This document provides a supplementary instruction manual for a Toshiba Totally-Enclosed Box Type Inverter model TOSVERT VF-S11. It describes additional safety precautions and exterior features of the inverter, including the operation panel, manual power switch, wiring ports, and terminal boards. Wiring diagrams and cautions for connecting cables are also included. The manual is intended to be used along with the primary instruction manual E6581158.

Uploaded by

Doni Wandoni
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
176 views8 pages

Instruction Manual (Supplementary) Totally-Enclosed Box Type Inverter

This document provides a supplementary instruction manual for a Toshiba Totally-Enclosed Box Type Inverter model TOSVERT VF-S11. It describes additional safety precautions and exterior features of the inverter, including the operation panel, manual power switch, wiring ports, and terminal boards. Wiring diagrams and cautions for connecting cables are also included. The manual is intended to be used along with the primary instruction manual E6581158.

Uploaded by

Doni Wandoni
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

E6581225②

Instruction Manual (Supplementary)


Totally-Enclosed Box Type Inverter
TOSVERT VF-S11
Thank you for purchasing a Toshiba “Totally-enclosed box type TOSVERT VF-S11 series inverter.”
This Manual gives a supplementary explanation of some items referred to in the instruction manual E6581158
included with the product. Please read this manual carefully along with the instruction manual E6581158.

1-phase 240V class 0.2 to 2.2kW


3-phase 240V class 0.4 to 4.0kW
3-phase 500V class 0.75 to 4.0kW

- To set makers -
Please see to it that this manual is supplied to the inverter’s end user, along with the instruction manual
E6581158.
E6581225

■Safety precautions
Before reading this manual, please read the following instructions in addition to “I. Safety Precautions,” of the
instruction manual E6581158.

■General Operation

Danger
• Circuit boards are exposed when the front cover is removed. So do not detach the
Mandatory
front cover when the inverter is energized or within 10 minutes after power is turned
off. Doing so could result in electric shock.

■Transportation

Warning
• When handling the inverter unit, hold it by both the sides firmly. If you hold it by the
Mandatory
fins at the upper and lower parts, you could get injured.

1
E6581225

■Exterior Features

(5)
TOSHIBA
(4) (1)
(3) 0.0 Mode key

(2) ▲ MODE

▼ ENT

Enter key
CHARGE lamp

Indicates that high voltage is Up key


still present within the
inverter. Do not open the
cover while this is lit.

(6) Down key

Side view
(7)

No. Devices Remarks


(1) Operation panel Equipped with ▲ , ▼ , MODE and ENT keys used to set
parameters, a 7-segment LED and a CHARGE lamp.(The
inverter does not have a RUN key, a STOP key and a
potentiometer control, which are provided for VF-S11 standard
series inverters.)
(2) Manual power ON-OFF switch Used to turn on and off power manually. Note 1:
(3) Slots (x 2) reserved for optional devices Slots for optional contact input switches. Note 2:
(4) Operation ON-OFF rotary switch Used to start and stop the inverter.
(5) Potentiometer for frequency setting Used to set the operation frequency of the inverter.
(6) Wiring port plate Steel plate with wiring portsThe effects of noise can be
reduced to some degree by fixing shielded parts of cables with
cable grounds or similar devices. See page 7.
(7) Name plate Label on which the ratings of the inverter unit is printed.
Note 1: The switch has the function of tripping (overcurrent tripping). If the switch is in the Trip position, inspect
the inverter before turning back on the power switch, because the inverter itself may be faulty.
Note 2: Recommended contact input switches: Harmony series (XB5 series)

2
E6581225

■Main circuit and control circuit terminal boards

Control signal cable connector


To front cover

Screw
Screw

Internal cooling fan

Control circuit terminal board

Screw
Screw

Main circuit terminal board 2


Main circuit terminal board 1
Motor output : U/T1, V/T2, W/T3,
Power supply : R/L1, S/L2, T/L3 Internal DC section : P0, PA/+,
(Single-phase : R/L1, S/L2) PB, PC/-

Screw
Screw

How to remove the front cover


1. Shut off the supply of electricity from the main power supply, and turn the manual power ON-OFF switch to
the OFF position.
2. Ten minutes or more after turning off power, check to be sure that the CHARGE lamp is not lit.
3. Remove the 6 screws* (indicated by the arrows in the figure) around the front cover.
(* 4 screws for single/three-phase 240V-0.75kW models and smaller)
4. Pull the front cover slowly toward you to remove it and detach the control signal cable connector.

How to attach the front cover


1. Attach the control signal cable connector.
2. Attach the front cover.
3. Set and tighten the 6 screws* (indicated by the arrows in the figure) around the front cover.
(* 4 screws for single/three-phase 240V-0.75kW models and smaller)

Caution: Attach the front cover securely.


Or else it does not serve as a protector compliant with IP54.
On top of that, it may become impossible to operate the keys on the operation panel.

About the built-in cooling fan


The inverter has a built-in cooling fan. The cooling fan has a useful life of approximately 30,000 hours (2 to 3
years when operated continuously), so it needs to be replaced periodically.
(Single/three-phase 240V-0.75kW models and smaller are not equipped with cooling fans.)
If the cooling fan does not operate normally, the temperatures of the internal electrical components will rise
high, and as a result their lives will be shortened. So inspect it periodically.

About the useful life of the manual power ON-OFF switch


The manual power ON-OFF switch has a useful life of approximately 5 years (if operated 12 hours per day at
an average yearly ambient temperature of 30°C), so it needs to be replaced periodically.

3
E6581225

■Wiring diagram

(1) Input power cable


(2) Output cable
(3) Control cable
(4) Control resistor (optional) cable
(5) Wiring port plate
(6) Grounding terminal
(7) Optional communications device
interconnect cable
(7) (Option)

(6)

(6)

(5)

(1) (4) (3) (2)

Cautions
• Circuit boards are exposed when the front cover is removed. Since high voltages are applied to some parts
of the circuit board, read Section 2.1, “Cautions on wiring,” of the instruction manual E6581158 carefully
before wiring.
When connecting cables, take care not to damage the circuit board with a screwdriver or a similar tool.
• To connect the power cable (to the manual power ON-OFF switch), torque the terminal screw to 1.7N·m
(recommended). (M4 screw)
• Never turn on the power ON-OFF switch before attaching the front cover.
Or you could get a shock.

The main circuit terminal board (input power cable) has terminals of a cable pinch type.
Before connecting a cable, strip off its sheath to a length of 10mm or so. Torque: 1.7N·m

Approx. 10mm

4
E6581225

■Diagram of cables connected at the factory

< WN type : Sink logic > < WP type : Source logic >

P24

PP VIB CC PP VIB CC

Red White Black F CC Red White Black F CC

Blue Blue Blue


Potentiometer for Potentiometer for
frequency setting frequency setting

Blue
Fw

Fw
0

0
Operation ON-OFF Operation ON-OFF
rotary switch rotary switch

Note: The colors indicated in the above figure refer to the colors of cables.

■Installation environment
• Operate in areas where ambient temperature ranges from -10°C to
10cm or more +40°C.
• Install the inverter in a well-ventilated place and mount it on a flat metal
plate in portrait orientation. Install the inverter so that it is not inclined
VFS11
5cm or more 5cm or more more than ±10° from the vertical.
• Leave a space of 10cm or more on the upper and lower sides of the
inverter, and a space of 5cm or more on each side.
• The inverter has a built-in cooling fan. The cooling fan has a useful life
of approximately 30,000 hours (2 to 3 years when operated
10cm or more
continuously), so it needs to be replaced periodically. The inverter has a
built-in cooling fan. (Single/three-phase 240V-0.75kW models and
smaller are not equipped with cooling fans.)
If the cooling fan does not operate normally, the temperatures of the
internal electrical components will rise high, and as a result their lives
will be shortened.
So inspect it periodically.

5
E6581225

■Outside dimensions

Applicable Outside dimensions (mm)


Voltage
Motor Inverter type Cable port
class W H D W1 H1 D1
(kW)
0.2 VFS11S-2002PLE
φ19×3
0.4 VFS11S-2004PLE 210 240 177 192 218 14
1-phase φ21×1
0.75 VFS11S-2007PLE
240V
1.5 VFS11S-2015PLE 215 297 206 197 277 14 φ19×1
2.2 VFS11S-2022PLE 230 340 222 212 320 14 φ23×3
0.4 VFS11-2004PME φ19×3
210 240 177 192 218 14
0.75 VFS11-2007PME φ21×1
3-phase
1.5 VFS11-2015PME
240V 215 297 206 197 277 14 φ19×1
2.2 VFS11-2022PME
φ23×3
4.0 VFS11-2037PME 230 340 222 212 320 14
0.75 VFS11-4007PLE
215 297 206 197 277 14
3-phase 1.5 VFS11-4015PLE φ19×1
500V 2.2 VFS11-4022PLE φ23×3
230 340 222 212 320 14
4.0 VFS11-4037PLE
H1 (Installation dimension)

2-R2.75

W1 (Installation dimension) 9
W
14
D

6
E6581225

■Specifications
Item Specification
Voltage class 1-phase 240V class/3-phase 240V class/3-phase 500V class
Applicable motor (kW) 0.2 0.4 0.75 1.5 2.2 4.0
Voltage class Model number VFS11S-/VFS11-
Model

1-phase 240V class VFS11S- 2002PLE 2004PLE 2007PLE 2015PLE 2022PLE -


3-phase 240V class VFS11- - 2004PME 2007PME 2015PME 2022PME 2037PME
3-phase 500V class VFS11- - - 4007PLE 4015PLE 4022PLE 4037PLE
Capacity (kVA) Note 1: 0.6 1.3 1.8 3.0 /3.0 /3.1 4.2 6.7 /7.2
1-phase 240V 1.5 (1.5) 3.3 (3.3) 4.8 (4.4) 8.0 (7.9) 11.0 (10.0) -
Output current (A)
Rating

3-phase 240V - 3.3 (3.3) 4.8 (4.4) 8.0 (7.9) 11.0 (10.0) 17.5 (16.4)
Note 2:
3-phase 500V - - 2.3 (2.1) 4.1 (3.7) 5.5 (5.0) 9.5 (8.6)
Output voltage Note 3: 240V class: 3-phase 200 to 240V, 500V class: 3-phase 380 to 500V
Overload current rating 150%-1min., 200%-0.5 sec. (50%-reduction value)
240V class: 1-phase/3-phase 200 to 240V-50/60Hz,
supply
Power

Voltage-frequency
500V class: 3-phase 380 to 500V-50/60Hz
Allowable fluctuation Voltage+10%, -15% Note 4:, Frequency±5%
Totally enclosed type (JEM1030) compliant with IP54/possible to bring into compliance
Protective method
with IP55 Note 5:
Self-cooled (with a built-in cooling fan. 1-phase/3-phase 240V-0.75kW or smaller:
Cooling method
Cooling fan not provided)
Color Munsel 5Y-8/0.5
Built-in filter 1-phase & 500V class: High-attenuation EMI filter, 3-phase 240V class: Standard filter
Indoor type. Altitude: Not more than 1000m.
Environments

Use environments
Place free from corrosive and explosive gases
Ambient temperature -10 to +40℃
Storage temperature -25 to +70℃
Relative humidity 20 to 93%
Vibration 5.9m/s2 or less (10 to 55Hz)
Note 1: Capacity is calculated at 220V for the 240V models and at 440V for the 500V models.
Note 2: Indicates rated output current setting when the PWM carrier frequency (parameter F300) is 4kHz or less.
The values between parentheses refer to output currents at PWM carrier frequencies of over 4kHz. They
need to be reduced further at frequencies over 12kHz (If a motor cable over 30m in length is used, it is
necessary to reduce them more. This means that the lives of the internal components will be shortened).
When the input power voltage of the 500V class model exceeds 480V, it is necessary to further reduce
the setting. The default setting of the PWM carrier frequency is 12kHz.
Note 3: The maximum output voltage is equal to the input supply voltage.
Note 4: ±10% when the inverter is operated continuously (under a load of 100%).
Note 5: IP54-compliant structures refer to structures that protect the contents from dust and harmful effects of
water that drops from every direction.
The inverter can be brought into compliance with IP55 specifications by making the wiring port
watertight.
(IP55-compliant structures refer to structures that protect the contents from dust and harmful effects of
water that comes in a jet from every direction.)
To bring the inverter into compliance with IP-55, use PG screw type cable grounds. Among cable
grounds available are skin-top grounds manufactured by LAPP (Germany).
When using this type of grounds, use them in combination with lock nuts specified below.
Cable port Cable ground Cable ground(EMC-compliant) Lock nut
φ19 hole MS11 MS-SC11 SM-11
φ21 hole MS13.5 MS-SC13.5 SM-13.5
φ23 hole MS16 MS-SC16 SM16
Note 6: For control specifications, parameters and functions, refer to the instruction manual E6581158.
Note 7: The factory default settings of the following parameters are different from those of the VFS-11 standard
type.
Title Function Standard VF-S11 Totally enclosed type VF-S11
cmod Command mode selection 1 0
fmod Frequency setting mode selection 0 2
Note 8: The inverter has a built-in cooling fan. The cooling fan has a useful life of approximately 30,000 hours (2
to 3 years when operated continuously), so it needs to be replaced periodically.
(Single/three-phase 240V-0.75kW models and smaller are not equipped with cooling fans.)
If the cooling fan does not operate normally, the temperatures of the internal electrical components will
rise high, and as a result their lives will be shortened. So inspect it periodically.
Note 9: The manual power ON-OFF switch has a useful life of approximately 5 years (if operated 12 hours per
day at an average yearly ambient temperature of 30°C), so it needs to be replaced periodically.