Sitrans L Point Level Transmitters Sitrans Lvs300: A5E44908583-AB
Sitrans L Point Level Transmitters Sitrans Lvs300: A5E44908583-AB
Sitrans L Point Level Transmitters Sitrans Lvs300: A5E44908583-AB
Installing/mounting 2
Connecting 3
SITRANS L
Operating 4
Point Level Transmitters
SITRANS LVS300 5
Service and maintenance
Technical data 6
Operating Instructions
Dimension drawings 7
05/2019
A5E44908583-AB
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
1 Introduction ................................................................................................................................................ 5
1.1 Applications...............................................................................................................................5
1.2 Function ....................................................................................................................................5
2 Installing/mounting ..................................................................................................................................... 7
2.1 General safety instructions .......................................................................................................7
2.2 Additional safety instructions for hazardous locations ..............................................................9
2.3 Mounting instructions ..............................................................................................................10
2.4 Zone classification ..................................................................................................................12
2.5 General notes .........................................................................................................................12
2.6 Permitted zones for mounting in partition wall ........................................................................13
2.7 Max. surface temperature and temperature class ..................................................................13
2.8 Manufacturing of the extension tube.......................................................................................14
2.9 Assembly of the unit................................................................................................................17
3 Connecting .............................................................................................................................................. 23
3.1 General safety instructions .....................................................................................................23
3.2 Additional safety instructions for hazardous locations ............................................................25
3.3 Connection ..............................................................................................................................27
3.4 Universal voltage ....................................................................................................................27
3.5 3-wire ......................................................................................................................................28
4 Operating ................................................................................................................................................. 29
4.1 Signal output ...........................................................................................................................29
4.2 Sensitivity setting ....................................................................................................................30
5 Service and maintenance ........................................................................................................................ 33
5.1 Maintenance notes..................................................................................................................33
5.2 Change of the electronic board...............................................................................................34
5.3 Disposal notes ........................................................................................................................35
6 Technical data ......................................................................................................................................... 37
6.1 Electrical data .........................................................................................................................37
6.2 Electronics ..............................................................................................................................37
6.3 Mechanical data ......................................................................................................................38
6.4 Operating conditions ...............................................................................................................39
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 3
Table of contents
SITRANS LVS300
4 Operating Instructions, 05/2019, A5E44908583-AB
Introduction 1
1.1 Applications
The device is used for level monitoring in all types of containers and silos.
It can be used with all powdery and granulated bulk materials with a density greater than
20 g/l (1.25 lb/ft3) that do not show a strong tendency to form crusts or deposits.
The units can be delivered with Ex-approvals for use in Dust Hazardous Areas.
A selection of fields of application:
● Building materials industry
– lime, moulding sand, etc.
● Food industry
– milk powder, flour, salt, etc.
● Plastics industry
– plastics granules etc.
● Timber industry
● Chemical industry
● Mechanical engineering
The LVS300 oscillating probe is normally screwed into the lateral container wall so that it is
level with the filling height to be registered and monitored.
The device can also be mounted from the top of the container. In this case an extension
piece is used to mount the probe level with the height to be registered.
The length of the probe can be up to 4 m (157”) with an extension.
The use of a sliding sleeve is recommended so that the switch point can be changed
continuously during operation of the device.
1.2 Function
The piezo-electrically stimulated oscillating rod vibrates at its mechanical resonance
frequency. If the probe is covered by the bulk material, the damping thus generated is
registered electronically and a corresponding signal output is actuated.
The oscillation of the rod ensures a certain self-cleaning effect.
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 5
Introduction
1.2 Function
① Pipe extension
② Optional sliding sleeve
③ Compact version or pipe extension
④ Compact version
⑤ Application in down pipe
SITRANS LVS300
6 Operating Instructions, 05/2019, A5E44908583-AB
Installing/mounting 2
2.1 General safety instructions
CAUTION
Process pressure
Improper installation may result in loss of process pressure.
CAUTION
Chemical resistance against the medium
Materials of construction are chosen based on their chemical compatibility (or inertness) for
general purposes. For exposure to specific environments, check with chemical compatibility
charts before installing.
CAUTION
Temperature range
The range of the ambient and process temperature of the device must be observed (see
Ambient Temperature (Page 39)and for Ex-approvals here). (Page 12)
CAUTION
Special conditions of use
Model 7ML5738 Extension tube is constructed using Industry Electrical conduit installed by
qualified personnel per equipment manual and NFPA 70 National Electrical Code (FM
Approved Unit).
Model 7ML5738 Extension tube is constructed using Industry Electrical conduit installed by
qualified personnel per equipment manual and CEC C22.1 Canadian Electrical Code.
CAUTION
Mechanical load
The torque at the fastening spot must not exceed 180 Nm (Pipe extension)/ 100 Nm
(Customer supplied pipe extension) ①
Maximum length "L“ in dependence on the deviation (in degrees) from vertical installation
②=Load
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 7
Installing/mounting
2.1 General safety instructions
Note
Mounting location
Keep distance to incoming material and to the silo wall. The installation has to be done so
that the sensor elements cannot hit the wall of the silo. The flow of the medium and fixtures
in the container must be considered. This is especially important for extension length more
than 3 m (118.1“).
Note
Sliding sleeve
SITRANS LVS300
8 Operating Instructions, 05/2019, A5E44908583-AB
Installing/mounting
2.2 Additional safety instructions for hazardous locations
① “Pressure tight” version: Tighten both straining screws M8 with 20 Nm to obtain resistance
against pressure.
Note
Flange mounting
A plastic sealing must be used to tighten the flange.
Note
Fastening of the threaded process connection
Mounting torque for the thread may not exceed 80 Nm. Use a 50 mm (1.97“). For units with
sliding sleeve, use a 55 mm (2.17“) open-end wrench. Do not fasten by turning the housing.
Note
Food grade material
The materials are available for the use under normal and predictable applications (according
to directive 1935/2004 Art.3). Other conditions can influence the safety.
Note
Installation regulations
For devices to be used in hazardous locations, the respective valid installation regulations
must be observed.
Note
Sparks
The installation has to be done so mechanical friction or impact can not cause sparks
between the aluminium enclosure and steel.
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 9
Installing/mounting
2.3 Mounting instructions
Note
Oscillating rod
Do not bend, shorten or extend the oscillating rod since this will destroy the device.
Note
Direction of the cable glands
When the unit is mounted from the side, ensure that the cable glands face downward and
are closed to avoid water penetration into the housing. The housing can be rotated against
the threaded connection after mounting.
Note
Sealing
Seal the process thread with Teflon tape in case of process pressure.
Note
Precaution for later dismounting/ Service
Grease the screws of the lid if corrosive atmosphere is present (e.g. close to sea).
Note
Switching point
Heavy bulk material -> the signal output switches when the oscillating rod is covered by a
few mm of material.
Light bulk material -> the signal output switches when the oscillating rod is covered a few cm
of material.
SITRANS LVS300
10 Operating Instructions, 05/2019, A5E44908583-AB
Installing/mounting
2.3 Mounting instructions
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 11
Installing/mounting
2.4 Zone classification
* in case of conductive dust, additional demands for the installation are possible.
Note
Marking
Devices with EX approval are marked on the nameplate.
CAUTION
Process pressure
The device construction allows process over-pressure up to 16 bar (232 psi). These
pressures are allowed for test purposes. The definition of the Ex approval are only valid for
a container-overpressure between -0.2 .. +0.1 bar (-2.9 .. +1.45 psi).
For higher or lower pressures the approvals are not valid.
Note
Process and ambient temperature
The permitted temperature ranges are marked on the nameplate. The max. permitted
ambient and process temperatures (including temperature derating) stated in this manual
must be observed.
SITRANS LVS300
12 Operating Instructions, 05/2019, A5E44908583-AB
Installing/mounting
2.6 Permitted zones for mounting in partition wall
① Compact version
② Pipe extension
③ Category (ATEX) 2D, Zone 21
④ Category (ATEX) 1D, Zone 20
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 13
Installing/mounting
2.8 Manufacturing of the extension tube
① ambient side
② process side
Max. ambient Max. process Max. surface tem- Temperature class Temperature class
temperature temperature perature (Division System) (Zone System
60°C (140°F) 120°C (248°F) 120°C (248°F) T4 T4
130°C (266°F) 130°C (266°F) T4 T4
140°C (284°F) 140°C (284°F) T3C T3
150°C (302°F) 150°C (302°F) T3C T3
CAUTION
Obtain instruction manual for proper manufacturing of the extension tube. In case of
deviation from the instruction manual, the unit is not safe for use in Hazardous Locations.
SITRANS LVS300
14 Operating Instructions, 05/2019, A5E44908583-AB
Installing/mounting
2.8 Manufacturing of the extension tube
CAUTION
Specific Conditions of Use
Model 7ML5738 Extension tube is constructed using Industry Electrical conduit installed by
qualified personnel per equipment manual and NFPA 70 National Electrical Code (FM
Approved Unit).
Model 7ML5738 Extension tube is constructed using Industry Electrical conduit installed by
qualified personnel per equipment manual and CEC C22.1 Canadian Electrical Code.
Note
Demands on the Extension tube
Material: Stainless steel 1.4301 (SS304) or 1.4305 (SS301) or 1.4571 (SS316Ti) or 1.4404
(SS316L)
The pipe must be manufactured from one single piece. It is not allowed to weld two or more
pieces together.
Carefully observe max. length, diameter, wall thickness, thread, tolerances as specified in
the drawing.
All sharp edges must be removed to protect the cable.
Thread testing
Each thread must be tested with go and no-go ring gauge according to standard EN 10226
(R 1“ version) or ANSI B 1.20.1 (NPT 1“ version).
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 15
Installing/mounting
2.8 Manufacturing of the extension tube
SITRANS LVS300
16 Operating Instructions, 05/2019, A5E44908583-AB
Installing/mounting
2.9 Assembly of the unit
CAUTION
The tube must be assembled very carefully to ensure permanent sealing, electrical
grounding and mechanical stability. Observe the follow mounting instructions.
CAUTION
Make sure that the thread of the extension tube and the thread of the screwed piece/
oscillating piece is the same type (do not mix R and NPT thread).
– Feed the connecting wire through the 1“ Extension pipe and the screwed piece. Use a
separate taut wire for easy working.
– Screw the 1“ Extension tube into the oscillating piece and the screwed piece.
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 17
Installing/mounting
2.9 Assembly of the unit
① Connecting wire
② Cable gland
③ Housing
④ Screwed piece
⑤ Extension pipe
⑥ Oscillating piece
⑦ Oscillating rod
① Housing
② Extension tube
SITRANS LVS300
18 Operating Instructions, 05/2019, A5E44908583-AB
Installing/mounting
2.9 Assembly of the unit
① red
white
blue
black
② red
③ Blue cable soldered to shield
④ Silicone hose
⑤ Shrinking tube
⑥ Blue cable sleeves on cables red/white
⑦ White cable sleeves on cables blue/black
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 19
Installing/mounting
2.9 Assembly of the unit
① Red
② White
③ Blue
④ Black
① Cable tie
6. Insert electronics
Insert the plug into the electronic, insert the electronics into the housing, and fix the
electronics plastic cover with 4 screws.
SITRANS LVS300
20 Operating Instructions, 05/2019, A5E44908583-AB
Installing/mounting
2.9 Assembly of the unit
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 21
Connecting 3
3.1 General safety instructions
CAUTION
Handling
In the case of inexpert handling or handling malpractice, the electric safety of the device
cannot be guaranteed.
Note
Protective earthing
Before any electrical installation, the device must be connected to the protective earthing
terminal inside the housing.
Note
Installation regulations
The local regulations or VDE 0100 (Regulations of German Electro technical Engineers)
must be observed.
WIth use of 24 V supply voltage, an approved power supply with reinforced insulation to
mains is required.
Note
Fuse
Use a fuse as stated in the connection diagrams(Connection (Page 27))
Note
RCCB protection
In the case of a defect, the distribution voltage must automatically be cut off by a RCCB
protection switch so as to protect the user of the device from indirect contact with dangerous
electric tensions.
Note
Power supply switch
A Power-supply-disconnecting switch must be provided and marked near the device.
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 23
Connecting
3.1 General safety instructions
Note
Wiring diagram
The electrical connections have to be made according to the wiring diagram.
Note
Supply voltage
Compare the supply voltage applied with the specifications given on the electronic and name
plate before switching the device on.
Note
Cable gland/ closing element
The screwed cable gland and closing element must have following specifications: Ingress
protection IP67, temperature range from -40°C to +70°C, UL or VDE certified (depending on
the country where the unit is installed), pull relief.
Make sure that the screwed cable gland safely seals the cable and that it is tight (danger of
water intrusion). Cable glands that are not used have to be locked with a closing element.
Note
Conduit system
In case of using a conduit system (with NPT thread) instead of a cable gland the regulations
of the country where the unit is installed must be observed. The conduit must have a tapered
thread either NPT 1/2“ or NPT 3/4” in accordance with the unit and ANSI B 1.20.1. Not used
inlets must be closed tight with a metal closing element.
Note
Field wiring cables
The diameter has to match to the clamping range of the used cable gland.
The cross section has to match with the clamping range of the connection terminals and
consider the max. current.
All field wirings must have insulation suitable for at least 250 V AC.
The temperature rating must be at least 90°C (194°F).
If higher immunity interferences as specified in the stated EMC standards are present (see
chapter approval), a shielded cable is required, otherwise an unshielded instrumentation
cable is satisfactory.
Note
Connecting the terminals
Make sure that max. 8 mm (0.31") of the pigtails are bared (danger of contact with live parts).
SITRANS LVS300
24 Operating Instructions, 05/2019, A5E44908583-AB
Connecting
3.2 Additional safety instructions for hazardous locations
Note
Guiding the cables in the terminal box
Cut the field wiring cables to appropriate length to fit properly into the terminal box.
Note
Relay and transistor protection
Provide protection for relay contacts and output transistors to protect the device against
spikes with inductive loads.
Note
Protection against static charging
The housing of the unit must be grounded in any case to avoid static charging of the unit on
applications with pneumatic conveying and non-metallic containers.
Note
External equipotential bonding terminal
Note
Field wiring
A pull relief must be provided for the field wiring cables, when the device is installed with the
factory provided cable glands.
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 25
Connecting
3.2 Additional safety instructions for hazardous locations
Note
Cable glands and conduit system for ATEX
Installation according to the regulations of the country, where the product is installed.
Not used entries have to be closed with blanking elements certified for this purpose.
Where available the factory provided parts must be used.
A strain relief must be provided for the field wiring cables, when the device is installed with
the factory provided cable glands.
The diameter of the field wiring cable must match to the clamping range of the cable clamp.
If other than the factory provided parts are used, following must be ensured:
1. The parts must have an approval adequate to the approval of the level sensor (certificate
and type of protection).
2. The approved temperature range must be from the min. ambient temperature of the level
sensor to the max. ambient temperature of the level sensor increased by 10 Kelvin.
3. The parts must be mounted according to the instructions of the supplier.
Note
Conduit system for FM
In addition the regulations of the country must be observed. The used flameproof seals and
blanking elements must have an adequate type approval and a temperature range of at least
–40°C (-40°F) to +80°C (176°F). In addition they shall be suitable for the conditions and
correctly installed. Where available the provided original parts of the manufacturer must be
used.
Note
Commissioning
Commissioning only with closed lid.
Note
Opening the lid
Before opening the lid take care, that no dust deposits or whirlings are present.
Do not remove the lid (cover) while circuits are alive.
SITRANS LVS300
26 Operating Instructions, 05/2019, A5E44908583-AB
Connecting
3.3 Connection
3.3 Connection
① Connecting terminals
② Protective Conductor Terminal
① Signal output
② Power supply
Power supply
21 V .. 230 V 50 - 60 Hz ±10%* 22 VA
22 V .. 45 V DC ±10%* 2 W
*incl. ±10% of EN 61010
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 27
Connecting
3.5 3-wire
Signal output:
Floating relay DPDT
3.5 3-wire
PNP
① Load
② Power supply
Power supply
20 .. 40 V DC ±10%*
Signal output:
max. 0.4 A
Output voltage equal to input voltage, drop <2.5 V
SITRANS LVS300
28 Operating Instructions, 05/2019, A5E44908583-AB
Operating 4
4.1 Signal output
FSL/FSH Setting
FSH: If the sensor is used to indicate full load, set FSL: If the sensor is used to indicate empty load,
to Fail Safe High. set to Fail Safe Low.
Power failure or line break is regarded as "full“ Power failure or line break is regarded as "empty“
signal (protection against overcharging). signal (protection against running dry).
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 29
Operating
4.2 Sensitivity setting
SITRANS LVS300
30 Operating Instructions, 05/2019, A5E44908583-AB
Operating
4.2 Sensitivity setting
If the bulk material is light and has few or no tendency to cake or deposit, the setting can be
set to position "II“ or "I" so as to increase the sensitivity of the probe.
The table indicates the approximate min. bulk density depending on the settings.
Please contact manufacturer if you intend to use the device for special purposes.
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 31
Operating
4.2 Sensitivity setting
SITRANS LVS300
32 Operating Instructions, 05/2019, A5E44908583-AB
Service and maintenance 5
5.1 Maintenance notes
CAUTION
Opening the lid (cover)
Before opening the lid for maintenance reasons observe following items:
- Do not remove the lid while circuits are alive.
- No dust deposits or whirlings are present.
- No rain can enter into the housing.
CAUTION
Frequent check of the unit
To ensure durable safety in hazardous locations and with electrical safety, following items
must be checked frequently depending on the application:
- Mechanical damage or corrosion of any components (housing side and sensor side) and
of the field wiring cables.
- Tight sealing of the process connection, cable glands and enclosure lid.
- Properly connected external PE cable (if present).
Note
Cleaning
If cleaning is required by the application, following must be observed:
- Cleaning agent must comply with the materials of the unit (chemical resistance). Mainly the
lid sealing, cable gland and the surface of the unit must be considered.
The cleaning process must be done in a way, that:
- The cleaning agent cannot enter into the unit through the lid sealing or cable gland.
- No mechanical damage of the lid sealing, cable gland or other parts can happen.
A possible accumulation of dust on the unit does not increase the maximum surface
temperature and must therefore not be removed for purposes of maintaining the surface
temperature in hazardous locations.
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 33
Service and maintenance
5.2 Change of the electronic board
CAUTION
Function test
A frequent function test may be required depending on the application.
Observe all relevant safety precautions related with a safe work depending on the
application (e.g. hazardous locations, hazardous bulk material, electric safety, process
pressure).
This test does not proof if the sensor is sensitive enough to measure the material of the
application.
Function test is done by stopping the vibration of the vibrating rod with appropriate means
and monitor if a correct change of the signal output from uncovered to covered happens.
Note
Production date
The production date can be traced by the serial number on the nameplate. Please contact
the manufacturer or your local distrubutor.
Note
Spare parts
All available spare parts are stated in the selection list.
SITRANS LVS300
34 Operating Instructions, 05/2019, A5E44908583-AB
Service and maintenance
5.3 Disposal notes
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 35
Service and maintenance
5.3 Disposal notes
SITRANS LVS300
36 Operating Instructions, 05/2019, A5E44908583-AB
Technical data 6
6.1 Electrical data
Electrical data
Connection terminals 0.14 - 2.5 mm2 (AWG 26 - 14)
Cable entry M20 x 1.5 screwed cable gland
NPT 1/2“ conduit connection
NPT 3/4” conduit connection
Clamping range (diameter) of the factory provided cable
glands: M20 x 1.5: 6 .. 12 mm (0.24 .. 0.47"")
Signal delay Sensor free -> covered ca. 1 sec
Sensor covered -> free ca. 1 .. 2 sec
Safety operation (FSL,FSH) Switchable for minimum or maximum safety
Vibration frequency ca. 330 Hz
Overvoltage category II
Pollution degree 2 (inside housing)
6.2 Electronics
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 37
Technical data
6.3 Mechanical data
Mechanical data
Housing Aluminum housing, powder coat
Seal between housing and lid: NBR
Seal between housing and process connection: NBR
Nameplate: polyester film
Degree of protection IP67 (EN 60529), NEMA Type 4X
Process connection Material: Compact version: stainless
steel 1.4301 (304)/ 1.4541
(321) or 1.4404 (316L)
Pipe extension: stainless
steel 1.4301 (304)/ 1.4541
(321) or 1.4404 (316L) (pro-
cess connection and pipe
extension)
Thread: G 1", G 1¼", G 1½" DIN 228;
NPT 1", NPT 1¼", NPT 1½"
ANSI B 1.20.1
Flange: according to selection
1.4541 (321) or 1.4404
(316L)
Tri-clamp: stainless steel 1.4301 (304)
or 1.4404 (316L)
2" (DN50) ISO 2852
All material food grade
Oscillator Material: stainless steel 1.4404 (316L) (food grade)
Sound level max. 50 dBA
Overall weight (ca.) Compact version: 1.3 kg (2.9 lbs)
Pipe extension: 1.3 kg (2.9 lbs) +1.3 kg/m (+2.9 lbs per
39.3“) extension
Customer supplied pipe extension: 1.8 kg (4.0 lbs) +1.3
kg/m (+2.9 lbs per 39.3“) extension
SITRANS LVS300
38 Operating Instructions, 05/2019, A5E44908583-AB
Technical data
6.4 Operating conditions
Operating conditions
Ambient temp. (housing) -40°C .. +60°C (-40 .. +140°F)
Process temperature -40°C .. +150°C (-40 .. +302°F)
For versions with Ex-approvals: see remarks here
(Page 12).
①Tamb
②Tprocess
Ventilation Ventilation is not required
Min. powder density Setting Min. powder density (ca.)
I 20 g/l (1.25 lb/ft3)
II 80 g/l (5 lb/ft3)
III 150 g/l (9.4 lb/ft3)
IV 300 g/l (18.7 lb/ft3)
Features of bulk material No strong tendency to cake or deposit
Max. mechanical load 400 N (@40°C, 104°F) laterally (on oscillator rod)
Recommended protection in case of high material load;
mounting of a protective angle above the probe
Max. mechanical torque Pipe extension: 180 Nm (@40°C, 104°F)
Customer supplied pipe extension: 100 Nm (@40°C, 104°F)
Max. process pressure 16 bar (232 psi)
For version with "sliding sleeve without process overpres-
sure": unpressurized.
The max. process pressure may be reduced with use of
flanges. Observe flange standards for pressure rating and
pressure derating with higher temperature.
For versions with Ex-approvals: see remarks here
(Page 12).
Vibration 1.5 (m/s2)2/Hz according to EN60068-2-64
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 39
Technical data
6.5 Transport and storage
Operating conditions
Relative humidity 0-100%, suitable for outdoor use
Altitude max. 2,000 m (6,562 ft)
Expected product lifetime Following parameters have a negative influence on the
expected product lifetime:
High ambient- and process temperature, corrosive environ-
ment, high vibration, high flow rate of abrasive bulk material
passing the sensor element.
6.6 Approvals
Approvals
General Purpose (Ordinary Locations) (Depending on se- CE EN 61010-1
lected version in price list.) FM
Hazardous Locations (Depending on selected version in ATEX Dust explosion ATEX II 1/2 D Ex
price list.) ta/tb IIIC T! Da/Db
FM Dust explosion Cl. II, III Div. 1 Gr.
E,F,G
EMC EN 61326 - A1
Food grade material According to directive 1935/2004/EC
SITRANS LVS300
40 Operating Instructions, 05/2019, A5E44908583-AB
Technical data
6.7 Options
Approvals
RoHS conform According to directive 2011/65/EU
Pressure Equipment Directive (2014/68/EU) The units are not subject to this directive, because they are
classified as „pressure-keeping equipment“ and do not have
a pressurized housing (see Art.1, Abs. 2.1.4).
The units are designed and manufactured in accordance to
the Pressure Equipment Directive.
The unit is NOT intended for use as an “equipment part with
safety function (Art.1, Abs. 2.1.3). If the units should be used
as "equipment part with safety function", please contact the
manufacturer.
6.7 Options
Options
Sliding sleeve (Pipe extension) G 1½“ ISO 228 or
1½” NPT ANSI B 1.20.1
or flanges
Material:1.4301 (304) or 1.4404 (316L)
Sealing material to the extension tube:
FKM or NBR
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 41
Technical data
6.7 Options
SITRANS LVS300
42 Operating Instructions, 05/2019, A5E44908583-AB
Dimension drawings 7
7.1 Head dimension
Head dimension
① Thread
② Tri-clamp
③ Flange
④ Temperature isolator
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 43
Dimension drawings
7.3 Pipe extension
① Thread
② Tri-clamp
③ Flange
④ Temperature isolator
SITRANS LVS300
44 Operating Instructions, 05/2019, A5E44908583-AB
Dimension drawings
7.4 Pipe extension - customer mounted
⑤ Triclamp
⑥ Thread
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 45
Dimension drawings
7.4 Pipe extension - customer mounted
SITRANS LVS300
46 Operating Instructions, 05/2019, A5E44908583-AB
Certificates and support A
A.1 Technical support
Technical support
If this documentation does not provide complete answers to any technical questions you may
have, contact Technical Support at:
● Support request (http://www.siemens.com/automation/support-request)
● More information about our Technical Support is available at
Technical Support (http://www.siemens.com/automation/csi/service)
Personal contact
If you have additional questions about the device, please contact your Siemens personal
contact at:
● Partner (http://www.automation.siemens.com/partner)
To find the personal contact for your product, go to "All Products and Branches" and select
"Products & Services > Industrial Automation > Process Instrumentation".
Documentation
You can find documentation on various products and systems at:
● Instructions and manuals
(http://www.siemens.com/processinstrumentation/documentation)
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 47
Certificates and support
A.2 Certificates
A.2 Certificates
You can find certificates on the Internet at Industry Online Support
(https://support.industry.siemens.com/cs/products?dtp=Certificate&mfn=ps&pnid=17456&lc=
en-WW) or on an included DVD.
SITRANS LVS300
48 Operating Instructions, 05/2019, A5E44908583-AB
Index
C
Certificates, 48
Compact Operating Instructions, 47
Customer Support, (Refer to Technical support)
D
Documentation, 47
H
Hotline, (Refer to Support request)
I
Instructions and manuals, 47
M
Manuals, 47
O
Operating Instructions, 47
S
Service, 47
Service & Support, 47
Internet, 47
Support, 47
Support request, 47
T
Technical support, 47
Partner, 47
Personal contact, 47
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB 49
Index
SITRANS LVS300
50 Operating Instructions, 05/2019, A5E44908583-AB