Power System Protection - Part 10
Power System Protection - Part 10
GENERATOR PROTECTION
MOTOR PROTECTION
BUS PROTECTION
851
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
GENERATOR PROTECTION
The generator protection system design should take into account
the types of faults and abnormal operating conditions that could be
present at the generating plant and provide means for detecting and
acting upon these conditions. The protection system design will
depend on the size of the generating unit.
These fault types and disturbance conditions are classified as:
Overload protection, and Overcurrent (short-circuit) problems
Stator electrical faults
Rotor electrical faults
Failure of prime mover (mechanical problems)
Failure of the field circuit
Hence we must protect the generator against the effect of these faults
and abnormalities using the following protection schemes:
Overload protection, and Overcurrent protection
Overvoltage and undervoltage protection
Overexcitation
Unbalanced loading (Currents ) –sequence relay
Loss of Excitation
Loss of synchronism
Phase Faults
Earth Faults
Abnormal Frequencies
Motoring
Overspeeding
Excessive vibration
Internal faults,
Stator and rotor thermal protection, and
Field ground.
851
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
To protect the generator against the failure of winding insulation and the
failure of the field circuit as well as the primemover failures, differential
protection is used with biased circulating current scheme. The theory of
circulating current differential protection is discussed fully in part 7. The
protection scheme is shown in Fig.1.Normally differential protection is
used for generators larger than or equal to 20MW.
Example 1
Figure 2 shows a biased percentage differential relay applied for the
protection of synchronous generator windings. The relay has 0.1A
minimum pick up current and a 10 %.
(a) Fault has occurred near the grounded neutral end of the generator
when the generator is carrying load. As a result, the currents flowing at
each end are as shown in the figure. Would the relay operate or not?
(b) would the relay operate at the given value of fault current in (a)
above mif the generator was carrying no load ?
(c ) On the same diagram , show the relay opersting characteristics and
the points that represent the operating and restraining currents in the
relay for the two conditions.
861
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
Fig.2
868
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
861
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
861
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
GROUND-FAULT PROTECTION
One of the main causes of ground faults is insulation failure. The zero
sequence impedance of a generator is usually lower than the positive or
negative sequence impedance, and hence, for a solidly grounded
generator, the single phase to ground-fault current is greater than the
threephase fault current. To limit the ground-fault current, generators are
usually grounded through an impedance.
OVEREXCITATION PROTECTION
When the ratio of the voltage to frequency (volts/Hz) exceeds 1.05 pu for
a generator, severe overheating can occur due to saturation of the
magnetic core of the generator and the subsequent inducement of stray
flux in components not designed to carry flux. Such overexcitation most
often occurs during start-up or shutdown while the unit is operating at
reduced frequencies, or during a complete load rejection which leaves
transmission lines connected to the generating station. Failure in the
excitation system can also cause overexcitation. Similar problems can
occur with the connected transformer.
861
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
OVERVOLTAGE PROTECTION
UNBALANCED CURRENTS
865
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
MOTOR PROTECTION
1. General
Fuses , thermal overload relay and contactors has proved itself an
effective and economical solution for small to medium-sized motors up
to about 150 hp.Two basic protections are used for these motor:
■ Thermal overload protection
■ Short-circuit (overcurrent) protection
866
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
Molded Case Circuit Breakers (MCCB) are used for low voltage
motors of high ratings.
Miniature circuit breakers (MCB) for small motors.
Fuses + contactor + thermal relay for L.V motors.
For high voltage motor: H.V. circuit breaker and differential
protection.
861
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
Example
861
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
If the starting current of the motor is say 500 A and the run-up time 10s,
then a 125 A fuse would be required. Examination of the fuse
time/current characteristic shows that at 500 A the 125 A fuse would
operate in 15 s. The fuse one size lower, 100 A, would operate in 4 s at
500 A and is, therefore, not suitable. The full-load current of the motor
would be, say, 83 A and although a 100 A fuse would deal with this
current it could not deal with the starting current for the duration of the
starting time. The fuse does not protect the motor against overload as
the rating of the fuse is always two to three times the full load current.
861
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
To summarize
Select a 32 A fuse.
811
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
Heating load - 30 kW
Select a 50 A fuse.
Fig. 3.
Motor 30 kW
Note that, whereas the lighting and heating loads are rated at the input
power, the motor is rated at the output power. The motor input power is
output power/efficiency, i.e. for 92% efficiency:
Also the heating and lighting loads are at unity power factor whereas the
motor power factor is, say, 0.83.
The starting current of, say, 7 x full load current for 10 s is 7 x 54.7 = 383
A.
818
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
2- It must carry the load plus the starting current of the motor:
From Fig. 4 a 125 A fuse would withstand 452.5 A for more than 10s.
811
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
3- The pre-arcing I2t must be greater than the total I2t of the 100 A fuse.
Figure 5 shows that a 160 A fuse would be required.
811
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
All these methods are based on KCL , namely , that the sum of all
current entering a node must be zero.Consider the two situations for
simple bus shown in Fig.1
811
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
A basic differential system is shown in Fig.2. All CTs must have same
ratio and polarity such that the current circulate amongst them is zero
(Id=0) for all external faults. For internal fault current Id=If will flow
through the relay.
Fig.2
If the CTs behaved ideally, the differential system shown in Fig.2 would
be very easy to implement using a simple overcurrent relay as shown in
Fig.3.
Fig.3
815
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
Fig.4
Consider a load bus with three outgoing feeders as shown in Fig.5 .This
bus is protected by differential relay with three restrain coil .The
protection scheme shown for one phase only.
Fig.5
816
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
I1 + I 2 = I3
I1’ + I 2’ - I3’ = 0 = Iop. The relay will not operate.
When there is fault:
I1 I2 I3 R
6000 10000 IF
Solution:
811
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
IF
I1 I2 I3 R
Feeder 1
Solution:
811
Power System Protection Part – X Dr.Prof. Mohammed Tawfeeq Alzuhairi
Fig.6
Fig.7
811