- To set makers -
Please see to it that this manual is supplied to the inverter’s end user, along with the instruction manual
E6581158.
E6581225
■Safety precautions
Before reading this manual, please read the following instructions in addition to “I. Safety Precautions,” of the
instruction manual E6581158.
■General Operation
Danger
• Circuit boards are exposed when the front cover is removed. So do not detach the
Mandatory
front cover when the inverter is energized or within 10 minutes after power is turned
off. Doing so could result in electric shock.
■Transportation
Warning
• When handling the inverter unit, hold it by both the sides firmly. If you hold it by the
Mandatory
fins at the upper and lower parts, you could get injured.
1
E6581225
■Exterior Features
(5)
TOSHIBA
(4) (1)
(3) 0.0 Mode key
(2) ▲ MODE
▼ ENT
Enter key
CHARGE lamp
Side view
(7)
2
E6581225
Screw
Screw
Screw
Screw
Screw
Screw
3
E6581225
■Wiring diagram
(6)
(6)
(5)
Cautions
• Circuit boards are exposed when the front cover is removed. Since high voltages are applied to some parts
of the circuit board, read Section 2.1, “Cautions on wiring,” of the instruction manual E6581158 carefully
before wiring.
When connecting cables, take care not to damage the circuit board with a screwdriver or a similar tool.
• To connect the power cable (to the manual power ON-OFF switch), torque the terminal screw to 1.7N·m
(recommended). (M4 screw)
• Never turn on the power ON-OFF switch before attaching the front cover.
Or you could get a shock.
The main circuit terminal board (input power cable) has terminals of a cable pinch type.
Before connecting a cable, strip off its sheath to a length of 10mm or so. Torque: 1.7N·m
Approx. 10mm
4
E6581225
< WN type : Sink logic > < WP type : Source logic >
P24
PP VIB CC PP VIB CC
Blue
Fw
Fw
0
0
Operation ON-OFF Operation ON-OFF
rotary switch rotary switch
Note: The colors indicated in the above figure refer to the colors of cables.
■Installation environment
• Operate in areas where ambient temperature ranges from -10°C to
10cm or more +40°C.
• Install the inverter in a well-ventilated place and mount it on a flat metal
plate in portrait orientation. Install the inverter so that it is not inclined
VFS11
5cm or more 5cm or more more than ±10° from the vertical.
• Leave a space of 10cm or more on the upper and lower sides of the
inverter, and a space of 5cm or more on each side.
• The inverter has a built-in cooling fan. The cooling fan has a useful life
of approximately 30,000 hours (2 to 3 years when operated
10cm or more
continuously), so it needs to be replaced periodically. The inverter has a
built-in cooling fan. (Single/three-phase 240V-0.75kW models and
smaller are not equipped with cooling fans.)
If the cooling fan does not operate normally, the temperatures of the
internal electrical components will rise high, and as a result their lives
will be shortened.
So inspect it periodically.
5
E6581225
■Outside dimensions
2-R2.75
W1 (Installation dimension) 9
W
14
D
6
E6581225
■Specifications
Item Specification
Voltage class 1-phase 240V class/3-phase 240V class/3-phase 500V class
Applicable motor (kW) 0.2 0.4 0.75 1.5 2.2 4.0
Voltage class Model number VFS11S-/VFS11-
Model
3-phase 240V - 3.3 (3.3) 4.8 (4.4) 8.0 (7.9) 11.0 (10.0) 17.5 (16.4)
Note 2:
3-phase 500V - - 2.3 (2.1) 4.1 (3.7) 5.5 (5.0) 9.5 (8.6)
Output voltage Note 3: 240V class: 3-phase 200 to 240V, 500V class: 3-phase 380 to 500V
Overload current rating 150%-1min., 200%-0.5 sec. (50%-reduction value)
240V class: 1-phase/3-phase 200 to 240V-50/60Hz,
supply
Power
Voltage-frequency
500V class: 3-phase 380 to 500V-50/60Hz
Allowable fluctuation Voltage+10%, -15% Note 4:, Frequency±5%
Totally enclosed type (JEM1030) compliant with IP54/possible to bring into compliance
Protective method
with IP55 Note 5:
Self-cooled (with a built-in cooling fan. 1-phase/3-phase 240V-0.75kW or smaller:
Cooling method
Cooling fan not provided)
Color Munsel 5Y-8/0.5
Built-in filter 1-phase & 500V class: High-attenuation EMI filter, 3-phase 240V class: Standard filter
Indoor type. Altitude: Not more than 1000m.
Environments
Use environments
Place free from corrosive and explosive gases
Ambient temperature -10 to +40℃
Storage temperature -25 to +70℃
Relative humidity 20 to 93%
Vibration 5.9m/s2 or less (10 to 55Hz)
Note 1: Capacity is calculated at 220V for the 240V models and at 440V for the 500V models.
Note 2: Indicates rated output current setting when the PWM carrier frequency (parameter F300) is 4kHz or less.
The values between parentheses refer to output currents at PWM carrier frequencies of over 4kHz. They
need to be reduced further at frequencies over 12kHz (If a motor cable over 30m in length is used, it is
necessary to reduce them more. This means that the lives of the internal components will be shortened).
When the input power voltage of the 500V class model exceeds 480V, it is necessary to further reduce
the setting. The default setting of the PWM carrier frequency is 12kHz.
Note 3: The maximum output voltage is equal to the input supply voltage.
Note 4: ±10% when the inverter is operated continuously (under a load of 100%).
Note 5: IP54-compliant structures refer to structures that protect the contents from dust and harmful effects of
water that drops from every direction.
The inverter can be brought into compliance with IP55 specifications by making the wiring port
watertight.
(IP55-compliant structures refer to structures that protect the contents from dust and harmful effects of
water that comes in a jet from every direction.)
To bring the inverter into compliance with IP-55, use PG screw type cable grounds. Among cable
grounds available are skin-top grounds manufactured by LAPP (Germany).
When using this type of grounds, use them in combination with lock nuts specified below.
Cable port Cable ground Cable ground(EMC-compliant) Lock nut
φ19 hole MS11 MS-SC11 SM-11
φ21 hole MS13.5 MS-SC13.5 SM-13.5
φ23 hole MS16 MS-SC16 SM16
Note 6: For control specifications, parameters and functions, refer to the instruction manual E6581158.
Note 7: The factory default settings of the following parameters are different from those of the VFS-11 standard
type.
Title Function Standard VF-S11 Totally enclosed type VF-S11
cmod Command mode selection 1 0
fmod Frequency setting mode selection 0 2
Note 8: The inverter has a built-in cooling fan. The cooling fan has a useful life of approximately 30,000 hours (2
to 3 years when operated continuously), so it needs to be replaced periodically.
(Single/three-phase 240V-0.75kW models and smaller are not equipped with cooling fans.)
If the cooling fan does not operate normally, the temperatures of the internal electrical components will
rise high, and as a result their lives will be shortened. So inspect it periodically.
Note 9: The manual power ON-OFF switch has a useful life of approximately 5 years (if operated 12 hours per
day at an average yearly ambient temperature of 30°C), so it needs to be replaced periodically.