An Alternative To Reduce Medium-Voltage Transient Recovery Voltage Peaks
An Alternative To Reduce Medium-Voltage Transient Recovery Voltage Peaks
An Alternative To Reduce Medium-Voltage Transient Recovery Voltage Peaks
Abstract - Circuit breakers can fail to interrupt three- considering present and 2003 substation configurations.
phase fault currents when power systems have
Transient Recovery Voltage (TRV) characteristics,
which exceed their ratings. This paper is the outcome of II. METHODOLOGY
a study for the reevaluation of three 15 kV breakers at
the CHESF (Companhia Hidroelétrica do São The TRV to which a circuit breaker is subjected depends
Francisco) Angelim substation, located in the northeast on the type of fault, its location and the type of switching
of Brazil. Digital simulations are carried out with ATP® circuit. These studies must consider:
(Alternative Transients Program) to compute the TRV
waveforms. Alternative actions are taken to bring • three-phase ungrounded terminal fault interruption
circuits within the 15 kV circuit breaker ratings when since it is usually the most severe TRV condition, with
the parameters of the simulated TRV exceed the the highest peak voltage magnitudes across the first
breaker ratings. A simple and cheap alternative to opening-pole of the breaker. This type of fault is used
reduce TRV peaks is the placement of ZnO devices as the basis for the breaker rating;
across the breaker terminals. • the short-line fault since it usually has the highest rate
of rise of the recovery voltage.
Keywords: Circuit Breakers, TRV, ZnO Devices,
Electromagnetic Transients. The ATP is used to compute the TRV waveforms and to
calculate its parameters [2]. These parameters are compared
with the TRV circuit breaker ratings.
I. INTRODUCTION
Recently, a study to examine TRV characteristics for III. CIRCUIT BREAKER RATINGS
medium-voltage circuit breakers was conducted by Swindler
et al [1]. It was considered 13.8 kV breakers in an oil In this TRV study, the NBR-7118 Brazilian Standard,
refinery in which circuit parameters as originally designed which is based in IEC-56 International Standard, 1987, is
would have exceeded the TRV (Transient Recovery Voltage) used [3]. Its purpose is to provide an application guide on the
ratings. Digital simulations were carried out with the EMTP TRV ratings for ac circuit breakers rated above 1000V. For
(Electromagnetic Transients Program) to analyze TRV circuit breakers rated 72.5 kV and below, the TRV is defined
parameters. Alternatives to bring circuits to within the 13.8 by the Two Parameter Method in which two TRV envelopes
kV circuit breaker ratings were presented. are used to define the TRV maximum value (Uc) and the rate
The circuit transient recovery voltage can be modified by of rise of the recovery voltage (RRRV). Fig. 1 shows TRV
the circuit breaker's design or by the use of additional envelope for 15 kV circuit breakers.
components like opening resistors, surge capacitors, grading
resistors or capacitors. The most common adopted solutions
are:
35
Table 7. Short-circuit breaking current levels.
30
Breaker Year I (kA) I max (kA) I (%)
TRV peak, kV
sc sc 25
1998 7.39 13.07 20
11T4 2003 9.30 40 16.44
15
1998 7.39 32.66
21Y4 16 10
2003 9.29 41.07
1998 7.38 32.60 5
21Y3 16
2003 9.27 40.98 0
11T4-1998 11T4-2003 21Y4-1998 21Y4-2003 21Y3-1998 21Y3-2003
Circuit Breaker - Year
no load 0.5 MW full load reference line
Three-Phase Faults
Fig. 5. Three-phase fault TRV peaks.
Fig. 4 shows the TRV waveform for the 11T4 breaker 3,0
when clearing a three-phase ungrounded terminal fault in
present configuration. The TRV peaks and rate of rise 2,5
calculated for each breaker opening operation are shown in
2,0
RRRV , kV/ µ s
figs. 5 and 6.
It is necessary to identify the short-circuit breaking 1,5
capacity for all breakers to be evaluated. From Table 7 and
Table 1, one can see that the interrupting current levels for 1,0
the 11T4, 21Y4 and 21Y3 breakers are in the range from 0
to 30%, from 30% to 60% and from 30% to 60% of their 0,5
exceeds the standard ratings in the following situations: no load 0.5 MW full load reference line
For the 21Y4 and 21Y3 breakers, The RRRV values Fig. 7 shows the TRV waveform for the 21Y3 breaker
exceed the standard ratings up to a 3 MW load for the when clearing a fault at 1 km from the breaker terminals for
years 1998-2002 and up to a 4.2 MW load for the years 2003 configuration. The calculated TRV parameters are
2003-2007. The TRV peaks exceeds the standard ratings for: shown in figs. 8 and 9. The parameters for short-line faults
are within standard values. The three-phase ungrounded
• no load at 13.8 kV bus, year 1998 to 2002; terminal fault at the 13.8 kV bus with no load presented the
• up to a 4.2 MW load, year 2003 to 2007. most severe TRV condition in all simulated cases.
0.0
ZnO device
-20.0
Circuit breaker
30
Fig. 10. ZnO device to reduce TRV peaks.
25
10
TRV - Phase A (kV)
5 20.0
0
1km-1998 1km-2003 3 km-1998 3 km-2003 5 km-1998 5 km-2003
Distance from breaker terminals - Year
no load 0.5 MW full load reference line 10.0
2,5
0.0
1,5
0,0
TRV - Phase A (kV)
20.0
1 km-1998 1 km-2003 3 km-1998 3 km-2003 5 km-1998 5 km-2003
Distance from breaker terminals - Year
no load 0.5 MW full load reference line
without with without with surge capacitor would reduce the RRRV to values within
ZnO ZnO ZnO ZnO the standard rating in the two configurations. With this
device device device device surge capacitor, a RRRV reduction of nearly 50% is
accomplished for the year 2003-2007 configuration.
11T4 28.07 15.44 2.51 2.14
Similarly, for the 21Y4 and 21Y3 circuit breakers, 159
1998
21Y4 27.92 15.50 1.90 1.72 nF (four ZnO disks) surge capacitors would bring the
21Y3 28.17 15.56 1.99 1.72 RRRV values to standard rating.
The use of four ZnO disks to reduce TRV peaks is more
11T4 33.73 16.86 2.92 2.43 appropriate and secure comparing to the use of three ZnO
2003
21Y4 33.72 15.60 2.54 1.93 disks. The maximum continuous operating voltage (MCOV)
of the arrester and its residual voltage are nearly 11.2 and 20
21Y3 33.94 15.67 2.60 1.98 kV, respectively.
21Y4 27.92 20.60 1.90 1.83 In some situations, the TRV exceeded the breaker
ratings. From simulation results, it was shown that the
21Y3 28.17 20.62 1.99 1.84 placement of ZnO devices across breaker terminals reduces
11T4 33.73 20.64 2.92 2.66 TRV peaks. Surge capacitors, at the source side, were used
to reduce the TRV rate of rise.
2003
21Y4 33.72 20.72 2.54 2.18 Although simulations have shown that ZnO devices
21Y3 33.94 20.81 2.60 2.14 placed across the breaker terminals are effective in
reducing TRV peaks, it would be interesting to carry out
40.0
laboratory or field tests for validation purposes.
VII. ACKNOWLEDGMENTS
30.0
0.0