ACS1000Water Manual English
ACS1000Water Manual English
ACS1000Water Manual English
315 to 5000 kW
400 to 6700 hp
User’s Manual
ACS 1000 Water-Cooled, 12-Pulse
Chapter 1 - Safety Instructions 1-1
Chapter 2 - Introduction 2-1
Chapter 3 - Design and Functional Description 3-1
Chapter 4 - I/O Interfaces and Application Macros 4-1
Chapter 5 - Parameter Viewing and Editing and Control
Panel Functions 5-1
Chapter 6 - Installation 6-1
Chapter 7 - Preparation for Commissioning 7-1
Chapter 8 - Operation 8-1
Chapter 9 - Preventive Maintenance 9-1
Chapter 10 - Trouble Shooting and Repair 10-1
Chapter 11 - Transportation, Storage, Disposal and
Recycling 11-1
Appendix A - Technical Data
Appendix B - Customer Specific Options
Appendix C - Quality Assurance
Appendix D - Applicable Codes and Standards
Appendix E - Layout and Mechanical Drawings
Appendix F - Wiring Diagrams
Appendix G - Part List and Spare Parts
Appendix H - Signal and Parameter Table
Appendix I - Inspection and Commissioning Record
Appendix K - Parameter Setting List
Appendix L - Subsupplier Data
Index
1.1 General
This chapter includes the safety instructions that must be complied with
when installing, operating and servicing the ACS 1000. The contents of
this chapter must therefore be read carefully before attempting any work
on, or with the unit.
The ACS 1000 User’s Manual is intended for the following three target
groups:
• Installation personnel
• Operators
• Maintenance personnel.
This manual is not intended for commissioning staff.
Operation The operator is mainly responsible for the operation of the ACS 1000
(starting and stopping the drive) using the control panel or a supervisory
control system.
1.1.3 Responsibilities
It is the owners responsibility to ensure that each person involved in the
installation, operation or maintenance of the ACS 1000 has received the
appropriate training or instructions and has thoroughly read and clearly
understood the safety instructions in this chapter.
Personnel involved in installing and servicing the ACS 1000 must observe
the relevant safety regulations and standards and the instructions given in
this manual.
The design and the specific safety features of the ACS 1000 allow safe
installation, operation and maintenance of the equipment. The ACS 1000
is equipped with the following safety features:
• Safety grounding isolator
• Electromechanical interlocking system; the safety grounding isolator
cannot be closed until the main circuit breaker is open and the DC link
capacitor is discharged down to a safe level.
• The doors of the medium voltage section cannot be opened as long
as the gounding isolator is not closed. Only the doors of the control
section can be opened during operation.
• Protection functions to prevent dangerous operating conditions and
damage to the converter.
• Protection functions for transformer, motor and other external equip-
ment.
Although the ACS 1000 is safe if all protection functions are operating,
some residual danger areas remain, if safety instructions are not
observed.
The ACS 1000 operates in a medium voltage environment usually
consisting of switch gear, power transformer, motor, cabling, driven
process and supervisory control system.
No threat arises from the interaction of these external components with the
ACS 1000. However, the safety concept for these and the overall process
are not part of the ACS 1000 safety concept.
Fan is coasting
Control section: down after
Danger from auxiliary shut-down
and external signal
voltages when front
door is open
Do not access the ACS 1000 or work on the motor or the power cables, if
the drive system is energized and not properly grounded!
After switching off the mains and after the motor has come to a stop, wait
approximately 5 minutes for the DC link capacitors to discharge. The light
GND.- ISOLATOR UNLOCKED must be on, before grounding the
ACS 1000.
Take appropriate measures when working on the ACS 1000, i.e deener-
gize and disconnect all external devices before work is started.
2.1 Overview
3.1.1 Converter
Overview The ACS 1000 is a medium voltage frequency converter for three phase
squirrel cage induction motors. Sophisticated microprocessor circuitry is
used for monitoring the motor electromagnetic status. These data and
Direct Torque Control enable state-of-the-art sensorless motor control.
The nearly sinusoidal converter output voltage makes the ACS 1000
ideally suitable for retrofit applications with existing standard induction
motors without the need for derating.
Input Circuit The ACS 1000 is equipped with a 12-pulse diode rectifier bridge (see
Figure 3-1) which is adequate for most supplying networks and the
harmonic requirements as demanded by standards such as IEEE 519.
The 3-phase AC line voltage is supplied to the rectifier bridges through the
3-winding converter transformer (see Figure 3-1). In order to obtain 12
pulse rectification, a 30° phase shift is necessary between the two
secondary windings of the transformer. Therefore one secondary is wye-
connected and the other is delta-connected.
The two fuseless rectifier bridges are connected in series, such, that the
DC voltages are added up. Therefore, the full DC bus current flows
through both bridges.
(Option)
NP M
Main circuit
breaker Converter
transformer
Fuseless Design The ACS 1000 features a patented design using the IGCT power semi-
conductor switching device for circuit protection instead of conventional
fuses.
The IGCT, which is placed between the DC link and the rectifier, can
directly isolate the inverter from the power supply side within
25 microseconds, making it 1000 times faster than the operational perfor-
mance of fuses.
The precharge resistors limit the current in the DC link when the converter
is energized. They are bypassed with the protection IGCTs as soon the DC
voltage reaches 79%. The main function of these protection IGCTs is to
open in case of a fault in order to prevent the rectifier to feed into the fault.
Common mode currents from the inverter can be limited with the optional
common mode choke (not shown in Figure 3-1) and damped with the
common mode damping resistor, if the transformer secondary cables
exceed a certain length (for details see Appendix A - Technical Data). The
common mode choke provides full reactance for the common mode
currents flowing through transformer secondary cables, DC link, output
filter and internal grounding bus of the converter. For the main DC current,
the choke forms practically no reactance thus enabling the main current to
pass unhindered.
Inverter Di/dt-chokes (not shown in Figure 3-1) are used in the inverter to protect
the inverter’s free wheeling diodes from excessive rates of current drop
during commutation.
Each leg of the 3-phase inverter bridge consists of a combination of 2
IGCTs for 3-level switching operation: the output is switched between
positive DC voltage, neutral point (NP) and negative DC voltage. Hence,
both the output voltage and the frequency can be controlled continuously
from zero to maximum, using Direct Torque Control.
Output Circuit At the converter output a LC sine filter with low pass charakteristic is used
for reducing the harmonic content of the output voltage. Current feedback
is used to actively control filter operation. The low pass frequency is
designed to be well below the lowest switching frequency used by the
inverter output stage. This greatly enhances the purity of both the voltage
and the current waveforms applied to the motor. With this filter, the voltage
waveform applied to the motor is nearly sinusoidal (see Figure 3-2). There-
fore, standard motors can be used at their nominal ratings. The filter also
eliminates all high dv/dt effects and thus voltage reflections in the motor
cables and stresses to the motor insulation are totally eliminated. Motor
bearing failures attributable to capacitively coupled high frequency current
are no longer an issue (the causal high frequency common mode voltage
is eliminated).
Control Equipment The control equipment is an integral part of the drive cabinet and provides
microprocessor based drive control and monitoring functions, supple-
mented with hardware and software protection features to safeguard
against faults and damages due to improper operating conditions and
equipment malfunction.
Mains
Rectifier
Speed controller +
acceleration compensator
Internal torque Torque Control Switch position
reference status signals commands
Torque DC bus
Torque Torque reference Optimum
comparator
reference controller pulse
Flux selector
Speed comparator
=
PID
reference Flux ~
Inverter
Actual torque status
ASIC
Flux Actual flux Switch
reference positions
controller
U Adaptive
U
f motor model
T f
Internal flux Output
f reference filter
Actual speed
DC bus voltage
Inverter current (4 measurements)
Filter current M
(3 measurements)
3~
5 Cooling
section
4 Converter section
ADCVI board
Current transformers
Clamp
resistors Rs
Batteries Ion exchange vessel
Motor starters and DC link Air-to-water heat
circuit breakers capacitor Cf exchanger
Aux. supply Filter reactor Lf Expansion vessel
transformer
Outlet for Ground isolator Rectifier stacks
cooling air supply Snubber
IOEC3 board capacitor Cr
IOEC4 board Common mode
(optional) choke Lcom
Cooling fan
Power terminals
Rectifier snubber
Main cooling pipe (feed) Cm, Fm (Varistor)
The cooling sytem consists of a water cooling circuit (Figure 3-7 a) and an
air cooling circuit (Figure 3-7 b). The main power components such as
rectifier, inverter, protection IGCTs, common mode and output filter reac-
tors are water-cooled. Filter capacitors, control section and other ancillary
components are air-cooled. The cooling unit is mounted in the cooling
section and is accessible while the ACS 1000 is running.
Main Cooling Circuit A centrifugal pump (a 2nd pump can be ordered optionally) circulates the
cooling water in the main circuit to the components to be cooled and back
to the water-to-water heat exchanger. The main cooling circuit is filled and
topped up through the make-up water valve which is part of the water
treatment circuit.
See Chapter 9 - Preventive Maintenance, Filling the Cooling Circuit, page
9-8 for the cooling water specification.
Water Treatment A portion of the main cooling water flow is directed through the water treat-
Circuit ment circuit equipped with ion exchanger, fine mechanical filter, air
removal facilities and expansion tank for maintaining constant static pres-
sure and providing storage volume for service water.
Raw Water Circuit The external raw water circuit is connected to the water-to-water heat
exchanger. Included in the circuit is a mechanical filter and a motor oper-
ated valve. The valve is opened or closed depending on the required
cooling capacity. A portion of the raw water is directed to an air-to-water-
cooler of the air cooling system.
See Chapter 6 - Installation, Raw Water Circuit, page 6-4 for the raw water
specification.
motor valve in the raw water circuit is closed or opened depending on the
temperature of the main cooling circuit.
If the ACS 1000 is stopped (the main circuit breaker is open, the auxiliary
voltage is switched on) the water conductivity increases after some time.
If the conductivity alarm level is reached, the pump is started automatically
to circulate the cooling water through the water treatment circuit.
.
3.5.1 General
This chapter provides information about the standard control, monitoring
and protection functions. For detailed information on parameter settings
for individual functions see Appendix H - Signal and Parameter Table.
The ACS 1000 is configured and customized by means of application
parameters. These parameters can be altered by the user, either using the
integrated CDP 312 control panel or a PC with the DriveWindow software
tool (see PC Tools, page 3-19).
Control and monitoring functions of the ACS 1000 can be activated by
setting parameters one by one or by invoking an application macro which
is optimized for a particular application. Therefore some of the functions
described in this chapter will be configured automatically if an application
macro is selected.
A description of the I/O boards and the application macros of the
ACS 1000 can be found in Chapter 4 - I/O Interfaces and Application
Macros.
Acceleration and The ACS 1000 provides two user-selectable acceleration and decelera-
Deceleration Ramps tion ramps. It is possible to adjust the acceleration/deceleration times
(0..1800 s) and select the ramp shape. Switching between the two ramps
can be controlled via a digital input.
The available ramp shape alternatives are:
Linear: Suitable for drives requiring long acceleration/deceleration where
S-curve ramping is not required.
S1: Suitable for short acc./dec. times. Motor
speed
S2: Suitable for medium acc./dec. times.
S1
S3: Suitable for long acc./dec. times. Linear
Accurate Speed The static speed control error is typically +0.1% (10 % of nominal slip) of
Control the motor nominal speed, which satisfies most industrial applications.
Auxiliary Ride Through The auxiliary ride through function guarantees correct fault indication and
proper trip sequencing in the event that the auxiliary power source feeding
the drive is lost. The function is activated by a parameter. During ride
through the power for the control circuits of the ACS 1000 is supplied by
internal batteries. The ride through time is limited to 1 sec.
Critical Speed The critical speed function is available for applications where certain motor
speeds or speed bands have to be avoided, for example, due to mechan-
ical resonance problems. Five different speeds or speed bands can be set.
Enhanced Flying Start This feature allows a rotating motor (e.g. a turbo-pump or a fan) to be
taken over by the ACS 1000. By means of the flying start function the
frequency of the motor is detected and the motor is started-up again by the
ACS 1000.
Flux Optimization Flux optimization of the ACS 1000 reduces the total energy consumption
and motor noise level when the drive operates below the nominal load.
The total efficiency (ACS 1000 and motor) can be improved by 1...10%,
depending on the load torque and speed.
Full Torque at Zero A motor fed by the ACS 1000 can develop short-term motor nominal
Speed torque at start-up without any pulse encoder or tachogenerator feedback.
This feature is essential for constant torque applications. However, for
long-term operation at zero speed a pulse encoder is required.
Motor ID Calculation Based on the nameplate data, all ACS 1000 internal motor control param-
eters will be automatically calculated. This procedure is usually performed
once during commissioning. However, the procedure can be repeated
whenever required (e.g. when the ACS 1000 will be hooked up to another
motor).
Power Loss Ride- If the incoming supply voltage is cut off, the ACS 1000 will continue to
Through operate in an active but non-torque producing mode by utilizing the kinetic
energy of the rotating motor and load. The ACS 1000 will be fully active as
long as the motor rotates and generates energy to the ACS 1000.
Speed Controller The speed controller has to be tuned during commissioning according to
Tuning the process requirements. It is possible to manually adjust the factory
default settings of all speed controller relevant parameters.
Automatic Restart The ACS 1000 can automatically reset itself after an undervoltage has
occurred.
If the automatic restart feature is activated and an undervoltage condition
occurs in the DC link, the programmable waiting time is started. If the
voltage recovers within the selected time, the fault will be reset automati-
cally and the converter resumes normal operation. If the waiting time has
elapsed and the voltage has not recovered, the converter is shut down.
Built-in PID Controller The software based PID Controller can be used to control process vari-
ables such as pressure, flow, or fluid level.
For details see Chapter 4 - I/O Interfaces and Application Macros, PID
Macro, page 4-19 .
External Control The ACS 1000 provides a control signal interface for two separate
Stations external control stations (EXT1 and EXT2). The active control station can
be changed via a digital input.
The control panel always overrides the other control signal sources when
switched to local mode.
For more information see Chapter 4 - I/O Interfaces and Application
Macros.
Local and Remote The ACS 1000 can receive operational commands via the control panel
Control and the pushbuttons on the front door or via remote control stations. The
local or remote control location is selected via the LOC/REM key on the
control panel. For details see Chapter 5 - Parameter Viewing and Editing
and Control Panel Functions.
Main Circuit Breaker All functions regarding the control of the main circuit breaker (opening,
Control closing, tripping, monitoring of feedback signals) are included in the
ACS 1000. Opening and closing commands can be given using the push-
buttons on the control section or they can be entered via external control
stations.
Parameter Lock The user can prevent unwanted parameter changes by activating the
Parameter Lock function.
Programmable Analog The analog outputs on each IOEC board are programmable.
Outputs
Depending on the setting of the corresponding parameters, the analog
output signals can represent for example:
• motor speed, process speed (scaled motor speed), output frequency,
output current, motor torque, motor power, DC bus voltage, output
voltage, application block output (process PID controller output),
active reference, reference deviation (difference between the
reference and the actual value of the process PID controller).
The selected analog output signals can be inverted and filtered. The
minimum signal level can be set to 0 mA, 4 mA or 10 mA.
Programmable Digital Four digital outputs on the IOEC 2 board can be programmed individually.
Outputs Each output has floating change-over contacts and can be allocated to an
internal binary control or status signal via parameter setting.
If the optional boards IOEC 3 and/or IOEC 4 are installed, a maximum of
12 additional digital outputs (6 on each board) are available.
Reference Signal The ACS 1000 offers several functions for processing the speed reference
Processing value.
• The reference value can be changed via two digital inputs: One
digital input increases the speed, the other decreases it. The active
reference is memorized in the control system.
• The ACS 1000 can form a reference out of two analog input signals
by using mathematical functions: Addition, Subtraction, Multiplica-
tion, Minimum selection, and Maximum selection.
If pre-defined constant speeds are selected, the actual speed reference is
overwritten (see also Constant Speeds, page 3-12).
The external reference can be scaled in such a way, that the signal
minimum and maximum values correspond to a speed other than the
nominal minimum and maximum speed limits.
Scalable Analog Inputs Each analog input can be adapted individually to the type and range of the
connected input signal:
• Signal type: voltage or current (selectable by DIP switches)
• Signal inversion: if a signal is inverted, the maximum input level corre-
sponds to the minimum signal value and vice versa
• Minimum level: 0 mA (0 V), 4 mA (2 V) or by input tuning function
(actual input value is read and set as minimum)
• Maximum level: 20 mA (10 V) or by input tuning function (actual input
value is read and set as maximum)
• Signal filtering time constant: adjustable between 0.01..10 s.
The offset of the analog inputs can be calibrated automatically or
manually.
3.5.4 Diagnostics
ACS 1000 Information The software version and the serial number of the ACS 1000 can be
displayed on the CDP 312 control panel.
Actual Signal Actual Signals are shown in parameter groups 1..5. The most significant
Monitoring ones are:
• ACS 1000 output frequency, current, voltage and power
• Motor speed and torque
• DC Link voltage
• Active control location (Local / External 1 / External 2)
• Reference values
• ACS 1000 inverter air temperature
• Operating time counter (h), kWh counter
• Digital I/O and analog I/O status
• PID controller actual values (if the PID Control Macro is selected).
For details on actual signals to be displayed see Chapter 5 - Parameter
Viewing and Editing and Control Panel Functions.
Fault History The Fault History contains information on the forty most recent faults
detected by the ACS 1000. Faults are displayed as text. For further details
see Chapter 5 - Parameter Viewing and Editing and Control Panel Func-
tions.
.
External Emergency The normally closed contacts of external emergency-off buttons can be
Off wired into the tripping loop.
External Motor An external motor protection relay can be connected to a pre-defined input
Protection of the ACS 1000. The input is integrated into the tripping loop by a
normally closed contact.
Line Unbalance A signal from a line unbalance protection relay can be monitored by wiring
Protection it into the tripping loop of the ACS 1000. If the signal is low the main circuit
breaker is tripped immediately.
Monitoring of Limit The values of several user selectable signals can be monitored for adjust-
Values able low and high limits.
The digital status of the active limit appears on the control panel display
and can also be allocated to a digital output.
Motor Stall The ACS 1000 protects the motor if a stall condition is detected. The stall
function can be enabled or disabled, the monitoring limits for stall
frequency (speed) and stall time can be set and the drive reaction on a
stall condition can be selected: alarm or shutdown.
Motor Winding The motor can be protected from overheating by activating the motor
Temperature winding temperature monitoring function.
The ACS 1000 standard solution offers three analog inputs for measuring
and monitoring the motor winding temperature.
Values for alarm and trip levels can be set.
Process Stop A process stop button or relay can be connected to a pre-defined input of
the ACS 1000. The actual process stop input must be closed during
normal operation. If the digital input opens, the drive control initiates a stop
command. The stop mode (ramp stop, stop at torque limit, or coast stop)
can be selected by a parameter. When the drive is stopped the main circuit
breaker is opened.
Underload Loss of motor load may indicate a process malfunction. ACS 1000
provides an underload function to protect the machinery and process in
such a serious fault condition. This monitoring function checks whether
the motor load is above the specified load curve. 5 different load curves
can be selected by the customer.
Undervoltage In order to detect a loss of the mains supply, the levels of the positive and
negative DC link voltage levels are monitored. If these voltage levels drop
below 70% of their nominal levels an undervoltage alarm is initiated and
power loss ride through is activated (provided it is selected). If the DC link
voltage levels drop below 65% of their nominal levels an undervoltage trip
is initiated.
Battery Test The back-up batteries are checked periodically by applying a known load
and by measuring the resulting voltage drop. If the charge of the batteries
is deficient, a fault message is displayed and either a normal stop or an
alarm is initiated.
Communication Fault Except for the measurement boards all communication links are realized
by DDCS (Distributed Drive Control System). If one of these links is
missing a trip is initiated.
Cooling Circuit The water temperature, the water pressure or the water conductivity of the
cooling water are monitored for alarm and trip levels. In addition, the status
of the cooling water pumps, the water level in the expansion vessel and
the auxiliary fan are monitored.
Charging Fault The intermediate DC link voltage is monitored while the DC link capacitors
are charged. If the voltage does not reach a certain level after a pre-set
time a trip will be initiated.
Ground Fault The current in the output filter ground leg is monitored and compared with
two thresholds. The first threshold is set to a fixed percentage of the peak
value of the nominal inverter current. The second threshold is adjustable
and compared with the RMS value of the ground current. If the ground
ID-Run Fault During commissioning an identification run has to be carried out. The
nominal data for identification of the system parameters have to be
entered. If incorrect values are used and therefore the system parameters
cannot be determined, a trip is initiated. In this case the identification run
has to be repeated, after the correct data have been entered.
Inverter Temperature To insure the inverter does not exceed normal temperature limits, the
current is monitored and limited to the maximum permitted level.
Measurement Loss On the ADCVI board (analog digital conversion for voltage and current)
analog signals are converted into digital signals. The digital signals are
then transmitted via PPCC (fiber-optic bus system) to the interface board
which is the main interface to the converter control.
To guarantee proper operation of the protection functions included in the
converter, the status of the communication is monitored on the interface
board. If a fault is detected a trip is initiated.
Motor Phase Loss The phase loss function monitors the status of the motor cable connec-
tions. The function is useful especially during motor starting: the
ACS 1000 detects if any of the motor phases are not connected and
refuses to start.
The phase loss function also monitors the motor connection status during
normal operation. The motor operating frequency must be above a
minimum level in order for this feature to function. Should a motor phase
loss be detected a trip is initiated.
Motor Overload The 3-phase RMS value of the motor current is monitored and compared
with three adjustable thresholds. A pickup delay for each threshold can
also be set. In case an overload is detected an alarm message will be
displayed and the converter will be shut down.
Operating System The operating system of the microprocessor board monitors different func-
tions within the control software and will initiate a trip if a malfunction is
detected. Such faults are displayed as “Control SW fault”. Should one of
these faults be initiated during operation, the system should be restarted.
Overcurrent The overcurrent trip limit for the ACS 1000 is 2.2 times the nominal
inverter rms current. If this level is exceeded a trip is initiated.
Overvoltage The levels of the positive and negative DC link voltage are monitored to
detect whether an improper overvoltage condition develops. If these
voltage levels rise above 130% of their nominal levels an overvoltage trip
is initiated. On rare occasions, a combination of conditions can result in
the motor entering a self excitation mode that can cause the DC link
voltage to continue to rise despite the fact that a trip has been imple-
mented. If this condition occurs and if the DC link voltage levels rise above
135% of their nominal levels, a second overvoltage trip is initiated that
causes the inner 6 IGCTs to be gated simultaneously such that the motor
windings are effectively shunted together. This eliminates the self excita-
tion voltage that is causing the DC link voltage to rise. To provide ultimate
reliability the second overvoltage trip is implemented both in software and
redundantly in hardware (140%).
Short Circuit in Rectifier A short circuit in the rectifier bridge is detected by monitoring the DC link
Bridge voltage. If a short circuit is detected a trip is initiated and the drive is
disconnected from the supply voltage (MCB opening time ≤100 ms).
Short Circuit in Inverter The inverter is monitored to ensure that a short circuit condition does not
exist. If a short circuit is detected a trip is initiated.
Supply Phase Loss If the voltage ripple in the intermediate dc link rises above a pre-set level,
a supply phase may be lost. A trip is initiated.
3.7.2 PC Tools
4.1 Overview
Swing frame
Electronic power
supply (EPS) board
IOEC 1
(standard)
IOEC 2
(standard)
Terminal block
X301
IOEC 3
(standard for
water-cooled
converters)
IOEC 4
(optional)
Stan Signal
I/O Signal Terminals Remarks
dard Inversion
Stan Signal
I/O Signal Terminals Remarks
dard Inversion
Stan Signal
I/O Signal Terminals Remarks
dard Inversion
DO 2.6 IOEC 2 Digital output to close the main circuit see par.
MCB ORD CLOSE X26/1-3 breaker, 21.05
pulse or maintained signal
DO 2.5 IOEC 2 Digital output to open the main circuit see par.
/MCB ORD OPEN X25/1-3 breaker, 21.05
pulse or maintained signal
Stan Signal
I/O Signal Terminals Remarks
dard Inversion
Stan Signal
I/O Signal Terminals Remarks
dard Inversion
Stan Signal
I/O Signal Terminals Remarks
dard Inversion
1
DI 3.8 IOEC 3 External signal from a motor vibration possible
VIBRATION SV ALARM X12/5-6 monitor for alarm indication
Stan Signal
I/O Signal Terminals Remarks
dard Inversion
Stan Signal
I/O Signal Terminal Remarks
dard Inversion
1
DI 3.13 X300 External signal from a supply voltage not
/SUPPL VOLT UNBALANCE X10-11 relay, possible
signal is active when low,
wired to tripping loop,
in case of trip:
- alarm is indicated
- main circuit breaker is tripped
Stan Signal
I/O Signal Terminal Remarks
dard Inversion
4.4.1 Overview
An application macro is a pre-programmed control software with specifi-
cally adapted parameter sets. Depending on the process, the appropriate
macro can be selected thus enabling a quick and easy start-up of the
ACS 1000.
All application macros have factory-set parameter values. These default
values can be left unchanged or they can be set individually according to
the needs by the ABB commissioning engineer. Ask the local ABB service
organization if more information is required.
The ACS 1000 can be operated using one of the following macros:
• Factory
• Speed Control
• Hand/Auto
• PID Control
• Sequential Control
• Torque Control
• Master/Follower
• User 1
• User 2
There are six digital inputs on IOEC board 2 marked STANDARD INPUT
which are assigned to the application macros. See Table 4-1. The function
of each digital input can change depending on the macro.
If I/Os are used which are not located on IOEC board 2 a reference to the
corresponding board is made.
Besides the standard and the macro specific I/Os, various optional I/Os
may be defined depending on the converter configuration. Refer to
Appendix B - Customer Specific Options for more details.
All other customer interface signals are the same for each application
macro. See also section Pre-defined I/O Signals, page 4-5.
The tables in the macro description only show the macro specific signal
allocations of digital and analog inputs. The digital outputs for status indi-
cations and for opening and closing the MCB as well as the analog outputs
are the same for all macros.
For detailed information on macro specific parameter settings see
Appendix H - Signal and Parameter Table, Chapter 3 - Default Parameter
Settings of Application Macros.
Suitable Applications The Factory Macro is the default-set macro. It covers most of the common
applications such as pumps, fans, conveyors and other industrial applica-
tions where constant speed is required.
Description All drive commands and reference settings can be given from the
CDP 312 control panel or from an external control station.
The control station is selected with the LOC/REM key on the control panel.
The control panel can be disabled by closing DI 1.8. The digital input can
be accessed via terminals X301:1 and X301:2.
In remote control the following default signal interface applies:
• The reference value is connected to AI 2.1.
• The start/stop command is wired to DI 2.1.
• The sense of rotation can be changed with DI 2.2. The default setting
is FORWARD. It can be changed to REVERSE either by setting
parameter 11.03 to REVERSE or via DI 2.2 if parameter 11.03 has
been set to REQUEST before.
• Three constant speeds can be selected via DI 2.5 and DI 2.6 when
the drive is in remote control.
• Two preset acceleration/deceleration ramps can be selected via
DI 2.4.
When the Factory Macro is active the drive is speed controlled.
Input
power 1 L -> 600.0 rpm 1
Ext. controls Status Running
MotSpeed 600.00 rpm
MotCurr 75.0 A
Input and Output The default I/O signals of the Factory Macro regarding opening/closing the
Signals MCB, starting/stopping the drive, speed, control location, reference and
actual values are shown in the following table. The corresponding para-
meters are listed as well. For further settings refer to Appendix H - Signal
and Parameter Table.
DI 2.7 IOEC 2 11.04 Pulse -> 1 = command for closing the main
REMOTE ORD MCB CLOSE X12/3-4 circuit breaker
Control Signal Diagram The control signal diagram of the Factory Macro in Figure 4-4 shows how
the control signals i.e. reference value, starting/stopping commands, MCB
opening/closing commands are interconnected in the application software
of the ACS 1000.
CONTROL
PANEL
REF
LOC
REM
START
START / STOP / DIRECTION
NOT SEL COMM.MODULE
LOCAL NOT USED START/STOP
STOP IOEC 2-DI 1,2
EXT1 REQUEST IOEC2-DI 8
KEYPAD REMOTE DIRECTION
FORWARD
COMM.MODULE EXT2 REVERSE
DIRECTION
NOT SEL
IOEC2-DI 1,2
11.03 16.01
KEYPAD
DIRECTION PROCESS STOP
COMM.MODULE EXT1
Suitable Applications The Speed Macro can be used for the same applications as the Factory
Macro. The only difference to the Factory Macro is that the motor control
parameters of the ACS 1000 will not be overwritten and set to 0 when the
macro is activated.
For further information see Factory Macro, page 4-11.
Suitable Applications The Hand/Auto Macro is suitable for applications where the speed has to
be controlled automatically by a process automation system and manually
by an external control panel. The active control station is selected via a
digital input.
The macro is also recommendable when two external control stations
exist from where the reference value can be set and the drive can be
started and stopped. The active control station for the reference value is
selected via a digital input.
Description Start/stop commands and reference settings can be given from the control
panel of the ACS 1000 or from one of two external control stations, EXT1
(Hand) or EXT2 (Auto) (see Figure 4-5).
The LOC/REM key on the control panel is used to enable the control panel
or the external control stations. The control panel can be disabled by
closing DI 1.8. The digital input can be accessed via terminals X301:1 and
X301:2.
The remote control station EXT1 or EXT2 is selected with DI 2.5.
The control signals of EXT1 (Hand) for starting and stopping are
connected to DI 2.1. Open/close commands for the MCB are wired to
DI 2.13 and DI 2.7. The reference value is connected to AI 2.1. The speed
reference value is given in rpm.
The commands from EXT 2 (Auto) for starting and stopping are connected
to DI 2.2 and for opening/closing the MCB to DI 2.3 and DI 2.4. The refer-
ence value is connected to AI 1.1. The analog input on IOEC 1 is acces-
sible through terminals X301:3 and 4. The speed reference value is given
as a percentage of the maximum speed of the drive (see parameters
12.07 and 12.08).
One constant speed can be selected through DI 2.6.
The drive is speed controlled when the Hand/Auto Macro is selected.
By default, the direction is fixed to FORWARD (see parameter 11.03).
Hand/Auto
Const.speed1 1 -> 600.0 rpm 1
Status Running
PLC MotSpeed 600.00 rpm
or
ext. controls
MotCurr 75.0 A
EXT2 (%) = Panel display in REMOTE:
Auto control Hand control: Reference is read from analog input AI 1.1.
M
3∼ Start/stop command is given through digital input DI 2.1.
Motor
Input and Output The default I/O signals of the Hand/Auto Macro regarding opening/closing
Signals the MCB, starting/stopping the drive, speed, control location, reference
and actual values are shown in the following table. The corresponding
parameters are listed as well. For further settings refer to Appendix H -
Signal and Parameter Table.
Control Signal Logic The control signal diagram of the Hand/Auto Macro in Figure 4-6 shows
how the control signals i.e. reference value, starting/stopping commands,
MCB opening/closing commands are interconnected in the application
software of the ACS 1000.
CONTROL
PANEL
REF
LOC
REM
START
START / STOP / DIRECTION
NOT SEL COMM.MODULE
LOCAL NOT USED START/STOP
STOP IOEC 2-DI 1
EXT1 REQUEST IOEC2-DI 8
KEYPAD REMOTE DIRECTION
FORWARD
COMM.MODULE EXT2 REVERSE
DIRECTION
NOT SEL
IOEC2-DI 6
11.03 16.01
KEYPAD
DIRECTION PROCESS STOP
COMM.MODULE IOEC 2-DI 5
Suitable applications The PID Macro is intended for the use with closed loop control systems
such as pressure control, level control and flow control. For example:
• Booster pumps of municipal water supply systems
• Automatic level control of water reservoirs
• Booster pumps of district heating systems
• Speed control of different types of material handling systems where
the material flow has to be regulated.
Reference
Level
trans-
ducer
Actual value
Pump
Description The PID Macro allows to control a process variable - such as pressure or
flow - by adjusting the speed of the motor accordingly.
Start/stop commands and reference settings can be given from the control
panel of the ACS 1000 or from an external control station.
The LOC/REM key on the control panel is used to enable the control panel
or the external control station. The control panel can be disabled by
closing DI 1.8. The digital input can be accessed via terminals X301:1 and
X301:2.
Parameter group 40 provides the necessary settings for the PID Macro.
The PID Macro requires IOEC board 4.
The process reference value is connected to AI 1.1. The customer termi-
nals for AI 1.1 are available on terminal block X301.
Two process feedback signals can be used. Actual value 1 is connected
to AI 4.1 and actual value 2 to AI 4.2. Parameter 40.06 provides the
settings regarding the number of feedback signals and their interconnec-
tion.
If the PID controller is part of a higher-level control system and the speed
of the motor is to be controlled directly, the speed reference value has to
be wired to AI 2.1.
The internal PID controller is bypassed if external control station EXT1 is
selected (DI 2.3 is open). Then the ACS 1000 no longer controls the
process variable but the speed of the motor directly.
Default actual signals shown on the control panel are MOTOR SPEED,
ACTUAL VALUE1 and CONTROL DEVIATION.
Input
power 0 L 1242.0 rpm I
MotSpeed 1242.0 rpm
Actual Value1 52.00 %
EXT1 CtrlDev 0.1 %
Ref.
Reference value, start/stop and direction
Actual value PT
PID EXT2
commands are given from the control panel. To
START/STOP(EXT1)
change to EXTERNAL , press the LOC REM key.
START/STOP(EXT2)
Speed/Process
(EXT1/EXT2)
0 52.1 % I
Run enable MotSpeed 1242.0 rpm
Const.speed Actual Value1 52.00 %
CtrlDev 0.1 %
External Control
Reference is read from analog input AI 1.1. Start/
EXT1 (rpm) = Direct speed control
M stop command is given through DI 2.1 when in
EXT2 (%) = Process PID control 3∼
direct speed control (EXT1) or through digital
Keypad Control
Motor input DI 2.6 when in Process Control (EXT2).
REF1 (rpm) = Direct speed control
REF2 (%) = Process PID control
Input and Output The default I/O signals of the PID Macro regarding opening/closing the
Signals MCB, starting/stopping the drive, speed, control location, reference and
actual values are shown in the following table. The corresponding para-
meters are listed as well. For further settings refer to Appendix H - Signal
and Parameter Table.
DI 2.7 IOEC 2 11.04 Pulse -> 1 = command for closing the main
REMOTE ORD MCB CLOSE X12/3-4 circuit breaker
Control Signal Diagram The control signal diagram of the PID Macro in Figure 4-8 shows how the
control signals i.e. reference value, starting/stopping commands, MCB
opening/closing commands are interconnected in the application software
of the ACS 1000.
CONTROL
PANEL
REF
LOC
REM
START
START / STOP / DIRECTION
NOT SEL COMM.MODULE
LOCAL NOT USED START/STOP
STOP IOEC 2-DI 1
EXT1 REQUEST IOEC2-DI 8
KEYPAD REMOTE DIRECTION
FORWARD
COMM.MODULE EXT2 REVERSE
DIRECTION
NOT SEL
IOEC2-DI 6
11.03 16.01
KEYPAD
DIRECTION PROCESS STOP
COMM.MODULE IOEC 2-DI 3
Suitable applications The Torque Macro is set up for processes requiring torque control, e.g.
mixers and slave drives. The torque reference comes from a process auto-
mation system or a control panel.
Description The Torque Macro is used in applications requiring torque control of the
motor. The settings for torque reference and torque reference handling
can be adjusted in parameter group 25 and 26 respectively.
The torque reference is given through AI 2.1 as a current signal. By
default, 0 mA correspond to 0% and 20 mA to 100% of the rated motor
torque.
The start and stop command is given through DI 2.1 and the sense of rota-
tion is changed by means of DI 2.2.
Changing from torque control to speed control is achieved by setting
DI 2.3 to low.
It is also possible to change the control location from external to local (i.e.
to control panel) by pressing the LOC/REM key. When LOCAL is selected
on the control panel the drive is speed controlled by default. If torque
control is required parameter 12.1 KEYPAD REF SELECT has to be
changed to REF2 (%). The control panel can be disabled by closing DI 1.8.
The digital input can be accessed via terminals X301:1 and X301:2.
Default settings for the display of the control panel are SPEED, TORQUE
and CONTROL LOCATION.
Input
0 L 1242.0 rpm I
power MotSpeed 1242.0 rpm
MotTorq 66.00 %
Ext. controls CtrlLoc LOCAL
EXT1 Reference value, start, stop and direction commands are given
Speed ref.
from the control panel. To change to EXTERNAL press LOC
Torque ref. EXT2 REM key.
0 50.0 % I
MotSpeed 1242.0 rpm
MotTorq 66.00 %
CtrlLoc EXT2
The reference value is read from AI 2.1 (if torque control is
M selected) or AI 1.1 (if speed control is selected). Start, stop and
3∼
direction commands are given through DI 2.1 and DI 2.2. Selec-
Motor tion between speed and torque control is done through DI 2.3.
External Control Keypad Control
EXT1 (rpm) = Speed control REF1 (rpm) = Speed control
EXT2 (%) = Torque control REF2 (%) = Torque control
Input and Output The default I/Os of the Torque Macro regarding opening/closing the MCB,
Signals starting/stopping the drive, speed, control location, reference and actual
values are shown in the following table. The corresponding parameters
are listed as well. For further settings refer to Appendix H - Signal and
Parameter Table.
DI 2.7 IOEC 2 11.04 Pulse -> 1 = command for closing the main
REMOTE ORD MCB CLOSE X12/3-4 circuit breaker
Control Signal Diagram The control signal diagram of the Torque Macro in Figure 4-10 shows how
the control signals i.e. reference value, starting/stopping commands, MCB
opening/closing commands are interconnected in the application software
of the ACS 1000.
REF. VALUE
CTRL. SIGNALS
DIG. INPUTS
IOEC 2: DI 1...6 EXT1 TORQUE CONTROL
DI 7,13 REMOTE LOOP
EXT2 26.01
LOCAL TORQ SELECTOR
REF2
(%)
CONTROL REF1
PANEL (rpm) 3.13
TORQ REF USED
REF
LOC
REM
START
START / STOP / DIRECTION
NOT SEL COMM.MODULE
LOCAL NOT USED START/STOP
STOP IOEC 2-DI 1,2
EXT1 REQUEST IOEC2-DI 8
KEYPAD REMOTE DIRECTION
FORWARD
COMM.MODULE EXT2 REVERSE
DIRECTION
NOT SEL
IOEC2-DI 1,2
11.03 16.01
KEYPAD
DIRECTION PROCESS STOP
COMM.MODULE IOEC 2-DI 3
Suitable Applications The Sequential Macro is typically used in processes requiring different
constant speed settings and/or different acceleration/deceleration settings
in addition to an adjustable speed reference value. Up to seven constant
speed settings and two acceleration/deceleration settings are possible.
The selection of the different settings can be automized by a process
control system or can be made manually by selector switches which are
connected to the corresponding digital inputs.
Description The macro offers seven preset constant speeds which can be activated by
DI 2.4, DI 2.5 and DI 2.6.
The parameters assigned for constant speed settings are in group 33.
Two preset acceleration/deceleration ramps are selectable via DI 2.3.
The start/stop command is connected to DI 2.1 and the sense of rotation
can be changed via DI 2.2.
An external speed reference value can be wired to AI 2.1. It is active if
DI 2.4, DI 2.5 and DI 2.6 are low.
Operational commands and reference value can also be given using the
control panel if set to local. The control panel can be disabled by closing
DI 1.8. The digital input can be accessed via terminals X301:1 and X301:2.
Default actual values shown on the Control Panel are FREQUENCY,
CURRENT and POWER.
Input Speed
power
Ext. controls Speed 3
Speed 2 Stop with
deceleration
ramp
Speed 1
Time
Accel1 Accel1 Accel2 Decel2
Start/Stop
Accel1/Decel1
M
3∼ Speed 1
Speed 2
Motor Accel2/Decel2
Speed 3
External control
EXT1 (rpm) = Speed control
EXT2 (%) = Speed control Example of sequential control using constant speeds and different
Keypad control acceleration and deceleration times.
REF1 (rpm) = Speed control
REF2 (%) = Speed control
Input and Output The default I/O signals of the Sequential Macro regarding opening/closing
Signals the MCB, starting/stopping the drive, speed, control location, reference
and actual values are shown in the following table. The corresponding
parameters are listed as well. For further settings refer to Appendix H -
Signal and Parameter Table.
Control Signal Diagram The control signal diagram of the Sequential Macro in Figure 4-12 shows
how the control signals i.e. reference value, starting/stopping commands,
CONTROL
PANEL
REF
LOC
REM
START
START / STOP / DIRECTION
NOT SEL COMM.MODULE
LOCAL NOT USED START/STOP
STOP IOEC 2-DI 1,2
EXT1 REQUEST IOEC2-DI 8
KEYPAD REMOTE DIRECTION
FORWARD
COMM.MODULE EXT2 REVERSE
DIRECTION
NOT SEL
IOEC2-DI 1,2
11.03 16.01
KEYPAD
DIRECTION PROCESS STOP
COMM.MODULE EXT1
Suitable Applications The Master/Follower Macro is designed for applications with several
ACS1000 drives where the motor shafts are coupled to each other by
gearing, chain, belt etc. Thanks to the Master/Follower Macro the load can
be evenly distributed between the drives or at some adjustable other ratio
which depends on the process.
Description All drive commands and reference settings for a master follower drive
configuration can be given from the control panel of the master drive or
from an external control station connected to the master drive. The
follower drive(s) receive(s) the control signals via a fibre-optic link from the
master drive.
Caution: Connect all control signals to the master drive only. The follower
Do not control the follower(s) with its (their) own control panel(s). Disable
the control panels of all follower drive(s) by setting parameter 16.02 PA-
RAMETER LOCK to LOCKED to prevent accidental use.
Do not control the follower through a fieldbus system.
Otherwise, the proper functioning of the drive system is affected and the
equipment may even be damaged.
Input Input
power power 1 L -> 600.0 rpm 1
Status Running
Ext. controls Drive link MotSpeed 600.00 rpm
MotCurr 75.0 A
Reference value, start/stop and direction commands are given from
the control panel. To change to EXTERNAL, press LOC REM key.
Input and Output The default I/O signals of the Master/Follower Macro regarding opening/
Signals closing the MCB, starting/stopping the drive, speed, control location, refer-
ence and actual values are shown in the following table. The corre-
sponding parameters are listed as well. For further settings refer to
Appendix H - Signal and Parameter Table.
The control signal diagrams of the master (see Figure 4-14) and of the
follower (see Figure 4-15) show how the control signals i.e. reference
value, starting/stopping commands, MCB opening/closing commands are
interconnected in the application software of the ACS 1000. Note that the
follower receives all control signals via the fibre-optic link (channel 2, fast
drive link) from the master.
REF. VALUE
CTRL. SIGNALS
DIG. INPUTS
IOEC 2: DI 1...6 EXT1 TORQUE CONTROL
DI 7,13 REMOTE LOOP
EXT2 26.01
LOCAL TORQ SELECTOR
REF2
(%)
CONTROL REF1
PANEL (rpm) 3.13
TORQ REF USED
REF
LOC
REM
START
START / STOP / DIRECTION
NOT SEL COMM.MODULE
LOCAL NOT USED START/STOP
STOP IOEC 2-DI 1,2
EXT1 REQUEST IOEC2-DI 8
KEYPAD REMOTE DIRECTION
FORWARD
COMM.MODULE EXT2 REVERSE
DIRECTION
NOT SEL
IOEC2-DI 1,2
11.03 16.01
KEYPAD
DIRECTION PROCESS STOP
COMM.MODULE EXT1
REF. VALUE
REF 2 * KEYPAD
REF SEL
REMOTE
REF2
KEYPAD (%)
CTRL. SIGNALS
LOCAL REF1
CH2
(rpm)
DDCS LINK
CONTROL
PANEL
REF
LOC
REM
START
START / STOP / DIRECTION
NOT SEL COMM.MODULE
LOCAL NOT USED START/STOP
STOP IOEC 2-DI 1,2
EXT1 REQUEST IOEC2-DI 8
KEYPAD REMOTE FORWARD DIRECTION
COMM.MODULE EXT2 REVERSE
DIRECTION
NOT SEL
IOEC2-DI 1,2
11.03 16.01
KEYPAD
DIRECTION PROCESS STOP
COMM.MODULE
5.1 Overview
This chapter describes the functions of the CDP 312 control panel and
offers instructions for setting parameters, calling up and displaying actual
values and messages and entering start and stop commands and setpoint
values.
Some parameter settings mentioned in this chapter may not match with
those in your drive. If in doubt, refer to Appendix H - Signal and Parameter
Table.
Running the ACS 1000, the motor and the equipment being driven with
incorrect data can result in improper operation, reduction in control accu-
racy and damage to equipment.
Only qualified and certified personnel shall operate the drive system, i.e.
personnel who are familiar with the machine and the operation of the drive
system and the hazards involved and who have aquired the certificate
after having attended the ABB service training.
Note: Before starting work on the ACS 1000 the general safety instruc-
tions in Chapter 1 - Safety Instructions must be read and understood.
The detachable control panel (see Figure 5-1) on the front door of the
converter is the basic user interface for:
• Viewing and setting parameters
• Monitoring the operation of the ACS 1000
Keypad Modes The CDP 312 control panel has the following keypad modes:
• Identification mode
• Actual Signal Display mode, selected by the ACT key
• Parameter mode, selected by the PAR key
• Function mode, selected by the FUNC key
• Drive Selection mode, selected by the DRIVE key.
Parameter Mode
Status line 1 L -> 600.0 rpm 0
Group number
and name
75 OPTION MODULES PAR
Group selection
Parameter Number 01 IOEC3 OptionBoard Fast value change
and name
Parameter value YES Parameter selection
Slow value change
Enter change mode
ENTER Accept new value
Function Mode
Status line 1 L -> 600.0 rpm 0
Selectable UPLOAD <= <= FUNC Row selection
functions
DOWNLOAD => =>
CONTRAST 4 ENTER Function start
Figure 5-2 Control Panel Display and Function of Control Panel Keys
LOC
REM
Keypad / external control Forward Start
RESET
Fault reset Reverse Stop
REF
Setpoint setting function
CDP312 PANEL
........
ID-NUMBER 1
After another few seconds, the display changes to the Actual Signal
Display mode.
When in Actual Signal Display mode, the fast UP/DOWN keys allow to
toggle between Actual Signal Display and Fault History Display.
4. to select a parameter
group 1 L -> 550.0 rpm 0
2 ACTUAL SIGNALS
01 ControlMode
SPEED-CTRL
Motor Parameters Parameter values which are characteristic for the motor in use are deter-
mined automatically (identification run) and cannot be changed by the
user.
Start-up Parameters The start-up parameters (parameter group 99), which comprise settings
for the control-panel language, the motor nominal data, the drive ID
number and the application macros must be determined and entered for
each drive.
Caution: If wrong parameter values are set, the proper functioning of the
! drive system can be affected and the equipment may even be damaged.
Do not change any parameter if the meaning of the parameter and the
effects of the change are not fully understood.
Selecting Parameters The Parameter mode is used to check and change the ACS 1000 param-
eters. When this mode is entered for the first time after the auxiliary
voltage of the drive has been switched on, the display will show the first
parameter of parameter group 11. The next time, the Parameter mode is
entered, the previously selected parameter is shown.
** Warning **
Write Access Denied
Parameter Setting
Not Possible
2. to select a different
group 1 L -> 550.0 rpm 0
75 OPTION MODULES
01 IOEC3 OptionBoard
YES
3. to select a parameter
1 L -> 550.0 rpm 0
75 OPTION MODULES
02 IOEC4 OptionBoard
NO
Setting the Contrast In the ACS 1000 the Function mode is used to set the contrast of the
display.
Table 5-6 Setting the Contrast of the Panel Display
2. to select a function (a
blinking cursor indicates 1 L -> 0.0 rpm 0
the selected function) UPLOAD <= <=
DOWNLOAD => =>
CONTRAST 4
Local / Remote Control The ACS 1000 can receive operational commands via the control panel
and the pushbuttons on the front door or via remote control stations. The
local or remote control location is selected via the LOC/REM key on the
control panel.
If LOCAL is selected, the commands for closing and opening the main
circuit breaker (MCB) are entered via the pushbuttons on the front door.
The commands for starting and stopping, for changing the direction and
the setpoint are entered on the control panel. In LOCAL mode no remote
command via digital inputs or a serial interface is accepted.
If REMOTE is selected, all control signals (MCB close/open, ACS 1000
start/stop, setpoint) come from one or two external control stations.The
operational commands are connected to digital inputs and up to two
setpoints are connected to analog inputs. As an alternative, the remote
control signals can be transmitted via a serial communication interface.
In remote control mode the ACS 1000 can also be operated via the control
panel and the pushbuttons on the front door, if the corresponding para-
meters are set to KEYPAD:
• Parameter 11.01 EXT1 STRT/STOP/DIR for external control station
1 and/or parameter 11.02 EXT2 STRT/STOP/DIR for control station 2
• Parameter 12.06 EXT REF2 SELECT.
For more information on LOCAL/REMOTE parameter settings see
Chapter 4 - I/O Interfaces and Application Macros, Chapter 8 - Operation
and Appendix H - Signal and Parameter Table.
Changing from LOCAL to REMOTE and vice versa is possible while the
ACS 1000 is running.
Changing from LOCAL to REMOTE:
• The motor does not stop if the external operational commands (MCB
close/open and ACS 1000 start/stop) from the remote control station
are set correctly.
• The speed follows the actual reference value at the analog input. If
there is a difference between the actual speed and the speed refer-
ence value, the speed follows a pre-set ramp until the actual refer-
ence value is reached.
Changing from REMOTE to LOCAL:
• The motor does not stop.
• The speed does not change (initial value for nref is the last actual
speed) which can now be changed via the CDP 312 control panel.
Disable Local LOCAL operation can be disabled via digital input DI 1.8 DISABLE LOCAL
on IOEC board 1. The digital input is accessible via terminals X301:1 and
2. If the input is set to high and REMOTE is selected on the control panel,
it is not possible to select LOCAL. This function is important when acci-
dental commands via the control panel must be prevented because the
ACS 1000 is operated via a remote control station.
Note: If the control panel is in LOCAL mode when DI 1.8 DISABLE LOCAL
is set to high, the LOCAL mode will not be disabled! Only after REMOTE
has been selected again, it is not possible to change to LOCAL.
Entering Start and Stop The control panel can be used to start ( ) and stop ( ) the drive.
Commands Therefore, the control panel must be
• in LOCAL mode
or
• if REMOTE is selected, parameter 11.01 EXT1 STRT/STOP/DIR or
parameter 11.02 EXT2 STRT/STOP/DIR must be set to KEYPAD.
Setting the Sense of The sense of rotation is selected on the control panel using the key
Rotation for forward direction and the key to reverse the direction. Both keys
can be used, if:
• the control panel is in LOCAL mode
and
• parameter 11.3 DIRECTION is set to REQUEST.
Parameter 11.3 provides 3 settings:
• FORWARD
• REVERSE
• REQUEST.
If parameter 11.3 is set to FORWARD or REVERSE, the sense if rotation
is fixed to the selected direction and cannot be changed using the and
key (see also Appendix H - Signal and Parameter Table).
An arrow on the display indicates the direction:
• If the motor is running, the arrow indicates the actual sense of rota-
tion.
• If the motor is not running, the arrow indicates the preselected sense
of rotation.
In the example below, reverse direction is shown.
When the sense of rotation is changed while the motor is running, the
speed will automatically ramp to zero and the motor will accelerate in
opposite direction to the preset speed. The direction of the arrow on the
display changes to the new sense of rotation, if the motor has reached
zero speed.
For more information see Chapter 8 - Operation.
Setting a Setpoint Before a setpoint can be changed via the control panel, select LOCAL by
pressing the LOC/REM key. The setpoint can then be changed at any
time.
Overview of Application The application macros are selected in parameter group 99 (start-up
Macros data). An overview of available application macros is given in Table 5-9.
Not included in the table are the User Macros 1 and 2. Instructions on how
to work with user macros can be found in section Creating a User Macro,
page 5-17.
Table 5-9 Available Application Macros
Macro Selection
Factory FACTORY
Hand/Auto HAND/AUTO
Master/Follower M/F-CTRL
Selecting an
Application Macro
4 Press ENTER.
Caution: Running the ACS 1000, the motor and the equipment being
After a User macro has been loaded, it needs to be checked, that the
parameter settings correspond to the motor in use.
Note: After a User macro has been loaded and parameters are changed,
the complete set of parameters must be saved in the User macro again, if
the changes are to become part of the user macro.
4 Press ENTER.
Recalling User Macro In order to recall the parameters saved in the User macro proceed as
Parameters described above. In step 5 select USER 1 LOAD or USER 2 LOAD instead
of USER 1 SAVE or USER 2 SAVE.
Note: IOEC board 3 is a standard I/O board in the water-cooled ACS 1000
converters and does not need to be activated.
4 Press ENTER.
5 Change the parameter setting using the slow UP/DOWN keys. The
fast UP/DOWN keys are for numeric values only.
4 Press ENTER.
6 Press ENTER to save the selection. The default settings for the active
application macro are restored.
6.1 Overview
Note: Before starting work on the ACS 1000 the general safety instruc-
tions in Chapter 1 - Safety Instructions must be read and understood.
Note: If the installation site conditions are not within the specifications or
if transportation or installation require special measures, contact the ABB
representative or the factory.
Base Dimensions and For drive dimensions see drawing Dimensions and floor mounting in
Clearances Appendix E - Layout and Mechanical Drawings.
All units must be mounted with adequate free space provided in accor-
dance with Table 6-1. Dimensions are given in mm with equivalent inches
in brackets.
Above (1)(3) Below (1) Left / Right (1) Front (2) Back
Notes:
1 Dimensions listed do neither include space for mov-
ing the cabinet, nor for cable and water entries.
2 Dimensions listed indicate maximum necessary door
swing area. Additional space may be needed to fulfill
local regulations.
3 Dimensions are above the optional redundant fan
unit.
Floor Levelling The ACS 1000 cabinet must be installed on an even surface and in upright
position.
Note: If the mounting surface is uneven, the doors of the cabinets become
misaligned and do not open or close properly.
Floor Fixings Holes for fixing the drive cabinet to the floor are located in the base of the
cabinet as indicated in Figure 6-2. The holes are accessible through the
cabinet and are suitable for M12 floor fixings.
x x
ACS 1000
x x x
Cable Ducts Cable ducts must be of non-flammable material, with non abrasive surface
and protected against humidity, dust and animals.
Parameter Value
pH 6–9
Hardness 3 – 15 dH
Raw Water Interface The raw water is connected to the cooling unit via two flexible hoses (part
of the supply). The hoses are either entered from the top, from the bottom
or from the side. Characteristic values of the raw water interface are given
in Table 6-3.
Table 6-3 Raw Water Interface Specification
ACS 1000-
ACS 1000-W1 Remarks
W2/-W3
Inlet
Outlet
Inlet
Hose length: 2 meters
Outlet
1. For raw water inlet from the side, an opening must be cut into the side wall
to mount the duct plate. An additional metall blanking plate with the same
dimensions as the original duct plate must be made.
Note: Make sure that no metall chips and dust remain in the cabinet.
Inlet
Outlet
Use the lifting lugs on the top of the converter if moved by crane.
Note: The front doors of the power sections of the ACS 1000 are mechan-
ically interlocked with the grounding switch.
The ACS 1000 is shipped with the grounding switch in grounded position.
In this position all doors of the power sections can be opened.
Should the grounding switch be in open position (not grounded) and the
auxiliary supply is not switched on, the doors of the power sections cannot
be opened.
To open the doors proceed as follows:
6 Remove the metall plate in the control section (see Figure 6-6).
7 Pull the attached wire towards the control section. The grounding
switch lock will be released.
8 Close the grounding switch (grounded position).
a b
Outlet
B
Customer side piping
Inlet
Outlet
1. If side entry is made at the installation site, an opening for the duct plate
must be cut into the side wall. The openings on the top and on the bottom,
which are not used, must be closed by a metall blanking plate.
Note: Make sure that no metall chips and dust remain in the cabinet.
C
Customer side piping
Outlet
D
Customer side piping
Inlet
Outlet
E
Customer side piping
Connect hoses to
Inlet inlet and outlet
Outlet
Transformer The cable from the circuit breaker to the transformer primary has no
Primary Cables special requirements. It should carry a voltage rating consistent with the
voltage present in the primary circuit. The ampacity rating should be
consistent with the size of the transformer in use and the protection
settings of the protection equipment. Derating of cable ampacity in accor-
dance with maximum expected ambient temperature, raceway fill factors,
and any other factors required by local electrical codes should be applied.
Installation should be in compliance with standard industry practice for
medium voltage equipment.
Transformer The cables from the transformer secondary windings to the ACS 1000
Secondary Cables busbars, are exposed to common mode voltages, resulting from normal
inverter operation. For this reason, it is necessary to use cables rated for
insulation levels of 5 kV (phase to earth) or higher for all transformer
secondary connections, regardless of the transformer secondary voltage
level (1327 V, 1903 V, or 2305 V). Cables rated for 5 kV are typically used
in North America, in Europe, cables rated for 6kV/10 kV are common.
For information on maximum permitted length of the transformer
secondary cables see Appendix A - Technical Data.
A cable with 3 individually shielded conductors or a cable with one overall
shield is recommended to insure compliance with EMC requirements, and
to provide a low impedance high frequency path through which the
common mode currents can flow. Shields should be terminated and
grounded in as short a distance as possible at both ends. The ACS 1000
includes a vertical ground busbar within the cable termination compart-
ment for this purpose.
A non-shielded 3-conductor cable with a continuous corrugated aluminum
armor may be used alternatively to the shielded cables described above.
A non-shielded steel armored cable or a non-shielded cable with inter-
locked armor should not be used. Connectors with 360° electrical contact
to the armor should be used to terminate the cable ends to ground.
The ampacity rating of the cable should be consistent with 125% of the
rated current of the ACS 1000 being supplied (allows for harmonic
content) and the protection settings of the protection equipment. Derating
of cable ampacity in accordance with maximum expected ambient temper-
ature, raceway fill factors, and any other factors required by local electrical
codes should be applied.
Installation should be in compliance with standard industry practice for
medium voltage equipment. Cables must be terminated with connectors
according to the cable manufacturer’s requirements.
If required by local electrical code an equipment safety ground wire should
be supplied either separately or by including it in the 3-conductor cable.
The ampacity of this conductor should be in accordance with the code.
Motor Cables There are no special requirements to be considered for the cable from the
ACS 1000 to the motor. A voltage rating consistent with the voltage
present in the motor circuit must be selected. The ampacity rating should
be consistent with the size of the motor being supplied and the overload
settings of the motor protection software as input to the ACS 1000.
Derating of cable ampacity in accordance with maximum expected
ambient temperature, raceway fill factors, and any other factors required
by local electrical codes should be applied. Installation should be in
compliance with standard industry practice for medium voltage equip-
ment.
Cable screening is not required for the motor cables since converter
output voltage and current are sinusoidal. Therefore no measures against
common mode currents are needed.
If required by local electrical code an equipment safety ground wire should
be supplied either separately or by including it in the 3 conductor cable.
The ampacity of this conductor should be in accordance with the code.
Motor cables are terminated within the ACS 1000 in the same way as
transformer secondary cables.
For information regarding the maximum recommended cable length for
motor cables see Appendix A - Technical Data.
Dimensioning When dimensioning the power cables, the actual situation (method of
Power Cables installation, voltage drop due to cable length etc.) and the local regulations
must be considered. To achieve best EMC it is recommended to use three
phase cables, individually shielded and with steel armouring.
Refer also to the specifications of the cable manufacturer.
Auxiliary Power Cable A 3-phase cable without neutral connector is required for the auxiliary
power supply. Select type and ratings according to the local regulations.
For ratings see also Appendix A - Technical Data.
Control Cables Control cables should be provided in accordance with Table 6-4. Cable
shields should be terminated on the ACS 1000 end only. Either single or
multiple twisted pair cables may be used.
Table 6-4 Recommended Control Cables
Cross-Section
Signal Type General Cable Type
(I/O Termination)
Analog Input Twisted pair(s) - Overall Shield 0.5 to 2.5 mm2 / AWG
20 to AWG 12
Analog Output Twisted pair(s) - Overall Shield 0.5 to 2.5 mm2 / AWG
20 to AWG 12
Power Cables Routing of mains and motor cables must be carried out in compliance with
the local regulations and according to the specifications and recommen-
dations of the cable manufacturer.
• If single phase cables are used, the cables with the three different
phases must be grouped close together to achieve EMC.
• If the cross section of the cable shielding is less than 50% of the cross
section of one phase, an additional grounding wire must be laid along
the power cables to avoid excessive heating losses in the cable
shieldings.
Cable Termination Cables must be terminated with connectors according to the cable manu-
facturer’s requirements.
Grounding Wire Routing of the grounding connection must comply with local regulations.
In some countries redundant cable routing is required.
Control Cables Control cables should not be laid in parallel to the power cables. If this
cannot be avoided, a minimum distance of 30 cm (12 in) must be main-
tained between control and power cables.
Control and power cables should be crossed at an angle of 90°.
Factory PE Transformer
ground
a1 b1 c1 a2 b2 c2
Shielding Armouring
Factory
ground ACS 1000
PE
Factory 7 8 9
ground ACS 1000
2-
7 8
2- 7 9
Motor
2U1
Front side 2V1
of cabinet
2W1
U2
V2
W2
1U1
1V1
1W1
Transformer and motor cable entry is from the bottom or from the top. The
entry plates mounted on top of the cable connection section must be relo-
cated to the base of the cabinet. The removable spacers on the upper
terminals must be relocated to the lower terminals, if the cables are
entered from below (see Connecting Transformer and Motor Cables, page
6-17).
The entry plates are suitable for cables with a maximum diameter of
45 mm.
! section.
Cables must not touch terminals of any other phase. A minimum clearance
of 20 mm must be maintained between each cable and the terminals of
any other phase. Adequate distance is obtained with spacers as shown in
Figure 6-17.
Minimum Creepage When a cable is connected to a busbar and spacers are used, attention
Distance has to be paid to the minimum required creepage distance. Depending on
the Comparative Tracking Index (CTI) of the insulation material of the
cable the following Minimum Creepage Distances (MCD) apply:
Table 6-5 Creepage Distance
MCD in mm CTI
63 600
71 400....600
80 175....400
If the CTI value of the insulation material is unknown, the values in row
three of the table apply.
Cable Entries
Aux. power
and control
cable entries
(front)
Danger: Make sure that the ACS 1000 is disconnected from the mains
and auxiliary supply.
• The main circuit breaker (MCB) must be open and in service position
(i.e. disconnected from mains and grounded).
• Auxiliary power supply must be disconnected.
• Any control equipment to be connected with the ACS 1000 is discon-
nected.
! or lead to malfunction.
Do not cut cables inside the cabinet. Make sure that dust and chips from
cable cutting and stripping cannot enter the cabinet.
6 Enter the conductors through the EMC sleeves of the entry plate as
shown in Figure 6-14 and Figure 6-15:
1 Strip cable insulation in the entry plate area. Tighten
the EMC sleeve on the stripped part of the cable with
cable ties.
2 Remove the entry plate if cable entry is not possible
otherwise and slide it onto the cable. After the
grounding connections are made, fasten the entry
plate.
3 IP 54: Remove the rubber grommets from the entry
plates and cut them to adequate diameter for the
transformer and the motor cable (Figure 6-15). To
ensure proper sealing, cut along the diameter
marking that corresponds to the cable diameter. Slide
the grommet onto the cable (Figure 6-14). The
grommet must fit tight to prevent water from entering
the cabinet. If necessary, seal the junctions with sili-
cone rubber.
Outer sheath
Entry plate
Cabinet roof
EMC sleeve
Strip conductor
insulation to
expose the shield Mounting
bracket
Strip conductor
insulation to
expose the shield EMC sleeve
Cabinet floor
Entry plate
End of cable shield
Figure 6-14 Cable Entry for Power Cables (IP 20 and IP 22).
Note: Tighten the EMC sleeve on the stripped part of the cable with cable
ties. For IP 54 units, add a rubber grommet on the cable.
A B
Grounding 7 Enter the grounding wire through an EMC sleeve of the entry plate
Connections and fasten it to the grounding bar. If there is no free entry available,
enter the grounding wire together with a phase conductor through the
EMC sleeve.
Connecting 10 If the cables are entered from below, relocate the 5 removable
Transformer and Motor spacers mounted on the top terminal bars, symmetrically to the lower
Cables terminals of the cabinet (Figure 6-17).
Busbar
Removable spacer
! or lead to malfunction.
Do not drill inside the cabinet. Make sure that dust and chips from drilling
cannot enter the cabinet.
! section.
High voltages can cause flashover between the potential of a phase and
earth.
Therefore cables must not touch terminals of any other phase. A minimum
clearance of 20 mm must be maintained between each cable and the
terminals of any other phase.
Note: When the door of the power cable section has been closed and the
plates have been rearranged, all provided screws must be mounted and
tightened to achieve best EMC.
Entry plate
Holes for
Base plate position screws
Entry plate
PE W V U
Copper foil
Figure 6-21 shows the control section with the swing frame removed. The
I/O boards, signal terminals and auxiliary terminals can also be seen. The
door of the power terminal section is closed.
Signal terminals
X300, X301
Access door to
power terminal section
I/O board
IOEC 3
I/O board
IOEC 4 (optional)
Caution: EMC must be achieved at all time.
! All fastening screws must be mounted and tightened, and the control
section door must be closed.
7.1 Overview
The ACS 1000 may only be commissioned by ABB staff or by their autho-
rized representative.
Performance tests are carried out by ABB staff in the presence of the
customer.
Note: The ACS 1000 has batteries installed in the control section. If the
drive has been stored for up to one year before commissioning, the
batteries must be replaced.
50
51N
51
AC time residual
overcurrent relay
Instantaneous/AC time
overcurrent relay
Vacuum Contactor
Trip signals
50
51N
51
AC time residual
overcurrent relay
Instantaneous/AC time
overcurrent relay
ACS 1000
MCB open Tripping loop
DO 2.5
X300
MCB close
DO 2.6
MCB is closed
DI 2.10
MCB is open
DI 2.9
MCB is available
DI 2.11
Current
x 10
Overload protection
7.4.2 Acceptance
When commissioning is completed, the commissioning report will be
signed by the customer as a sign of acceptance and by the ABB commis-
sioning engineer. One copy will be retained by the customer, a second
copy by ABB. The customer will then receive confirmation from ABB,
including a record of all actual parameter settings.
7.4.3 Warranty
Warranty will start on the date of acceptance, i. e. upon the signing of the
commissioning report by both parties, and will last 1 year.
8.1 Introduction
This chapter outlines the regular operation using the CDP312 control
panel and the pushbuttons on the control section after the ACS 1000 has
been properly installed according to Chapter 6 - Installation and commis-
sioned.
Remote Control When the ACS 1000 is controlled by a PLC or operated from external
stations, the reference value, the open and close commands of the MCB
and the start and stop commands are received via digital inputs or a
fieldbus adapter module. In these cases the control interface is adapted to
the specific configuration and therefore remote control operation is not
described in this chapter.
Note: Before starting to operate the ACS 1000 the general safety instruc-
tions in Chapter 1 - Safety Instructions must be read and understood.
Running the ACS 1000, the motor and the equipment being driven with
incorrect data can result in improper operation, reduction in control accu-
racy and damage to equipment.
Only qualified and certified personnel shall operate the drive system, i.e.
personnel who are familiar with the machine and the operation of the drive
system and the hazards involved and who have aquired the certificate
after having attended the ABB service training.
All doors, including the door of the power cable section must be closed
before energizing the ACS 1000.
! All fastening screws must be mounted and tightened, and the control
section door must be closed.
Switch off the auxiliary voltage to shut down the cooling system.
• All cabinet doors, including the protective separation door and the
control section door are closed
• The grounding isolator is in open position.
Grounding isolator
EMERGENCY OFF
button
CLOSED
OPEN
6 Clear the fault buffer on the CDP 312 control panel (see Chapter 5 -
Parameter Viewing and Editing and Control Panel Functions, Table 5-
3). No error message must be displayed.
H Min S
9 To change the setpoint press REF on the CDP 312 control panel.
! The sense of rotation can only be changed using the control panel keys, if
parameter 11.3 DIRECTION is set to REQUEST.
The ACS 1000 can be stopped using one of the stop modes selected in
parameter group 21 (see Appendix H - Signal and Parameter Table).
1 Press the STOP key on the CDP 312 control panel.
Danger: High voltage! The capacitors of the intermediate DC link are still
charged.
Do not access the power circuit or the motor after an operational stop!
Before accessing the power circuit, disconnect the ASC 1000 from the
mains power supply and ground the drive system as described in section
De-energizing the ACS 1000, page 8-8.
To disconnect the drive from the main power supply, proceed as follows:
1 Stop the ACS 1000 (see previous section).
2 Press the main circuit OFFLINE button on the control section door of
the ACS 1000 (see Figure 8-1). The MCB opens.
Do not access the ACS 1000, the motor or the power cables as long as
the drive system is not properly grounded.
After switching off the mains and after the motor has come to a stop, wait
approximately 5 minutes for the DC link capacitors to discharge. The light
GND.- ISOLATOR UNLOCKED must be on, before grounding the
ACS 1000.
ON !
tor
I s olaed
nd.- lock
G un
Figure 8-2 Grounding Isolator Unlocked
4 Close the grounding isolator located on the right side of the control
section.
CLOSED
OPEN
Figure 8-3 Grounding Isolator Closed
The display shows:
5 Open input and output isolators (if present) and secure the MCB
(rack-out, lock-out, tag-out).
6 Switch off the auxiliary voltage.
7 The drive system is now dead, and safe access is possible.
Switch off the auxiliary voltage to shut down the cooling system.
An emergency stop is initiated if the tripping loop opens. The tripping loop
is a hardwired, fail-safe protective circuit, provided to trip the main circuit
breaker directly. Contacts from EMERGENCY OFF buttons and other
external protection devices are series connected to the tripping loop. If
one of the contacts opens the drive shuts down (see Appendix F - Wiring
Diagrams).
Do not access the ACS 1000, the motor and the power cables as long as
the drive system is not properly grounded.
After switching off the mains and after the motor has come to a stop, wait
approximately 5 minutes for the DC link capacitors to discharge. The light
GND.- ISOLATOR UNLOCKED must be on, before grounding the
ACS 1000.
9.1 Introduction
This chapter contains the maintenance schedule and step by step instruc-
tions of specific maintenance tasks.
Maintenance, parts replacement and other work on the ACS 1000 must
only be carried out by qualified personnel in compliance with local regula-
tions.
Note: To maintain safe and reliable operation of the ACS 1000, ABB
recommends taking out a service contract with the local ABB service
organization. For more information contact your local service represen-
tative.
Service Training Maintenance and service training courses are offered by ABB. Customer
staff having successfully attended such courses, will be certified to do
maintenance and repair work on the ACS 1000 after the warranty period.
For further information contact your local ABB service representative.
Log Book All maintenance activity should be recorded in the maintenance log book
including:
• Date and time
• Any maintenance work
• Cooling water data (conductivity, temperature, pres-
sure and water level in expansion tank) before and
after the maintenance routine.
ABB Service Address For further assistance, contact your ABB sales representative for the
address of the local ABB service organization.
Danger: Do not access the ACS 1000 or work on the motor or the power
cables, if the drive system is energized and not properly grounded!
After switching off the mains and after the motor has come to a stop, wait
approximately 5 minutes for the DC link capacitors to discharge. The light
GND.- ISOLATOR UNLOCKED must be on, before grounding the
ACS 1000.
Cable connections Qualified ABB After 1 year, then See Checking Wire and Cable Connections,
personnel service* every 4 years page 9-4
Replacing batteries Qualified (ABB Every 2 years See Replacing Batteries, page 9-5
personnel service)*
Replacing de-ionizer Qualified If necessary (at See Changing the Ion Exchange Vessel, page
resin personnel least every 2 9-13
years)
Cooling pump(s) Qualified Weekly Check for smooth operation without excessive
personnel noise and vibration
See Removing and Installing a Cooling Pump,
page 9-17
Replacing micro-filter Qualified When replacing See Replacing the Micro-Filter, page 9-15
personnel de-ionizer resin
(at least every 2
years)
Water conductivity Qualified Weekly See Checking Water Conductivity, page 9-23
(main cooling circuit) personnel
Water level in Qualified Weekly See Checking Water Level, page 9-24
expansion tank personnel
! is applied.
Note: Even if the battery has been disconnected, the LED Battery
Connected on the EPS board stays on, until the next test cycle of the
battery is started again.
- + -
+
- + -
+
4 1
3
2
Switch off the auxiliary voltage to shut down the cooling system.
Note: Valves, tubes and hoses are delicate parts.
Do not bend or put any pressure on the valves, plastic tubes and hoses.
Warning: In case of glycol in the cooling water refer to Cooling Water with
Anit-Freeze, page 9-9 for safety information.
Note: The converter has been drained for repair purposes only. To drain
the converter completely (for storage purposes) contact your ABB repre-
sentative.
! If a cooling pump runs dry, the pump seals will be damaged immediately.
Cooling Water Drinking water of good quality must be used in the main cooling circuit.
However, it is recommended to fill the circuit with deionized water to
extend the lifetime of the ion exchange resin. For change intervalls see
Maintenance Schedule, page 9-3.
The cooling water should conform to the values in Table 9-2.
If in doubt about the quality of the drinking water on your premises contact
your local water utility.
Parameter Value
pH 6 – 8.5
Hardness 3 – 10 dH
Note: Inhibitors and other chemicals must not be added to the water.
Cooling Water with When the ACS 1000 has been ordered with an anti-freeze, a container
Anit-Freeze with the appropriate type and amount of glycol is delivered with the drive.
Avoid skin and eye contact and wear protective clothing including rubber
gloves and goggles when handling ethylene glycol.
Food stuffs and beverages must be kept separate from the place of work.
The safety data sheet supplied by the supplier of ethylen glycol (e.g.
SwedeWater) must be followed.
! The converter cannot be started since the conductivity level remains too
high.
Only pure ethylene glycol which acts only as an anti-freeze and has no
inhibitors for corrosion protection is permitted for the ACS 1000.
In the following table the characteristic values of the anti-freeze are listed:
pH-Value neutral
In the following table the values for the desired frostproofing are listed:
Table 9-4 Water Ethylene Glycol Concentration for the Desired Frost-
proofing
- 10 °C (14 °F) 20 % 80 %
- 20 °C (-4 °F) 34 % 66 %
- 30 °C (-22 °F) 44 % 56 %
- 40 °C (-40 °F) 52 % 48 %
Filling the System 1 Switch off the motor protection switch(es) -Q11/( -Q12) of the
pump(s).
2 Switch on the auxiliary voltage with switch -Q1.
3 Close valves V1, V11, V15, V80, V81*.
4 Open valves V2*, V5, V12, V17*.
(*depending on version of cooling unit and application)
7 Stop the filling when the water level in the expansion vessel is approx.
80 %.
8 Close valve V14 and open valve V1, V11 and V15 (in case it has not
been opened yet).
9 Open the priming plug on the pump house(s) (see Figure 9-3) and
deaerate the pump(s). Close the plug again.
Priming plug
Note: The temporary jumper must be removed before the drive goes into
operation.
The auxiliary supply has to be turned off befor starting work at terminal
X10.
12 Check the system pressure. If the pressure remains below trip level
(2 bar) the rotation of the pump is not correct. In this case the rotation
of the pump must be reversed by changing two phases on the
terminal X10.
13 In case of a single pump drive run the pump for 30 minutes to
deaerate the drive and proceed with step 18.
14 In case of a redundant system install a temporary jumper.
• Disconnect the connector X22 from IOEC board 1.
• Connect a jumper (cross-section 1 mm2) between
X22-1 and X22-3 of connector X22.
• Plug the connector X22 back into IOEC board 1.
Note: The temporary jumper must be removed before the drive goes into
operation.
15 Let the first pump run for 10 minutes and then turn off Q11.
16 Switch on Q12.
17 Run the second pump for 30 minutes to deaerate the drive.
18 Close valve V17* while the pump is running.
19 Close valve V11 and fill up the expansion vessel according to step 6
to step 8.
20 Close valve V12.
21 Disconnect the hose.
22 In case a temporary jumper (step 10 and step 14) has been used, it
must be removed.
23 In case of a redundant pump close Q11.
24 Reset the alarm. Refer to Appendix H - Signal and Parameter Table.
After filling the cooling circuit the conductivity value might not be in the
permitted range (conductivity alarm level: 0.5 µS/cm, conductivity trip
level: 0.7 µS/cm).
The auto-cooling sequence starts automatically. For more information
refer to Appendix H - Signal and Parameter Table.
Note: When filling cooling water while the ACS 1000 is in operation, the
drive may trip on a conductivity fault.
4 Stop the filling when the water level in the expansion vessel is approx-
imately 80%.
5 Close valve V14.
6 Open valve V11.
7 Remove the hose.
Warning: When the drive is in operation, voltages are present in the con-
trol section.
Caution: Avoid skin and eye contact with the deionizer resin.
If the hose gets stuck, push it first towards the coupling and then out.
3 Unhook the 2 rubber belts (2 in Figure 9-4) and carefully move the
vessel out of the cabinet.
4 Cover the openings of the hose couplings appropriately to prevent dirt
from entering.
3
OUT IN
4
3
1
Resin
4
2
Mounting a new 8 Dismount the distributor head of the spare vessel according to step 5
Exchange Vessel and step 6.
9 Slowly push the distributor head and tube with the hose couplings into
the spare vessel.
10 Lift the ion exchange vessel back to the cabinet and fix it with the two
rubber belts.
11 Reconnect the 3 hoses to the vessel in the correct order (push in
approx. 10 mm).
Note: IN and OUT is marked on the distributor head. The hose from the
distributor head to the filter Z2 must be connected to OUT.
Disposal of Ion Dispose of the vessel and the exhausted resin according to local regula-
Exchange Vessel tions. Refer to the Safety Data Sheet 8-1000-193 in Appendix L - Subsup-
plier Data or consult your local ABB service organization.
Removing the Pump in 1 De-energize the ACS 1000 according to Chapter 8 - Operation, De-
a Single Pump Drive energizing the ACS 1000, page 8-8.
2 Unhook the 2 rubber mounting belts (see Figure 9-7) and carefully lift
the ion exchange vessel out of the cabinet. The connecting tubes are
long enough, so that the ion exchange vessel has not to be discon-
nected.
3 Switch off the motor protection switch -Q11 of the pump. The motor
protection switch is located in the control section. Make sure that it
cannot be switched on by accident.
Pump 1
Pump 2
(optional)
K11/K12
Priming plug
(drain plug is situated
below)
6 Open the motor terminal box and check the pump terminals for
voltage.
7 Disconnect the power supply cable in the motor terminal box (see
Figure 9-10).
Note: Mark the cables for later identification.
8 Loosen the metal clamp around the pump house (see Figure 9-10).
Metal Clamp
Power Supply
Note: Be careful not to damage the O-ring between the pump house and
the motor.
Note: The pump motor might be stuck and is therefore hard to remove.
Remounting the Pump 1 Move the pump back into the water cooling cabinet.
in a Single Pump Drive
2 Slide the impeller into the pump house (moisten the O-ring with
water). Be careful not to damage the O-ring between the pump house
and the motor.
3 Remount the four bolts on the pump stand. Tighten the four bolts on
the pump stand by hand lightly.
4 Remount the clamp to the pump house (5...6 Nm).
5 Tighten the four bolts on the pump stand (21...26 Nm).
6 Connect the power supply cable to the motor terminal box.
7 Open valve V1.
8 Open the priming plug on the pump house (see Figure 9-9) and
deaerate the pump. Close the plug again.
9 Open valve V14 to relief air. Close the valve again.
10 Open valve V5 and V15.
11 Open valve V12.
12 Install a temporary jumper.
• Disconnect the connector X21 from IOEC board 1.
• Connect a the jumper (cross-section 1 mm2) between
X21-1 and X21-3 of connector X21.
• Plug the connector X21 back into IOEC board 1.
Note: The temporary jumper must be removed before the drive goes into
operation.
13 Switch on the motor protection switch -Q11 (see Figure 9-8) and the
auxiliary power supply (-Q1).
14 Check the system pressure. If the pressure remains below trip level
(2 bar) the rotation of the pump is not correct. In this case the rotation
of the pump must be reversed by changing two phases in the motor
terminal box. (Refer to Changing Rotation of Pump, page 9-23.)
15 Reset the alarm. Refer to Appendix H - Signal and Parameter Table.
16 As soon as the conductivity is below alarm level (0.5 µS) the drive can
be started again.
17 After running the pump for 30 min. close valve V12.
18 Check for leaks.
19 Carefully lift the ion exchange vessel back to the cabinet and remount
the two rubber belts.
20 Refill cooling liquid if needed according to Adding Water to the
Cooling System, page 9-13.
Removing the Pump in 1 Switch off the motor protection switch of the pump to be removed:
a Redundant Pump
• -Q11 for pump 1 (upper pump)
Drive
• -Q12 for pump 2 (lower pump).
Warning: When the drive is in operation, voltages are present in the con-
trol section.
2 Unhook the 2 rubber mounting belts (see Figure 9-7) and carefully lift
the ion exchange vessel out of the cabinet. The connecting tubes are
long enough, so that the ion exchange vessel has not to be discon-
nected.
3 Close valve V1/(V2). Secure the valves in order not to be opened by
accident (e.g. by using tape). The pump is now isolated between
valve V1/(V2) and check valve V3/(V4).
4 Drain the pump P1/(P2) through the drain plug on the lower side of
the pump house (not visible in Figure 9-9). (About 3 liters of water will
run out.) Remount the drain plug.
5 Open the motor terminal box and check the pump terminals for
voltage.
6 Disconnect the power supply cable in the motor terminal box (see
Figure 9-10).
Note: Mark the cables for later identification.
7 Loosen the metal clamp around the pump house (see Figure 9-10).
8 Fasten the pump motor in a suitable way in order to prevent it from
falling down (depending on the pump fixing, this is not always neces-
sary).
9 Loosen the four bolts on the pump stand (see Figure 9-9).
10 The motor, including impeller and the mechanical seal can now be
pulled from the pump house out of the converter cabinet.
Note: Be careful not to damage the O-ring between the pump house and
the motor.
Note: The pump motor might be stuck and is therefore hard to remove.
Remounting the Pump 1 Move the pump back into the water cooling cabinet.
in a Redundant Pump
2 Slide the impeller into the pump house. Be careful not to damage the
Drive
O-ring between the pump house and the motor.
3 Remount the four bolts on the pump stand. Tighten the four bolts on
the pump stand by hand lightly.
4 Remount the clamp at the pump house (5-6 Nm).
5 Tighten the four bolts on the pump stand (21...26 Nm).
6 Connect the power supply cable to the motor terminal box.
7 Open valve V1/(V2).
8 Open the priming plug on the pump house (see Figure 9-9) and
deaerate the pump. Close the plug again.
The pump that has been exchanged has to be deaerated and must there-
fore run for a short time in parallel with the other pump. For this reason the
pump must be started manually according to the following procedure:
9 Depending on which pump has been exchanged one of the following
two procedures has to be followed:
Manual start of pump 1 (closing K11 (see Figure 9-8)):
• Go to the IOEC board 1, digital output DO 1.1.
• Disconnect the connector X21 from IOEC board 1.
• Connect a temporary jumper (cross-section 1 mm2)
between X21-1 and X21-3, but do not loosen X21-2.
• Plug the connector X21 back into IOEC board 1.
Manual start of pump 2 (closing K12 (see Figure 9-8)):
• Go to the IOEC board 1, digital output DO 1.2.
• Disconnect the connector X22 from IOEC board 1.
• Install a temporary jumper (cross-section 1 mm2)
between X22-1 and X22-3, but do not loosen X22-2.
• Plug the connector X22 back into IOEC board 1.
10 Monitor the system pressure and remember the value. Refer to
Checking Water Pressure, page 9-24.
11 Switch on -Q11/(-Q12) to start the pump.
12 Run the pump for 10 seconds and monitor the system pressure. If the
system pressure rises by 0,3 bar or more the pump is working
correctly. If the system pressure does not rise, the rotation of the
pump must be reversed, by changing two phases in the motor
terminal box. (Refer to Changing Rotation of Pump, page 9-23.)
13 Stop the pump by switching off -Q11/(-Q12).
14 Wait for 1 minute (in order not to overload the fuses) and then start
the pump again and run it for 10 seconds.
Changing Rotation of 1 Switch off the motor protection switch of the pump:
Pump
• -Q11 for pump 1 (upper pump)
• -Q12 for pump 2 (lower pump).
The motor protection switches are located in the control section.
Make sure that they cannot be switched on by accident. See also
Figure 9-8.
2 Open the connection box in the water-cooling section and check the
pump terminals 22, 23, 24 (upper pump) or 25, 26, 27 (lower pump)
for voltage.
3 Change two phases of the power supply cables of the corresponding
pump.
4 In case of a single pump drive proceed with Remounting the Pump in
a Single Pump Drive, page 9-19, step 13.
In case of a redundant pump drive proceed with Remounting the
Pump in a Redundant Pump Drive, page 9-22, step 10.
If the conductivity exceeds the alarm threshold of 0.5 µS, the control
panel displays the alarm message WtrConduct.
If the conductivity exceeds the trip threshold of 0.7 µS, the drive shuts
down and the panel displays the message WtrConduct.
10.1 Overview
Note: To maintain safe and reliable operation of the ACS 1000, ABB re-
commends taking out a service contract with the local ABB service orga-
nization. For more information contact your local service representative.
During the warranty period, any repair work must be carried out exclu-
sively by ABB service personnel. After the warranty period repair work can
be carried out by ABB service personnel or by qualified personnel who
have attended a service training on the ACS 1000.
For further information on the service training, contact your local ABB
service representative.
Note: Before starting work on the ACS 1000 the general safety regula-
tions in Chapter 1 - Safety Instructions must be read and understood.
Do not attempt any work on the ACS 1000 which is not described in this
chapter.
All electrical, installation or repair work must only be carried out by quali-
fied personnel in compliance with local regulations.
Do not work on the ACS 1000, the motor or the power cables, if the drive
system is not properly grounded!
After switching off the mains and after the motor has come to a stop, wait
approximately 5 minutes for the DC link capacitors to discharge. The light
GND.-ISOLATOR UNLOCKED must be on, before grounding the
ACS 1000.
Take appropriate measures when working on the ACS 1000, i.e deener-
gize and disconnect all external devices before work is started.
Danger: Some loads can cause the motor to rotate! Therefore, always
disconnect, short or block the motor before work is started.
Avoid skin and eye contact and wear protective clothing including rubber
gloves and goggles when handling the ethylene glycol.
Food stuffs and beverages must be kept separate from the place of work.
The safety data sheet for ethylen glycol (see Appendix L - Subsupplier
Data) must be followed.
! iary voltage is switched on, even if the ACS 1000 is de-energized. The
pump is switched on if the temperature decreases below 5 °C (for W1
type) or 15 °C (for W2/W3 types).
Switch off the auxiliary voltage to shut down the cooling system.
Note: For your own safety, follow exactly the instructions in Table 10-1 for
fault finding and troubleshooting. Do not attempt any repair work on the
ACS 1000 beyond these instructions. Before starting to troubleshoot,
carefully read the warnings at the beginning of this chapter.
4 If the fault is rectified start the ACS 1000 according to Chapter 8 - Op-
eration.
The MCB is controlled and monitored entirely by the ACS 1000. There-
fore, no external opening command must be given to the MCB, if a fault
condition occurs.
Table 10-1 provides a list of all alarm and fault messages and information
on possible causes and suggestions on rectifying these.
The table does not give information or instructions on how to proceed
when printed circuit boards or other components have to be replaced or
checked or measurements have to be carried out. For information on
these refer to the software based ABB Service Tool and to appropriate
ABB service documentation. Also, when motor parameters or filter param-
eters have to be changed or an ID run has to be carried out, refer to the
appropriate ABB documentation.
Some of the alarm and fault messages relate to the specific equipment in
use (MCB, transformer, cooling system, synchronized bypass equipment,
braking chopper, etc.) and the configuration of the drive system. If the
equipment is not configured in the corresponding parameter or the alarm
or fault is not enabled, the related alarm and fault messages will not
appear on the display.
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
AI3 IO4 Slos Analog Input 3 on IOEC 4 Signal Loss - Check wire connections x S
- Check analog signal with a multimeter
- Loose or disconnected wire(s)
- Signal below pre-set minimum level
AI4 IO4 Slos Analog Input 4 on IOEC 4 Signal Loss - Check wire connections x S
- Check analog signal with multimeter
- Loose or disconnected wire(s)
- Signal below pre-set minimum level
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Aux Pow Fail Auxiliary Power Failure - Check 32 V AC for EPS board 2b
Auxiliary power supply of EPS board - Check LED on EPS board
If EPS board is working:
- No auxiliary voltage - Check ribbon cable between EPS
- Defective INT board and INT board for proper connection
Battery Battery voltage below 21.5 V - Check fuse (F114) on EPS board x 1a
Down - Check all battery connections for
- Blown fuse on EPS board tightness
- Loose battery connections - Check ribbon cable connection
- Loose ribbon cable between EPS and INT -Replace battery (see Chapter 9 - Pre-
board ventive Maintenance, Replacing Bat-
- Defective battery teries, page 9-5)
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Battery Miss Battery is not connected properly - Check fuse (F114) on EPS board x 1a
- Check all battery connections for
- Blown fuse on EPS board tightness
- Loose battery connections - Check ribbon cable connection
- Loose ribbon cable between EPS and INT
board
BChop Gusp Braking Chopper Gate Unit Power Supply - Call ABB service 2b
Message relates to optional braking chopper
BChop Temp Braking Chopper Temperature Hardware - If problem persists call ABB service x
HW Message relates to optional braking chopper
Response threshold of external thermal
protecting device reached (monitored via DI 4.4
on IOEC 4)
Braking chopper is switched off until
temperature is below trip threshold
Operation of ACS 1000 is still possible but
without braking ability (braking should be
possible again after approx. 30 minutes)
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
BChop Temp Braking Chopper Temperature Software - If problem persists call ABB service x
SW Message relates to optional braking chopper
Temperature limit of braking chopper exceeded
(monitored by software based thermal model)
Braking chopper is switched off until
temperature is below trip treshold.
Operation of ACS 1000 is still possible but
without braking ability (braking should be
possible again after approx. 30 minutes)
BrakChop Off Braking Chopper Off - If problem persists call ABB service x
Message relates to optional braking chopper
BResi Temp Hi Braking Resistor Temperature High - If problem persists call ABB service x
Temperature limit of braking resistor exceeded
(monitored by software based thermal model)
Danger! Braking chopper is not switched off.
Operation of ACS 1000 is still possible with
braking ability
BrgDE Mlos Bearing Temperature Driven End Measurement - Check signal at AI 2 on IOEC3 (signal x S
Loss must be > 4mA or > 2V)
No signal at AI 2 on IOEC 3 - Check wiring between external tem-
Related parameter: perature measuring device and
P 35.01 BEARING TEMP PROTECTION DE ACS 1000
enables the protecting function and selects the - Check cable shielding and grounding
type of shut down - Check power supply of measuring de-
vice
- Signal below pre-set minimum value
- Loose or disconnected wire(s)
- Poor signal grounding
- Defective power supply of measuring device
- Defective temperature measuring device
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
BrgNDE Mlos Bearing Temperature Non-Driven End - Check signal at AI 3 on IOEC3 (signal x S
Measurement Loss must be > 4mA or > 2V)
No signal at AI 3 on IOEC 3 - Check wiring between external tem-
Related parameter: perature measuring device and
P 35.04 BEARING TEMP PROTECTION NDE ACS 1000
enables the protecting function and selects the - Check cable shielding and grounding
type of shut down - Check power supply of measuring de-
vice
- Signal below pre-set minimum value
- Loose or disconnected wire(s)
- Poor signal grounding
- Defective power supply of measuring device
- Temperature measuring device defective
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Buchholz Signal from transformer Buchholz relay - Check transformer according to the x 1b
The message represents either an alarm or a instructions in transformer manual
fault depending on the digital input: - Check wiring of Buchholz protecting
DI 4 on IOEC 3 generates an alarm circuit
DI 5 on IOEC 3 generates a fault
Related parameter:
P 36.05 TRAFO BUCHHOLZ PROTECTION
enables DI 4 and 5
CH0 LinkEr Channel 0 Link Error - Check that parameter settings corre- x S
Related parameter: spond to the external communication
P 70.05 CH0 COM LOSS CTRL selects the interface
reaction on communcation loss - Check power supply of external com-
munication interface
- Communication time-out setting too short - Check connections and polarity of fi-
- Wrong parameter settings bre optics
- DDCS fiber optic cables are not properly con-
nected or have wrong polarity
- External communication interface connected
to CH0 interrupts the communcation
CH2 LinkEr Channel 2 Link Error - Check that parameter settings ac- x S
Related parameter: cording to master/follower manual are
P 70.14 CH2 COM LOSS CTRL selects the correct
reaction on communcation loss - Check that power supply is on
- Check connections and polarity of fi-
- Communication time-out too short bre optics
- Wrong parameter settings for master/follower
- DDCS fiber optic cables are not properly con-
nected or have wrong polarity
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
CoSensDirty Conductivity Sensor Dirty - Remove, clean and install the sensor x
Cooling water conductivity sensor is dirty See also Chapter 9 - Preventive Main-
tenance, Checking Water Conductivi-
- Water conductivity above limit value ty, page 9-23
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
EPS Fault Electronic Power Supply Fault - Check supply voltage of EPS 2b
- Check + 20 VDC output of EPS
- 32 VAC from transformer T1 missing - Check ribbon cable between EPS and
- Defective EPS or INT board INT board
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
ExtOverspeed Trip signal from external overspeed protecting - Check external overspeed protecting 1b
device, connected to tripping loop and device
monitored via DI 1 on IOEC 3. Signal can be - Check that all trip limit settings are
disabled by putting a jumper across the correctly set
terminals of DI 1 - Check wiring between external pro-
tecting device and ACS 1000
- Overspeed protecting device tripped - Check wiring to protecting device in-
- Loose or disconnected wire(s) puts
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
- Earth fault
- Defective current transducer
- Defective ADCVI board
- Defective SCA subboard
- Defective INT board
Ground Fault Ground fault detected - Check complete drive system (trans- 3
The earth fault function protects against earth former, ACS 1000, motor and power
faults in motor, motor cable, transformer cables)
secondary or inverter. The function is based on
measuring the current in the earth connection
of the star point of sine filter capacitors to
ground
- Earth fault
- Defective current transducer
- Defective ADCVI board
- Defective SCA subboard
- Defective INT board
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
GUSP1 Cur The standby current of Gate Unit Power Supply - Check the GUSP 2b
1 is too high - Check the IGCT
- Gate Unit is defective - Check the EPS board
- One of the IGCTs is defective
- EPS board is defective
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
GUSP2 Cur The standby current of Gate Unit Power Supply - Check the GUSP 2b
2 is too high - Check the IGCT
- Gate Unit is defective - Check the EPS board
- One of the IGCTs is defective
- EPS board is defective
Heater Miniature circut breaker of motor heater or - Measure heater circuit resistance x
cabinet heater tripped. Monitored via DI 12 on - Check miniature circuit breakers Q22
IOEC 1 and Q23
Related parameter: - Check parameter settings
P 38.01 MOTOR HEATER and P 38.04 - Check wiring
CABINET HEATER have to be set to YES, if
motor and cabinet heater are installed
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
InvCurrSOA Inverter Current Safe Operating Area - Check that the flash SW is compatible 2a
The inverter output current is too high for the ACS1000 converter type
Software and hardware based protection - Measure the input supply voltage.
The semiconductors are protected when being Measure all three phase to phase volt-
operated outside the safe operation area, i.e. ages under normal operation. Verify
when the DC link voltage is higher than in the results.
normal operation. The inverter output current - Verify that the cable connections are
and the DC link voltage are measured by the tight and properly grounded and
ADCVI board, which sends the data via the INT shielded
board to the AMC3 board - Check that motor and drive are cor-
Read the fault logger first to find out the primary rectly dimensioned
cause. If only fault "InvCurrSOA" exists in the - Check if the fault only occurs during
fault logger, the reason can be one of the listed acceleration. Increase the accelera-
below. The "InvCurrSOA" fault can also follow tion time if necessary
another fault. In this case read also the - Check fault history buffer for other re-
definition of the fault(s) preceding the lated error messages
"InvCurrSOA" fault
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
LimitSuperv Some actual and reference signals are - Check limit settings in parameter x
monitored for limit values. If one of the signals group 32 SUPERVISION
is at the pre-set limit the alarm comes up
Link AB Lost The Power Plate Communication System - Check optical link for proper connec- 2b
(PPCS) is used as a communication protocol tions and polarity
between the AMC3 board and the INT board.
The boards are connected via two fiber optic
PPCS links. An interruption in one of the
communication links is detected by the control
SW of the AMC3 board and a trip is initiated.
Two LED's on the INT board indicate when
data is transferred in the links A and B
Link C Lost The communication between the INT board - Check optical link for proper connec- 2b
and the ADCVI board uses three PPCS links tions and polarity
and three unidirectional signal links. Link C is
connected to the ADCVI board and monitored
by the EPLD logic located on the INT board. If
link C is lost a trip is initiated. "A1" and "A8"
fiber optic connectors on the ADCVI board
belong to link C
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
MacroChange Alarm message is displayed while new macro - Do not switch on the MCB while mac- x 1b
is loaded. ro is changed
MCB Control ACS 1000 is unable to operate the main circuit - Check that parameter settings are 2b
breaker correct and correspond to the MCB
Related parameter group: control interface
21 START/STOP/MCB FUNCTION - Check MCB functions according to
the MCB user’s manual and circuit di-
- Wrong parameter settings agram
- MCB tripped or in test position - Check external wiring and shielding
- Malfunction of MCB
- Loose or disconnected wire(s)
- Control cables shields not properly grounded
MCB Discrep The alarm MCB Discrepancy comes up, if the - Check that parameter settings are x
feedback signals ‘open’ and ‘close’ from the correct and correspond to the MCB
main circuit breaker are both high or low control interface
- Check MCB functions according to
- Wrong parameter settings the MCB user’s manual and circuit di-
- Malfunction of MCB agram
- Loose or disconnected wire(s) - Check external wiring and shielding
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
MotCooler Miniature cicuit breaker Q21 tripped - Check and reset Q21. Check that trip x S
The auxiliary contact of Q21 is monitored via setting corresponds to the motor cool-
DI 12 on IOEC 3 er current
Related parameter: - Check that cables and wires are prop-
P 38.02 MOTOR COOLER enables the erly connected and that all terminals
function and selects the alarm or shut down are tightened
Mot Overload Software based protection function, monitors - Verify overload curve parameters x S
over/underload of the motor. - Verify that driven equipment works
If activated, the actual RMS motor current is properly
continuously compared with alarm and trip
limits set in a load curve.
If the RMS value of the motor current stays
above the set overload alarm curve longer than
the specified delay time an alarm comes up.
If the RMS value of the motor current stays
above the set overload trip curve longer than
the specified delay time the drive is stopped.
Related message: “Mot Underload”.
Mot Phase L Motor Phase Loss - Check all motor cables and connec- 1b
The phase loss function monitors the motor tions
cable connections by measuring the converter - Check motor contactors and safety
output currents. If a phase is detected to be switches
missing, the drive does not start or shuts down - Try to avoid continuous operation at
during operation low frequency. If necessary make
SW function - motor phase loss tests to prove that low speed is not the
cause of the fault
- Motor cables and connections
- Defective Current transformer
- Defective SCA subprint
- Defective ADCVI board
- Low speed. If the motor runs continuously
with a frequency just above the monitoring
frequency threshold, the motor phase current
may cause an unnecessary trip condition
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Mot Phase Motor Phase Unbalanced - Check all motor cables and connec- x S
Unbal If the function is activated and the motor tions
frequency is above 5 Hz the three phases of - Check motor contactors and safety
the motor cables are monitored for equal switches
current loading to prevent overheating of the - Verify parameters
cable. If the maximum permissible current
difference between two motor phases exceeds
the parameter adjustable alarm limit an alarm
comes up and if the current difference exceeds
the programmable trip limit the drive stops.
Mot Prot SW Motor Protection Software - Verify that the parameter settings are 1a
The 3-phase RMS value of the motor current is correct and correspond to the motor
monitored and compared with 3 adjustable and load values
thresholds. A pickup delay for each threshold - Check motor loadability curve to see
can also be set. In case of an overload if loading at low speeds is permitted
condition the message Mot Prot SW is for the motor
displayed and the drive shuts down - Check that the dimensioning of the
Related parameters: motor and drive are correct
P 30.07....P 30.09 MOTOR PROT CURRENT
LEVEL set the current threshold
P 30.10...P 30.12 MOTOR PROT TIME
determine the pickup delay
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
MotorStall The motor stall function protects the motor - Check the loading near the stall area x 2a
against overheating by monitoring the output by lowering the stall frequency tempo-
frequency and the output current rarily (P 30.14). Start the cycle to see
Related parameters: if the fault is removed. Be careful not
P 30.13 STALL FUNCTION enables the to overheat the motor
function and selects the alarm or shut down. - Check that the motor and the convert-
If the output frequency is lower than the er are correctly dimensioned and
permitted limit, set in P 30.14 STALL FREQ HI, match the required load
and the current is close to its high limit, a - Check the normal load of the drive
counter in the software is started. If the counter and verify the proper functioning of
reaches a preset time limit, set in P 30.15 the driven equipment and the motor
STALL TIME a fault or warning is activated, bearings
depending on P 30.13
Mot Underload Software based protection function, monitors - Verify underload curve parameters x S
over/underload of the motor. - Verify that driven equipment works
If activated, the actual RMS motor current is properly
continuously compared with alarm and trip
limits set in a load curve.
If the RMS value of the motor current stays
below the set underload alarm curve longer
than the specified delay time an alarm comes
up.
If the RMS value of the motor current stays
below the set underload trip curve longer than
the specified delay time the drive is stopped.
Related message: “Mot Overload”.
- Motor vibrations
- Defective vibration protecting device
- Loose or disconnected wire(s)
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
MotWdg MLos Motor Winding Measurement Loss - Check signal level at analog inputs x S
At least one of 3 temperature signals is lost or (signal must be > 4mA or > 2V)
below a set minimum value. The corresponding - Check wiring between external tem-
analog inputs for the temperature signals on perature sensors and ACS 1000
IOEC 2 are: - Check cable shielding and grounding
AI 2 for phase U - Check power supply of measuring de-
AI 3 for phase V vice
AI 4 for phase W
The reaction of the drive, if a signal is lost, can
be selected for each temperature in parameter:
P 30.02 for phase U
P 30.03 for phase V
P 30.04 for phase W
MotWdg Temp Motor Winding Temperature Hardware - Check motor cooling fan or motor x S
HW The motor winding temperature is too high. The cooling pump for proper functioning
temperature in phase U, V and W is monitored and their protecting devices
by PT100 or PTC sensors. A 4...20 mA signal - Check temperature of the coolant and
of each phase is connected to AI 2, 3 and 4 on make adjustments if the temperature
IOEC 2 is too high
P 30.05 MOT TEMP ALM L sets alarm limit - Check that motor and drive are cor-
P 30.06 MOT TEMP TRIP L. sets trip limit rectly dimensioned. Check that torque
P 30.01 EXT MOTOR THERM PROT selects and power limits of the drive are prop-
the reaction of the drive, if the limits are erly set
exceeded - Check that overtemperature alarm
and trip limits are correctly set
- Motor cooling not sufficient
- Motor temperature too high
- Overload condition
- Wrong parameters settings
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
- Flash memory
NoMotorData Motor data are missing or wrong - Check that the motor data parameters 2b
in group 99 correspond to the data on
- Wrong parameter settings the motor rating plate
OS Fault Operating System Fault - Turn the power off. Check that the 2b
AMC3 board is also switched off (
- Flash memory. An error in the application soft- LED 'P' is off)
ware in the flash memory or an error during - Switch the power on again and restart
download from the flash memory may have the ACS 1000
occurred
OutsAirMLos Outside Air Temperature Measurement Loss - Measure actual signal at the analog x S
The analog signal of an outside air temperature input on IOEC 3. If the signal is below
is monitored via AI 4 on IOEC 3. Signal loss is 2 mA, the auxiliary power supply of
detected, if the actual signal decreases below the transmitters may be defective
2 mA. - If signal is missing, check the wiring
Related parameter: between the measuring device and
P 37.04 OUTSIDE AIR TEMP PROTECTION the ACS 1000
enables the function and selects the alarm or - Check the auxiliary power supply of
fault the measuring device
- Measuring circuit
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Overvoltage Overvoltage condition in DC circuit when the - If the alarm occurs even when the x
drive is “Ready to start” drive is “Ready to start”, the supply
voltage is probably too high. Check
- Mains supply the inverter measured DC voltage lev-
- Defective ADCVI board els. Read parameters:
- DefectiveSVA subboard P 02.02 DC VOLTAGE Udc1
- Defective INT board P 02.04 DC VOLTAGE Udc2
P 02.06 DC VOLTAGE Udc1 + Udc2
Measure the input voltages phase to
phase under normal operation. Verify
the results
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Panel Lost The communication to the CDP 312 control - Check that the cable from AMC3 x 2b
panel is interrupted board via NDPI to the control panel is
If the drive is in torque control mode and if the properly connected
control panel is the active control station and
the communication is lost, the drive shuts
down. If the drive is controlled from an external
control station and the keypad is selected as
control station, the drive is shuts down as well.
In any other mode only an alarm is initiated
- Loose connection
Press Stop The alarm is displayed after the Filter ID run Press the STOP key on the CDP 312 x
has been completed control panel
ProcessStop External process stop signal or run permissive - Check the external process stop cir- x 2b
Signal is connected to DI 2.8 on IOEC 2 or cuit
received via serial communications interface - Check wiring and connections
Related parameters:
P 16.01 PROCESS STOP activates and
selects the signal source
P 21.03 PROCESS STOP selects stop mode
P 21.04 PROCESS STOP MCB MODE selects,
if MCB opens or stays closed after a process
stop command
P 21.05 PROCESS STOP SPEED DIF
monitors the deceleration of the drive
- Process stop
- Loose or disconnect wire(s)
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Pump 1/2 Cooling pump malfunction ACS 1000 with one pump: x 1b
ACS 1000 with one pump: If motor protecting - Check motor protecting switch Q11
switch Q11 trips, the message Pump 1/2 is - Check wiring between IOEC 1, DI 1.1
displayed and the drive is shut down and Q11
ACS 1000 with two pumps: If one of the motor - Check pump bearings and pump
protecting switches Q11 or Q12 trips, the alarm M11for possible overload
message Pump 1/2 is displayed and the
healthy pump is switched on ACS 1000 with two pumps:
If both motor protecting switches trip, the - Check motor protecting switch Q12
message Pump 1/2 is displayed and the drive - Check wiring between IOEC 1, DI 1.2
is shut down and Q12
Q11 is monitored via DI 1.1 on IOEC 1 - Check pump bearings and pump M12
Q12 is monitored via DI 1.2 on IOEC 1 for possible overload
Related parameters:
P 41.09 WATER COOLING PUMP
SELECTION activates the selected water
cooling pump
P 41.10 PUMP ALARM RESET is used to reset
the alarm
RideThrough The ride-through function keeps the drive in - Check if the parameters are set prop- x 2b
operation if the mains power is interrupted. The erly
function uses the kinetic energy of the rotating - Check the inverter measured DC volt-
motor and load to maintain the DC voltage. ages. Read parameters:
If the ride-through function is activated and the P 2.02 DC VOLTAGE Udc1
DC link voltage decreases below 80 %, the P 2.04 DC VOLTAGE Udc2
alarm message RideThrough is displayed. P 2.06 DC VOLTAGE Udc1 + Udc2
If the DC voltage stays below 80 % and the Measure the input voltages phase to
maximum ride-through time is elapsed or the phase under normal operation. Verify
speed derceases below the minimum speed the results. If power interruption are
limit, the fault massage RideThrough is frequent, monitor the DC voltage us-
displayed and the drive shuts down ing the DriveWindow tool or monitor
Related parameters: the supply voltage by means of a net-
P 39.01 RIDE THROUGH ENABLE activates work analyzer
the ride-through function
P 39.02 RIDE THROUGH TIME defines the
maximum ride-through time
P 39.03 RIDE THROUGH MIN SPEED defines
the minimum speed limit during ride-through
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
- Parameter setting for breaker opening time
not appropriate
- Sbp(i) tripped or in test position
- Malfunction of Sbp(i)
- Loose or disconnected wires control circuit
- Control cable shields not properly grounded
Self Exci HW Self Excitation Hardware - Check the DC voltage, see parame- 3
Self excitation causes the voltage in the DC link ters P 02.02 to P 02.09
to rise. If the DC link voltage is above the limit - Check if mains supply voltage is with-
of 133% of the nominal voltage, the drive shuts in the permitted limits. See Appendix
down A - Technical Data
The hardware based protection function
monitors the positive and negative DC link
voltages
The OVVP board is used to detect the
overvoltage condition. The measured values
are transmitted via the INT board to the AMC3
board
Self Exci SW Self Excitation Software - Check the DC voltage, see parame- 3
Self excitation causes the voltage in the DC link ters P 02.02 to P 02.09
to rise. If the DC link voltage is above the limit - Check if mains supply voltage is with-
of 133% of the nominal voltage, the drive shuts in the permitted limits. See Appendix
down A - Technical Data
Overvoltage detection is based in software by
monitoring the positive and negative DC link
voltages. The ADCVI board measures the DC
link voltages. The measured values are
transmitted via the INT board to the AMC3
board
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Short Circuit A short circuit in the input rectifier bridge, DC - Check fault history buffer for 3
link or inverter is present, if an undervoltage other, related error messages
alarm and fault occur within 200 µs If only a "ShortCircuit" fault message
Short circuit protection is based on monitoring is recorded in the fault logger, the rec-
the DC link voltage tifier, most probably the rectifier bridge
diode(s) has (have) a short. Check
- Short-circuit the rectifier components
If other faults are recorded at the
same time, the short circuit is either in
the DC link or the inverter
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
SM2 Not Avl See SM1 Not Avl See SM1 Not Avl x
SM3 Not Avl See SM1 Not Avl See SM1 Not Avl x
SM4 Not Avl See SM1 Not Avl See SM1 Not Avl x
Swfreq HW Switching Frequency Hardware - Do not try to restart the ACS1000. In- 2a
Switching frequency exceeds permitted limit correct control SW may cause serious
The switching frequency is controlled and damage to the ACS1000
monitored in the software. A hardware based Always contact the ABB service orga-
protection function in the EPLD logic prevents nization
the switching frequency from increasing too
high, if the control software fails
Swfreq SW Switching Frequency Software - Do not try to restart the ACS1000. In- 2a
Switching frequency too high correct control SW may cause serious
damage to the ACS1000
- Wrong system parameters Always contact the ABB service orga-
- Defective INT board nization
- Defective AMC board
- Defective ADCVI board
- Defective SVA subboard
- Defective SCA subboard
- Defective current transducer
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Tacho Comm Tacho Communication - Check the dip switch settings of the x 1a
The communication between pulse encoder, pulse encoder module according to
encoder module (NTAC-02) and AMC3 board the manual. Measure tacho pulses.
(channel 5) is lost Replace the pulse encoder if neces-
Related parameter: sary
P 50.05 ENCODER ALM/FLT selects the alarm - Check 24 VDC power supply of pulse
or fault encoder module and AMC3 board
Check that connections are tight.
- Pulse encoder - Check and verify the following param-
- Pulse encoder not compatible with pulse en- eters:
coder type P 50.02 SPEED MEAS MODE
- Disconnected power supply P 50.04 ENCODER PULSE NR
- Wrong parameter settings P 75.03 ENCODER MODULE
- Optic link - Check that the connections of the fi-
- Defective AMC board ber optic cables in the communication
link between AMC3 board and pulse
encoder module are tight
Tacho Meas Tacho Measurement - Check that all wires between pulse x 1a
Difference between measured speed and encoder and encoder module (NTAC-
estimated speed too big 02)are connected in the right way.
Related parameter: Check that the shields of the signal
P 50.05 ENCODER ALM/FLT selects the alarm wires are grounded properly. Check
or fault encoder signal for interferences.
- Check that the pulse encoder is prop-
- Loose, disconnected or mixed up wires erly coupled to the motor
- Pulse encoder coupling - Check that the parameter settings
- Wrong parameter settings correspond to the pulse encoder in
- Non-compatible pulse encoder use
- Check that pulse encoder is compati-
ble with pulse encoder module
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
TrippingLoop A contact from one or more protecting devices - Check which external protecting de- 2b
connected to the tripping loop (terminal strip vice initiated the trip
X300) is open. Each contact is monitored via a - Check that the tripping loop is wired
digital input. The message TrippingLoop relates according to the wiring diagrams
to DI 4 on IOEC 1
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Undervoltage Temporary undervoltage in the DC circuit - Check that the mains voltage is within x 2b
The protective function is used to monitor the +/-10% of the nominal voltage. See
mains voltage parameters:
If the DC voltage decreases below 71 % of the P 02.03 DC VOLTAGE Udc1
nominal voltage an alarm is generated (only if P 02.05 DC VOLTAGE Udc2
the Ride Through function is not activated) P 02.06 DC VOLTAGE Udc1 + Udc2
If the DC voltage decreases below 65 % a trip - Check if alarm is caused by an exter-
is initiated nal event (e.g. temporary loss of sup-
ply voltage)
- Supply voltage low - Check fault history buffer for other,
- Defective ADCVI board possibly related error messages
- Defective SVA subboard
- Defective INT board
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
Wrong EPLD EPLD is not compatible with the SW version Call ABB service 1b
WtrLevelLow Water Level Low - Check cooling water level. See Chap- 1b
Water level in expansion tank is low ter 9 - Preventive Maintenance, Add-
The water level is monitored by a level switch ing Water to the Cooling System,
connected to DI 9 on IOEC 1 page 9-13 for topping up the cooling
system
- Leakage in cooling water circuit - Check that all bleed/drain valves are
- Loose or disconnected wires in monitoring closed
circuit - Check complete cooling system for
- Control cable shields not properly grounded leaks
- Check wiring and shielding of measur-
ing circuit
Table 10-1 Alarm and Fault Messages and Fault Rectification (Continued)
of Shut down
Alarm
Meaning of the Message
Type
Message Test and Rectification
- Possible Causes
11.1 Introduction
11.3 Packing
Note: The conservation measures taken for the transport packing are only
useful as long as the packing is kept unopened and in its original condition.
For loading and unloading the converter with the help of a hoisting device,
the following points have to be observed:
Use the lifting lugs on the top of the converter if moved by crane.
• The lifting eyes may only be removed after the converter has been in-
stalled at its final position. They have to be remounted if the converter
has to be transported again.
• The material and diameter of the transport rope or chain have to cor-
respond to the weight of the converter unit.
Lifting Angle The minimum lifting angle between the rope or chain and the converter
unit is 45° (see Figure 11-1).
Caution: The fan cover must not be mounted while lifting the converter
! unit.
45° 45°
Center of Gravity
x
Front View
Top View
Converter Type: W1 W2 W3
11.5 Unpacking
1000
ACS
11.6 Storage
Note: The ACS 1000 is delivered with batteries. After 1 year, when the
converter is unpacked and ready for commissioning, the batteries must be
replaced.
Note: Pay attention to always fulfill the ambient conditions during the
storage period according to Appendix A - Technical Data.
Storage after Shutdown If the converter has to be stored after it has been unpacked or after it has
been in service, proceed as follows:
1 Drain the cooling circuit completely (contact your ABB representative)
or add the appropriate amount of glycol for frostproofing, if the drive
is to be stored in ambient temperatures below 0 °C (32 °F). See
Chapter 9 - Preventive Maintenance, Cooling Water with Anit-Freeze,
page 9-9.
Inspect the spare parts immediately after receipt for possible transporta-
tion damages and report any damage to the forwarder and insurance
company.
Should you have further questions, consult the commercial terms in the
purchasing agreement, your local ABB representative or the manufac-
turer:
ABB Switzerland Ltd,
Medium Voltage Drives
Mr. Rainer Hosp
CH-5300 Turgi
Switzerland
E-Mail: [email protected]
Fax: +41 58 589 29 84
Tel: +41 58 589 22 33