curves complied with IEC and ANSI are provided for • Overexcitation detection.
selection. Up to four zero-sequence overcurrent protections • Harmonic blocking function.
are provided. • CT failure detection supervision.
• VT failure detection supervision.
• Two-stage residual overvoltage protection. (59G)
IDMT curves complied with IEC and ANSI are provided for • Tripping circuit supervision.
selection. • Self diagnostic.
• Fault Recorder.
• Two-stage definite-time and inverse-time phase overvoltage
protection. (59P)
IDMT curves complied with IEC and ANSI are provided for Communications
selection. • Two 10Base-T/100Base-TX (RJ45) ports and two optional
100Base-FX ports with IEC 61850-8-1 MMS and GOOSE for
• Four-stage undervoltage protection. (27) non-time-critical message, IEC 60870-5-103 over TCP/IP or
Rate-of-change of voltage is provided for the blocking. DNP 3.0
• Two RS-485 rear ports with IEC 60870-5-103
• Thermal overload protection. (49)
Thermal overload protection based on fundamental current • Six or Eight 100Base-FX ports with IEC 61850-9-2 Sampling
or harmonic current is provided for tripping and alarm. Value and GOOSE for time-critical message
• One RS-485 rear port for clock synchronization
• Breaker failure protection. (50BF) • One RS-232 rear port for printer
Breaker failure protection for each breaker is supplied to
• One faceplate RJ45 port for testing and setting
initiate re-tripping and adjacent breaker tripping.
• Clock synchronization via Pulse-Per-Second, IRIG-B and
• Pole disagreement protection. (62PD) SNTP
External binary input and zero-sequence/negative-sequence
current are used to detect the pole disagreement state of the
circuit breaker.
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<30W (for conventional substation application)
Quiescent condition
<35W (for smart substation application)
Burden
<35W (for conventional substation application)
Operating condition
<40W (for smart substation application)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 200In
for half a cycle 250In
Burden <0.2VA/phase < 0.25VA/phase
Transducer Input
Standard IEC 60255-1:2009
Input range 0-20mA 0-10V 0-250V
Input resistance 235Ω 8.8kΩ 248kΩ
Accuracy 0.5 class 0.5 class 0.5 class
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Housing color Silver grey
Protection class: IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 35 W
Burden
Operating condition < 45 W
Backup battery type 1/2AA, 3.6V, 60mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1min
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×353.6×285 (unit: mm)
Trepanning dimensions (W×H) 450×355 (unit: mm) M6 screw
Mounting Flush mounted
Housing material Aluminum
Housing color Silver grey
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA) Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
- Mechanical tests
- Electrical tests
- Environmental tests
Functions Features
Protection and Monitoring • The relay is designed based on NR’s well established and
• Mechanical protection (26: oil and winding temperature; 63: proven hardware platform with multi-processor architecture.
gas, pressure; 71: oil level; etc) The multi CPU technology supports the parallel operation of
CPU modules.
• Self diagnostic
• Auxiliary power supervision • The relay provides GPS clock synchronization, including
second pulse, IRIG-B and SNTP.
• Event recorder including 1024 disturbance records, 1024
binary events, 1024 supervision events and 1024 operating • The connector type is optional, one is the plug in/out terminal
logs connector and the other is the screw terminal connector. The
unique plug in/out terminal connectors are used to connect
the rear panel to the terminal blocks on the rack or cabinet,
Communication
making on-site commissioning and replacement much easier
• Two 10Base-T/100Base-TX (RJ45) ports and two optional
than using traditional screw terminals.
100Base-FX ports with IEC 61850-8-1 MMS and GOOSE for
non-time-critical message, IEC 60870-5-103 over TCP/IP or • The relay is compatible with IEC 61850-8-1 MMS, GOOSE
DNP 3.0 and IEC 61850-9-2 Sampling Value and provides the
• Two RS-485 rear ports with IEC 60870-5-103 independent interfaces for station bus and process bus
respectively.
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Housing color Silver grey
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type Test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Features
• Seven (7) channels of mechanical quantity inputs are for
signaling. Five (5) channels of mechanical quantity inputs
are for instantaneous tripping. Three (3) channels of
mechanical quantity inputs are for tripping with time delay.
Technical data
Power Supply
Rated Voltage (Un) 24 Vdc, 30 Vdc, 48 Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
Thermal continuously 120 V 120 V 200V
withstand 10s 200 V 200 V 350V
capability 1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class per IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800bps~57600bps
Transmission distance < 1000m@4800bps
RS-485 (EIA) Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type ST
Baud rate 4800bps~57600bps
Transmission standard 100Base-FX,
Transmission distance <1500m
RS-485 (EIA) Optical(Optional)
Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type RJ-45
Transmission rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2
Connector type SC
Ethernet
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Transmission distance < 1500m
Optical(optional) Optical Fiber Type Multi-mode or single-mode
853/1310nm for multi-mode
Wavelength
1310/1550nm for single-mode
Fiber size 62.5/125μm (core DIA/claddingDIA)
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Rear interface connecting local HMI with personal computer via RCSPC software
Port number 1
Local HMI communication
Application
Download program of protection relay
RS-232 (EIA)
Baud rate 4800bps~57600bps
Connector type 9 pin D-type female connector
Safety level Isolation to ELV level
Interfaces connecting printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<10W (for conventional substation application)
Quiescent condition
<15W (for smart substation application)
Burden
<15W (for conventional substation application)
Operating condition
<20W (for smart substation application)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Application object For protection For metering
Rated current (In) 1A 5A 1A 5A
Linear to 30In 30In 2In 2In
continuously 3In 3In 2In 2In
for 10s 30In 30In 12In 12In
Thermal withstand capability
for 1s 100In 100In 30In 30In
for half a cycle 250In 250In 75In 75In
Burden <0.1VA/phase <0.2VA/phase <0.2VA/phase <0.4VA/phase
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 48V 110V 125V 220V 250V
Rated current 1.2mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 55% rated voltage
Maximum permissive voltage 120% rated voltage
Withstand 2000Vac, 2800Vdc
Resolving time for logic input <1ms
Read more on the web
www.nrelect.com read more on www.nrelect.com 125
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
Max system voltage 380Vac, 250Vdc 380Vac, 250Vdc
Voltage across open contact 1000V RMS for 1 minute 1200V RMS for 1 minute
5.0A @ 380Vac 8.0A @ 380Vac
Continuous carry
5.0A @ 250Vdc 8.0A @ 250Vdc
Pickup time <8ms <10ms
Drop-off time <5ms <8ms
6A for 3000ms 10A for 3000ms
Short duration current
15A for 500ms 20A for 500ms
0.6A @ 48Vdc, L/R=40ms 0.6A @ 48Vdc, L/R=40ms
Breaking capacity (L/R=40ms) 0.1A @ 110Vdc, L/R=40ms 0.3A @ 110Vdc, L/R=40ms
0.05A @ 220Vdc, L/R=40ms 0.2A @ 220Vdc, L/R=40ms
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 225.00×177.00×224.80 (unit: mm)
Trepanning dimensions (W×H) 226.00×178.00, M5 screw (unit: mm)
Mounting Flush mounted
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- Serial Port for RTU/SCADA
Port number 0 or 2
Baud rate 4800 ~ 115200bps
Protocol IEC60870-5-103:1997 or DNP3.0
Maximal capacity 32
Transmission distance <1000m @ 4800bps
Safety level Isolation to ELV level
- Print Port
Port number 1
Type RS-232
Baud Rate 4800 ~ 115200bps
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type Test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Features
• The typical operating time of unrestraint current differential
protection is 35ms.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 142.4×266.0×203 (unit: mm)
Trepanning dimension (W×H) 154.0×268.0, M5 screw
Mounting Flush mounted
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
• Self diagnostic.
• Fault and disturbance recorder.
• Rear communication ports: Ethernet with IEC 61850,
2 RS-485 with IEC 60870-5-103, 1 RS-485 for clock
synchronization, 1 RS-232 for communication to printer.
Features
• The typical operating time of unrestraint current differential
protection is 35ms.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 284.2×266.0×203.0 (unit: mm)
Trepanning dimension (W×H) 296.2×268.0, M5 screw
Mounting Flush mounted
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Functions Features
• Voltage controlled directional phase overcurrent protection. • The overcurrent protection can be supervised by voltage
(67P) control elements.
• Voltage controlled phase overcurrent protection. (50P/51P) • The overvoltage protection can be supervised by zero
• Directional neutral overcurrent protection. (67N) sequence current element.
• Neutral overcurrent protection. (50N/51N) • The RCS-9681 relay constantly measures a large amount
• Ground overcurrent protection. (50G/51G) of analog quantities, such as phase voltage, phase-to-
phase voltage, zero sequence voltage, phase current, zero
• Ground overvoltage protection. (59G)
sequence current, active power, reactive power, power factor
• Over excitation protection. (24) and frequency.
• Thermal overload protection. (49)
• O n t h e p r e m i s e o f 2 4 s a m p l e s p e r c y c l e , a l l d a t a
• Cooler initiation function during overload. (49) measurement, calculation and logic discrimination can be
• On-load-tap-change (OLTC) blocking function during finished within one sampling period. The event recording and
overload. (49) protection logic calculation are completed simultaneously.
• Remote control and measurements. • The relay provides GPS clock synchronization, including
• CT circuit failure supervision. (CTS) message, second pulse and IRIG-B synchronization.
• VT circuit failure supervision. (VTS) • The format of event report is compatible with international
• Tripping circuit supervision. COMTRADE file.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 142.4×266.0×203 (unit: mm)
Trepanning dimension (W×H) 154.0×268.0, M5 screw
Mounting Flush mounted
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Features
• O n t h e p r e m i s e o f 2 4 s a m p l e s p e r c y c l e , a l l d a t a
measurement, calculation and logic discrimination can be
finished within one sampling period. The event recording and
Functions protection logic calculation are completed simultaneously.
• Three-stage voltage controlled overcurrent protection. • Overcurrent protection can be supervised by voltage control
(50P/51P) elements.
• Two- stage negative sequence overcurrent protection. • Definite time of negative sequence overcurrent protection is
(50Q/51Q) provided for high voltage side of the transformer.
• Three-stage zero sequence overcurrent protection for HV
side. (50N/51N) • Definite time and inverse time of negative sequence
• Three-stage zero sequence overcurrent protection for LV overcurrent protection are both provided for the low voltage
side. (50N/51N) side of transformer.
• Ground overcurrent protection for HV side. (50/51G) • The RCS-9621 relay constantly measures a large amount
• Ground overvoltage protection for HV side. (59G) of analog quantities, such as phase voltage, phase-to-
• Under voltage protection. (27) phase voltage, zero-sequence voltage, phase current, zero-
• Mechanical protection. (26: oil and winding temperature; 63: sequence current, active power, reactive power, power factor
gas, pressure; 71: oil level; etc) and frequency.
• Thermal overload protection. (49) • The relay can monitor the status of the circuit breaker.
• Remote control and measurement
• CT circuit failure supervision. (CTS) • The relay provides GPS clock synchronization, including
• VT circuit failure supervision.(VTS) message, second pulse and IRIG-B synchronization.
• Tripping circuit supervision. • The relay is equipped with Ethernet ports with the IEC 61850
• Voltage and current drift auto adjustment. protocol and RS-485 ports with IEC 60870-5-103 protocol.
• Self diagnostict.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs:
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 4ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 142.4×266.0×203 (unit: mm)
Trepanning dimension (W×H) 154.0×268.0, M5 screw
Mounting Flush mounted
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Features
• On the premise of 24 samples per cycle, all data
measurement, calculation and logic discrimination can be
done within one sampling period. The event recording and
protection logic calculation are completed simultaneously.
Functions • Power supply of mechanical quantity input circuit is
monitored.
• Mechanical protection. (26: oil and winding temperature; 63:
gas, pressure; 71: oil level; etc) • Mechanical protection and other auxiliary relay circuit are
• 8 (up to 12 by configuring No.9 IO module) channels of independent to each other.
mechanical quantity input are provided for trip or alarm. • The relay provides GPS clock synchronization, including
• Voltage switchover relays message, second pulse and IRIG-B synchronization.
• Remote control and measurement • The relay is equipped with two EIA RS-485 standardized
• AC voltage auto-switching function. interfaces and two Ethernet interfaces. The Ethernet
• Tripping circuit supervision. interfaces are optional: electrical or optical.
• Self diagnostic. • The relay is compatible with IEC 61850 protocol and IEC
• GPS clock synchronization. 60870-5-103 protocol.
• Fault and disturbance recorder. • Fault and disturbance recording function: 64 latest tripping
• 64 tripping reports and 256 SOE (Sequence of Events) records, 6 latest fault wave (up to 15s), 64 latest equipment
records. self-check alarm records, 64 latest alarm records of
equipment operating abnormality, 64 user operating records
• Rear communication ports: Ethernet with IEC 61850,
and 256 records of time-tagged sequence of event can be
recorded.
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 284.2×266.0×203 (unit: mm)
Trepanning dimensions (W×H) 296.2×268.0, M5 screw
Mounting Flush mounted
Front side: IP40, up to IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +60°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Ethernet Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Connector type SC
Optical
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
IEC61000-4-8:2001, Class V
Power frequency magnetic field immunity 100A/m continuous
1000A/m for 1-3s
IEC61000-4-9:2001, Class V
Pulse magnetic field immunity 6.4/16 us
1000A/m for 3s
IEC61000-4-10:2001, Class V
Damped oscillatory magnetic field immunity
100kHz & 1MHz – 100A/m
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Management
• Circuit breaker status monitoring.
• Remote control and measurements.
• Tripping/Closing circuit supervision.
• Multiple setting groups.
• 64 Trip records.
• 64 Self-check alarm records.
• 64 Operating alarm records.
• 64 User operating records.
• 8 Disturbance records FR.
• 256 SOE records, latest records of following elements state
changing: operating abnormality alarm elements, self-check
alarm elements, protection elements, binary input elements
• Circuit breaker operating time monitoring.
Auxiliary Testing
Functions • Virtual SOE records generation.
• Unrestrained current differential protection. (87UT) • Virtual fault wave records generation.
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11
Per IEC 61000-4-11:2004, IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition <15W
Burden
Operating condition <25W
Backup battery type ML2032, 3V, 65mAh
AC Voltage Inputs
Standard Per IEC 60255-6, 1988
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs:
Rated Voltage 110VDC 220VDC 125VDC 250VDC
Pickup voltage 77VDC 154VDC 87.5VDC 175VDC
Dropout voltage 60.5VDC 121VDC 68.8VDC 137.5VDC
Maximum permitted voltage 150V 300V 150V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000Vac rms for 1min
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Bounce time 1ms 1ms
Dropout time(Typical/Max) 8ms/10ms 4ms/10ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Atmospheric Environment
Standard IEC60255-6:1988
Operating temperature range -25 °C ~ +55 °C
Transport and storage temperature range -40 °C ~ +70 °C
Permissible humidity 5% ~ 95%, condensation not permissible
Mechanical Specifications
Enclosure dimensions (W×H×D) 142.4×266.0×203.0 (unit: mm)
Trepanning dimensions (W×H) 154×268.0 (unit: mm), M5 screw
Mounting Way Flush mounted
Local control panel Small control module: 3 LED indicators, a 9-key keypad and a 160×80-dot LCD
Housing material Aluminum
Housing color Silver grey
Front side: IP51
Protection class Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Ethernet
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Optical Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Fiber Type Multi-mode
Wavelength 1300nm
Ethernet Optical
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces for communicating with a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:1974, 16 hours at +55°C
Dry cold test IEC60068-2-1:1990, 16 hours at -25°C
IEC60068-2-30:1980, two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Auxiliary Testing
• Virtual SOE records generation
Functions • Virtual measurement values generation
• Virtual tripping reports generation
Protection and control
• Virtual fault wave records generation
• Non-directional overcurrent protection. (50P/51P)
• Non-directional earth fault protection. (50G/51G)
• Instantaneous zero sequence overcurrent protection. (50N)
• Negative sequence overcurrent protection. (51Q) Features
• Voltage controlled element. (VCE) • On the premise of 24 samples per cycle, all data
• Earth fault protection. (64) measurement, calculation and logic discrimination can be
finished within one sampling period. The event recording and
• Thermal overload supervision. (49)
protection logic calculation can be completed simultaneously.
• Mechanical protection. (MR)
• Definite time and inverse time of overcurrent protection are
• Voltage and current drift auto adjustment.
both provided.
• Self diagnostic.
• Definite time of negative sequence overcurrent protection is
• Voltage transformer supervision. (VTS)
provided for high voltage side of transformer.
• Current transformer supervision. (CTS)
• Definite time and inverse time of negative sequence
• Rear communication ports: printer.
overcurrent protection are both provided for low voltage side
• Rear communication ports: RS-485.
of transformer.
• Time synchronization port.
• Overcurrent protection can be controlled by voltage element.
Management • It constantly measures and calculates a large mount of
• Circuit breaker status monitoring. analog quantities, such as phase-to-phase voltage, phase
• Remote control and measurements. current, neutral current, active power, reactive power, power
• Tripping circuit supervision. factor and frequency.
• Multiple GPS clock synchronization, including message, • Fault and disturbance record function: 64 latest fault reports,
pulse per second, and IRIG-B synchronization. 8 latest fault wave (up to 15s), 64 user operating records
of users to equipment, and 256 records of time tagged
• This relay is equipped with two EIA RS-485 standardized
sequence of event can be recorded.
interfaces and two Ethernet interfaces. Two alternative
designs of Ethernet interfaces are provided: electrical or
optical.
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11
Per IEC 61000-4-11:2004, IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition <15W
Burden
Operating condition <25W
Backup battery type ML2032, 3V, 65mAh
AC Voltage Inputs
Standard Per IEC 60255-6, 1988
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Input
Rated Voltage 110VDC 220VDC 125VDC 250VDC
Pickup voltage 77VDC 154VDC 87.5VDC 175VDC
Dropout voltage 60.5VDC 121VDC 68.8VDC 137.5VDC
Maximum permitted voltage 150V 300V 150V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000Vac rms for 1min
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Bounce time 1ms 1ms
Dropout time(Typical/Max) 8ms/10ms 4ms/10ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Atmospheric Environment
Standard IEC60255-6:1988
Operating temperature range -25 °C ~ +55 °C
Transport and storage temperature range -40 °C ~ +70 °C
Permissible humidity 5% ~ 95%, condensation not permissible
Mechanical Specifications
Enclosure dimensions (W×H×D) 142.4×266.0×203.0 (unit: mm)
Trepanning dimensions (W×H) 154×268.0 (unit: mm), M5 screw
Mounting Way Flush mounted
Local control panel Small control module: 3 LED indicators, a 9-key keypad and a 160×80-dot LCD
Housing material Aluminum
Housing color Silver grey
Front side: IP51
Protection class Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Ethernet
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Optical Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Fiber Type Multi-mode
Wavelength 1300nm
Ethernet Optical
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces for communicating with a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:1974, 16 hours at +55°C
Dry cold test IEC60068-2-1:1990, 16 hours at -25°C
IEC60068-2-30:1980, two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Function Index
Functional
Function RCS-917 RCS-9647
Code
Main protection
Unrestraint current differential protection 87U √ √
Percentage current differential protection 87P √ √
DPFC current differential protection 87D √
Zero sequence current differential protection REF √
Inter-turn fault protection √
Back-up protection
Phase overcurrent protection 50P, 51P √ √
Zero sequence overcurrent protection 50N, 51N √ √
Ground overcurrent protection 50G, 51G √
Thermal overload protection 49 √ √
Miscellaneous
Mechanical protection √ √
CT circuit failure supervision CTS √
VT circuit failure supervision VTS √
Tripping/Closing circuit supervision TCS/CCS √
GPS clock synchronization √ √
Remote control √
Analog quantity measurements √
Fault and disturbance recorder √ √
Self diagnostic test √ √
Voltage and current drift auto adjustment √ √
IEC 60870-5-103 protocol √ √
IEC 61850 protocol √ √
Features
• Main and backup protections are integrated in one set
of protection equipment. Protection information such as
sampled data and binary inputs are shared by all elements.
• Two-stage zero sequence overcurrent protection. (50N/51N) • The connector type can be selected as plug in/out terminal
• Thermal overload protection. (49) connector or crimp terminal connector. The unique plug in/
out terminal connectors from the relay rear panel to the
• Thermal overload protection for grounded reactor. (49G)
terminal blocks on the rack or cabinet makes the on-site
• Mechanical protection. commissioning and replacement much easier than the
• CT circuit failure supervision. (VTS) traditional screw terminals when you do the commissioning.
• VT circuit failure supervision. (CTS) • On the premise of 24 samples per cycle, all data
• Voltage and current drift auto adjustment. measurement, calculation and logic discrimination can be
• Self diagnostic. finished within one sampling period. The event recording and
protection logic calculation are completed simultaneously.
• Fault and disturbance recorder.
• GPS clock synchronization. • The relay provides GPS clock synchronization, including
message, second pulse, minute pulse and IRIG-B
• 64 pieces of tripping reports
synchronization.
• 64 pieces of alarm reports
• The relay is compatible with multiple protocols- IEC61850
and IEC 60870-5-103. It provides networking interface such
as RS485, RS232 Ethernet and optical-fiber port.
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 200In
for half a cycle 250In
Burden <0.2VA/phase < 0.25VA/phase
Analog voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V 200V (Broken delta for residual voltage)
linear to 1~170V 1~233V
continuously 200V 220V
Thermal withstand capability 10s 260V 380V
1s 300V 420V
Burden < 0.20VA/phase @Un < 0.8VA/phase@Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type Test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
• Self diagnostic.
• GPS clock synchronization.
• Fault and disturbance recorder.
• 64 tripping reports and 256 SOE (Sequence of Events)
records.
• High resolution oscillography of last 8 oscillograms
(compatible with international COMTRADE format)
• Rear communication ports: 2 Ethernet interfaces with IEC
61850, 2 RS-485 with IEC 60870-5-103, 1 RS-485 for clock
synchronization, 1 RS-232 for communication to printer.
Features
• Definite time and inverse time characteristics of overcurrent
and zero sequence overcurrent protections are both provided
respectively.
• Thermal overload protection. (49) • This relay can communication with SAS or RTU using IEC
• Remote control and measurements. 61850 and IEC60870-5-103.
• CT circuit failure supervision.(CTS) • The format of event report is compatible with international
• VT circuit failure supervision.(VTS) COMTRADE file.
• Tripping circuit supervision. • The relay is equipped with Ethernet ports with the IEC 61850
• Voltage and current drift auto adjustment. protocol and RS-485 ports with IEC 60870-5-103 protocol.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 142.4×266.0×203 (unit: mm)
Trepanning dimension (W×H) 154.0×268.0, M5 screw
Mounting Flush mounted
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Function Index
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<30W (for conventional substation application)
Quiescent condition
<35W (for smart substation application)
Burden
<35W (for conventional substation application)
Operating condition
<40W (for smart substation application)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 200In
for half a cycle 250In
Burden <0.2VA/phase < 0.25VA/phase
Analog Voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V 200V (Broken delta for residual voltage)
linear to 1~170V 1~233V
continuously 200V 220V
Thermal withstand capability 10s 260V 380V
1s 300V 420V
Burden < 0.20VA/phase @Un < 0.8VA/phase@Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Housing color Silver grey
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Features
• High-performance hardware platform and modularized
design(MCU+DSP). MCU manages general fault detector
element and DSP manages protection and metering.
The data acquisition system is completely independent
Functions of electronic circuit. The DC power supply of output relay
is switched on only if the general fault detector element
• Breaker failure protection (50) operates so as to avoid maloperation resulting from damage
• Pole discrepancy protection (52) of any apparatus.
• Two stages overcurrent protection (67P) • Up to 0.01Hz accurate frequency metering, wide range of
• Two stages zero-sequence overcurrent protection (67G) frequency tracing. Frequency can be accurately traced within
the range of 40Hz~65Hz.
• Automatic reclosure (AR) function (79)
• Synchronism check (25) • The self-adaptive floating threshold only reflects the
deviation of power frequency component, thus is immune to
• Frequency tracking
system imbalance and system disturbance.
• VT circuit supervision
• 24 samples per cycle, all task including data measurement,
• CT circuit supervision
protection calculation, logic discrimination, event recording
• Self diagnostic and protection logic calculation can be completed within one
• DC power supply supervision sampling period.
• Event recorder, including 256 binary input change reports, • Flexible automatic reclosure mode supporting multiple
256 self-supervision reports and 256 control reports initiation mode and check mode.
• Disturbance recorder, including 256 fault reports and 6 fault
• Overcurrent protection is provided in the relay for energizing
waveforms
a faulty bus or energizing a faulty line.
• GPS clock synchronization – PPS (pulse per second), PPM
(pulse per minute) and IRIG-B signal • The connector type can be selected as plug in/out terminal
connector or crimp terminal connector. The unique plug in/
• 2 RS-485 communication rear ports conform to IEC 60870-
out terminal connectors from the relay rear panel to the
5-103 protocol
terminal blocks on the rack or cabinet makes the on-site
• 1 RS-485 communication rear ports for clock synchronization commissioning and replacement much easier than the
• 2 or 4 optional Ethernet ports, IEC 61850, or IEC 60870-5- traditional screw terminals when you do the commissioning.
103 over TCP/IP
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
Thermal continuously 120 V 120 V 200V
withstand 10s 200 V 200 V 350V
capability 1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class per IEC60529:2001
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800bps~57600bps
Transmission distance < 1000m@4800bps
RS-485 (EIA) Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type ST
Baud rate 4800bps~57600bps
Transmission standard 100Base-FX,
Transmission distance <1500m
RS-485 (EIA) Optical(Optional)
Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type RJ-45
Transmission rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2
Connector type SC
Ethernet
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Transmission distance < 1500m
Optical(optional) Optical Fiber Type Multi-mode or single-mode
853/1310nm for multi-mode
Wavelength
1310/1550nm for single-mode
Fiber size 62.5/125μm (core DIA/claddingDIA)
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Rear interface connecting local HMI with personal computer via RCSPC software
Port number 1
Local HMI communication
Application
Download program of protection relay
RS-232 (EIA)
Baud rate 4800bps~57600bps
Connector type 9 pin D-type female connector
Safety level Isolation to ELV level
Interfaces connecting printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Features
• Overcurrent protection is provided in the relay for energizing
a faulty bus or energizing a faulty line.
• Self diagnostic test. • On the premise of 24 samples per cycle, all data
• Current drift auto regulation. measurement, calculation and logic discrimination can
be completed within one sampling period. The event
• Event Recorder including 128 binary input change reports,
recording and protection logic calculation are completed
128 self-supervision reports and 128 operating reports.
simultaneously.
• Disturbance recorder including 128 fault reports, and 24
waveforms. • The relay provides GPS clock synchronization, including
message, second pulse, minute pulse and IRIG-B
• Self diagnostic.
synchronization.
• 2 RS-485 communication rear ports conform to IEC 60870-
5-103 protocol • The relay is compatible with multiple protocols- IEC61850
and IEC 60870-5-103. It provides networking interface such
• 1 RS-485 communication rear ports for clock synchronization
as RS485, RS232 and Ethernet port.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
Thermal continuously 120 V 120 V 200V
withstand 10s 200 V 200 V 350V
capability 1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class per IEC60529:2001
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800bps~57600bps
Transmission distance < 1000m@4800bps
RS-485 (EIA) Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type ST
Baud rate 4800bps~57600bps
Transmission standard 100Base-FX,
Transmission distance <1500m
RS-485 (EIA) Optical(Optional)
Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type RJ-45
Transmission rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2
Connector type SC
Ethernet
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Transmission distance < 1500m
Optical(optional) Optical Fiber Type Multi-mode or single-mode
853/1310nm for multi-mode
Wavelength
1310/1550nm for single-mode
Fiber size 62.5/125μm (core DIA/claddingDIA)
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Rear interface connecting local HMI with personal computer via RCSPC software
Port number 1
Local HMI communication
Application
Download program of protection relay
RS-232 (EIA)
Baud rate 4800bps~57600bps
Connector type 9 pin D-type female connector
Safety level Isolation to ELV level
Interfaces connecting printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
- Realtime compensation function based on control circuit • Measurement of current and voltage, as well as monitoring of
voltage operation status are realized.
- Realtime compensation function based on mechanism • 32 operation records, 64 self-check records, and 64 binary
ambient temperature quantity/status change records are provided.
- Compensation function based on resting time • RS232 debugging serial port is provided. Software (PC end)
can be used for communication with the device, facilitating
• Current zero-drift automatic calibration function setup of settings, display of sampling, display of message,
and fault recording.
• 32-bit microprocessor is adopted to have faster calculation • Friendly HMI allows easy operation and commissioning.
and more reliable performance.
• Elaborate anti-interference assembly design with fully
• Complete phase selection closing/tripping function is enclosed chassis provide strong resistance to vibration and
provided and can be freely enabled or disabled. EM interference.
Technical data-
Item Description
Pole-segregated switching Open, Close
Auxiliary Power Supply 80% ~ 120% of rated voltage
Rated Voltage:
30Vdc/110Vdc/220Vdc;
110Vac ~ 220Vac
Rated Frequency (50 Hz or 60Hz) ± 5%
Power Consumption Steady state: <10W
Transient: <15W
Burden < 0.5 VA/Phase @ 1A
<1.0 VA/Phase @ 5A
Open/Close Circuit Current Adaptive
AC current Rated: 1 A or 5 A
Thermal withstand: 3In, Continuously
30In, 10 sec
100In, 1 sec
250In, half cycle
Function Index
RCS-985RS
RCS-985SS
RCS-985TS
RCS-985G
RCS-985B
RCS-985C
RCS-985A
RCS-985T
PCS-985
Functional
Function
Code
Typical Applications
Auxiliary Transformer
• Detect CT Saturation by asynchronous method
• Differential protection. (87T)
For external fault, waveform discrimination of phase current
• Voltage controlled overcurrent protection at HV side. (50P)
and differential current is adopted. Maloperation will not occur
• Stator earth-fault protection with external voltage injection • Powerful communication function
principle 2 independent Ethernet interfaces and 2 independent RS-
The protection adopts digital technology to calculate the 485 communication interfaces are provided. Power industry
earth fault resistance accurately. The protection is adaptive communication standard IEC60870-5-103, Modbus protocol
for various operation conditions, such as stillness, no-load, and new generation substation communication standard
shutdown, startup and connected to power grid. IEC61850 are supported.
• Rotor earth-fault protection with ping-pong principle • Complete event recording function
DC current is input by high-performance isolated amplifier. 64 faults and operation sequence, 64 fault waveforms,
Via switching two different electronic switches, the PCS- results of 256 self-supervision reports, and 1024 binary
985 solves four different ground-loop equations to compute signal change reports can be recorded.
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
Quiescent condition <50W
Burden
Operating condition <70W
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 100In
for half a cycle 250In
Burden <0.15VA/phase < 0.25VA/phase
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 48V 110V 125V 220V 250V
Rated current 1.2mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 55%~70% of rated voltage
Dropout voltage <55% of rated voltage
Maximum permissive voltage 120% of rated voltage
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current
[email protected] [email protected]
0.4A resistance 0.2A resistance
Breaking capacity (L/R=40ms)
0.2A inductive(L/R=40ms) 0.05A inductive (L/R=40ms)
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×354.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×354.0mm, M6 screw
Housing color Silver grey
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type Test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
• Voltage controlled overcurrent protection at HV side. (50P/ • Two discrimination principles for inrush current are provided:
51P) harmonics restraint and waveform distortion restraint.
• Voltage controlled zero-sequence overcurrent protection at • Based on the operation sequence of DPFC restraint current
HV side. (50N/ 51N) element and DPFC differential current element of differential
• Voltage controlled directional zero-sequence overcurrent protection, external fault with CT saturation or internal fault
protection at HV side. (67N) can be distinguished correctly.
• Zero-sequence overvoltage protection at HV side (Gap • The transverse differential protection adopts percentage
overvoltage). (59N) phase current restraint and floating threshold to achieve high
• Zero-sequence overcurrent protection at HV side (Gap sensitivity in internal fault and high security in external fault.
overcurrent). (50N/51N)
• The loss-of-excitation protection adopts optimizing protection
• Overexcitation protection. (24) scheme in which stator impedance criteria, reactive power
• Thermal overload protection. (49) criteria, rotor voltage criteria, busbar voltage criteria and
• Out-of-step protection adopts three-impedance element • Percentage differential principle is used to enhance the ability
to distinguish out-of-step from steady oscillation. The to detect CT circuit failure and to avoid maloperations.
protection can accurately locate the position of oscillation
• Various GPS clock synchronizations: second/minute pulse
center and record theoscillation slide numbers of external
via binary input or RS-485, message via communication
and internal oscillation respectively in realtime.
ports and IRIG-B synchronization.
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 40 W
Burden
Operating condition < 70 W
Backup battery type 1/2AA, 3.6V, 60mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
40In (Transformer related) 40In (Transformer related)
Linear to (non-offset AC current) 20In (Generator related) 20In (Generator related)
2In (for metering CT) 2In (for metering CT)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1min
Continuous carry 8A 5A
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×532.6mm×285 mm
Trepanning dimensions (W×H) 450mm×534mm M6 screw
Mounting Flush mounted
Housing material Aluminum
Housing color Silver grey
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~38400bps
Transmission distance < 1000m@4800bps
Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
RS-485 (EIA) Connector type ST
Baud rate 4800 ~ 38400bps
Transmission standard 100Base-FX,
Transmission distance <1500m
Optical (Optional)
Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Rear interface for local HMI with personal computer via RCSPC software
Port number 1
Local human-machine communication
Application
Download program of protection relay
RS-232 (EIA)
Baud rate 4800 ~ 9600bps
Connector type 9 pin D-type female connector
Safety level Isolation to ELV level
Interfaces for communicating with a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
- Mechanical tests
- Electrical tests
- Environmental tests
• The CT current output will be corrected before calculation to • CT circuit failure alarm and blocking is integrated. This
eliminate the influence of different CT ratio function adopts percentage differential principle. Detection
ability of CT circuit failure can be enhanced significantly and
• Two discrimination principles for inrush current are provided:
unwanted operation can be avoided then.
harmonics restraint and waveform distortion restraint.
• The connector type can be selected as plug in/out terminal
• CT saturation detecting logic can prevent mal-operation in
connector or screw terminal connector. The unique plug
case of external fault and improve operational performance
in/out terminal connectors from the relay rear panel to
under condition of internal fault. For external faults, mal-
the terminal blocks on the rack or cabinet makes the on-
operation can be avoided if the transfer time from primary to
site commissioning and replacement much easier than the
secondary side of CT is no less than 5ms.
traditional screw terminals when you do the commissioning.
• The transverse differential protection adopts the percentage
• Various GPS clock synchronizations are provided: second/
phase current restraint and the floating threshold to
minute pulse via binary input or RS-485, message via
enhance ensitivity and reliability. The filtration ratio of third
communication ports and IRIG-B synchronization.
component can be increased to over 100 with the application
of frequency tracking technique, digital filter technique and • The relay is equipped with Ethernet ports with IEC 61850 (one
Fourier transformation technique. additional communication unit is required) and RS-485 ports
with IEC 60870-5-103.
• More than 500 sampled data including differential current
and phase angle can be displayed on LCD. More than
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
40In (Transformer related) 40In (Transformer related)
Linear to (non-offset AC current) 20In (Generator related) 20In (Generator related)
2In (for metering CT) 2In (for metering CT)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1min
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 4ms/10ms (only DSP)
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×532.6mm×285 mm
Trepanning dimensions (W×H) 450mm×534mm M6 screw
Mounting Flush mounted
Housing material Aluminum
Housing color Silver grey
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Type Test
- Electromagnetic compatibility (EMC)
- Electrical tests
- Environmental tests
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 15 W
Burden
Operating condition < 25 W
Backup battery type 1/2AA, 3.6V, 60mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 40In (Transformer related) 40In (Transformer related)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Mechanical Specifications
Enclosure dimensions (W×H×D) 213.2mm×266mm×232mm
Trepanning dimensions (W×H) 215mm×267mm, M5 screw
Mounting Flush mounted
Housing material Aluminum
Housing color Silver grey
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~38400bps
Transmission distance < 1000m@4800bps
Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
RS-485 (EIA) Connector type ST
Baud rate 4800 ~ 38400bps
Transmission standard 100Base-FX,
Transmission distance <1500m
Optical (Optional)
Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Rear interface for local HMI with personal computer via RCSPC software
Port number 1
Local human-machine communication
Application
Download program of protection relay
RS-232 (EIA)
Baud rate 4800 ~ 9600bps
Connector type 9 pin D-type female connector
Safety level Isolation to ELV level
Interfaces for communicating with a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
- Mechanical tests
- Electrical tests
- Environmental tests
Functions
Protection and control
• Variable slope percentage differential protection (7 sides • Voltage controlled overcurrent protection of branches at LV
maximum). (87T) side. (50P/51P)
• Unrestrained differential protection. (50/87UT) • Pole disagreement protection. (62PD)
• Restricted earth fault protection(zero-sequence differential • Over excitation protection. (24)
current protection) at HV side. (64REF/87G) • Thermal overload protection. (49)
• Restricted earth fault protection(zero-sequence differential • Cooling initiation function. (49)
current protection) at LV side A. (64REF/87G)
• On-load tap change (OLTC) blocking function during
• Restricted earth fault protection(zero-sequence differential overload. (49)
current protection) at LV side B. (64REF/87G)
• Zero-sequence voltage alarm of branches at LV side. (59G)
• Voltage controlled overcurrent protection at HV side. (50P/
• VT circuit failure supervision.
51P)
• CT circuit failure supervision.
• Voltage controlled directional zero-sequence overcurrent
protection at HV side. (50N/51N/67N) • CT saturation detection.
Communication
• 2 RS-485 communication rear ports conform to IEC 60870-5-
103 protocol or Modbus protocol.
• 3 optional Ethernet ports conform to IEC 60870-5-103
protocol over TCP/IP.
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 40 W
Burden
Operating condition < 70 W
Backup battery type 1/2AA, 3.6V, 60mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
40In (Transformer related) 40In (Transformer related)
Linear to (non-offset AC current) 20In (Generator related) 20In (Generator related)
2In (for metering CT) 2In (for metering CT)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1min
Making Capacity 30A
Continuous carry 5A, 8A, 10A (select one) 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 4ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×353.6mm×285mm
Trepanning dimensions (W×H) 450mm×355mm, M6 screw
Mounting Flush mounted
Housing material Aluminum
Housing color Silver grey
Front side: IP40, up to IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~38400bps
Transmission distance < 1000m@4800bps
Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type ST
RS-485 (EIA)
Baud rate 4800 ~ 38400bps
Transmission standard 100Base-FX,
Transmission distance <1500m
Optical (Optional) Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
IEC60870-5-103:1997
Protocol
MODBUS
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
- Mechanical tests
- Electrical tests
- Environmental tests
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 15 W
Burden
Operating condition < 25 W
Backup battery type ML2032, 3V, 65mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 40In (Transformer related) 40In (Transformer related)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Mechanical Specifications
Enclosure dimensions (W×H×D) 213.1mm×266.0mm×203.0mm
Trepanning dimensions (W×H) 225mm×268.0mm, M5 screw
Mounting Flush mounted
Housing material Aluminum
Housing color Silver grey
Front side: IP40, up to IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA) Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or MODBUS
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or MODBUS
Safety level Isolation to ELV level
Interfaces for communicating with a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
- Mechanical tests
- Electrical tests
- Environmental tests
• S e m i - a u t o m a t i c S y n c h r o n i z i n g M o d e : T h e
closing command is issued manually to initiate
synchronism process, the other functions are
provided automatically just the same as automatic
synchronizing mode.
Features
Functions • Frequency tracking technology is adopted. By the aid of
that, real-time value of frequency, voltage and phase are
• Automatic synchronizing (25A) calculated with high precision on every sampling point.
• Semi-automatic synchronizing (25SA)
• The equipment uses an integral front panel and closed
• Manual synchronizing (25M) cabinet. High and low level signals are separated strictly.
• Multi-generator paralleling solution: capability of 10 circuit With well designed software anti-EMI facilities, the
breakers’ synchronization. To any of the circuit breakers, equipment’s capability of interference immunity is highly
frequency and voltage regulation can be done separately. enhanced. Furthermore, its electromagnetic radiation also
• Remote/local control paralleling mode satisfies relevant international standards.
• Blocking signal to other equipments • Flexible communication function
• Receive blocking signal from other equipments - 2 RS-485 communication rear ports conform to IEC 60870-5-103
protocol
• Communicate with substation automation system via
- 1 RS-485 communication rear ports for clock synchronization
serial port on IEC60870-5-103 or Ethernet port based on
- 4 rear Ethernet ports (optional), IEC 61850
IEC60870-5-103 or IEC61850.
• GPS clock synchronization – message, PPS (pulse • Monitoring and Metering
per second), PPM (pulse per minute), and IRIG-B - Event Recorder including 64 reports of status change of binary
synchronization. input, 64 self-supervision reports and 256 operating reports.
- Disturbance recorder including 64 fault reports, and 24
• Oscillograph, 8 cycles ahead of closing signal and 2 cycles
waveforms (The file format of disturbance recorder is compatible
after closing signal.
with international COMTRADE file.)
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1min
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177mm×291mm
Trepanning dimensions (W×H) 450mm×179.0mm, M6 screw
Mounting Flush mounted
Housing material Aluminum
Housing color Silver grey
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Type Test
- Electromagnetic compatibility (EMC)
- Mechanical tests
- Electrical tests
- Environmental tests
Function Index
PCS-9691E
RCS-9613
RCS-9615
RCS-9625
RCS-9651
RCS-9629
RCS-9611
PCS-9651
PCS-9655
PCS-9611
Functional
Function
Code
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<10W (for conventional substation application)
Quiescent condition
<15W (for smart substation application)
Burden
<15W (for conventional substation application)
Operating condition
<20W (for smart substation application)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Application object For protection For metering
Rated current (In) 1A 5A 1A 5A
Linear to 30In 30In 2In 2In
continuously 3In 3In 2In 2In
for 10s 30In 30In 12In 12In
Thermal withstand capability
for 1s 100In 100In 30In 30In
for half a cycle 250In 250In 75In 75In
Burden <0.1VA/phase <0.2VA/phase <0.2VA/phase <0.4VA/phase
Analog Voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V
linear to 1~130V
continuously 120V
Thermal withstand capability 10s 200V
1s 250V
Burden < 0.10VA/phase @Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 48V 110V 125V 220V 250V
Rated current 1.2mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 55% rated voltage
Maximum permissive voltage 120% rated voltage
Withstand 2000Vac, 2800Vdc
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
Mechanical Specifications
Enclosure dimensions (W×H×D) 225.00×177.00×224.80 (unit: mm)
Trepanning dimensions (W×H) 226.00×178.00, M5 screw (unit: mm)
Mounting Flush mounted
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- Serial Port for RTU/SCADA
Port number 0 or 2
Baud rate 4800 ~ 115200bps
Protocol IEC60870-5-103:1997 or DNP3.0
Maximal capacity 32
Transmission distance <1000m @ 4800bps
Safety level Isolation to ELV level
Type Test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Functions
• Three-stage phase overcurrent protection. (50P/51P) Features
• Three-stage directional phase overcurrent protection. (67P)
• Definite time and inverse time characteristics of overcurrent
• Three-stage neutral overcurrent protection. (67N) protection are both provided.
• Three-stage zero sequence overcurrent protection. (50/51N)
• Overcurrent protection could be supervised by directional
• Time negative sequence overcurrent protection. (51Q) element and voltage elements.
• Under/Overvoltage protection. (27/59)
• Undefrequency protection that can be supervised by rate-of-
• Breaker failure protection. (50BF) change elements would shed loads before out-of-step.
• Underfrequency protection. (81)
• The relay constantly measures a large mount of analog
• Frequency rate-of-change protection. (81R) quantities, such as phase voltage, phase-to-phase voltage,
• Thermal overload protection. (49) neutral voltage, phase current, neutral current, active power,
• Arc-flash protection. (51PAF) reactive power, power factor and frequency.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 4ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 142.4×266.0×203 (unit: mm)
Trepanning dimension (W×H) 154.0×268.0, M5 screw
Mounting Flush mounted
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Features
• Definite time and inverse time characteristics of overcurrent
Functions protection are both provided.
• Tripping circuit supervision. • The relay provides GPS clock synchronization, including
• CT failure detection logic. message, second pulse and IRIG-B synchronization.
• VT failure detection logic. • The relay is equipped with Ethernet ports with the IEC 61850
• Synchro-check voltage failure supervision. protocol and RS-485 ports with IEC 60870-5-103 protocol.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 4ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 142.4×266.0×203 (unit: mm)
Trepanning dimension (W×H) 154.0×268.0, M5 screw
Mounting Flush mounted
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Features
• The built-in reliable power swing blocking logic can properly
supervise the distance elements during a power swing. The
Functions power swing blocking logic can make the relay untrip for an
external fault during a power swing and pickup for an internal
• Three-zone phase-to-phase distance protection. (21P) fault.
• Two-stage overcurrent protection. (50P/51P)
• Under frequency protection that could be supervised by rate-
• Zero sequence overcurrent protection. (50N/51N) of-change element would shed loads before out-of-step.
• Underfrequency protection. (81U)
• The relay constantly measures a large mount of analog
• Frequency rate-of-change element. (7F)
quantities, such as phase voltage, phase-to-phase voltage,
• Switch-onto-fault (SOTF) logic. neutral voltage, phase current, neutral current, active power,
• Overload protection. (49) reactive power, power factor and frequency.
• Synchronism check. (25)
• O n t h e p r e m i s e o f 2 4 s a m p l e s p e r c y c l e , a l l d a t a
• Auto-reclosing (three-pole). (79) measurement, calculation and logic discrimination can be
• Power swing blocking. (68) finished within one sampling period. The event recording and
• Accelerated tripping during unsymmetrical faults. protection logic calculation are completed simultaneously.
• Accelerated tripping during double circuit line faults. • The relay provides GPS clock synchronization, including
• Remote control and measurement. second pulse and IRIG-B synchronization.
• Tripping circuit supervision. • The relay is equipped with Ethernet ports with the IEC 61850
• CT failure detection logic. protocol or IEC 60870-5-103 protocol and RS-485 ports with
• VT failure detection logic. IEC 60870-5-103 protocol.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 4ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 142.4×266.0×203 (unit: mm)
Trepanning dimension (W×H) 154.0×268.0, M5 screw
Mounting Flush mounted
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Auxiliary Testing
• Virtual SOE records generation
• Virtual measurement values generation
• Virtual tripping reports generation
• Virtual fault wave records generation
Functions
Features
Protection and control
• O n t h e p r e m i s e o f 2 4 s a m p l e s p e r c y c l e , a l l d a t a
• Overcurrent protection (50P/51P)
measurement, calculation and logic discrimination can be
• Zero sequence overcurrent protection (50N/51N) finished within one sampling period. The event recording and
• Directional overcurrent protection. (67P) protection logic calculation can be finished simultaneously.
• Voltage control element (VCE) • Definite time and inverse time of overcurrent protection are
• One shot three poles auto-reclose (79) both provided.
• Synchronism check function (25) • Overcurrent protection can be controlled by voltage element.
• Switch-on-to-fault logic (SOTF)
• This relay constantly measures and calculates a large
• Earth fault protection (64) amount of analog quantities, such as phase-to-phase
• Thermal overload protection (49) voltage, phase current, neutral current, active power, reactive
• Voltage and current drift auto adjustment power, power factor and frequency.
• Self diagnostic • It can monitor and record the operating time of opening/
• Bus and feeder voltage transformer supervision (VTS) closing circuit breakers.
• Current transformer supervision (CTS) • Various methods of GPS clock synchronization, including
• Rear communication ports: printer message, pulse per second, and IRIG-B synchronization.
• Rear communication ports: RS-485 • This relay is equipped with two EIA RS-485 standardized
• Time synchronization port interfaces and two Ethernet interfaces. The Ethernet interface
has two alternative designs: electrical or optical.
AC Voltage Inputs
Standard Per IEC 60255-6, 1988
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 220VDC 125VDC 250VDC
Pickup voltage 77VDC 154VDC 87.5VDC 175VDC
Dropout voltage 60.5VDC 121VDC 68.8VDC 137.5VDC
Maximum permitted voltage 150V 300V 150V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000Vac rms for 1min
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Bounce time 1ms 1ms
Dropout time(Typical/Max) 8ms/10ms 4ms/10ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
DC Output
Output range 4 ~ 20mA
Max load resistance 500ohm
Max output voltage 10V
Atmospheric Environment
Standard IEC60255-6:1988
Operating temperature range -25 °C ~ +55 °C
Transport and storage temperature range -40 °C ~ +70 °C
Permissible humidity 5% ~ 95%, condensation not permissible
Mechanical Specifications
Enclosure dimensions (W×H×D) 142.4×266.0×203.0 (unit: mm)
Trepanning dimensions (W×H) 154×268.0 (unit: mm), M5 screw
Mounting Way Flush mounted
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces for communicating with a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2007 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz /450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2008 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:1974, 16 hours at +55°C
Dry cold test IEC60068-2-1:1990, 16 hours at -25°C
IEC60068-2-30:1980, two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Features
• The voltages inputs and external binary inputs connecting to
breaker auxiliary contacts are used to detect the abnormal
state.
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Application object For protection For metering
Rated current (In) 1A 5A 1A 5A
Linear to 30In 30In 2In 2In
continuously 3In 3In 2In 2In
for 10s 30In 30In 12In 12In
Thermal withstand capability
for 1s 100In 100In 30In 30In
for half a cycle 250In 250In 75In 75In
Burden <0.1VA/phase <0.2VA/phase <0.2VA/phase <0.4VA/phase
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 48V 110V 125V 220V 250V
Rated current 1.2mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 55% rated voltage
Maximum permissive voltage 120% rated voltage
Withstand 2000Vac, 2800Vdc
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
Max system voltage 380Vac, 250Vdc 380Vac, 250Vdc
Voltage across open contact 1000V RMS for 1 minute 1200V RMS for 1 minute
5.0A @ 380Vac 8.0A @ 380Vac
Continuous carry
5.0A @ 250Vdc 8.0A @ 250Vdc
Pickup time <8ms <10ms
Drop-off time <5ms <8ms
6A for 3000ms 10A for 3000ms
Short duration current
15A for 500ms 20A for 500ms
0.6A @ 48Vdc, L/R=40ms 0.6A @ 48Vdc, L/R=40ms
Breaking capacity (L/R=40ms) 0.1A @ 110Vdc, L/R=40ms 0.3A @ 110Vdc, L/R=40ms
0.05A @ 220Vdc, L/R=40ms 0.2A @ 220Vdc, L/R=40ms
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
communication Port
- Serial Port for RTU/SCADA
Port number 0 or 2
Baud rate 4800 ~ 115200bps
Protocol IEC60870-5-103:1997 or DNP3.0
Maximal capacity 32
Transmission distance <1000m @ 4800bps
Safety level Isolation to ELV level
- Print Port
Port number 1
Type RS-232
Baud Rate 4800 ~ 115200bps
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type Test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Functions
• Rear communication ports: Ethernet with IEC 61850 or IEC
• Automatic transfer logic
60870-5-103, 2 RS-485 with IEC 60870-5-103, 1 RS-485 for
• Two-level overcurrent protection. (50P/51P)
clock synchronization, 1 RS-232 for communication to printer.
• Zero sequence overcurrent protection. (50N/51N)
• Overcurrent protection for energizing a faulty bus or a faulty
line. (50E)
Features
• Overload shedding function.
• Auto-switching control scheme could be blocked by voltage
• Synchronism check. (25)
element, current element or state of breakers.
• Remote control and measurements.
• Energization protection algorithm is reliable, practical and
• Circuit breaker monitoring.
adaptive.
• CT failure detection logic.
• Overcurrent protection can be supervised by voltage
• VT failure detection logic.
elements.
• Tripping circuit supervision.
• The RCS-9651 relay constantly measures a large mount
• Current drift auto adjustment.
of analog quantities, such as phase current, active power,
• Self diagnostic test. reactive power and power factor.
• GPS clock synchronization.
• O n t h e p r e m i s e o f 2 4 s a m p l e s p e r c y c l e , a l l d a t a
• Fault Recorder. measurement, calculation and logic discrimination could be
• 64 tripping reports and 256 SOE (Sequence of Events) done within one sampling period. The event recording and
records. protection logic calculation are completed simultaneously.
• High resolution oscillography of last 8 oscillograms. • The relay provides GPS clock synchronization, including
(Compatible with international COMTRADE format) message, second pulse and IRIG-B synchronization.
• The relay is equipped with Ethernet ports with the IEC 61850
protocol and RS-485 ports with IEC 60870-5-103 protocol.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 4ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 142.4×266.0×203 (unit: mm)
Trepanning dimension (W×H) 154.0×268.0, M5 screw
Mounting Flush mounted
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Features
• O n t h e p r e m i s e o f 2 4 s a m p l e s p e r c y c l e , a l l d a t a
measurement, calculation and logic discrimination can be
finished within one sampling period. The event recording and
Functions protection logic calculation can be finished simultaneously.
AC Voltage Inputs
Standard Per IEC 60255-6, 1988
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs:
Rated Voltage 110VDC 220VDC 125VDC 250VDC
Pickup voltage 77VDC 154VDC 87.5VDC 175VDC
Dropout voltage 60.5VDC 121VDC 68.8VDC 137.5VDC
Maximum permitted voltage 150V 300V 150V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000Vac rms for 1min
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Bounce time 1ms 1ms
Dropout time(Typical/Max) 8ms/10ms 4ms/10ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
DC Output
Output range 4 ~ 20mA
Max load resistance 500ohm
Max output voltage 10V
Atmospheric Environment
Standard IEC60255-6:1988
Operating temperature range -25 °C ~ +55 °C
Transport and storage temperature range -40 °C ~ +70 °C
Permissible humidity 5% ~ 95%, condensation not permissible
Mechanical Specifications
Enclosure dimensions (W×H×D) 142.4×266.0×203.0 (unit: mm)
Trepanning dimensions (W×H) 154×268.0 (unit: mm), M5 screw
Mounting Way Flush mounted
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Ethernet
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Optical Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Fiber Type Multi-mode
Wavelength 1300nm
Ethernet Optical
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces for communicating with a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2007 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz /450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:1974, 16 hours at +55°C
Dry cold test IEC60068-2-1:1990, 16 hours at -25°C
IEC60068-2-30:1980, two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Management
• Circuit breaker status monitoring
• Circuit breaker control
• 64 Fault records and 64 Disturbance records
• 1024 SOE records, latest records of following elements
state changing: operating abnormality alarm elements, self-
check alarm elements, protection elements and binary input
elements.
In normal operation, the power supply of busbar is provided by
the main power supply branch, and the standby power supply is
ready for switching. If circuit breaker CB3 is closed, the standby
power supply is in hot standby state; if tcircuit breaker CB3 is Features
opened, the standby power supply is in cold standby state.
• This device can provide all kinds of switching functions:
If the main power supply has fault, the PCS-9655 will trip normal manual switching, accident switching, loss-of-busbar-
circuit breaker “CB1”, and the voltage of busbar is lost. Due to voltage switching and circuit breaker mal-operation switching.
the mechanical inertia of motor load of busbar, the composite
• This device also provides useful auxiliary functions such as
feedback voltage of busbar is decaying gradually. In this
two stages of undervoltage load shedding protection and the
procedure, if the standby power supply is put into service at
SOTF overcurrent protection.
an improper moment, the voltage difference between busbar
residual voltage and standby power supply voltage will have a • The PCS-9655 adopts automatic frequency tracking
greater impact on other equipments in the power plant. Then technology in the busbar voltage measurement to calculate
the switching operation will be failed, and the busbar voltage is the frequency and the phase of busbar voltage fast and
lost absolutely. accurately.
The PCS-9655 high speed transfer device can select the optimal • The PCS-9655 supports different GPS clock synchronization,
moment for switching the standby power supply into service to including communication message, pulse per second, and
ensure the safety and reliability of switching operation. IRIG-B synchronization.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 482.6×177.0×291.0 (unit: mm)
Trepanning dimension (W×H) 450.0×179.0, M5 screw
Mounting Flush mounted
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Control
• 10 configurable binary inputs
• 7 binary outputs for DC voltage (including 4 configurable
contacts), 9 binary outputs for AC voltage (including 6
configurable contacts)
Functions • 8 LEDs, including 5 configurable LEDs
• Local/remote opening/closing logic of breaker
Protection
• Faceplate buttons for local control of breaker
• Three-stage phase overcurrent protection. (50/51P)
• Three-stage neutral overcurrent protection. (50/51N)
Communication and HMI
• Three-stage negative sequence overcurrent protection. • One RS-232 port for testing
(50/51Q)
• Two RS-485 ports for communication with SCADA
• Directional ground time overcurrent protection. (67G)
• IEC 60870-5-103 DNP 3.0 serial, and MODBUS protocol
• Breaker failure protection. (51BF)
• RCS-PC assistant software for testing
• Thermal overload protection. (49)
• Clock Synchronization
• Broken conductor protection. (46BC)
• Undervoltage/overvoltage protection. (27/59)
• Multi-slot three-pole auto-reclosing (Up to 3 slots). (79) Features
• Ten (10) available curves complied with ANSI and IEC
• O n t h e p r e m i s e o f 3 2 s a m p l e s p e r c y c l e , a l l d a t a
standard. (IDMT)
measurement, calculation and logic discrimination could be
• Thermal model overload curve. done within one sampling period. The event recording and
• Voltage transformer supervision. (VTS) protection logic calculation are completed simultaneously.
• Current transformer supervision. (CTS) • Definite time and inverse time of phase overcurrent protection
• Current drift auto-adjustment are both provided.
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition < 10 W
Burden
Operating condition < 15 W
Backup battery type ML2032, 3V, 65mAh
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.5VA/phase @ In < 0.1VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 57.7V (Phase) 63.5V (Phase)
linear to 100 V 115V
continuously 69.3V 76.3V
Thermal withstand capability 10s 115.5V 127.1V
1s 144.4V 158.9V
Burden <0.5 VA/phase @ Un <0.5 VA/phase @ Un
Binary Inputs
Rated Voltage 110VDC 220VDC
Pickup voltage 77VDC 154VDC
Dropout voltage 60.5VDC 121VDC
Maximum permitted voltage 150V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000VAC RMS fro 1minute
Mechanical Specifications
Enclosure dimension (W×H×D) 188.92×177.00×165.31 (unit: mm)
Trepanning dimension (W×H) 173.0×178.0, M5 screw
Mounting Flush mounted
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 19200bps
Transmission distance < 500m@4800bps
RS-485 (EIA) Maximal capacity 32
IEC60870-5-103:1997, , MODBUS or DNP 3.0
Protocol
serial
Safety level Isolation to ELV level
Interfaces for debugging through RCS-PC software
Port number 1
RS-232 (EIA) Baud rate 19200bps
Safety level Isolation to ELV level
Port number 2
RS-485 (EIA) Baud rate 4800 ~ 19200bps
Safety level 32
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Functional
Function RCS-9641 RCS-9642 RCS-9626 RCS-9627
Code
Protection for Motor
Unrestraint current differential protection 87U √ √
Percentage restraint current differential protection 87P √ √
Phase overcurrent protection 50P/51P √ √ √ √
Zero sequence overcurrent protection 50N/51N √ √
Negative sequence overcurrent protection 50Q/51Q √ √ √ √
Over voltage protection 59 √ √
Under voltage protection 27 √ √ √ √
Ground detector protection 64 √ √ √ √
Thermal overload protection 49 √ √ √ √
Miscellaneous
Mechanical protection MR √ √ √ √
CT failure detection logic CTS √ √ √ √
VT failure detection logic VTS √ √ √ √
GPS clock synchronization √ √ √ √
Remote control and measurements √ √ √ √
Fault Recorder FR √ √ √ √
IEC 60870-5-103 protocol √ √ √ √
MODBUS protocol √ √
• Fault Recorder.
• 64 tripping reports and 256 SOE (Sequence of Events)
records.
• High resolution oscillography of last 8 oscillograms
(compatible with international COMTRADE format)
• Rear communication ports: Up to three Ethernet ports with
IEC 61850, 2 RS-485 ports with IEC 60870-5-103 protocol,
one RS-485 for clock synchronization, one RS-232 for
communication to printer.
Features
• Definite time and inverse time characteristics of inverse
sequence overcurrent protection are both provided.
Functions • The relay can monitor and record the operating times of
opening/closing circuit breakers.
• Motor startup supervision. (66) • The inverse sequence overcurrent protection is used for
• Two-stage overcurrent protection. (50P/51P) inter-turn fault and unbalance fault, including open pole or
• Two-stage inverse sequence overcurrent protection. (50Q/ reverse phase sequence.
51Q) • The stator ground detector protection constitutes of zero
• Definite time zero sequence overcurrent protection. (50N) sequence overcurrent protection and zero sequence voltage
• Stator ground protection. (64) protection.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 4ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 142.4×266.0×203 (unit: mm)
Trepanning dimension (W×H) 154.0×268.0, M5 screw
Mounting Flush mounted
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Features
• The typical operating time of differential protection is less
than 25ms.It is the main protection for phase fault.
• Definite time and inverse time characteristics of inverse
sequence overcurrent protection are both provided.
• Inverse sequence overcurrent protection is used for inter-
turn fault and unbalance fault, including open pole or reverse
Functions phase sequence.
• Stator ground detector protection constitutes of zero
• Unrestraint current differential protection. (87UM)
sequence overcurrent protection and zero sequence voltage
• Percentage restraint current differential protection. (87PM) protection.
• Three-stage overcurrent protection. (50P, 51P)
• The RCS-9642 relay constantly measures a large mount of
• Three-stage inverse sequence overcurrent protection. (50Q, analog quantities, such as phase voltage, phase-to-phase
51Q) voltage, phase current, active power, reactive power, power
• Stator ground detector protection. (64) factor and frequency.
• Under voltage protection. (27) • The relay can monitor the status of circuit breaker.
• Over voltage protection. (59) • O n t h e p r e m i s e o f 2 4 s a m p l e s p e r c y c l e , a l l d a t a
• Thermal protection. (49) measurement, calculation and logic discrimination could be
• Mechanical protection. (MR) done within one sampling period. The event recording and
protection logic calculation are completed simultaneously.
• Overload protection.
• The relay provides GPS clock synchronization, including
• Tripping circuit supervision.
message, second pulse and IRIG-B synchronization.
• Remote control and measurements.
• The HMI interface with a LCD and a 9-button keypad on the
• CT failure detection logic.
front panel is friendly to users.
• VT failure detection logic.
• The format of event report is compatible with international
• Voltage and current drift auto regulation.
COMTRADE file.
• Self diagnostic.
• The relay can be integrated in SAS or RTU. The relay is
• GPS clock synchronization.
equipped with Ethernet ports with the IEC 61850 protocol
• Fault Recorder. and RS-485 ports with IEC 60870-5-103 protocol.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs:
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 4ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 142.4×266.0×203 (unit: mm)
Trepanning dimension (W×H) 154.0×268.0, M5 screw
Mounting Flush mounted
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Management
• Circuit breaker status monitoring
• Remote control and measurements
• Tripping circuit supervision
• Three-phase current and zero-sequence current metering
• Motor startup current monitoring
• Thermal capacity monitoring
• Multiple setting groups
• 64 Trip records
• 64 Operating alarm records
• 64 User operating records
• 8 Disturbance records FR
• 256 SOE records, latest records of following elements
state changing: operating abnormality alarm elements, self-
check alarm elements, protection elements and binary input
Functions elements.
• Circuit breaker operating time monitoring
Protection and control
• Time overcurrent protection (50P/51P) Auxiliary Testing
• Ground overcurrent protection (50G/51G) • Virtual SOE records generation
• Zero sequence overcurrent protection (50N/51N) • Virtual measurement values generation
• Starts per hour, time between starts (66) • Virtual tripping reports generation
• Negative sequence overcurrent protection (46) • Virtual fault wave records generation
• Thermal overload protection (49)
• Residual overcurrent protection (51G)
• Under voltage protection (27) Features
• Mechanical protection (MR) • O n t h e p r e m i s e o f 2 4 s a m p l e s p e r c y c l e , a l l d a t a
• Locked rotor protection measurement, calculation and logic discrimination can be
• Voltage and current drift auto adjustment finished within one sampling period. The event recording and
protection logic calculation can be finished simultaneously.
• Self diagnostic
• Voltage transformer supervision (VTS) • The RCS-9626 relay constantly measures and calculates a
large amount of analog quantities, such as phase voltage,
• Current transformer supervision (CTS)
phase-to-phase voltage, phase current, neutral current,
• Rear communication ports: printer active power, reactive power, power factor and frequency.
• Rear communication ports: RS-485/Ethernet
• The relay can monitor and record the operating time of
• Time synchronization port opening/closing circuit breakers.
• The relay is equipped with one EIA RS-485 standardized • Perfect fault and disturbance record function: 64 latest fault
interfaces and two Ethernet interfaces. Two alternative reports, 8 latest fault wave (up to 15s), 64 user operating
designs of Ethernet interfaces are provided: electrical or records of users to equipment, and 256 records of time tagged
optical. sequence of event can be recorded.
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11
Per IEC 61000-4-11:2004, IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition <15W
Burden
Operating condition <25W
Backup battery type ML2032, 3V, 65mAh
AC Voltage Inputs
Standard Per IEC 60255-6, 1988
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 220VDC 125VDC 250VDC
Pickup voltage 77VDC 154VDC 87.5VDC 175VDC
Dropout voltage 60.5VDC 121VDC 68.8VDC 137.5VDC
Maximum permitted voltage 150V 300V 150V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000Vac rms for 1min
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Bounce time 1ms 1ms
Dropout time(Typical/Max) 8ms/10ms 4ms/10ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Atmospheric Environment
Standard IEC60255-6:1988
Operating temperature range -25 °C ~ +55 °C
Transport and storage temperature range -40 °C ~ +70 °C
Permissible humidity 5% ~ 95%, condensation not permissible
Mechanical Specifications
Enclosure dimensions (W×H×D) 142.4×266.0×203.0 (unit: mm)
Trepanning dimensions (W×H) 154×268.0 (unit: mm), M5 screw
Mounting Way Flush mounted
Local control panel Small control module: 3 LED indicators, a 9-key keypad and a 160×80-dot LCD
Housing material Aluminum
Housing color Silver grey
Front side: IP51
Protection class Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Ethernet
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Optical Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Fiber Type Multi-mode
Wavelength 1300nm
Ethernet Optical
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces for communicating with a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:1974, 16 hours at +55°C
Dry cold test IEC60068-2-1:1990, 16 hours at -25°C
IEC60068-2-30:1980, two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Management
• Circuit breaker status monitoring.
• Remote control and measurements.
• Tripping circuit supervision.
• Multiple setting groups.
• 64 Trip records.
• 64 Operating alarm records.
• 4 Self-check alarm records.
• 64 User operating records.
• 8 Disturbance records FR.
• 256 SOE records, latest records of following elements
state changing: operating abnormality alarm elements, self-
check alarm elements, protection elements and binary input
elements.
• Circuit breaker operating time monitoring.
Technical data
Power Supply
Rated Voltage (Un) 24Vdc, 30 Vdc, 48Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11
Per IEC 61000-4-11:2004, IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Quiescent condition <15W
Burden
Operating condition <25W
Backup battery type ML2032, 3V, 65mAh
AC Voltage Inputs
Standard Per IEC 60255-6, 1988
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
continuously 120 V 120 V 200V
Thermal withstand capability 10s 200 V 200 V 350V
1s 250 V 250 V 400V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 220VDC 125VDC 250VDC
Pickup voltage 77VDC 154VDC 87.5VDC 175VDC
Dropout voltage 60.5VDC 121VDC 68.8VDC 137.5VDC
Maximum permitted voltage 150V 300V 150V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000Vac rms for 1min
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Bounce time 1ms 1ms
Dropout time(Typical/Max) 8ms/10ms 4ms/10ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
DC Output
Output range 4 ~ 20mA
Max load resistance 500ohm
Mechanical Specifications
Enclosure dimensions (W×H×D) 142.4×266.0×203.0 (unit: mm)
Trepanning dimensions (W×H) 154×268.0 (unit: mm), M5 screw
Mounting Way Flush mounted
Local control panel Small control module: 3 LED indicators, a 9-key keypad and a 160×80-dot LCD
Housing material Aluminum
Housing color Silver grey
Front side: IP51
Protection class Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces for communicating with a printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
Type Test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:1974, 16 hours at +55°C
Dry cold test IEC60068-2-1:1990, 16 hours at -25°C
IEC60068-2-30:1980, two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Function Index
Features
• The RCS-9631 integrates protection, control, monitoring and
metering functions for the capacitor in one rack.
• Current transformer supervision. • The relay provides GPS clock synchronization, including
• Circuit breaker status monitoring. second pulse, minute pulse and IRIG-B synchronization.
• Circuit breaker control. • The relay is compatible with multiple protocols- IEC61850
• GPS clock synchronization. and IEC 60870-5-103. It provides networking interface such
as RS485, RS232 and Ethernet port.
• Fault Recorder.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs:
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V 200 V
linear to 100 V 173 V 230 V
continuously 120 V 120 V 200 V
Thermal withstand capability 10s 200 V 200 V 350 V
1s 250 V 250 V 400 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 77VDC 87.5VDC 154VDC 175VDC
Dropout voltage 60.5VDC 68.8VDC 121VDC 137.5VDC
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000VAC RMS fro 1minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 4ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimension (W×H×D) 142.4×266.0×203 (unit: mm)
Trepanning dimension (W×H) 154.0×268.0, M5 screw
Mounting Flush mounted
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces connecting with RTU/SCADA
Port number 2
Baud rate 4800 ~ 38400bps
Transmission distance < 1000m@4800bps
RS-485 (EIA)
Maximal capacity 32
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2~3
Connector type RJ-45
Transmission Rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2~3
Ethernet
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Optical Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 1500m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Interfaces connecting with printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
RS-485 (EIA) Transmission distance < 500m
Maximal capacity 32
Timing standard PPS, IRIG-B
RS-485 (EIA)
Safety level Isolation to ELV level
Type test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
PCS-221
Merging Unit
Technical data
Power Supply
Standard IEC 60255-11:2008
Rated Voltage (Un) 110V/125V, 220V/250V
Voltage Range 80%Un~120%Un
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
Quiescent condition <25W
Burden
Operating condition <30W
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Analog voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V 200V (Broken delta for residual voltage)
linear to 1~170V 1~233V
continuously 200V 220V
Thermal withstand capability 10s 260V 380V
1s 300V 420V
Burden < 0.20VA/phase @Un < 0.8VA/phase@Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 55% rated voltage
Maximum permissive voltage 120% rated voltage
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Signal contact
Output mode Potential-free contact
8A@380V AC
Continuous carry
8A@250V DC
Pickup time <10ms
Drop-off time <8ms
10A for 3000ms
Short duration current
20A for 500ms
0.6A @ 48Vdc , L/R=40ms
Breaking capacity (L/R=40ms) 0.3A @ 110Vdc, L/R=40ms
0.2A @ 220Vdc, L/R=40ms
380V AC
Maximal working voltage
250V DC
Test voltage across open contact 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 225.00mm× 177.00 ×268.80mm
Mounting Flush mounted
Trepanning dimensions (W×H) 226.00mm×178.0mm, M6 screw
Housing color Silver grey
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Type test
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
Features
• All plug-in modules in this device can be smoothly upgraded
to keep compatible with UAPC platform, thereby provides a
solid protection on users' investment in equipment for a long
period.
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropoff voltage <55% of rated voltage
Maximum permissive voltage 120% of rated voltage
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Output mode Potential free contact
8A@380V AC
Continuous carry
8A@250V DC
Pickup time <10ms
Drop-off time <8ms
10A@3s
Short duration current
[email protected]
0.7A@48Vdc
Breaking capacity (L/R=40ms) 0.3A@110Vdc
0.2A@220Vdc
380V AC
Maximal working voltage
250V DC
Test voltage across open contact 1200V RMS for 1minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Housing color Silver grey
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- For Process Level
Characteristic Glass optical fiber
Connector typel LC
Fibre type Multi mode
Transmission distance <2km
Wave length 1310nm
Transmission power Min. -20.0dBm
Minimum receiving power Min. -30.0dBm
Margin Min +3.0dB
• Monitoring of circuit breaker operation characteristics • Flexible communication mode is provided with 2 independent
The device acquires the operation curve of circuit breaker optical Ethernet interfaces and 1 RS-232 debugging port.
via offset sensor to detect the potential problem of circuit New generation substation communication standard
breaker, and to issue an alarm. IEC61850 is supported.
NR’s electronic CTs/VTs are suitable for both gas-insulated Remote end module: The electronic CT/VT for GIS is
switchgears air-insulated switchgears and have been proven composed of two duplicated remote end modules which are
in the laboratory and are successfully put in-service in real used to receive and process output signals for low power CT,
substation applications worldwide. air core coil and capacitor voltage divider. The output signals
of remote end module are transmitted to merging units through
optical fibers. Primary sensors and remote end modules are all
Active Current Transformer installed at low voltage side with duplicated configuration.
Capacitor voltage divider: The capacitor voltage divider - Medium and Low Voltage Electronic CT/VT
can divide high voltage into low voltage signal and send it Medium and low voltage electronic CTs/VTs are installed in
to remote modules for processing. It also can be used as an 10kV-35kV switchgear cabinets or outdoor to measure primary
communication carrier device. current and voltage. The output signals are delivered to digital
measurement devices, bay control units and protective relays. It
Merging unit: Merging units are placed in control rooms to
is composed of low power CTs (LPCTs), transport modules and
provide laser power supply and receive three-phase current
remote onsite acquisition units etc.
and voltage signals. The output of merging units will be sent to
protection and control devices using IEC60044-8 or IEC61850-
9-1/2 protocol.
- DC Electronic CT
DC electronic CTs are intended for applications in HVDC
converter station. It measures DC current and harmonic current,
and output digital signals to protection and control devices in
converter station. The DC electronic CT is composed of four
parts:
Technical data
- Electronic CT/VT for GIS Application
Max. operation voltage Um(kV) 126 252 363 550
Withstand voltage (kV) 230 460 510 680
Lightening impulse withstand voltage(kV) 550 950/1050 1175 1550
Switching impulse withstand voltage(kV) - - 950 1175
Rated primary voltage(kV) 110/ √3 220/√3 330/√3 500/√3
Rated primary current(A) 300~3000 300~3000 300~3000 300~3000
Short time thermal current, 3S (kA), 3s 40 50 50 63
Features
• Signals are transmitted via optic fibers at HV side without any • FOCTs are composed of three parts:
electrical circuit. High insulation property of optical fiber can - Fiber optic transmission system: FOCT uses fiber optic
guarantee the complete electrical separation to prevent the transmission system to connect HV side and LV side. It
risk of open circuit on LV side. delivers optic signals from source to primary current sensor
• No magnetic saturation and ferromagnetic resonance. and transmits feedback signals to modulator circuit.
• Wide dynamic measuring range and high measuring - Signal modulating device: The signal modulating device
accuracy. includes light source and optic components such as
detector and primary current signal processing system.
• With benefit in wide range of frequency response, FOCTs The circuit processing system of merging unit receives and
can measure high-order harmonic, transient current and DC processes three-phase current signals and output digital
current more accurately. current signals to protective relays.
• FOCT has strong universality to adapt to various current • The complete symmetrical reciprocal optical design can
transformers with different voltage levels and different current greatly reduce the risks of environmental impact to guarantee
rating. higher reliability of optic circuit. The light-weight sensing
• Oil insulation is replaced by simplified insulation structure to ring can be widely applied to the traditional column-type CT,
eliminate flaming and explosion risks. The small volume and bushing-type CT and also can be integrated in GIS.
light weight can help to save the installation space.
PCS-9700
Substation Automation System
System Architecture converts them into digital information and distributes them to
various IEDs in bay level. Gigabit switch is supplied for process
bus to realize the real-time information transmission. Process
• System Architecture bus can be configured as redundant Ethernet based on optical
The system comprises three or four levels in hierarchical fiber.
structure: Station Level, Network Level, Bay Level and optional
Process Level. • Typical structure description
• Station level consists of host, operator station and engineer
• Station Level station. Several computers or single computer configuration
The station level is a distributed system comprising a single can be adopted.
computer host or several hosts. It provides supervisory, control
• Windows or UNIX can be used as the operation system.
and management functions for operators in the substation. Man-
machine interface is friendly and easy to handle. The structure • T he gateway can adopt RCS-9698G/H device, channel
makes it flexible to be extended and reliable to be operated. switching equipment and channel interface.
By applying the component technology, “plug-and-play” can
• RCS-9785 can be used as the GPS receiver.
be realized for software functions. It can communicate with
dispatching centers or other concentrated control stations using • PCS and RCS series protection equipments can connect
different standard protocols such as IEC-60870-5-101 and IEC- with station level directly by two 100M Ethernet ports or by
60870-5-104. two RS-485 ports through protocol converter.
Figure 2. Double-Star Ethernet Structure of PCS-9700 Automation Figure 3. Ring Ethernet Structure of PCS-9700 Automation System
System Complied with IEC61850 Complied with IEC61850
Electromagnetic compatibility
Electrostatic discharge IEC 61000-4-2, class 4
Radiated, radio-frequency electromagnetic field IEC 61000-4-3, class 3
Electrical fast transient/burst IEC 61000-4-4, class 4
Surge IEC 61000-4-5, class 3
Conducted disturbances, induced by radio-frequency fields IEC 61000-4-6, class 3
Power frequency magnetic field IEC 61000-4-8, class 4
Pulse magnetic field IEC 61000-4-9, class 5
Damped oscillatory magnetic field IEC 61000-4-10, class 5
Oscillatory waves IEC 61000-4-12, class 2
Maximum capacity
Telesignal 65535
Telemetering 65535
Telecounting 65535
Telecontrol 65535
Teleregulation 65535
Total number of stations can be comprised in system of a controlling
65535
station
Accuracy
Resolution of A/D conversion 14 bits
GPS clock synchronism ≤ 1 ms
GPS clock synchronism ≤ 2 ms
Total error of analog quantity measurement
Voltage and current ≤ 0.2%
Active and reactive power ≤ 0.5%
Power frequency ≤ ±0.01 Hz
Refreshing cycle
Telemetering, from acquisition input to communication interface output ≤ 3 sec
Telesignal, from change of state input to communication interface output ≤ 3 sec
Telecontrol, from command creation to communication interface output ≤ 1 sec
Updating period of analog quantities on chart ≤ 3 sec
Updating period of change of state on chart ≤ 2 sec
Switch over time of standby hosts ≤20s
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
• Real-time data acquisition and processing • Module and object oriented technology are used to build up
• Control operation, synchronism checking and interlocking the system.
• Setup and maintenance of data base • The design adopts international standard such as C++, TCP/
• Reactive power and voltage automatic regulation IP, OLEDB, SQL and ActiveX etc.
• Configurable alarm processing • Supporting various interfaces, such as DDE and share
memory, supporting flexible network structure, connecting
• Sequence of events record and post-fault review
easily with other systems
- Configuration and displaying of graph and chart • Supporting cross platform function.
Interface editor is an important tool to generate geographic • The system can operate in UNIX, LINUX and Windows
graphs, single line diagrams, reports and bar charts. It provides platform and can be installed in computers with different OS.
convenient compilation function such as graph and report • Friendly HMI with online help function which is easy to learn
creation to make preparation work more convenient, fast and and use.
efficient.
• Adopting unified commercial and realtime database,
equipment oriented database management system to support
- List of events
equipment online configuration and realtime verification
The system can provide various information, such as protection
function.
information protection, list of protection events, real-time and
historical curves and real-time and historical reports. • Realizing network information by mutually exchanging,
processing and verifying technologies based on softbus
Besides, users can perform the following functions via the technology.
main interface, such as the reset of protection signals and • Switch over of redundant equipments without disturbance
configuration of protection setting, post-fault review and display through network and nodes redundant configuration.
of the result in picture form, and supervisory on communication • Well-designed online self-diagnosing function to identify the
bit stream, etc. failures of equipments and network on time.
• Self-restoration function helps system to restore to normal
- On-line calculation and reports preparing
operation mode if the program losses control.
Based on the real-time data acquired, the system can make
calculation on current, voltage, active and reactive power and • Having well-designed online self-diagnosing function, finding
power factor, statistics of maximum and minimum value per day, the failure of equipments and network of system on time,
month and year of assigned quantities and duration of these then giving alarming information
values’ occurrence. • Having self-restoration function, system can restore to the
normal operation mode if the program losses control.
• Voltage and current drift auto adjustment • All AC quantity inputs can be sampled simultaneously to
• Self diagnostic test ensure the accuracy of analog quantity measurement which
is up to 15th harmonic component.
• Total 1024 SOE, including alarm, binary input change and
human operation reports • The BCU provides optional RTD input module and 4-20mA
• Up to 4 Ethernet ports with IEC 61850-8-1 for station bus DC input module for detection of temperature. And optional
4-20mA outputs are provided for AGC implementation.
• 2 optional fiber Ethernet ports for process bus, support
GOOSE and IEC61850-9-2 • Software and hardware timing are both adopted with 1ms
• 2 RS-485 communication rear ports conform to IEC 60870-5- timing accuracy to ensure the resolution of sequence of
103 protocol events.
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<20W (for conventional substation application)
Quiescent condition
<25W (for smart substation application)
Burden
<25W (for conventional substation application)
Operating condition
<30W (for smart substation application)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range 90% ~ 110% fn
Accuracy 0.2 class
Rated current (In) 1A 5A
Linear to 0.05In~2In
continuously 2In
for 10s 12In
Thermal withstand capability
for 1s 30In
for half a cycle 75In
Burden < 0.2VA/phase @In < 0.4VA/phase @In
Analog voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range 90% ~ 110% fn
Rated phase-to-phase voltage (Un) 100~130V
linear to 1~130V
Accuracy 0.2 class
continuously 130V
Thermal withstand capability 10s 200V
1s 250V
Burden < 0.10VA/phase @Un
Transducer Inputs
Standard IEC 60255-1:2009
Input range 0-20mA 0~5V 0~48V 0~250V
Input resistance 235Ω 4.4 kΩ 54.2 kΩ 248 kΩ
Accuracy 0.5 class 0.5 class 0.5 class 0.5 class
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 48V 110V 125V 220V 250V
Rated current 1.2mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 55%~70% of rated voltage
Maximum permissive voltage 120% rated voltage
Withstand 2000Vac, 2800Vdc
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
Max system voltage 380Vac, 250Vdc 380Vac, 250Vdc
Voltage across open contact 1000V RMS for 1 minute 1200V RMS for 1 minute
5.0A @ 380Vac 8.0A @ 380Vac
Continuous carry
5.0A @ 250Vdc 8.0A @ 250Vdc
Pickup time <8ms <10ms
Drop-off time <5ms <8ms
6A@3s 10A@3s
Short duration current
[email protected] [email protected]
0.6A @ 48Vdc, L/R=40ms 0.6A @ 48Vdc, L/R=40ms
Breaking capacity (L/R=40ms) 0.1A @ 110Vdc, L/R=40ms 0.3A @ 110Vdc, L/R=40ms
0.05A @ 220Vdc, L/R=40ms 0.2A @ 220Vdc, L/R=40ms
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6× 177.0 ×230.2 (unit: mm)
Trepanning dimensions (W×H) 450.0×179.0, M6 screw (unit: mm)
Mounting Flush mounted
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- Ethernet Port for RTU/SCADA
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850
Safety level Isolation to ELV level
- Print Port
9702C
9703C
9704C
9705C
9706C
9707C
9708C
9709C
9710C
Module
Pulse accumulation 4 4 4 4 4 4 4 4 4 4
5VT 5VT 8VT 5VT 5VT 5VT 8VT
AC inputs 13VT 26VT 26VT
4CT 4CT 7CT 4CT 4CT 4CT 7CT
Transducer inputs 15 8 8 8 0 0 0 8 8 15
Binary inputs 134 56 56 80 62 62 86 56 56 134
Binary outputs 16 16 16 8 16 0 8 8 16 16
Analog output 0 0 0 0 0 0 0 4 0 0
CB Synchronization 1 0 1 2 1 0 1 1 2 0
Interlocking function √ √ √ √ √ √ √ √ √
Interlocking criteria
√ √ √ √ √ √
status output function
15th harmonic √ √ √ √ √ √ √ √ √ √
Features
• The equipment is designed based on a 32 bits CPU and DSP • Software and hardware timing adopts 1ms timing accuracy to
hardware platform. It adopts real-time multitasks operation ensure the resolution of sequence of events.
system with high processing ability. • The control circuits adopt many block, permit and verify
• The device adopts 14 bits high accuracy A/D converter so facilities, including bay level transverse interlock function
that all AC quantity inputs can be sampled simultaneously to based on network communication so that security of local
ensure the accuracy of analog quantity measurement. and remote control can be ensured.
• A group of voltage and current analog inputs, and the basic • The network of equipments adopts 100M optic fiber or twisted
contents consist of current, voltage, frequency, electric wire Ethernet. And It is convenient and easy to be setup.
energy calculation, power and power factor
Technical Data
Power Supply
Rated Voltage (Un) 48Vdc, 110Vdc/125Vdc, 220Vdc/250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:1979
Voltage dips and voltage short interruptions 20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
20In 20In
Linear to (non-offset AC current)
2In (for metering) 2In (for metering)
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1988
Rated Voltage (Un) 100 V/√3, 110 V/√3 100 V, 110 V
linear to 106 V 175 V
continuously 173V 173V
Thermal withstand capability 10s 240 V 240 V
1s 300 V 300 V
Burden <0.2 VA/phase @ Un <0.5 VA/phase @ Un
Binary Inputs
Rated Voltage 110Vdc 220VdcC 125Vdc 220Vdc
Pickup voltage 77Vdc 154Vdc 87.5Vdc 175.0Vdc
Dropout voltage 60.5Vdc 121Vdc 68.8Vdc 137.5Vdc
Maximum permitted voltage 150V 300Vdc 150Vdc 300V
Withstand 2000Vac
Binary Outputs
Item Tripping contact Signal contact
Output model potential free contact
Max system voltage 250Vac/dc
Test voltage across open contact 1000VAC RMS fro 1minute
5A @250V AC 8A @250V AC
Continuous carry
0.3A @220V DC 0.3A @220V DC
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
482.6 × 266 × 291, (unit: mm), RCS-9701C,RCS-9710C
Enclosure dimension (W×H×D)
213.6 × 266 × 291, (unit: mm), others
450 ×267, (unit: mm), M6 screw, RCS-9701C,RCS-9710C
Trepanning dimension (W×H)
215 ×267, (unit: mm), M5/M6 screw, others
Mounting Flush mounted
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Functions
- Collect Information from IEDs
Depending on the applied protocol and database configuration, so on.) and any desired RTU protocols (any new protocols are
and also owing to its powerful communication interface, RCS- provided on client’s request). Moreover, information sent to
9798G/H can communicate with various IEDs in a substation, dispatching center can be selected according to the necessity.
and automatically collect any wanted information from them,
e.g. sequence of events (SOE), binary signals, transformer tap - Information marshalling and synthesizing
position, pulse counting of electricity quantity, communication An important aspect of multiple protocol applications of RCS-
states and so on. In addition, all the collected information can 9698G/H (e.g. communicate with several dispatching centers) is
be sent to dispatching center. the proper marshalling of the data to be transferred according to
the appropriated RTU protocols. With the help of Configuration
- Small-capacity memory storage Tool, signal synthesization is implemented, such as General
With small-capacity of industrial-grade NANDFLASH memory Alarm, General Failure.
(128MBytes for single machine while 256MBytes for dual
machine system), information of events(protection relays’ self- - Signal transmitting
checking information, trip event records, fault information, Depending on the utilized RTU protocol, all the collected signals
settings modification records and so on), remote command can be selectively sent to dispatching center. Signal selection
from dispatching center including selecting and executing of the can be done during RCS-9698G/H database configuration by
binary output and setting modifications, remote regulation of Configuration Tool.
transformer tap position, remotely signal reset event and so on
are stored, which are automatically collected from various BCU, - Multiple Switchover Scheme for Dual-machine
protection relays and some other auxiliary IEDs. Configuration
Whenever an error happens in the HOST MACHINE (e.g.
- Settings management CPU or power supply failure), the HOT STAND-BY MACHINE
RCS-9698G/H can upload/download and modify settings (only will be forced to be as a host one. With a dedicated seamless
the currently activated group of setting can be managed) of switchover technique, the equipment will guarantee that records
various expected protection relays and auxiliary IEDs. Setting are not lost during a switchover. There are up to four kinds of
management can be done by Debugging Tool or achieved by dual-machine switching scheme.
dispatching center up to the applied protocol.
- Time Management
- Communicate with dispatching center via various As the equipment Real Time Clock has small drift per day,
protocol and interfaces therefore, in order to have a correct time for time tagging of
Appreciated to its powerful communication function, RCS- event etc., the operator should set its time periodically or it
9698G/H can send all collected information to dispatching should be synchronized by a master clock. With a correct clock,
center via multiple standard communication interface (e.g. the equipment can be configured to synchronize its managed
electrical/optical Ethernet port, electrical/optical serial port and IED’s clock.
Technical data
Power Supply
Rated Voltage (Un) 110V/125Vdc, 220V/250Vdc, 48V DC
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11
Per IEC 61000-4-11:2004, IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
Burden 45W for single machine, 90W for dual machine configuration
Backup battery type ML2032, 3V, 65mAh
Mechanical Specifications
Enclosure dimensions 482.6×177.0×291 (unit: mm)
Trepanning dimensions 450.0×179.0, M6 screw
Mounting Way Flush mounted
Front side: IP51
Protection class Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Ethernet channel interfaces
Single machine: 4 ~ 16
Port number
Dual machine: 8 ~ 32
Connector type RJ-45
Ethernet Transmission Rate 10M/100Mbps auto-negotiation
Transmission standard 10Base-T/100Base-TX
Transmission distance < 100m
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Functions
• Universal protocol converter
The RCS-9794A/B is a highly-reliable, fully non-blocking
intelligent protocol converter, which supports interworking
between a wide range of protocols.
Features
• Various communication protocols can be selected flexibly for
• Linking protection equipments and other IEDs to substation
each communication port,
automation system
The RCS-9794 can send data from protective relays and • Suitable for installation in cubicles.
other IEDs to SAS. It also can send the control commands
of SAS to local bay units. • Supporting dual machine system configuration with the merit
of absolutely electrical independence.
• Linking protection equipments and other IEDs to remote
• Dual Ethernet communication is used for the upward
terminal units
communication with local HMI or RTUs at station level to
The RCS-9794 can send data from protective relays
ensure the reliability of all upward communication.
and other IEDs to RTUs. It can also send the remote
commands of remote control center to local bay units. • Embedded multiple processor architecture, all processors
are mutually independent and parallel running. Moreover,
• Inspection and monitor of communication status the equipment can equalize load among each processor. In
The RCS-9794 can inspect and monitor the communication this way, it exploits the merit of distributed multiprocessor
status of various equipments. If a connection or a
system’s parallel processing ability.
disconnection happens, the RCS-9794 will send the
change-of-state message to a station level device, such as • Configurable communication interfaces.
a local HMI or RTU.
• Hardware time synchronization (pulse per second (PPS))
• Clock synchronization and system time unification
• Various communication interfaces can be selected flexibly
The RCS-9794 can receive Pulses Per Second (PPS)
according to the engineering requirements. Serial ports,
and the timing messages from a GPS device. It will also
copper Ethernet ports, fiber serial ports and fiber Ethernet
synchronize its clock with the GPS device and send the
timing messages to the equipments that are connect to it. ports can be selected.
Mechanical Specifications
Enclosure dimensions (WxHxD) 482.6 × 177 × 291 (Unit: mm)
Trepanning dimensions 450×179, M6 screw
Mounting Way Flush mounted
Front side: IP51
Protection class Rear side, connection terminals: IP20
Other Sides: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +60°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Serial Interfaces
Baud rate 300bits/s ~ 38400bits/s
Copper Transmission distance < 1000m@4800bps
Safety level Isolation to ELV level
Baud rate 300bits/s ~ 38400bits/s
RS-232/422/485 Optical Fiber Type Multi-mode
Connector type ST
Fiber
Wavelength 850nm
Transmission distance ≤ 2000m
Safety level Isolation to ELV level
Baud rate 9600bits/s
Copper
Safety level Isolation to ELV level
Connector type 9600bits/s
LonWorks Optical Fiber Type Multi-mode
Connector type ST
Fiber
Wavelength 850nm
Transmission distance ≤ 2000m
Safety level Isolation to ELV level
Ethernet Interfaces
Connector type RJ-45
Transmission Rate 100Mbits/s
Copper Ethernet Ports) Transmission standard 100BASE-TX
Transmission distance < 100m
Safety level Isolation to ELV level
Connector type SC
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Fiber Ethernet Ports Optical Fiber Type Multi-mode
Wavelength 1300nm
Transmission distance < 2000m
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Technical Data
AC Power Supply
Rated Voltage (Un) 110V AC, 220V AC
Variation (80% ~ 120%)Un
500ms for interruption without de-energizing, dips 60% of Un without reset up to 12 cycles;
Voltage dips and voltage
dips 30% of Un without reset up to 30 cycles;
short interruptions (IEC 61000-4-11:2004)
dips 20% of Un without reset up to 300 cycles
DC Power Supply
110V DC, 125V DC, 220V DC, 250V DC;
Rated Voltage (Un)
48V DC power supply is available if a specified power supply module is selected
Variation (80% ~ 120%)Un
IEC 61000-4-17:2002
Ripple in the DC auxiliary voltage
Max 15% of the DC value.
IEC 61000-4-29:2000
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
PCS-9881: <13W
PCS-9882A: <10W
Burden (no load) PCS-9882B: <9W
PCS-9882C: <8W
PCS-9882D: <8W
PCS-9881: <26W
PCS-9882A: <16W
Burden (Full load) PCS-9882B: <31W
PCS-9882C: <14W
PCS-9882D: <14W
Mechanical Specifications
Enclosure dimensions (WxHxD) 482.6 ×44.4 ×216 (Unit: mm)
Trepanning dimensions 450×44.45 (unit: mm), M6 screw
Upper/Left/Right side: IP50
Protection class Front side: IP40, up to IP51
Rear side: IP30
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Interface Type RJ45
Transmission Rate 100Mbits/s
100Mbits/s Ethernet Port Transmission standard 10Base-T/100Base-TX
Transmission distance < 100 meters
Safety level Isolation to ELV level
Characteristic Glass optical fiber
Connector type LC
Transmission standard 100Base-FX
50/125 multi mode fiber
100Mbits/s Optical Fiber Port
Fiber type 62.5/125 multi mode fiber
9/125 single mode fiber
Multi mode: <2km
Transmission distance
Single mode: <40km
Characteristic Glass optical fiber
Connector type LC
Transmission standard 100Base-FX
50/125 multi mode fiber
Fiber type 62.5/125 multi mode fiber
1000Mbits/s Optical Fiber Port 9/125 single mode fiber
Multi mode: <500m
Single mode: <10km
Transmission distance If procured by users themselves, the
transmission distance is subject to
the SFP transceiver module.
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Technical Data
Power Supply
Rated Voltage (Un) 110Vdc/125Vdc, 220Vdc/250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:1979
Burden <40W
Binary Outputs
Item Signal contact
Output model Potential-free contact
Max system voltage 380Vac, 250Vdc
Test voltage across open contact 1200V RMS for 1min
8.0A @ 380Vac
Continuous carry
8.0A @ 250Vdc
0.7A@48Vdc
Breaking capacity at 250Vdc 0.3A@110Vdc
0.2A@220Vdc
10A@3s
Short duration current
[email protected]
Pickup time < 10ms
Dropout time < 8ms
Bounce time 1ms
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +60°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Ports to Transmit Clock Synchronization Signals
Connector type RJ45
Transmission Rate 100Mbps
Transmission standard 10Base-T/100Base-TX
Ethernet
Transmission distance < 100m
Protocol SNTP
Safety level Isolation to ELV level
Synchronization Standard Serial Port Timing Messages(9.6kbit/s) or IRIG-B
Transmission distance <30m
RS-232
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
Synchronization Standard Serial Port Timing Messages(9.6kbit/s) or IRIG-B
Transmission distance <500m
RS-485 (EIA)
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
Characteristic Glass optical fiber
Connector type ST or SC
Fiber type 62.6/125 μm for multi-mode
Transmission standard(for IEEE1588) 100Base-FX
Optical Fiber Port
Protocol IRIG Standard 200-04 or IEEE1588
Transmission distance <2km
Wave length 820nm
Synchronization Standard IRIG-B
Output voltage 0 - 5V
Output impedance 50Ω
TTL Port
Transmission distance <100m
Safety level Isolation to ELV level
Ports to Receive Clock Synchronization Signals
Synchronization Standard IRIG-B
RS-485 (EIA) Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
Synchronization Standard IRIG-B
TTL Port Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
Characteristic Glass optical fiber
Connector type ST
Optical Fiber Port Fiber type 62.6/125 μm for multi-mode
Wave length 820nm
Synchronization Standard IRIG-B
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Technical data
Power Supply
Rated Voltage (Un) 110Vdc/125Vdc, 220Vdc/250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:1979
Burden <40W
Binary Outputs
Item Signal contact
Output model Potential-free contact
Max system voltage 380Vac, 250Vdc
Test voltage across open contact 1000V RMS for 1min
Continuous carry 8.0A
0.4A resistance
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms)
Short duration current 50A for 200ms
Pickup time 5ms/10ms
Dropout time < 8ms
Bounce time 1ms
Mechanical Specifications
Enclosure dimension (W×H×D) 482.6×177.0×291.0, (unit: mm)
Trepanning dimension (W×H) 450.0×179.0, (unit: mm), M6 screw
Mounting Flush mounted
Front side: IP51
Protection class (per IEC60529:2001) Rear side, connection terminals: IP20
Other Sides: IP30
Communication Interfaces
Communication medium Parameters
Interfaces to connect the synchronized devices
Port number 7 per module
Connector type RJ45
Transmission Rate 100Mbps
Transmission standard 10Base-T/100Base-TX
Ethernet
Transmission distance < 100m
Protocol SNTP
Safety level Isolation to ELV level
Port number 7 per module
RS-232 Transmission distance <30m
Safety level Isolation to ELV level
Port number 7 per module
Maximal capacity 32
RS-485 (EIA)
Transmission distance <500m
Safety level Isolation to ELV level
Port number 8 per module
Operating voltage ≤ 300Vdc
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
PCS-9100
Distribution Control System for
Thermal Control (DCS)
The PCS-9100 series distribution control system is a • Control system for auxiliary generator: The PCS-9100 series
comprehensive control platform intended for the application realizes safe and integration control for auxiliary generators
to main generators and auxiliary generators in power plants in thermal power plant by platform construction, which
and process control in industrial fields. The PCS-9100 series provides various process controls for auxiliary generators
is designed based on the deep cooperation with a worldwide with highly control safety and stability.
well-know DCS manufacturing company and integrates NR’s
• The PCS-9100 series adopts distribution control platform
technical advantage in power plant and thermodynamic
from Honeywell, US.
measurement. It provides distributed control and centralized
operation, which makes the system flexible to configure and
easy to maintain.
Features
Functions • Integrated design method which is of high reliability and
availability.
• Control system for main generator: The PCS-9100 series
realizes integrated turbine, boiler and electric control which • High-tech application platform with integrated database and
are applicable for all kinds of power plants. It adopts many advanced application software package.
powerful functions incorporates data acquisition system, • System diagnostic and performance analysis capabilities.
modulating control system, sequence control system, furnace
safeguard supervisory system, electrical control system and • Providing remote diagnostic, digital graphic management
digital electric-hydraulic control system. system and complete security protection for both system and
devices.
• Process Displays
- Area Displays
- Overview / Trend (24points/12axes)/ Sequence Module /
Message
- Alarm (Summary / Annunciator)
• Unit Displays
- Trend / Alarm Summary
• Group Displays
- Group / Group trend (8points/2axes)/ Hourly Averages /
- Process Module Group
The PCS-9700 Electrical Control System is designed based the traditional centralized structure, and this makes the system
on a large scale of object-oriented software platform to realize more reliable, easier to extend and maintain.
hierarchical distributed control functions via Ethernet, including
protection, measurement and monitoring. The integrated design and practice in the PCS-9700
considerably reduce the cost of multiple stand-along devices.
The PCS-9700 series ECS system is a cost effective auxiliary Furthermore, direct connection between the bay-level devices
BCU of a DCS system for the power plant electrical system. It and the dual Ethernet networks can enhance reliability of the
provides high performance bay control for the auxiliary system ECS system.
in power plant, such as start-up/stand-by transformers, auxiliary
transformers, DC power supply system and other intelligent NR’s PCS-9700 series ECS system are fully compatible with
devices. The system adopts bay-oriented and object-oriented IEC61850 standard and they have been applied to many power
configuration with layered distributed architecture to replace plants and put into service successfully already.
The PCS-9700 Network Control System is a monitoring system whole system is designed elaborately which makes each device
designed for power system network of all voltage levels. It safe, reliable and easy for communication. By using component
provides variety monitoring functions including: technology, the PCS-9700 NCS realizes plug and play of
hardware and software function. Anti-interference capability
• Safety monitoring of electrical devices
ensures long-term safety operation of network devices under
• Complete telecontrol functions for power system dispatching, complex industrial environment. The software and hardware
incorporating remote metering, remote dispatching, remote platform of e network communication devices are composed
control and remote signal transmit. of innovative embedded processor, real-time multifunction
• Real-time monitoring of electrical parameters and other operating system and accurate synchronization system. The
electrical devices if necessary operation system of PCS-9700 NCS series is compatible with
Windows and UNIX system.
• AGC and AVC functions
• Power plant operation management and economic power
NR’s PCS-9700 NCS system is fully compatible with IEC61850
distribution between each generator set.
standard and they have been applied to many power plants and
put into service successfully already.
The PCS-9700 series NCS system adopts object-oriented
structure which is flexible to configure and easy to extend. The
• The excitation system is capable of continuously supplying • All control operations, detailed alarms and operating
ceiling voltage 1.8 times the generator rated field voltage for conditions are possible and activated by an operator panel
mounted in front door of the AVR (Automatic Voltage
15 seconds.
Regulator) cubicle.
PCS-9580
Static Var Compensator (SVC)
Benefits
• Increase power factor by dynamic reactive power
compensation.
• Eliminate voltage distortion caused by harmonics.
• Stabilize voltage and reduce voltage fluctuation and flicker.
• Balance three-phase load current and eliminate negative
sequence current.
• Increase operation safety of impact loading equipment and
its adjacent electrical equipment.
- Capacitor/filtering banks
Capacitor/filtering banks can supply sufficient capacitive reactive
power to power grid and filter harmful harmonics. It is composed
of capacitors and other auxiliary components such as filtering
reactors and filtering resistors.
• Interface to other control systems such as substation The Control Pulse(CP) will be converted to optic Firing
monitoring system, including: one communication manager Pulse (FP) by VCU and finally converted to electric FP by
(protocol converter) is arranged to transmit SVC alarm TCU to trigger thyristor. If the thyristor is not forward biased
information, protection information, important status or damaged, the control system will issue an alarm or stop
information and operation parameters to substation operating according to the signal sent from TCU.
monitoring system or remote dispatch system and receive
control and status information from substation monitoring The optic triggering system is a new reliable technology which
system and remote dispatch system; receive time uses light to trigger thyristor. It integrates forward overvoltage
comparison signal of the substation main GPS clock. The protection components, and thyristor management units are
specific configuration and functions are further described in used instead of thyristor control units.
the subsequent chapters.
• Thyristor Break-over Voltage Protection
Thyristor can be damaged by large crossed forward voltage
if it is not conducting during the system operation. Thus it is
Functions and Features essential to force the thyristor to conduct before reaching the
break-over voltage. The break over diode(BOD) is usually
• Optimized system design used to protection thyristor from being damaged by forward
overvoltage. However, a series connected BOD can cause a
NR has introduced RTDS, analog simulation system and
large deviation in break-over voltage. To solve this problem,
EMTDC in the design processes to study system voltage,
NR invented the unique protection circuit integrated in thyristor
system stability, active and reactive power distribution and
valves. It reduces the break-over voltage deviation to the
restraint harmonics so as to optimize SVC system design.
minimum value, and the break-over voltage can be fixed
manually to adapt to different types of thyristor.
The optimized filter groups can filter large amount of harmful
harmonics, provide fundamental frequency reactive power
• Water Cooling System
and minimize dynamic active losses.
NR’s SVC system uses the industrial-class hermetic water
cooling system with de-ionized water to cool valves. This
- The customized SVC system can analyse system power
patented cooling radiator features low thermal resistance and
quality to check injected harmonic current and filter
low water resistance. With its high reliability characteristic, water
resonance.
cooling systems have been applied to many industrial areas
such like aviation, power generation and HVDC transmission.
- The most optimized regulation mode will be selected based
on the actual situation of each installation place to gain the
• Reliable protection and control system
most effective voltage/reactive power regulation.
The protection and control of Static Var Compensator uses the
reliable software and hardware platform of HVDC control and
• Thyristor valve
protection system. The high integrated software platform uses
NR’s Thyristor Controlled Reactor(TCR) has advantages of
graphic programming and test tools to realize different control
compacted structures, less area occupation and light weight,
functions. The universal hardware platform is equipped with
which make valve installations and maintenance work much
multi-functional modular to achieve data acquisition, control and
easier. Assembling of valve is completed in factory before
monitoring functions.
shipping to ease on-site installation. Only the electrical
A static synchronous compensator(STATCOM) is a regulating • Suppressing of harmonics is effective even the capacity
device used on reactive AC power transmission in FACTS equipment is expanded.
application. It is based on a voltage-source converter and can • Filtering branch circuit can be removed.
act as either a source or sink of reactive AC power to a power
• Low voltage harmonics.
network. Large capacity inductors and capacitors are replaced
by high power electronics conductors. The STATCOM can • Small voltage aberration rate at interconnection point and
automatically generate inductive or capacitive power, and adjust small harmonic current injected to grid.
the amount of output reactive power considerding load property • The use of H bridge cascading STATCOM can greatly save
and system operation situations. land resource and bring significant economic benefits to
industrial end users.
NR’s STATCOM adopts multilevel modularization design
to solve the consistency problem of voltage stress for each NR's H bridge cascading STATCOM is composed of power
equipment in series connection arrangement. The use of units, reactors, starting units and control units. Control units
industrial grade components significantly reduces costs and provide the control of normal operation, running mode switching
improves device reliability. The multi-level output votlage has and data exchange with substation automation system.
low harmonic components, which can effectively reduce the
voltage distortion factor at interconnection point and decrease The H bridge cascading STATCOM provides the direct dynamic
the injecting harmonic current to grid. reactive power compensation for HV busbar. The compensation
is realized by the series cascading connection of full-controlled
The STATCOM is designed in H bridge cascading structure, converter bridges. The compensation characteristics are shown
bringing the following benefits to end users: in the following diagram.
• Low requirements of operation conditions to aviod complex
harmonic measurement.
The PCS-9570 series products are designed based on tens electronic transformers and the protection & control
of years' experences on the protection & control solutions system.
for tHVAC relay protection. The AC digital sampling based
• Embedded structure offering high integration
on electronic transformers effectively settles the interference
The UAPC platform developed by NR features good
problem on site during AC analog sampling of traditional series
performance, rapid processing and modular interface/card
compensators. The protection and control model based on
plug-ins and has been widely used in HVDC transmission
IEC61850 can implement sequence control of substation series
systems.
compensators to automatically switch-in or switch-over capacitor
banks with series compensators so as to optimize the power • Duplicated protection configuration
flows and improve transmission capacity in smart substations.
• Independent duplicated protection blocking circuits
The series products are mainly applicable to the capacitor series
compensators in the AC transmission lines of 66kV~1000kV. • Simple operation and easy maintenance
The traditional protection mode is applied to system from
operation interfaces to value settings to ease operation
and maintainance.
Features
• Electronic transformers and duplicated configuration of
• Safe and reliable primary system merging units (MU)
It is designed with safe and reliable coordination between The electronic transformers and duplicated configuration
the capacitor bank, MOV, spark gap, damping circuit, offer stronger anti-interference capability.
PCS-9563
PV Grid-Interconnection system
The grid side converter and the generator side converter are - Primary part
controlled by two control units. The grid side control unit is used
to maintain DC busbar voltage stability and ensure high quality • The primary part of converter system consists of power
input current waveform and unit power factor. The generator modules (the integrated power unit composed of IGBT
side control unit is used to controls the rotor current torque and its drive, protection, and heat dissipation accessories
and the excitation components of doubly fed motor to adjust its etc.), filtering system, temperature control system, pre-
active power and reactive power output, and tracks active power charging system, low voltage ride through system, and power
order and reactive power order, so that the doubly fed motor distribution system etc.
can run on the optimum power curve of wind turbine to realize • The power module consists of three groups of grid side
the maximum capture of wind power. power units and 3 groups of generator side power units
• The temperature control system monitors temperature and • Complete fault recording function conformed to IEEE
humidity of key parts inside the cabinet. It controls the cabinet COMTRADE format;
internal temperature and humidity within an acceptable
• High reliable and flexible integrated protection system;
range through heating, air-cooling heat dissipation, and
dehumidifying.. • Grid interconnection control strategy based on self-
adaptive positioning of rotor can realize “zero” impulse grid
• The pre-charging system is used to raise the DC voltage
synchronization;
of DC capacitor to certain amplitude prior to the startup
of converter, thereby reducing the current impulse during • Photo-electric encoder which adopts software reset mode
converter startup to the maximum extent. can improve the accuracy and reliability of motor rotation
speed acquisition;
• The low voltage system adopts active crowbar circuit. In
case of operation fault, line fault, or rotor high voltage, the • High voltage and low voltage ride through control strategy are
low voltage system can protection the power semiconductor used to guarantee the converter fault ride through capability;
devices at motor side in order to achieve low voltage ride
• Harmonics suppression control strategy and dead zone
through. Thus the converter system can supply current to the
compensation strategy are adopted to effectively ensure the
grid even in the case of grid fault.
quality of power delivered from converter to grid;
• The power distribution system provides uninterrupted power
• Compatible with various industrial fieldbus communication
supply for each active device of converter.
interfaces, such as CANopen and Profibus.
Architecture
Figure 1 shows a power stability control system composed of • Transmit data to Execution Stations & Master Stations
one master station, several sub-master stations and execution • Acquire data and drive control outputs
stations. Communications between master station and sub-
master stations are implemented by optical fibers. Up to 30 sub-
Execution Station:
stations can be connected to a master station. Each station has
one central unit and several bay units, which is called stability • Calculate local-scale control tactic tables
controller. • Transmit data to Sub-master Station
• Acquire data and execute tripping or close commands
Stability Controller
PCS-992 Stability Controllers are installed in substations/power
plants of the power gridis installed in dispatching centers to
Figure 1. The typical structure of power stability control system
Master Station
• Calculate system-scale control tactic tables
• Transmit data to Sub-master Stations & other Master
Stations
• Distribute tactic tables to Sub-master Stations (If online)
Sub-master Station:
• Calculate region-scale control tactic tables PCS-992 Stability Controller
• Discriminate system operation mode. • Perform control functions that are not related to system
operation modes such as transformers or lines overload
• Establish power transfer limits.
discrimination.
• Implement stability control tactics.
Features
• The controller is based on NR’s well established and proven
UAPC hardware platform with multi-processor architecture.
Functions The multi CPU technology supports parallel operating
simultaneously.
• Out-of-step discrimination.
- Quick stage of out-of-step. • The two independent data acquisition paths can prevent any
undesired trip caused by component failure. One works as a
- Slow stage of out-of-step.
fault detector and the other is designed for protection and its
• Protection zone restriction logic. Tripping outputs are supervised by the fault detector to
• Out-of-step protection.(78) prevent a mal-operation.
• VT circuit supervision (VTS) • Introducing measured impedance characteristic with perspic-
• CT circuit supervision (CTS) uous physical conception for out-of-step condition detection
• Voltage and current drift auto regulation. criterion.
• Pilot communication schemes with fiber, carrier or other • The relay provides GPS clock synchronization, including
channels. second pulse, minute pulse and IRIG-B synchronization.
• 2 optional Ethernet ports with IEC 61850 protocol. • The relay is compatible with IEC 61850-8-1 MMS, GOOSE
and IEC 61850-9-2 Sampling Value and provides the
• 2 RS-485 communication rear ports with IEC 60870-5-103
independent interfaces for station bus and process bus
protocol.
respectively.
• 1 RS-485 communication rear ports for clock synchroniza-
tion.
• 1 RS-232 communication rear ports or RS-485 for printer.
• 1 RS-232 communication faceplate port for testing and set-
ting.
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 200In
for half a cycle 250In
Burden <0.2VA/phase < 0.25VA/phase
Analog voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V 200V (Broken delta for residual voltage)
linear to 1~170V 1~233V
continuously 200V 220V
Thermal withstand capability 10s 260V 380V
1s 300V 420V
Burden < 0.20VA/phase @Un < 0.8VA/phase@Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Features
Functions • The device is built on DSP hardware platform with 14 bits
high accuracy A/D converter. DSP hardware performs data
• Out-of-step discrimination. acquisition, voltage, current and power-angle calculations,
and protection logic discrimination.
- Quick stage of out-of-step.
• Introducing measured impedance characteristic with
- Slow stage of out-of-step.
perspicuous physical conception for out-of-step condition
• Protection zone restriction detection criterion.
• Out-of-step protection.(78) • Flexible hardware/software configuration with modular
• VT circuit supervision (VTS) design structure.
• CT circuit supervision (CTS) • D a t a m e a s u r e m e n t , p r o t e c t i o n c a l c u l a t i o n , l o g i c
• Voltage and current drift auto regulation. discrimination, event recording and protection logic
calculation are processed within one sampling period.
• Self diagnostic test.
• Out-of-step discrimination for parallel lines.
• GPS clock synchronization.
• Fast tripping mode and slow tripping mode are provided for
• Fault Recorder.
different oscillation cycles.
• 128 event reports.
• The patented adaptive floating threshold is immune to
• High resolution oscillography of last 24 oscillograms. system unbalance and disturbance.
(Compatible with international COMTRADE format)
• The relay provides GPS clock synchronization, including
• Rear communication ports: 4 optional Ethernet ports or 2 RS- second pulse, minute pulse and IRIG-B synchronization.
485 conformed to IEC 60870-5-103 protocol, 1 RS-485 for
• The relay is compatible with IEC61850 and IEC 60870-5-
clock synchronization, 1 RS-232 or RS-485 for printer.
103.
• Front communication port: 1 RS-232 for testing and setting.
Technical data
Power Supply
Rated Voltage (Un) 24 Vdc, 30 Vdc, 48 Vdc, 64 Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Per IEC 60255-11:2008
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
Thermal continuously 120 V 120 V 200V
withstand 10s 200 V 200 V 350V
capability 1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class per IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Type test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
• Blocking element of frequency abnormality • 1 RS-232 communication rear ports or RS-485 for printer.
• Blocking element of dead bus • 1 RS-232 communication faceplate port for testing and set-
ting.
• Rear communication ports: Ethernet (Optional) or 2 RS-485 with
IEC60870-5-103 protocol, 1 RS-485 with clock synchronization,
1 RS-232 or RS-485 with printer. Features
• Front communication port: 1 RS-232 for testing and setting.
• The RCS-994 can accelerate load shedding to prevent power
system collapse when the system voltage or the frequency
Under-voltage Control Scheme decreases sharply and it will bring voltage back to the
• 4 basic stages from stage 1 to stage 4 operation range afterward.
• 2 special stage
• The power swing blocking function based on the analysis of
• 2 accelerated stages
df/dt and du/dt can prevent mal-operation caused by short-
• Blocking element of du/dt circuit fault or abnormal conditions of voltage and frequency.
• Blocking element of voltage abnormality
• The patented adaptive floating threshold method is adopted,
which is insensitive to system unbalance and disturbance.
Assistant function
The measuring element can get both high security and high
• VT circuit failure detection logic speed simultaneously.
• Zero drift adjustment of sampling data
• The relay provides GPS clock synchronization, including
• Self diagnostic test. second pulse, minute pulse, and IRIG-B synchronization.
• Online diagnostics of hardware circuit.
• The relay is compatible with multiple protocols- IEC61850
• Event Recorder including 64 binary input change reports and 64 and IEC 60870-5-103. The RCS-901 provides networking
self-supervision reports. interface such as RS485, RS232 and Ethernet port.
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 200In
for half a cycle 250In
Burden <0.2VA/phase < 0.25VA/phase
Analog voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V 200V (Broken delta for residual voltage)
linear to 1~170V 1~233V
continuously 200V 220V
Thermal withstand capability 10s 260V 380V
1s 300V 420V
Burden < 0.20VA/phase @Un < 0.8VA/phase@Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Communication
• 2 RS-485 communication rear ports conform to IEC 60870-5-
103 protocol
Functions • 1 RS-485 communication rear ports for clock synchronization
• 1 RS-232 or RS-485 (can be set by jumper) communication
Under-frequency Control Scheme rear ports for printer
• Four basic stages from stage 1 to stage 4
• 1 RS-232 communication faceplate port for testing and
• 2 special stage setting
• 2 accelerated stages • 2 optional Ethernet ports, IEC 61850, or IEC 60870-5-103
• Blocking element of df/dt over TCP/IP
• Blocking element of frequency abnormality
• Blocking element of dead bus
• Rear communication ports: Ethernet (Optional) or 2 RS-485 with Features
IEC60870-5-103 protocol, 1 RS-485 with clock synchronization,
• The RCS-994 can accelerate load shedding to prevent power
1 RS-232 or RS-485 with printer.
system collapse when the system voltage or the frequency
• Front communication port: 1 RS-232 for testing and setting. decreases sharply and it will bring voltage back to the
operation range afterward.
Under-voltage Control Scheme
• The power swing blocking function based on the analysis of
• 4 basic stages from stage 1 to stage 4
df/dt and du/dt can prevent mal-operation caused by short-
• 2 special stage circuit fault or abnormal conditions of voltage and frequency.
• 2 accelerated stages
• The patented adaptive floating threshold method is adopted,
• Blocking element of du/dt
which is insensitive to system unbalance and disturbance.
• Blocking element of voltage abnormality The measuring element can get both high security and high
speed simultaneously.
Assistant function
• The relay provides GPS clock synchronization, including
• VT circuit failure detection logic
second pulse, minute pulse, and IRIG-B synchronization.
• Zero drift adjustment of sampling data
• The relay is compatible with multiple protocols- IEC61850
• Self diagnostic test.
and IEC 60870-5-103. The RCS-901 provides networking
• Online diagnostics of hardware circuit. interface such as RS485, RS232 and Ethernet port.
AC Current Inputs
Rated frequency 50Hz, 60Hz, ±10%
Phase rotation ABC
Rated Current (In) 1A 5A
Linear to (non-offset AC current) 30In 30In
continuously 3In 3In
for 10s 30In 30In
Thermal withstand capability
for 1s 100In 100In
for half a cycle 250In 250In
Burden <0.2VA/phase @ In < 0.5VA/phase @ In
AC Voltage Inputs
Standard Per IEC 60255-6:1998
Rated Voltage (Un) 100V/√3, 110V/√3 100V, 110V 200V
linear to 100 V 173 V 230V
Thermal continuously 120 V 120 V 200V
withstand 10s 200 V 200 V 350V
capability 1s 250 V 250 V 400V
Burden <0.2 VA/phase @Un <0.5 VA/phase @Un <2.5 VA/phase @Un
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class per IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Communication Interfaces
Communication medium Parameters
Interfaces for communicating with RTU/SCADA
Port number 2
Baud rate 4800bps~57600bps
Transmission distance < 1000m@4800bps
RS-485 (EIA) Electrical Maximal capacity 32
Twisted Pair Screened twisted pair cable
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type ST
Baud rate 4800bps~57600bps
Transmission standard 100Base-FX,
Transmission distance <1500m
RS-485 (EIA) Optical(Optional)
Optical Fiber Type Multi-mode Fiber
Wavelength 850/820nm
Fiber size 62.5/125μm (core DIA/cladding DIA)
Protocol IEC60870-5-103:1997
Safety level Isolation to ELV level
Port number 2
Connector type RJ-45
Transmission rate 100Mbits/s
Electrical Transmission standard 100Base-TX
Transmission distance < 100m
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Port number 2
Connector type SC
Ethernet
Transmission Rate 100Mbits/s
Transmission standard 100Base-FX
Transmission distance < 1500m
Optical(optional) Optical Fiber Type Multi-mode or single-mode
853/1310nm for multi-mode
Wavelength
1310/1550nm for single-mode
Fiber size 62.5/125μm (core DIA/claddingDIA)
Protocol IEC60870-5-103:1997 or IEC61850
Safety level Isolation to ELV level
Rear interface connecting local HMI with personal computer via RCSPC software
Port number 1
Local HMI communication
Application
Download program of protection relay
RS-232 (EIA)
Baud rate 4800bps~57600bps
Connector type 9 pin D-type female connector
Safety level Isolation to ELV level
Interfaces connecting printer
Port number 1
Baud rate 4800 ~ 38400bps
RS-232 (EIA)
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Interfaces for clock synchronization
Port number 1
Transmission distance < 500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
PCS-996A
Phasor Measurement Unit
• Communication to PMUs
PCS-996B PMU for Generation
- Ponit-to-point optical fiber for real-time phasor data
• Time-tagged current/ voltage phasor measurement
- 10/100MBaseTx/Fx for transient record data
• RMS value, frequency, df/dt measurement - IEC 60044-8 & IEC 61850 / IEC 608705-103
• Distrubance & fault data record
• Communication to Remote Control Center
• Synchronized phasor via GPS time signal - 4 *10/100MBaseTx or 10/100BaseFx ports
• Measurement of generator source voltage, rotor angle - Via SONET/SDH network
- IEEE 1344 & IEEE C37.118 protocol
• Measurement of excitation system voltage, current & speed
• Up to 24 voltage/24 current inputs, 36 BIs & 4 optional BOs • Data Backup
• Dual communictions to PDC: 1*Point-to-Point optical fiber & - Up to 128 GB Non-Volatile memory
1*10/100BaseTx or 10/100BaseFx - Up to 14 days data
- Disturbance & Fault record data via LAN using IEC 61850
or IEC 60870-5-103
Figure1. Typically Architecture for Integration in WAMS
Integration to WAMS
The PCS-996 fully supports communications to Wide Area
Measurement System (WAMS) based on international
protocols(IEEE Std C37.118-2005, IEC 60870-5-103 and
IEC 61850). The measured vector quantities are transmitted
from PCS-996A to WAMS via communication network and
assembled for advanced supervision and analysis. It allows
direct comparison of phasor from various locations in the power
system.
Integration to PSCS
The measured vector quantities can be transmitted from PCS-
996A to Power Stability Control System (PSCS) for the stability
control. In case of imbalance between generation and load
or severe disturbance evolving power oscillations, PSCS cab
take fast and reliable emergency actions, such as generator
shut-down, load-shedding, to ensure the system stability for
defending power system against blackouts.
Figure 2. Typically Architecture for Integration in PSCS
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<30W (for conventional substation application)
Quiescent condition
<35W (for smart substation application)
Burden
<35W (for conventional substation application)
Operating condition
<40W (for smart substation application)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Analog voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V 200V (Broken delta for residual voltage)
linear to 1~170V 1~233V
continuously 200V 220V
Thermal withstand capability 10s 260V 380V
1s 300V 420V
Burden < 0.20VA/phase @Un < 0.8VA/phase@Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Housing color Silver grey
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
The DFR-MS is c om pos ed of m as ter s tation h u m a n - • Alarming: it checks the fault report, events and waveforms
machine interface(MHMI) and local station human-machine received from DRs
interface(LHMI). Functions of MHMI and LHMI mainly include:
• Analysis function: DFR-MS can call waveform files and
perform analysis using dedicated analysis tool;
Master station human-machine interface(MHMI)
• Parameters configuration: all parameters of DR in the whole • Remote control: the management system supports remote
system can be configured and uploaded to devices; control, remote time synchronization and remote reset.
Recording
• Slow recording @1 ~ 50Hz , for long term power quality
• Triggered recording @ 9600Hz, for short term transient monitoring
process.
• Extract recording @ 9600Hz, extract fault channels from all
• Continuous recording @1200Hz, for middle term dynamic channels of triggered records automatically, for information
process efficiency.
- Negative sequence over upper limit • 1 Ethernet interface used for FTP service of continuous
- Zero sequence over upper limit recording and real-time waveform display
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<30W (for conventional substation application)
Quiescent condition
<35W (for smart substation application)
Burden
<35W (for conventional substation application)
Operating condition
<40W (for smart substation application)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 200In
for half a cycle 250In
Burden <0.2VA/phase < 0.25VA/phase
Analog voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V 200V (Broken delta for residual voltage)
linear to 1~170V 1~233V
continuously 200V 220V
Thermal withstand capability 10s 260V 380V
1s 300V 420V
Burden < 0.20VA/phase @Un < 0.8VA/phase@Un
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Housing color Silver grey
Protection class : IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated Current (In) 1A 5A
Linear to 0.05In ~ 40In
continuously 4In
for 10s 30In
Thermal withstand capability
for 1s 200In
for half a cycle 250In
Burden <0.2VA/phase < 0.25VA/phase
Analog voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V 200V (Broken delta for residual voltage)
linear to 1~170V 1~233V
continuously 200V 220V
Thermal withstand capability 10s 260V 380V
1s 300V 420V
Burden < 0.20VA/phase @Un < 0.8VA/phase@Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting
Functions & control devices in power plants. The device adopts unit
architecture that hardware and software can be flexibly
Recording Functions assembled and upgraded in the future.
• Initiating recording based on AC voltage
- Phase voltage sudden change
- Positive-sequence voltage sudden change
• Initiating recording based on binary input
- Zero-sequence voltage sudden change
• Initiating recording based on system oscillation
• Initiating recording based on AC current
• Initiating recording manually
- Phases voltage sudden change
- Positive-sequence voltage sudden change • Initiating recording remotely
- Zero-sequence voltage sudden change • Continuous recording (24hours uninterrupted recording)
• Initiating recording based on AC voltage out-of-limit
Auxiliary Function
• Initiating recording based on AC current out-of-limit • Self diagnostic test
• Initiating recording based on positive-sequence and • Loss of DC power supply alarm
negative-sequence component out-of-limit
• Hardware circuit online detection
• Initiating recording based on DC sudden change or DC
component out-of-limit • Support IRIG-B time synchronization
• Initiating recording based on over-excitation out-of-limit • 1 RS-485 serial port used for GPS time synchronization
• Initiating recording based on reverse power out-of-limit • 1 RS-232 serial port used to test and configure device
• Initiating recording based on low-frequency overcurrent or • 1 Ethernet interface used for FTP service of continuous
zero-sequence voltage for startup/shutdown recording and real-time waveform display
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
<30W (for conventional substation application)
Quiescent condition
<35W (for smart substation application)
Burden
<35W (for conventional substation application)
Operating condition
<40W (for smart substation application)
Analog voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn±5Hz
Rated phase-to-phase voltage (Un) 100~130V 200V (Broken delta for residual voltage)
linear to 1~170V 1~233V
continuously 200V 220V
Thermal withstand capability 10s 260V 380V
1s 300V 420V
Burden < 0.20VA/phase @Un < 0.8VA/phase@Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
5A@250V AC 8A@380V AC
Continuous carry
5A@250V DC 8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
6A@3s 10A@3s
Short duration current [email protected] [email protected]
[email protected] [email protected]
0.6A@48VDC 0.7A@48VDC
Breaking capacity (L/R=40ms) 0.2A@110VDC 0.3A@110VDC
0.1A@220VDC 0.2A@220VDC
380V AC 380V AC
Maximal working voltage
250V DC 250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Housing color Silver grey
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
PCS-9000
Energy Management System
PCS-9000 energy management system (EMS) is a computer- database management, coordinated man-machine interactive
aided tool used by operators of electric utility grids to monitor, interface, transmission of network information, interprocess
control, and optimize the performance of generation and/or communication, system management and alarm service etc.
transmission system. It adopts advanced network management, It can be transplanted and distributed on various hardware
object-oriented database and visualized cross-platform platform structures. Each application function constructed on
technology. the basis of PCS-9000 ASP is a building block that can be
integrated with other functions or implemented separately.
The system operates based on the latest IEC61970 standard,
providing a unified application platform for large scale energy
management of power enterprises. The PCS-9000 energy Electric power applications based on ASP
management system includes SCADA, Automatic Generation PCS-9000 Energy Management System provides full
Control(AGC), Power Advanced Software(PAS), Dispatching series power system applications to improve power system
Training Simulator(DTS), Automatic Voltage Control(AVC), management level. Its modular functions can be easily
Wide Area Measurement System(WAMS), OMS(Operation customized to meet the demands of control centers. In addition,
the PCS-9000 energy management system is extensible for
Management System) and WEB applications. It can be
function upgrade to satisfy user demands in the future.
easily integrated with other systems conformed to IEC61970
standard to protect the existing investments and reduce internal PCS-9000 system typical configuration scheme is shown in
information and function redundancy. Figure 1. PCS-9000 series products include:
The PCS-9002 is a state-of-the-art Distribution Management • SCADA: It is responsible for data acquisition, monitoring
System(DMS) operating on IEC61970 and IEC61968 standard. and control, and issuing system alarms when abnormal
It features complete automation of dispatching, distribution, conditions occur.
operation and service through the management of distribution • DA: It's responsible for fault detection, fault locating, fault
network, thereby ensuring the reliable and economical operation clearance and recovery in the distribution network.
of distribution system.
• AM/FM/GIS: Automated Mapping/Facilities Management/
Geographic Information Management.
The PCS-9002 uses SCADA data as the base data and
adopts Geographic Information System(GIS) as the display • DJM: It manages the day to day management of power
platform, and integrates SCADA/DA, GIS and the Distribution distribution and provides complete automation of the work
Job Management System. It scientifically manages the process.
whole distribution system and enhances economic benefits • DPAS: It realizes the load forecasting, reactive power
by introducing the concept of integration of real-time data optimization, load flow calculation and power loss
acquisition, distribution automation and management, calculation.
and places emphasis on the application of distribution job
management and related system data interactions. The self-
developed and customized flexible working-flow management Features
platform substantially improves management efficiency, and
ensures that the system functions are tightly combined with the
• Comply with IEC 61970 and IEC 61968 standard
internal working flows of the power enterprise.
It adopts open architecture and integrated application
platform to meet the expandable requirements of distribution
functions.
System Structure
• Hardware-independent
The distribution management functions consist of SCADA, DA, The application of hardware-independent technology and
GIS, power distribution job management, video monitoring, middleware technology provides a convenient combination of
distribution power application software and so on. different computer platforms on which to build a distribution
management system.
PCS-9550
HVDC Control & Protection System
A well-designed control and protection system can maximally Control and Protection
exert the advantages of HVDC transmission technology in the
following aspects: System Structure
• Long distance bulk power transmission
A complete PCS-9550 HVDC control and protection system can
• Underground or underwater cables transmission be divided into the following sub-systems:
• Asynchronous interconnection of AC system
• Offshore transmission Interface with remote control center (e.g. state dispatching
center, provincial dispatching center and remote central control,)
• Multi-terminal systems
This sub-system consists of telecontrol workstations and
• Power delivery to large urban areas
Remote Terminal Units(RTUs) for point-to-point communication
with remote control centers.
NR's PCS-9550 HVDC control and protection system provides
steady, reliable, and efficient control and protection for various
types of HVDC transmission systems of different voltage levels. Operator control system
It is applicable to: Operator control system is so called SCADA system. It
• Classic UHVDC and HVDC transmission project consists of station LAN, operator workstations(OWS), engineer
workstations(EWS), SER terminals, system servers, station
• VSC-based HVDC transmission project
clock and etc. The operator control system is used as the
man-machine interface during HVDC operation which has the
The PCS-9550 HVDC control and protection system makes full
following functions:
use of its advantages and brings the biggest convenience to
new and retrofit HVDC transmission projects.
• Generate control pulse for converter valve For the redundant control system, one system is active and the
• Maintain the synchronization between control pulse and other is on hot standby. System self-supervision and automatic
commutation voltage switch-over functions are used to ensure that the relative
healthy system is active. Operators may also manually select
• Keep interval equal between control pulses
the system operating state.
• Deblock/block converter valve with smooth and stable
startup/shutdown
• Regulate trigger angle of converter valves within the - Performance and Features
designed range to satisfy the ordered amount of power/
current. • Fully digitalization - all complex control and protection
• Adjust converter transformer tap changers according to functions are realized by software precisely
the operation status of AC and DC system • Open-ended - based on well-proved and common
• Implement sequence control of HVDC system industrial standards
• High reliability
DC protection system • High integration level
DC protection system ensures the safe operation of whole • Easy to cooperate with converters in various techniques
HVDC system. It includes DC protection(PPR), DC filter • Visual programming and debugging tools with cross-
protection(DFP), converter transformer protection(CTP) and AC platform capability
filter protection(AFP).
• High-performance distributed system with the fastest
interrupt response time of 25us;
DC electronic CT
DC electronic CT is used in HVDC converter station to convert module etc, and thus it has good temperature stability and
the DC current and supply the signals to control and protection well performance on EMC;
devices. The DC electronic current transformer is composed • The air-core coil is wounded in equalized turns in reverse
of converter, air-core coil, remote-end module, optical insulator
directions, which has well performance on external field
and merging unit. The digital outputs of DC electronic CT is
interference;
transmitted by optical fibers.
• The optical fiber composite insulator (optical insulator) has
advantages of high reliability and small volume which make
- Features the CT easy for transportation and installation;
• The product solves the problems caused by high operating • The remote-end is powered by laser. The laser power can
temperature, component fault and abnormal optical be adjusted in real-time according to the operating situation
interface; of remote-end module;
• The current divider adopts the unique symmetrical wiring • The remote-end module has two independent analog
technology to eliminate the influence of external magnetic sampling circuits to perform duplicated sampling, real-time
interference on the output signals; comparison and verification, and self-check functions;
• It has high measurement accuracy (Class 0.2) and fast • The remote-end modules are extensible, and can be flexibly
response time(step response pickup time < 125us); combined with merging units to meet various application
demands of DC control & protection system;
• The product structure can eliminate the radiation problem of
squirrel-cage current divider and its impact on remote-end • The merging unit is operating based on IEC60044-8 or
TDM bus. It has good compatibility and system integration
capability;
- Features
MUX-2M/MUX-64
Interface Unit
MUX-2M and MUX-64 relay digital signal interface units are MUX-2M and MUX-64 can be installed in communication rooms
communication interfaces between RCS-900 series current near digital multiplexer communication devices. It connects with
differential protection relays, RCS-900 series permissive the multiplexer communication device via 75Ω or 120Ω coaxial
teleprotection relays, and RCS-900 series power system cable and connects with a protection relay by optical fiber.
stability control relays. Connections between MUX and relays
are implemented by optical fibers. MUX-2M and MUX-64 also
can be connected to multiplexers through electrical interface
with 2048kbit/s or 64kbit/s bit rate.
Technical data
Power Supply
Auxiliary Voltage -48V DC (0V grounded)
Operating Range -32VDC~63VDC
Nominal Burden 10W
Interface Specifications
Device MUX-64 MUX-2MC
Mechanical Specifications
Dimensions 482.6 mm (W) x 44.4 mm (H) x 229mm (G)
Enclosure Protection Per IEC60259:2001
IP40 for front panel
PCS-912/913 power line carrier transceiver uses transmission • Wide working scope with margin of 4dB~36dB.
lines as the channel medium to transmit blocking protection
• Operation of receiving circuit is immune to CPU failure. Thus
signals over long distances. Normally, it starts to send signals
the device mal-operation can be avoided since the blocking
only if it receives initiating commands from protection devices.
signals sent from offside transceiver will not be lost.
Thus it can be used with high voltage line protection to form the
high frequency blocking protection for 110kV~500kV system. • The interface module supports 24Vdc, 110Vdc and 220Vdc
binary inputs according to practical requirements.
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
Quiescent condition <30W
Burden
Operating condition <55W
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage (Un) 24V
Rated current 1.2mA
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permissive voltage 120%Un
Withstand 2000VAC
Other Electrical Specifications
Operating frequency range 40kHz ~ 400kHz
Center operating frequency (42 + 4n) kHz recommended, n=0,1...89
Transmission frequency error <10Hz
Estimated frequency error <10Hz
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6mm×177.0mm×291.0mm
Mounting Flush mounted
Trepanning dimensions (W×H) 450.0mm×179.0mm, M6 screw
Housing color Silver grey
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80…1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
CJX/CZX
Interposing Relay Set
Binary Inputs
Rated Voltage (Un) 110VDC 125VDC 220VDC 250VDC
Pickup voltage 70%Un
Dropout voltage 55%Un
Maximum permitted voltage 150V 150V 300V 300V
Withstand 2000Vac
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Making Capacity >1000W at L/R=40ms
Continuous carry 8A 5A
0.4A resistive 0.2A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.05A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 5ms/10ms 10ms/15ms
Dropout time (Typ/Max) 4ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations minimum 100,000 operations minimum
Durability
unloaded contact 10,000,000 operations minimum 10,000,000 operations minimum
Mechanical Specifications
Enclosure dimensions (W×H×D) 482.6×177×291 (unit: mm)
Trepanning dimensions (W×H) 450×179 (unit: mm), M6 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class per IEC60529:2001
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Type test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Technical data
Power Supply
Rated Voltage (Un) 110Vdc, 125Vdc, 220Vdc, 250Vdc
Variation (80% ~ 120%)Un
Ripple in the DC auxiliary voltage Max 15% of the DC value. Per IEC 60255-11:2008
Binary Inputs
Rated Voltage 110VDC 125VDC 220VDC 250VDC
Pickup voltage 55% ~ 70%Un
Dropoff voltage > 10% Un
Maximum continuous voltage
132V 150V 264V 300V
withstand
Insulation withstand 2000Vac
Binary Outputs
Item Output contact Signal contacts
Output model potential free contact
Max system voltage 250VAC/DC
Test voltage across open contact 1000VAC RMS for 1 minute
Read more on the web
388 read more on www.nrelect.com www.nrelect.com
Continuous carry 8A 8A
0.4A resistive 0.4A resistive
Breaking capacity at 250Vdc
0.2A inductive(L/R=40ms) 0.2A inductive(L/R=40ms)
Short duration current 50A for 200ms 50A for 200ms
Pickup time(Typ/Max) 10ms/15ms 10ms/15ms
Drop off time (Typ/Max) 8ms/10ms 8ms/10ms
Bounce time 1ms 1ms
loaded contact 100,000 operations 100,000 operations
Durability
unloaded contact 10,000,000 operations 10,000,000 operations
Mechanical Specifications
Enclosure dimensions (W×H×D) 35×177×189 (unit: mm)
Trepanning dimensions (W×H) 37×179 (unit: mm), M3 screw
Mounting Way Flush mounted
Housing material Aluminum
Housing color Silver grey
Protection class per IEC60529:2001
Front side IP51
Other sides IP30
Rear side, connection terminals IP20
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Relative humidity 5%~95%, without condensation
Type test
- Electromagnetic compatibility (EMC)
1MHz burst disturbance tests IEC60255-22-1:2007 (idt IEC61000-4-2:1995), Class III
- Common mode 2.5kV
- Differential mode 1.0kV
Electrostatic discharge tests IEC60255-22-2 :2008 (idt IEC 61000-4-2) Class IV
- For contact discharge 8.0kV
- For air discharge 15.0kV
Radio frequency interference tests IEC60255-22-3:2000 (idt IEC 61000-4-3:1995 ) class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC 61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us, 2kV, line to earth; 1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6:2001, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
IEC61000-4-8:2001, Class V
Power frequency magnetic field immunity 100A/m continuous
1000A/m for 1-3s
IEC61000-4-9:2001, Class V
Pulse magnetic field immunity 6.4/16 us
1000A/m for 3s
IEC61000-4-10:2001, Class V
Damped oscillatory magnetic field immunity
100kHz & 1MHz – 100A/m
- Mechanical tests
Vibration IEC60255-21-1:1988, Class I
Shock and bump IEC60255-21-2:1988, Class I
- Electrical tests
Dielectric tests IEC60255-5:2000, test voltage: 2kV, 50Hz, 1min
Impulse voltage tests IEC60255-5:2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50μs, source energy 0.5J
Insulation measurement IEC60255-5:2000, insulation resistance >100MΩ, 500Vdc
- Environmental tests
Dry heat test IEC60068-2-2:2007, Test Bd for 16 hours at +55°C
Dry cold test IEC60068-2-1:2007, Test Ad for 16 hours at -25°C
IEC60068-2-30:2005, Test Db for two (12+12 hours) cycles, 95%RH,
Damp heat test, cyclic
low temperature +25°C, high temperature +55°C
Read more on the web
www.nrelect.com read more on www.nrelect.com 389
RCS-9662
Auxiliary Relay Set
According to the different combinations of voltage parallel Type Paralleling module Switching
modules and switchover modules, five types of RCS-9662 are 9662A 4 0
defined as listed in the table below. configuration and busbar 9662B 0 4
voltage transformers. AC voltage switchover circuit is equipped 9662C 2 2
for application to substation with double busbar configuration 9662D 3 1
and busbar voltage transformers. 9662E 1 3
Technical data
Power Supply
Standard IEC 60255-11:2008
Auxiliary Voltage 250V, 220 V, 125V, 110 V,
Voltage Range -20%, +15%
Burden Quiescent condition <20W
Mechanical Specifications
Dimensions 150.4 mm (W) x 226.8 mm (D) x 296mm (H)
Flush Type Mounting Cutout Flush Type Mounting Cutout
Enclosure Protection Per IEC60259:2001
IP40 for front panel
Performance
Pickup Voltage of Relay 55%-65% nominal voltage
Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible
Introduction
NR provides various reliable state-of-the-art wiring terminals to • The whole series covers various conductor terminating modes:
satisfy different user requirements, including screw terminals, screw connection, weld connection, clamp connection and crimp
weld terminals, clamp terminals and crimp terminals. The connection to satisfy various requirements.
terminals provided by NR feature reliable performance, easy
operation and maintenance, good mechanical properties, high
electric properties, and strong resistance to environmental
conditions.
DL Series Screw Terminals for AC
Inputs
These terminals can be used on all protection and automation
equipment of NR. A series of high quality wiring terminals have DL series terminals are applicable to AC current/voltage inputs,
been developed using screw, crimp, and welded connection and can be used for RCS-900 series protection, RCS-9700
technologies, in combination with specified applications. series bay control unit, PCS-900 series protection among
others.
These terminals provide many various advantages, some of
them being:
Features
• Traditional screw type press-fit plug structural form
• Protective casing is optional, to improve its safe protection XH series terminals adopt a reliable welding technique which
performance features reliable connection, small connection resistance, and
life-long maintenance-free property. In addition the provision
of protective casing provides better and more reliable safety
performance as compared with other connectors.
JX Series Screw Terminals
for AC Inputs XH series terminals can be used for binary input/output, power
supply, and DC quantities input/output etc. These terminals
JX series terminals are used for AC current/voltage inputs, and are applicable to RCS-900 series protection, RCS-9600 series
applicable to RCS-9600 series protection, PCS-9600 series protection and RCS-9700 series bay control unit etc. 0.14-2.5
protection, and PCS-9720 series distribution automation unit mm² or AWG 26-14 cables can be connected, rated operating
etc. voltage is 600V, rated operating current is 5A, applicable
operating temperature range is -40°C-125°C, and contact
0.14 mm²-4.0 mm² or AWG 26-12 cables can be connected resistance between conductors is less than 2mΩ. Application in
with a rated operating voltage of 600V and rated operating electric power system can be satisfied.
current of 20A with the applicable operating temperature range
being between -40°C-125°C, and contact resistance between
conductors is less than 1mΩ. Effect on AC quantity measuring
precision is small and its application in electric power system
Features
can be realized. • Plugging/unplugging type terminals allow for card
replacements without removing/re-connecting wires
Internal view of XH weld terminal with wire XH weld terminal with wire
JX screw terminals JX screw terminal with wire • Wires are connected by soldering, which provide stable,
reliable, small resistance, and life-long maintenance-free
connections
XH series screw terminals are used for binary input/output, These terminals can adapt to severe environment conditions
power supply, and DC quantities input/output etc. These and can be used for binary inputs/outputs, power supply, and
terminals are applicable for RCS-900 8U/12U rack protection DC quantities input/output etc. These terminals are applicable to
and RCS-9600 series protection among others. RCS-900 4U rack protection and RCS-9700 series bay control
unit.
0.14-2.5 mm² or AWG 26-14 cables can be connected with a
rated operating voltage of 600V, rated operating current of 5A, 0.14-2.5 mm² or AWG 26-14 cables can be connected, with
with an applicable operating temperature range of -40°C-125°C, a rated operating voltage of 600V, rated operating current
and contact resistance between conductors is less than 3mΩ. is 5A and thee applicable operating temperature range is
Application in electric power system can be satisfied. -40°C-125°C, and contact resistance between conductors is
less than 4mΩ. Application in electric power system can be
XH series screw type terminals adopting balance wheel satisfied. To install these terminals a special connector crimping
clamping wiring mode and have the advantages of large hole tool shall be used.
position density, strong wiring capacity, front operation, and
good safe protection performance etc.
Features
• Front withdrawal plug form is adopted, providing for simple
structure and easy assembling.
XH screw terminal with wire • High density hole position wiring can be realized, providing
an outstanding additional advantage.
Special Tools Note: Adjusting knob of connector crimping tool can be used to
control final position of mouth, to ensure tightness of wire crimp
For installation and wire connection of XH series crimp connection.
connection terminals, special tools are needed including
assembler ZPQ-01, remover QXQ-03, and connector crimping • Assembling of Plug
tool YJQ-001. The connection ferrule after crimp connection is shown in
Fig.6. Normally to push it into the terminal at the wiring side an
assembler tool is not required.
In case the wire cross sectional area is less than 0.75 mm², as
shown in Fig.7, place assembler tool close to the connection
Fig. 1 Assembler ZPQ-01 Fig. 2 Remover QXQ-03 Fig. 3 Crimping tool YJQ-001 ferrule (Fig.6) and insert them together into the terminal. Later,
withdraw the assembler.
Example of Application
• Stripping of Wire Tip
Use stripper to remove insulation layer at tip of multi-strand
wire. Length of exposed conductor shall be ensured at about
Fig. 6 Connection cylinder after crimp Fig. 7 Guiding to feed
8mm. In case two wires need to be pressed into one hole,
the length of the exposed wire core shall be ensured at about
15mm. Exposed parts shall be combined and then about 8mm • Removal
of length shall be reserved for crimping. Remaining exposed In case a wire needs to be removed, as shown in Fig. 8, insert
length of wire core shall wrapped by hot shrink tube. Note that the remover into the hole about 5mm deep in the direction of
stripping of tip must not damage the wire core. mating face and pull the handels back to the end. Then slowly
push it forward till the wire comes out.
PCS - Explorer
Project Management Under the “Program Config” node, users can use the visualized
configuration to set device input, output, parameters, and
The PCS-Explorer can be used to manage the configurations configure variables. Double click the “Program Config” node; the
of PCS series device and applications of different operations of existing configurable plug-in modules and the subpages will be
project file in PCS-Explorer. displayed. Users also can create their own pages, then add new
elements, and use relevant editing tools to control the signals
- Operations of Project Files of elements. Moreover, logic programming can be realized to
The PCS-Explorer takes substation as a unit to manage configure customized logic functions under relevant pages (CPU
engineering projects. All PCS series devices in this substation module page or DSP module page).
are grouped in a project for configuration and management.
- Plug-in Modules
- Variable Database and Symbol Database Under the “Program Config” node, configurable plug-in modules
In a newly established or opened existing project file, for the first will be displayed. These plug-in modules are consistent with
click on any device nodes, PCS-Explorer will read the project actual hardware configuration. Generally speaking, module
symbol database automatically and analyze visible documents name is the combination of corresponding slot name and
to form the variable database module type, or the combination of corresponding slot name
and module function.
Offline Configuration
- Page Operations
The PCS-Explorer provides offline configuration function to Specific control rules of relevant signals and parameters of a
manage and control PCS series devices under offline mode, plug-in module are realized by its pages. Number of pages may
including basic information, hardware module, system functions be provided for one plug-in module. Users can operate in pages
and function groups. according to their requirements.
- Device Setup
Click “Device Config”→“Device Setup” node, and four labels
are displayed in the edit window. These labels are used to set
device information, configure hardware module, system level
options and function groups respectively.
The PCS-PC software kit is an auxiliary software designed to simplify the management of
NR’s PCS family products. It provides efficient functionality for device configuration and
commissioning including device setup, configuration & setting, programmable logic development,
test & commission, and fault analysis for PCS series devices. With an intuitive matrix structure,
the software offers easy-to-use configuration capabilities for I/O mapping and signal mapping.
Additionally, sampled values and signal statuses are monitored by the PCS-PC tool. It scans
and retrieves disturbance information for automatic report file generation. Waveform analysis is
integrated for post-fault diagnostic.
PCS-PC takes a substation as a management unit to configure, and is able to manage several
devices in the same substation. It is adaptive to both off-line mode and on-line mode. Under
offline mode, the software can fulfill functions configuration, I/O configuration, programmable
logic and modify settings. Under on-line mode, the software communicates with devices through
Etherne port, downloads program and config documents to devices, modify settings and views
realtime state of devices. Personal computer can connect to the PCS series device via the RJ45
interface in the front plate of the device. The main functions is listed in the table below.
Functions
Functions Offline Online
Modify Setting ● ●
View real-time state of device′s analog
values/binary signals ●
Display event recorder ●
Waveform analysis ●
Remote control ●
Upload/download files ●
Privilege management ● ●
System configuration ● ●
Functions configuration ●
LCD configuration ●
Programmable logic ●
Binary signals configuration ●
Reset LED ●
Time synchronization ●
Read device′s clock ●
Event report read ●
● ●
File download/upload ●
Authority management ● ●
- System Config
System config is used to setup the basic information of
deviced, including recording time, hardware configuration,
display mode and plug-in module configuration. Device
setting can be implemented online or offline.
- Function Config
Functions config can setup each protection function of
device(enable or disable), allowing users to select the
protection functions to be equipped to devices.
- Signal Config
Binary signal config enables users to setup the source and
the type of binary inputs, binary outputs, LED, GOOSE,
analog quantity and LED indicators.
- Setting Config
The software provides setting config function to modify
settings under off-line mode including value display, range,
unit and so on. Under off-line mode, users can modify and
print settings, export and import the setting file.
- LCD Editor
The software allows users to edit LCD main interface,
including display interface, analog quantity, switch, circuit
breaker and the related device type.
- Programmable Logic
The PCS-PC provides programmable logic function to
edit enable/disable protection functions and configure the
output contact of output relay, alarm signal and triggering
signal of recording.
The RCS-PC application software kit is developed for users to set, test and manage NR’s
RCS series products. It can communicate with RCS series protection devices and make the
commission test and management of NR’s relay. It offers full library of RCS series relays and
users can select the appropriate types according to the specific applications. The application
software simplifies commissioning with uploading and downloading of setting files, relay
configuration, event and fault recorder analysis, management of disturbance records, real-
time measurement visualization. It is used to read and modify settings, configure relays, view
sampled values, tripping report, change of binary input and device abnormality. Personal
computer can communicate with RCS series relays via RS-232 port or RJ-45 port and retrieve
messages from relays. The software is based on Windows NT 4.0, Windows 2000 or Windows
XP operating system.
If the communication is built, the type of relay will be displayed, and the title bar will also display
the type of relay and version of firmware.
- Report
Users can view various reports, including tripping report,
abnormality report and changes of binary input. They can be
saved as recorder files respectively. The waveform records
will be stored with the format of COMTRADE. They can be
displayed and analyzed by the integrated analysis tools. All
these reports can be printed via RCS-PC.
- Waveform Analysis
Users can read, view and analyze the recorded waveform from
the protection devices. The user can also save the wave files
- Firmware Downloading and open it later.
Users can download the newest firmware and check the current
version of firmware from manufacturer to update the device.
- Device Configuration
Users can configure the binary inputs/outputs, programmable
logics, LEDs via RCS-PC if the devices support.
- Signal reset
Users can reset all magnetic latched output relays and signal
relays via RCS-PC by clicking the “Signal reset” button.
- Clock Synchronization
Users can synchronize the clock of the device as the time of
• Build the single line diagram for the primary system of the
substation.
Funcitons
Create, save and edit SCL Files
The main interface includes the Menu Bar and Tool Bar, SCL
Browser Window, IED Selection Window and Property Window,
Through the SubNetwork configuration window, users can The Substation Configuration Window enables the specific
configure ConnectedAP, Address, GSE and SMV under one configuration of one certain Substation in the SCL file.
SubNetwork in the SCL file.
The SCL configuration tool supports the construction of
For each created ConnectedAP, SCL Configurator will single line diagram for the primary system of substation in
create a default Address configuration item, and meanwhile the graphical form, automatically generates the substation
the GSEControl and SampledValueControl under the model which conforms to the definition in IEC61850-6
AccessPoint will generate the corresponding GSE and SMV according to the single line diagram and sets the association
configuration items for each control block. of substation model with the logical node of IED, etc.
• IED Configuration