3phase TSD
3phase TSD
3phase TSD
12/4/2016
Page 01 of 114
Page 02 of 114
INDEX
Slno Description Page Slno Description Page
1. P1- P2 Fault & Acknowledgement 02 21 SS18 –FLG2 70
2. SS 01-Main Power 03 22 SS19 –Train Bus 72
3. Fatal Error T/S 11 23 Troubles without fault messages 73
4. SS 02-Traction Bogie-1 18 24 B.P not charging on Loco alone 74
5. SS 03-Traction Bogie-2 26 25 Loco Brakes not releasing 76
6. SS 04-Harmonic Filter 34 26 152, 154,160 & 237.1 operation 76
7. SS 05-Hotel Load 37 27 Resetting OF MCB 77
8. SS 06-Aux Converter -1 38 28 Important Points to remember 77
9. SS 07-Aux Converter -2 40 Addl. fault Messages in SR 1/2 of
10. SS 08-Aux Converter -3 43 29 MICAS with ABB or BHEL or 79
11. MCB tripping - BUR problem 45 Medha & BT -IGBT fitted Locos
12. SS09 -Battery system 46 Fault Messages in TCN & IGBT 81
30
13. S10 –Brake system 50 SR fitted BHEL Locos
14. SS11 –Auxiliaries -HB1 57 Addl./ Change in fault Messages of 85
31 IGBT fitted Medha Locos
15. SS12 –Auxiliaries-HB2 59
16. SS13 –CAB-1 61 EBV Crew Message Fault codes in 93
32 CCB2 Knorr Brake system
17. SS14 –CAB-2 63
18. SS15 –Fire Detection Unit 65 33 Simplified Circuits 95
19. SS16 –Speedometer 67 34 Notes 112
20. SS17 –FLG1 68
Page 03 of 114
P1 fault Indications: LSFI Flickers and BPFA glows. P1 Fault message will appear on display screen
Protective actions:
1. Protective turn off -VCB open, Converters DC link drop down and contactors open, some cases
Pantograph will lower : Reasons: Problem in (SR) converter processors or converter, Gate units, DC link
over voltage or current, ‘MUB’ over temperature
2. Tripping of VCB- Only VCB open & Converter contactors remains closed.: Reasons: Limit monitoring of
SR, BUR & other reasons.
3. Total Loss of Tractive Effort: Action of Traction Inter lock &, Start/ Run inter Lock. Reasons for Traction
Inter lock –VCD action, initiation of Emergency Brakes, Fault angle transmitter and battery voltage on 86
volts. Reasons for Start / Run inter Lock: Parking brake applied, Direct brake applied, A9 applied, Low MR
5.6 kg/cm2, 70 cock or 74 cock closed, Fire alarm.
4. Isolation counter activated ( resets after MCE OFF & ON). If P1 fault occurs twice or thrice in 30 minutes
without resetting counter causes to isolate the concerned sub system. The action to be taken must be
initiated immediately& follow TSD.
1. P2 fault Indications: BPFA only glows. P2 Fault message will appear on display screen. No protective
actions. But it may leads to P1 fault. The faults can be remedied manually by Loco Pilot. & follow TSD.
Acknowledgement: Acknowledge the fault messages By BPFA on run/ while initially energising (BL OFF to
‘D’ mode) till fault screen clears or BPFA Extinguishes (may be 2 or more faults at a time). If Display is
hanged (Fault screen not cleared) may be due to DDA 1/2. Life sign missing. If Unsuccessful, activate rear
cab to acknowledge the fault.
Fault No. Fault Message DDS Messages Trouble shooting for CLIs/TLCs
F0101P1 Loco XXXXXX SS01: HBB1:0002-VCB will not 1. Bring Throttle to ‘0’ Acknowledge the fault by
Main Power open BPFA.
VCB STUCK IN ON STB1:0004- VCB will not 2. Try to clear the block section by Coasting &
POSITION Loco will open bring the loco / train to dead stop
be shut down 3. Switch OFF & ON the MCE and try.
F0101P1
Loco XXXXXX SS01 4. If unsuccessful Switch OFF & ON the MCE
: Main Power once again.
MAIN POWER 5. Try to raise Panto & close VCB and resume
ISOLATED traction, If not successful, try from rear cab
VCB Inhibited Loco is 6. If unsuccessful, ask relief Loco and Record in
dead Log book.
F0102P1 Loco XXXXX SS01 : HBB1:0003 VCB will not 1. Bring Throttle to ‘0’ Acknowledge the fault by
Main Power close BPFA
VCB STUCK IN OFF STB1:0003- VCB will not 2. Close VCB & if VCB closes resume traction
POSITION close 3. If VCB does not close, try to clear the block
Try to close VCB section by coasting & bring the loco / train to
again dead stop.
4. Ensure VCB cut out cock is open, VCB
F0102P1 control block coupler intact and no air
leakage near VCB, if any leakages try to
attend the same. Ensure VCB coupler fixed
properly. & try
Loco XXXXX SS01 : 5. Close VCB in cooling Mode , if VCB closes
Main Power 6. Try to close VCB in D mode by 154 on ’I’ &
MAIN POWER try.
Page 05 of 114
ISOLATED 7. If unsuccessful, Place 154 on II position and
VCB Inhibited Loco is Switch OFF & ON the MCE & try.
dead 8. Once again switch off & on MCE and try.
9. If not successful, try from rear cab
10. If unsuccessful ask relief Loco and Record in
Logbook
F0103P1 Loco XXXXX SS01 : HBB2:0002 No pressure in 1. Acknowledge fault by pressing BPFA.
Main Power pan 1 2. Press “ZPT” to ‘DN’ Command and ensure
LOW PRESSURE STB2:0002-No pressure in FLG-504
PANTO/FAULTY pan 2 3. Operate two times IG-38 key (Horizontal in
PANTO E70 and vertical in CCB2) and Pan 1 &2
Check Isolating coc’s are in horizontal position .
Cock, Check Aux. 4. Check the Panto reservoir pressure (more
Reservoir Pressure than 5.2 Kg/cm2) in the gauge provided on
pneumatic panel.
F0103P1 5. If pressure is low, ensure that MCPA is
working & its Drain Cock (Parallel to pipe) is
closed. In case of CCB-2 Locos - Press
"PANS-TP"(test Point)/ D/C in CCB2 to drain
out the moisture & try. Close ULV / CP1&2
ULV cocs and try. Open after energising.
6. If Auxiliary compressor not working, Check
the MCB 48.1 “ON” (in SB2).If tripped reset
the same.
7. Check the contactor 48.2, if it is not closed,
tap the pressure switch 26 , (5th from left on
Pn.panel in E70 & "PANS-PS" in CCB2)
8. If pressure is available, change the position
of panto selector Switch (85) on pneumatic
Page 06 of 114
panel and try to raise other pantograph
9. If Panto is raising and message appears ,
Gently tap the pressure switch no.7th & 8th
from left (130.4/1 & 130.4/2 available in E70
panel & "PAN1 PS & PAN2 PS" in CCB2
panel).
10. If the above pressure switch is not picking up
within 35 Sec causes to disable VCB or if
VCB closes it will open after 2 seconds
11. If both Pantos are not raising from one cab,
Switch OFF& ON MCE and try and Try by
changing the cab
12. If VCB closes and then trips with the above
message, may be due to Pressure dropping
through VCB after closing VCB. Inform to
TLC & Record in Log book,
F0104P1 Loco XXXXX SS01 : FLG1:0041-Primary 1. Bring throttle to ‘0’ position.
Main Power voltage below min 2. If sudden BP pressure drops switch on flasher
CATENARY FLG2:0041-Primary light and act as G&SR .
VOLTAGE OUT OF voltage below min. 3. Acknowledge the fault by BPFA
LIMIT FLG1:0042-Primary 4. If ‘U’ meter is not deviating then either no
Watch Catenary voltage above max. tension or PT fuse blown off .Lower Panto
Voltmeter FLG2:0042-Primary once and raise the panto.
Close VCB When voltage above max. 5. When panto touches OHE, a minor spark with
Voltage is OK SLG1:0020-Primary ‘choo’ sound indicates Tension is available.
voltage < min. Stop the train and conform with TLC/TPC .
F0104P1 SLG2:0020-Primary 6. If there no OHE Wait for catenary voltage to
voltage < min. raise above17.5 KV but less than 29 Kv.
SLG1:0021-Primary 7. Ensure OHE voltage in Simulation Screen, If it
Page 07 of 114
voltage > max. is above 29 inform to TPC/TLC to reduce.
SLG2:0021-Primary After OHE voltage gets restored, reclose the
voltage > max. VCB and resume traction.
SLG2:0079-Ventilation 8. If OHE is available and ‘U’ meter not
bogie BUR-2 disturb deviating, Lower Panto and check PT
2Amps fuse in SB1 panel, renew with good
one after taking safety precautions.
9. If U meter deviates, check DDS messages . If
DDS message is SLG1-0020 isolate SR-1 by
opening MCB 127.1/1 & Switch 154-1 in SB1
or if the message is SLG2-0020 isolate SR-2
by opening MCE 127.1/2 in SB2 and switch
154-II position and try.
10. If the message from both SLG1 0020 &
SLG2 0020 it may be OHE problem, if OHE
supply is normal. Switch OFF & ON MCE
and try.
11.Try by changing panto.& Cab. If unsuccessful,
Contact TLC & Record in Log book.
F0104P1 Loco XXXXXSS01 In case of WAP-5 MU Operation with single
:Main Power operation.
“CATENARY 11. Bring throttle to ‘0’ position.
VOLTAGE OUT OF 12. Check the HV connecting cable between two
LIMIT” locos.
(From Slave loco 13. If HV cable damaged isolate slave loco
only and not from electrically by opening both isolators (by
master loco during pressing BPIso) and operate the loco as
WAP-5 MU single.
Operation With 14. Warning: Mechanical coupling of multi not to
Page 08 of 114
Single Panto) be opened as it will cause damage to the HV
cable.
15. If HV cable is OK, Follow above point no.2
to 10.
(From Slave loco only and not from master loco
during WAP-5 MU Operation With Single Panto)
F0105P1 Loco XXXXX SS01 : FLG1:0086-Dist.both trafo 1. VCB does not trips, Try to clear the block
Main Power oil circuits section if TE available or by coasting.
FLG2:0086-Dist.both trafo 2. If VCB trips, Bring throttle to ‘0’ position.
TRANSFORMER OIL oil circuits Acknowledge the fault by BPFA & close
TEMPERATURE OR SLG1:0019-Transformer VCB.
PRESSURE NOT temperature>limit 2(84 3. Check the oil level in both the expansion
OK Deg C) tanks of transformer and converters in
SLG2:0019-Transformer Machine rooms located near Oil Cooling
TE/BE reduction or temperature>limit 2(84 Deg Unit. It should be above Min Mark.
VCB trips C) 4. Check both Transformer oil pumps & OCBs
Try to close VCB if SLG1:0063-Transformer MCBs (62.1/1&, 59.1/1 in HB-1 & 62.1/2 &
open F0105P1 temperature>limit 1(80 Deg 59.1/2) in HB-2 Cubicle.
C) 5. Reset once if tripped after opening VCB &
SLG2:0063-Transformer try.
temperature>limit 1(80 Deg 6. If any MCB of above is repeatedly tripping or
C) Oil pumps/OCBs are not working, keep
concern MCB in open condition and isolate
concerned SR by changing 154 to I & open
MCB 127.1/1 (SB1), or 154 – II & open MCB
127.1/2 after opening VCB.
7. If MCBs are normal, ensure the working of
Transformer oil pumps & OCBs. Keep Loco
in idle mode for 10 minutes.
Page 09 of 114
Isolation Loco XXXXX SS01 : 8. If Main power isolated, Check DDS
Message Main Power messages, if SLG1:0019 Isolate SR1 &
MAIN POWER SLG2:0019 Isolate SR2.
ISOLATED. VCB 9. Switch OFF& ON MCE and try.
Inhibited Loco is 10. If unsuccessful, Ask relief Loco and Record
dead in Log book
F0106P1 Loco XXXXX SS01 : 1. Bring throttle to ‘0’ Acknowledge the fault by
Main Power BPFA
FILTER ON/OFF 2. Try to clear the block section by Coasting &
SLG1:0059-Contactor 8.1
CONTACTOR bring the loco / train to dead stop.
stuck on fatal SLG2:0059-
STUCK ON 3. Switch OFF & ON MCE and try.
Contactor 8.1 stuck on fatal
VCB will not close 4. If DDS message is SLG1-0059 isolate SR1
again F0106P1 by opening MCB 127.1/1 & 154-1 in SB1 &
try.
Isolation SS01 : Main Power 5. If unsuccessful, normalize the above if no
Message MAIN POWER abnormality in HF Ckt, Close FB coc, Trip
ISOLATED MCB 127.2/1 in SB-1 panel & switch OFF &
ON MCE and try. Ack. fault messages.
6. If successful clear section or work with
40KMPH.
7. After clearing section normalize FB coc and
MCB 127.2/1 & switch OFF & ON MCE and
try
8. If unsuccessful ask relief Loco & record in
Log book
F0107P1 Loco XXXXX SS01 : SLG1:0037- Pre charge 1. Bring throttle to ‘0’ Acknowledge the fault by
Main Power cont. stuck on fatal BPFA
PRECHARGE OR SLG2:0037- Pre charge 2. Try to clear the block section by Coasting &
MAIN cont. stuck on fatal bring the loco / train to dead stop.
Page 010 of 114
CONTACTOR 3. Switch OFF& ON MCE and try.
STUCK ON 4. If unsuccessful, check the back ground
Main converters message, SLG1 0037 or 0039 isolate SR1
blocked F0107P1 SLG1:0039- Converter by opening MCB 127.1/1 & 154-1 in SB1
contactor stuck on and close SR1 coc or if the message is
SLG2:0039- Converter SLG2-0037 or 39 isolate SR-2 by opening
contactor stuck on MCB 127.1/2 in SB2 and 154-II position
and close SR2 coc.
5. Switch OFF& ON MCE and try once again
Loco XXXXX SS01 : 6. Work the train with single Bogie if Load and
Main Power road permits then talk to TLC and act
MAIN POWER accordingly.
ISOLATED. VCB 7. If unsuccessful, Ask relief Loco and Record
inhibited Loco is in Log book.
dead
F0108P1 Loco XXXXX SS01 : SLG1:0025 – Primary 1. Bring throttle to ‘0’ position and press BPFA
Main Power current > max. 2. Don’t close VCB until you check OCR 78 &
PRIMARY OVER SLG2:0025 – Primary oil points in the Machine Room
CURRENT current > max. 3. Try to clear the block section by Coasting &
Check over current bring the loco / train to stop.
relay flag 4. Check the OCR 78 & Check the oil levels in
Close VCB after oil expansion tanks of Transformer and SRs
unlocking relay for sign of overheating/ sparking of
F0108P1 STB1:0002 – Primary connection, any abnormal raise / colour
current above max. change (black) / oil splash through vent pipe
of transformer and Machine room.
Loco XXXXX SS01 : 5. If any abnormality is noticed shut down the
Main Power Loco, use fire extinguishers if required and
MAIN POWER ask relief Loco.
Page 011 of 114
ISOLATED VCB 6. If no abnormality is noticed reset OCR 78 (
inhibited Loco is Mechanical Locking if provided) by moving
dead the screw clock wise provided on the front
side of the relay .The relay flag shall
disappear• and close VCB and work
onwards.
7. If not successful after making one attempt
then VCB will be inhibited
.9. Ask for relief Loco without losing time and
Record in Log book.
F0109P1 Loco XXXXX SS01 : SLG1:0024-BUR current > 1. Bring throttle to ‘0’ position. Acknowledge the
Main Power max. fault by BPFA
AUX. WINDING SLG2:0024-BUR current > 2. Close VCB and resume traction.
OVER CURRENT max. 3. If problem persists isolation message will
Try to close VCB appear, acknowledge by pressing enter
again button.
Loco XXXXX SS01 : 4. Switch OFF & ON the Control Electronics and
Main Power Try.
MAIN POWER 5. Check the back ground message & Isolate
ISOLATED BUR1 or 2 or 3 one by one by opening MCB
VCB inhibited Loco is 127.22/1 or 127.22/2 or 127.22/3 and try.
dead Before normalizing MCB switch off MCE.
6. If unsuccessful open MCB 127.1/1 & 154-I for
SR1, open MCB 127.1/2 & 154-II for SR2 and
try.
7. If unsuccessful ask relief Loco &record in Log
book.
Page 012 of 114
F0110P1 Loco XXXXX SS01 : FLG1: 0026 –Subsystem 1. Bring throttle to ‘0’ position. Ack. the fault by
Main Power 02 & 03 off BPFA
FATAL ERROR IN FLG2: 0026 –Subsystem 2. Try to clear the block section by Coasting &
MAIN 02 & 03 off bring the loco / train to dead stop.
CIRCUIT FLG1: 0027 –Subsystem 3. Check the back ground Message. and 154 in
Turn OFF the loco. 13 & 14 off normal
FLG2: 0027 –Subsystem 4. If MR / FP/ BP pressure drops with DDS
13 & 14 off messages SLG1/2: 0040 keep MPJ on ‘0’,
FLG1: 0028 –Processor switch off / ON MCE. Energize the Loco and
STB1 & STB2 off attend the leakages.
FLG2: 0028 – Processor5. Check MCBs in SB1/2 panels if found tripped;
STB1 & STB2 off reset the same or if MCB 127.24 tripped in
FLG1: 0029 – Processor SB2 isolate BUR-2& reset after switching off
HBB1 & HBB2 off MCE and try
FLG2: 0029 – Processor6. Check any MCBs tripped in HB1/2 panels,
HBB1& HBB2 off check concern auxiliary if any abnormalities
FLG1: 0030 – Processor do not reset the MCB and isolate its related
STB1 & HBB1 off Bogie. Switch off /ON MCE & try.
FLG2: 0030– Processor 7. If MCBs in HB1/2 panels are normal with
STB1 & HBB1 off “Con. oil temperature too high” from both SRs
FLG1: 0031 – Processor or both MCB s 59.1/1 & 59.1/2 alternatively
STB2 & HBB2 off tripping - isolate BUR1 or If MCBs in HB1/2
panels are normal with “Con. oil pressure not
ok” from both SRs / both MCBs 63.1/1 &
63.1/2 alternatively tripping - isolate BUR2
(in this cases, SR1 and then SR2 will be
isolated) - switch off /ON MCE & try
Loco XXXXX SS01 : FLG1: 0032 –Subsystem 8. In case of IGBT based BURs tripping with
Main Power 06 & 07 off
Page 013 of 114
MAIN POWER FLG2: 0032 –Subsystem Inverter fault and MCB 54.1/2 repeatedly
ISOLATED 06 & 07 off tripping or MRB2 found any abnormality,
VCB inhibited Loco is FLG1: 0033 –Subsystem switch OFF/ON MCE & clear section and
dead 06 & 08 off contact TLC
FLG2: 0033 –Subsystem 9. Messages from ASC1/2 or NSC1/2 like- Error
06 & 08 off MVB, Error BS/MUB Overload. Isolate
FLG1: 0034–Subsystem concern SR (trip MCB 127.1/1 & 154-I for
07 & 08 off SR1 and MCB 127.1/2 & 154-II for SR2) –
FLG2: 0034 –Subsystem MCE OFF/ON and try.
07 & 08 off 10. Messages related to Life sign missing from
any two of FLG1/2 or STB1/2 or HBB 1/2 or if
no abnormality - switch off /ON MCE and try.
11. If the back ground message reads inverter
over current or DC link over current, find out
the sequence of BURs isolation and act as
per procedure given at the end of ss01.
Page 014 of 114
12. (Additional Instructions for SS01) Procedure to be followed when ever two BURs are isolated in
following sequence when the back ground messages reads
BUR inverter over current or DC link Trip MCB 59.1/1, place 154 to ‘I’ and Switch OFF/ ON MCE. Close VCB.
over current - BUR1 first then BUR 2 If normal work with Bogie II .If trips again, Normalize MCB 59.1/1 & trip
are isolated Problem may be with MCB 59.1/2, place 154 to ‘II’ and Switch OFF & ON MCE. Close VCB.
OCB1 or OCB2 Work with Bogie ‘I’
BUR inverter over current or DC link Trip MCB 53.1/1, place 154 to ‘I’ and Switch OFF/ON MCE. Close VCB.
over current- BUR2 first then BUR1 If normal work with Bogie II.
are isolated Problem may be with Trip MCB 53.1/2 , place 154 to ‘II’ and Switch OFF/ ON MCE. Close
TMB1/TMB2 VCB. If normal work with Bogie I.
BUR inverter over current or DC link Trip MCBs 62.1/1, 63.1/1, place 154 to ‘I’ and Switch OFF/ON MCE.
over current- BUR2 first then BUR3 Close VCB. If normal work with Bogie II. Trip MCBs 62.1/2, 63.1/2, place
are isolated Problem may be with 154 to ‘II’ and Switch OFF & ON MCE. Close VCB. If normal work with
TR oil Pump 1 / 2 or TR Converter 1 / Bogie I.
2
BUR inverter over current or DC link Trip MCBs 47.1/1, 47.1/2 and Switch OFF & ON MCE. Close VCB. If
over current- BUR3 first then BUR2 VCB trips, Problem CHBA. Then trip VCB & MCB 100 (HB-2 Panel) and
are isolated Problem may be with normalize MCBs 47.1/1, 47.1/2. inform TLC & work without CHBA .If
MCP 1/ 2 or CHBA VCB does not trips after opening MCBs 47.1/1, 47.1/2.Find out defective
MCP and isolate the same.
BUR inverter over current or DC link Trip MCBs55.1/1, 55.1/2 and Switch OFF & ON MCE. Close VCB. If and
over current- BUR3 first then BUR1 work normally & inform to TLC When ever time permits ,Trip VCB ,find
are isolated Problem may be with out defective SCB and isolate the same.
Scavenger blowers 1 or 2
Note: 1. If the back ground messages are related to SR1/2, isolate related SR by opening MCB 127.1/1 for SR1
and MCB 127.1/2 for SR2 after switching off MCE & try. If unsuccessful, ask relief Loco and Record in Log book.
2. In case of MU Locos, if Leading Loco fails, place 154 on I &II position and clear section with leading Loco till the
battery voltage reaches 86v.
Page 015 of 114
F0404P1
Page 037 of 114
F0401P2 Loco XXXSS01: SLG1:0073 contactor 8.1 1. Acknowledge through BPFA.
Harmonic filter stuck on 2. Avoid brining Throttle to ‘0’. Do not open
FILTER SLG2:0073 contactor 8.1 VCB and Clear section and stop the train.
CONTACTOR 8.1 stuck on 3. Open & close VCB. If it is not possible to
STUCKON close VCB again. Switch OFF/ON MCE & try.
If VCB opens it 4. If unsuccessful, contact TLC and make a
will not close remark in log book.
again
F0401P2
F0504P1 Over Current In LSDJ, & BPFA 1. Acknowledge fault by pressing BPFA.
Hotel Load Circuit. will glow, LSFI will 2. Press BLDJ to close VCB.
Try to close the start blinking
VCB again
When both head lights is not glowing while working from cab2:Check MCB
310.1/2 provided in SB2 panel, if tripped, reset it and work further. If still
unsuccessful, open headlight cover and change the light assembly
2. Indication Lamps not Check MCB 127.91/1, if found tripped reset once directly & try. If unsuccessful,
glowing & Loco VCD Buzzer will not work –isolate VCD and continue traction by watching meters,
working normal from Gauges & Fault display and inform to TLC.
Cab-1 Leading.
3. Indication Lamps not Check MCB 127.91/2, if found tripped reset once directly & try. If unsuccessful,
glowing & Loco VCD Buzzer will not work –isolate VCD and continue traction by watching meters,
working normal from Gauges & Fault display and inform to TLC
Cab-2 Leading.
4. Bogie isolated while In locos provided with cab redundancy , if any particular bogie senses Catenary
trying to close VCB/On voltage out of range concerned bogie gets isolated while trying to close VCB / on
Run without VCB run after Acknowledgement . DDS message will be power Converter off.
tripping- “Catenary If Bogie required / time permits switch off/on MCE & try.
voltage out of range’.
Page 075 of 114
B.P not charging on Loco alone.
5. E 70 Brake system 1. Ensure DBC handle (A9) on run position leading Cab and Neutral position in
trail cab. Ensure ZBAN in OFF position in ‘A ‘panel.
2. ALP Emergency brake handle are in normal condition & both side angle
cocks closed condition.
3. If Air leakage from Emergency Exhaust (near ALP footsteps), Operate A9 to
emergency & try.
4. Ensure TPWS coc in both cabs are closed otherwise BP pressure will drop
on MPJ to F/R.
5. If Air leakage from ‘Z port’ (below Pneumatic panel and above bogie MR1
side) due to Emergency Valve (IP). Reset VCD if acted & try. Check MCB
127.7 MCB is normal.
6. Gently tap with wooden piece on left side top portion of E70 and try.
7. Switch off Control Electronics and switch ON once & try.
8. Change the cab and try, If unsuccessful, trip MCB 127.92 and try.
9. Drain out pressure completely and try.
10. If unsuccessful, ask relief loco..
6. Knorr’s Computer 1. Ensure Mode switch is in Lead position in Cab and trail in Rear Cab.
Controlled Brake (CCB 2. ALP Emergency brake handle are in normal condition & both side angle
1.5) cocks closed condition
3. Rear cab A9 Handle in Full service and Locked condition. PTDC handle in
position-III (centre).
4. Parking Brakes are released condition, if not release the same. PER Cos in
Horizontal position.
5. Penalty brakes will apply if any one of PB-PDS, PB-BUS, PB-R-COS is
isolated normalize the same.
6. Keep A-9 from RUN to FS. Wait for 10 seconds; then again keep it to RUN.
7. If Air leakage below Pneumatic panel and above bogie MR1 side is due to
Page 076 of 114
Emergency Valve (IP). Reset VCD if acted by Keeping A-9 to Emergency
and press BPVR & try.
8. Keep A-9 to Emergency (EMER) for 10 seconds and again keep to RUN
position & try.
9. Operate 74 coc (close & open) 2 or 3 times and try. Ack. the fault message
through BPFA.
10. Switch off Control Electronics and switch ON once & try.
11. Change the cab and try, If unsuccessful, trip 127.92 and try
12. If unsuccessful, clear section with PTDC mode and inform to TLC.
7. BP pressure not 1. Observe Brake Controller LCD display messages & follow in case of
Charging When Auto/A9 penalty.
Handle on ‘Run’ 2. Ensure cab set up is OK.( Auto/A9 handle position Locked in FS in rear Cab
Position in Lead and Mode switch in Lead position in Lead cab and Trail Position in rear Cab,
Cab.(CCB-2) ALP Emergency brake handle in both cabs and BP Angle Coc are closed)
3. Check Pneumatic Coc position -47 closed (Out), 136-open (Horizontal), 74-
open (Vertical) and PER-COS in closed (Horizontal) condition. Press Test
points in ‘BP- CP’ valve area and try.
4. Operate Auto handle to Emergency 2 or 3 times ( okay to Run) and try
5. Operate 74 coc ( close & open) 2 or 3 times and try. Ack. the fault message
through BPFA.
6. If unsuccessful, trip MCB 127.92 and try. , If unsuccessful, place 237.1 –
‘0’and try
7. Switch off/on MCE and try, If Unsuccessful try from rear cab. If MCB 127.7
trips, reset once.
8. If again Unsuccessful clear section with PTDC mode operation.
Note: If rear cab ‘Auto Brake handle’ in Emergency, Brake electronics
failure message will be displayed in some Locos.
Page 077 of 114
8. Trouble shooting for With SA-9.
Loco Brakes not 1. Operate SA-9 for 2 to 3 times. Ensure rear Cab SA9 in released condition.
releasing in 3Ø 2. Switch off Control Electronics and switch ON once.
Locomotive
3. If still unsuccessful, close 94 COCK and try and make remark in log book.
With A-9.
1. Ensure BP is 5 Kgs/cm2.
2. Operate C3W Distributor valve QRV (Quick Release Valve) available in
Pneumatic Panel.
3. Isolate C3W valve and operate QRV (Quickly Release Valve) and try.
4. If still unsuccessful, close Bogie COCs and after releasing BC pressure, open
and try.
Note : In case of Knorr brake system Press 20TP and 16 TP nipples in pneumatic
panel
8. Procedure for MCE Stop the train, MPJ-0, Open VCB & Lower Panto . Move BL Key ‘D’ to ’Off
‘OFF’: wait for 2 sec , Off’ to ’C’ 10 sec (observe SPM Display & DDS Display
blanked off) and ’C’-to off.
9. Operation of Rotary 152 (Failure mode operation): - Bring Throttle to ‘0’ and operate to ‘1’ position
Switches 152, 154,160 & for Failure mode operation.
237.1.in SB-1 154( Bogie cut-out):- On standstill , bring Throttle ‘0’ and MPJ-F /R, On run –
Open VCB and Change the switch to required position (I for Bogie1 or II for
Bogie2) after 10 sec concern Bogie will be isolated.
On trial / or if erroneous operation of 154 takes place (isolation of Bogie 1 / 2), to
restore rotate 154 to required position and switch OFF/ON MCE
160 (Configuration):- Loco on standstill condition and MPJ on ‘0’. Change 160–
Page 078 of 114
‘0’ to ‘1’ (MPS of Loco) / ‘1’ to ‘0’ position (Max 15 Kmph).
237.1 Vigilance device cut-off:- Loco on standstill condition and Change the
switch to ‘0’ position. VCD will be isolated.
10. Resetting of MCB: (HB1/2 MCBs - open VCB, SB1/2 Electronics related MCBs & 110 - switch off
MCE).
ABB make MCB - To reset MCB, the marking in the tripping mechanism below
the switch knob should be made vertical for all the three phases before resetting
the MCB knob. Lift the Knob with both hands.
MG and Schneider MCB:- For resetting a tripped breaker, first move the switch
to ‘OFF’ position and then switch it ON’.
11. Important Points to 1. Ensure that all sand boxes are filled with dry fine sand and sanders are
remember working properly.
2. Check Torque arm bolts for each TM, Traction link for any abnormality and
their all bolts are intact.
3. Read and note down the fault message (Example: F0201P1). Acknowledge
the fault message by BPFA (Bring Throttle-‘0’ Ack fault messages,otherwise
protective action remains in force for P1 fault)
4. To view back ground Message select HOME -3rd (Process information) -
2nd (commissioning Data) -1st (Diagnostic Data set) options & Press Enter
on each. Contact TLC/SSE for advice only with list of back ground
messages for particular fault.
5. After moving BL key to D mode, if Pilot lamps are not glowing & CE not
getting on, press 126 & 218 Knobs in SB1.
6. On Panto raise (ZPT-“UP”) command, if display remains showing FLG- 504,
press 130.1 relay plunger in SB2 to get FLG-550.
7. On VCB close (BLDJ –ON) command, if Display remains showing FLG-550,
press 136.4 relay plunger SB1 & try.
Page 079 of 114
8. While on run, if bogie meter suddenly not respond and DDS reads TE in Kn,
Bring Throttle to ‘0’, trip VCB and reclose VCB.
9. While on run, if bogie isolated without any message, at convent place, switch
OFF/ON MCE to bring isolated bogie in to service.
10. If ASC1/2 :0052/0053/0054 Error Tacho generator 1/2/3 permanent fault is
available in any one Bogie and switch off /on MCE for other reasons may
cause to develop “ speed not increasing more than 1 kmph with heavy jerk”.
12. Points to remember in 1. SR1 and SR2 cut out cocks are in closed condition since converter
IGBT locos contactors are Electromagnetic/ Motorized Contactors.
2. Water with /glycol mixture / Antifrogen N as a cooling medium BHEL /ABB /
Bombardier makes IGBT SRs. Its level between Min-Max.
3. In BHEL IGBT SR ‘s are provided Locos an additional MCB provided for SR
coolant pump and Located below the SR coolant Pump .
4. In some IGBT locos, Due to space consistent the message for isolation of TM
will be display in SS-04 & SS-05 fault messages.
5. BHEL IGBT Locos controlled by TCN based network .Isolation of cab due
to card failure will not take place.
The messages in BHEL make (IGBT + TCN based network) Locos will be
displayed as given below (Example: ICP1 instead of FLG1).
Addl. fault Messages in SR 1/2 of MICAS with ABB or BHEL or Medha & BT -IGBT fitted Locos
Fault no. Fault message DDS Messages Action to be taken by crew
F0403P2 / DCU2:0097-MC1 1. Acknowledge the fault by pressing BPFA &
Motor1-Bogie1
F0211P2 / Bogie 1 Isolated resume normal operation.
Isolated
F0208P2 2. Inform TLC and record in the logbook.
F0404P2 DCU1:0098-MC2 1. Acknowledge the fault by pressing BPFA &
Motor2-Bogie1
/F0212P2 / Bogie 1 Isolated resume normal operation.
Isolated
F0209P2 2. Inform TLC and record in the logbook.
F0405P2 DCU3:0099-MC3 1. Acknowledge the fault by pressing BPFA &
Motor3-Bogie1
/F0213P2 Bogie 1 Isolated resume normal operation.
Isolated
/ F0210P2 2. Inform TLC and record in the logbook.
F0406P2 Line Converter DCU1:0100-LC1 1. Acknowledge the fault by pressing BPFA &
/ F0214P2 1-Bogie1 Bogie 1 Isolated resume normal operation.
/ F0211P2 Isolated 2. Inform TLC and record in the logbook.
F0407P2 / DCU2:0101-LC2 1. Acknowledge the fault by pressing BPFA & resume
Line Converter
F0215P2/ Bogie 1 Isolated normal operation.
2-Bogie1
F0212P2 2. Inform TLC and record in the logbook.
Isolated
F0503P2 DCU5:0097-MC1 1. Acknowledge the fault by pressing BPFA & resume
Motor1-Bogie2
/F0311P2 Bogie 2 Isolated normal operation.
Isolated
/ F0308P2 2. Inform TLC and record in the logbook.
F0504P2 / DCU4:0098-MC2 1. Acknowledge the fault by pressing BPFA &
Motor2-Bogie2
F0312P2 / Bogie 2 Isolated resume normal operation.
Isolated
F0309P2 2. Inform TLC and record in the logbook.
F0505P2 DCU6:0099-MC3 1. Acknowledge the fault by pressing BPFA &
Motor3-Bogie2
/ F0313P2 Bogie 2 Isolated resume normal operation.
Isolated
F0310P2 2. . Inform TLC and record in the logbook.
Page 081 of 114
F0506P2 / Line Converter DCU4:0100-LC1 1. Acknowledge the fault by pressing BPFA &
F0314P2 1-Bogie2 Bogie 2 Isolated resume normal operation.
/ F0311P2 Isolated 2. Inform TLC and record in the logbook.
F0507P2 Line Converter DCU6:0101-LC2 1. Acknowledge the fault by pressing BPFA &
/ F0315P2/ 2-Bogie2 Bogie 2 Isolated resume normal operation.
F0312P2 Isolated 2. Inform TLC and record in the logbook.
Loco XXXXX LSFI 1. Acknowledge the fault by pressing BPFA.
SS02 : Traction FLG2:0068-Timeout 2. If Load /Road permits, Place 154 on ‘1’ on VCB
Bogie 1 LINE LC pulse bogie1 open condition & close VCB. press ‘Enter’
F0207P2 in CONVERTER VCI:0066-Lifesign 3. Resume normal operation with half TE/BE
BT make ISOLATED from V1DX1 missing 4. If Load/Road does not permit / at convenient
SR BOGIE VCI:0067-Lifesign station, ensure 154-Normal and Switch OFF &
1Reduced from V1DX2 missing ON MCE & try.
Traction/ 5. If unsuccessful Inform TLC and record in the
Braking effort logbook
LSFI 1. Acknowledge the fault by pressing BPFA .
LINE
FLG1:0069-Timeout 2. If Load /Road permits, Place 154 on ‘II’ on VCB
CONVERTER
LC pulse bogie2 open condition & close VCB. press ‘Enter’
F0307P2 in ISOLATED
VCI:0068-Lifesign 3. Resume normal operation with half TE/BE
BT make BOGIE 2
from V2DX1 missing 4. If Load/Road does not permit / at convenient
SR Reduced
VCI:0069-Lifesign station, ensure 154-Normal and Switch OFF &
Traction/
from V2DX2 missing ON MCE & try.If unsuccessful Inform TLC and
Braking effort
record in the logbook
Page 082 of 114
Fault Messages in TCN & IGBT SR fitted BHEL Locos , except SS13, SS14,SS17& SS18 other subsystem
faults Trouble shooting procedure is same as MICAS GTO based Locos
SS13 – CAB1
Fault No Fault Message Effect/ DDS Messages Action to be taken by crew
F1301P1 SS13: Cab1 LSFI Driving from Cab 1 1. Press BPFA. Clear section with normal
DISTURBANCE still possible; operation.
IN ICP1:0006-Lifesign from 2. Switch OFF the Electronics and Switch it ON.
PROCESSOR RBU2 missing Raise panto, close VCB and resume Traction.
RBU2 ICP2:0006-Lifesign from 3. If the Fault still persists acknowledge the fault
RBU2 missing and Drive normally from any CAB.
RBU2:0001-Lifesign from
ICP missing
F1302P1 SS13: Cab 1 LSFI Driving from Cab 1 1. Press BPFA. Clear section with normal
DISTURBANCE still possible; operation.
IN ICP1:0004-Lifesign from 2. Switch OFF the Electronics and Switch it ON.
PROCESSOR RBU1 missing Raise panto, close VCB and resume traction.
RBU1 ICP2:0004-Lifesign from 3. If the Fault still persists acknowledge the fault
RBU1 missing and Drive normally from any CAB.
RBU1:0001-Lifesign from 4. CAB-1 TE/BE meters will not be available.
ICP missing 5. Through CAB-1 loco will be operated in failure
Mode(Auto activation)
6. Through CAB-2 normal loco operation
F1303P1 REVERSER Cab 1 may get isolated, 1. Bring Throttle to ‘0’, Acknowledge through
DEFECTIVE drive from BPFA
Drive from cab 2 2. Operate Reverser 2-3 times and try.
cab 2 ICP1:0025-Cab1 forward 3. If unsuccessful try to clear the block section by
& revers selected coasting. Switch OFF and ON MCE and try.
ICP2:0025-Cab1 forward 4. If the same message repeats, change to Cab-2
Page 083 of 114
& revers selected and work further with rear cab.
5. Inform TLC and make a remark in logbook.
F1304P1 SS13:Cab 1 Driving still possible 1. Switch OFF the Electronics and Switch it ON.
RBU1 RIOM Raise panto, close VCB and resume traction.
EXTENSION 2. If the same message repeats, change to Cab-2.
FAULT Inform TLC and record in Loco logbook.
3. Read out DDS messages and check which
RIOM extension to replace
F1305P1 SS13:Cab 1 Driving still possible 1. Switch OFF the Electronics and Switch it ON
RBU2 RIOM once again. Raise panto, close VCB and resume
EXTENSION traction.
FAULT 2. If the same message repeats, change to Cab-2.
Inform TLC and record in Loco log book.
3. Read out DDS messages and check which
RIOM extension to replace.
SS14 – CAB2
F1401P1 SS14: Cab 2 ICP1:0007-Lifesign from 1. Switch OFF the Electronics and Switch it ON.
DISTURBANCE RBU4 missing Raise panto, close VCB and resume Traction.
IN ICP2:0007-Lifesign from 2. If the Fault still persists acknowledge the fault
PROCESSOR RBU4 missing and Drive normally from any CAB
RBU4, RBU4:0001-Lifesign from
ICP missing
F1402P1 SS14: Cab 2 ICP1:0005-Lifesign from 1. Switch OFF the Electronics and Switch it ON.
DISTURBANCE RBU3 missingICP2:0005- Raise panto, close VCB and resume traction.
IN Lifesign from RBU3 2. If the Fault still persists acknowledge the fault
PROCESSOR missingRBU3:0001- and Drive normally from any CAB.
RBU3 Lifesign from ICP missing 3. CAB-2 TE/BE meters will not be available.
Driving from 4. Through CAB-2 loco will be operated in failure
Page 084 of 114
Cab 2 still Mode only.
possible, 5. Through CAB-1 normal loco operation.
F1403 P1 REVERSER ICP1:0045-Cab2 forward 1. Bring Throttle to ‘0’, Acknowledge through
DEFECTIVE & revers selected BPFA
Drive from ICP2:0045-Cab2 forward 2. Operate Reverser 2-3 times and try.
cab 1 & revers selected 3. If unsuccessful try to clear the block section by
coasting .Switch OFF and ON MCE and try.
4. If the same message repeats, change to Cab-1
and work further with rear cab.
5. Inform TLC and make a remark in logbook
F1404P1 SS14:Cab 2 1. Switch OFF the Electronics and Switch it ON
RBU3 RIOM Raise panto, close VCB and resume traction.
EXTENSION 2. If the same message repeats, change to Cab-1.
FAULT Inform TLC and record in Loco logbook.
3. Read out DDS messages and check which
RIOM extension to replace.
F1405P1 SS14:Cab 2 1. Switch OFF the Electronics and Switch it ON
RBU4 RIOM once again. Raise panto, close VCB and resume
EXTENSION traction
FAULT
SS17 –ICP1
F1701P1 SS17: ICP2:0001-Lifesign from 1. I.CP1 will be isolated 1. Resume Normal
Processor ICP1 ICP1 missing Traction.
DISTURBANCE 2. Inform TLC and record in the logbook.
IN 3.
PROCESSOR
ICP2
Page 085 of 114
SS17: ICP2 is isolated 4. Multiple Operations is not possible.
Processor ICP1, 5. Resume normal traction.
ICP2 6. Inform TLC and record in the logbook.
ISOLATED 7.
Press<Enter>
F1702P1,F1703P1,F1704P1 Trouble shooting procedure is same as MICAS GTO based Locos
SS18 –ICP2
SS18: ICP1:0001-Lifesign from 1. Switch OFF the Electronics and Switch it ON
F1801P1 Processor ICP2 ICP2 missing once again.
DISTURBANCE ICP2:0001-Lifesign from 2.
IN ICP1 missing
PROCESSOR
ICP1
SS18: ICP1 will be isolated 3.If the same message repeats resume normal
Processor ICP2 traction.
ICP1 4. No regenerative braking power is available. So
ISOLATED control the train/loco with help of pneumatic
Press<Enter> brake (A9 or SA9)
5. Inform TLC and record in the logbook.
F1782P1,F1803P1,F1804P1 Trouble shooting procedure is same as MICAS GTO based Locos
Page 086 of 114
Addl./ Change in fault Messages of IGBT fitted Medha Locos, except SS13, SS14,SS17& SS18 other
subsystem faults Trouble shooting procedure is same as MICAS GTO based Locos
SS13-CAB1
Fault No Fault Message Lamp & DDS message Action to be taken by crew
F1303P1 Loco XXXXX Driving from Cab 1 still 1. Operate Reverser 2-3 times .Switch OFF the
SS13: Cab 1 possible; Electronics and Switch it ON once again. Raise
REVERSER MCC1/2: simulataneously panto, close VCB and resume traction.
DEFECTIVE CAB1 FORWARD & 2. If the same message repeats, change to Cab-2.
Drive from cab 2 REVERSE SELECTED. Inform TLC and record in Loco logbook.
F1303P1 On Ack. LSFI glows
continuously
F1304P1 Loco XXXXX 1. Throttle is to be moved to center.
SS13: Cab 1 MCC1/2: simulataneously 2. Switch OFF the Electronics and switch it ON, if
START RUN CAB1 TRACTION & message is repeats, try from other CAB to clear
INTERLOCK BRAKING SELECTED the section.
Simultaneous
Motoring & On Ack. LSFI glows
Braking continuously
command from
Throttle of CAB1
F1304P1
F1301P2 Loco XXXXX MCC1/2: Communication 1. Record the fault in the log book and continue
SS13: Cab 1 between MCC & DIP1 is Normal operation
DISTURBANCE failed in VCU1 Note: Following functions will not work: Constant
IN Speed control will not work from CAB1,Simulation
PROCESSOR mode will not work, PVEF will not functions from
-DIP1 F1301P2 CAB1, 47.1/1 MCB tripping cannot be detected
Page 087 of 114
F1302P2 Loco XXXXX MCC1/2:Communication 3. 1. Record the fault in the log book and continue
SS13: Cab 1 between MCC & DIP2 is Normal operation
DISTURBANCE failed in VCU1 4. Note: Following functions will not work:
IN 5. MCBs(53.1/1,54.1/1, 55.1/1,56.1/1,59.1/1)
PROCESSOR tripping cannot be detected
-DIP2 F1302P2
F1303P2 Loco XXXXX MCC1/2:Communication 1. 1. Record the fault in the log book and continue
SS13: Cab 1 between MCC & DIP3 is Normal operation
DISTURBANCE failed in VCU1 2. Note: Following functions will not work: Earth
IN Faults(control, Filter,415_110) cannot be
PROCESSOR detected, MCBs(62.1/1,63.1/1) tripping cannot
-DIP3 F1303P2 be detected
F1304P2 Loco XXXXX MCC1/2:Communication 1. Record the fault in the log book and continue
SS13: Cab 1 between MCC & DIP4 is Normal operation
DISTURBANCE failed in VCU1
IN
PROCESSOR
-DIP4 F1304P2
F1305P2 Loco XXXXX MCC1/2:Communication 1. Record the fault in the log book and continue
SS13: Cab 1 between MCC & DOP1 is Normal operation
DISTURBANCE failed in VCU1 2. Note: Lamp indications will not work, Lamp
IN indications can be seen on TFT display unit.
PROCESSOR
-DOP1 F1305P2
F1306P2 Loco XXXXX MCC1/2:Communication 1. Record the fault in the log book and continue
SS13: Cab 1 between MCC & DOP2 is Normal operation
DISTURBANCE failed in VCU1 2. Note: Air dryer will not work. Isolate Air dryers
IN and inform to TLC.
PROCESSOR
Page 088 of 114
-DOP2 F1306P2
F1307P2 Loco XXXXX MCC1/2:Communication 1. Record the fault in the log book and continue
SS13: Cab 1 between MCC & DOP3 is Normal operation
DISTURBANCE failed in VCU1
IN
PROCESSOR
-DOP3
F1307P2
SS14 – CAB-2
F1403P1 Loco XXXXX LSFI MCC1/2: 1. Operate Reverser 2-3 times .Switch OFF the
SS14: Cab 2 simulataneously CAB1 Electronics and Switch it ON once again. Raise
REVERSER FORWARD & panto, close VCB and resume traction.
DEFECTIVE REVERSE SELECTED 2. If the same message repeats, change to Cab-1.
Drive from cab 1 3. Inform TLC & record in logbook.
F1403P1
F1404P1 Loco XXXXX LSFI MCC1/2: 1. Throttle is to be moved to center.
SS14: Cab 2 simulataneously CAB1 2. Switch OFF the Electronics and switch ON, if
START RUN TRACTION & message is repeats, try from other CAB to clear
INTERLOCK BRAKING SELECTED the section.
Simultaneous
Motoring &
Braking
command from
Throttle of CAB2
F1401P2 Loco XXXXX MCC1/2: Communication 1. Record the fault in the log book and continue
SS14: Cab 2 between MCC & DIP1 is Normal operation
DISTURBANCE failed in VCU2 Note: Following functions will not work: Constant
Page 089 of 114
IN Speed control will not work from CAB2, PVEF will
PROCESSOR not function from CAB2, MCBs(47.1/2,54.1/2,59.1/2)
-DIP1 F1401P2 tripping cannot be detected
F1402P2 Loco XXXXX MCC1/2:Communication 1. Record the fault in the log book and continue
SS14: Cab 2 between MCC & DIP2 is Normal operation
DISTURBANCE failed in VCU2 2. Note: Following functions will not work:
IN MCBs(53.1/2,55.1/2,56.1/2) tripping cannot be
PROCESSOR detected.
-DIP2 F1402P2
F1403P2 Loco XXXXX MCC1/2:Communication 1. Record the fault in the log book and continue
SS14: Cab 2 between MCC & DIP3 is Normal operation
DISTURBANCE failed in VCU2 2. Note: Following functions will not work:
IN 3. Smog warn can not be detected,
PROCESSOR MCBs(62.1/2,63.1/2) tripping can not be
-DIP3 F1403P2
detected
F1404P2 Loco XXXXX MCC1/2:Communication 1. Record the fault in the log book and continue
SS14: Cab 2 between MCC & DIP4 is Normal operation
DISTURBANCE failed in VCU2
IN
PROCESSOR -
DIP4 F1404P2
F1405P2 Loco XXXXX MCC1/2:Communication 1. Record the fault in the log book
SS14: Cab 2 between MCC & DOP1 is 2. ZPT switch is moved to Dn position. And Panto
DISTURBANCE failed in VCU2 Selection switch(129.1) in Pneumatic panel
IN should be kept in position 1. and ZPT is moved
PROCESSOR to Up position and check the Panto 2 is raised
-DOP1 F1405P2 and continue Normal operation
3. Note: Lamp indications will not work, Lamp
Page 090 of 114
indications can be seen on TFT display unit
Panto 2 cannot be raised.
F1406P2 Loco XXXXX MCC1/2:Communication 1. Record the fault in the log book.
SS14: Cab 2 between MCC & DOP2 is 2. ZPT switch is moved to Dn position. And Panto
DISTURBANCE failed in VCU2 3. Selection switch(129.1) in Pneumatic panel
IN should bekept in position 2. and ZPT is moved
PROCESSOR to Up position and check the Panto 2 is raised
-DOP2 F1406P2 and continue Normal operation
Note : Panto 1 can not be raised Sanding valves will
not work
F1407P2 Loco XXXXX MCC1/2:Communication 1. Record the fault in the log book and continue
SS14: Cab 2 between MCC & DOP3 is Normal operation
DISTURBANCE failed in VCU2
IN
PROCESSOR -
DOP3
F1407P2
Note: If Cab-1 or Cab-2 get hanged and not getting activated after making Control Electronics OFF and ON, then
check all MCBs in SB-1 and SB-2 and reset it if found tripped.
Page 091 of 114
SS17 –MCC1
F1701P1 Loco XXX SS17: MCC2: 1. Resume Normal Traction.
Processor MCC1 COMMUNICATION 2. Inform TLC and record in the logbook.
DISTURBANCE IN WITH MCC1 IS FAILED
PROCESSOR MCC1
MCC1will be isolated
F1701P1
Loco XXX SS17: LSFI MCC1 is isolated 1. Resume Normal Traction.
Processor MCC1 2. Inform TLC and record in the logbook
MCC1 ISOLATED , 3. Note: Only failure mode operation is
Refer to driver’s possible from CAB1, TE/BE meters will not
manual work in CAB1, the TE/BE % values can be
Press<Enter> seen through display
F1703P1 Loco XXX S17: MCC1/2: CAB1 ANGLE 1. Bring TE/BE Throttle to ‘0’.
Processor MCC1 TRANSMITTER FAILED 2. Acknowledge the Fault with illuminated
FAULT IN ANGLE button BPFA.
TRANSMITTER OF 3. Drive loco in Failure Mode Operation (by
THROTTLE operating Rotating Switch 152 from ‘0’ to ‘1’
Bring TE/BE Throttle position) located in SB1 panel.
to zero 4. Resume normal traction with 152 switch in
Operate switch failure failure mode position. If not success,
mode operate switch 152 (SB-1) 2-3 times.
F1703P1 5. Switch OFF the control electronics.
6. Try from rear cab. If not success, inform
TLC and record in the logbook.
F1704P1 Loco XXX SS17: LSFI Panto will not rise 1. Bring TE/BE Throttle to ‘0’.
Processor MCC1 2. Switch OFF the control electronics.
SIMULATION MCC1/2: SIMULATION 3. Check if Simulation key 179 in SB1 panel is
Page 092 of 114
SWITCH POSITION FAULT on ‘0’ position. If not, operate it from ‘1’ to ‘0’
NOT MATCHING position.
Check simulation key 4. Resume Normal Traction.
on 5. Inform TLC and record in the logbook.
master/slave
F1704P1
F1701P2 Loco XXX SS17: DDS will not stored in 1. 1. Resume Normal Traction.
Processor MCC1 DMC1, 2. 2. Inform TLC and record in the logbook.
DISTURBANCE IN DDS will store in DMC2
PROCESSOR DMC MCC2:
1 COMMUNICATION
DMC 1 will be isolated BETWEEN MCC1 &
No fault data will be DMC1 IS FAILED
stored in DMC1
Press<Enter>
F1701P2
SS18 –MCC2
F1801P1 Loco XXX SS18: MCC1: 1. Switch OFF the Electronics and Switch it ON
Processor MCC2 COMMUNICATION once again.
DISTURBANCE IN WITH MCC2 IS FAILED
PROCESSOR
MCC2, MCC2will be
isolated F1801P1
Loco XXX SS18: LSFI 1. If the same message repeats resume normal
Processor MCC2 traction.
FLG2 ISOLATED MCC2 is isolated, 2. No regenerative braking power is available.
Refer to driver’s So control the train/loco with help of
manual pneumatic brake (A9 or SA9).When apply A9
Page 093 of 114
Press<Enter> insure TE/BE Throttle to ‘0’ position.
3. Inform TLC and record in the logbook.
Note: Only failure mode operation is possible
from CAB2, TE/BE meters will not work in CAB2,
the TE/BE % values can be seen through display
,Regenerative Brake not available
F1803P1 Loco XXX SS18: MCC1/2: CAB2 ANGLE 1. Bring TE/BE Throttle to ‘0’.
Processor MCC2 TRANSMITTER 2. Acknowledge the Fault with illuminated
FAULT IN ANGLE FAILED button BPFA.
TRANSMITTER OF 3. Drive loco in Failure Mode Operation (by
THROTTLE operating Rotating Switch 152 from ‘0’ to ‘1’
Bring TE/BE Throttle position) located in SB1panel.
to zero 4. Resume normal traction with 152 switch in
Operate switch failure failure mode position. If not success ,
mode operate switch 152 (SB-1) 2-3 times.
F1803P1 5. Switch OFF the control electronics.
6. Try from rear cab. If not success, inform TLC
and record in the logbook.
F1804P1 Loco XXX SS18: LSFI Panto will not rise 1. Bring TE/BE Throttle to ‘0’.
Processor MCC2 2. Switch OFF the control electronics.
SIMULATION MCC1/2: SIMULATION 3. Check if Simulation key 179 in SB1 panel is
SWITCH POSITION FAULT on ‘0’ position. If not, operate it from ‘1’ to ‘0’
NOT MATCHING position.
Check simulation key 4. Resume Normal Traction. & Inform TLC and
on master/slave record in the logbook.
F1804P1
F1801P2 Loco XXX SS18: DDS will not store in 1. Resume Normal Traction.
Processor MCC2 2. Inform TLC and record in the logbook.
Page 094 of 114
DISTURBANCE IN DMC2,
PROCESSOR DMC 2
DMC 2 will be isolated DDS will store in DMC1
No fault data will be MCC1:
stored in COMMUNICATION
DMC2 BETWEEN MCC2 &
F1801P2 DMC2
IS FAILED