Installation Instructions For CMP Cable Gland Type Tmc2X
Installation Instructions For CMP Cable Gland Type Tmc2X
Installation Instructions For CMP Cable Gland Type Tmc2X
TECHNICAL DATA
CABLE GLAND TYPE : TMC2X
INGRESS PROTECTION : IP66, NEMA 4X
2776
Tel: +44 191 265 7411 • Fax: +44 1670 715 646 IFS 15 05/19
E-Mail: [email protected] • Web: www.cmp-products.com ATEX / IECEx 8 04/19
www.cmp-products.com
INSTALLATION INSTRUCTIONS FOR CMP TMC2X 3. Electrical tape MUST be wrapped around the tips of the cable cores.
This is to ensure the cable cores are together and also to cover any sharp edges
that could potentially tear the Resin Dam during installation.
1. RapidEx Resin 4 5 6 7 8 9
2. Resin Tube
3. Entry Component
4. Sealant Tape or Inner Jacket
5. Resin Dam
6. End Stop
7. Grounding Spring
8. Jacket Seal
9. Outer Nut 4. Pass the cable through the gland until the armor makes contact with the end stop. If it is not possible for the insulated con-
1 2 3
ductors to pass through the end stop then it should be removed so that the armor can make contact with the integral end stop
PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION within the entry component. At this stage unscrew the Outer Nut and slide it back over the cable, enough to have access to the
Armor Spacer. If no access is gained repeat step 2 and trim the outer jacket up to “L” plus 10%. Assemble the gland.
1. Cable preparation — Without Inner Jacket
Strip back the jacket armor to suit the equipment geometry.
Hand tighten the Outer Nut to compress the
Outer Jacket
Grounding Spring to secure the armor. Do not over
Tape 2. tighten the Outer Nut. Remove electrical tape from
Cable Fillers Cut Tape to Length cable core tips. Separate the cable cores slightly to
Length = groove in hexagon to front of Outer Nut allow resin to flow between them. When insulating
Cable Cores
grounding conductors are present, spread the
3. strands slightly to allow the resin to form a full seal.
After the tape has been applied, cut
---
---
the cable fillers to the edge of the tape. Refer to ‘RapidEx’ assembly instructions to fill
Using the measure guide, wrap electrical tape around the the gland resin tube with the required amount
fillers and cores of the cables to the required length Note: For instrumentation cables utilizing shielded cable, individual/ of RapidEx.
overall drain wires, see Installation Guidance Notes overleaf.
1.
1. Cable preparation — With Inner Jacket 5. Once the resin has cured, loosen the Outer Nut to ensure that the Grounding Spring is not gripping the cable. Slide the Outer
Strip back the jacket armor to suit the equipment geometry. Nut back over the cable, enough to loosen the Armor Spacer from the Entry Component. Screw the Entry Component into the
Cut Inner Jacket to Length enclosure. Retighten the Armor Spacer when the entry component is fully tightened into the enclosure.
Length = groove in hexagon to front of Outer Nut
jacket is too large for the Resin Dam, cut off and
replace with electrical tape.
2. Using the armor measure guide, expose the armor further by stripping back the cable jacket
Cut Outer Jacket to Length 6. Finally, holding the cable central in the gland, tighten the Outer Nut to compress the Grounding Spring to secure the armor
Length = Groove in hexagon to rear of Outer Nut and the seal to engage the cable jacket. Do not over tighten the Outer Nut. The Entry Component and Outer Nut do not have to
close face to face.
increased by up to 10%.
www.cmp-products.com www.cmp-products.com