Isolators/Grounding Switches Data Sheets 110 KV Ab Switches
Isolators/Grounding Switches Data Sheets 110 KV Ab Switches
2013
11 Maximum Temperature
a) Of current carrying parts when carrying rated : ------------Max. temperatuure 950 C-----------------
continuous current Degree C. --------Temp. 450 C over ambient of 500 C-------
13 Operation
15 Total length of break per pole (min. air distance across : ---------------------------1250 mm-------------------------
the isolating distance) mm.
16 Insulation level
17 Earthing Switch
a) Rated current carrying capacity : Amps : -------No rated current but our earth switch
capable to withstood short time current only
18 Switch contacts
a) Type of contacts
c) Area of contacts : Sq.mm : 650 Sq.mm for Main Switch Female Contact
400 Sq.mm for Earth Switch Female Contact
643 Sq. mm for Main Switch Male Contact
463 Sq. mm for Earth Switch Male Contact
ii) Material and size of plate : ------6 mm thick MS Plate, hot dip galvanized------
20 Clearance:
c) Between live parts and earth : --Equal to dry arcing distance of the insulator--
21 Bearing
b) Material and size of housing : LM-6, Gravity Die cast sutable for 40 ID Bearing
c) No. of bushes, joints, location & size : -------6 Nos. Tandem pipe clamps 16 ID-------
22 Operating GI Pipe
i) Tandem Pipe:
E PSS DS SB 1320 05.03.2013
f) No. of Clamp and material and size : ------------3 Nos. MS Flat, 8 mm thick-------------
a) Between rotating stool bearing & down pipe : Universal joint. Universal joint
b) Size, Material and Grade in other parts : ------M12 and above are HDG of grade 4.6-------
a) Material & size of elevator plate below fixed insulator: --------250x75x5 mm thick MS HDG Plate-----------
33 Terminal Pad
34 Clamp body
a) i) Alloy composition :
---------------Confirmed--------------
ii) Plating if any :
b) Bolts :
36 Motor details:
d) Frequency : 50 HZ
39 Control Cabinet:
E PSS DS SB 1320 05.03.2013
b) Thickness :
---------------------------Not applicable------------------
c) Degree of protection :
40 Switch Design:
42 Base: