RISH Master 3440 Digital Multifunction Instrument
RISH Master 3440 Digital Multifunction Instrument
RISH Master 3440 Digital Multifunction Instrument
Application:
Rish Master 3440 measures important electrical parameters in 3 phase and single
phase Network & replaces the multiple analog panel meters. It measures electrical
parameters like AC current, Voltage, frequency, active energy import & active energy
export, Current Demand, kW Demand, kVA Demand and Max Current Demand, Max
kW Demand and Max kVA Demand. The instrument has optional output as one pulse
output or two pulse output for energy measurement.
Product Features:
On site programmable PT/CT ratios:
It is possible to program primary of external potential Transformer (PT), primary of
external Current Transformer (CT) on site locally via front panel keys by entering into
Programming mode or remotely via MODBUS (RS485)
EMC Compatibility
Preliminary Data sheet subject to change without notice Compliance to International standard IEC 61326
1
RISH Master 3440 Digital Multifunction Instrument
Technical Specifications: Display update rate:
Input Voltage: Response time to step input
1 sec approx.
Nominal input voltage (AC RMS) Phase –Neutral 57.7 - 277V L-N Line-Line 100 -
480V L-L Applicable Standards:
Max continuous input voltage 120% of rated value EMC IEC 61326
Immunity IEC 61000-4-3. 10V/m min – Level
Input Current:
3 industrial low level
Nominal input current 1 or 5A AC RMS (programmable on site) Safety IEC 61010-1-2001 , Permanently
System CT primary values Std. values up to 4kA (1 or 5 Amp ) connected use
Max continuous input current 120% of rated value IP for water & dust IEC60529
Auxiliary Supply: Pollution degree: 2
Installation category: III
AC Auxiliary Supply 110 V AC -15% / +20% / 230 V AC -15% / +20% / High Voltage Test 2.2 kV AC, 50Hz for 1 minute
380 VAC-15% / +20 ,45 to 66 Hz between all electrical circuits
ACDC Auxiliary Supply 100V… 250 VAC DC
Environmental
VA Burden:
Operating temperature -10 to +55°C
Nominal input voltage burden < 0.2 VA approx. per phase
Storage temperature -20 to +65°C
Nominal input current burden < 0.6 VA approx. per phase
Relative humidity 0... 90% non condensing
AC Supply burden 4 VA
Warm up time Minimum 3 minute
Overload Withstand: Shock 15g in 3 planes
Voltage 2 x rated value for 1 second, repeated 10 times at Vibration 10... 55 Hz, 0.15mm amplitude
10 second intervals Enclosure IP54 (front face only)
Current 20x for 1 second, repeated 5 times at 5 min Ampere Hour:
Operating Measuring Ranges Default pulse rate CT secondary = 1A Max pulse rate
Voltage 5… 120% of rated value 3600 pulses/Ah *
Current 5 … 120% of rated value divisor CT secondary = 5A Max pulse rate
Frequency 40…70 Hz 720 pulses/Ah
Power Factor 0.5 Lag ... 1... 0.8 Lead Other Pulse rate
divisors
Reference conditions for Accuracy: 10 CT secondary = 1A Max pulse rate
Reference temperature 23°C +/- 2°C 3600 pulses/10Ah *
Input waveform Sinusoidal (distortion factor 0.005) CT secondary = 5A Max pulse rate
Input frequency 50 or 60 Hz ±2% 720 pulses/10Ah
Auxiliary supply voltage Rated Value ±1% 100 CT secondary = 1A Max pulse rate
Auxiliary supply frequency Rated Value ±1% 3600 pulses/100Ah *
Power Factor 0.866 lag….1….0.866 lead CT secondary = 5A Max pulse rate
720 pulses/100Ah
Accuracy: 1000 CT secondary = 1A Max pulse rate
Voltage ±0.5% of range (50... 100% of rated value) 3600 pulses/1000Ah *
Current ±0.5% of range (10... 100% of rated value) CT secondary = 5A Max pulse rate
Frequency 0.15% of mid frequency 720 pulses/1000Ah
Active Power ±0.5% of range (10... 100% of rated value) Pulse duration 60 ms, 100 ms or 200 ms
Re-Active Power ±0.5% of range (10... 100% of rated value) *No. of Pulses = Maximum Pulses
Apparent Power ±0.5% of range (10... 100% of rated value) CT Ratio
Active energy (kWh) 1% (IEC 62053-21) Active P.F. 0.866 lag... Where, CT Ratio = (CT primary/ CT Secondary)
1...0.866 lead
Limit Output Option:
Re Active energy (kVArh) 1 % ( I E C 62053-21) 0.866 lag... 1...0.866 lead
Apparent energy (kVAh) 1% Limit can be assigned to different measured parameters. It can be
Ampere Hour (kAh) 1% configured in one of the four modes given below.
Phase angle & Power Factor 1 % of range 1) Hi alarm & Energized Relay
Accuracy of Analog Output 1 % of Output end value 2) Hi alarm & De-energized Relay
Influence of Variations: 3) Lo alarm & Energized Relay
4) Lo alarm & De-energized Relay
Temperature coefficient :(for rated 0.025%/°°C for Voltage (50... 120% of rated
value value) and PT Secondary Ranges for Various Input Voltage:
range of use (0…50°C)) 0.05%/°°C for Current (10... 120% of rated value) Input Voltage PT Secondary Settable Range
110V L-L (63.5V L-N) 100V – 120V L-L (57V – 69V L-N)
230V L-L (133V L-N) 121V – 239V L-L (70V – 139V L-N)
Pulsed Output Option: 415V L-L (239.6V L-N) 240V – 480V L-L (140V – 277V L-N)
With user selectable Trip point, Hysteresis, Energizing delay and De-
Energy (can be programmed for different energy parameters energizing delay.
simultaneously):
RISH Master 3440 Digital Multifunction Instrument
Relay contact 1 NO + 1 NC
Switching Voltage & Current for Relay 240 VDC ,5 A
Default pulse rate 1 per Wh (up to 3600W), 1 per kWh (up to 3600kW), 1 per MWh (above 3600 kWh)
divisor
Other Pulse rate
divisors
10 1 per 10 Wh (up to 3600W), 1 per 10kWh (up to 3600kW), 1 per 10MWh (above 3600 kWh)
100 1 per 100Wh (up to 3600W), 1 per 100kWh (up to 3600kW), 1 per 100MWh (above 3600 kWh)
1000 1 per 1000Wh (up to 3600W), 1 per 1000kWh (up to 3600kW), 1 per 1000MWh (above 3600 kWh)
Pulse duration 60 ms, 100 ms or 200 ms
Above options are also applicable to Apparent & reactive Energy.
2
RISH Master 3440 Digital Multifunction Instrument
For 3 Phase 4 Wire Unbalanced Load
2 5 8 11 1 3 4 6 7 9 2 5 8 11 1 3 4 6 7 9
k I
k I
L1 L1 k
X L I X
L2 L2 K X
X
X K L X
L3 L3
XX X K LX X X
N N
for Direct operated meter for CT operated meter
2 5 8 1 3 7 9 2 5 8 1 3 7 9 2 11 1 3 2 11 1 3
k I
k I
L1 L1
L2 X K L K IX L1 L1
X L2 X X K L X
X X N N
L3 L3
K L
for Direct operated meter for CT operated meter for Direct operated meter for CT operated meter