0% found this document useful (0 votes)
54 views4 pages

Current Transformer - Doc Version 1

This site inspection and test record documents the testing of a current transformer at an electrical substation, including megger tests of the primary and secondary windings, a polarity test, measurements of winding resistances and testing of voltage ratios between cores and phases. Test data was recorded for cores 1 and 2, including winding resistances and voltage ratios between phases. Personnel signatures confirm the tests were performed and witnessed.

Uploaded by

JAYKUMAR SINGH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
54 views4 pages

Current Transformer - Doc Version 1

This site inspection and test record documents the testing of a current transformer at an electrical substation, including megger tests of the primary and secondary windings, a polarity test, measurements of winding resistances and testing of voltage ratios between cores and phases. Test data was recorded for cores 1 and 2, including winding resistances and voltage ratios between phases. Personnel signatures confirm the tests were performed and witnessed.

Uploaded by

JAYKUMAR SINGH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 4

SITE INSPECTION AND TEST

RECORD ATS
Description: Order no.: Record no. :
CURRENT TRANSFORMER 534/22/3
Customer: End Client: Sheet:
ALFANAR SEC-CTA of3
Site: Panel / Designation / Location no.: Project no.:
S/S 9015 S10348

A. GENERAL DATA AND INFORMATION:

BAY:___________________ SERIAL NO : R ---------------- Y --------------- B ----------------

CT TYPE:________________

MAKE:__________________

Core No. Ratio Class Rct Burden Vkp DUTY

Core 1 (1S1-1S3)

Core 1 (1S2-1S3)

Core 2 (2S1-2S3)

Core 2 (2S2-2S3)
1) Megger Test:

PRIMARY TEST 5000 V DC - 1.0 MIN.

Tested by Witnessed by:


Name : Name
Signature & Date: Signature & Date:
SITE INSPECTION AND TEST
RECORD ATS
Description: Order no.: Record no. :
CURRENT TRANSFORMER 534/22/3
Customer: End Client: Sheet:
ALFANAR SEC-CTA of3
Site: Panel / Designation / Location no.: Project no.:
S/S 9015 S10348

SECONDARY TEST 1000 V DC - 1.0 MIN.

2) Polarity Test:

P1 P2

S1 S2

Tested by Witnessed by:


Name : Name
Signature & Date: Signature & Date:
SITE INSPECTION AND TEST
RECORD ATS
Description: Order no.: Record no. :
CURRENT TRANSFORMER 534/22/3
Customer: End Client: Sheet:
ALFANAR SEC-CTA of3
Site: Panel / Designation / Location no.: Project no.:
S/S 9015 S10348

3) CT WINDING RESISTANCE:

CORE 1 CORE 2
PHASE
1S1-1S3 1S2-1S3 2S1-2S3 2S2-2S3

T= Degree.

4) CT RATIO TEST:

CT RATIO:

5) CT MAG. CURVE:

See the attached sheets

Tested by Witnessed by:


Name : Name
Signature & Date: Signature & Date:
SITE INSPECTION AND TEST
RECORD ATS
Description: Order no.: Record no. :
CURRENT TRANSFORMER 534/22/3
Customer: End Client: Sheet:
ALFANAR SEC-CTA of3
Site: Panel / Designation / Location no.: Project no.:
S/S 9015 S10348

- OIL LEVEL :

Tested by Witnessed by:


Name : Name
Signature & Date: Signature & Date: