Burner
Burner
Burner
Multi-Burner Environments
by Willy Vandermeer
1
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
2
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
3
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
of the flame envelope or to control flame tem- tion process. In stable flames, the flame front
perature on low-NOx burners. It is brought in appears to be stationary. The flame moves
downstream of the secondary air. toward the burner-nozzle(s) at the same speed
that the fuel-air mixture leaves the burner. A
Figure 3: Oil register burner
variety of feed ranges exist in a wide range of
WINDBOX
burner designs. Common flame characteristics
AIR
REGISTER are as follows:
• Production of heat energy
THROAT
• Expansion of gases
OIL NOZZLE • By-product production.
• Radiation emission.
OIL
DIFUSER
• Ionization within the flame envelope.
GUN
Btu/lb Kcal/Kg
(Btu/Gal) (Kcal/L)
FUEL BURNED
FLAME FRONT FLAME ENVELOPE
Gross Net Gross Net
4
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
Figure 5: Schematic control diagram of automatic oil- vapor by application of heat at the flame-front.
fired unit, steam atomized
By atomizing the oil into millions of tiny droplets,
F.D. FAN
the exposed surface area is increased and the
oil can vaporize at its highest rate. For good
atomizing and vaporizing a large volume of air
must be mixed initially with the oil particles.
Mechanical atomization. Atomization with-
out the used of either air or steam is synony-
mous with pressure atomizing. The nozzle
consists of a system of slots tangential to a
OIL SUPPLY small inner whirl chamber followed by a small
orifice. When passing through the slots, the vol-
OIL RETURN
ume of liquid increases. The high velocity pre-
ATOMIZING
STEAM SUPPLY vailing in the whirl chamber tangentially imparts
CONDENSATE a centrifugal effect that forces the oil against the
RETURN
STEAM ATOMIZING
OIL BURNER walls of the nozzle. It passes through the ori-
fices in the nozzle tip and into the combustion
Large capacity oil burners use two steps to
chamber, fanning out into a cone shaped spray
combust the oil — atomizing and vaporization.
of very small particles.
Vaporization converts oil from the liquid to
IGNITER
BUNKER (SILO)
COAL BURNER
TO OTHER
BURNERS
BUNKER
SHUTOFF GATE
BURNER LINE,
FEEDER PURGE & COOLING
HOT AIR VALVE Motor FEEDER
PRIMARY
RAW FUEL
AIR GATE BURNER SHUTOFF
PRIMARY AIR VALVE(B)
HOT AIR
DAMPER SHUTOFF GATE
PRIMARY
AIR REGULATING PULVERIZER
TEMPERING
Motor DAMPER
AIR
PRIMARY
TEMPERING
AIR FAN
AIR DAMPER
SEAL
SUPPLY
5
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
Figure 7: Typical main burner fuel supply system for gas-fired, multi-burner boiler.
PSL B
SS
V
S S Q R
1
S
PI PI PSH PSL PI B
C
S SS
J
A PI
MAIN GAS D
SUPPLY T K
BURNERS
O B
SS
D
1
B
SS
To ignition system (see above)
6
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
7
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
Figure 9: Fuel supply system for gas fired, multi-burner boiler igniters.
C5
G G
C5
K S G G
PI
F
T IGNITERS
GAS (PERMANENTLY C5
SUPPLY INSTALLED)
G G
C5 Individual igniter atmospheric vent valve
F Igniter fuel control valve
G Individual igniter safety shutoff valve
K Pressure relief valve C5
S Fuel pressure gauge
T Manual shutoff valve G G
Figure 10: Front-fired boiler. the center of the of the furnace area. Tangen-
tially fired boilers have four burners per level,
and variations are in the burner decks.
8
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
into two groups — the combustion control sions can also occur in associated boiler
system and the burner management system. passes, and ducts that convey the combustible
The combustion control system regulates gases to the stack.
the furnace fuel and air inputs to maintain air-to- A number of conditions can arise in connec-
fuel ratio. This ratio must be within the limits tion with the burner’s operation to produce
required for continuous combustion and flame explosive conditions. The most common are:
stability throughout the operating range. 1. Momentary loss of flame at the burner due
The burner management system must be a to interrupted fuel or air supply, followed by
stand-alone system dedicated to boiler safety. It delayed ignition of the accumulated fuel-air
assists the operator in safe starting and stop- mixture.
ping of burners while preventing operator error. 2. Fuel leakage into an idle furnace followed
A burner management system (BMS) includes by ignition of the accumulated combustible
the following components. mixture by a spark (or other source of igni-
• Interlock system. tion).
• Fuel trip system. 3. Repeated unsuccessful attempts to light-off
• Master fuel trip system. burner(s) without appropriate purging. This
• Master fuel trip relay. results in ignition of the accumulated com-
• Flame monitoring and trip system. bustible mixture.
• Ignition subsystem. 4. The accumulation of an explosive mixture of
• Main burner subsystem. fuel and air. This happens as a result of loss
Figure 12: Opposed fired boiler. of flame or incomplete combustion at one or
more burners during normal operation, or
SUPER HEATERS during lighting of additional burners.
9
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
flames and respond to the presence or absence from fuel oil and powdered coal, and burner
of their targeted flame. This recognition occurs front-area “hazardous area classification.”
within a specified flame failure response time These situations require special attention to
(FFRT) without being influenced by extraneous each type of application with attention to prod-
signals radiating from neighboring burners or uct specification and enclosure ratings. Each
furnace background. The detectors are con- flame detection control is specifically designed
nected to associated controllers. In industrial to fulfill selected functions and the burner tech-
multi-burner environments, FSG detection may nician must customize to meet his particular
be located in extreme conditions of high ambi- application.
ent temperatures, vibrations, dirt, and moisture
Figure 13: Burner Management System interlock and logic for natural gas fired, multi-burner boiler (NFPA 8502)
The most important criteria in hardware the technician in selection of the correct control.
selection is determined by the application. Con- The most basic flame characteristics are:
trols with the appropriate features must be 1. Production of heat energy.
selected. The control must be able to monitor 2. Expansion of gases.
it’s targeted flame, regardless of adjacent burn- 3. By-product production.
ers or furnace conditions. Awareness of differ- 4. Radiation emission.
ent characteristics of flames can greatly assist 5. Ionization within the flame envelope.
10
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
Heat energy from a flame is not a good method Figure 14: Electron flow through ionization within the
flame envelope.
of flame detection. Sensors used to detect the
presence or absence of heat respond too
slowly. In addition, such a system requires
directly inserting a sensing device into the
flame. This method necessitates high mainte-
nance costs.
Expansion of gases created by the com-
bustion of fuel-air mixture can be detected and
used as a flame detection method. However, it
is not useful for main burner flame detection.
Because this system requires the detection of
minute changes in pressures at the burner noz- FLAME IONIZATION PRINCIPLE
zle, it requires tubing from the nozzle back to
Heat in the flame causes the molecules in and
delicate pressure measuring devices. They
around the flame envelope to collide with one
require high-maintenance to keep operational.
another. The force of the collision frees some of
Production of by-products. This is a reli- the outer electrons of the atoms forming the
able method of combustion detection, but, as molecules. This creates free electrons and pos-
with heat energy, response time is slow and itive ions, allowing a very small current to be
detecting individual flames in multi-burner fur- conducted through the flame. The whole pro-
naces is unlikely. cess is called Flame Ionization.
Emission or radiation and ionization Within the flame there is very low conductiv-
within the flame are the most commonly used ity and resistance can vary from 100,000 to
flame characteristics measured with flame safe- 100,000,000 ohms. Current conducted through
guard hardware. In multi-burner FSG systems, the flame (flame current) is generally in the
emission of radiation is the main flame detec- range of 2-4 micro amps.
tion method. Ionization, when used, is only
If two electrodes were placed in a flame as in
appropriate for gas-igniter flame detection.
Figure 14, and a voltage applied, a current
could be conducted between the two rods
(Flame Rods). Naturally the positively charged
ions would flow to the negatively charged rod.
In order to use this process to determine pres-
ence of flame and to prevent the potential haz-
ard of a high resistance short to ground
(effectively simulating flame signal), the flame
current is rectified. Generally referred to as a
Flame Rectification System, this is achieved
by placing a grounding electrode in the flame
11
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
which is several times (generally 4 times) larger will result in an AC type flame current which is
than the flame rod or electrode. An AC supply rejected by the FSG control. The large ground-
voltage is applied across the electrodes. In the ing electrode generally forms part of the burner
first half of the AC cycle, the flame rod is posi- fuel nozzle as shown in figure 15.
tive and the ground rod is negative. The posi- Flame rods are small diameter metal rods
tively charged ions will flow to the negatively supported by an insulator. The tip-end of the
charged grounding area. rod can project into the flame. They typically are
The large grounding area increases the made of Kanthol, a high temperature alloy
capacity to hold electrons. This results in a rela- capable of operating in temperatures of up to
tive high flame current flowing through the 2400 F (1300C). Other materials with higher -
flame during the first half cycle. temperature ratings, such as Globar (a ceramic
material) are also available.
Figure 15: Typical ignition gas burner assembly using
flame rectification detection system. Applications for flame rod, rectification type
flame detection in multi-burner applications are
FLAME generally found in the supervision of gas fired
ELECTRODE
igniter flames.
Requirements for successful applications
FLAME include:
GROUND
IGNITION • Gas burners only (premixed where possi-
ELECTRODE
ble).
FLAME
RETENTION • Adequate flame rod to grounding area pro-
NOZZLE portioning (4 to 1 minimum).
• Stable flame (no movement from flame(rod).
• Proper placement of flame rod in flame
(short as possible, yet adequate contact).
• Proper rectifying flame current and associ-
ated circuitry.
12
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
second to four seconds. 400 to 800 nanometers are visible to the human
Flames emit radiation along a wide band of eye. The blue visible light is towards the ultra-
the electromagnetic spectrum called the flame violet, and the red visible lights is toward the
spectrum. infra-red portion of the flame spectrum. Flame
detectors are sensitive within either ultra-violet,
This spectrum consists of ultra-violet, visi-
visible or infra-red radiation. Various aspects
ble, and infra-red radiation. Ultra-violet and
determine the proper selection of flame detec-
infra-red radiation are at the opposite extremes
tor type.
of the flame spectrum and only wavelengths of
+I(A)
+Imax
FLAME ROD “RECTIFIED” CURRENT
+Imax
-Imax >4
EARTH (ZERO) POTENTIAL
0 t
BURNER FRONTPLATE
-Imax
-I(A)
Figure 17 show the flame spectrum and Infra red is emitted at about ninety percent
each associated curve of commonly used fuels. of total radiation emitted by burner flames and
Ultra-violet (at about one percent) is the least is found mostly in the last 2/3 of the flame. Hot
available of the three types of radiation from a furnace parts (such as refractories) emit IR
flame. Generally, the first 1/3 of a burner flame radiation when above 1000°F.
is the main source of ultra-violet radiation. High
temperature flames emit high amounts of UV
ULTRA-VIOLET FLAME DETECTION
radiation. Both oil and gas flames radiate suffi- Flame scanners operating in UV wave-
cient UV for detection. Visible radiation length use an ultra-violet detection tube. In this
amounts to ten percent of total radiation and is type of system the flame is considered present
detectable by the human eye in the various col- when UV radiation is detected. Differentiation or
ors: discrimination between the targeted flame
• Blue with orange-yellow for gas flames and neighboring flames or background, is
• Bright yellow for oil and powdered coal achieved by discriminatory scanner sighting.
flames. This sees as little as possible of the background
13
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
and is then combined with signal sensitivity blindness is important to prevent stray light
adjust or threshold settings to tune out detection from sources other than the flame
unwanted signal at the detector’s controllers. spectrum. UV detection tubes are made with
UV detection tubes should be sensitive only in quartz, the tube is then sealed and filled with
the far UV wavelength range (200 to 300 nano- gas. They contain two electrodes connected to
meters) to be considered solar blind. Solar a source of AC voltage.
80 COAL GAS
60 REFRACTORY
AT 3000 F
40 REFRACTORY
AT 1000F
20
100 200 300 400 500 600 700 800 900 1000 1100 1200
2.8 3.8 WAVELENGTH IN NANOMETERS
3.2
14
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
Figure 18: Radiation sources as emitted from a gas Figure 19: Ultra violet radiation detection tube.
flame.
ELECTRODES
MAX 1/3 LENGTH OF FLAME
QUARTZ TUBE
15
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
flame intensity. When the flame disappears, the the tube. This can also result from over-heating
count zeros, except for very infrequent firings the tube, subjecting it to excessive voltages, or
inherent in this type of design to which the sys- subjecting it to excessive UV radiation for long
tem does not respond. periods of time.
UV flame detectors respond to UV sources Deteriorated tubes can operate in random
in a flame. However, is possible for the detector failure mode — sometimes firing continuously
to respond to other sources of UV radiation after having started and failing to quench, or fir-
such as: ing inconsistently and causing nuisance shut-
• Hot refractory (well above 2000 F) downs. Tubes can also fail, causing the tube to
• Spark ignition fire as soon as the normal operating current is
• Welding arcs applied (regardless of the presence of UV radi-
• Halogen light. ation).
Care should be taken to avoid picking up Flame safeguard systems will always pick-
unwanted signal from any of these sources at up faulty UV detecting tubes during start-up and
(or near) the burner front. no flame or signal should be present to cause
Ultra-violet detection tubes can deteriorate system lockout if signal from a bad tube hap-
due to degeneration of the special gas inside pens during flame-off conditions.
8 7 +HOT PULSE
SCANNER SUPPLY MULTIPLYING
CIRCUIT
LINE SUPPLY 120V
COMMON CIRCUIT COMMON +
If a tube starts to fail during normal operat- check system for a UV tube-type flame detec-
ing flame-on conditions, the bad tube would not tor, consists of an optical shutter placed directly
be recognized until a system re-start is initiated. in the path of the UV radiation from the tube.
To prevent this from happening, the scanner The shutter opens and closes continuously,
self-check systems were developed. A self- effecting blocking the UV radiation for a brief
16
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
period (0.25 to.75 seconds, depending on the Figure 21: Ultra-violet tube detector, AC current
operation principle.
design, but less than the FFRT).
The system drives the scanner self-check QUENCH
17
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
red radiation, together with visible light, ative to amplitude of radiation >400 nm. visible
accounts for about 99 percent of total flame infra-red region on the cell.
spectrum radiation (See Figure 18). IR and visi- Figure 22 shows the response of the PbS
ble light (400 nanometer wavelength and cell to radiation from a steady light source such
upward) do not effectively detect the presence as a DC flash light, and a flame which provides
or absence of flame. A boiler with multiple burn- a flickering type radiation. The cell responds by
ers and hot, glowing refractory contains an modulating, harmonized with the variations in
abundance of visible and IR radiation. Detect- radiation amplitudes given off by the combus-
ing the presence or absence of these would not tion process.
be a reliable method to detect the condition of
Not only do flames flicker in this way, the
the targeted flame.
flicker frequency is actually different within the
Figure 22: PbS cell response to radiation from steady zones of the flame.
light and from flame flicker.
Figure 18 shows the ultra-violet region of
RELATIVE RESISTANCE
the flame, nearest the nozzle, the ignition
100
zone, which has the least amplitude, but the
80
60
highest flame frequency. Therefore, a photode-
40 tector mounted on the burner-front, looking par-
20
allel with the fuel flow, has the best possible
0 TIME
view of the ignition zone of the targeted flame.
STEADY LIGHT FLAME
SOURCE FLICKER
Should this targeted flame disappear, it
would likely pick up radiation of lower frequency
Reliable detection of the targeted flame from either adjacent or opposed burner’s flame
requires the IR detector to distinguish between envelopes.
the modulating frequency of the radiation it Flame flicker frequency is noted in Hertz.
receives. IR radiates from a flame in many fre- Flicker frequencies in flames can be found from
quencies (Flame Flicker). As fuel ignites with 5 upwards to well over 200 Hz. Variations in
oxygen during the burning process it initiates higher or lower frequencies found in flames are
many small explosions. Each explosion emits dependent on a variety of functions in burner
light and IR radiation, giving the flame an design and type of fuel burned. Designs such
appearance of comparatively steady shape and as gun-type or ring-type produce flames with a
glow. wide range of frequencies. However, spud-type
The flame constantly moves - changing (gas) and low NOx burners do not. Fuel oils and
shape and brightness. The function of the pho- coal produce wide ranges of frequencies; gas
todetector is to monitor flame flicker to distin- (particularly low-NOx) burners do not.
guish between flame and other sources of The ability of the photodetector to detect
radiation. The photodetector most commonly flame flicker frequency can be adversely
used is the PbS (lead sulfide) photo resistor. affected by overpowering, low-frequency radia-
The PbS cell lowers its electrical resistance rel- tion from furnace background light or heat.
18
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
Strong sources of this low frequency radia- Figure 24: Example of typical flame flicker analysis for
flame “on” and flame “off” (background)
tion will have a saturation effect. Also called condition.
washout, saturation inhibits the cell’s ability to 100%
maintain a high enough electrical resistance
value. This renders it unable to monitor flame
flicker. Flame on
AMPLITUDE
Figure 23: PbS photodetector in saturation from
abundant low frequency radiation. Discrimination
Flame"on"
RELATIVE RESISTANCE
Background
100
80
"on" “off”
60 0 50 100 150 200Hz
40 Background Background FLAME FREQUENCY
20
0 The curves in Figure 24 indicate the relative
TIME
amplitude of this radiation at the corresponding
flame flicker frequency. The “flame on” curve
shows a relatively high amplitude in the 50 to
120 Hz range received from the ignition zone of
The flash-light in Figure 23 represents the the flame.
lower frequency IR-visible light radiation from The “flame off” (background) curve shows
furnace background, made up of adjacent or these 50 to 120 Hz frequencies at a much lower
opposed burner-flames, and the flame repre- amplitude. The cause of this difference is that
sents the ignition zone of the targeted flame. although the “flame off” condition receives
The furnace background radiation focused on nearly the same frequencies from adjacent
the detector drastically reduces its electrical flames in the background, they are further away
resistance. This leaves almost no room for the from the detector. Therefore, there is less
cell to respond to flame flicker modulation. amplitude. This difference in amplitude at
To minimize this saturation effect, sight the selected frequencies allows the flame detection
detector so that radiation from the ignition zone system to discriminate.
is maximized and radiation from furnace back- In a set-up such as this, where the detector
ground is minimized. This is sometimes impos- is sighted at the ignition zone of the targeted
sible because of burner design. flame, it is not uncommon to find that the lowest
Oil and coal flames have strong radiation in frequencies increase dramatically in a “flame
the visible wavelength and gas flames do not. off” condition. This happens because the igni-
When looking through a burner’s sight-glass it tion zone of the targeted flame “masks” the
is easy to confirm that oil and coal burn brightly, bright background low-frequency radiation
whereas gas flames tend to be more transpar- while the targeted flame is on. When the tar-
ent or dim. However, all fuels radiate profusely geted flame disappears, the background radia-
in the infra-red region of the flame spectrum. tion comes into full view is shown in the curve.
19
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
+HOT
1
4
DC/AC SUPPLY CIRCUIT
COMMON COMMON
20
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
Figure 26: Example of bandpass filter selectivity to flame Figure 27: Example of detector receiving radiation from
flicker frequency, to achieve maximum both targeted flame, and adjacent flame or
discrimination. background.
100%
Background Flame on
AMPLITUDE
Bandpass A Bandpass B
21
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
22
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
ground radiation.
• Ensuring pilot flame is detected only when
in proper position to light-off main flame.
• Minimizing excessive heat radiation from TILTING
MECHANISM
burner front.
• Minimizing electrical noise from burner-
front, particularly spark ignition sources.
• Protection from excessive furnace pres- Tilting burners control superheater tempera-
sures. tures by directing fuel-flow upwards (towards
• Hazardous area classification compliance. the superheater), or downward (away from the
• Materials and paint specifications. superheater).
Providing a clear view of the primary com-
bustion zone is influenced by the design of the
burner. Ideally, the detector is mounted in such
a way that the line of sight intersects the pri-
mary combustion zone at a slight angle (5-10°).
23
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
Figure 31: Two fiber optic scanner assemblies installed individual burner’s flame (provided the fuel
on tilting oil burner.
ignites before entering the fireball). A fiber optic
scanner assembly includes an objective lens,
FIBER OPTIC SCANNER
mounted near the interface of the windbox and
OIL GUN furnace area. The fiber optic bundle is enclosed
within a series of flexible stainless steel tubes
and brings the flame radiation to the detector
FIBER OPTIC SCANNER
within the scanner’s assembly, located outside
OIL GUN
DIFFUSER the windbox.
An inner carrier assembly containing the
FIBER OPTICS fiber optics is inserted into an outer carrier, The
Fiber optic scanners allow optimal viewing in scanner electronics assembly is them attached.
burners where movable vanes, air compart- The outer carrier assembly is permanently fas-
ments, or burner nozzles would obscure or tened to the burner front. (See Figures 31 and
move the target flame away from the line of 32). The extreme end of the outer carrier which
sight. In tangentially fired boilers, where individ- holds the fiber optic lens, is usually made of
ual burner flames tend to form fireballs, a fiber- stainless steel and welded to the burner front to
optic scanner can detect the presence of an allow the best possible viewing angle.
Figure 32: Cutaway view of fiber optic scanner assembly (shown without outer carrier).
The inner carrier assembly containing the fiber and lens should be protected from tempera-
optic bundle and lens assembly, can be tures in excess of 800F (430C). Optical field of
removed from the outer carrier for servicing. view is 13 square inches at 3 feet. (110 sq. cm
Fiber optics and lens are made of high tem- at 1.00 meter).
perature glass for infra-red use, and quartz Lenses are available to assist the user in
when used with UV detectors. The assembly viewing the primary combustion zone when
requires protection from over-heating, and this location of the lens-holder cannot be near
is done with purge-air. Volume required for enough to the burner nozzle. These lenses look
purge-air is from 4 to 15 SCFM (113 to 425 L/ at an angle (skew), allowing the primary com-
M), depending on the application. Fiber optics bustion zone to be viewed as opposed to view-
24
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
ing too far into the furnace area. If, due to tle as possible of adjacent flame or background
mounting limitations of the outer-carrier’s lens- radiation in the field of view.
holder, insufficient discrimination results, a 5 For example, if the situation shown in Fig-
degree or 9 degree skewed lens can be ure 34 is a side-view of a multi-burner, six over
installed. When using a skewed lens, the user six arrangement, then aiming the scanners as
can rotate the inner carrier assembly to find the shown would help eliminate unwanted signal.
primary combustion zone during commissioning The same viewing pattern would also be rele-
of the system. As the inner carrier assembly is vant to avoid unwanted signal from opposed
easily removable, the user can experiment with burner arrangements. In multiple-burner-level
various degrees in skewed lenses until a suit- arrangements, scanners mounted on the mid-
able lens has been found. dle row of burners would not be able to view
Figure 33: Fiber optic scanner assembly using skewed areas without background radiation. Many
lens to view primary combustion zone. burners do not allow freedom to provide angle
on the scanner’s sight. The only available scan-
STRAIGHT
LENS ner mounting may be on the burner-front (Fig-
FIBER OPTIC ASSEMBLY
ure 29) with only a straight-ahead view into the
furnace through the burner internals. In these
OIL BURNER
SKEWED
LENS
situations only flame detection systems with the
most advanced electronic discrimination capa-
bilities should be used.
DISCRIMINATION
Close attention to viewing angle during scanner
mounting will minimize view of adjacent
flames or background radiation. If possible, Elimination of unwanted signal by mechani-
the scanner should be mounted to include as lit- cally limiting the scanner’s view of adjacent
25
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
flames can be achieved while concentrating on system, steps must be taken to ensure that
the flame’s primary ignition zone. To do this, when the pilot is detected it will light off its main
install either an orifice in front of the detector, or burner’s flame under all conditions. For exam-
extend the detector’s sight-tube. Since viewing ple, if an optical detector is used for pilot flame
adjacent flames or background radiation cannot detection and the detector’s view is on axis
be avoided, then it is best to view as little of it as along the burner center, the system may detect
possible. the pilot even though the pilot flame is too far
back from the main flame nozzle to light off the
Figure 35: Effects on field of view by extending scanner’s
sight tube. main flame. Using a flame rectification system
(Figure 15) for the pilot burner (gas pilots only)
FIELD OF VIEW
= ANGLE OF VIEW would give greater control over the pilot flame’s
TG
2
=
D/2
L
=
D
2L
location when detected.
LENS Alternately, and in the use of oil fired pilot
1
D
2
burners, the way the pilot lights-off the main
CELL burner safely and reliably will be in the burner
designs.
L1
L2 Figure 36: Flame detector mounting arrangements.
HEAT INSULATING
Figure 35 shows how to calculate the effect of NIPPLE
26
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
ing/purge air connection. an ohm check from unit chassis to the nearest
• When heat radiation from burner front area proven earth ground. This reading should not
is extreme, other devices, such as water- exceed 1000 ohms. The chassis will be used to
cooled housings or additional heat-shields tie all suppression components to ground. This
may be required. makes it essential that it be noise-free. Next, it
See Figure 36 for common scanner mounting is necessary to assure that neutral is at, or
arrangements including common accessories. neat, ground potential. Verify this with a voltme-
ter check between neutral and ground. On the
ELECTRICAL NOISE
AC range, it should not be more than 50 milli-
Minimizing effects of electrical noise from volts. If it is greater than this amount, the sec-
the burner front area, particularly the spark igni- ondary of the AC transformer supplying the
tion sources is an important consideration dur- instrument should be checked by an electrician.
ing installation of flame detectors. When using All wires coming into or out of the microproces-
the non-metallic, heat insulating nipple (Figure sor based instrument can be classified into
36), the detector will also be effectively isolated three different categories.
from the burner front. Electrical noise is a varia- 1. Analog (i.e. 4-20 mA, T/C, RTD, V or mV
tion in frequency or voltage beyond the nor- DC).
mally expected range. It exists in the industrial 2. Relay or SSR outputs.
environment as RF (Radio Frequency) noise or 3. AC.
a short duration transient voltage spike.
Each of these must be isolated from each other
Noise can be carried by, or modified by AC and from any wires coming from devices. If they
or DC voltages. Therefore, any wire to a micro- need to be parallel with any other lines, then
processor-based instrument can potentially maintain a minimum 6-inch space between the
carry noise. The immunity to noise is controlled wires. Remember that the only wires that can
by the operating environment of the unit and the be run together in a bundle are those of the
amount of noise suppression nearby. Even with same category. If the wires must cross each
noise suppression, an instrument cannot over- other, do so at 90 degrees. This minimizes the
come noise unless it’s environment (i.e. loca- contact with other wires and reduces cross talk.
tion, wiring, and power) meets minimum Cross talk is the EMF (Electro Magnetic Flux)
installation guidelines. emitted by a wire as current passes through it.
Listed below are some of the common This EMF can be picked up by other wires run-
sources of severe noise: ning in the same bundle. Shielded cable is a
1. Ignition transformers single or multi-pair of insulated wires; with each
2. Arc welders pair wrapped in an un-insulated wire (shield)
3. Mechanical contact relays wrapped with foil, and all inside a cover of plas-
4. Solenoids tic insulation.
5. Motors Analog signals should be run with a
Earth ground must be attached to the unit’s shielded cable. Terminal lead length should be
chassis. To verify that it is earth ground, make as short as possible, keeping them protected by
27
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
the shielding. The shielding should be All fittings must be constructed with speci-
grounded at one end only. The preferred fied materials (ASME) according to the pres-
grounding location is the microprocessor based sures involved. Purge or cooling air is generally
unit since its chassis should be at ground not required in arrangements like these.
potential. Shielding helps eliminate RF and
EMF noise the wires may be exposed to.
HAZARDOUS AREA CLASSIFICATION
Detectors needing hazardous area classifica-
Figure 37: Installation details of flame detector
installation for high furnace pressure tion compliance must be mounted inside an
applications. enclosure of the appropriate NEMA or
HEAT INSULATING CENELEC rating.
NIPPLE
The enclosure in Figure 38 can be adapted
for use with fiber optic detectors. Alternately,
fiber optic assemblies can be used to locate the
SWIVEL
MOUNT detector-head outside the hazardous classified
area. Non-incendive detectors can be used in
lieu of the requirement for special enclosures,
when specifications allow.
BALL
VALVE
Figure 38: Cut-away view of flame detector mounted in
hazardous area enclosure.
high temperature glass for infra-red and quartz THREADED FOR ACCESS
TO DETECTOR
28
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
Figure 39: Basic electrical connections to controller greater than the compartor’s (fixed) threshold,
the control will energize its flame relay. If the
FLAME OFF(NC)
FLAME
flame signal drops below the flame relay’s
BMS
COMMON
threshold (or is absent) for a period longer than
RELAY
FLAME ON (NO) the FFRT, the flame relay will drop out. In the
SCANNER SIGNAL
above method, the drop-in and pull-out thresh-
old of the flame relay remains fixed and the
CONTROLLER'S SCANNER POWER (+) SCANNER adjustments allow the operator to manipulate
ELECTRONIC
COMPONENTS SCANNER NEUTRAL(-) the flame signal controlling the flame relay.
AND
CIRCUITRY For example, with a flame detector mounted
SCANNER SELF CHECK
on the burner-front and connected to its appro-
POWER (+) priate controller and with the targeted flame-off,
NEUTRAL (-)
POWER sensitivity set to maximum, the controller
receives a detector output signal value of 45%
PROTECTIVE GROUND
as displayed on the control or with separate
voltmeter connected. This would represent the
Figure 39 shows the most basic electrical con-
signal value of the background radiation. The
nections to a simplified schematic of a single
control’s flame relay pull-in value is likely to be
channel controller. The controller will operate
around a 30% value. The operator can now
the flame relay within a strategy based on its
adjust the sensitivity dial (or screwdriver adjust-
design. The most simple flame relay control
ment) to limit the detector output signal value to
strategy converts the flame detector’s output
0%, preventing the flame relay from switching
signal into current. The current operates the
on. When the targeted flame is turned on, the
flame relay and as long as this current is suffi-
controller may display a detector output signal
cient to hold-in the relay, the controller is signal-
value of say 60%, ample to energize the flame
ing a flame-on condition. When the detector
relay. At this stage, the operator could select an
reduces its output signal based on flame radia-
even lower sensitivity setting of, for example,
tion (targeted flame-off), the current to the
50%, to assure discrimination between the
flame relay is also reduced. If this occurs for a
presence of absence of the targeted flame.
period longer than the flame failure response
time (FFRT), the flame relay will drop out
(flame-off condition).
29
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
Figure 40: External connections to controller with dual detector inputs and option select feature.
MARGINAL ALARM RELAY FLAME RELAY AUXILIARY FLAME RELAY
SPDT DPDT
POWER
SHUTTER POWER (+)
SCANNER "A" MOV
SIGNAL
COMMON NEUTRAL (-)
POWER MOV
SHUTTER
SCANNER "B"
SIGNAL
PROTECTIVE GROUND
COMMON
30
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
When the flame signal becomes marginal, be an ultra-violet and the other an infra-red
approaching the flame relay drop-out setpoint type.
for longer than the allowable period, the mar- In more simplistic controllers, both input sig-
ginal alarm relay will pull-in, activating an exter- nals from the detectors (A + B) are used indis-
nal alarm device. The pull-in threshold of the criminately by the control. If strategy requires
marginal alarm relay is adjustable and should blocking one detector’s signal, then the use of
be set above the flame relay drop-out thresh- external relays would be required.
old. It should be set high enough to allow cor-
More sophisticated controllers with duall
rective action, but not too high for nuisance
flame detector inputs, are provided with an
trips.
option select feature (see figure 40). Using the
FAULT RELAY OPTION option select lets the operator remotely select
from a menu of scanner options: A only, B only,
Some controllers are equipped with a fault
A and B, A or B, A xor B, and A plus B. Each of
relay. The purpose of the fault relay is to
the scanner options are available during pro-
announce when the system does not respond
gramming of the setpoints when commissioning
to the flame detector’s or control amplifier self-
the system. The operator programs in the scan-
check function properly. Controllers without a
ner option into either of the control options.
fault relay, directly open the flame relay when a
Then, switching between control options, the
self-check failure is determined. Controllers
system selects the appropriate scanner option.
supplied with a fault relay, maintain the flame
With controllers such as this, the operator is
relay energized during a self-check failure, but
also allowed to program two complete setpoint
its fault relay will trip, energizing a timed alarm
parameters into either option. This allows flexi-
function in the BMS before a burner trip. This
bility in scanner logic selection and also control
allows the operator to remedy the fault before a
parameters in both control options.
burner trip is initiated. When this function is not
desired, the flame and fault relay can be wired TYPE OF CONTROLLER ENCLOSURE
in series.
Controllers are manufactured in various archi-
ANALOG OUTPUT tectural designs; panel-mount, base-mount,
DIN-rail, and rack-mount. Design selection is
Almost all controllers have an analog output for
dependent upon the application.
flame signal strength monitoring. The output
may be a mA type (0-20 or 4-20) or voltage (0, - PANEL MOUNT
3, or 0-10). When connected to an appropriate
Panel mount controllers (see Figure 41) mount
service test-meter a continuous readout of
directly in their control cabinet and are wired to
flame signal strength is provided.
the external wiring terminals. They are “one-
OPTION SELECT piece” construction. Advantages of this design
include relative ease of installation (no base,
Controllers often have provision for the connec-
rack, or DIN rail required). Access to wiring ter-
tion of two flame detectors. These detectors
minals for servicing is easy. A disadvantage is
can be different types. For example, one could
the panel-mount’s large footprint, especially
31
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
when multiple controllers must be housed in the base will also add to the controller’s total height
same cabinet. If, for example, twenty four con- dimension, possible requiring a deeper cabinet
trollers are required, cabinet space may be a for mounting the control. Base-mounted con-
problem. Panel mount controllers need to have trollers (depending on their NEMA or IP rating),
all wiring undone and redone when replacing may also be mounted external to control cabi-
the control. A base, or rack-mount control nets.
requires less work at this stage.
Figure 42: Single Channel “base mounted” controller
with LED signal strength indication.
Figure 41: Dual channel “panel mount” controller with
side-entry wiring terminals.
SELECTED
ALTERNATE
WIRINGTERMINALS
WIRINGTERMINALS
FLAME FLAME
DUALCHANNEL
CONTROLLER
DIN RAIL
Compact in design, DIN rail controllers are suit-
able when multiple units for a small space are
Simple panel mount applications might include needed. DIN-rail mounting allows flexibility in
burner-deck mounted operator control panels, combining controllers and associated power
one at each burner. With its relatively low pro- supplies on the same rail.
file, this installation in explosion-proof cabinets
Figure 43: DIN rail mounted controllers
suits this style control.
32
FLAME SAFEGUARD CONTROLS IN MULTI-BURNER ENVIRONMENTS
Figure 44: Programmable, single channel, “Rack Today’s microprocessor-based systems han-
Mounted” controllers in a half-rack.
dle both modulating and digital logic functions.
Future boilers, turbines, and furnaces will
require the design and installation of progres-
MONOVOLT
sively more sophisticated FSG controls. With
the large installed base of controls and the
CVP
Flame Relay Flame Relay V
Marginal Relay Marginal Relay
Scanner Option Scanner Option
Modify
Up Mdfy
Modify
Up Mdfy
need to upgrade equipment, this is an interest-
ing and exciting time to be involved in this
Next Enter Next Enter
Down Down
Help Help
Back Back
SUMMARY
Application of Flame Safeguard controls
should only be undertaken by individuals with
knowledge of the combustion process. A thor-
ough knowledge of control and instrumentation
is mandatory.
Understanding and solving application
problems involves:
1. A full understanding of the problem. All
objectives, including performance must be
clear. Safety is paramount to any applica-
tion. Difficulty in achieving strong and reli-
able flame signal cannot interfere with the
ultimate goal of reliably detecting the tar-
geted flame “on” and “off.”
2. Determining various alternative solutions to
the problem can present different advan-
tages and disadvantages. On-site testing of
equipment is often required, allowing the
user to test various types of detectors and
accessories.
3. Make the best selection based on the
results of the tests and assure that they are
implemented.
Flame Safeguard solutions require application
knowledge. Economic justification may influ-
ence decisions, but should not interfere with
appropriate solutions.
33