3x1Kw Geysers 3000 100% 3000: 1KW For Each Square or Part of A 100 Square

- The document provides information to calculate the maximum number of 1kW water heaters that can be installed given the specifications of a 10kVA transformer, floor area of 301m2, motors, heater, and lights. - Calculations show the maximum load on the transformer is 9500W and existing load is 6350W, leaving 3150W available. With each 1kW water heater using 4.545A, 3 heaters could be added within the circuit's capacity. - An alternative method using a table confirms adding 3 heaters brings the total load to 9350W, below the transformer maximum of 9500W.

Uploaded by

ShuaibSolomon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views

3x1Kw Geysers 3000 100% 3000: 1KW For Each Square or Part of A 100 Square

- The document provides information to calculate the maximum number of 1kW water heaters that can be installed given the specifications of a 10kVA transformer, floor area of 301m2, motors, heater, and lights. - Calculations show the maximum load on the transformer is 9500W and existing load is 6350W, leaving 3150W available. With each 1kW water heater using 4.545A, 3 heaters could be added within the circuit's capacity. - An alternative method using a table confirms adding 3 heaters brings the total load to 9350W, below the transformer maximum of 9500W.

Uploaded by

ShuaibSolomon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

3.

1 Calculate from the following information, the maximum amount of water heaters
of 1kW each that may be installed according to the regulations:
o 10kVa/220 v single phase transformer using a power factor of 0.95
o Floor area 301m²
o Two 0.75kW single phase motors
o One electric oil heater of 500w
o 20 lights

3.2 Test your answer by making use of any other alternative method.

KVA = KW x PF = 10000 x 0.95 = 9500

Floor area is 301 thus 0-100 = 5KW


100-200= 1
200-300= 1
300-400= 1 remember 1KW for each square or part of a 100 square
Thus 8 KW
Always do the calculation in a table format and in watts because otherwise you can
easily confuse yourself
Connected load Diversity Estimated load
factor
SSO (switch socket outlets) 8000 50% 4000
2x .75kw motors = 750x2 1500 100% 1500
1x oil heater 500 50% 250
20 lights x 60W ea 1200 50% 600
ToTAL 11200 6350

Transformer output 9500 – 6350 = 3150 watt still available


Now you can either redo the table method or do the amp calculations
Connected load Diversity Estimated load
factor
SSO (switch socket outlets) 8000 50% 4000
2x .75kw motors = 750x2 1500 100% 1500
1x oil heater 500 50% 250
20 lights x 60W ea 1200 50% 600
3x1Kw geysers 3000 100% 3000
ToTAL 14200 9350
Which is less than the transformer max load thus acceptable

9500 / 220 = 43.18A FLC (full load current) which we must not exceed
6350 / 220 = 28.86 amp load
14.316 A spare

1 x gey = 1000 / 220 = 4.545A for each heater


14.316 / 4.545 = 3.15 but you don’t get half a geyser thus 3 geysers can be added

6350 + 3000 = 9350 / 220 = 42.5 amp because a circuit breaker is design and
manufactured with 125% of the rated current a 40A circuit breaker can be used for the
main switch.
Student wrong methods used below
3.1 answer:

Total load :
o Socket outlets -Floor area 301 m² = (5 kw for first 100 m²) + (1kw for second
100m²) +( 1kw for part of third 100m²) TOTAL = 7kw x diversity of .5 =
3.5kw
o Motors = (.75kW x 2 ) = 1.5kW x diversity factor of 1 =1.5kW
o Electric oil heater = 0.5kW x diversity of .5 = .25kW
o 20 lights ( 20 x 60watts ) = 1200watts = 1.2kw x diversity of .5 = .6kW
o
o TOTAL LOAD ( 3.5kW+1.5kW+0.25kW+.6kW) = 5.85kW

Therefore total current required = 5.85kW / 220v = 5850 /220 = 26.6A

Max supply from transformer at full load (10000 *.95) /220 = 43.18 amps.

43.18 max load 8 90% = 38.86amps allowable.

Therefore remaining amperage is 38.86-26.6 = 12.26Amps.

Each heater requires: 1kw


Therefore amps required per is 1kw/220 1000/220= 4.54 amps x diversity factor of 1
= 4.54 Amps.

Therefore total amount of water heaters allowed is 12.26amps/4.54 amps = 2.7.

To check total load with two connected : 26.6amps + (4.54 x 2) = 35.68


To check total load with three connected 26.6amps + (4.53 x 3) = 40.19

Therefore to enable the transformer to be loaded at 90% max only two may be added.