SYS600 Status Codes

Download as pdf or txt
Download as pdf or txt
You are on page 1of 232

MicroSCADA Pro SYS600 9.

4
Status Codes
Trace back information:
Workspace Main version a54
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

Contents

1 Copyrights ............................................................................................. 7

2 Introduction ........................................................................................... 9
2.1 This manual .................................................................................. 9
2.2 Use of symbols ............................................................................. 9
2.3 Intended audience ........................................................................ 10
2.4 Related documents ....................................................................... 10
2.5 Document conventions ................................................................. 10
2.6 Document revisions ...................................................................... 11

3 Handling errors ..................................................................................... 13


3.1 Reliability of data .......................................................................... 13
3.2 SCIL errors ................................................................................... 13
3.3 System messages ........................................................................ 14
3.4 Grouping of status codes .............................................................. 15

4 Status Codes ......................................................................................... 19


4.1 Reliability of Data .......................................................................... 19
4.1.1 OK Status Code .............................................................. 19
4.1.2 Almost OK Status Codes ................................................ 19
4.1.3 Common Non-Valid Status Codes .................................. 20
4.2 Base System Status Codes .......................................................... 20
4.2.1 SCIL Language (SCIL) Error Codes ............................... 20
4.2.2 Picture Handling (PICO) Status Codes ........................... 42
4.2.3 Report Database (REPF and REPR) Status Codes ....... 44
4.2.4 Process Database (PROF and TOPO) Status Codes .... 50
4.2.5 NET Interface (NETI) Status Codes ............................... 65
4.2.6 Picture Database (PICF) Status Codes .......................... 66
4.2.7 Picture Graphics (PICO) Status Codes .......................... 66
4.2.8 File Handling (FILE) Status Codes ................................. 68
4.2.9 OPC Data Access Server (OPCS) Status Codes ........... 69
4.2.10 Printer Spooler (PRIN) Status Codes ............................. 70
4.2.11 System (SYST) Status Codes ........................................ 70
4.2.12 User Account and Session Management (USER) Status
Codes ............................................................................. 80
4.2.13 TCP/IP (INPC) Status Codes .......................................... 83
4.2.14 OPC Data Access Client (OPCC) Status Codes ............ 83
4.2.15 OpenSSL (OSSL) Status Codes ..................................... 84
4.3 NET Status Codes ........................................................................ 84
4.3.1 Common NET Status Codes .......................................... 84
4.3.2 Redundant Frontend Status Codes ................................ 85
4.3.3 Errors in ACP Message Structure ................................... 85

3
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4.3.4 Common NET Application Layer Status Codes .............. 86


4.3.5 System Process Status Codes ....................................... 87
4.3.6 STA Device Status Codes (ANSI X3.28) ........................ 87
4.3.7 STA Device, Message Split Status Codes (ANSI X3.28) . 91
4.3.8 SID Devices Status Codes (ADLP80/180 slave) ............ 91
4.3.9 SIN Devices Status Codes (ADLP180 master) .............. 92
4.3.10 RTU Device Status Codes (RP570 master) ................... 94
4.3.11 RTU Device, Terminal Status Codes (RP570 master) .... 96
4.3.12 PCL Device Status Codes (P214) .................................. 99
4.3.13 SAT Device Status Codes (COMLI slave) ...................... 100
4.3.14 BAG Device Status Codes (INSUM master) ...................101
4.3.15 LCU Device Status Codes (LCU500 master) ................. 101
4.3.16 PAC Device Status Codes .............................................. 102
4.3.17 PRI Device Status Codes (ASCII printer) ....................... 103
4.3.18 SPA Device Status Codes (SPA master) ........................ 104
4.3.19 BPO (Bit Pad One) Device Status Codes ....................... 106
4.3.20 REX Device Status Codes (LON) ................................... 106
4.3.21 LMK Device Status Codes (LON) ................................... 108
4.3.22 SPI device status codes (RP570 slave) ..........................109
4.3.23 MON (Monitor) Device Status Codes ............................. 111
4.3.24 ADE Device Status Codes (General ASCII) ................... 111
4.3.25 PCO Device Status Codes (RCOM master) ................... 111
4.3.26 WES Device Status Codes (Westinghouse F4F slave) ...112
4.3.27 ATR Device Status Codes (Alpha/IEC1107) ................... 113
4.3.28 PLC Device Status Codes (General PLC/Modbus) ........ 114
4.3.29 ICC Device Status Codes (IEC60870-5-101/103/104) ....115
4.3.30 DNP Device Status Codes (DNP 3.0) .............................118
4.3.31 NET Network Layer Status Codes .................................. 121
4.3.32 Common NET Link Layer Status Codes ......................... 124
4.3.33 ANSI X3.28 Full Duplex Protocol Status Codes (XF) ..... 125
4.3.34 ANSI X3.28 Half Duplex Protocol Status Codes (XH) .... 126
4.3.35 ADLP80 Slave Protocol Status Codes (AD) ................... 126
4.3.36 ADLP180 Slave Protocol Status Codes (AL) .................. 127
4.3.37 RP570 Slave Protocol Status Codes (RP) ......................127
4.3.38 Common RAM Protocol Status Codes (RM) .................. 127
4.3.39 Integrated Link Status Codes (IL) ................................... 127
4.3.40 LAN Link Status Codes (LN) ...........................................127
4.3.41 On Line Configuration Errors in NETC Modules ............. 128
4.3.42 Auto Dialling Status Codes ............................................. 130
4.3.43 COM-1 Protocol Status Codes (CO) ...............................131
4.3.44 RP570 Master Protocol Status Codes (SR) ....................132
4.3.45 P214 Master Protocol Status Codes (PR) ...................... 133
4.3.46 FT1.2 Framing Status Codes (TC) ................................. 133
4.3.47 INSUM Master Protocol Status Codes (IS) .....................133
4.3.48 COMLI Slave Protocol Status Codes (CL) ......................134
4.3.49 LCU500 Master Protocol Status Codes (LC) .................. 134

4
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

4.3.50 ADLP180 Master Protocol Status Codes (AM) ............... 134


4.3.51 SPA Master Protocol Status Codes (SP) ........................ 135
4.3.52 General ASCII Protocol Status Codes (AG) ................... 135
4.3.53 RCOM Master Protocol Status Codes (PC) ....................136
4.3.54 Westinghouse F4F Slave Protocol Status Codes (WE) ...136
4.3.55 Alpha Protocol Status Codes (AT) .................................. 136
4.3.56 IEC1107 Protocol Status Codes (IE) .............................. 137
4.3.57 General PLC/Modbus Protocol Status Codes (PG) ........ 137
4.3.58 LON Protocol Status Codes (LO) ................................... 137
4.3.59 IEC60870-5-101/103 Protocol Status Codes (IG) .......... 138
4.3.60 DNP 3.0 Protocol Status Codes (DG) .............................139
4.3.61 LAN Link Status Codes (LN) ...........................................140
4.3.62 IEC60870-5-104 Protocol Status Codes (IT) .................. 140
4.3.63 PLC2 Error Codes (biased by 20000) .............................141
4.3.64 SCA TLS Error Codes .................................................... 141
4.4 Operating System Status Codes .................................................. 148
4.4.1 Win32 Error Codes ......................................................... 148
4.5 Data Transfer Status Codes ......................................................... 225
4.5.1 DDE Status Codes ..........................................................225
4.5.2 ODBC Status Codes ....................................................... 225
4.5.3 ODBC Error Codes ......................................................... 226
4.6 Status Codes Transmitted by NET to External Devices ............... 227
4.6.1 Status Codes Transmitted by NET to a PLC .................. 227

5
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1 Copyrights

The information in this document is subject to change without notice and should not be
construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any
errors that may appear in this document.
In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB Oy
be liable for incidental or consequential damages arising from the use of any software
or hardware described in this document.
This document and parts thereof must not be reproduced or copied without written
permission from ABB Oy, and the contents thereof must not be imparted to a third party
nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
Copyright © 2016 ABB Oy. All rights reserved.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their respective
holders.
Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.
Third Party Copyright Notices
List of Third Party Copyright notices are documented in "3rd party licenses.txt" and
included in SYS600 and DMS600 installation packages.

7
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2 Introduction

2.1 This manual


This manual provides information on errors, which might appear in the SYS600 system.
The manual provides general advices and lists the status codes with some explanations.

Status Codes
Handling error situations, system events and data reliability in SCIL is based on status
codes. Status codes are positive integers with descriptive names, for example 188 =
SCIL_UNDEFINED_VARIABLE. A status code may be generated, for example, in the
following situations:
• A SCIL statement has a syntax error
• A station is suspended due to a communication disturbance
• An incorrect value is set to an attribute of an application object
Status codes are classified into two main categories: base system status codes and NET
status codes. Base system status codes include the codes related to SCIL execution, base
system and data bases. NET status codes include the codes related to communication
via an NET unit.

2.2 Use of symbols


This publication includes warning, caution and information symbols where appropriate
to point out safety-related or other important information. It also includes tips to point
out useful hints to the reader. The corresponding symbols should be interpreted as follows:

Warning icon indicates the presence of a hazard which could


! result in personal injury.

Caution icon indicates important information or a warning


related to the concept discussed in the text. It might indicate
the presence of a hazard, which could result in corruption of
software or damage to equipment/property.

Information icon alerts the reader to relevant factors and


conditions.

Tip icon indicates advice on, for example, how to design a


project or how to use a certain function.

9
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

Although warning hazards are related to personal injury, and caution hazards are
associated with equipment or property damage, it should be understood that operation
of damaged equipment could, under certain operational conditions, result in degraded
process performance leading to personal injury or death. Therefore, comply fully with
all warnings and caution notices.

2.3 Intended audience


This manual is intended for installation personnel, administrators and skilled operators
to support installation of the software.

2.4 Related documents


This manual is a part of the SYS600 User Manuals. In addition to this manual there are
several other SYS600 manuals published with revision 9.4

2.5 Document conventions


The following conventions are used for the presentation of material:
• The words in names of screen elements (for example, the title in the title bar of a
dialog, the label for a field of a dialog box) are initially capitalized.
• Capital letters are used for file names.
• Capital letters are used for the name of a keyboard key if it is labeled on the keyboard.
For example, press the CTRL key. Although the Enter and Shift keys are not labeled
they are written in capital letters, e.g. press ENTER.
• Lowercase letters are used for the name of a keyboard key that is not labeled on the
keyboard. For example, the space bar, comma key and so on.
• Press CTRL+C indicates that the user must hold down the CTRL key while pressing
the C key (in this case, to copy a selected object).
• Press ALT E C indicates that the user presses and releases each key in sequence (in
this case, to copy a selected object).
• The names of push and toggle buttons are boldfaced. For example, click OK.
• The names of menus and menu items are boldfaced. For example, the File menu.
- The following convention is used for menu operations: Menu Name > Menu
Item > Cascaded Menu Item. For example: select File > Open > New Project.
- The Start menu name always refers to the Start menu on the Windows Task
Bar.
• System prompts/messages and user responses/input are shown in the Courier font.
For example, if the user enters a value that is out of range, the following message
is displayed: Entered value is not valid.
The user may be told to enter the string MIF349 in a field. The string is shown as
follows in the procedure: MIF349
• Variables are shown using lowercase letters: sequence name

10
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2.6 Document revisions


Version Revision number Date History
A 9.4 16.5.2014 New document
B 9.4 FP1 3.6.2015 Document updated
C 9.4 FP2 3.6.2016 Document updated

11
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

3 Handling errors

The status codes are positive integers with descriptive names. The purpose of status
codes are:
• To show the reliability of calculated data and process data
• To inform about errors that occur during the execution of SCIL programs and
evaluation of SCIL expressions
• To inform an application of certain events taking place in the process communication
system or in the communication units

3.1 Reliability of data


In SCIL, each evaluated expression gets a status code, which indicates the reliability of
the value. As a rule, the status code is determined by the most unreliable operand included
in the expression. Data written by the programmer or entered by the user always has the
status code 0. An unreliable status code may be caused by a process object or data object
value with a bad status (OS attribute). It may also be caused by some operators when
the operands do not match and by some SCIL functions.
The status code of an application object value is the value of the OS attribute of the
object. For process and data objects the code indicates the reliability of the OV attribute.
For command procedures it indicates the success of the latest program execution.
The OS attribute of a process object is updated at each updating of the OV value in the
process database. Process objects can be assigned the status codes 0, 1, 2, 3 and 10. OS
is updated by the base system, which determines the status code based on the system
messages sent by NET.
The status code of a process object affects the status codes of the data objects that use
the process object value in their expressions. If the logging function (LF attribute) is
DIRECT, the status code for the process object is copied to the status code of the data
object.
The status code of an expression can be read with the SCIL function GET_STATUS and
written with the function SET_STATUS.

3.2 SCIL errors


A SCIL error is usually caused by a syntax error in the program, but it may also be
caused, for example, by a database error or a communication error during the execution
of a SCIL program.
Depending on the error handling policy defined by using the #ERROR command, the
error may cause:
• An error message or activation of an error handling program (CONTINUE, STOP)

13
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

• An immediate stop of the program execution (STOP, EVENT)


• No action (IGNORE)
For more information on error handling policies see the #ERROR command in the
Programming Language SCIL manual.
An error handling program allows for building procedures handling error messages. If
the error handling policy is CONTINUE or STOP, a SCIL error generates a standard
error message unless defined otherwise in an error handling program.
Errors in Visual SCIL dialogs are shown in the Error Viewer by default. The Error Viewer
shows the status code, the line in the program where the error occurred and the error
state.
When the pictures are shown on the screen, the status codes are part of standard error
messages written on the top line of the application window. This is done unless no other
ways to handle error messages are defined in the named program called
ERROR_HANDLER. These error messages have the following format:
code1 code2 SCIL STATEMENT OR EXPRESSION

The 'code1' states roughly in which circumstances the error occurred. This code is always
a picture handling code (801 ... 999). The 'code2' specifies the error more accurately.
The SCIL statement or expression that caused the error message is usually, but not
always, shown and the error is marked to help to correct it.
A status code may also appear in a message shown in the SYS600 Notification Windows.
Usually the message refers to errors in command procedures or in system configuration.
In some cases it is the result of errors in the report database, the process database, the
file handling or the operating system interface.
Normally, the message in the Notification Window has the following format:
time module: object name or message STATUS = code
SCIL STATEMENT OR EXPRESSION

The message is displayed in all active SYS600 Notification Windows connected to the
base system that generates the message. The message is also stored in a file in the base
system computer. The file is located in the \SC\SYS\ACTIVE\SYS_ directory and has
the name SYS_LOG.CSV.

3.3 System messages


System messages are internal SYS600 messages sent to one or several applications. Most
system messages are status codes generated by NET. Some station types (STY objects)
may also generate codes sent as system messages.
By means of certain communication system object attributes (SE, MS, MI, CA), the
system messages can be directed to the chosen applications and process objects. By
defining process objects for receiving the system messages, the programmer can define
various consequential actions to be activated at certain system message codes. This kind

14
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

of action could be for example a request for a line switch when the status sent by the
main communication line indicates a communication disturbance.
The current status of some communication system objects can be read by reading the
value of the OS attribute of the object. Setting the OS attribute forces the object to
retransmit its current status as a system message.
After a system message, which indicate that connection to a station has been broken, all
process objects belonging to that station will get obsolete status, i.e. the value of their
OS attribute will be 2.

3.4 Grouping of status codes


Status code 0 is the OK status indicating that no error has occurred. Codes 1 to 9 are
warning, or almost OK, status codes. A value with an almost OK status can be used in
expressions without an error, but the result of the expression gets a non-zero status. The
codes 10 ... 10 000 are mainly error codes. The codes from 10 001 upwards indicate
partly errors, partly system messages.
Note that some of the status codes are used with other operating systems than Windows
and older versions of the product. They are still included in this manual to facilitate
debugging of systems comprising of these different components.
The status codes are grouped into the following groups:

Reliability of Data

0 OK Status Code
1 ... 9 Almost OK Status Codes
10 ... Common Non-Valid Status Codes

Base System Status Codes

101 ... 799 SCIL Language (SCIL) Error Codes


801 ... 999 Picture Handling (PICO) Status Codes
1001 ... 1999 Report Database (REPF and REPR) Status Codes
2001 ... 2999 Process Database (PROF and TOPO) Status Codes
3001 ... 3099 NET Interface (NETI) Status Codes
4001 ... 4199 Picture Database (PICF) Status Codes
4201 ... 4299 Picture Graphics (PICO) Status Codes
5001 ... 5099 File Handling (FILE) Status Codes
5501 ... 5599 OPC Data Access Server (OPCS) Status Codes
6101 ... 6199 Printer Spooler (PRIN) Status Codes

15
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

7001 ... 7999 System (SYST) Status Codes


8001 ... 8099 User Account and Session Management (USER) Status Codes
8301 ... 8399 TCP/IP (INPC) Status Codes
8401 ... 8499 OPC Data Access Client (OPCC) Status Codes

NET Status Codes

10001 ... 10009 Common NET Status Codes


10500 ... 10514 Redundant Frontend Status Codes
11001 ... 11033 Errors in ACP Message Structure
12002 ... 12022 Common NET Application Layer Status Codes
12101 ... 12106 System Process Status Codes
12301 ... 12399 STA Device Status Codes (ANSI X3.28)
12401 ... 12410 STA Device, Message Split Status Codes (ANSI X3.28)
12450 ... 12487 SID Devices Status Codes (ADLP80/180 slave)
12501 ... 12585 SIN Devices Status Codes (ADLP180 master)
12601 ... 12693 RTU Device Status Codes (RP570 master)
12701 ... 12789 RTU Device, Terminal Status Codes (RP570 master)
12801 ... 12831 PCL Device Status Codes (P214)
12851 ... 12873 SAT Device Status Codes (COMLI slave)
12901 ... 12910 BAG Device Status Codes (INSUM master)
12950 ... 12999 LCU Device Status Codes (LCU500 master)
13001 ... 13023 PAC Device Status Codes
13101 ... 13126 PRI Device Status Codes (ASCII printer)
13201 ... 13260 SPA Device Status Codes (SPA master)
13302 ... 13306 BPO (Bit Pad One) Device Status Codes
13272 ... 13371 REX Device Status Codes (LON)
13401 ... 13444 LMK Device Status Codes (LON)
13450 ... 13499 SPI device status codes (RP570 slave)
13501 ... 13504 MON (Monitor) Device Status Codes
13551 ... 13553 ADE Device Status Codes (General ASCII)
13601 ... 13636 PCO Device Status Codes (RCOM master)
13651 ... 13679 WES Device Status Codes (Westinghouse F4F slave)
13751 ... 13762 ATR Device Status Codes (Alpha/IEC1107)

16
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

13800 ... 13840 PLC Device Status Codes (General PLC/Modbus)


13851 ... 13889 ICC Device Status Codes (IEC60870-5-101/103/104)
13901 ... 13954 DNP Device Status Codes (DNP 3.0)
14001 ... 14088 NET Network Layer Status Codes
16001 ... 16048 Common NET Link Layer Status Codes
16101 ... 16109 ANSI X3.28 Full Duplex Protocol Status Codes (XF)
16201 ... 16213 ANSI X3.28 Half Duplex Protocol Status Codes (XH)
16250 ... 16252 ADLP80 Slave Protocol Status Codes (AD)
16270 ... 16272 ADLP180 Slave Protocol Status Codes (AL)
16280 ... 16284 RP570 Slave Protocol Status Codes (RP)
16301 ... 16303 Common RAM Protocol Status Codes (RM)
16311 ... 16313 Integrated Link Status Codes (IL)
16320 ... 16327 LAN Link Status Codes (LN)
16600 ... 16653 On Line Configuration Errors in NETC Modules
16700 ... 16735 Auto Dialling Status Codes
16750 ... 16759 COM-1 Protocol Status Codes (CO)
16801 ... 16828 RP570 Master Protocol Status Codes (SR)
16851 ... 16861 P214 Master Protocol Status Codes (PR)
16901 ... 16901 FT1.2 Framing Status Codes (TC)
16950 ... 16956 INSUM Master Protocol Status Codes (IS)
17001 ... 17004 COMLI Slave Protocol Status Codes (CL)
17101 ... 17113 LCU500 Master Protocol Status Codes (LC)
17151 ... 17159 ADLP180 Master Protocol Status Codes (AM)
17201 ... 17233 SPA Master Protocol Status Codes (SP)
17251 ... 17260 General ASCII Protocol Status Codes (AG)
17301 ... 17327 RCOM Master Protocol Status Codes (PC)
17351 ... 17354 Westinghouse F4F Slave Protocol Status Codes (WE)
17401 ... 17410 Alpha Protocol Status Codes (AT)
17450 ... 17458 IEC1107 Protocol Status Codes (IE)
17500 ... 17520 General PLC/Modbus Protocol Status Codes (PG)
17550 ... 17556 LON Protocol Status Codes (LO)
17600 ... 17620 IEC60870-5-101/103 Protocol Status Codes (IG)
17650 ... 17700 DNP 3.0 Protocol Status Codes (DG)

17
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

17750 ... 17752 LAN Link Status Codes (LN)


17800 ... 17820 IEC60870-5-104 Protocol Status Codes (IT)
20000 ... 20176 PLC2 Error Codes (biased by 20000)
2000 ... 2578 SCA TLS Error Codes

Status Codes Transmitted by NET to External Devices

Operating System Status Codes

Win32 Error Codes

Data Transfer Status Codes

DDE Status Codes


ODBC Status Codes
ODBC Error Codes

Status Codes Transmitted by NET to External Devices

Status Codes Transmitted by NET to a PLC

18
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

4 Status Codes

About this chapter


In this chapter all SYS600 status codes are listed. Some possible reasons why these status
codes appear are also presented. Status codes are divided into the following sections:
4.1 Reliability of Data: Status codes that indicate reliability of data.
4.2 Base System Status Codes: Status codes that are related to the base system.
4.3 NET Status Codes: Status codes that are related to communication and
NET units.
4.4 Operating System Status Codes: Operating system status codes
4.5 Data Transfer Status Codes: Data transfer status codes
4.6 Status Codes Transmitted by NET to External Devices: Status codes
transmitted by a NET unit to external devices

4.1 Reliability of Data

4.1.1 OK Status Code

0 OK_STATUS

4.1.2 Almost OK Status Codes

1 SUSPICIOUS_STATUS

The reason why the value is uncertain may be:


• The value of a data object is uncertain, if the sampling has failed and the logging
function is other than DIRECT or COPY
• The element in the vector resulting from the vector functions HIGH, LOW, SUM
and MEAN has status 1, if not all elements in the argument vector have status code
0 or 3
• An element in the vector obtained with the vector function CUMULATE has this
status, if not all elements used for calculating it have status 0
• If a vector operation is done and the operands do not have the same number of
elements, the results of odd elements get this status
• If not all elements in a vector operation or function have status 0, the resulting
element gets status 1

19
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

• A process object gets this status when the RTU has marked the process object value
faulty
2 OBSOLETE_STATUS
The OV-attribute (BI, BO, AI, AO, DI, DO, DB, PC or BS) gets this status when the
connection to the RTU has been lost. This status code indicates that the value of the
OV-attribute may be out of date.
3 FAULTY_TIME_STATUS
A process object gets this status when the RTU has not marked the registration time
correctly.
4 AMBIGUOUS_TIME_STATUS
Local time represents a time that may be either standard or daylight saving time.
9 LAST_VALID_STATUS
The highest status code number that is considered valid.

4.1.3 Common Non-Valid Status Codes

10 NOT_SAMPLED_STATUS

The reasons may be:


• The value of the process object has not been received from the station
• The value of the data object has not been calculated
• The vector element has not got any value
• The element(s) in the result vectors from the functions HIGH, LOW, SUM, MEAN
and CUMULATE get the status 10, if all elements of the argument vector have
status codes=10

4.2 Base System Status Codes

4.2.1 SCIL Language (SCIL) Error Codes

101 SCIL_PROPAGATED_ERROR
102 SCIL_ARGUMENT_LIST_EXPECTED
103 SCIL_END_OF_SEQUENCE
104 SCIL_PROPAGATE_LOOP_EXIT
105 SCIL_QUIT_PROGRAM
106 SCIL_BIT_INDEX_OUT_OF_RANGE
The bit index is not in the range 0 ... 17 (in octal form).

20
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

107 SCIL_BLANK_FIELD
Blank spaces have been given to a numerical field.
108 SCIL_BOOLEAN_EXPRESSION_EXPECTED
109 SCIL_CLOSING_APOSTROPHE_EXPECTED
111 SCIL_EXPANSION_NOT_COMPILED
112 SCIL_COMMA_OR_RIGHT_PAREN_EXPECTED
A variable or argument list is erroneous.
113 SCIL_END_OF_ARGUMENT_LIST_EXPECTED
114 SCIL_END_OF_LINE_EXPECTED
115 SCIL_END_OF_LINE_INSTEAD_OF_OPERAND
117 SCIL_EXPANDED_LINE_TOO_LONG
After the variable extension the line contains more than 255 characters.
118 SCIL_EXTRANEOUS_BLOCK_END
The program contains a #BLOCK_END without a corresponding
#BLOCK.
119 SCIL_EXTRANEOUS_ELSE
The program contains an #ELSE which has no corresponding #IF.
120 SCIL_EXTRANEOUS_ELSE_IF
The program contains an #ELSE_IF which has no corresponding #IF.
121 SCIL_EXTRANEOUS_THEN
The program contains a #THEN which has no corresponding #IF.
122 SCIL_FIELD_TOO_SHORT
125 SCIL_GET_SUPPORTED_ONLY_FOR_ME_ATTRIBUTE
In a GET statement you may only use the attribute ME together with a
system object.
126 SCIL_ILLEGAL_EXPRESSION_TYPE
127 SCIL_ILLEGAL_KEYWORD
The name of the SCIL command is wrong.
131 SCIL_ILLEGAL_SYSTEM_DEVICE_NUMBER
The name of the system object is wrong.
134 SCIL_INDEX_OVERFLOW
The index of the variable is larger than the number of elements.
137 SCIL_INTEGER_OVERFLOW
Too large number has been entered into an integer field.
138 SCIL_INVALID_BIT_INDEX_RANGE
When defining an index range, either both limits or none is given with
a bit address.

21
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

Example:
STA1:SME(7^1..13^) and
STA1:SME(7^..13^4) are incorrect, but
STA1:SME(7^..13^) and
STA1:SME(7^1..13^4) are correct

139 SCIL_INVALID_NET_REPLY_FOR_BIT_GET
The base system and the frontend do not communicate properly. Contact
an ABB representative.
143 SCIL_INVALID_TIME
Time has been given in an incorrect way with the #SET_TIME command.
144 SCIL_LOG_OP_WITH_NON_BOOLEANS
The expression on the left or right side of a logical operand is not a
boolean value.
145 SCIL_LOW_INDEX_GREATER_THAN_HIGH
148 SCIL_MESSAGE_BUFFER_OVERFLOW
The control of the process (SET command) has failed, because the data
to be transmitted does not fit into the message buffer. Divide the SET
statement into at least two statements.
149 SCIL_MIXED_LOGICAL_OPERATORS
Parenthesis must be used to group the logical operators in expressions.
Example:
The statement %A > 10 AND %B < 5 OR %C == 3
is incorrect.
Correct statements:
%A >10 AND (%B < 5 OR %C == 3)
(%A > 10 AND %B < 5) OR %C == 3

151 SCIL_NEGATION_OF_NONBOOLEAN
A non-boolean value has been used with the NOT operand.
152 SCIL_NET_COMMUNICATION_TIMEOUT
This error code is normally caused by inconsistencies in the base system
and frontend configurations.
153 SCIL_NON_BINARY_ELEMENT_IN_BIT_SET
155 SCIL_NON_INTEGER_BIT_INDEX
156 SCIL_NON_INTEGER_INDEX
158 SCIL_NON_NUMERIC_FIELD
A non-numerical value has been entered into a numerical field.
159 SCIL_NEGATIVE_INDEX
162 SCIL_NOT_YET_IMPLEMENTED
167 SCIL_NO_MEMORY_ADDRESS_GIVEN

22
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

170 SCIL_OBJECT_EXPECTED
171 SCIL_OBJECT_NAME_EXPECTED
172 SCIL_OPERATOR_INSTEAD_OF_OPERAND
174 SCIL_VARIABLE_LIST_EXPECTED
The variable list together with a #EXEC, #LIST or #PRINT command
is incorrect.
175 SCIL_PRINTER_NUMBER_EXPECTED
176 SCIL_RELATIONAL_OPERATOR_EXPECTED
In a representation of type SELECTOR the condition is incorrectly
written.
178 SCIL_RESERVED_WORD_INSTEAD_OF_OPERAND
A SCIL command has been given instead of an expression.
179 SCIL_RIGHT_PAREN_EXPECTED
A right parenthesis is missing in a SCIL expression.
180 SCIL_RIGHT_PAREN_INSTEAD_OF_OPERAND
183 SCIL_THEN_EXPECTED
#THEN is missing in a conditional statement.
186 SCIL_UNARY_OP_WITH_NONNUMERIC
The positive and negative signs may only be followed by a numerical
value.
187 SCIL_INCOMPATIBLE_TYPES
Because of their data type, the two operands cannot be combined with
the operator in question.
188 SCIL_UNDEFINED_VARIABLE
190 SCIL_UNKNOWN_ATTRIBUTE
191 SCIL_UNKNOWN_FUNCTION
The base system main program is incorrectly generated. Contact an ABB
representative.
192 SCIL_UNKNOWN_SYSTEM_DEVICE_TYPE
The name of a system object is incorrectly formed.
193 SCIL_UNSUPPORTED_DATA_TYPE_IN_NET_REPLY
The base system and the frontend do not communicate properly. Contact
an ABB representative.
194 SCIL_VALUE_RANGE_OUT_OF_ORDER
The third and fourth arguments of the functions CLASSIFY and RE-
VERSE are incompatible, since the third argument is greater than the
fourth.
195 SCIL_VECTOR_ARGUMENT_EXPECTED
196 SCIL_NAME_LIST_USE_ERROR

23
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

197 SCIL_EMPTY_NAME_LIST_PATTERN
198 SCIL_ILLEGAL_NAME_LIST_PATTERN
201 SCIL_ARGUMENT_OUT_OF_RANGE
202 SCIL_INTEGER_ARGUMENT_EXPECTED
203 SCIL_REAL_ARGUMENT_EXPECTED
204 SCIL_BOOLEAN_ARGUMENT_EXPECTED
205 SCIL_TIME_ARGUMENT_EXPECTED
206 SCIL_TEXT_ARGUMENT_EXPECTED
207 SCIL_NUMERIC_ARGUMENT_EXPECTED
208 SCIL_REAL_VECTOR_ARGUMENT_EXPECTED
209 SCIL_ARGUMENT_LIST_TOO_LONG
210 SCIL_ARGUMENT_LIST_TOO_SHORT
211 SCIL_COMMA_EXPECTED
Commas are missing in an argument list.
212 SCIL_STRING_LENGTH_NOT_1
The argument of the text function ASCII_CODE should be a single
character or a vector of single characters.
213 SCIL_NON_NUMERIC_STRING
The argument of the function DEC_SCAN, OCT_SCAN or HEX_SCAN
contains illegal characters.
214 SCIL_BLANK_STRING
215 SCIL_SPACOM_COMMUNICATION_ERROR
220 SCIL_NO_ATTRIBUTE_ALLOWED
221 SCIL_EVENT_OBJECT_EXPECTED
222 SCIL_DIVIDE_BY_ZERO
The right operand in a division (/) or DIV or MOD operation is zero.
224 SCIL_INDEX_NOT_ALLOWED
225 SCIL_OBJECT_NOT_EXECUTABLE
The object type can not be executed with the #EXEC command.
229 SCIL_LIST_ARITHMETICS_ILLEGAL
List type expressions can not be operated with arithmetical operators.
231 SCIL_V_OBJECT_NOT_FOUND
234 SCIL_UNKNOWN_QUERY_ORDER
235 SCIL_QUERY_NOT_ACTIVE The PROD_QUERY
has been called though it was not initialized with the INIT_QUERY
command.

24
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

236 SCIL_MAX_QUERY_LENGTH_ZERO
Process query (PROD_QUERY) can not be performed because the
APLn:BQL attribute is == 0.
237 SCIL_ATTRIBUTE_NAME_EXPECTED
238 SCIL_LEFT_PAREN_EXPECTED
A left parenthesis is missing.
239 SCIL_INVALID_OCTAL_CONSTANT
240 SCIL_OPERAND_EXPECTED
241 SCIL_INDEX_RANGE_NOT_ALLOWED
242 SCIL_EQUAL_SIGN_EXPECTED
243 SCIL_LIST_VALUE_EXPECTED
244 SCIL_ONLY_INTEGER_AND_TEXT_EXPANSION_ ALLOWED
245 SCIL_INVALID_DATA_TYPE_FOR_EXPANSION
246 SCIL_LIST_OVERFLOW
248 SCIL_NON_TEXT_OBJECT_NAME
249 SCIL_EMBEDDED_BLANK_IN_OBJECT_NAME
An object name contains a blank space.
250 SCIL_BLANK_OBJECT_NAME
251 SCIL_OBJECT_NAME_TOO_LONG
252 SCIL_OBJECT_NAME_BEGIN_NON_ALPHANUMERIC
253 SCIL_INVALID_CHARACTER_IN_OBJECT_NAME
254 SCIL_EMBEDDED_BLANK_IN_NAME
256 SCIL_NAME_TOO_LONG
257 SCIL_NAME_BEGIN_NON_ALPHANUMERIC
258 SCIL_INVALID_CHARACTER_IN_NAME
259 SCIL_END_OF_SEARCH
260 SCIL_BEGINNING_OF_SEARCH
261 SCIL_INVALID_SEARCH_NUMBER
262 SCIL_INVALID_SEARCH_OBJECT_TYPE
263 SCIL_INVALID_SEARCH_ORDER_FOR_OBJ_TYPE
264 SCIL_INVALID_SEARCH_START_LOCATION
265 SCIL_INVALID_APPLICATION_NUMBER
266 SCIL_INVALID_OBJECT_TYPE
267 SCIL_INVALID_OBJECT_INDEX

25
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

268 SCIL_UNIT_NUMBER_OUT_OF_RANGE
269 SCIL_BIT_ADDRESS_OUT_OF_RANGE
270 SCIL_SEARCH_NOT_INITIALIZED
The browsing with NEXT and PREV has not been initialized with the
#SEARCH command.
271 SCIL_AGGREGATE_TOO_LONG
272 SCIL_DATA_FETCH_ARGUMENT_3_INVALID
273 SCIL_DATA_FETCH_ARGUMENT_4_INVALID
274 SCIL_DATA_FETCH_INVALID_INDEX1
275 SCIL_DATA_FETCH_INVALID_STEP
276 SCIL_DATA_FETCH_INVALID_SHIFT
277 SCIL_LIST_ARGUMENT_EXPECTED
278 SCIL_DATA_STORE_ARGUMENT_4_INVALID
279 SCIL_DATA_STORE_INVALID_INDEX1
280 SCIL_DATA_STORE_INVALID_STEP
282 SCIL_APL_APL_COMMUNICATION_TIMEOUT
283 SCIL_APL_APL_REPLY_SEQUENCE_ERROR
284 SCIL_APL_APL_COMMAND_SEQUENCE_ERROR
285 SCIL_APL_APL_MESSAGE_INCONSISTENT
286 SCIL_APL_APL_COMMAND_BUFFER_OVERFLOW
287 SCIL_APL_APL_UNKNOWN_COMMAND_FUNCTION
289 SCIL_TEXT_EXPRESSION_EXPECTED
291 SCIL_INVALID_RTU_OBJECT_FOR_BIT_SET
292 SCIL_RTU_OBJECT_NOT_SETTABLE
293 SCIL_INVALID_DATA_TYPE_IN_RTU_SET
296 SCIL_APPLICATION_IS_COLD
297 SCIL_APPLICATION_IS_NOT_HOT
298 SCIL_FILE_NUMBER_OUT_OF_RANGE
299 SCIL_FILE_NUMBER_ALREADY_IN_USE
300 SCIL_FILE_NUMBER_NOT_IN_USE
301 SCIL_VARIABLE_NAME_EXPECTED
302 SCIL_KEY_LENGTH_OUT_OF_RANGE
303 SCIL_DATA_TO_BE_WRITTEN_TOO_LONG
304 SCIL_SPACOM_PROTOCOL_NOT_SUPPORTED

26
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

307 SCIL_INDEX_TOO_BIG
308 SCIL_NUMERIC_VECTOR_ARGUMENT_EXPECTED
310 SCIL_INVALID_SEARCH_ORDER
311 SCIL_TOO_MANY_NESTED_STATEMENTS
312 SCIL_EXTRANEOUS_LOOP_EXIT
313 SCIL_EXTRANEOUS_LOOP_END
314 SCIL_BLOCK_END_MISSING
315 SCIL_LOOP_END_MISSING
316 SCIL_INVALID_ERROR_KEYWORD
317 SCIL_INVALID_ON_KEYWORD
318 SCIL_EVENT_OR_ERROR_KEYWORD_EXPECTED
320 SCIL_INTEGER_EXPRESSION_EXPECTED
321 SCIL_MAX_LOOP_COUNT_EXCEEDED
322 SCIL_ELLIPSE_EXPECTED
323 SCIL_INVALID_DATA_TYPE_IN_SET
324 SCIL_PROGRAM_TOO_LONG
325 SCIL_PROGRAM_EXTERNALLY_TERMINATED
326 SCIL_PATH_NAME_TOO_LONG
328 SCIL_FILE_NAME_TOO_LONG
329 SCIL_INVALID_CHARACTER_IN_FILE_NAME
330 SCIL_EMPTY_FILE_NAME
333 SCIL_TOO_MANY_DIRECTORIES_IN_PATH
334 SCIL_UNDEFINED_PATH
335 SCIL_EMPTY_PATH
337 SCIL_TOO_MANY_LIBRARIES_IN_REPLIB
338 SCIL_UNDEFINED_REPLIB
339 SCIL_EMPTY_REPLIB_DEFINITION
340 SCIL_REPLIB_NAME_EXPECTED
341 SCIL_INVALID_LIBRARY_DEFINITION
343 SCIL_PATH_NAME_EXPECTED
344 SCIL_INVALID_DIRECTORY_DEFINITION
345 SCIL_STATUS_CODE_OUT_OF_RANGE
346 SCIL_GET_NOT_SUPPORTED_FOR_THIS_STATION

27
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

347 SCIL_BIT_STRING_ARGUMENT_EXPECTED
348 SCIL_INTEGER_OR_BIT_ARGUMENT_EXPECTED
350 SCIL_BIT_SCAN_ARGUMENT_NOT_0_1
351 SCIL_IP_NUMBER_OUT_OF_RANGE
352 SCIL_INVALID_IP_NAME
353 SCIL_INTEGRATED_PROGRAM_NOT_STARTED
354 SCIL_INTEGRATED_PROGRAM_ALREADY_STARTED
355 SCIL_NO_APPLICATION_CONTEXT
357 SCIL_INVALID_GC_NUMBER
358 SCIL_GC_NUMBER_OUT_OF_RANGE
359 SCIL_INVALID_SCALING_FACTOR
360 SCIL_INVALID_COORDINATE
361 SCIL_INVALID_COLOR
362 SCIL_INVALID_FONT
363 SCIL_INVALID_GRAPHICS_OPTION
364 SCIL_INVALID_WIDTH
365 SCIL_INVALID_HEIGHT
366 SCIL_INVALID_RADIUS
367 SCIL_INVALID_SEMI_MAJOR_AXIS
368 SCIL_INVALID_ANGLE
369 SCIL_INVALID_GC_FUNCTION
370 SCIL_INVALID_LINE_WIDTH
371 SCIL_INVALID_LINE_STYLE
372 SCIL_INVALID_CAP_STYLE
373 SCIL_INVALID_JOIN_STYLE
374 SCIL_INVALID_DASH_LIST
375 SCIL_INVALID_DASH_OFFSET
376 SCIL_INVALID_ARC_MODE
377 SCIL_INVALID_GC_COMPONENT
378 SCIL_GC_COMPONENT_NAME_EXPECTED
379 SCIL_DOUBLE_GC_COMPONENT_NAME
380 SCIL_COLON_EXPECTED
381 SCIL_POP_WITHOUT_MATCHING_PUSH

28
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

382 SCIL_INVALID_CANVAS_ARGUMENT
383 SCIL_INVALID_COLOR_SPECIFICATION
384 SCIL_INVALID_FONT_SPECIFICATION
386 SCIL_CANVAS_NOT_FOUND
387 SCIL_INVALID_CANVAS_NAME
388 SCIL_PEND_OFF_WITHOUT_MATCHING_PEND_ON
389 SCIL_UNDEFINED_COLOR
390 SCIL_UNDEFINED_FONT
391 SCIL_UNDEFINED_GC
392 SCIL_INVALID_RGB_COLOR
393 SCIL_INVALID_GRAPHICAL_SCOPE
394 SCIL_INTEGER_OR_VECTOR_ARGUMENT_EXPECTED
395 SCIL_COLOR_NUMBER_OUT_OF_RANGE
397 SCIL_FONT_NUMBER_OUT_OF_RANGE
398 SCIL_APPLICATION_TEXT_DATABASE_FULL
399 SCIL_MEMORY_EXHAUSTED
400 SCIL_TIME_OR_LIST_ARGUMENT_EXPECTED
401 SCIL_CL_OR_US_MISSING_OR_INVALID
402 SCIL_KEY_POSITION_OUT_OF_RANGE
403 SCIL_INVALID_SORT_DATA
404 SCIL_INVALID_SELECT_ATTRIBUTE_VECTORS
405 SCIL_VECTOR_OR_LIST_ARGUMENT_EXPECTED
406 SCIL_SELECT_CONDITION_TOO_LONG
407 SCIL_CONTINUATION_LINE_MISSING
408 SCIL_UNKNOWN_IDENTIFIER
409 SCIL_IDENTIFIER_TOO_LONG
410 SCIL_IDENTIFIER_EXPECTED
411 SCIL_COMMAND_TOO_LONG
412 SCIL_CLOSING_QUOTE_MISSING
413 SCIL_WHEN_OUTSIDE_CASE
414 SCIL_OTHERWISE_OUTSIDE_CASE
415 SCIL_EXTRANEOUS_CASE_END
416 SCIL_CASE_END_MISSING

29
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

417 SCIL_INVALID_CASE_SELECTOR_DATA_TYPE
418 SCIL_WHEN_OR_OTHERWISE_EXPECTED
419 SCIL_CASE_END_EXPECTED
420 SCIL_FILE_IS_READ_ONLY
421 SCIL_ATTRIBUTE_NOT_FOUND
422 SCIL_CLASS_NAME_EXPECTED
423 SCIL_WINDOW_NAME_EXPECTED
424 SCIL_PICTURE_NAME_EXPECTED
425 SCIL_REPRESENTATION_NAME_EXPECTED
426 SCIL_EMBEDDED_BLANK_IN_IDENTIFIER
427 SCIL_INVALID_CHARACTER_IN_IDENTIFIER
428 SCIL_IDENTIFIER_MUST_BEGIN_WITH_LETTER
430 SCIL_INVALID_NAME
431 SCIL_INVALID_EDIT_KEYWORD
432 SCIL_EXECUTION_DELAY_OUT_OF_RANGE
433 SCIL_INVALID_DATA_TYPE
434 SCIL_STRING_TOO_LONG
435 SCIL_STRING_ARGUMENT_EXPECTED
436 SCIL_INTEGER_VECTOR_EXPECTED
437 SCIL_TEXT_VECTOR_EXPECTED
438 SCIL_NEGATIVE_MODULUS
439 SCIL_INTEGER_TEXT_VECTOR_EXPECTED
440 SCIL_BYTE_STRING_ARGUMENT_EXPECTED
441 SCIL_COMMA_OR_COLON_EXPECTED
442 SCIL_CORRUPTED_P_CODE
443 SCIL_COMPILER_VERSION_MISMATCH
444 SCIL_STACK_OVERFLOW
445 SCIL_INDEX_STACK_OVERFLOW
446 SCIL_IDENTIFIER_STACK_OVERFLOW
447 SCIL_VARIABLE_STACK_OVERFLOW
448 SCIL_VECTOR_TOO_SHORT
449 SCIL_VARIABLE_IS_READ_ONLY
450 SCIL_CLASS_NOT_FOUND

30
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

451 SCIL_INSTANCE_OF_CLASS_NOT_ALLOWED
452 SCIL_ATTRIBUTE_IS_WRITE_ONLY
453 SCIL_ATTRIBUTE_IS_READ_ONLY
454 SCIL_METHOD_NOT_FOUND
456 SCIL_INVALID_ENUMERATION_CONSTANT
457 SCIL_INVALID_FLAG_CONSTANT
459 SCIL_INVALID_POINT_ARGUMENT
460 SCIL_INVALID_RECT_ARGUMENT
461 SCIL_EXCEPTION_IN_METHOD_CALL
462 SCIL_EXCEPTION_IN_SET_ATTRIBUTE
463 SCIL_EXCEPTION_IN_GET_ATTRIBUTE
464 SCIL_EXCEPTION_IN_CREATE
465 SCIL_EXCEPTION_IN_CREATE_APPEND
466 SCIL_CALLBACK_NOT_FOUND
467 SCIL_CHARACTER_ARGUMENT_EXPECTED
468 SCIL_SQL_ALLOC_ENVIRONMENT_FAILED
469 SCIL_SQL_ENVIRONMENT_LOST
470 SCIL_TOO_MANY_OPEN_SQL_CONNECTIONS
471 SCIL_SQL_CONNECTION_NOT_OPEN
472 SCIL_TOO_MANY_SQL_STATEMENTS_OPEN
473 SCIL_SQL_STATEMENT_NOT_OPEN
476 SCIL_INVALID_KEYWORD_ARGUMENT
477 SCIL_VS_OBJECT_NOT_FOUND
478 SCIL_NOT_A_VS_OBJECT
479 SCIL_VS_OBJECT_OF_WRONG_CLASS
480 SCIL_TRACE_NOT_ACTIVE
481 SCIL_VECTOR_TOO_LONG
482 SCIL_DDE_INSTANCE_INIT_FAILED
483 SCIL_TOO_MANY_OPEN_DDE_CONNECTIONS
484 SCIL_DDE_CONNECTION_NOT_OPEN
485 SCIL_INVALID_COLUMN_POSITION
486 SCIL_INVALID_COLUMN_WIDTH
487 SCIL_COLUMN_COUNT_MISMATCH

31
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

488 SCIL_COLUMN_LENGTH_MISMATCH
489 SCIL_VECTOR_VECTOR_ARGUMENT_EXPECTED
490 SCIL_INVALID_FILE_NAME
491 SCIL_NOT_A_VALID_RESOURCE_FILE
492 SCIL_TAG_NOT_FOUND
493 SCIL_LOAD_OF_CLASS_NOT_ALLOWED
494 SCIL_EXCEPTION_IN_LOAD
495 SCIL_INVALID_PROGRAM_RESOURCE
496 SCIL_INVALID_METHOD_NAME
497 SCIL_PICTURE_ALREADY_LOADED
498 SCIL_PICTURE_NOT_LOADED
499 SCIL_PICTURE_LOADED_FOR_READ_ONLY
500 SCIL_REPRESENTATION_LIBRARY_ALREADY_LOADED
501 SCIL_REPRESENTATION_LIBRARY_NOT_LOADED
502 SCIL_REPRESENTATION_ALREADY_LOADED
503 SCIL_REPRESENTATION_NOT_LOADED
504 SCIL_DUPLICATE_OBJECT_NAME
505 SCIL_ATTRIBUTE_OR_METHOD_NOT_FOUND
506 SCIL_PERIOD_EXPECTED
507 SCIL_OBJECT_IS_NOT_LOCAL
508 SCIL_ACTION_METHOD_NOT_FOUND
509 SCIL_EXTERNAL_PROGRAM_DOES_NOT_RESPOND
510 SCIL_AEP_NOT_STARTED
511 SCIL_INVALID_AEP_NAME
513 SCIL_MAIN_DIALOG_MAY_NOT_BE_CREATED
514 SCIL_INVALID_COPY_LOGICALS
515 SCIL_INVALID_DEFAULT_PATH
516 SCIL_VS_OBJECT_NOT_STARTED
517 SCIL_CONTEXT_BOUNDARY_VIOLATION
518 SCIL_OBJECT_OF_WRONG_CLASS
519 SCIL_MOUSE_NOT_SUPPORTED_IN_MAIN_DIALOG
520 SCIL_METHODS_NOT_AN_ARRAY
521 SCIL_METHOD_DESCRIPTOR_NOT_A_DICTIONARY

32
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

522 SCIL_METHOD_TYPE_MISSING
523 SCIL_METHOD_TYPE_NOT_AN_INTEGER
524 SCIL_METHOD_TYPE_OUT_OF_RANGE
525 SCIL_METHOD_PROGRAM_MISSING
526 SCIL_METHOD_PROGRAM_NOT_A_STRING
527 SCIL_METHOD_CYCLE_MISSING
528 SCIL_METHOD_CYCLE_NOT_A_FLOAT
529 SCIL_METHOD_CYCLE_OUT_OF_RANGE
530 SCIL_METHOD_NAME_MISSING
531 SCIL_METHOD_NAME_NOT_A_STRING
532 SCIL_ACTION_DOES_NOT_EXIST
534 SCIL_METHOD_EVENTS_MISSING
535 SCIL_METHOD_EVENTS_NOT_AN_ARRAY
536 SCIL_METHOD_EVENT_NOT_A_STRING
537 SCIL_RESERVED_OBJECT_NAME
539 SCIL_ATTRIBUTE_IS_LOAD_ONLY
540 SCIL_INVALID_OBJECT_NAME
541 SCIL_INVALID_LANGUAGE_NAME
542 SCIL_TEXTS_NOT_A_DICTIONARY
543 SCIL_INVALID_TEXT_IDENTIFIER
544 SCIL_TEXT_DESCRIPTOR_NOT_A_DICTIONARY
545 SCIL_INVALID_TEXT_TRANSLATION
546 SCIL_INVALID_FONT_ATTRIBUTE_NAME
547 SCIL_INVALID_FONT_ATTRIBUTE_VALUE
548 SCIL_INVALID_FONT_FAMILY
549 SCIL_INVALID_FONT_POINT_SIZE
550 SCIL_INVALID_FONT_SCIL_SIZE
551 SCIL_INVALID_FONT_FACE
552 SCIL_INVALID_FONT_ENCODING
553 SCIL_OBJECT_REFERENCED_BY_ANOTHER_OBJECT
554 SCIL_OBJECT_REFERENCE_LOOP
555 SCIL_INVALID_SECTION_NAME
556 SCIL_INVALID_KEY_NAME

33
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

557 SCIL_INVALID_KEY_VALUE
558 SCIL_SECTION_DOES_NOT_EXIST
559 SCIL_KEY_DOES_NOT_EXIST
560 SCIL_INVALID_PARAMETER_FILE_FORMAT
562 SCIL_INVALID_INT_PAIR_VALUE
565 SCIL_UNLOCK_WITHOUT_MATCHING_LOCK
566 SCIL_INVALID_SEARCH_DIRECTION
567 SCIL_INVALID_SEARCH_CONDITION
568 SCIL_SEARCH_START_ARGUMENT_MISSING
569 SCIL_INVALID_SEARCH_OBJECT_LIST
570 SCIL_DUPLICATE_ATTRIBUTE_OR_METHOD_NAME
571 SCIL_PRODUCT_NOT_FOUND
572 SCIL_PAK_KEY_LIST_TOO_LONG
573 SCIL_INVALID_PAK_KEY_VALUE
574 SCIL_INVALID_PAK_KEY_LIST
575 SCIL_AUTHORIZATION_KEY_MISMATCH
577 SCIL_SYSTEM_ID_MISMATCH
578 SCIL_NO_SCIL_CONTEXT
579 SCIL_EXCEPTION_IN_COMPLETE
580 SCIL_VARIABLE_ALIASING_ERROR
581 SCIL_ALIAS_STACK_OVERFLOW
583 SCIL_TWO_LETTER_ATTRIBUTE_NAME_EXPECTED
584 SCIL_HISTORY_DATABASE_MANAGER_NOT_STARTED
585 SCIL_TOO_MANY_HDB_SESSIONS
586 SCIL_INDEX_OUT_OF_RANGE
587 SCIL_INTEGER_OR_TEXT_ARGUMENT_EXPECTED
588 SCIL_TOO_MANY_ATTRIBUTES
589 SCIL_NO_DIRECTORIES_SPECIFIED
590 SCIL_NO_PERIOD_SPECIFIED
591 SCIL_PERIOD_TOO_LONG
592 SCIL_INVALID_EVENT_IDENTIFIER
593 SCIL_TOO_MANY_DIRECTORIES
594 SCIL_NOT_A_BCD_NUMBER

34
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

595 SCIL_TOO_MANY_IMAGES
596 SCIL_NO_IMAGE_SPECIFIED
597 SCIL_INVALID_DATA_POINT_VALUE
598 SCIL_INVALID_DATA_SET_VALUE
599 SCIL_NOT_A_SCIL_COMMAND
600 SCIL_INVALID_VECTOR_LENGTH
601 SCIL_INVALID_FM_TAG
602 SCIL_FM_HIERARCHY_VIOLATION
603 SCIL_FM_HIERARCHY_TOO_DEEP
604 SCIL_INVALID_FM_DRIVE
605 SCIL_INVALID_FM_DIRECTORY
606 SCIL_INVALID_FM_FILE
607 SCIL_INVALID_UNC_NAME
608 SCIL_NULL_FILE_NAME
609 SCIL_NO_CURRENT_DIRECTORY
610 SCIL_CONTRADICTORY_KEYWORD_ARGUMENT
611 SCIL_DRIVE_TAG_EXPECTED
612 SCIL_DIRECTORY_TAG_EXPECTED
613 SCIL_FILE_TAG_EXPECTED
614 SCIL_ABSOLUTE_TAG_EXPECTED
617 SCIL_PARAMETER_FILE_LINE_TOO_LONG
618 SCIL_NAME_MUST_BEGIN_WITH_SLASH
619 SCIL_DIRECTORY_OR_FILE_TAG_EXPECTED
620 SCIL_TEXT_OR_BYTE_STRING_ARGUMENT_EXPECTED
621 SCIL_INVALID_AXIS_PROPERTY_LIST
622 SCIL_INVALID_DATASET_PROPERTY_LIST
623 SCIL_INVALID_HAIRLINE_PROPERTY_LIST
624 SCIL_INVALID_PROGRAM_STRUCTURE
625 SCIL_WRONG_HP_ATTRIBUTE_SETTING
This error is raised when INIT_QUERY by order "E" or "H" is attempted
while history database (or no history) is used by the application
(APL:BHP is set to "LOG").

35
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

626 SCIL_PRINT_JOB_NOT_CONFIRMED
User pressed Cancel on VS_PRINT_OBJECT's print job confirmation
dialog.
627 SCIL_PRINT_SETUP_NOT_CONFIRMED
User pressed Cancel on VS_PRINT_OBJECT's print setup dialog.
628 SCIL_PRINT_SESSION_ALREADY_OPEN
VS_PRINT_OBJECT' s print session was already open when calling
_OPEN_PRINT_SESSION. Session has been opened by
_OPEN_PRINTER or _OPEN_PRINT_SESSION. This error is returned
also by _SETUP_PRINTER if print session is already open.
629 SCIL_PRINT_SESSION_NOT_OPEN
VS_PRINT_OBJECT' s print session was not open when calling
_CLOSE_PRINT_SESSION
630 SCIL_KERNEL_REVISION_MISMATCH
This status code may be returned in the STATUS attribute of the return
value of the LICENSE_MANAGER("GET", ) function.
631 SCIL_LICENSE_HAS_EXPIRED
This status code may be returned in the STATUS attribute of the return
value of the LICENSE_MANAGER("GET", ) function.
632 SCIL_DUPLICATE_VARIABLE_OR_ARGUMENT_NAME
Attempt to declare two arguments or variables with same name.
633 SCIL_LOCAL_COMMAND_OUT_OF_ORDER #LOCAL
command may not be preceded by other commands than #ARGUMENT.
634 SCIL_ARGUMENT_NAME_EXPECTED
Argument list in #ARGUMENT command invalid.
635 SCIL_ARGUMENT_COMMAND_OUT_OF_ORDER
#ARGUMENT command may not be preceded by other commands.
636 SCIL_ACTUAL_ARGUMENT_MISSING
Caller of SCIL program has not supplied value to each named argument.
637 SCIL_ARGUMENTS_ARE_READ_ONLY
Attempt to modify the value of an argument.
638 SCIL_EXPANDED_NAME_NOT_ALLOWED
Attempt to create the name of local variable using expansion.
639 SCIL_REFERENCE_STACK_OVERFLOW
The depth of variable component access exceeds 100 components
(compiled SCIL only).
640 SCIL_VECTOR_VALUE_EXPECTED
Attempt to use indexing on data that is not a vector.
641 SCIL_OBJECT_PATH_TOO_DEEP
An object path of a VS object contains more than 63 components.

36
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

642 SCIL_COMPONENT_NOT_SETTABLE
Attempt to set a component of an attribute of an object when the attribute
may be written only as a whole.
643 SCIL_ATTRIBUTE_ALIASING_ERROR
Attempt to modify the value of an object attribute while the attribute is
referenced somewhere else.
644 SCIL_REGISTRY_KEY_NOT_FOUND
The specified key is not found in the registry.
645 SCIL_REGISTRY_VALUE_NOT_FOUND
The registry key does not contain the specified value name.
646 SCIL_REGISTRY_DATATYPE_NOT_SUPPORTED
The data type of the registry value is not supported by SCIL.
647 SCIL_NOT_CALLED_BY_ERROR_HANDLER
Function was called by somebody else than an error handler.
648 SCIL_OUT_OF_CALL_STACK
This code is returned in STATUS attribute of the function call result, if
frame number is out of range.
649 SCIL_ALIAS_CHECKING_BEEN_DISABLED
Arguments may not be queried because NO_ALIAS_CHECKING has
been used.
650 SCIL_TOO_MANY_AEPS
Attempt to start more than 999 application extension programs.
651 SCIL_INVALID_SYS_TIME_PAR_FILE_FORMAT
Parameter file SYS_TIME.PAR is not of valid format.
652 SCIL_INVALID_TIME_ZONE_RULE
Given time zone rule is invalid.
653 SCIL_INVALID_CL_ATTRIBUTE_VALUE
The CL attribute of qualified time is not of data type TIME.
654 SCIL_INVALID_MS_ATTRIBUTE_VALUE
The MS attribute of qualified time is of invalid data type or out of range.
655 SCIL_INVALID_DS_ATTRIBUTE_VALUE
The DS attribute of qualified time is not BOOLEAN.
656 SCIL_CL_ATTRIBUTE_MISSING
CL attribute is missing in a qualified time.
657 SCIL_DOUBLE_ARGUMENT_EXPECTED
The argument of a high precision function is of an invalid data type.
658 SCIL_DATA_FILE_INCONSISTENT
The SCIL database file has been corrupted.

37
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

659 SCIL_DATA_FILE_VERSION_MISMATCH
The SCIL database file has been written in a newer format than can be
handled.
660 SCIL_DATA_SECTION_NOT_FOUND
The SCIL database does not contain the given section.
661 SCIL_DATA_SECTION_ALREADY_EXISTS
Attempt to create a SCIL database section that already exists.
662 SCIL_TOO_MANY_DATA_FILES_OPEN
Only 10 SCIL databases may be open simultaneously.
663 SCIL_INVALID_DATA_FILE_HANDLE
The handle of the SCIL database is not an integer 1 ... 10.
664 SCIL_DATA_FILE_NOT_OPEN
Attempt to use a SCIL database that is not open.
665 SCIL_INVALID_DATA_FILE_COMPONENT
The 'component' argument is not syntactically valid.
666 SCIL_LINE_TOO_LONG
The text line is too long (> 255 characters).
667 SCIL_INVALID_INDEX
The given object index is invalid.
668 SCIL_OPC_NAME_NOT_FOUND
Attempt to access a non-existing name in the OPC Name Database.
669 SCIL_OPC_NAME_ALREADY_EXISTS
Attempt to create an OPC name that already exists as the value of the
ON attribute of some application object.
670 SCIL_OPC_NAME_TOO_LONG
Attempt to create an OPC name that is longer than 255 characters.
671 SCIL_INVALID_OPC_NAME_DEFINITION
The OPC name definition is not a list, or does not contain the SCIL at-
tribute.
672 SCIL_APPLICATION_NUMBER_NOT_ALLOWED
673 SCIL_INVALID_OBJECT_SUBTYPE
The 'subtype' argument of OBJECT_ATTRIBUTE_INFO is invalid.
674 SCIL_INVALID_CSV_FIELD_SPECIFICATION
The 'fields' argument of CSV_TO_SCIL is invalid.
675 SCIL_TOO_MANY_CSV_FIELDS
The CSV record contains more fields than expected.
676 SCIL_CSV_FIELD_DELIMITER_NOT_KNOWN
The CSV_TO_SCIL function was unable to deduce the used field delim-
iter character.

38
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

677 SCIL_CSV_SYNTAX_ERROR
The syntax of the CSV record is invalid.
678 SCIL_CSV_CLOSING_QUOTE_MISSING
The closing quote (") was missing in the CSV record.
679 SCIL_CSV_FIELDS_MISSING
The CSV record contains fewer fields than expected.
680 SCIL_LICENSE_MIRRORING_VIOLATION
The system is not licensed to create stations with this mirroring role.
681 SCIL_LICENSE_HSB_VIOLATION
The system is not licensed to start shadowing.
682 SCIL_LICENSE_PROTOCOL_VIOLATION
The system is not licensed to create stations of this station type.
683 SCIL_LICENSE_PROCESS_IO_VIOLATION
The system has used all the licensed process io’s.
684 SCIL_LICENSE_APPL_OPC_SERVERS_VIOLATION
Too many application OPC servers (AOPCS) try to connect to the OPC
Data Access Server.
685 SCIL_LICENSE_OPC_DA_CLIENTS_VIOLATION
Too many OPC Data Access Clients started.
686 SCIL_LICENSE_OPC_AE_CLIENTS_VIOLATION
Too many OPC Alarm and Event Clients started.
687 SCIL_INVALID_OPC_SERVER_CLSID
The syntax of the class id (CLSID) attribute or argument is invalid.
688 SCIL_OPC_SERVER_NOT_FOUND
The OPC server cannot be found or started in the specified node.
689 SCIL_OPC_COMMUNICATION_ERROR
There is currently no connection to the OPC server, or the communication
fails during the execution of the SCIL function.
690 SCIL_OPC_CLIENT_NOT_RUNNING
Attempt to access an OPC client with SCIL while the client is not run-
ning.
691 SCIL_INVALID_ACK_TIME
The 'cookie' or 'active_time' argument of OPC_AE_ACKNOWLEDGE
function is invalid (not recognized by the server).
693 SCIL_LICENSE_OPC_AE_SERVER_VIOLATION
Attempt to start an OPC Alarms and Events Server without a license.
694 SCIL_LICENSE_HISTORY_DATA_VIOLATION
The system has used all the licensed data object records.
695 SCIL_INVALID_ALARM_LIST
The 'lists' argument of SCIL_APPLICATION_ALARMS call is invalid.

39
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

696 SCIL_AMBIGUOUS_CLSID
The class ID of the OPC server is given as an argument and also defined
by the node.
697 SCIL_OPC_ACCESS_DENIED
The user and password of impersonated OPC access are wrong.
698 SCIL_APPLICATION_STATE_IS_CHANGING
Attempt to change the application state (AS) or the shadowing state (SS)
of an application while another state change is in progress.
699 SCIL_INVALID_DATE
700 SCIL_YEAR_OUT_OF_RANGE
701 SCIL_MONTH_OUT_OF_RANGE
702 SCIL_DAY_OUT_OF_RANGE
703 SCIL_INVALID_HOUR
704 SCIL_INVALID_MINUTE
705 SCIL_INVALID_SECOND
706 SCIL_INVALID_MILLISECONDS
707 SCIL_INVALID_RESOLUTION
710 SCIL_LICENSE_BUSBAR_COLORING_VIOLATION
The system is not licensed to start network topology calculation.
711 SCIL_REAL_EXPRESSION_EXPECTED
712 SCIL_LIST_VECTOR_EXPECTED
713 SCIL_APL_BOI_UNDEFINED
Query in OI (Object Identifier) order not possible because the OI structure
(APL:BOI) is undefined.
714 SCIL_OI_STRUCTURE_MISMATCH
The given OI (Object Identifier) does not comply to the OI structure of
the application (APL:BOI).
715 SCIL_NO_MATCH_IN_CASE_FUNCTION
The selector argument does not match with any case branch and "OTH-
ERWISE" branch is not given.
716 SCIL_DATA_TYPE_MISMATCH
The arguments of CHOOSE function are not type compatible.
717 SCIL_DYNAMIC_ATTRIBUTES_NOT_ALLOWED
Only configuration attributes are allowed in this SDDL use case.
718 SCIL_ATTRIBUTE_NOT_READABLE
Write-only attributes are not allowed in SDDL expressions.
719 SCIL_APL_CONTEXT_NOT_VISIBLE
The context variable APL is not allowed in this SDDL use case.

40
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

720 SCIL_SYS_CONTEXT_NOT_VISIBLE
The context variable SYS is not allowed in this SDDL use case.
721 SCIL_UNKNOWN_CONTEXT_VARIABLE
The given context variable does not match any of the object attributes.
722 SCIL_FUNCTION_HAS_SIDE_EFFECTS
Functions used in SDDL expressions are not allowed to have any side
effects.
723 SCIL_FUNCTION_NOT_DETERMINISTIC
Only deterministic functions are allowed in this SDDL use case.
724 SCIL_FUNCTION_SCOPE_TOO_WIDE
The scope of the function is too wide in this SDDL use case (accesses
data outside the SDDL context).
726 SCIL_INVALID_ATTRIBUTE_REFERENCE
Reference to an object attribute does not match the data type of the at-
tribute.
727 SCIL_INVALID_SDDL_OPTION
728 SCIL_ONLY_COMMON_ATTRIBUTES_ALLOWED
Object subtype specific attributes are not allowed in this SDDL use case.
729 SCIL_EXPANSION_NOT_ALLOWED_IN_SDDL
Variable expansion must not be used in SDDL expression.
730 SCIL_GLOBAL_VARIABLES_NOT_ALLOWED_IN_SDDL SDDL
expressions have no access to global variables.
731 SCIL_VS_OBJECTS_NOT_ALLOWED_IN_SDDL
SDDL expressions have no access to Visual SCIL objects.
732 SCIL_OBJECT_REFERENCE_NOT_ALLOWED_IN_SDDL
SDDL expressions do have access to object attributes only via context
variables.
733 SCIL_LICENSE_HIS_DATABASES_VIOLATION
Attempt to connect to too many Historian databases.
734 SCIL_LICENSE_HIS_TAGS_VIOLATION
Attempt to connect too many objects to Historian database.
735 SCIL_API_MESSAGE_INCONSISTENT
736 SCIL_API_CONNECTION_CLOSED
737 SCIL_API_VERSION_MISMATCH
738 SCIL_API_SERVER_START_FAILURE
739 SCIL_READ_ONLY_VIOLATION
SCIL program running in read-only mode attempts to modify system
data.
740 SCIL_EXTERNAL_API_ACCESS_DENIED

41
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4.2.2 Picture Handling (PICO) Status Codes

805 PICO_PICTURE_NOT_FOUND
812 PICO_CREATE_ERROR_IN_SEND
Handling of the help file PR_SPOOL _n.PIR (n = monitor number),
needed for the execution of the SEND_PIC statement, does not succeed.
815 PICO_NO_SEND_DEVICE_NAME
The device name (LPT) is missing in a !SEND_PIC statement.
817 PICO_INVALID_SEND_DEVICE_NUMBER
820 PICO_ECHO_REPRESENTATION_NOT_A_FIELD
The representation type of the window in the INPUT_VAR statement
is not a FIELD.
821 PICO_ECHO_WINDOW_OUT_OF_SCREEN
The window given in an !INPUT_VAR statement falls outside the screen.
822 PICO_ECHO_REPRESENTATION_NOT_FOUND
823 PICO_ILLEGAL_VALUE_TYPE_FOR_ECHO_FIELD
The field mentioned in !INPUT_VAR statement has the wrong datatype.
824 PICO_GET_FIELD_SPEC_ERROR_IN_INPUT
826 PICO_GET_FIRST_COMMAND_ERROR_IN_INPUT
827 PICO_INPUT_ERROR
832 PICO_WINDOW_NOT_FOUND_IN_SHOW
The window called by !SHOW does not exist in the picture.
833 PICO_OPEN_REPR_ERROR_IN_SHOW
835 PICO_ILLEGAL_VALUE_TYPE_IN_SHOW
The expression to be shown in a window is not of the right data type.
848 PICO_INVALID_ERROR_ARGUMENT
849 PICO_UPDATE_INTERVAL_OUT_OF_RANGE
851 PICO_NO_ALTERNATIVE_OPEN
The value of the expression given with a !SHOW command has no
branch in the SELECTOR.
856 PICO_GET_NEXT_ALTERNATIVE_ERROR
858 PICO_OPEN_PICTURE_ERROR_IN_SHOW_PICTURE
The picture to be shown in the window can not be found.
860 PICO_GET_BACKGROUND_ERROR_IN_SHOW
865 PICO_EXTRANEOUS_MODULENAME
876 PICO_SCIL_ERROR_IN_KEY_SEQUENCE
878 PICO_SCIL_ERROR_IN_UPDATE_SEQUENCE

42
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

879 PICO_SCIL_ERROR_IN_DRAW_SEQUENCE
880 PICO_SCIL_ERROR_IN_START_SEQUENCE
881 PICO_SCIL_ERROR_IN_EVENT_SEQUENCE
882 PICO_SCIL_ERROR_IN_EXIT_SEQUENCE
883 PICO_SCIL_ERROR_IN_CALLBACK_SEQUENCE
884 PICO_SCIL_ERROR_IN_BACKGROUND_SEQUENCE
885 PICO_SCIL_ERROR_IN_METHOD_SEQUENCE
888 PICO_GET_FIELD_SPEC_ERROR_IN_SHOW
889 PICO_EVALUATE_CONDITION_ERROR
The conditional expression in a SELECTOR is wrong.
892 PICO_WINDOW_FORMULA_EVALUATION_ERROR
The expression given in the window definition form is wrong.
896 PICO_NO_MODULE_TO_SEND_MESSAGE
The cause for the error message may be that one of the characters #, !
or @ is missing at the beginning of the line.
898 PICO_UNKNOWN_SEND_DEVICE
900 PICO_GET_BC_SPEC_ERROR_IN_SHOW
901 PICO_GET_MF_SPEC_ERROR_IN_SHOW
902 PICO_GET_WIN_EXT_ERROR_IN_SHOW
905 PICO_INVALID_EXTENSION_TYPE
906 PICO_INVALID_VALUES_IN_BC_SPEC
The definition of a bar or a curve is inconsequent.
910 PICO_EVALUATE_CONDITION_LINE_ERROR
A programmable exception is erroneous.
911 PICO_EVALUATE_LINE_ERROR_IN_BC_LIMITS
The limit expressions for a bar or a curve are erroneous.
921 PICO_WINDOW_NOT_FOUND
922 PICO_QUADRANT_OPEN_ERROR
923 PICO_TOO_MANY_NESTED_PICTURES
926 PICO_INVALID_WINDOW_POSITION
929 PICO_INPUT_KEY_ERROR
930 PICO_INVALID_INPUT_KEY_KEYWORD
931 PICO_MICRO_LIBRARY_MODE_ALREADY_SET
932 PICO_MICRO_LIBRARY_MODE_NOT_SET
933 PICO_APPLICATION_CLOSE_TIMEOUT

43
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

935 PICO_EDITOR_MODE_ALREADY_SET
936 PICO_EDITOR_MODE_NOT_SET
937 PICO_RECURSIVE_SHOW
939 PICO_TOO_MANY_NESTED_PUSH_COMMANDS
940 PICO_MEMORY_EXHAUSTED
941 PICO_WINDOW_ALREADY_EXISTS
943 PICO_NAMED_PROGRAM_NOT_FOUND
944 PICO_METHOD_NOT_FOUND
945 PICO_INVALID_CALLBACK_RESOURCE
946 PICO_REGISTER_TOO_LONG
947 PICO_WINDOW_HAS_NO_REPRESENTATION
950 PICO_NO_PARENT_WINDOW
951 PICO_PICTURE_NAME_MISSING
953 PICO_TOO_MANY_PICTURE_CONTEXTS
954 PICO_TOO_MANY_PICTURE_CONTAINERS
955 PICO_SEMIGRAPHICS_IN_MAIN_DIALOG
956 PICO_WINDOW_HAS_NO_CONTEXT
957 PICO_TOO_MANY_QUEUED_EXECUTIONS
958 PICO_MMC_PROGRAM_RUNNING
960 PICO_DRAWING_AREA_UNMANAGED
961 PICO_INPUT_TIMEOUT
962 PICO_MODULENAME_NOT_SUPPORTED

4.2.3 Report Database (REPF and REPR) Status Codes

1005 REPF_END_OF_LIST
1007 REPF_INDEX_TOO_HIGH
1009 REPF_LR_TOO_HIGH
1012 REPF_SOURCE_DOES_NOT_EXIST
1016 REPF_UNKNOWN_ATTRIBUTE
1021 REPF_ATTRIBUTE_NOT_WRITABLE
1022 REPF_INVALID_REPORT_OBJECT_VALUE
1023 REPF_EVENT_CHANNEL_OBJECTS_ARE_NOT_INDEXED

44
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1024 REPF_UNKNOWN_EVENT_CHANNEL_ATTRIBUTE
1027 REPF_ON_ATTRIBUTE_TOO_LONG
1028 REPF_ON_ATTRIBUTE_NON_TEXT
1029 REPF_CM_ATTRIBUTE_NON_TEXT
1033 REPF_UNKNOWN_DC_ATTRIBUTE
1034 REPF_DC_ATTRIBUTE_NOT_INDEXED
1037 REPF_UNKNOWN_TIME_CHANNEL_ATTRIBUTE
1038 REPF_ATTRIBUTE_NOT_INDEXED
1039 REPF_INDEX_OUT_OF_RANGE
1040 REPF_NON_TEXT_COMMENT
1042 REPF_ATTRIBUTE_MUST_BE_INDEXED
1043 REPF_VECTOR_TOO_SHORT
1044 REPF_SU_ATTRIBUTE_OUT_OF_RANGE
1045 REPF_SU_ATTRIBUTE_NON_INTEGER
1046 REPF_NON_TIME_SY_ATTRIBUTE
1047 REPF_NEGATIVE_CY_ATTRIBUTE
1048 REPF_NON_INTEGER_CY_ATTRIBUTE
1049 REPF_NON_TEXT_CD_ATTRIBUTE
1050 REPF_DC_OBJECT_TABLE_FULL
1051 REPF_TIME_CHANNEL_TABLE_FULL
1052 REPF_EVENT_CHANNEL_TABLE_FULL
1053 REPF_EVENT_CHANNEL_DOES_NOT_EXIST
1054 REPF_TIME_CHANNEL_DOES_NOT_EXIST
1055 REPF_DC_OBJECT_DOES_NOT_EXIST
1059 REPF_INVALID_OT_ATTRIBUTE_VALUE
1060 REPF_INVALID_ON_ATTRIBUTE_VALUE
1061 REPF_INVALID_CM_ATTRIBUTE_VALUE
1062 REPF_BAD_EVENT_CHANNEL_ATTRIBUTE_STATUS
1063 REPF_ON_ATTRIBUTE_MISSING
1064 REPF_OT_ATTRIBUTE_MISSING
1065 REPF_EVENT_CHANNEL_ALREADY_EXISTS
1066 REPF_IU_ATTRIBUTE_OUT_OF_RANGE
1067 REPF_INVALID_IU_ATTRIBUTE_VALUE

45
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1068 REPF_BAD_TIME_CHANNEL_ATTRIBUTE_STATUS
1069 REPF_INVALID_SY_SU_CY_OR_CD_ATTR_VALUE
1070 REPF_INVALID_SY_ATTRIBUTE_VALUE
1071 REPF_INVALID_SU_ATTRIBUTE_VALUE
1072 REPF_INVALID_CY_ATTRIBUTE_VALUE
1073 REPF_INVALID_CD_ATTRIBUTE_VALUE
1074 REPF_TIME_CHANNEL_ALREADY_EXISTS
1075 REPF_TIME_CHANNEL_NOT_EMPTY
1076 REPF_EP_ATTRIBUTE_OUT_OF_RANGE
1077 REPF_INVALID_EP_ATTRIBUTE_VALUE
1078 REPF_HR_ATTRIBUTE_OUT_OF_RANGE
1079 REPF_INVALID_HR_ATTRIBUTE_VALUE
1080 REPF_LF_ATTRIBUTE_OUT_OF_RANGE
1081 REPF_INVALID_LF_ATTRIBUTE_VALUE
1082 REPF_PS_ATTRIBUTE_OUT_OF_RANGE
1083 REPF_INVALID_PS_ATTRIBUTE_VALUE
1084 REPF_INVALID_IN_ATTRIBUTE_VALUE
1085 REPF_BAD_DC_OBJECT_ATTRIBUTE_STATUS
1087 REPF_PS_ATTRIBUTE_MISSING
1088 REPF_COPY_SOURCE_DOES_NOT_EXIST
1089 REPF_SR_ATTRIBUTE_MISSING
1090 REPF_DC_OBJECT_ALREADY_EXISTS
1091 REPF_DATA_STORE_INVALID_INDEX
1092 REPF_DATA_STORE_OV_INVALID
1093 REPF_DATA_STORE_OV_MISSING
1094 REPF_DATA_STORE_RT_INVALID
1095 REPF_DATA_STORE_OS_INVALID
1097 REPF_TS_ATTRIBUTE_OUT_OF_RANGE
1098 REPF_INVALID_TS_ATTRIBUTE_VALUE
1099 REPF_PE_ATTRIBUTE_OUT_OF_RANGE
1100 REPF_INVALID_PE_ATTRIBUTE_VALUE
1101 REPF_PQ_ATTRIBUTE_OUT_OF_RANGE
1102 REPF_INVALID_PQ_ATTRIBUTE_VALUE

46
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1103 REPF_MO_ATTRIBUTE_OUT_OF_RANGE
1104 REPF_INVALID_MO_ATTRIBUTE_VALUE
1105 REPF_HN_ATTRIBUTE_OUT_OF_RANGE
1106 REPF_INVALID_HN_ATTRIBUTE_VALUE
1107 REPF_SE_ATTRIBUTE_OUT_OF_RANGE
1108 REPF_INVALID_SE_ATTRIBUTE_VALUE
1109 REPF_APPLICATION_CLOSE_TIMEOUT
1110 REPF_SX_ATTRIBUTE_OUT_OF_RANGE
1111 REPF_INVALID_SX_ATTRIBUTE_VALUE
1112 REPF_OBJECT_IS_LOCKED
1113 REPF_HISTORY_PAGE_TABLE_FULL
1114 REPF_VERSION_NUMBER_MISMATCH
1115 REPF_RDB_HEADER_INCONSISTENT
1116 REPF_INCONSISTENT_DATA_RECORD
1117 REPF_MEMORY_EXHAUSTED
1118 REPF_EXECUTION_QUEUE_FULL
1119 REPF_OBJECT_NOT_IN_USE
1120 REPF_INVALID_ST_ATTRIBUTE_VALUE
1121 REPF_INVALID_SN_ATTRIBUTE_VALUE
1122 REPF_SN_ATTRIBUTE_MISSING
1123 REPF_ST_ATTRIBUTE_MISSING
1124 REPF_INVALID_TC_ATTRIBUTE_VALUE
1125 REPF_INVALID_CP_ATTRIBUTE_VALUE
1126 REPF_INVALID_FI_ATTRIBUTE_VALUE
FI is not an integer.
1127 REPF_INVALID_FX_ATTRIBUTE_VALUE
FX is non-text.
1128 REPF_INVALID_VT_ATTRIBUTE_VALUE
VT is none of the allowed keyword values.
1129 REPF_INVALID_VL_ATTRIBUTE_VALUE
VL is not an integer.
1130 REPF_VL_ATTRIBUTE_OUT_OF_RANGE
VL is out of range. See description of data object attribute VL for valid
values.

47
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1131 REPF_VT_ATTRIBUTE_MAY_NOT_BE_CHANGED
Attempt to change VT attribute value directly or indirectly via COPY
command.
1133 REPF_INVALID_SP_ATTRIBUTE_VALUE
The SP attribute is of invalid data type or out of range.
1134 REPF_INVALID_DP_ATTRIBUTE_VALUE
The DP attribute is of invalid data type or out of range.
1135 REPF_SP_YES_INVALID_WHEN_MO
The SP attribute of a memory-only time channel may not be "YES".
1136 REPF_BAD_LOGGING_PROFILE_ATTRIBUTE_STATUS
1137 REPF_LOGGING_PROFILE_ALREADY_EXISTS
1138 REPF_LOGGING_PROFILE_DOES_NOT_EXIST
1139 REPF_UNKNOWN_LOGGING_PROFILE_ATTRIBUTE
1140 REPF_LOGGING_PROFILE_TABLE_FULL
1142 REPF_LOGGING_TAG_TABLE_FULL
Too many database objects connected to logging.
1143 REPF_LOGGING_PROFILE_OF_WRONG_PT
1144 REPF_INVALID_LN_ATTRIBUTE_VALUE
1145 REPF_INVALID_DI_ATTRIBUTE_VALUE
1148 REPF_INVALID_CA_ATTRIBUTE_VALUE
1149 REPF_INVALID_DA_ATTRIBUTE_VALUE
1150 REPF_INVALID_US_ATTRIBUTE_VALUE
1151 REPF_INVALID_PW_ATTRIBUTE_VALUE
1152 REPF_INVALID_NP_ATTRIBUTE_VALUE
1153 REPF_INVALID_HC_ATTRIBUTE_VALUE
1154 REPF_0_1_VALUE_EXPECTED
1155 REPF_INVALID_DISCRETENESS
1157 REPF_ATTRIBUTE_CONTAINS_DUPLICATES
1158 REPF_PT_ATTRIBUTE_MISSING
1159 REPF_INVALID_PT_ATTRIBUTE_VALUE
1160 REPF_REFERENCE_COUNT_NON_ZERO
Attempt to delete a logging profile which is still used by another database
object.
1161 REPF_LOGGING_NAME_TOO_LONG
Attempt to create a Historian tag with a name longer than 32 characters.
1163 REPF_PT_ATTRIBUTE_NOT_MODIFIABLE

48
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1164 REPF_DB_TAG_TABLE_FULL
Too many Historian tags are created.
1165 REPF_VT_NOT_VALID_FOR_LOGGING
Only integer and real type data objects may be logged.
1166 REPF_LOGGING_PROFILES_MAY_NOT_BE_RENAMED
1167 REPF_LOGGING_DATABASE_NOT_CONNECTED
1168 REPF_INVALID_ND_ATTRIBUTE_VALUE
1169 REPF_INVALID_DD_ATTRIBUTE_VALUE
1170 REPF_INVALID_ED_ATTRIBUTE_VALUE
1171 REPF_DUPLICATE_DA_ATTRIBUTE_VALUE
Two DATABASE logging profiles must not have the same database
address.
1172 REPF_LOGGING_DATABASE_IS_IN_USE
Attributes DA, US and PW can be modified only when the DATABASE
logging profile object is out of use (IU = 0).
1499 REPF_INITIALIZED
1501 REPR_INSTRUCTION_NOT_FOR_SCIL
1502 REPR_BOOLEAN_EXPRESSION_EXPECTED
1503 REPR_NUMERIC_VALUE_EXPECTED
The command procedure contains a picture command or the characters
# and @ are missing in the beginning of the line.
1504 REPR_RECURSIVE_TIME_CHANNEL_EXECUTION
1505 REPR_INTEGER_VALUE_EXPECTED
This status code is generated by the REPR processes, if the evaluation
of the data expression (IN attribute) results in an invalid data type.
1506 REPR_TIME_VALUE_EXPECTED
This status code is generated by the REPR processes, if the evaluation
of the data expression (IN attribute) results in an invalid data type.
1507 REPR_TEXT_VALUE_EXPECTED
This status code is generated by the REPR processes, if the evaluation
of the data expression (IN attribute) results in an invalid data type.
1508 REPR_TEXT_VALUE_TOO_LONG
This status code is generated by the REPR processes, if the evaluation
of the data expression (IN attribute) results in a text that is longer than
the VL attribute allows.

49
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4.2.4 Process Database (PROF and TOPO) Status Codes

2001 PROF_ATTRIBUTE_DOES_NOT_EXIST
The process object has not got the attribute in question.
2005 PROF_DATATYPE_SYNCHRONIZE_ERROR
The base system and the frontend do not communicate properly. Contact
an ABB representative.
2012 PROF_OBJECT_ON_MANUAL
The GET command is not allowed if the object is on MANUAL.
2013 PROF_OBJECT_SWITCHED_OFF
While the object is switched off, it cannot be updated with GET, and the
object value attributes (OV, BI, BO, AI, AO, etc.) cannot be written with
SET.
2014 PROF_OUTPUT_NOT_WITHIN_LIMITS
You have tried to set the AO attribute value outside the range LO .. HO.
2017 PROF_UNSUPPORTED_DATATYPE_IN_UPDATE
The base system and the frontend do not communicate properly. Contact
an ABB representative.
2018 PROF_UPDATE_CAPABILITY_ERROR
The BI, AI, DI, PC, DB attributes of a genuine (not fictitious) process
object cannot be written with the SET command if the object is in AUTO
state.
2019 PROF_LOGICAL_INDEX_TOO_HIGH
The index of a process object may be at most 65535.
2020 PROF_ILLEGAL_VALUE_TYPE
2021 PROF_ATTRIBUTE_NOT_UPDATABLE
2022 PROF_ATTRIBUTE_NOT_GETTABLE
2023 PROF_ATTRIBUTE_VALUE_OUT_OF_RANGE
2054 PROF_OBJECT_NOT_IN_USE
2055 PROF_UNKNOWN_ATTRIBUTE
2056 PROF_OBJECT_DOES_NOT_EXIST
2057 PROF_INDEX_DOES_NOT_EXIST
2058 PROF_SCALE_OBJECTS_NOT_GETTABLE
2059 PROF_PROCESS_GROUP_TABLE_FULL
2060 PROF_PROCESS_OBJECT_TABLE_FULL
2061 PROF_SCALE_OBJECT_TABLE_FULL
2063 PROF_UNKNOWN_SCALING_ALGORITHM
2064 PROF_NON_INTEGER_SCALING_ALGORITHM

50
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2065 PROF_ILLEGAL_SCALING_CONSTANT
2066 PROF_BAD_SCALING_CONSTANT_STATUS
2067 PROF_TOO_MANY_SCALING_CONSTANTS
2068 PROF_BAD_SCALE_ATTRIBUTE_STATUS
2069 PROF_SCALING_CONSTANTS_MISSING
2070 PROF_SCALING_ALGORITHM_MISSING
2071 PROF_SCALE_ALREADY_EXISTS
2072 PROF_SCALE_DOES_NOT_EXIST
2073 PROF_SCALE_REFERENCE_COUNT_NON_ZERO
2074 PROF_ATTRIBUTE_NOT_INDEXED
2075 PROF_SCALING_CONSTANT_INDEX_TOO_HIGH
2076 PROF_ADDRESS_DOES_NOT_EXIST
2077 PROF_GROUP_REFERENCE_COUNT_NON_ZERO
2078 PROF_INVALID_LN_ATTRIBUTE_VALUE
2079 PROF_IX_ATTRIBUTE_OUT_OF_RANGE
2080 PROF_INVALID_IX_ATTRIBUTE_VALUE
2081 PROF_UN_ATTRIBUTE_OUT_OF_RANGE
2082 PROF_INVALID_UN_ATTRIBUTE_VALUE
2083 PROF_INVALID_OA_ATTRIBUTE_VALUE
2084 PROF_OB_ATTRIBUTE_OUT_OF_RANGE
2085 PROF_INVALID_OB_ATTRIBUTE_VALUE
2086 PROF_OT_ATTRIBUTE_OUT_OF_RANGE
2087 PROF_INVALID_OT_ATTRIBUTE_VALUE
2088 PROF_SS_ATTRIBUTE_OUT_OF_RANGE
2089 PROF_INVALID_SS_ATTRIBUTE_VALUE
2090 PROF_INVALID_IU_ATTRIBUTE_VALUE
2091 PROF_INVALID_ST_ATTRIBUTE_VALUE
2092 PROF_INVALID_SN_ATTRIBUTE_VALUE
2093 PROF_INVALID_AI_ATTRIBUTE_VALUE
2094 PROF_INVALID_HI_ATTRIBUTE_VALUE
2095 PROF_INVALID_LI_ATTRIBUTE_VALUE
2096 PROF_INVALID_AO_ATTRIBUTE_VALUE
2097 PROF_INVALID_HO_ATTRIBUTE_VALUE

51
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2098 PROF_INVALID_LO_ATTRIBUTE_VALUE
2099 PROF_INVALID_BI_ATTRIBUTE_VALUE
2100 PROF_INVALID_BO_ATTRIBUTE_VALUE
2101 PROF_INVALID_AG_ATTRIBUTE_VALUE
2102 PROF_AC_ATTRIBUTE_OUT_OF_RANGE
2103 PROF_INVALID_AC_ATTRIBUTE_VALUE
2104 PROF_INVALID_AE_ATTRIBUTE_VALUE
2105 PROF_INVALID_AN_ATTRIBUTE_VALUE
2107 PROF_INVALID_RC_ATTRIBUTE_VALUE
2108 PROF_INVALID_AB_ATTRIBUTE_VALUE
2109 PROF_LD_ATTRIBUTE_OUT_OF_RANGE
2110 PROF_INVALID_LD_ATTRIBUTE_VALUE
2111 PROF_PD_ATTRIBUTE_OUT_OF_RANGE
2112 PROF_INVALID_PD_ATTRIBUTE_VALUE
2113 PROF_INVALID_PI_ATTRIBUTE_VALUE
2114 PROF_INVALID_CX_ATTRIBUTE_VALUE
2115 PROF_INVALID_OX_ATTRIBUTE_VALUE
2116 PROF_INVALID_DX_ATTRIBUTE_VALUE
2117 PROF_INVALID_LF_ATTRIBUTE_VALUE
2118 PROF_INVALID_PF_ATTRIBUTE_VALUE
2119 PROF_INVALID_EE_ATTRIBUTE_VALUE
2120 PROF_INVALID_HE_ATTRIBUTE_VALUE
2122 PROF_BAD_PROCESS_ATTRIBUTE_STATUS
2123 PROF_GT_ATTRIBUTE_OUT_OF_RANGE
2124 PROF_INVALID_GT_ATTRIBUTE_VALUE
2125 PROF_INVALID_GC_ATTRIBUTE_VALUE
2126 PROF_OBJECT_ALREADY_EXISTS
2127 PROF_NEITHER_PT_NOR_OV_ATTRIBUTE_GIVEN
2129 PROF_PT_ATTRIBUTE_OUT_OF_RANGE
2130 PROF_INVALID_PT_ATTRIBUTE_VALUE
2131 PROF_BIT_ADDRESS_MISSING
2133 PROF_LO_AND_HO_OUT_OF_ORDER
2134 PROF_BIT_ADDRESS_NOT_ALLOWED

52
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2135 PROF_INDEX_ALREADY_EXISTS
2136 PROF_PHYSICAL_ADDRESS_OVERLAP
2137 PROF_AA_ATTRIBUTE_OUT_OF_RANGE
2138 PROF_INVALID_AA_ATTRIBUTE_VALUE
2139 PROF_INVALID_AF_ATTRIBUTE_VALUE
2140 PROF_HA_ATTRIBUTE_OUT_OF_RANGE
2141 PROF_INVALID_HA_ATTRIBUTE_VALUE
2142 PROF_INVALID_HF_ATTRIBUTE_VALUE
2143 PROF_ALARM_LIMITS_OUT_OF_ORDER
2144 PROF_SE_AND_SP_NOT_SUPPORTED_BY_STATION
SE and SP attributes are not supported by the BO process object.
2144 PROF_SE_AND_SP_NOT_SUPPORTED_BY_STATION
2145 PROF_PA_ATTRIBUTE_OUT_OF_RANGE
2146 PROF_INVALID_PA_ATTRIBUTE_VALUE
2147 PROF_DB_ATTRIBUTE_OUT_OF_RANGE
2148 PROF_INVALID_DB_ATTRIBUTE_VALUE
2149 PROF_LA_ATTRIBUTE_OUT_OF_RANGE
2150 PROF_INVALID_LA_ATTRIBUTE_VALUE
2151 PROF_INVALID_DI_ATTRIBUTE_VALUE
2152 PROF_INVALID_DO_ATTRIBUTE_VALUE
2153 PROF_INVALID_LW_ATTRIBUTE_VALUE
2154 PROF_INVALID_HW_ATTRIBUTE_VALUE
2155 PROF_INVALID_SZ_ATTRIBUTE_VALUE
2156 PROF_INVALID_PC_ATTRIBUTE_VALUE
2157 PROF_INVALID_SC_ATTRIBUTE_VALUE
2158 PROF_BC_ATTRIBUTE_OUT_OF_RANGE
2159 PROF_INVALID_BC_ATTRIBUTE_VALUE
2160 PROF_ODD_OB_NOT_ALLOWED
2162 PROF_INVALID_ATTRIBUTE_IN_LIST_SET
2163 PROF_OV_ATTRIBUTE_MISSING_IN_LIST_SET
2165 PROF_OBJECT_ON_AUTO
2166 PROF_INDEX_RANGE_NOT_ALLOWED
2167 PROF_INVALID_RT_ATTRIBUTE_VALUE

53
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2168 PROF_INVALID_RM_ATTRIBUTE_VALUE
2169 PROF_INVALID_PU_ATTRIBUTE_VALUE
2170 PROF_INVALID_NV_ATTRIBUTE_VALUE
2171 PROF_NV_ATTRIBUTE_OUT_OF_RANGE
2172 PROF_INVALID_FI_ATTRIBUTE_VALUE
2173 PROF_INVALID_FX_ATTRIBUTE_VALUE
2174 PROF_VERSION_NUMBER_MISMATCH
2175 PROF_INCONSISTENT_DATA_RECORD
2176 PROF_NO_MORE_FOUND
2177 PROF_OA_ATTRIBUTE_OUT_OF_RANGE
2178 PROF_DI_ATTRIBUTE_OUT_OF_RANGE
2179 PROF_DO_ATTRIBUTE_OUT_OF_RANGE
2181 PROF_INVALID_BS_ATTRIBUTE_VALUE
2182 PROF_INCONSISTENT_SCALE_RECORD
2183 PROF_SCALING_CONSTANTS_OUT_OF_ORDER
2184 PROF_INVALID_SCALING_CONSTANT_COUNT
2185 PROF_INVALID_CE_ATTRIBUTE_VALUE
2186 PROF_INVALID_CL_ATTRIBUTE_VALUE
2187 PROF_OBJECT_IS_NOT_FREE_TYPE
2188 PROF_INTERNAL_ERROR
2189 PROF_F_OBJECT_IS_MISSING
2190 PROF_INDEX_OUT_OF_RANGE
2191 PROF_VECTOR_ATTRIBUTE_LENGTH_ERROR
2192 PROF_BAD_ATTRIBUTE_VALUE_STATUS
2193 PROF_UNSIGNED_1_ATTRIBUTE_OUT_OF_RANGE
2194 PROF_SIGNED_1_ATTRIBUTE_OUT_OF_RANGE
2195 PROF_UNSIGNED_2_ATTRIBUTE_OUT_OF_RANGE
2196 PROF_SIGNED_2_ATTRIBUTE_OUT_OF_RANGE
2197 PROF_INTEGER_ATTRIBUTE_TYPE_MISMATCH
2198 PROF_REAL_ATTRIBUTE_TYPE_MISMATCH
2199 PROF_BOOLEAN_ATTRIBUTE_TYPE_MISMATCH
2200 PROF_TIME_ATTRIBUTE_TYPE_MISMATCH
2201 PROF_TEXT_ATTRIBUTE_TYPE_MISMATCH

54
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2202 PROF_BIT_STRING_ATTRIBUTE_TYPE_MISMATCH
2203 PROF_BIT_STRING_ATTRIBUTE_LENGTH_ERROR
2204 PROF_FREE_TYPE_OBJECTS_NOT_GETTABLE
2205 PROF_FREE_TYPE_DOES_NOT_EXIST
2206 PROF_ZERO_LENGTH_VECTOR_VALUE
2207 PROF_INVALID_AX_ATTRIBUTE_VALUE
2208 PROF_INVALID_AP_ATTRIBUTE_VALUE
2209 PROF_INVALID_AH_ATTRIBUTE_VALUE
2210 PROF_INVALID_AD_ATTRIBUTE_VALUE
2211 PROF_INVALID_AS_ATTRIBUTE_VALUE
2212 PROF_FREE_ATTRIBUTE_NAME_ALREADY_IN_USE
2213 PROF_FREE_TYPE_REFERENCE_COUNT_NON_ZERO
2214 PROF_DUPLICATE_FREE_TYPE_OBJECT_NAME
2215 PROF_DUPLICATE_PT_ATTRIBUTE_VALUE
2216 PROF_A_ATTRIBUTES_MUST_HAVE_SAME_SIZE
2217 PROF_TOO_MANY_FREE_ATTRIBUTES
2218 PROF_A_ATTRIBUTES_MUST_BE_VECTOR_TYPE
2219 PROF_PT_ATTRIBUTE_MISSING
2220 PROF_AN_ATTRIBUTE_MISSING
2221 PROF_AT_ATTRIBUTE_MISSING
2222 PROF_AL_ATTRIBUTE_MISSING
2223 PROF_FREE_TYPE_ALREADY_EXISTS
2224 PROF_INVALID_OV_ATTRIBUTE_VALUE
2225 PROF_AI_ATTRIBUTE_OUT_OF_RANGE
2226 PROF_INVALID_AT_ATTRIBUTE_VALUE
2227 PROF_INVALID_AL_ATTRIBUTE_VALUE
2228 PROF_AL_ATTRIBUTE_OUT_OF_RANGE
2229 PROF_FREE_ATTRIBUTE_SPACE_EXHAUSTED
2230 PROF_AI_ATTRIBUTE_MAY_NOT_BE_MODIFIED
2231 PROF_AT_ATTRIBUTE_MAY_NOT_BE_MODIFIED
2232 PROF_AL_ATTRIBUTE_MAY_NOT_BE_MODIFIED
2233 PROF_LN_ATTRIBUTE_MAY_NOT_BE_MODIFIED
2234 PROF_PT_ATTRIBUTE_MAY_NOT_BE_MODIFIED

55
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2235 PROF_OV_ATTRIBUTE_MAY_NOT_BE_INDEXED
2236 PROF_WRITING_TOO_MANY_BYTES
2237 PROF_TEXT_ATTRIBUTE_LENGTH_ERROR
2238 PROF_NO_OV_ATTRIBUTE_IN_FREE_TYPE
2239 PROF_AD_ATTRIBUTE_OUT_OF_RANGE
2240 PROF_INVALID_OS_ATTRIBUTE_VALUE
2242 PROF_MEMORY_EXHAUSTED
2243 PROF_HISTORY_OBJECT_TABLE_FULL
2244 PROF_INVALID_HL_ATTRIBUTE_VALUE
2245 PROF_HL_ATTRIBUTE_OUT_OF_RANGE
2246 PROF_OBJECT_IS_FREE_TYPE
2247 PROF_INVALID_OI_ATTRIBUTE_VALUE
2248 PROF_INVALID_RI_ATTRIBUTE_VALUE
2249 PROF_INVALID_RX_ATTRIBUTE_VALUE
2250 PROF_INVALID_PH_ATTRIBUTE_VALUE
2251 PROF_INVALID_HH_ATTRIBUTE_VALUE
2252 PROF_INVALID_AZ_ATTRIBUTE_VALUE
2253 PROF_INVALID_OF_ATTRIBUTE_VALUE
2254 PROF_INVALID_BL_ATTRIBUTE_VALUE
2255 PROF_INVALID_SB_ATTRIBUTE_VALUE
2256 PROF_INVALID_OR_ATTRIBUTE_VALUE
2257 PROF_INVALID_RA_ATTRIBUTE_VALUE
2258 PROF_INVALID_RB_ATTRIBUTE_VALUE
2259 PROF_INVALID_CT_ATTRIBUTE_VALUE
2260 PROF_INVALID_ZD_ATTRIBUTE_VALUE
2261 PROF_INVALID_ZE_ATTRIBUTE_VALUE
2262 PROF_INVALID_EP_ATTRIBUTE_VALUE
2263 PROF_OBJECT_UPDATE_BLOCKED
2264 PROF_CT_HISTORY_NOT_IMPLEMENTED_FOR_FREE_ OBJECTS
2265 PROF_INVALID_PB_ATTRIBUTE_VALUE
2266 PROF_INVALID_XB_ATTRIBUTE_VALUE
2267 PROF_INVALID_HB_ATTRIBUTE_VALUE
2268 PROF_INVALID_UB_ATTRIBUTE_VALUE

56
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2269 PROF_INVALID_OG_ATTRIBUTE_VALUE
2270 PROF_OG_ATTRIBUTE_OUT_OF_RANGE
2271 PROF_INVALID_QL_ATTRIBUTE_VALUE
2272 PROF_QL_ATTRIBUTE_OUT_OF_RANGE
2273 PROF_INVALID_TY_ATTRIBUTE_VALUE
2274 PROF_TY_ATTRIBUTE_OUT_OF_RANGE
2275 PROF_INVALID_TH_ATTRIBUTE_VALUE
2276 PROF_CT_ATTRIBUTE_OUT_OF_RANGE
2277 PROF_INVALID_SE_ATTRIBUTE_VALUE
2278 PROF_INVALID_HT_ATTRIBUTE_VALUE
2279 PROF_INVALID_HM_ATTRIBUTE_VALUE
2280 PROF_HM_ATTRIBUTE_OUT_OF_RANGE
2281 PROF_INVALID_HD_ATTRIBUTE_VALUE
2282 PROF_HD_ATTRIBUTE_OUT_OF_RANGE
2283 PROF_INVALID_ET_ATTRIBUTE_VALUE
2284 PROF_INVALID_EM_ATTRIBUTE_VALUE
2285 PROF_EM_ATTRIBUTE_OUT_OF_RANGE
2286 PROF_INVALID_ED_ATTRIBUTE_VALUE
2287 PROF_ED_ATTRIBUTE_OUT_OF_RANGE
2288 PROF_INVALID_CA_ATTRIBUTE_VALUE
2289 PROF_INVALID_EX_ATTRIBUTE_VALUE
2290 PROF_OS_ATTRIBUTE_OUT_OF_RANGE
2291 PROF_RM_ATTRIBUTE_OUT_OF_RANGE
2292 PROF_INVALID_AM_ATTRIBUTE_VALUE
2293 PROF_AM_ATTRIBUTE_OUT_OF_RANGE
2294 PROF_INVALID_YT_ATTRIBUTE_VALUE
2295 PROF_INVALID_YM_ATTRIBUTE_VALUE
2296 PROF_YM_ATTRIBUTE_OUT_OF_RANGE
2297 PROF_INVALID_AR_ATTRIBUTE_VALUE
2298 PROF_INVALID_CO_ATTRIBUTE_VALUE
2299 PROF_INVALID_SP_ATTRIBUTE_VALUE
2300 PROF_INVALID_MV_ATTRIBUTE_VALUE
2301 PROF_INVALID_XV_ATTRIBUTE_VALUE

57
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2302 PROF_INVALID_MT_ATTRIBUTE_VALUE
2303 PROF_INVALID_MM_ATTRIBUTE_VALUE
2304 PROF_MM_ATTRIBUTE_OUT_OF_RANGE
2305 PROF_INVALID_XT_ATTRIBUTE_VALUE
2306 PROF_INVALID_XM_ATTRIBUTE_VALUE
2307 PROF_XM_ATTRIBUTE_OUT_OF_RANGE
2308 PROF_AZ_ATTRIBUTE_OUT_OF_RANGE
2309 PROF_INVALID_TI_ATTRIBUTE_VALUE
2310 PROF_INVALID_IR_ATTRIBUTE
IR value should be integer 0 or 1 (or boolean FALSE or TRUE).
2311 PROF_IR_ATTRIBUTE_MAY_NOT_BE_MODIFIED
IR attribute may not be changed by SET or MODIFY.
2312 PROF_SCALE_NOT_ALLOWED_WHEN_IR_IS_1
Integer value AI objects are not scaled.
2313 PROF_INVALID_SU_ATTRIBUTE_VALUE
SU should be set to integer value 0 or 1 (or boolean value FALSE or
TRUE).
2314 PROF_OBJECT_ADDRESS_NOT_ALLOWED
OA attribute must be 0 for FT process objects.
2315 PROF_INVALID_FN_ATTRIBUTE_VALUE
FN attribute should have a file tag value.
2316 PROF_INVALID_ID_ATTRIBUTE_VALUE
ID attribute should have a byte string value.
2317 PROF_OBJECT_NOT_ON_AUTO
File transfer possible only if SS == AUTO.
2319 PROF_FILE_TRANSFER_IN_PROGRESS
Trying to set FF, ID or FN attribute while file transfer is in progress.
2320 PROF_FILE_TRANSFER_TIMEOUT
NET has not sent anything for a minute.
2321 PROF_FILE_TRANSFER_CANCELED
NET has sent a message belonging to a file transfer that has been can-
celed.
2322 PROF_INVALID_FILE_TRANSFER_ID
NET has sent a message belonging to an inactive file transfer.
2323 PROF_INVALID_FILE_TRANSFER_DATA
NET has sent a file transfer message that SYS cannot interpret.

58
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2324 PROF_MESSAGE_SEQUENCE_NUMBER_OUT_OF_ORDER
A file transfer message NET ->
SYS has been lost.
2325 PROF_SU_ATTRIBUTE_NOT_SUPPORTED
The SU attribute is not implemented for free type process objects.
2326 PROF_INVALID_TT_ATTRIBUTE_VALUE
2327 PROF_TT_ATTRIBUTE_OUT_OF_RANGE
2328 PROF_MIRROR_CONFIGURATION_MISMATCH
The mirroring configurations in the image application and in the host
application do not match.
2329 PROF_MIRRORING_HOST_DISCONNECTED
The host application is disconnected.
2330 PROF_INVALID_PO_ATTRIBUTE_VALUE
The PO attribute is of invalid data type or out of range.
2332 PROF_IMAGE_DISABLED
Mirroring to the image application has been disabled.
2333 PROF_HOST_DISABLED
Mirroring from the host application has been disabled.
2334 PROF_INVALID_GI_ATTRIBUTE_VALUE
The GI attribute is of invalid data type or out of range.
2335 PROF_INVALID_RQ_ATTRIBUTE_VALUE
The RQ attribute is of invalid data type or out of range.
2336 PROF_INVALID_ON_ATTRIBUTE_VALUE
The ON attribute is of invalid data type.
2337 PROF_EH_ATTRIBUTE_NOT_IMPLEMENTED
EH attribute is not implemented for process objects of user-defined types.
2338 PROF_INVALID_EH_ATTRIBUTE_VALUE
The EH attribute does not denote an object name.
2339 PROF_EVENT_HANDLING_DOES_NOT_EXIST
The event handling (H) object does not exist.
2340 PROF_EVENT_HANDLING_ALREADY_EXISTS
Attempt to create an H object that already exists.
2341 PROF_EVENT_HANDLING_OBJECT_TABLE_FULL
The maximum number of H objects (~ 65 000) exceeded.
2342 PROF_EVENT_HANDLING_OBJECTS_NOT_GETTABLE
You cannot apply #GET command to H objects
2343 PROF_EVENT_HANDLING_REFERENCE_COUNT_NON_ZERO
Attempt to delete an H object that is referenced by process objects.

59
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2345 PROF_INVALID_VC_ATTRIBUTE_VALUE
The VC attribute is of invalid data type.
2346 PROF_VC_ATTRIBUTE_OUT_OF_RANGE
The VC attribute value is not in the range 0 ... 255.
2347 PROF_INVALID_VL_ATTRIBUTE_VALUE
The VL attribute is of invalid data type.
2348 PROF_ST_ATTRIBUTE_LENGTH_MISMATCH
The length of the ST attribute does not match with the value of the VC
attribute.
2349 PROF_MT_ATTRIBUTE_LENGTH_MISMATCH
The length of the MT attribute does not match with the value of the VC
attribute.
2350 PROF_PREDEFINED_H_OBJECTS_ARE_READ_ONLY
Attempt to modify or delete a predefined event handling object.
2351 PROF_INVALID_VF_ATTRIBUTE_VALUE
The VF attribute is of invalid data type.
2352 PROF_INVALID_VF_ATTRIBUTE_SYNTAX
The syntax of the VF attribute is incorrect.
2353 PROF_VC_ATTRIBUTE_NOT_ASCENDING
The elements of the VC attribute vector are not given in ascending order.
2354 PROF_INVALID_IN_ATTRIBUTE_VALUE
The IN attribute is of invalid data type.
2355 PROF_DUPLICATE_IN_ATTRIBUTE_VALUE
There already exists an object with the same IN attribute value in the
same unit.
2356 PROF_IN_ATTRIBUTE_TOO_LONG
The length of the IN attribute exceeds 255 characters.
2357 PROF_INVALID_IG_ATTRIBUTE_VALUE
The IG attribute is of invalid data type.
2358 PROF_IG_ATTRIBUTE_TOO_LONG
The length of the IG attribute exceeds 255 characters.
2359 PROF_LIST_SET_NOT_SUPPORTED
Type '#SET obj:POV = LIST(OV=...)' command not supported for this
process object type.
2360 PROF_OBJECT_IS_ADDRESSED_BY_IN_ATTRIBUTE
Attempt to address an IN-addressed process signal by using an OA ad-
dress.
2361 PROF_OBJECT_IS_ADDRESSED_BY_OA_ATTRIBUTE
Attempt to address an OA-addressed process signal by using an IN ad-
dress.

60
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2362 PROF_IN_ATTRIBUTE_MISSING
Attempt to create a process object without an IN attribute, when the
process object type requires one.
2363 PROF_INVALID_OE_ATTRIBUTE_VALUE
2364 PROF_OE_ATTRIBUTE_OUT_OF_RANGE
2365 PROF_EVENT_HANDLING_OBJECT_OF_WRONG_TYPE
Attempt to connect an OE (OPC Event) type process object to a conven-
tional (SYS) event handling object or a non-OE process object to an
OPC A&E (AEC) event handling object.
2366 PROF_INVALID_ND_ATTRIBUTE_VALUE
2367 PROF_ND_ATTRIBUTE_OUT_OF_RANGE
2368 PROF_INVALID_CI_ATTRIBUTE_VALUE
2369 PROF_INVALID_CD_ATTRIBUTE_VALUE
2370 PROF_AEC_EVENT_ALREADY_DEFINED
An event handling object for this ND/CI/ET/CN combination already
exists.
2371 PROF_CONDITION_NAME_NOT_ALLOWED
Condition name allowed only for condition event handling objects (ET
= "CONDITION").
2372 PROF_CONDITION_NAME_MISSING
Condition name is mandatory for condition event handling objects (ET
= "CONDITION").
2373 PROF_SUBCONDITION_NAMES_NOT_ALLOWED
Subcondition names are allowed only for multi-state conditions.
2374 PROF_ATTRIBUTE_MAY_NOT_BE_MODIFIED
Attributes ND, CI, ET and CN of an AEC event handling object may
not be modified after the object has been created.
2375 PROF_INVALID_CN_ATTRIBUTE_VALUE
2376 PROF_DUPLICATE_AE_EVENT_ADDRESS
A process object connected to this OPC A&E event already exists.
2377 PROF_TOO_MANY_CONDITIONS_FOR_THE_SOURCE
2378 PROF_OE_OBJECTS_ALLOWED_ONLY_IN_OAE_STATIONS
Attempt to create an OE process object in a unit that is not an OAE sta-
tion.
2379 PROF_MORE_THAN_ONE_UNIT_IN_AN_OPC_AE_NODE
Only one unit of an application may be connected to any OPC_AE node.
2380 PROF_EVENT_HANDLING_OBJECT_OF_WRONG_NODE
The EH attribute refers to an event handling object of a node other than
the node of the station.

61
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2381 PROF_ATTRIBUTE_NOT_SETTABLE_IN_OE_OBJECTS
Attributes IN and EH of an OE process object may not be changed by
a #SET command (#MODIFY must be used instead).
2382 PROF_ONLY_OE_OBJECTS_ALLOWED_IN_OAE_STATIONS
Attempt to create a non-OE process object in a unit that is an OAE sta-
tion.
2383 PROF_NOT_A_CONDITION_EVENT
Attempt to acknowledge an OPC A&E event that is not a condition
event.
2384 PROF_NOT_AN_OPC_EVENT_OBJECT
Attempt to acknowledge an OPC A&E event of a non-OE process object.
2385 PROF_CD_ATTRIBUTE_TOO_BIG Attempt to create a CD attribute
that takes space more than 64 kB.
2386 PROF_OS_ATTRIBUTE_MISSING_IN_OE_LIST_SET
Only the substituted OS attribute of an OE process object may be set in
list format, e.g. #SET OE_OBJECT:P = LIST(SU = 1, OS = 2)
2387 PROF_ONLY_OS_2_ALLOWED_IN_OE_LIST_SET
The list format may only be used to set the object status (OS) to 2, no
other value is accepted.
2388 PROF_INVALID_ES_ATTRIBUTE_VALUE
2389 PROF_DUPLICATE_ES_EH_ATTRIBUTE_VALUE
Attempt to define two process objects with the same ES/EH attribute
values.
2390 PROF_INVALID_OS_ET_ATTRIBUTE_VALUE
2391 PROF_INVALID_OS_CI_ATTRIBUTE_VALUE
2392 PROF_INVALID_OS_CD_ATTRIBUTE_VALUE
2393 PROF_INVALID_OS_SE_ATTRIBUTE_VALUE
2394 PROF_INVALID_OC_ATTRIBUTE_VALUE
2395 PROF_INVALID_OC_CI_ATTRIBUTE_VALUE
2396 PROF_INVALID_OC_CD_ATTRIBUTE_VALUE
2397 PROF_INVALID_OC_CN_ATTRIBUTE_VALUE
2398 PROF_INVALID_OC_DS_ATTRIBUTE_VALUE
2399 PROF_INVALID_OC_SI_ATTRIBUTE_VALUE
2400 PROF_INVALID_OC_SU_ATTRIBUTE_VALUE
2401 PROF_INVALID_OC_SI_CD_ATTRIBUTE_VALUE
2402 PROF_INVALID_OC_SI_SE_ATTRIBUTE_VALUE
2403 PROF_INVALID_OC_SU_SD_ATTRIBUTE_VALUE

62
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2404 PROF_INVALID_OC_SU_SE_ATTRIBUTE_VALUE
2405 PROF_INVALID_OC_SU_SN_ATTRIBUTE_VALUE
2406 PROF_OS_ATTRIBUTE_UNDEFINED
2407 PROF_OC_ATTRIBUTE_UNDEFINED
2408 PROF_OS_CI_ATTRIBUTE_UNDEFINED
2409 PROF_OS_ET_ATTRIBUTE_UNDEFINED
2410 PROF_OS_SE_ATTRIBUTE_UNDEFINED
2411 PROF_OC_CN_ATTRIBUTE_UNDEFINED
2412 PROF_OC_CI_ATTRIBUTE_UNDEFINED
2413 PROF_OC_SI_ATTRIBUTE_UNDEFINED
2414 PROF_OC_SI_SE_ATTRIBUTE_UNDEFINED
2415 PROF_OC_SU_SN_ATTRIBUTE_UNDEFINED
2416 PROF_OC_SU_SE_ATTRIBUTE_UNDEFINED
2417 PROF_DUPLICATE_SUBCONDITION_NAME
2418 PROF_CATEGORY_EVENT_TYPE_MISMATCH
2419 PROF_CATEGORY_DESCRIPTION_MISMATCH
2420 PROF_OS_SE_ATTRIBUTE_OF_WRONG_LENGTH
2421 PROF_ST_ATTRIBUTE_TOO_SHORT
2422 PROF_DUPLICATE_CONDITION_NAME
2423 PROF_OPC_AE_SERVER_START_TIMEOUT
Process oaes.exe did not start properly.
2424 PROF_INVALID_DP_ATTRIBUTE_VALUE
2425 PROF_DP_ATTRIBUTE_OUT_OF_RANGE
2426 PROF_INVALID_PV_ATTRIBUTE_VALUE
2427 PROF_INVALID_RZ_ATTRIBUTE_VALUE
2428 PROF_RZ_ATTRIBUTE_OUT_OF_RANGE
2429 PROF_UN_REFERS_TO_PRIMARY_OR_SECONDARY_STA
2430 PROF_TOPOLOGY_MODEL_ALREADY_EXISTS
2431 PROF_TOPOLOGY_MODEL_ALREADY_RUNNING
2433 PROF_TOPOLOGY_MODEL_DOES_NOT_EXIST
2434 PROF_TOPOLOGY_MODEL_IS_RUNNING
2435 PROF_TOPOLOGY_MODEL_NOT_STARTED
2437 PROF_NT_OBJECTS_NOT_CONFIGURABLE_BY_SCIL

63
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2438 PROF_OBJECT_REFERENCED_BY_TOPOLOGY_MODEL
2439 PROF_ATTRIBUTE_NOT_SETTABLE_IN_NT_OBJECTS
2440 PROF_TOPOLOGY_SCHEMA_DOES_NOT_EXIST
2441 PROF_INVALID_NM_ATTRIBUTE_VALUE
2442 PROF_TOPOLOGY_CALCULATION_TOO_LENGTHY
2445 PROF_LOGGING_PROFILE_DOES_NOT_EXIST
2449 PROF_PT_NOT_VALID_FOR_LOGGING
2450 PROF_INVALID_TM_ATTRIBUTE_VALUE
2451 PROF_RECURSIVE_SDDL_EVALUATION
The state or event text SDDL expression contains a reference to itself.
For example, the state text (SX) contains a reference to attribute SX.
2801 TOPO_MODEL_CONTAINS_ERRORS
2802 TOPO_MODEL_CONTAINS_EXTRA_FIELDS
2803 TOPO_MODEL_MALFORMED_COMMENT
2804 TOPO_MODEL_MALFORMED_GENERATION_DATE
2805 TOPO_MODEL_MALFORMED_GENERATOR_ID
2806 TOPO_MODEL_MALFORMED_NAME
2807 TOPO_MODEL_MISSING_NAME
2808 TOPO_MODEL_MISSING_SCHEMA
2809 TOPO_MODEL_MISSING_VERSION
2810 TOPO_MODEL_MISSING_GENERATION_DATE
2811 TOPO_MODEL_MISSING_GENERATOR_ID
2812 TOPO_MODEL_MISSING_OBJECTS
2813 TOPO_MODEL_OBJECTS_NOT_VECTOR_OR_EMPTY
2814 TOPO_MODEL_UNSUPPORTED_SCHEMA
2815 TOPO_MODEL_UNSUPPORTED_VERSION
2816 TOPO_OBJECT_CN_REFERENCES_MISSING_OBJECT
2817 TOPO_OBJECT_CN_CROSS_REFERENCE_NOT_FOUND
2818 TOPO_OBJECT_CONTAINS_EXTRA_FIELDS
2819 TOPO_OBJECT_IS_NOT_LIST
2820 TOPO_OBJECT_MALFORMED_CN
2821 TOPO_OBJECT_MALFORMED_CN_ITEM
2822 TOPO_OBJECT_MALFORMED_OBJECT_REF
2823 TOPO_OBJECT_MALFORMED_IX

64
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2824 TOPO_OBJECT_MALFORMED_LN
2825 TOPO_OBJECT_MALFORMED_NS
2826 TOPO_OBJECT_MALFORMED_OI
2827 TOPO_OBJECT_MALFORMED_GENERATED_BY
2828 TOPO_OBJECT_MISSING_CN
2829 TOPO_OBJECT_MISSING_IX
2830 TOPO_OBJECT_MISSING_LN
2831 TOPO_OBJECT_MISSING_NS
2832 TOPO_OBJECT_NO_NOT_ALLOWED_FOR_NS
2833 TOPO_OBJECT_NO_REQUIRED_FOR_NS
2834 TOPO_TRIGGER_PO_NOT_FOUND
2835 TOPO_TRIGGER_PO_IN_ANOTHER_MODEL
2837 TOPO_TRIGGER_PO_NOT_DB_OR_BI
2838 TOPO_WARN_PROCESS_OBJECT_REF_CHANGED
2839 TOPO_DUPLICATE_REFERENCE
2840 TOPO_PO_NOT_AI
2841 TOPO_OBJECT_LV_NOT_ALLOWED_FOR_NS
2842 TOPO_MODEL_MALFORMED_BUILT_FROM
2843 TOPO_LEVELS_OUT_OF_ORDER
2844 TOPO_INVALID_LEVEL_DEFINITION
2845 TOPO_OBJECT_CH_NOT_ALLOWED_FOR_NS
2846 TOPO_OBJECT_CH_REFERENCES_MISSING_OBJ
2847 TOPO_NT_IN_ANOTHER_MODEL
2848 TOPO_NT_EXISTS
2849 TOPO_TRIGGER_PO_NOT_AI_OR_BI
2850 TOPO_DUPLICATE_OBJECT

4.2.5 NET Interface (NETI) Status Codes

3001 NETI_NO_SCS_DRIVER_FOR_DEVICE
3002 NETI_SPURIOUS_REPLY_TO_SCS
The base system and the frontend do not communicate properly, contact
an ABB representative.
3014 NETI_UNKNOWN_NS_INDEX

65
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4.2.6 Picture Database (PICF) Status Codes

4001 PICF_INVALID_NAME
An invalid name has been given to a picture, representation or window.
4002 PICF_NOT_FOUND
The named picture, representation or window does not exist.
4003 PICF_ALREADY_EXISTS
The name given to a picture, representation or window is already in use.
4004 PICF_END_OF_LIST
4005 PICF_SHARE_ERROR
You are trying to edit, delete or rename a picture or representation which
is in use (normally in another monitor).
4006 PICF_USE_ERROR
Internal error situation in the base system program. Contact an ABB
representative.
4007 PICF_NO_PIC_FILE
The file is probably corrupted.
4009 PICF_DUPLICATE_PICTURE_FUNCTION_NAME
4010 PICF_TOO_MANY_PICTURE_FUNCTIONS
4014 PICF_DUPLICATE_WINDOW_NAME
4015 PICF_FUNCTION_KEY_OVERLAP
4016 PICF_TOO_MANY_REPRESENTATION_LIBRARIES
4018 PICF_MEMORY_EXHAUSTED
4019 PICF_ZERO_WIDTH_FIELD
4021 PICF_DUPLICATE_NAMED_PROGRAM_NAME
4022 PICF_FIELD_SPECIFICATION_TOO_LONG
4023 PICF_BACKGROUND_IN_ANCIENT_FORMAT
4024 PICF_PICTURE_IS_NOT_LOCKED
Attempt to unlock a picture that is not locked.

4.2.7 Picture Graphics (PICO) Status Codes

4208 PICO_NOT_A_SETTABLE_ATTRIBUTE
4209 PICO_INVALID_PARAMETER
4211 PICO_ELEMENT_TYPE_MISSING
4212 PICO_INVALID_ELEMENT_TYPE
4213 PICO_X_ATTRIBUTE_MISSING

66
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

4214 PICO_INVALID_X_ATTRIBUTE
4215 PICO_Y_ATTRIBUTE_MISSING
4216 PICO_INVALID_Y_ATTRIBUTE
4217 PICO_X1_ATTRIBUTE_MISSING
4218 PICO_INVALID_X1_ATTRIBUTE
4219 PICO_Y1_ATTRIBUTE_MISSING
4220 PICO_INVALID_Y1_ATTRIBUTE
4221 PICO_X2_ATTRIBUTE_MISSING
4222 PICO_INVALID_X2_ATTRIBUTE
4223 PICO_Y2_ATTRIBUTE_MISSING
4224 PICO_INVALID_Y2_ATTRIBUTE
4225 PICO_WIDTH_ATTRIBUTE_MISSING
4226 PICO_INVALID_WIDTH_ATTRIBUTE
4227 PICO_HEIGHT_ATTRIBUTE_MISSING
4228 PICO_INVALID_HEIGHT_ATTRIBUTE
4229 PICO_RADIUS1_ATTRIBUTE_MISSING
4230 PICO_INVALID_RADIUS1_ATTRIBUTE
4231 PICO_RADIUS2_ATTRIBUTE_MISSING
4232 PICO_INVALID_RADIUS2_ATTRIBUTE
4233 PICO_RADIUS_ATTRIBUTE_MISSING
4234 PICO_INVALID_RADIUS_ATTRIBUTE
4235 PICO_ANGLE1_ATTRIBUTE_MISSING
4236 PICO_INVALID_ANGLE1_ATTRIBUTE
4237 PICO_ANGLE2_ATTRIBUTE_MISSING
4238 PICO_INVALID_ANGLE2_ATTRIBUTE
4239 PICO_INVALID_FILL_ATTRIBUTE
4240 PICO_INVALID_RELATIVE_ATTRIBUTE
4241 PICO_ELEMENT_NOT_FOUND
4242 PICO_INVALID_GC_NR_ATTRIBUTE
4243 PICO_INVALID_SCOPE_ATTRIBUTE
4244 PICO_INVALID_FUNCTION_ATTRIBUTE
4245 PICO_INVALID_FOREGROUND_ATTRIBUTE
4246 PICO_INVALID_BACKGROUND_ATTRIBUTE

67
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4247 PICO_INVALID_LINE_WIDTH_ATTRIBUTE
4248 PICO_INVALID_LINE_STYLE_ATTRIBUTE
4249 PICO_INVALID_CAP_STYLE_ATTRIBUTE
4250 PICO_INVALID_JOIN_STYLE_ATTRIBUTE
4251 PICO_INVALID_ARC_MODE_ATTRIBUTE
4252 PICO_INVALID_FONT_ATTRIBUTE
4253 PICO_INVALID_DASH_LIST_ATTRIBUTE
4254 PICO_INVALID_DASH_OFFSET_ATTRIBUTE
4255 PICO_INVALID_NAME_ATTRIBUTE
4256 PICO_TEXT_ATTRIBUTE_MISSING
4257 PICO_INVALID_TEXT_ATTRIBUTE
4259 PICO_INVALID_ALIGN_ATTRIBUTE
4261 PICO_FILENAME_ATTRIBUTE_MISSING
4262 PICO_INVALID_FILENAME_ATTRIBUTE
4263 PICO_IMAGES_ATTRIBUTE_MISSING
4264 PICO_INVALID_IMAGE_ATTRIBUTE

4.2.8 File Handling (FILE) Status Codes

5001 FILE_ILLEGAL_FILE_NAME
5002 FILE_END_OF_FILE
5003 FILE_I_O_ERROR
5004 FILE_NO_SPACE_ON_VOLUME
5005 FILE_SHARING_CONFLICT
5007 FILE_DOES_NOT_EXIST
5008 FILE_ALREADY_EXISTS
5009 FILE_IN_USE
5010 FILE_PATH_DOES_NOT_EXIST
5012 FILE_RECORD_NOT_FOUND
5013 FILE_RECORD_ALREADY_EXISTS
5014 FILE_NO_FREE_BLOCKS
5015 FILE_INCONSISTENT
5016 FILE_INVALID_KEY_SIZE

68
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

5017 FILE_DIRECTORY_NOT_EMPTY
5018 FILE_DEVICE_NOT_INITIALIZED
5019 FILE_DEVICE_ALREADY_INITIALIZED
5020 FILE_DEVICE_OR_DIRECTORY_DOES_NOT_EXIST
5022 FILE_TOO_MANY_DIRECTORIES_OPEN
5023 FILE_MEMORY_EXHAUSTED
5024 FILE_TIMEOUT
5025 FILE_NOT_IMPLEMENTED
5026 FILE_DIRECTORY_DOES_NOT_EXIST
5027 FILE_CREATE_DIRECTORY_FAILED
5028 FILE_NAME_RESERVED_TO_OPERATING_SYSTEM
5029 FILE_PIPES_NOT_SUPPORTED
5030 FILE_DRIVE_DOES_NOT_EXIST
5031 FILE_ACCESS_DENIED
5032 FILE_NETWORK_ACCESS_FAILED
5033 FILE_NOT_SAME_DEVICE
5034 FILE_WRITE_PROTECTED
5035 FILE_RECORD_TOO_LONG
5036 FILE_DIRECTORY_IN_USE
5037 FILE_DRIVE_NOT_READY
5038 FILE_INVALID_FILE_VERSION
File version number of a file is invalid, the file is corrupted.

4.2.9 OPC Data Access Server (OPCS) Status Codes

5501 OPCS_ITEM_NAME_TOO_LONG
OPC item name is too long (> 255 characters).
5502 OPCS_INVALID_CHARACTER_IN_ITEM_NAME
OPC item name contains an invalid character.
5503 OPCS_INVALID_USE_OF_DELIMITERS_IN_ITEM_NAME
For example, two consecutive dots.
5504 OPCS_INVALID_USE_OF_SPACES_IN_ITEM_NAME
For example, leading or trailing spaces.
5505 OPCS_ITEM_NAME_ALREADY_EXISTS
Attempt to give the same value to the ON attribute of two objects.

69
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

5507 OPCS_SERVER_START_TIMEOUT
The OPC server did not start in a reasonable time.
5508 OPCS_SERVER_ALREADY_RUNNING
Attempt to start a second OPC server.
5509 OPCS_ITEM_NOT_READABLE
5510 OPCS_ITEM_NOT_WRITEABLE
5513 OPCS_REPLAY_OVERFLOW

4.2.10 Printer Spooler (PRIN) Status Codes

6101 PRIN_APPLICATION_CLOSE_TIMEOUT

4.2.11 System (SYST) Status Codes

7001 SYST_NO_SUCH_TASK
7002 SYST_STATION_ROUTING_TABLE_ERROR
7003 SYST_APPLICATION_ROUTING_TABLE_ERROR
7004 SYST_PRINTER_ROUTING_TABLE_ERROR
7005 SYST_UNKNOWN_BASE_SYSTEM_OBJECT
7006 SYST_UNKNOWN_BASE_SYSTEM_ATTRIBUTE
7009 SYST_BAD_BASE_SYSTEM_ATTRIBUTE_STATUS
7010 SYST_INVALID_ND_ATTRIBUTE_VALUE
7011 SYST_ND_ATTRIBUTE_OUT_OF_RANGE
7012 SYST_INVALID_SA_ATTRIBUTE_VALUE
7013 SYST_SA_ATTRIBUTE_OUT_OF_RANGE
7014 SYST_INVALID_SN_ATTRIBUTE_VALUE
7015 SYST_INVALID_TT_ATTRIBUTE_VALUE
7017 SYST_INVALID_TN_ATTRIBUTE_VALUE
7018 SYST_TN_ATTRIBUTE_OUT_OF_RANGE
7019 SYST_INVALID_NA_ATTRIBUTE_VALUE
7020 SYST_INVALID_ST_ATTRIBUTE_VALUE
7021 SYST_INVALID_AP_ATTRIBUTE_VALUE
7022 SYST_AP_ATTRIBUTE_OUT_OF_RANGE
7023 SYST_INVALID_PR_ATTRIBUTE_VALUE

70
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

7024 SYST_PR_ATTRIBUTE_OUT_OF_RANGE
7025 SYST_INVALID_MO_ATTRIBUTE_VALUE
7026 SYST_MO_ATTRIBUTE_OUT_OF_RANGE
7029 SYST_INVALID_SS_ATTRIBUTE_VALUE
7030 SYST_INVALID_DC_ATTRIBUTE_VALUE
7031 SYST_INVALID_SD_ATTRIBUTE_VALUE
7032 SYST_INVALID_MA_ATTRIBUTE_VALUE
7033 SYST_INVALID_DT_ATTRIBUTE_VALUE
7034 SYST_INVALID_LP_ATTRIBUTE_VALUE
7035 SYST_LP_ATTRIBUTE_OUT_OF_RANGE
7036 SYST_INVALID_IA_ATTRIBUTE_VALUE
7037 SYST_IA_ATTRIBUTE_OUT_OF_RANGE
7038 SYST_INVALID_LT_ATTRIBUTE_VALUE
7039 SYST_INVALID_LI_ATTRIBUTE_VALUE
7040 SYST_LI_ATTRIBUTE_OUT_OF_RANGE
7041 SYST_INVALID_NN_ATTRIBUTE_VALUE
7042 SYST_APPLICATION_ALREADY_EXISTS
7043 SYST_PRINTER_ALREADY_EXISTS
7044 SYST_MONITOR_ALREADY_EXISTS
7046 SYST_LINK_ALREADY_EXISTS
7047 SYST_NODE_ALREADY_EXISTS
7049 SYST_APPLICATION_DOES_NOT_EXIST
7050 SYST_PRINTER_DOES_NOT_EXIST
7055 SYST_ATTRIBUTE_NOT_INDEXED
7056 SYST_OBJECT_NUMBER_OUT_OF_RANGE
7057 SYST_APPLICATION_NUMBER_OUT_OF_RANGE
7058 SYST_PRINTER_NUMBER_OUT_OF_RANGE
7059 SYST_MONITOR_NUMBER_OUT_OF_RANGE
7060 SYST_STATION_NUMBER_OUT_OF_RANGE
7061 SYST_REPR_TASK_NUMBER_OUT_OF_RANGE
7062 SYST_PRIN_TASK_NUMBER_OUT_OF_RANGE
7063 SYST_ALARM_CLASS_OUT_OF_RANGE
7065 SYST_INVALID_DN_ATTRIBUTE_VALUE

71
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

7066 SYST_DN_ATTRIBUTE_OUT_OF_RANGE
7067 SYST_INVALID_SH_ATTRIBUTE_VALUE
7068 SYST_SH_ATTRIBUTE_OUT_OF_RANGE
7069 SYST_STATION_ALREADY_EXISTS
7070 SYST_INVALID_DS_ATTRIBUTE_VALUE
7073 SYST_INVALID_DM_ATTRIBUTE_VALUE
7074 SYST_DM_ATTRIBUTE_OUT_OF_RANGE
7075 SYST_INVALID_TI_ATTRIBUTE_VALUE
7076 SYST_TI_ATTRIBUTE_OUT_OF_RANGE
7077 SYST_INVALID_PC_ATTRIBUTE_VALUE
7078 SYST_PC_ATTRIBUTE_OUT_OF_RANGE
7079 SYST_INVALID_RC_ATTRIBUTE_VALUE
7080 SYST_RC_ATTRIBUTE_OUT_OF_RANGE
7081 SYST_INVALID_EP_ATTRIBUTE_VALUE
7083 SYST_INVALID_ED_ATTRIBUTE_VALUE
7084 SYST_INVALID_SP_ATTRIBUTE_VALUE
7085 SYST_SP_ATTRIBUTE_OUT_OF_RANGE
7088 SYST_INVALID_TD_ATTRIBUTE_VALUE
7089 SYST_INVALID_AA_ATTRIBUTE_VALUE
7090 SYST_AA_ATTRIBUTE_OUT_OF_RANGE
7091 SYST_INVALID_AS_ATTRIBUTE_VALUE
7092 SYST_INVALID_QM_ATTRIBUTE_VALUE
7093 SYST_QM_ATTRIBUTE_OUT_OF_RANGE
7094 SYST_INVALID_PM_ATTRIBUTE_VALUE
7095 SYST_PM_ATTRIBUTE_OUT_OF_RANGE
7096 SYST_ST_ATTRIBUTE_OUT_OF_RANGE
7097 SYST_INVALID_PQ_ATTRIBUTE_VALUE
7098 SYST_PQ_ATTRIBUTE_OUT_OF_RANGE
7099 SYST_INVALID_QL_ATTRIBUTE_VALUE
7100 SYST_QL_ATTRIBUTE_OUT_OF_RANGE
7101 SYST_INVALID_HB_ATTRIBUTE_VALUE
7102 SYST_HB_ATTRIBUTE_OUT_OF_RANGE
7103 SYST_INVALID_EM_ATTRIBUTE_VALUE

72
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

7104 SYST_EM_ATTRIBUTE_OUT_OF_RANGE
7113 SYST_NA_ATTRIBUTE_OUT_OF_RANGE
7116 SYST_INVALID_ER_ATTRIBUTE_VALUE
7117 SYST_ER_ATTRIBUTE_OUT_OF_RANGE
7119 SYST_INVALID_SV_OR_UV_ATTRIBUTE_VALUE
7120 SYST_VECTOR_VALUE_EXPECTED
7122 SYST_ATTRIBUTE_NOT_SETTABLE
7123 SYST_APPLICATION_NAME_MISSING
7124 SYST_APPLICATION_IS_RUNNING
7125 SYST_PRINTER_IS_RUNNING
7126 SYST_MONITOR_IS_RUNNING
7128 SYST_LINK_IS_RUNNING
7129 SYST_ATTRIBUTE_INDEX_OUT_OF_RANGE
7130 SYST_SINGLE_INDEX_EXPECTED
7131 SYST_INVALID_RS_ATTRIBUTE_VALUE
7132 SYST_RS_ATTRIBUTE_OUT_OF_RANGE
7133 SYST_INVALID_CL_ATTRIBUTE_VALUE
7134 SYST_INVALID_CA_ATTRIBUTE_VALUE
7135 SYST_CA_ATTRIBUTE_OUT_OF_RANGE
7136 SYST_INVALID_CF_ATTRIBUTE_VALUE
7137 SYST_CF_ATTRIBUTE_OUT_OF_RANGE
7138 SYST_INVALID_TZ_ATTRIBUTE_VALUE
7139 SYST_TZ_ATTRIBUTE_OUT_OF_RANGE
7140 SYST_INVALID_TF_ATTRIBUTE_VALUE
7141 SYST_TF_ATTRIBUTE_OUT_OF_RANGE
7142 SYST_STATION_DOES_NOT_EXIST
7143 SYST_NODE_ROUTING_ERROR
7144 SYST_INVALID_PS_ATTRIBUTE_VALUE
7145 SYST_PS_ATTRIBUTE_OUT_OF_RANGE
7146 SYST_INVALID_MS_ATTRIBUTE_VALUE
7147 SYST_MS_ATTRIBUTE_OUT_OF_RANGE
7150 SYST_APPLICATION_IS_NOT_LOCAL
7153 SYST_INVALID_LD_ATTRIBUTE_VALUE

73
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

7154 SYST_INVALID_LL_ATTRIBUTE_VALUE
7155 SYST_INVALID_LF_ATTRIBUTE_VALUE
7156 SYST_INVALID_OD_ATTRIBUTE_VALUE
7157 SYST_FAILED_TO_START_PROGRAM
7158 SYST_APPLICATION_IS_LOCAL
7159 SYST_PRINTER_NOT_IN_NET
7160 SYST_INVALID_TR_ATTRIBUTE_VALUE
7161 SYST_LAN_LINK_ALREADY_RUNNING
7162 SYST_INVALID_PN_ATTRIBUTE_VALUE
7163 SYST_INVALID_HF_ATTRIBUTE_VALUE
7164 SYST_INVALID_FS_ATTRIBUTE_VALUE
7165 SYST_SN_ATTRIBUTE_OUT_OF_RANGE
7166 SYST_INVALID_SHADOWING_PHASE
7167 SYST_INVALID_SW_ATTRIBUTE_VALUE
7168 SYST_SW_ATTRIBUTE_OUT_OF_RANGE
7169 SYST_INVALID_SC_ATTRIBUTE_VALUE
7170 SYST_SC_ATTRIBUTE_OUT_OF_RANGE
7171 SYST_INVALID_SF_ATTRIBUTE_VALUE
7172 SYST_SF_ATTRIBUTE_OUT_OF_RANGE
7173 SYST_INVALID_SR_ATTRIBUTE_VALUE
7174 SYST_SR_ATTRIBUTE_OUT_OF_RANGE
7175 SYST_SHADOW_CONNECTION_REQUEST_FAILED
7176 SYST_SHADOWING_ALREADY_ACTIVE
7177 SYST_SHADOWING_IS_DISABLED
7178 SYST_EXECUTION_QUEUE_OUT_OF_RANGE
7179 SYST_INVALID_DB_ATTRIBUTE_VALUE
7180 SYST_NODE_NUMBER_OUT_OF_RANGE
7181 SYST_STATION_TYPE_ALREADY_EXISTS
7182 SYST_INVALID_DI_ATTRIBUTE_VALUE
7183 SYST_DI_ATTRIBUTE_OUT_OF_RANGE
7184 SYST_SHADOWING_TRANSMISSION_TIMEOUT
7185 SYST_SHADOWING_REVISION_INCOMPATIBLE
7186 SYST_SHADOW_MEMORY_DUMP_FAILED

74
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

7187 SYST_SHADOW_RECEIVER_ALREADY_CONNECTED
7188 SYST_SHADOW_MESSAGE_SEQUENCE_ERROR
7189 SYST_INVALID_SI_ATTRIBUTE_VALUE
7190 SYST_SI_ATTRIBUTE_OUT_OF_RANGE
7191 SYST_INVALID_SY_ATTRIBUTE_VALUE
7192 SYST_SY_ATTRIBUTE_OUT_OF_RANGE
7193 SYST_MEMORY_EXHAUSTED
7194 SYST_LOCAL_SHADOWING_FAILED
7195 SYST_NO_LOCAL_RAM_SHADOWING
7196 SYST_INVALID_AQ_ATTRIBUTE_VALUE
7197 SYST_INVALID_IL_ATTRIBUTE_VALUE
7198 SYST_IL_ATTRIBUTE_OUT_OF_RANGE
7199 SYST_INVALID_BP_ATTRIBUTE_VALUE
7200 SYST_CL_ATTRIBUTE_OUT_OF_RANGE
7201 SYST_ATTRIBUTE_IS_WRITE_ONLY
7202 SYST_PRINTER_IS_NOT_RUNNING
7203 SYST_INVALID_EE_ATTRIBUTE_VALUE
7204 SYST_EE_ATTRIBUTE_OUT_OF_RANGE
7205 SYST_INVALID_RN_ATTRIBUTE_VALUE
7206 SYST_RN_ATTRIBUTE_OUT_OF_RANGE
7207 SYST_DT_ATTRIBUTE_OUT_OF_RANGE
7208 SYST_INVALID_SL_ATTRIBUTE_VALUE
7209 SYST_SL_ATTRIBUTE_OUT_OF_RANGE
7210 SYST_INVALID_CS_ATTRIBUTE_VALUE
7211 SYST_PRINTER_CONTROL_TIMEOUT
7212 SYST_PRINTER_OPEN_ERROR
7213 SYST_NOT_A_TRANSPARENT_PRINTER
7214 SYST_INVALID_CX_ATTRIBUTE_VALUE
7215 SYST_INVALID_OJ_ATTRIBUTE_VALUE
7216 SYST_OJ_ATTRIBUTE_OUT_OF_RANGE
7218 SYST_SYSTEM_ALREADY_RUNNING
7219 SYST_INVALID_TS_ATTRIBUTE_VALUE
7220 SYST_INVALID_SQ_ATTRIBUTE_VALUE

75
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

7221 SYST_SQ_ATTRIBUTE_OUT_OF_RANGE
7223 SYST_INVALID_DE_ATTRIBUTE_VALUE
7224 SYST_DE_ATTRIBUTE_OUT_OF_RANGE
7225 SYST_NOT_AN_INTEGRATED_LINK
7226 SYST_RS_NOT_SUPPORTED_FOR_THE_LINK_TYPE
7229 SYST_INVALID_QP_ATTRIBUTE_VALUE
7230 SYST_INVALID_QD_ATTRIBUTE_VALUE
7231 SYST_QD_ATTRIBUTE_OUT_OF_RANGE
7232 SYST_PARALLEL_QUEUE_OUT_OF_RANGE
7233 SYST_INVALID_LA_ATTRIBUTE_VALUE
7238 SYST_INVALID_CT_ATTRIBUTE_VALUE
7240 SYST_INVALID_DU_ATTRIBUTE_VALUE
7241 SYST_DU_ATTRIBUTE_OUT_OF_RANGE
7242 SYST_INVALID_PH_ATTRIBUTE_VALUE
7243 SYST_INVALID_RL_ATTRIBUTE_VALUE
7244 SYST_INVALID_HP_ATTRIBUTE_VALUE
7245 SYST_EXTERNAL_COMMUNICATION_BLOCKED
7246 SYST_INVALID_OE_ATTRIBUTE_VALUE
7247 SYST_OE_ATTRIBUTE_OUT_OF_RANGE
7248 SYST_INVALID_OT_ATTRIBUTE_VALUE
7249 SYST_INVALID_CD_ATTRIBUTE_VALUE
7250 SYST_NO_EXTERNAL_CLOCK
7251 SYST_OT_ATTRIBUTE_OUT_OF_RANGE
7252 SYST_INVALID_QE_ATTRIBUTE_VALUE
The value set to the QE attribute of a APL:B object is invalid.
7253 SYST_QE_ATTRIBUTE_OUT_OF_RANGE
The value set to the QE attribute of a APL:B object is out of range.
7254 SYST_INVALID_ME_ATTRIBUTE_VALUE
The value set to the ME attribute of a SYS:B object is invalid.
7255 SYST_ME_ATTRIBUTE_OUT_OF_RANGE
The value set to the BE attribute of a SYS:B object is out of range.
7256 SYST_INVALID_AD_ATTRIBUTE_VALUE
The value set to the AD attribute of a SYS:B object is invalid.

76
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

7257 SYST_AUDIO_ALARM_DEVICE_NOT_STARTED
AUDIO_ALARM function failed because there is no audio alarm card
in the system or the card has not been started (SYS:BAA not set).
7258 SYST_OUTPUT_PROCESS_OBJECTS_DISABLED
This error code is raised by SCIL commands trying to use functionality
not enabled in the license or lack of a valid license.
7259 SYST_DIALOG_EDITOR_DISABLED
This error code is raised by SCIL commands trying to use functionality
not enabled in the license or lack of a valid license.
7260 SYST_PICTURE_EDITOR_DISABLED
This error code is raised by SCIL commands trying to use functionality
not enabled in the license or lack of a valid license.
7261 SYST_INVALID_HS_ATTRIBUTE_VALUE
The HS attribute is of invalid data type or out of range.
7262 SYST_HS_ATTRIBUTE_OUT_OF_RANGE
The HS attribute is out of range.
7263 SYST_INVALID_BN_ATTRIBUTE_VALUE
The BN attribute is of invalid data type or out of range.
7264 SYST_DUPLICATE_BN_ATTRIBUTE_VALUE
Base system object names must be unique.
7265 SYST_INVALID_BM_ATTRIBUTE_VALUE
The BM attribute is of invalid data type or out of range.
7266 SYST_BM_ATTRIBUTE_OUT_OF_RANGE
The BM attribute is out of range.
7267 SYST_BM_ATTRIBUTE_MISSING
The object number must be supplied when creating a base system object
by name.
7268 SYST_INVALID_BT_ATTRIBUTE_VALUE
The BT attribute is of invalid data type or out of range.
7269 SYST_BT_ATTRIBUTE_MISSING
The object number must be supplied when creating a base system object
by name.
7270 SYST_INVALID_IS_ATTRIBUTE_VALUE
7271 SYST_IS_ATTRIBUTE_OUT_OF_RANGE
7272 SYST_INVALID_MR_ATTRIBUTE_VALUE
7273 SYST_INVALID_TM_ATTRIBUTE_VALUE
The TM attribute is of invalid data type or out of range.
7274 SYST_INVALID_TB_ATTRIBUTE_VALUE
The TB attribute is of invalid data type.

77
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

7275 SYST_TB_ATTRIBUTE_OUT_OF_RANGE
The TB attribute is out of range.
7276 SYST_INVALID_AE_ATTRIBUTE_VALUE
7277 SYST_INVALID_ID_ATTRIBUTE_VALUE
7278 SYST_INVALID_HD_ATTRIBUTE_VALUE
7279 SYST_INVALID_IE_ATTRIBUTE_VALUE
7280 SYST_IE_ATTRIBUTE_OUT_OF_RANGE
7281 SYST_INVALID_HE_ATTRIBUTE_VALUE
7282 SYST_HE_ATTRIBUTE_OUT_OF_RANGE
7283 SYST_AMBIGUOUS_IS_MAPPING
The IS attribute value contains same application twice.
7284 SYST_INVALID_AW_ATTRIBUTE_VALUE
7285 SYST_AW_ATTRIBUTE_OUT_OF_RANGE
7286 SYST_INVALID_DF_ATTRIBUTE_VALUE
7287 SYST_DF_ATTRIBUTE_OUT_OF_RANGE
7288 SYST_INVALID_OP_ATTRIBUTE_VALUE
7289 SYST_OP_ATTRIBUTE_OUT_OF_RANGE
7290 SYST_INVALID_PA_ATTRIBUTE_VALUE
7291 SYST_PA_ATTRIBUTE_OUT_OF_RANGE
7293 SYST_ED_ATTRIBUTE_OUT_OF_RANGE
7294 SYST_INVALID_NT_ATTRIBUTE_VALUE
7295 SYST_OP_ATTRIBUTE_MISSING
Cannot start an OPC DA or A&E client, because the OP attribute is not
set in the corresponding node object.
7296 SYST_OP_ATTRIBUTE_CI_MISSING
Cannot start an OPC DA or A&E client, because the OP attribute of the
corresponding node object does not contain a CI field.
7297 SYST_INVALID_OP_ATTRIBUTE_CI_VALUE
Cannot start an OPC DA or A&E client, because the CI field of the OP
attribute of the corresponding node object does not specify a valid class
id.
7298 SYST_INVALID_OP_ATTRIBUTE_SK_VALUE
Cannot start an OPC DA or A&E client, because the SK field of the OP
attribute of the corresponding node object is invalid.
7299 SYST_INVALID_OP_ATTRIBUTE_SN_VALUE
Cannot start an OPC DA or A&E client, because the SN field of the OP
attribute of the corresponding node object is invalid.

78
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

7300 SYST_INVALID_OP_ATTRIBUTE_GR_VALUE
Cannot start an OPC DA client, because the GR field of the OP attribute
of the corresponding node object is invalid.
7301 SYST_OPC_DA_NODE_NAME_UNKNOWN
Cannot start an OPC DA client, because the RN attribute of the corres-
ponding node refers to a node with no name (NN not set).
7302 SYST_OPCC_ALREADY_EXISTS
7303 SYST_NOT_AN_OPC_STATION
Cannot start an OPC DA client, because the station object for the unit
does not specify an OPC station.
7304 SYST_NOT_AN_OPC_DA_NODE
Cannot start an OPC DA client, because the corresponding node object
does not specify an OPC_DA node.
7305 SYST_STATION_ND_MISSING
Cannot start an OPC DA or A&E client, because the corresponding sta-
tion object does not have a valid ND attribute.
7306 SYST_OPC_AE_NODE_NAME_UNKNOWN
Cannot start an OPC A&E client, because the RN attribute of the corres-
ponding node refers to a node with no name (NN not set).
7307 SYST_NOT_AN_OAE_STATION
Cannot start an OPC A&E client, because the station object for the unit
does not specify an OAE station.
7308 SYST_NOT_AN_OPC_AE_NODE
Cannot start an OPC A&E client, because the corresponding node object
does not specify an OPC_AE node.
7309 SYST_INVALID_OP_ATTRIBUTE_AA_VALUE
Cannot start an OPC A&E client, because the AA field of the OP attribute
of the corresponding node object is invalid.
7310 SYST_INVALID_PP_ATTRIBUTE_VALUE
7311 SYST_INVALID_SM_ATTRIBUTE_VALUE
7320 SYST_INVALID_OP_ATTRIBUTE_US_VALUE
Cannot start an OPC DA or A&E client, because the US field of the OP
attribute of the corresponding node object is invalid.
7321 SYST_INVALID_OP_ATTRIBUTE_PW_VALUE
Cannot start an OPC DA or A&E client, because the PW field of the OP
attribute of the corresponding node object is invalid.
7322 SYST_NODE_NAME_UNKNOWN
An OPC function is unable to deduce the target computer name.
7323 SYST_INVALID_IT_ATTRIBUTE_VALUE
7324 SYST_IT_ATTRIBUTE_OUT_OF_RANGE

79
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

7325 SYST_INVALID_DD_ATTRIBUTE_VALUE
7326 SYST_AS_ATTRIBUTE_OUT_OF_RANGE
7327 SYST_SS_ATTRIBUTE_OUT_OF_RANGE
7328 SYST_INVALID_RR_ATTRIBUTE_VALUE
7329 SYST_ND_AND_TN_MUST_BE_0_IN_PROXY_STATION
7330 SYST_INVALID_REDUNDANCY_CONFIGURATION
7331 SYST_NOT_A_PROXY_STATION
7332 SYST_STATION_IS_IN_USE
7333 SYST_DUPLICATE_ND_ST_TN
7334 SYST_INVALID_PF_ATTRIBUTE_VALUE
7335 SYST_APL_UNREACHABLE
7336 SYST_INVALID_OI_ATTRIBUTE_VALUE
7337 SYST_PROXY_APL_CONFIGURATION_ERROR
HS attribute defined in a non-proxy application or it denotes a proxy
application.
7338 SYST_INVALID_LS_ATTRIBUTE_VALUE
7339 SYST_INVALID_EY_ATTRIBUTE_VALUE
7340 SYST_INVALID_UA_ATTRIBUTE_VALUE
7341 SYST_ONLY_6_UAL_SERVERS_ALLOWED
7343 SYST_UAL_CONFIGURATION_ERROR
7344 SYST_UAL_CONFIGURATION_TIMEOUT
7345 SYST_INVALID_PI_ATTRIBUTE_VALUE
7346 SYST_INVALID_AI_ATTRIBUTE_VALUE
7347 SYST_AI_ATTRIBUTE_OUT_OF_RANGE
7348 SYST_INVALID_CE_ATTRIBUTE_VALUE
7349 SYST_CE_ATTRIBUTE_OUT_OF_RANGE
7351 SYST_INVALID_WL_ATTRIBUTE_VALUE

4.2.12 User Account and Session Management (USER) Status Codes

8002 USER_ROLE_CAN_BE_SELECTED_ONLY_AT_LOGIN
8003 USER_INVALID_ROLE_SELCTION
8004 USER_DUPLICATE_AUTHORIZATION_GROUP_NAME
8005 USER_DUPLICATE_AUTHORIZATION

80
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

8006 USER_DUPLICATE_ROLE_NAME
8007 USER_DUPLICATE_USER_NAME
8008 USER_UNSUPPORTED_UAM_VERSION
8009 USER_INVALID_AUTHORIZATION_GROUP_NAME
8010 USER_AUTHORIZATION_GROUP_DOES_NOT_EXIST
8011 USER_AUTHORIZATION_GROUP_IS_IN_USE
8012 USER_ROLE_DOES_NOT_EXIST
8013 USER_ROLE_IS_IN_USE
8014 USER_PREDEFINED_ROLE_MAY_NOT_BE_REMOVED
8015 USER_USER_DOES_NOT_EXIST
8016 USER_THE_ONLY_ADMINISTRATOR_MAY_NOT_BE_REMOVED
8017 USER_PASSWORD_POLICY_VIOLATION
8018 USER_INVALID_PASSWORD_POLICY
8019 USER_INVALID_ROLE_NAME
8020 USER_INVALID_USER_NAME
8021 USER_INVALID_TIMEOUT_VALUE
8022 USER_UNKNOWN_ROLE_ATTRIBUTE
8023 USER_INVALID_AUTHORIZATION
8024 USER_INVALID_AUTHORIZATION_LEVEL
8025 USER_AUTHORIZATION_LEVEL_OUT_OF_RANGE
8026 USER_GENERAL_AUTHORIZATION_MISSING
8027 USER_UNKNOWN_USER_ATTRIBUTEE
8028 USER_INVALID_ROLE_LIST
8029 USER_INVALID_LANGUAGE_NAME
8030 USER_INVALID_DISABLED_VALUE
8031 USER_INVALID_PASSWORD_VALUE
8032 USER_ROLES_MISSING
8033 USER_ALREADY_LOGGED_IN
8034 USER_NOT_LOGGED_IN
8035 USER_INVALID_USER_OR_PASSWORD
8036 USER_SESSION_NOT_VALID
8037 USER_PREDEFINED_USER_MAY_NOT_BE_REMOVED
8038 USER_AUTHORIZATION_FAILURE

81
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

8039 USER_CANNOT_REMOVE_OR_DISABLE_MYSELF
8040 USER_GUEST_USER_MAY_NOT_BE_CHANGED
8041 USER_INVALID_FORCE_PASSWORD_CHANGE_VALUE
8042 USER_LAST_GENERAL_5_AUTHORIZATION
8043 USER_NAME_NOT_VALID_AS_A_FILE_NAME
8044 USER_CAM_NOT_AVAILABLE
8045 USER_GUEST_HAS_NO_PASSWORD
8049 USER_LOGIN_FAIL_WRONG_CR
8051 USER_LOGIN_FAIL_EXPIRED
8052 USER_LOGIN_FAIL_LOCKED
8053 USER_LOGIN_FAIL_DISABLED
8054 USER_LOGIN_FAIL_NO_ROLES
8055 USER_LOGIN_FAIL_NO_CAM
8056 USER_LOGIN_FAIL_SINGLE_USER_LOGIN
8057 USER_ANONYMOUS_ROLE_UNASSIGNED
8058 USER_ANONYMOUS_ROLE_ALREADY_ASSIGNED
8059 USER_LOGIN_FAIL_ANONYMOUS_LOGIN_DISABLED
8060 USER_LOGIN_FAIL_ANONYMOUS_FIRST_LOGIN
8061 USER_ANONYMOUS_USER_MAY_NOT_BE_MODIFIED
8062 USER_ANONYMOUS_ROLE_MAY_NOT_BE_ASSIGNED
8063 USER_DUPLICATE_LOGIN_ADDRESS_NAME
8064 USER_INVALID_LOGIN_ADDRESS_ROLES_VALUE
8065 USER_INVALID_SINGLE_SESSION_VALUE
8066 USER_DUPLICATE_AOR_NAME
8067 USER_INVALID_AOR_DATA
8068 USER_OVERLAPPING_AOR
8069 USER_NON_EXISTENT_AOR_OBJECT_IDENTIFIER
8070 USER_OVERLAP_NOT_ALLOWED_WHEN_EAR_IN_USE
8071 USER_AOR_MUST_BE_ENABLED_WHEN_EAR_IN_USE
8072 USER_AOR_DOES_NOT_EXIST
8073 USER_INVALID_AOR_ROLES
8074 USER_EAR_ROLE_OUT_OF_RANGE
8075 USER_LOGIN_FAIL_EAR_SINGLE_LOCATION

82
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

8076 USER_NOT_SUPPORTED_WHEN_CAM_IN_USE
8077 USER_NO_EAR_ROLE_FOR_THE_AOR
8078 USER_HAS_NO_OPERATOR_EAR_ROLE
8079 USER_NOT_AUTHORIZED_TO_SET_EAR
8080 USER_EAR_NOT_IN_USE
8081 USER_ROLE_IS_IN_AOR_USE

4.2.13 TCP/IP (INPC) Status Codes

8301 INPC_TCPIP_COMMUNICATION_INIT_FAILED
8302 INPC_TCPIP_LINK_ABORTED
8303 INPC_TCPIP_CONNECTION_REQUEST_FAILED
8304 INPC_TCPIP_TRANSMIT_IO_FAILED
8306 INPC_TCPIP_UNKNOWN_HOST
8307 INPC_IP_ADDRESS_NOT_WHITELISTED

4.2.14 OPC Data Access Client (OPCC) Status Codes

8401 OPCC_NO_CONNECTION_TO_SERVER
Attempt to access an OPC item while there is no connection to the OPC
DA Server.
8402 OPCC_ITEM_NOT_FOUND_IN_SERVER
Attempt to access an OPC item that does not exist in the OPC DA
Server.
8403 OPCC_ITEM_NOT_WRITABLE
Attempt to set an OPC item that is not writable.
8404 OPCC_INVALID_WRITE_VALUE
Attempt to set an OPC item to a value rejected by the OPC DA Server.
8405 OPCC_WRITE_FAILURE
Unspecified failure when setting an OPC item value.
8406 OPCC_UNIT_NOT_STARTED
Attempt to refresh the data from an OPC unit that has not been started
(function OPC_DA_REFRESH).
8407 OPCC_GROUP_DOES_NOT_EXIST
Attempt to refresh the data from an OPC group that has not been defined
(function OPC_DA_REFRESH).

83
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

8408 OPCC_GROUP_IS_OUTPUT_ONLY
Attempt to refresh the data from an output-only OPC group (function
OPC_DA_REFRESH).
8409 OPCC_REFRESH_IN_PROGRESS
Attempt to refresh the data from an OPC unit while another refresh is
still in progress (function OPC_DA_REFRESH).
8410 OPCC_REFRESH_TIMEOUT
The OPC DA Server did not respond to a refresh request (function
OPC_DA_REFRESH).

4.2.15 OpenSSL (OSSL) Status Codes

9300 OSSL_COMMUNICATION_ERROR
9301 OSSL_X509_CERTIFICATE_CREATION_FAILED
9302 OSSL_BAD_KEY_STORAGE
9303 OSSL_CERTIFICATE_NOT_KNOWN
9304 OSSL_CERTIFICATE_MISMATCH
9305 OSSL_DISCONNECTED
9306 OSSL_CONNECTION_WITH_UNKNOWN_SA
9307 OSSL_UNSECURE_CONNECTION_NOT_ALLOWED

4.3 NET Status Codes

4.3.1 Common NET Status Codes

10001 NETP_SYSTEM_INITIALIZED
10002 NETP_IU_ATRIBUTE_WAS_EXPECTED
The base system and the frontend do not communicate properly with
each other. Contact an ABB representative.
10003 NETP_TIMEOUT_WHILE_WAITING_ACKNOWLEDGE
The base system and the frontend do not communicate properly with
each other. Contact an ABB representative.
10004 NETP_UNKNOWN_CONFIGURATION_OBJECT
10005 NETP_UNKNOWN_SCM_FUNCTION
The base system and the frontend do not communicate properly with
each other. Contact an ABB representative.
10006 NETP_OUT_OF_MEMORY

84
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

10007 NETP_CONFLICT_IN_PRECONFIGURATION
10008 NETP_PROTOCOL_NOT_SUPPORTED
10009 NETP_NAME_IS_LOGICAL_OR_UNDEFINED

4.3.2 Redundant Frontend Status Codes

10500 REFP_NO_REPLY_FROM_STANDBY_FE
10501 REFP_NO_REPLY_FROM_HOT_FE
10502 REFP_NO_BUFFER
10503 REFC_HOT_FE_NOT_RESPONDING
10504 REFC_UNDEFINED_PEER_NODE
10505 REFC_INVALID_PEER_NODE_NUMBER
10506 REFC_INVALID_RUNNING_MODE
10507 REFC_INVALID_SHADOWING_MODE
10508 REFC_TRANSFER_DATA_LENGTH_MISMATCH
10509 REFC_INVALID_TRANSFER_DATA_ID
10510 REFC_SC_DATA_OVERFLOW
10511 REFC_INVALID_INDEX_RANGE
10512 REFC_INVALID_SH_AND_RM_VALUE_COMBINATION
10513 REFP_PEER_HAS_LOST_APL_CONNECTION
10514 REFC_INITIALIZATION_NOT_COMPLETE

4.3.3 Errors in ACP Message Structure

11001 BUFMS_BINARY_TYPE_EXPECTED
11002 BUFMS_BUFFER_OVERFLOW
11003 BUFMS_CHARACTER_TYPE_EXPECTED
11005 BUFMS_SIGNED_16_OUT_OF_RANGE
11006 BUFMS_SIGNED_16_TYPE_EXPECTED
11007 BUFMS_SIGNED_32_TYPE_EXPECTED
11009 BUFMS_TIMESTAMP_ITEM_EXPECTED
11010 BUFMS_UNKNOWN_DATA_TYPE
11011 BUFMS_UNSIGNED_16_OUT_OF_RANGE
11012 BUFMS_UNSIGNED_16_TYPE_EXPECTED

85
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

11014 BUFMS_UNSIGNED_8_OUT_OF_RANGE
11015 BUFMS_UNSIGNED_8_TYPE_EXPECTED
11016 BUFMS_ZERO_LENGTH_DATA_ARRAY
The base system and the frontend do not communicate properly. Contact
an ABB representative.
11017 BUFMS_BIT_VALUE_TYPE_EXPECTED
11018 BUFMS_FULL_TIMESTAMP_TYPE_EXPECTED
11019 BUFMS_ADDRESS_TYPE_EXPECTED
11020 BUFMS_BIT_STREAM_TYPE_EXPECTED
11021 BUFMS_SIGNED_8_OUT_OF_RANGE
11022 BUFMS_SIGNED_8_TYPE_EXPECTED
11023 BUFMS_SIGNED_32_OUT_OF_RANGE
11024 BUFMS_UNSIGNED_32_OUT_OF_RANGE
11025 BUFMS_UNSIGNED_32_TYPE_EXPECTED
11026 BUFMS_FLOAT_32_TYPE_EXPECTED
11027 BUFMS_EXTENDED_ADDRESS_TYPE_EXPECTED
11028 BUFMS_SIGNED_64_OUT_OF_RANGE
11029 BUFMS_SIGNED_64_TYPE_EXPECTED
11030 BUFMS_UNSIGNED_64_OUT_OF_RANGE
11031 BUFMS_UNSIGNED_64_TYPE_EXPECTED
11032 BUFMS_FLOAT_64_TYPE_EXPECTED
11033 BUFMS_TEXT_TYPE_EXPECTED

4.3.4 Common NET Application Layer Status Codes

12002 APPL_DEVICE_ALREADY_RESERVED The device is occupied by


another SYS600 process.
12003 APPL_DEVICE_ATTRIBUTE_NOT_CHANGEABLE
12004 APPL_DEVICE_NOT_RESERVED
12006 APPL_ILLEGAL_SOURCE_FOR_GIVEN_CMD
The sender has not the right to give the command in question.
12007 APPL_MESSAGE_BUFFER_OVERFLOW
12008 APPL_INVALID_VALUE_FOR_CHOSEN_ATTRIBUTE
12010 APPL_NONEXISTENT_DEVICE_ATTRIBUTE

86
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

12011 APPL_UNKNOWN_COMMAND_SOURCE
The sender of the command is unknown.
12012 APPL_RELEASE_CMD_FROM_WRONG_PROCESS
12013 APPL_INVALID_AL_ATTRIBUTE_VALUE
12014 APPL_INVALID_MI_ATTRIBUTE_VALUE
12015 APPL_INVALID_MS_ATTRIBUTE_VALUE
12016 APPL_INVALID_MI_ATTRIBUTE_INDEX
12017 APPL_INVALID_ED_INDEX
12018 APPL_UNKNOWN_ED_TRANSLATION
12019 APPL_DATA_TYPE_OVERFLOW
12020 APPL_INVALID_AS_ATTRIBUTE_VALUE
12021 APPL_UNKNOWN_EDEV_DEVICE_TYPE
12022 APPL_INVALID_MS_ATTRIBUTE_INDEX

4.3.5 System Process Status Codes

12101 SYSC_REPLY_MESSAGE_TIMEOUT
12102 SYSC_SCM_DATA_IGNORED
12103 SYSC_UNDEFINED_SYS_CONNECTION
12104 SYSC_INVALID_RT_ATTRIBUTE_VALUE
12105 SYSC_INVALID_SU_ATTRIBUTE_VALUE
12106 SYSC_STATION_NOT_DEFINED_IN_BASE_SYSTEM

4.3.6 STA Device Status Codes (ANSI X3.28)

12301 STAC_AB_DATA_ITEM_OVERFLOW
12302 STAC_AB_DATA_OVERFLOW
12303 STAC_ATTRIBUTE_IS_READ_ONLY
12304 STAC_ATTRIBUTE_IS_WRITE_ONLY
12305 STAC_COMMAND_AND_DATA_TYPE_IN_CONFLICT
The command type (read/write) is not allowed for the chosen memory
area.
12306 STAC_COMMAND_NOT_IMPLEMENTED
12307 STAC_DIAGNOSTIC_CT_RESET_DATA_ERROR

87
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

12308 STAC_DIAGNOSTIC_LOOP_TEST_DATA_ERROR
12309 STAC_DOWNLOAD_NOT_IMPLEMENTED
12310 STAC_FUNCTION_NOT_IMPLEMENTED
12311 STAC_ILLEGAL_DIGIT_IN_BCD_NUMBER
Undefined or incorrectly defined memory area.
12312 STAC_ILLEGAL_MESSAGE_LENGTH
12314 STAC_ILLEGAL_PLC2_COMMAND_CODE
12315 STAC_ILLEGAL_SC_DATA_TYPE_COMBINATION
Analog and digital data cannot be included in the same message.
12316 STAC_INDEX_RANGE_CROSSES_RUNG_BOUNDARY
A read or write command refers to an address area which is not totally
within the same memory area.
12317 STAC_INTERNET_COMM_NOT_IMPLEMENTED
12318 STAC_MEMORY_RUNG_DEFINITION_ERROR
12319 STAC_NONCONTIGOUS_BIT_WRITE_MEMORY_AREA
12320 STAC_NO_MEMORY_RUNG_CHOSEN_FOR_READ_DATA
12321 STAC_PLC2_DATA_CODE_NOT_IMPLEMENTED
12322 STAC_SC_DATA_OVERFLOW
12323 STAC_SC_TO_AB_ITEM_TYPE_INCOMPATIBILITY
The data elements of the SCM message can not be transformed according
to the memory area code attribute.
12324 STAC_UNDEFINED_PLC2_MEMORY_ADDRESS
12325 STAC_UNKNOWN_DESTINATION_STATION
12326 STAC_UNKNOWN_LOGICAL_DESTINATION
12327 STAC_UNKNOWN_LOGICAL_SOURCE
12328 STAC_UNKNOWN_SOURCE_STATION
12329 STAC_ZERO_LENGTH_DATA_ARRAY
12330 STAP_AB_SC_CONVERSION_ERROR
The message can not be transformed from the form used in the RTU to
the one used by the main program (SCM).
12332 STAP_ILLEGAL_AB_COMMAND_DESTINATION
12333 STAP_STATION_LINE_ERROR
The CTS or the DCD line of the RS232 connection is inactive. The cable
is uncoupled, the hand shaking signals are incorrectly coupled or the
modem is incorrectly coupled.
12334 STAP_REPLY_TIMEOUT

88
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

12335 STAP_SC_AB_CONVERSION_ERROR
The message can not be transformed from the form used by the main
program (SCM) to the one used by the RTU (ABM).
12336 STAP_SIGNAL_QUEUE_EMPTY
12337 STAP_STATION_SUSPENDED
The RTU is suspended. The reason may be:
12338 STAP_STATION_SUSPENDED_AND_LINE_ERROR
The error situations 12333 and 12337 have occurred simultaneously.
12339 STAP_STOPPED
The IU attribute of the station is 0 (not in use).
12340 STAC_ILLEGAL_OCTAL_BCD_DIGIT
The memory address appearing in a spontaneous message does not follow
the coding way chosen in the memory area definition (the attribute BF).
12341 STAC_INVALID_AD_ATTRIBUTE_VALUE
12342 STAC_INVALID_AT_ATTRIBUTE_VALUE
12343 STAC_INVALID_BF_ATTRIBUTE_VALUE
12344 STAC_INVALID_CO_ATTRIBUTE_VALUE
12345 STAC_INVALID_DI_ATTRIBUTE_VALUE
12346 STAC_INVALID_DT_ATTRIBUTE_VALUE
12347 STAC_INVALID_LE_ATTRIBUTE_VALUE
12348 STAC_INVALID_MEMORY_RUNG_NUMBER
12349 STAC_INVALID_MR_ATTRIBUTE_VALUE
12350 STAC_INVALID_PH_ATTRIBUTE_VALUE
12351 STAC_INVALID_RT_ATTRIBUTE_VALUE
12352 STAC_INVALID_SE_ATTRIBUTE_VALUE
12353 STAC_INVALID_SU_ATTRIBUTE_VALUE
12354 STAC_INVALID_TS_ATTRIBUTE_VALUE
12355 STAC_UNKNOWN_MEMORY_RUNG
12357 STAC_MEMORY_RUNG_ALREADY_EXISTS
12358 STAC_UNKNOWN_STA_ATTRIBUTE
12359 STAC_DIAGNOSTIC_CMD_TRANSMISSION_ERROR
12360 STAC_INVALID_DE_ATTRIBUTE_VALUE
12361 STAC_STATION_RESERVED_BY_OTHER_SYSTEM
12362 STAC_MEMORY_ALLOCATION_FAILED
Memory reservation does not succeed. Contact an ABB representative.

89
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

12365 STAC_INVALID_FS_ATTRIBUTE_VALUE
12366 STAC_UNKNOWN_DIAGNOSTIC_COUNTER
12367 STAC_INVALID_INDEX_RANGE
12368 STAP_SUSPENSIVE_STATUS_IN_REPLY_MSG
12369 STAC_PLC_IN_PROGRAM_LOAD_MODE
12370 STAC_PLC_IN_TEST_MODE
12371 STAC_PLC_IN_REMOTE_PROGRAM_LOAD_MODE
12372 STAC_PLC_IN_REMOTE_TEST_MODE
12373 STAC_PLC_IN_DOWNLOAD_MODE
12374 STAC_UNKNOWN_PLC_MODE
12375 STAC_ERROR_IN_PLC_PROG_COMM_ZONE
12376 STAC_NO_INTERFACE_PLC_PROCESSOR_COMM
12377 STAC_PLC_SHUTDOWN_IN_EFFECT
12378 STAC_PLC_SHUTDOWN_REQUESTED
12379 STAC_MAJOR_PLC_PROCESSOR_FAULT
12380 STAC_UNKNOWN_COMMUNICATION_INTERFACE_TYPE
12381 STAC_INVALID_DIAGNOSTIC_STATUS
12382 STAC_SPLIT_PROCESS_DOES_NOT_EXIST
The SPLIT function has not been activated for the station in question.
12383 STAC_PROGRAM_CASE_ERROR
12384 STAC_INVALID_SP_ATTRIBUTE_VALUE
12385 STAC_INVALID_WORD_ADDRESS
12386 STAP_REPLY_TX_FAILURE
12387 STAC_INVALID_CP_ATTRIBUTE_VALUE
12388 STAC_READ_SIZE_OVERFLOW
12389 STAC_INVALID_MC_ATTRIBUTE_VALUE
12390 STAC_ORIGINAL_STATION_DOES_NOT_EXIST
12391 STAC_ORIGINAL_MEMORY_AREA_DOES_NOT_EXIST
12392 STAC_AB_DATA_LENGTH_MISMATCH
12393 STAC_AB_DATA_TYPE_MISMATCH
12394 STAC_ITEM_ADDRESS_OVERFLOW
12395 STAC_READ_SIZE_MISMATCH
Mismatch in the read reply data length.
12396 STAC_INVALID_ST_ATTRIBUTE_VALUE

90
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

12397 STAC_TIMESYNC_MEMORY_AREA_NOT_DEFINED
12399 STAC_INVALID_TIMESTAMP_RECEIVED

4.3.7 STA Device, Message Split Status Codes (ANSI X3.28)

12401 STMC_NON_VALID_SPLIT_REPLY
12402 STMP_SPLIT_ORIG_DEST_FAIL
Failed to send the message to the stations defined in the RTU.
12403 STMP_SPLIT_SEC_DEST_FAIL
Failed to send the message to the receivers of the SPLIT message defined
in NET.
12404 STMP_SPLIT_TOTAL_FAIL
The message was not successfully sent to any receiving station.
12405 STMC_SPLIT_ORIG_DEST_FAIL
Sending the message to the target station defined in the RTU did not
succeed.
12406 STMC_SPLIT_SEC_DEST_FAIL
Failed to send the message to the receivers of the SPLIT message defined
in NET.
12407 STMC_SPLIT_TOTAL_FAIL
The message was not successfully sent to any receiving station.
12408 STMC_SPLIT_NEAR_SEC_DEST_FAIL
12409 STMC_SPLIT_NEAR_TOTAL_FAIL
12410 STMC_SEC_OK_STATUS

4.3.8 SID Devices Status Codes (ADLP80/180 slave)

12450 SIDC_INVALID_INDEX_RANGE
12451 SIDC_ILLEGAL_ATTRIBUTE_VALUE
12453 SIDC_UNKNOWN_DIAGNOSTIC_COUNTER
12454 SIDC_SC_DATA_OVERFLOW
12455 SIDC_UNKNOWN_SID_ATTRIBUTE
12456 SIDC_TEV_BUFFER_OVERFLOW
12457 SIDC_UNKNOWN_FNC_RECEIVED
12458 SIDC_INVALID_FNC_RECEIVED
12459 SIDC_FCOM_COLDSTART_RECEIVED

91
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

12460 SIDC_UNKNOWN_FCOM_RECEIVED
12461 SIDC_ILLEGAL_FCOM_RECEIVED
12462 SIDC_CBXC_RECEIVED
12463 SIDC_IHC_RECEIVED
12464 SIDC_IHC_FAILED
12465 SIDC_EXC_FAILED
12466 SIDC_ERMI_BUFFER_OVERFLOW
12467 SIDC_PREV_PC_VALUE_NOT_YET_REPORTED
12468 SIDC_PULSECOUNTER_IS_BLOCKED
12469 SIDC_ARGUMENT_EXPECTED
12470 SIDC_TOO_MANY_ARGUMENTS
12471 SIDC_NOT_ACTIVE_OR_NO_FTAB_LOADED
12472 SIDC_FCOM_ACTIVATE_RECEIVED
12474 SIDC_UNKNOWN_FTAB_RECEIVED
12475 SIDC_POINT_NOT_INITIALIZED_WHILE_DI_0
12480 SIDP_CBXC_RECEIVED
12481 SIDP_IHC_RECEIVED
12482 SIDP_EXC_FAILED
12483 SIDP_ILLEGAL_FNC_RECEIVED
12484 SIDP_COMMUNICATION_WITH_CS_LOST
12485 SIDP_COMMUNICATION_WITH_CS_ESTABLISHED
12486 SIDP_UNIMPLEMENTED_FNC_RECEIVED
12487 SIDP_UNABLE_TO_ALLOCATE_MEMORY

4.3.9 SIN Devices Status Codes (ADLP180 master)

12501 SINC_AD_DATA_ITEM_OVERFLOW
12502 SINC_AD_DATA_OVERFLOW
12503 SINC_ATTRIBUTE_IS_READ_ONLY
12504 SINC_ATTRIBUTE_IS_WRITE_ONLY
12505 SINC_COMMAND_AND_DATA_TYPE_IN_CONFLICT
12506 SINC_COMMAND_NOT_IMPLEMENTED
12507 SINC_DIAGNOSTIC_CT_RESET_DATA_ERROR

92
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

12508 SINC_DIAGNOSTIC_LOOP_TEST_DATA_ERROR
12509 SINC_DOWNLOAD_NOT_IMPLEMENTED
12510 SINC_FUNCTION_NOT_IMPLEMENTED
12512 SINC_ILLEGAL_MESSAGE_LENGTH
12514 SINC_ILLEGAL_SINDAC_COMMAND_CODE
12515 SINC_ILLEGAL_SC_DATA_TYPE_COMBINATION
12516 SINC_INDEX_RANGE_CROSSES_PRIORITY_BOUNDARY
12517 SINC_INTERNET_COMM_NOT_IMPLEMENTED
12518 SINC_MEMORY_DEFINITION_ERROR
12521 SINC_EVENT_BUFFER_OVERFLOW
12522 SINC_SC_DATA_OVERFLOW
12523 SINC_SC_TO_AD_ITEM_TYPE_INCOMPATIBILITY
12525 SINC_UNKNOWN_DESTINATION_STATION
12526 SINC_UNKNOWN_LOGICAL_DESTINATION
12527 SINC_UNKNOWN_LOGICAL_SOURCE
12528 SINC_UNKNOWN_SOURCE_STATION
12529 SINC_ZERO_LENGTH_DATA_ARRAY
12539 SINP_STOPPED
12540 SINP_SCI_RECEIVED
12541 SINP_CBXC_RECEIVED
12542 SINP_IHC_RECEIVED
12543 SINP_EXC_FAILED
12544 SINP_IHC_FAILED
12550 SINC_NO_PENDING_EVENTS
12556 SINC_ILLEGAL_ATTRIBUTE_VALUE
12557 SINC_ILLEGAL_SIN_ATTRIBUTE
12558 SINC_UNKNOWN_SIN_ATTRIBUTE
12559 SINC_DIAGNOSTIC_CMD_TRANSMISSION_ERROR
12562 SINC_MEMORY_ALLOCATION_FAILED
12566 SINC_UNKNOWN_DIAGNOSTIC_COUNTER
12567 SINC_INVALID_INDEX_RANGE
12568 SINC_INVALID_CONFIGURATION
12580 SINC_UNKNOWN_COMMUNICATION_INTERFACE_TYPE

93
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

12581 SINC_INVALID_DIAGNOSTIC_STATUS
12585 SINC_INVALID_WORD_ADDRESS

4.3.10 RTU Device Status Codes (RP570 master)

12601 RTUP_UNEXPECTED_RESPONSE
12602 RTUP_DEVICE_SUSPENDED
12603 RTUP_TIMEOUT_WHILE_WAITING_RESPONSE
12604 RTUP_DEVICE_STOPPED
12605 RTUP_DEVICE_STARTED
12606 RTUP_STATUS_CHECK_REQUESTED
12607 RTUP_TOTAL_BROADCAST_FAILURE
12608 RTUP_PARTIAL_BROADCAST_FAILURE
12609 RTUP_FAILED_TO_INITIALIZE_BC_TELEGRAM
12610 RTUP_BROADCAST_SUCCESSFULL
12611 RTUP_SB_TRANSFER_NOT_CONFIRMED
12612 RTUS_SUB_RTU_DOES_NOT_EXIST
12613 RTUS_SUB_RTU_DOES_NOT_ANSWER
12614 RTUS_OUT_OF_SERVICE
12615 RTUS_UNEXPECTED_ANSWER_FROM_SUB_RTU
12616 RTUS_NEXT_LEVEL_ROUTER_DOES_NOT_ANSWER
12617 RTUS_NEXT_LEVEL_ROUTER_OUT_OF_SERVICE
12618 RTUS_UNEXPECTED_ANSWER_FROM_NEXT_ROUTER
12619 RTUS_COMMAND_BUFFER_OVERFLOW
12620 RTUS_SUB_RTU_COMLINE_INOPERABLE
12621 RTUS_THIS_ROUTER_IS_DEACTIVATED
12622 RTUS_COMMAND_TO_SUB_RTU_IS_ACTIVE
12623 RTUS_INTERNAL_ERROR_23ZG20
12624 RTUS_INTERNAL_ERROR_23LK20
12625 RTUS_COMM_LOST_WITH_OTHER_CC
12626 RTUS_COMM_OK_WITH_OTHER_CC
12627 RTUS_SYNCHRONIZED_FROM_THIS_CC
12628 RTUS_NOT_SYNCHRONIZED_FROM_THIS_CC

94
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

12629 RTUS_FTAB_LOADED_FROM_THIS_CC
12630 RTUS_FTAB_NOT_LOADED_FROM_THIS_CC
12651 RTUC_UNKNOWN_DIAGNOSTIC_COUNTER
12652 RTUC_INVALID_RT_ATTRIBUTE_VALUE
12653 RTUC_SC_DATA_OVERFLOW
12654 RTUC_INVALID_TAG_NUMBER
12655 RTUC_TAGGED_EVENT_NOT_FOUND
12656 RTUC_TAGGED_MESSAGE_NOT_FOUND
12657 RTUC_UNKNOWN_RTU_ATTRIBUTE
12658 RTUC_INVALID_INDEX_RANGE
12659 RTUC_INVALID_IDENT_NUMBER
12660 RTUC_INVALID_SE_ATTRIBUTE_VALUE
12661 RTUC_ILLEGAL_APPLICATION_FOR_OPERATION
12662 RTUC_ATTRIBUTE_IS_WRITE_ONLY
12663 RTUC_ONLY_CHARACTER_ARRAYS_ALLOWED
12664 RTUC_ILLEGAL_LENGTH_FOR_TD
12665 RTUC_NOT_EXECUTED_RESPONSE
12666 RTUC_UNEXPECTED_RESPONSE
12667 RTUC_INVALID_FCOM_NUMBER
12668 RTUC_FCOM_NUMBER_NOT_USED
12669 RTUC_NOT_ENOUGH_INFO_FOR_FCOM
12670 RTUC_ILLEGAL_FCOM_INFO
12671 RTUC_TERMINAL_STATUS_OVERFLOW
12672 RTUC_EVENT_RECORDING_MESSAGES_LOST
12673 RTUC_ONLY_WRITE_IS_POSSIBLE
12674 RTUC_ILLEGAL_OBJECT_TYPE
12675 RTUC_ILLEGAL_OBJECT_ADDRESS
12676 RTUC_UNEXPECTED_VALUE
12677 RTUC_UNEXPECTED_COMMAND_TYPE
12678 RTUC_ILLEGAL_LENGTH_FOR_FT
12679 RTUC_DEVICE_MUST_BE_ALLOCATED
12680 RTUC_RTU_ADDRESS_NOT_CONFIGURED
12681 RTUC_INVALID_SC_ATTRIBUTE_VALUE

95
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

12682 RTUC_ILLEGAL_BROADCAST_ACTION
12683 RTUC_TRANSPARENT_DATA_PENDING
12684 RTUC_TRANSPARENT_DATA_OVERFLOW
12685 RTUC_NO_TRANSPARENT_DATA_PENDING
12686 RTUC_TRANSFER_DATA_LENGTH_MISMATCH
12687 RTUC_MEMORY_ALLOCATION_FAILED
12688 RTUC_ROUTER_RTU_ADDRESS_NOT_FOUND
12689 RTUC_INVALID_HR_ATTRIBUTE_VALUE
12690 RTUC_INVALID_SM_ATTRIBUTE_VALUE
12691 RTUC_INVALID_TA_ATTRIBUTE_VALUE
12692 RTUC_CANNOT_GET_MESSAGE_BUFFER
12693 RTUC_INVALID_TA_ATTRIBUTE_INDEX

4.3.11 RTU Device, Terminal Status Codes (RP570 master)

12701 RTUS_INDICATION_FAULTY
12702 RTUS_INDICATION_OK
12703 RTUS_ANALOG_VALUE_FAULTY
12704 RTUS_ANALOG_VALUE_OK
12705 RTUS_DIGITAL_VALUE_FAULTY
12706 RTUS_DIGITAL_VALUE_OK
12707 RTUS_PULSE_COUNTER_FAULTY
12708 RTUS_PULSE_COUNTER_OK
12709 RTUS_COMMAND_OUTPUT_FAULTY
12710 RTUS_COMMAND_OUTPUT_OK
12711 RTUS_SETPOINT_OUTPUT_FAULTY
12712 RTUS_SETPOINT_OUTPUT_OK
12713 RTUS_GENERAL_OUTPUT_FAULTY
12714 RTUS_GENERAL_OUTPUT_OK
12715 RTUS_RTU_FAULTY
12716 RTUS_RTU_OK
12717 RTUS_RTU_ACTIVE
12718 RTUS_RTU_NOT_ACTIVE

96
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

12719 RTUS_RTU_SYNCHRONIZED
12720 RTUS_RTU_NOT_SYNCHRONIZED
12721 RTUS_EXTERNAL_CLOCK_INOPERABLE
12722 RTUS_EXTERNAL_CLOCK_OPERABLE
12723 RTUS_LOCAL_PRINTER_OFFLINE
12724 RTUS_LOCAL_PRINTER_ONLINE
12725 RTUS_COMMAND_OUTPUTS_BLOCKED
12726 RTUS_COMMAND_OUTPUTS_DEBLOCKED
12727 RTUS_AC_FAILURE
12728 RTUS_AC_OK
12729 RTUS_BATTERY_LOW
12730 RTUS_BATTERY_OK
12731 RTUS_LOCAL_PRINTER_FAILURE
12732 RTUS_LOCAL_PRINTER_OK
12733 RTUS_RWM_BATTERY_FAULTY
12734 RTUS_RWM_BATTERY_OK
12735 RTUS_PLAIN_TEXTS_LOADED
12736 RTUS_PLAIN_TEXTS_NOT_LOADED
12737 RTUS_BACKUP_FOR_PLAIN_TEXTS_FAULTY
12738 RTUS_BACKUP_FOR_PLAIN_TEXTS_OK
12739 RTUS_PROCESS_VOLTAGE_FAULTY
12740 RTUS_PROCESS_VOLTAGE_OK
12741 RTUS_LOCAL_WARNING
12742 RTUS_END_OF_LOCAL_WARNING
12743 RTUS_SUBORDINARE_RTU_IS_INOPERABLE
12744 RTUS_SUBORDINARE_RTU_IS_OPERABLE
12745 RTUS_SUBORDINARE_RTU_IS_OUT_OF_SERVICE
12746 RTUS_SUBORDINARE_RTU_IS_INSERVICE
12747 RTUS_HOST1_IS_DISCONNECTED
12748 RTUS_HOST1_IS_CONNECTED
12749 RTUS_HOST2_IS_DISCONNECTED
12750 RTUS_HOST2_IS_CONNECTED
12751 RTUS_HOST3_IS_DISCONNECTED

97
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

12752 RTUS_HOST3_IS_CONNECTED
12753 RTUS_HOST1_IS_PRIMARY_HOST
12754 RTUS_HOST2_IS_PRIMARY_HOST
12755 RTUS_HOST3_IS_PRIMARY_HOST
12756 RTUS_YOU_ARE_PRIMARY_HOST
12757 RTUS_YOU_ARE_NOT_PRIMARY_HOST
12758 RTUS_SUBORD_RTU_LINE_1_IS_INOPERABLE
12759 RTUS_SUBORD_RTU_LINE_1_IS_OPERABLE
12760 RTUS_SUBORD_RTU_LINE_2_IS_INOPERABLE
12761 RTUS_SUBORD_RTU_LINE_2_IS_OPERABLE
12762 RTUS_SUBORD_RTU_LINE_3_IS_INOPERABLE
12763 RTUS_SUBORD_RTU_LINE_3_IS_OPERABLE
12764 RTUS_SUBORD_RTU_LINE_4_IS_INOPERABLE
12765 RTUS_SUBORD_RTU_LINE_4_IS_OPERABLE
12766 RTUS_SUBORD_RTU_LINE_5_IS_INOPERABLE
12767 RTUS_SUBORD_RTU_LINE_5_IS_OPERABLE
12768 RTUS_SUBORD_RTU_LINE_6_IS_INOPERABLE
12769 RTUS_SUBORD_RTU_LINE_6_IS_OPERABLE
12770 RTUS_SUBORD_RTU_LINE_7_IS_INOPERABLE
12771 RTUS_SUBORD_RTU_LINE_7_IS_OPERABLE
12772 RTUS_SUBORD_RTU_LINE_8_IS_INOPERABLE
12773 RTUS_SUBORD_RTU_LINE_8_IS_OPERABLE
12774 RTUS_SUBORD_RTU_LINE_9_IS_INOPERABLE
12775 RTUS_SUBORD_RTU_LINE_9_IS_OPERABLE
12776 RTUS_SUBORD_RTU_LINE_10_IS_INOPERABLE
12777 RTUS_SUBORD_RTU_LINE_10_IS_OPERABLE
12778 RTUS_SUBORD_RTU_LINE_11_IS_INOPERABLE
12779 RTUS_SUBORD_RTU_LINE_11_IS_OPERABLE
12780 RTUS_SUBORD_RTU_LINE_12_IS_INOPERABLE
12781 RTUS_SUBORD_RTU_LINE_12_IS_OPERABLE
12782 RTUS_SUBORD_RTU_LINE_13_IS_INOPERABLE
12783 RTUS_SUBORD_RTU_LINE_13_IS_OPERABLE
12784 RTUS_SUBORD_RTU_LINE_14_IS_INOPERABLE

98
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

12785 RTUS_SUBORD_RTU_LINE_14_IS_OPERABLE
12786 RTUS_SUBORD_RTU_LINE_15_IS_INOPERABLE
12787 RTUS_SUBORD_RTU_LINE_15_IS_OPERABLE
12788 RTUS_SUBORD_RTU_LINE_16_IS_INOPERABLE
12789 RTUS_SUBORD_RTU_LINE_16_IS_OPERABLE

4.3.12 PCL Device Status Codes (P214)

12801 PCLP_STATION_SUSPENDED
12802 PCLP_REPLY_TIMEOUT
12803 PCLP_STOPPED
12804 PCLP_UNEXPECTED_PR_COMMAND
12805 PCLP_SIGNAL_QUEUE_EMPTY
12806 PCLP_UNEXPECTED_PR_REPLY
12807 PCLP_STATION_LINE_ERROR
12808 PCLC_UNKNOWN_DESTINATION_STATION
12809 PCLC_ATTRIBUTE_IS_WRITE_ONLY
12810 PCLC_COMM_NOT_IMPLEMENTED
12811 PCLC_INTERNET_COMM_NOT_IMPLEMENTED
12812 PCLC_UNKNOWN_STA_ATTRIBUTE
12813 PCLC_NOT_VALID_COMMAND
12814 PCLC_ILLEGAL_COMMAND_CODE
12815 PCLC_MESSAGE_CODING_ERROR
Result of an invalid transaction length.
12816 PCLC_UNKNOWN_PCL_ATTRIBUTE
12817 PCLC_UNKNOWN_DIAGNOSTIC_COUNTER
12818 PCLC_SC_DATA_OVERFLOW
12819 PCLC_INVALID_INDEX_RANGE
12820 PCLC_INVALID_RT_ATTRIBUTE_VALUE
12821 PCLC_ILLEGAL_LENGTH_FOR_GP
12822 PCLC_ONLY_CHARACTER_TYPE_ALLOWED
12823 PCLC_UNDEFINED_EV_CODE
12824 PCLC_NO_MESSAGE_DATA
12825 PCLC_ILLEGAL_LENGTH_FOR_ST

99
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

12826 PCLC_ATTRIBUTE_IS_BROADCAST_ONLY
12827 PCLC_ILLEGAL_BROADCAST_ATTRIBUTE
12828 PCLC_INVALID_PCL_ADDRESS
12829 PCLC_DEVICE_MUST_BE_ALLOCATED
12830 PCLC_UNKNOWN_EVENT_TYPE
Result of an event type which has no handling routine.
12831 PCLC_INTERNAL_BUFFER_FILLING_ERROR
Result of a buffer overflow in the protocol conversion.

4.3.13 SAT Device Status Codes (COMLI slave)

12851 SATC_EVENT_QUEUE_EMPTY
12852 SATC_EVENT_QUEUE_OVERFLOW
12853 SATC_EVENT_QUEUE_CORRUPTED
12854 SATP_STOPPED
12855 SATC_UNKNOWN_ATTRIBUTE
12856 SATC_INVALID_BCD_CODE
12857 SATP_MESSAGE_TRANSLATION_ERROR
12858 SATP_CHARACTER_FORMAT_ERROR
12859 SATC_SCM_MESSAGE_FILLING_ERROR
12860 SATC_EVENT_QUEUE_FULL
12861 SATC_INVALID_EVENT_QUEUE_ADDRESS
12862 SATC_NO_UNACCEPTED_EVENTS
12863 SATC_UNKNOWN_DIAGNOSTIC_COUNTER
12864 SATC_INVALID_RT_ATTRIBUTE_VALUE
12865 SATC_INVALID_REGISTER_ADDRESS
12866 SATC_SC_DATA_OVERFLOW
12867 SATC_INVALID_INDEX_RANGE
12868 SATC_EMPTY_MESSAGE
12869 SATC_INVALID_EVENT_CODE
12870 SATC_THIS_EVENT_QUEUE_SLOT_IS_EMPTY
12871 SATC_IV_NUM_OUT_OF_RANGE
12872 SATC_EV_NUM_OUT_OF_RANGE
12873 SATC_RV_NUM_OUT_OF_RANGE

100
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

4.3.14 BAG Device Status Codes (INSUM master)

12901 BAGP_STOPPED
12902 BAGC_UNKNOWN_BAG_ATTRIBUTE
12903 BAGP_REPLY_TIMEOUT
12904 BAGP_STATION_LINE_ERROR
12905 BAGP_STATION_SUSPENDED
12906 BAGP_CANNOT_GET_POLL_MESSAGE
12907 BAGP_CANNOT_GET_REPLY_BUFFER
12908 BAGP_SYS_TIMEOUT
12909 BAGC_ATTRIBUTE_IS_READ_ONLY
12910 BAGC_ATTRIBUTE_IS_WRITE_ONLY

4.3.15 LCU Device Status Codes (LCU500 master)

12950 LCUC_INVALID_ATTRIBUTE_VALUE
12951 LCUC_INVALID_ATTRIBUTE_INDEX
12952 LCUC_MEMORY_ALLOC_FAILED
12953 LCUC_NO_DATA_AVAILABLE
12954 LCUC_UNEXPECTED_VALUE_TYPE
12955 LCUC_ILLEGAL_ANALOG_OUTPUT_ADDR
12956 LCUC_ILLEGAL_DIGITAL_OUTPUT_ADDR
12957 LCUC_ILLEGAL_OBJECT_TYPE
12958 LCUC_DEVICE_MUST_BE_ALLOCATED
12959 LCUC_REQ_D_DATA_AVAILABLE
12960 LCUC_SC_DATA_OVERFLOW
12961 LCUC_TOO_LONG_D_MES_RECEIVED
12962 LCUC_LCU_ADDRESS_NOT_CONFIGURED
12963 LCUC_UNKNOWN_DIAGNOSTIC_COUNTER
12964 LCUC_REQ_D_FAILED
12965 LCUC_INVALID_INDEX_RANGE
12966 LCUC_UNKNOWN_LCU_ATTRIBUTE
12967 LCUC_SET_D_FAILED
12968 LCUC_DO_DATABASE_NOT_VALID

101
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

12969 LCUC_REQ_S_AFTER_SET_D_FAILED
12970 LCUC_STS_AFTER_SET_D_AVAILABLE
12971 LCUC_RTM_NO_DESTINATION_LINES_AVAILABLE
12972 LCUC_UNEXPECTED_RESPONSE
12973 LCUC_ATTRIBUTE_IS_READ_ONLY
12974 LCUC_ILLEGAL_APPLICATION_FOR_OPERATION
12975 LCUC_ATTRIBUTE_IS_WRITE_ONLY
12976 LCUC_ILLEGAL_BROADCAST_ACTION
12978 LCUC_RTM_MEMORY_ALLOC_FAILED
12979 LCUC_INVALID_RTM_ATTR_ARRAY
12980 LCUC_RTM_ALREADY_ACTIVE
12981 LCUC_RTM_INVALID_LINE_NUMBER
12985 LCUP_UNEXPECTED_DEV_REPLY_MSG_TYPE
12986 LCUP_LOCAL_GI_RESET_FAILED
12987 LCUP_TIMEOUT_WHILE_DOING_LOCAL_SET_GI
12988 LCUP_LOCAL_SET_GI_FAILED
12989 LCUP_DEVICE_SUSPENDED
12990 LCUP_DEVICE_STOPPED
12991 LCUP_DEVICE_STARTED
12992 LCUP_OUT_OF_BUFFERS
12994 LCUP_TIMEOUT_WHILE_WAITING_RESPONSE
12995 LCUP_UNEXPECTED_BC_REPLY
12996 LCUP_BROADCAST_FAILURE
12997 LCUP_EXCEPTION_DETECTED
12998 LCUP_LINE_ERROR_CAUSED_PA_READ_FAIL
12999 LCUP_TIMEOUT_WHILE_DOING_PERIODIC_PA_READ
Timeout when a reply to PA poll is waited.

4.3.16 PAC Device Status Codes

13001 PACP_ALLOCATION_FAILED
13002 PACP_CANNOT_GET_MESSAGE
13003 PACP_NO_PAC_REPLY
13004 PACP_NOT_CORRECT_PAC_REPLY

102
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

13005 PACP_TRANSITION_TO_SUSPENDED
13006 PACP_TRANSITION_TO_STOPPED
13007 PACP_IN_SUSPENDED_STATE
13008 PACP_IN_STOPPED_STATE
13009 PACC_UNKNOWN_PAC5_ATTRIBUTE
13010 PACC_UNKNOWN_DIAGNOSTIC_COUNTER
13011 PACC_SC_DATA_OVERFLOW
13012 PACC_INVALID_INDEX_RANGE
13013 PACC_INVALID_RT_ATTRIBUTE_VALUE
13014 PACC_INVALID_ART_ATTRIBUTE_VALUE
13015 PACC_INVALID_PD_ATTRIBUTE_VALUE
13016 PACC_UNKNOWN_BASE_ADDRESS
13017 PACC_LED_IMAGE_INDEX_OUT_OF_RANGE
13018 PACC_INVALID_KEY_COUNT_ATTRIBUTE_VALUE
13019 PACC_INVALID_LED_COUNT_ATTRIBUTE_VALUE
13020 PACC_DIAGNOSTIC_COUNTER_OVERFLOW
13021 PACC_PAC_MESSAGE_OVERFLOW
13022 PACC_PAC_MESSAGE_READ_ERROR
13023 PACC_INVALID_SCM_KEY_ADDRESS

4.3.17 PRI Device Status Codes (ASCII printer)

13101 PRIP_INVALID_PRINT_COMMAND_SOURCE
13102 PRIC_MESSAGE_BUFFER_OVERFLOW
Contact an ABB representative.
13103 PRIP_PRINTER_OFF_LINE
The printer is in off-line state (the printouts remain in the SYS600 prin-
tout queue). The reason may be, e.g.:
Paper is out
The printer has been switched off manually
The printer is erronous NET sends a system message (address = the MI
attribute of the printer) when the printer is switched offline (value =
13103) or online (value = 0).
13104 PRIP_PRINTER_ON_LINE
13105 PRIP_PRINTER_RESERVED_BY_OTHER_PROCESS
13106 PRIC_UNKNOWN_PRINTER_ATTRIBUTE

103
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

13107 PRIC_RELEASE_CMD_FROM_WRONG_PROCESS
13108 PRIC_INVALID_COLOR_MESSAGE_FORMAT
The reason may be that printer has not been defined as a color printer
in the base system.
13109 PRIC_MESSAGE_FILLING_ERROR
13110 PRIC_PRINTER_IN_USE
The attribute cannot be changed while the printer is in use.
13111 PRIC_INVALID_PT_ATTRIBUTE_VALUE
13112 PRIC_INVALID_PE_ATTRIBUTE_VALUE
13113 PRIP_NO_MORE_ITEMS_IN_BUFFER
13115 PRIC_INVALID_INDEX_RANGE
13116 PRIC_EMPTY_MESSAGE
The reason may be that printout format has not been defined or that there
is no format picture.
13117 PRIC_SC_DATA_OVERFLOW
13118 PRIC_NO_MORE_LINE_PAIRS_IN_BUFFER
13119 PRIP_NO_PRINTER_CONNECTION
13120 PRIP_PRINTER_OFF_LINE_AND_NO_CONNECTION
13121 PRIP_PRINTER_NOT_IN_USE
13122 PRIC_INVALID_PIXEL_PATTERN
13123 PRIC_MEMORY_ALLOCATION_FAILED
13124 PRIP_PRINTER_STOPPED
13125 PRIP_PRINTER_NOT_READY
13126 PRIC_PRINTER_OFF_LINE_STATE_CANCELLED

4.3.18 SPA Device Status Codes (SPA master)

13201 SPAC_SC_DATA_OVERFLOW
13202 SPAC_TOO_LONG_REPLY_RECEIVED
13203 SPAC_SPA_ADDRESS_NOT_CONFIGURED
13204 SPAC_DEVICE_MUST_BE_ALLOCATED
13205 SPAC_UNKNOWN_DIAGNOSTIC_COUNTER
13206 SPAC_INVALID_INDEX_RANGE
13207 SPAC_INVALID_RT_ATTRIBUTE_VALUE
13208 SPAC_UNKNOWN_SPA_ATTRIBUTE

104
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

13209 SPAC_ILLEGAL_APPLICATION_FOR_OPERATION
13210 SPAC_ATTRIBUTE_IS_WRITE_ONLY
13211 SPAC_ILLEGAL_BROADCAST_ACTION
13212 SPAC_UNEXPECTED_RESPONSE
13213 SPAC_INVALID_ATTRIBUTE_VALUE
13214 SPAC_CHAR_TYPE_EXPECTED
13215 SPAC_INTERNAL_ERROR
13216 SPAC_INVALID_POINT_DEFINITION
13217 SPAC_DATABASE_UPDATE_COMPLETED
13218 SPAC_TOO_MANY_ARGUMENTS
13219 SPAC_ARGUMENT_EXPECTED
13220 SPAC_UNABLE_TO_ALLOCATE_MEMORY
13221 SPAC_POINT_DEFINITION_NOT_FOUND
13222 SPAC_NO_ACKNOWLEDGE_RESPONSE
13223 SPAC_UNEXPECTED_VALUE_TYPE
13224 SPAC_ILLEGAL_OBJECT_TYPE
13225 SPAC_ONLY_WRITE_IS_POSSIBLE
13226 SPAC_NO_ACKNOWLEDGE_REPLY
13227 SPAC_EVENT_DATA_DISCREPANCY_DETECTED
13228 SPAC_NO_SM_REPLY_AVAILABLE
13229 SPAC_OUT_OF_BUFFERS
13230 SPAC_SM_ATTR_ACCESS_VIOLATION
13231 SPAC_PARAMETER_TRANSFER_RESERVED
13232 SPAC_PARAMETER_TRANSFER_RELEASE_DENIED
13233 SPAC_POINT_ALREADY_EXISTS
13234 SPAC_NV_INDEX_ALREADY_EXISTS
13235 SPAC_NV_POLL_FAILED
13236 SPAC_TOO_MANY_POINTS_IN_DEFINITION
Too many analog input or counter input points configured to the same
poll.
13251 SPAP_DEVICE_SUSPENDED
13252 SPAP_DEVICE_STOPPED
13253 SPAP_DEVICE_STARTED
13254 SPAP_OUT_OF_BUFFERS

105
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

13255 SPAP_TIMEOUT_WHILE_WAITING_RESPONSE
13256 SPAP_UNEXPECTED_BC_REPLY
13257 SPAP_BROADCAST_FAILURE
13258 SPAP_DATABASE_UPDATE_COMPLETED
13259 SPAP_INTERNAL_TIMEOUT
This error is returned by the External OPC DA client when a command
is issued and the OPC server does not inform the result of the OPC write
operation within the time specified by parameter ReadWriteTimeout.
Possible reason for this is that the mentioned timeout is too short or the
OPC server has entered an erroneous state.
13260 SPAP_ATTRIBUTE_IS_WAITING_FOR_READ
This error is returned by the External OPC DA client when a subsequent
write command has been issued to a custom STA attribute which is
connected to an item having an exclusive write access. The attribute
should be read before a new write is accepted.

4.3.19 BPO (Bit Pad One) Device Status Codes

13302 BPOC_UNKNOWN_BIT_PAD_ONE_ATTRIBUTE
13303 BPOC_UNKNOWN_MONITOR_NUMBER
13304 BPOC_INVALID_MO_ATTRIBUTE_VALUE
13305 BPOC_INVALID_INDEX_RANGE
13306 BPOC_INVALID_BT_ATTRIBUTE_VALUE

4.3.20 REX Device Status Codes (LON)

13272 REXP_DEVICE_STOPPED
13273 REXP_DEVICE_STARTED
13274 REXP_DEVICE_HALTED
13275 REXP_OUT_OF_BUFFERS
13276 REXP_TIMEOUT_WHILE_WAITING_RESPONSE
13277 REXP_DEVICE_CONNECTING
13278 REXP_DISCONN_IND_RECEIVED
13279 REXP_CONN_CON_RECEIVED
13280 REXP_EVENT_SESSION_REJECTED
13281 REXP_EVENT_SESSION_SETUP_TIMEOUT

106
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

13282 REXP_RUNNING_MODE_OPERATION_CONFLICT
13283 REXP_DEVICE_WAITING_GO_COMMANDS
When session setup command has been successfully executed, the REX
device in PC-NET sends this status code to indicate that it is ready to
receive the General Object Handling Commands (REX GO attribute)
from the SYS600 application.
13284 REXP_SETUP_SESSION_REJECTED
If the device sends a negative response to the General Object Handling
command, the SCIL command will get this status.
13285 REXP_SETUP_SESSION_TIMEOUT
If the device sends a negative response to the General Object Handling
command, the SCIL command will get this status.
13311 REXC_SC_DATA_OVERFLOW
13312 REXC_LON_ADDRESS_NOT_CONFIGURED
13313 REXC_DEVICE_MUST_BE_ALLOCATED
13314 REXC_UNKNOWN_DIAGNOSTIC_COUNTER
13315 REXC_INVALID_INDEX_RANGE
13316 REXC_ILLEGAL_APPLICATION_FOR_OPERATION
13317 REXC_ATTRIBUTE_IS_WRITE_ONLY
13318 REXC_INVALID_ATTRIBUTE_VALUE
13319 REXC_CHAR_TYPE_EXPECTED
13320 REXC_INTERNAL_ERROR
13321 REXC_INVALID_POINT_DEFINITION
13322 REXC_TOO_MANY_ARGUMENTS
13323 REXC_ARGUMENT_EXPECTED
13324 REXC_UNABLE_TO_ALLOCATE_MEMORY
13325 REXC_POINT_DEFINITION_NOT_FOUND
13326 REXC_NO_ACKNOWLEDGE_RESPONSE
13327 REXC_UNEXPECTED_VALUE_TYPE
13328 REXC_ILLEGAL_OBJECT_TYPE
13329 REXC_ONLY_WRITE_IS_POSSIBLE
13330 REXC_NO_ACKNOWLEDGE_REPLY
13331 REXC_NO_SM_REPLY_AVAILABLE
13332 REXC_OUT_OF_BUFFERS
13333 REXC_SM_ATTR_ACCESS_VIOLATION

107
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

13334 REXC_PARAMETER_TRANSFER_RESERVED
13335 REXC_PARAMETER_TRANSFER_RELEASE_DENIED
13336 REXC_ILLEGAL_BROADCAST_ACTION
13337 REXC_ILLEGAL_IEC_EVENT_RECEIVED
13338 REXC_GI_ACTIVATION_CONF_RECEIVED
13339 REXC_GI_TERMINATION_RECEIVED
13340 REXC_UNABLE_TO_CONVERT_FROM_SC_COMMAND
13341 REXC_INVALID_RT_ATTRIBUTE_VALUE
13342 REXC_UNKNOWN_LON_ATTRIBUTE
13345 REXC_FT_CHECKSUM_ERROR
Checksum error in download or upload procedure.
13346 REXC_FT_DEVICE_MEMORY_ERROR
Unsuccessful memory allocation in device.
13347 REXC_FT_COMMUNICATION_SERVICE_ERROR
13348 REXC_FT_FILE_OR_DIR_ID_ERROR
File or directory with given ID does not exist.
13349 REXC_FT_DEVICE_UNABLE_TO_PERFORM_COMMAND
The requested file from device could not uploaded or deleted. Negative
response from device.
13350 REXC_FT_COMMUNICATION_TIMEOUT
13351 REXC_FT_SIMULTANEOUS_SERVICE_NOT_ALLOWED
13352 REXC_FT_CANCELLED_BY_DEVICE
13353 REXC_FT_DIRECTORY_ENTRY_CREATED_BY_DEVICE
13354 REXC_FT_FILE_OR_DIRECTORY_DOES_NOT_EXIST
13355 REXC_MAX_NACK_LIMIT_EXCEEDED
13371 REXP_DEVICE_SUSPENDED

4.3.21 LMK Device Status Codes (LON)

13401 LMKP_DEVICE_SUSPENDED
13402 LMKP_DEVICE_STARTED
13403 LMKP_DEVICE_STOPPED
13404 LMKP_DEVICE_ALREADY_STARTED
13405 LMKP_DEVICE_ALREADY_STOPPED
13406 LMKP_OUT_OF_MESSAGE_BUFFERS

108
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

13407 LMKP_TIMEOUT_WHILE_WAITING_COMPLETION
13408 LMKP_TIMEOUT_WHILE_WAITING_REPLY
13409 LMKP_NV_POLL_FAILED
13421 LMKC_ATTRIBUTE_IS_WRITE_ONLY
13422 LMKC_ILLEGAL_APPLICATION_FOR_OPERATION
13423 LMKC_ONLY_WRITE_IS_POSSIBLE
13424 LMKC_NO_POINT_FOR_THIS_SYS_INDEX_FOUND
13425 LMKC_POINT_NOT_AN_OUTPUT
13426 LMKC_DATA_OUT_OF_RANGE_FOR_OUTPUT_TYPE
13427 LMKC_WRONG_DATA_TYPE_FOR_OUTPUT_TYPE
13428 LMKC_UNKNOWN_LMK_ATTRIBUTE
13429 LMKC_INTERNAL_ERROR
13430 LMKC_SC_DATA_OVERFLOW
13431 LMKC_NO_LM_REPLY_AVAILABLE
13432 LMKC_INVALID_RT_ATTRIBUTE_VALUE
13433 LMKC_ARGUMENT_EXPECTED
13434 LMKC_INVALID_INDEX_RANGE
13435 LMKC_INVALID_ATTRIBUTE_VALUE
13436 LMKC_PARAMETER_TRANSFER_RESERVED
13437 LMKC_PARAMETER_TRANSFER_RELEASE_DENIED
13438 LMKC_UNKNOWN_DIAGNOSTIC_COUNTER
13439 LMKC_DEVICE_MUST_BE_ALLOCATED
13440 LMKC_UNABLE_TO_ALLOCATE_MEMORY
13441 LMKC_TOO_MANY_ARGUMENTS
13442 LMKC_POINT_ALREADY_EXISTS
13443 LMKC_NV_INDEX_ALREADY_EXISTS
13444 LMKC_POINT_DEFINITION_NOT_FOUND

4.3.22 SPI device status codes (RP570 slave)

13450 SPIC_INVALID_INDEX_RANGE
13451 SPIC_ILLEGAL_ATTRIBUTE_VALUE
13453 SPIC_UNKNOWN_DIAGNOSTIC_COUNTER

109
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

13454 SPIC_SC_DATA_OVERFLOW
13455 SPIC_UNKNOWN_SPI_ATTRIBUTE
13456 SPIC_TEV_BUFFER_OVERFLOW
13457 SPIC_UNKNOWN_FNC_RECEIVED
13458 SPIC_INVALID_FNC_RECEIVED
13459 SPIC_FCOM_COLDSTART_RECEIVED
13460 SPIC_UNKNOWN_FCOM_RECEIVED
13461 SPIC_ILLEGAL_FCOM_RECEIVED
13462 SPIC_CBXC_RECEIVED
13463 SPIC_IHC_RECEIVED
13464 SPIC_IHC_FAILED
13465 SPIC_EXC_FAILED
13466 SPIC_ERMI_BUFFER_OVERFLOW
13467 SPIC_PREV_PC_VALUE_NOT_YET_REPORTED
13468 SPIC_PULSECOUNTER_IS_BLOCKED
13469 SPIC_ARGUMENT_EXPECTED
13470 SPIC_TOO_MANY_ARGUMENTS
13471 SPIC_NOT_ACTIVE_OR_NO_FTAB_LOADED
13472 SPIC_FCOM_ACTIVATE_RECEIVED
13473 SPIC_FCOM_DEACTIVATE_RECEIVED
13474 SPIC_UNKNOWN_FTAB_RECEIVED
13475 SPIC_INVALID_FTAB
13476 SPIC_FTAB_NOT_IMPLEMENTED
13477 SPIC_POINT_NOT_INITIALIZED_WHILE_DI_0
13478 SPIC_ERMX_NOT_RECORDED
13479 SPIC_INVALID_FUNCTION_CODE
13480 SPIP_CBXC_RECEIVED
13481 SPIP_IHC_RECEIVED
13482 SPIP_EXC_FAILED
13483 SPIP_ILLEGAL_FNC_RECEIVED
13484 SPIP_COMMUNICATION_WITH_CS_LOST
13485 SPIP_COMMUNICATION_WITH_CS_ESTABLISHED
13486 SPIP_UNIMPLEMENTED_FNC_RECEIVED

110
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

13487 SPIP_UNABLE_TO_ALLOCATE_MEMORY
13488 SPIP_COMMANDS_BLOCKED_FROM_MASTER
13489 SPIP_STATION_STOPPED
SPI station object is in stopped state.
13490 SPIC_NOT_IN_EXCLUSIVE_COMMAND_MODE
13491 SPIC_INVALID_TEV_NUMBER
13492 SPIC_TDR_QUEUE_FULL
13493 SPIC_EXCLUSIVE_COMMAND_TIMEOUT
13494 SPIC_INVALID_TDR_LENGTH
13495 SPIC_INVALID_TSTA_ID
13496 SPIC_NO_ACTIVE_COMMAND
This status is returned when the application writes to the SPI station at-
tribute CS and no active select or execute command is waiting for status.
It is possible that the timeout defined by attribute AT has occurred.
13499 SPIP_INITIATE_DATABASE_REINITIALIZATION
This status code is only used by Modbus slave application.

4.3.23 MON (Monitor) Device Status Codes

13501 MONC_INVALID_MONITOR_ADDRESS
13502 MONC_MONITOR_IN_USE
13503 MONC_UNKNOWN_MONITOR_ATTRIBUTE
13504 MONC_INVALID_INDEX_RANGE

4.3.24 ADE Device Status Codes (General ASCII)

13551 ADEC_INVALID_INDEX_RANGE
13552 ADEC_SC_DATA_OVERFLOW
13553 ADEC_UNKNOWN_ADEMCO_ATTRIBUTE

4.3.25 PCO Device Status Codes (RCOM master)

13601 PCOP_DEVICE_STARTED
13602 PCOP_TIMEOUT_WHILE_WAITING_RESPONSE
13603 PCOP_DEVICE_SUSPENDED

111
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

13604 PCOP_DEVICE_RESPONDING_AGAIN
13605 PCOP_DEVICE_RESTARTED_QUEUE_EMPTY
13606 PCOP_DEVICE_STOPPED
13621 PCOC_INVALID_INDEX_RANGE
13622 PCOC_SC_DATA_OVERFLOW
13623 PCOC_UNKNOWN_RCOM_ATTRIBUTE
13624 PCOC_INVALID_ATTRIBUTE_VALUE
13625 PCOC_PLC_PROGRAM_NOT_RESPONDING
13626 PCOC_ILLEGAL_APPLICATION_FOR_OPERATION
13627 PCOC_ATTRIBUTE_IS_WRITE_ONLY
13628 PCOC_FCOM_NUMBER_NOT_USED
13629 PCOC_INVALID_FCOM_NUMBER
13630 PCOC_UNEXPECTED_RESPONSE
13631 PCOC_SYSTEM_MESSAGE_RECEIVED
13632 PCOC_INVALID_RT_ATTRIBUTE_VALUE
13633 PCOC_RCOM_UNIT_NOT_NORMALIZED
13634 PCOC_NOT_VALID_FOR_BROADCAST
13635 PCOC_OUT_OF_BUFFERS
13636 PCOC_SUBSTATION_PLC_STOPPED

4.3.26 WES Device Status Codes (Westinghouse F4F slave)

13651 WESC_TT_QUEUE_EMPTY
13652 WESC_TT_QUEUE_OVERFLOW
13653 WESC_TT_QUEUE_CORRUPTED
13654 WESP_STOPPED
13655 WESC_UNKNOWN_ATTRIBUTE
13656 WESC_INVALID_CRC_CODE
13657 WESP_MESSAGE_TRANSLATION_ERROR
13658 WESP_CHARACTER_FORMAT_ERROR
13659 WESC_SCM_MESSAGE_FILLING_ERROR
13660 WESC_EVENT_QUEUE_FULL
13661 WESC_INVALID_EVENT_QUEUE_ADDRESS

112
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

13662 WESC_NO_UNACCEPTED_EVENTS
13663 WESC_UNKNOWN_DIAGNOSTIC_COUNTER
13664 WESC_INVALID_RT_ATTRIBUTE_VALUE
13665 WESC_INVALID_REGISTER_ADDRESS
13666 WESC_SC_DATA_OVERFLOW
13667 WESC_INVALID_INDEX_RANGE
13668 WESC_EMPTY_MESSAGE
13669 WESC_INVALID_EVENT_CODE
13670 WESC_THIS_EVENT_QUEUE_SLOT_IS_EMPTY
13671 WESC_ID_NUM_OUT_OF_RANGE
13672 WESC_AV_NUM_OUT_OF_RANGE
13673 WESC_TT_NUM_OUT_OF_RANGE
13674 WESC_TT_QUEUE_FULL
13675 WESC_NOT_IMPLEMENTED
13676 WESC_INVALID_FT_VECTOR_LENGTH
13677 WESC_INVALID_CATEGORY_NUMBER
13678 WESC_INVALID_GROUP_NUMBER
13679 WESC_INVALID_BINARY_VALUE

4.3.27 ATR Device Status Codes (Alpha/IEC1107)

13751 ATRP_SESSION_BEGIN
13752 ATRP_NOT_ALLOWED_WHILE_COMMUNICATING
13753 ATRP_SESSION_END
13754 ATRP_SESSION_ABORTED
13755 ATRP_SESSION_STOPPED
13756 ATRC_UNKNOWN_ATTRIBUTE
13757 ATRC_SESSION_FIFO_FULL
13758 ATRC_TOO_LONG_MESSAGE
13759 ATRC_STATION_NOT_IN_USE
13760 ATRC_LINE_NOT_IN_USE
13761 ATRC_ILLEGAL_ATTRIBUTE_VALUE
13762 ATRC_LINE_RESERVED

113
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4.3.28 PLC Device Status Codes (General PLC/Modbus)

13800 PLCP_IN_INITIALIZE_DB_STATE
13801 PLCP_DEVICE_SUSPENDED
13802 PLCP_STOPPED
13803 PLCP_STARTTED
13804 PLCC_MESSAGE_FILLING_ERROR
13805 PLCC_INVALID_OBJECT_TYPE
13806 PLCC_INVALID_ADDRESS
13807 PLCC_INVALID_DATA
13808 PLCC_INVALID_OBJECT_INDEX
13809 PLCC_NOT_IMPLENTED_FUNCTION
13810 PLCC_NOT_EXPECTED_FUNCTION_CODE_FROM_PLC
13811 PLCC_ILLEGAL_PLC_FUNCTION
13812 PLCC_ILLEGAL_PLC_DATA_ADDRESS
13813 PLCC_ILLEGAL_PLC_DATA_VALUE
13814 PLCC_SLAVE_DEVICE_FAILURE
13815 PLCC_ACKNOWLEDGE
13816 PLCC_SLAVE_DEVICE_BUSY
13817 PLCC_NEGATIVE_ACKNOWLEDGE
13818 PLCC_MEMORY_PARITY_ERROR
13819 PLCC_UNKNOWN_DIAGNOSTIC_COUNTER
13820 PLCC_INVALID_TOPIC_NUMBER
13821 PLCC_INVALID_OBJECT_ADDRESS
13822 PLCC_INVALID_OBJECT_FORMAT
13823 PLCC_SC_DATA_OVERFLOW
13824 PLCC_INVALID_INDEX_RANGE
13825 PLCC_UNKNOWN_ATTRIBUTE
13826 PLCC_LOCAL_RESPONSE
13827 PLCP_TIMEOUT_WHILE_WAITING_RESPONSE
13828 PLCP_EVENT_BUFFER_OK
13829 PLCP_EVENT_BUFFER_OVERFLOW
13830 PLCP_EVENT_BUFFER_ERROR
13831 PLCC_UNKNOWN_FUNCTION

114
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

13832 PLCC_NO_ADDITIONAL_DATA_AVAILABLE
Station attribute AD does not contain any data.
13833 PLCC_INVALID_ATTRIBUTE_VALUE
Returned to SCIL if the entered value in attribute setting is invalid.
13834 PLCC_INTERNAL_ERROR
Internal software error.
13835 PLCC_TOO_LONG_REPLY_RECEIVED
The response from the device was too long for an attribute read.
13836 PLCC_MM_ATTRIBUTE_ACCESS_VIOLATION
The MM attribute must be read from the same application it was written.
13837 PLCC_NO_MM_REPLY_AVAILABLE
No saved reply from the device exists.
13838 PLCC_INVALID_POLLING_INTERVAL
The entered polling interval value is out of allowed range.
13839 PLCC_GATEWAY_PATH_UNAVAILABLE
This error code is returned when the IED responds with exception 10
(Gateway paths not available).
13840 PLCC_GATEWAY_TARGET_FAILED_TO_RESPOND
This error code is returned when the IED responds with exception 11
(The targeted device failed to respond).

4.3.29 ICC Device Status Codes (IEC60870-5-101/103/104)

13851 ICCC_INVALID_ATTRIBUTE_VALUE
The value set to an attribute of a IEC station is incorrect, e.g. one of the
elements of the vector written to the SD attribute is out of range.
13852 ICCC_INVALID_INDEX_RANGE
The index range used when accessing an attribute of an IEC station is
incorrect.
13853 ICCC_INVALID_ATTRIBUTE
The STA object attribute used is not valid for IEC 60870-5-101 slave
protocol.
13854 ICCC_ASDU_TABLE_NOT_CREATED
Internal software error.
13855 ICCC_UNKNOWN_ASDU_NAME
The name of the ASDU written to the SD or EV attribute is not supported.
13856 ICCC_ASDU_QUEUE_FULL
No more events can be written to one of the queues by using the SD or
EV attribute since the queue is full.

115
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

13857 ICCC_MESSAGE_BUFFER_FULL
Internal software error. The value of ML attribute may be too small.
13858 ICCC_MESSAGE_FILLING_ERROR
Internal software error. The value of ML attribute may be too small.
13859 ICCC_UNKNOWN_ASDU
The number of the ASDU written to the SD or EV attribute is not sup-
ported.
13860 ICCC_NO_ACTIVE_COMMAND
There is not a preceding command with the address given when confirm-
ing a command using the CF attribute. Either the address is incorrect or
the command has not been received.
13861 ICCC_INVALID_QUEUE_NUMBER
The index of the SD or EV attribute is incorrect.
13862 ICCC_SC_DATA_OVERFLOW
Internal software error.
13863 ICCC_DEVICE_SUSPENDED
The IEC station is in suspended state. The reason for this could be that
the link is not properly established (e.g. incorrect cable wiring) or the
master station does not respond.
13864 ICCC_MESSAGE_SENDING_ERROR
Internal software error. This may be a result of problem in wiring or
hardware.
13865 ICCC_REMOTE_DEVICE_REPLIES_WITH_NACK
The master did not accept the message but responded with negative ac-
knowledgement instead. Not used in unbalanced mode.
13866 ICCC_LINK_NOT_READY
A message is sent to a line with a non-established communication.
13867 ICCC_CONFIRMATION_OF_CMD_IS_NOT_READY
13868 ICCC_OUT_OF_BUFFERS
Internal software error. Operation could not be completed since the
buffer pool has ran out of buffers.
13869 ICCC_DONT_REPLY
Internal software error.
13870 ICCC_CONFIRMATION_TIMEOUT
An activation confirmation to a command was not received from the
IEC slave in the time defined by the RT attribute.
13871 ICCC_NEGATIVE_CONFIRMATION
The activation confirmation received from the IEC slave was negative,
i.e. the command failed.
13872 ICCC_DEVICE_STOPPED
The station has been set out of use using the IU attribute.

116
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

13873 ICCC_NO_ADDRESS_IN_ACP
Internal software error.
13874 ICCC_UNEXPECTED_OV_VALUE
13875 ICCC_UNEXPECTED_TYPE_IN_ACP
Internal software error.
13876 ICCC_UNSUPPORTED_COMMAND_TYPE
The value of the TY attribute written to an output process object is not
a type id of a supported ASDU.
13877 ICCC_OV_VALUE_NOT_FOUND
OV attribute is missing from the list written to an output process object.
13878 ICCC_OG_VALUE_NOT_FOUND
13879 ICCC_QL_VALUE_NOT_FOUND
QL attribute is missing from the list written to an output process object.
13880 ICCC_TY_VALUE_NOT_FOUND
TY attribute is missing from the list written to an output process object.
13881 ICCC_DEVICE_STARTED
The station has been set to use by using the IU attribute.
13882 ICCC_NO_WRITE_WHEN_LINE_IN_USE
The attribute writing is not allowed when the line is in use.
13883 ICCC_FILETRANSFER_ALREADY_IN_PROGRESS
File transfer session is already active and another session is tried to ini-
tiate from SCIL.
13884 ICCC_FILETRANSFER_FILELIMIT_EXCEEDED
Maximum amount of defined files or subdirectories has been exceeded.
13885 ICCC_FILETRANSFER_SERVICE_NOT_AVAILABLE
Internal allocation of the file transfer system has failed.
13886 ICCC_FILETRANSFER_FILE_ALREADY_DEFINED
Given file is already defined.
13887 ICCC_FILETRANSFER_NO_SUCH_FILE
13888 ICCC_BROADCAST_NOT_SUPPORTED
Sending of the broadcast time synchronization is not possible in IEC104 .
13889 ICCC_DATA_WRITE_STATUS_CHANGES_TO_OK
The status changed from error status to OK_STATUS, should be inter-
preted as OK_STATUS. This status is returned only if the data write
errors to a slave station are filtered by using the attribute SF.

117
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4.3.30 DNP Device Status Codes (DNP 3.0)

13901 DNPC_INVALID_ATTRIBUTE_VALUE
The value set to an attribute of a DNP station is out of range.
13902 DNPC_INVALID_INDEX_RANGE
The index range used when accessing an attribute of a DNP station is
incorrect.
13903 DNPC_INVALID_ATTRIBUTE
The STA object attribute used is not valid for DNP V3.00 slave protocol.
13904 DNPC_EVENT_QUEUE_FULL
No more events can be written to one of the unsolicited message queues
using the EV attribute since the queue is full.
13905 DNPC_MESSAGE_BUFFER_FULL
Internal software error.
13906 DNPC_MESSAGE_FILLING_ERROR
Internal software error.
13907 DNPC_UNKNOWN_OBJECT_TYPE
The data object type used with the SD or EV attributes is not supported.
13909 DNPC_SC_DATA_OVERFLOW
Internal software error.
13910 DNPC_DEVICE_SUSPENDED
The DNP station is in suspended state. The reason for this could be that
the link is not properly established (e.g. incorrect cable wiring) or the
master station does not respond.
13911 DNPC_MESSAGE_SENDING_ERROR
Internal software error. Device status is set to this value if the message
handling has failed. The sending may fail due to e.g. an error in the
physical communication link.
13912 DNPC_REMOTE_DEVICE_REPLIES_WITH_NACK
The DNP slave station responses with a negative acknowledgement.
13913 DNPC_LINE_NOT_READY
A command is sent to a line with a non-established communication.
13914 DNPC_OUT_OF_BUFFERS
Internal software error.
13915 DNPC_RESPONSE_TIMEOUT
13916 DNPC_CONFIRMATION_TIMEOUT
The time determined by the RT attribute (first APDU) or RT+AT attrib-
utes (last APDU) has expired while waiting for a response from the
slave.
13918 DNPC_DEVICE_STOPPED
The station has been set out of use using the IU attribute.

118
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

13919 DNPC_DEVICE_STARTED
The station has been set to use using the IU attribute.
13920 DNPC_UNEXPECTED_OV_VALUE
The value set to the OV attribute of an output process object is not valid.
13921 DNPC_ERROR_IN_ACP
Internal software error.
13924 DNPC-NET_BUFFER_ERROR
Internal software error.
13925 DNPC_NO_ACTIVE_COMMAND
There is not a preceding command with the address given when confirm-
ing a command using the CF attribute. Either the address is incorrect or
the command has not been received.
13926 DNPC_INTERNAL_ERROR
Internal software error.
13927 DNPC_LINK_LINE_DOES_NOT_EXIST
The line to which the DNP station is created is incorrect (not a DNP
line).
13928 DNPC_NOT_ENOUGH_ITEMS
The vector, that is written to SD or EV attribute does not have correct
number of elements.
13929 DNPC_INVALID_EVENT_CLASS
The index of the SD or EV attribute is incorrect.
13930 DNPC_POINT_NOT_INITIALIZED_WHILE_DI_0
Data is written to a data point which has not been initialised using the
SD attribute while the DI attribute is set to 0.
13931 DNPC_UNKNOWN_CONTROL_BLOCK
The CODE item of a received control block message is unknown.
13934 DNPC_UNEXPECTED_TYPE_IN_SUBITEM
Internal software error.
13935 DNPC_UNSUPPORTED_OV_TYPE
The data type of the OV subitem is not supported by the requested
function.
13936 DNPC_APDU_SCAN_ERROR
Internal software error.
13937 DNPC_UNKNOWN_VARIATION
The variation received from the slave is not supported.
13938 DNPC_ACP_MESSAGE_FULL
Internal use only.
13939 DNPC_UNKNOWN_QUALIFIER
Internal use only.

119
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

13940 DNPC_ALLOCATION_FAILED
Internal software error.
13941 DNPC_BACKGROUND_POLL_ACTIVE
A command was issued while the DNP master station was waiting for
a response to a data poll request.
13942 DNPC_PREVIOUS_CMD_STILL_ACTIVE
A command was issued while the DNP master station was waiting for
a response to the previous command.
13943 DNPC_POLL_NOT_DEFINED
A poll has not been defined for the index used when reading the SD at-
tribute.
13944 DNPC_ANOTHER_COMMAND_ALREADY_PENDING
This status is returned when one command from SCIL is already waiting
to be sent (MT-timer is on) and user issues a new command from SCIL.
This situation is possible only when parallel execution of SCIL proced-
ures is possible.
13945 DNPC_BROADCAST_NOT_ALLOWED
This status is returned if a broadcast operation is requested from SCIL
and it is not possible with the requested command.
13946 DNPC_UNKNOWN_USER
The given user number or name has not been defined for the station in
keystorage file 
13947 DNPC_ATTRIBUTE_SETTING_NOT_POSSIBLE
The setting of the attribute is not possible.
13948 DNPC_USER_AUTHENTICATION_NOT_INITIALIZED
The user which has issued the command has not been authenticated by
the remote device. The reason for this could be a mismatch in the update
keys, mac algorithms or in the key lengths.
13949 DNPC_ATTRIBUTE_SETTING_PROHIBITED
The setting of the attribute is prohibited by a setting in the keystorage
file. Contact the administrator of the keystorage file. 
13950 DNPC_NO_KEYSTORAGE_FILE_DEFINEDThe
keystorage file has not been defined with the KS attribute of the NET
node. 
13951 DNPC_NO_MATCHING_ID_IN_KEYSTORAGE
The ZT attribute of the STA object does not match with any of the station
id values in the keystorage file.
13952 DNPC_NO_KEYSTORAGE_ID_DEFINED
The ZT attribute has not been defined.

120
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

13953 DNPC_DATA_WRITE_STATUS_CHANGES_TO_OK
The status changed from error status to OK_STATUS, should be inter-
preted as OK_STATUS. This status is returned only if the data write
errors to a slave station are filtered by using the attribute SF.
13954 DNPC_TOO_MANY_PARAMETERS
An attribute reference from SCIL contains too many parameters.

4.3.31 NET Network Layer Status Codes

14001 NETW_APPLICATION_PROCESS_DOES_NOT_EXIST
14002 NETW_ATTRIBUTE_ACCESS_RIGHT_VIOLATION
The user has tried to set an attribute that can be read only, or read an at-
tribute that can be set only.
14003 NETW_ATTRIBUTE_INDEX_RANGE_ERROR
14004 NETW_DESTINATION_DEVICE_IN_USE
While a device is in use (IU = 1) it cannot be deleted on-line.
14005 NETW_DESTINATION_DEVICE_NOT_IN_USE
While the device is out of use, it is not possible to communicate with it.
14006 NETW_DESTINATION_LINE_NOT_IN_USE
14007 NETW_INVALID_AB_MESSAGE_LENGTH
14009 NETW_INVALID_SC_FUNCTION_VALUE
14010 NETW_INVALID_SC_FUNCTION_VALUE_FOR_REPLY
14012 NETW_LINK_PROCESS_DOES_NOT_EXIST
14013 NETW_LOGICAL_NAME_TRANSLATION_ERROR
14014 NETW_LOGICAL_NAME_WITHOUT_TRANSLATION
14015 NETW_NET_PROCESS_DOES_NOT_EXIST
14016 NETW_UNKNOWN_DESTINATION_DEVICE
14017 NETW_UNKNOWN_DESTINATION_LINE
14018 NETW_UNKNOWN_DEVICE_ATTRIBUTE
14019 NETW_UNKNOWN_LOGICAL_NAME
14020 NETW_UNKNOWN_PHYSICAL_NAME
14024 NETW_DEVICE_DOES_NOT_EXIST
14025 NETW_DEVICE_IN_USE_CANT_BE_DELETED
14026 NETW_ERROR_IN_MESSAGE_DATA_STRUCTURE
14029 NETW_INDEX_RANGE_NOT_ALLOWED

121
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

14030 NETW_LINE_MUST_BE_STOPPED_FIRST
The operation demands that the line is taken out of use first (IU=0).
14031 NETW_MAX_PHYSICAL_BPO_NUMBER_EXCEEDED
14032 NETW_MAX_PHYSICAL_SID_NUMBER_EXCEEDED
14033 NETW_MAX_PHYSICAL_PAC_NUMBER_EXCEEDED
14034 NETW_MAX_PHYSICAL_SAT_NUMBER_EXCEEDED
14037 NETW_UNACCEPTABLE_CHARACTER_ITEM
14038 NETW_UNACCEPTABLE_LOGICAL_NAME_FORMAT
14040 NETW_MAX_PHYSICAL_MON_NUMBER_EXCEEDED
14041 NETW_MAX_PHYSICAL_SYS_NUMBER_EXCEEDED
14042 NETW_MAX_PHYSICAL_STA_NUMBER_EXCEEDED
14043 NETW_MAX_PHYSICAL_PRI_NUMBER_EXCEEDED
14044 NETW_INVALID_STATION_ADDRESS
14045 NETW_MESSAGE_BUFFER_OVERFLOW
14046 NETW_LINE_NUMBER_OUT_OF_RANGE
14047 NETW_LINE_DOES_NOT_EXIST
14048 NETW_DEVICE_TYPES_CANT_BE_MIXED
14049 NETW_ROUTING_INFO_MISSING
14050 NETW_UNKNOWN_SOURCE_DEVICE
14051 NETW_SOURCE_DEVICE_NOT_IN_USE
14052 NETW_WRONG_DESTINATION_TYPE
14053 NETW_UNWAITED_REPLY
14054 NETW_INVALID_DEVICE_TYPE
14055 NETW_OUT_OF_MEMORY
The free memory in NET is not enough for the execution of the desired
operation.
14056 NETW_FUNCTION_NOT_IMPLEMENTED
14057 NETW_INVALID_LOGICAL_NAME_TRANSLATION
14058 NETW_UNKNOWN_LOGICAL_NAME_TRANSLATION
14059 NETW_INVALID_LOGICAL_NAME
14060 NETW_INVALID_LOGICAL_NAME_RANGE
14061 NETW_NAME_IS_PHYSICAL
14062 NETW_LOGICAL_NAME_ALREADY_RESERVED
14063 NETW_UNKNOWN_DEVICE_TYPE

122
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

14064 NETW_DEVICE_ALREADY_EXISTS
14065 NETW_LDS_TRANSLATION_LIMIT_EXCEEDED
The message has been routed forwards in the NET network as many
times as defined for maximum by the TL attribute. The message is no
more sent to the object device. An answer message with this error code
is sent to the message sender.
14066 NETW_LINK_ACE_PROCESS_DOES_NOT_EXIST
The line has not an autocaller process.
14067 NETW_DESTINATION_LINE_IN_USE
The destination line is in use and therefore its attributes may not be up-
dated.
14068 NETW_LINE_IS_NOT_AN_ACE_LINE
14069 NETW_NO_CONNECTION_ON_ACE_LINE
14070 NETW_MAX_PHYSICAL_NET_NUMBER_EXCEEDED
14071 NETW_INVALID_PHYSICAL_DEVICE_NUMBER
14072 NETW_MAX_PHYSICAL_RTU_NUMBER_EXCEEDED
14073 NETW_MAX_PHYSICAL_PCL_NUMBER_EXCEEDED
14074 NETW_MAX_PHYSICAL_SIN_NUMBER_EXCEEDED
14075 NETW_TC_TELEGRAM_TYPE_UNDEFINED
14076 NETW_TRANSLATION_LOOP_NOT_ALLOWED
14077 NETW_PROCESS_TABLE_FULL
14078 NETW_MAX_PHYSICAL_LCU_NUMBER_EXCEEDED
14079 NETW_MAX_PHYSICAL_ADE_NUMBER_EXCEEDED
14080 NETW_MAX_PHYSICAL_SPA_NUMBER_EXCEEDED
14081 NETW_MAX_PHYSICAL_EDEV_NUMBER_EXCEEDED
14082 NETW_INVALID_DV_ATTRIBUTE_INDEX
14083 NETW_MAX_PHYSICAL_SPI_NUMBER_EXCEEDED
14084 NETW_NODE_REFERENCED_CANT_BE_DELETED
14085 NETW_LINE_IS_FULL
14086 NETW_INVALID_DEVICE_TYPE_FOR_THIS_LINE
14087 NETW_MAX_PHYSICAL_REX_NUMBER_EXCEEDED
14088 NETW_MAX_PHYSICAL_LMK_NUMBER_EXCEEDED

123
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4.3.32 Common NET Link Layer Status Codes

16001 LINK_CTS_LINE_IS_INACTIVE
NET does not get Clear To Send signal.
16002 LINK_CTS_LINE_REMAINS_INACTIVE
NET does not get Clear To Send signal.
16003 LINK_DCD_LINE_IS_INACTIVE
NET does not get Data Carrier Detect.
16004 LINK_DCD_LINE_REMAINS_INACTIVE
16005 LINK_ATTRIBUTE_NOT_YET_IMPLEMENTED
16006 LINK_CN_ATTRIBUTE_NOT_YET_IMPLEMENTED
16007 LINK_CREATION_OF_LINK_PROCESSES_FAILED
16008 LINK_DEVICES_MUST_BE_DELETED_FIRST
16009 LINK_IS_ATTRIBUTE_NOT_YET_IMPLEMENTED
16011 LINK_LINE_ATTRIBUTE_VALUE_OUT_OF_RANGE
16012 LINK_MEMORY_EXCEEDED_FOR_PRIORITY_POOL
16013 LINK_NOT_ENOUGH_MEMORY_FOR_LINE_BUFFERS
16014 LINK_ONLY_RAM_PROTOCOL_ALLOWED_ON_LIN_13
16015 LINK_RAM_PROTOCOL_ALLOWED_ONLY_ON_LIN_13
16016 LINK_REDUNDANCY_REQUIRED_FOR_ANSI_X3
16018 LINK_MEMORY_EXCEEDED_FOR_NORMAL_POOL
16019 LINK_LINE_MUST_FIRST_BE_STOPPED
The operation demands that the line is taken out of use (IU = 0).
16020 LINK_ONLY_8_DATA_BITS_ALLOWED
16021 LINK_OPERATION_NOT_ALLOWED_ON_LINE_13
16022 LINK_NOT_ENOUGH_MEMORY
There is not enough free memory for this operation.
16023 LINK_LINE_NOT_CREATED
16024 LINK_INVALID_LINE_NUMBER
16025 LINK_STATION_ADDRESS_ALREADY_IN_USE
16026 LINK_INVALID_DEV_SA_ATTRIBUTE_VALUE
Allowed values for the ANSI station address: In decimal form: 8..63,
72..254 (255 = Broadcast). In octal form: 10..77, 110..376 (377 =
Broadcast).
16027 LINK_INDEX_RANGE_ERROR
16028 LINK_NONACCEPTABLE_PHONE_NUMBER

124
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

16029 LINK_NO_CONNECTION_OPEN
16030 LINK_CONNECTED_ACE_LINE_CANT_BE_STOPPED
A connection is open on the line, and therefore it cannot be stopped.
16031 LINK_DIAL_FAILS_BECAUSE_LINE_NOT_IDLE
16032 LINK_NO_ACE_ON_THIS_LINE
16033 LINK_INVALID_DEV_PA_ATTRIBUTE_VALUE
16034 LINK_LINE_NUMBER_OUT_OF_RANGE
16035 LINK_LINE_DOES_NOT_EXIST
16036 LINK_DEVICE_TYPE_NOT_ALLOWED_ON_LINE
16037 LINK_ONLY_RAM_OR_COM1_PROTOCOL_ON_LIN_13
16038 LINK_RAM_OR_COM1_PROTOCOL_ONLY_ON_LIN_13
16039 LINK_REDUNDANCY_NOT_CONFIGURABLE
16040 LINK_SA_USED_ON_ANOTHER_LINE
16041 LINK_CTS_FAILURE
16042 LINK_ONLY_RM_OR_IL_ALLOWED_ON_LIN_13
16043 LINK_IL_PROTOCOL_ALLOWED_ONLY_ON_LIN_13
16044 LINK_LINE_OPEN_FAIL
16045 LINK_LINE_CLOSE_ABNORMAL
16046 LINK_LINE_ALREADY_RUNNING
16047 LINK_LINE_CONTINUOUSLY_RESERVED
16048 LINE_LINE_ANALYSATOR_INIT_FAILED
The initialization of the analysator module failed

4.3.33 ANSI X3.28 Full Duplex Protocol Status Codes (XF)

16101 XFTP_ENQ_LIMIT_EXCEEDED
The device did not answer until the ENQ limit was reached. The reason
may be e.g. that the transmission speed has been incorrectly defined
(differently in NET and the RTU).
16102 XFTP_LINE_STUCKED
Clear To Send and Data Carrier Detect are OK, but the messages are not
transmitted on the line. The reason may be e.g. that Transmit Data and
Receive Data are connected incorrectly.
16103 XFTP_MODEM_LINE_ERROR_DURING_TRANSMISSION
16104 XFTP_MODEM_LINE_ERROR_IN_RESPONSE_WAIT
16105 XFTP_NAK_LIMIT_EXCEEDED

125
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

16106 XFTP_LINE_PASSIVATED
The connection has been broken.
16107 XFTP_LINE_ACTIVATED_BY_LOCAL
The dialling is successful and connection is arising (full duplex).
16108 XFTP_LINE_ACTIVATED_BY_REMOTE
NET is answering to the call and connection is arising.
16109 XFTP_LINE_IS_PASSIVE

4.3.34 ANSI X3.28 Half Duplex Protocol Status Codes (XH)

16201 XHCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
The Clear To Send signal changed to inactive during the transmission
(on ANSI X3.28/AB Half Duplex protocol).
16202 XHCP_CTS_LINE_IS_CONTINUOUSLY_INACTIVE
16204 XHCP_DST_STATION_IS_NOT_ON_THIS_LINE
16205 XHCP_TIMEOUT_WHILE_WAITING_ACK
The RTU did not answer with ACK until the waiting time (the TI attrib-
ute) was up, although the message has been sent again. The reason may
be, e.g. that NET does not get Data Carrier Detect signal or that the
transmission speed has been defined differently.
16206 XHCP_TIMEOUT_WHILE_WAITING_CTS
16207 XHCP_LINE_PASSIVATED
The connection has been broken.
16208 XHCP_LINE_ACTIVATED_BY_LOCAL
The dialling is successful and connection is arising (half duplex).
16209 XHCP_LINE_ACTIVATED_BY_REMOTE
NET is answering to the call and connection is arising.
16210 XHCP_LINE_IS_PASSIVE
16211 XHCP_TIMEOUT_WHILE_WAITING_PASSIVE_CTS
16212 XHCP_ACTIVE_DCD_PREVENTS_ACK_TX
16213 XHCP_ACTIVE_DCD_PREVENTS_NAK_TX

4.3.35 ADLP80 Slave Protocol Status Codes (AD)

16250 ADCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
16251 ADCP_CTS_LINE_IS_CONTINUOUSLY_INACTIVE
16252 ADCP_TIMEOUT_WHILE_WAITING_CTS

126
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

4.3.36 ADLP180 Slave Protocol Status Codes (AL)

16270 ALCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
16271 ALCP_CTS_LINE_IS_CONTINUOUSLY_INACTIVE
16272 ALCP_TIMEOUT_WHILE_WAITING_CTS

4.3.37 RP570 Slave Protocol Status Codes (RP)

16280 RPCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
16281 RPCP_CTS_LINE_IS_CONTINUOUSLY_INACTIVE
16282 RPCP_TIMEOUT_WHILE_WAITING_CTS
16283 RPCP_UNKNOWN_RP_PROTOCOL_MODE
An invalid value is given to the PM line attribute.
16284 RPCP_LINE_STOPPED
RP570/RP571 slave line is in stopped state.

4.3.38 Common RAM Protocol Status Codes (RM)

16301 RMTP_MESSAGE_RESPONDED_TO_BY_NAK
1. NET has no free message buffer for the message sent by the base
system. This is not an error situation, only an occasional overload
situation. A new attempt after a while may succeed.
2. The base system has no free memory for the message sent by NET.
16302 RMTP_TIMEOUT_WHILE_WAITING_ACK
Line in NET is raised with one.
16303 RMTP_NET_NOT_RUNNING

4.3.39 Integrated Link Status Codes (IL)

16311 ILTP_MESSAGE_RESPONDED_TO_BY_NAK
16312 ILTP_TIMEOUT_WHILE_WAITING_ACK
16313 ILTP_NET_NOT_RUNNING

4.3.40 LAN Link Status Codes (LN)

16320 LNTP_SENDING_FAILED
Internal use only.

127
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

16321 LNTP_NO_LOCAL_CONNECTION
Line is out of use since local connection has failed.
16325 LNRP_ALLOCATION_FAILED
Line is out of use since dynamic data allocation has failed.
16326 LNRP_LISTEN_PORT_USED
Line is out of use since the listen socket creation failed.
16327 LNRP_LOCAL_CONNECTION_OK
Local connection has been successfully created.

4.3.41 On Line Configuration Errors in NETC Modules

16600 NETC_DATA_OUT_OF_LIMITS_IN_CONFIG_WRITE
16601 NETC_DC_COUNTERS_FOR_NET_NOT_IMPLEMENTED
16602 NETC_DIAGNOSTIC_COUNTER_INDEX_TOO_LARGE
16603 NETC_DIAGNOSTIC_COUNTER_INDEX_TOO_SMALL
Does not apply for the VMS operating system.
16604 NETC_ERROR_IN_MESSAGE_DATA_FORMAT
16605 NETC_IU_ALREADY_CLEARED
16606 NETC_IU_ALREADY_SET
16607 NETC_LAST_INDEX_SMALLER_THAN_FIRST
16608 NETC_LINE_DOES_NOT_EXIST
16609 NETC_LINE_NUMBER_OUT_OF_RANGE
16610 NETC_LINE_MUST_BE_STOPPED_FIRST
16611 NETC_MESSAGE_DATA_STRUCTURE_ERROR
16612 NETC_MI_ATTRIBUTE_INDEX_TOO_LARGE
16613 NETC_MI_ATTRIBUTE_INDEX_TOO_SMALL
16614 NETC_MS_ATTRIBUTE_VALUE_OUT_OF_RANGE
16615 NETC_NN_EXCEEDS_MAX_PHYSICAL_NET_NUMBER
16616 NETC_NO_APPLICATION_PROCESS_PRESENT
16617 NETC_NO_DATA_ITEMS_IN_MESSAGE
16618 NETC_OLD_PROTOCOL_MUST_BE_RESET_FIRST
16619 NETC_SA_ATTRIBUTE_VALUE_OUT_OF_RANGE
16620 NETC_STATION_ADDRESS_ALREADY_IN_USE
16621 NETC_SUGGESTED_NAME_ALREADY_IN_USE
16622 NETC_SYS_MUST_BE_CONFIGURED_FIRST

128
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

16623 NETC_TL_ATTRIBUTE_NOT_YET_IMPLEMENTED
16624 NETC_UNKNOWN_ATTRIBUTE
16625 NETC_ZERO_NOT_ALLOWED_AS_FIRST_INDEX
16626 NETC_ZERO_TRANSLATION_LIMIT_NOT_ALLOWED
16627 NETC_ATTRIBUTE_NOT_YET_IMPLEMENTED
16628 NETC_ERROR_IN_MESSAGE_INDEX_RANGE
16629 NETC_LINE_BUFFER_ATTR_INDEX_TOO_SMALL
16630 NETC_LINE_BUFFER_ATTR_INDEX_TOO_LARGE
Does not apply for the VMS operating system.
16631 NETC_INVALID_MA_INDEX
16632 NETC_INVALID_MU_INDEX
16633 NETC_MAIL_UPDATED
16634 NETC_TRANSLATION_LIMIT_TOO_LARGE
16635 NETC_CS_IMPLEMENTED_FOR_XH_PROTOCOL_ONLY
16636 NETC_INVALID_SE_VALUE
16637 NETC_PROGRAM_RESTART_NOT_IMPLEMENTED
16638 NETC_UNDEFINED_NET_CONNECTION
16639 NETC_NET_CONNECTION_NR_OUT_OF_RANGE
16640 NETC_NOT_ATTRIBUTE_OF_CURRENT_PROTOCOL
16641 NETC_MESSAGE_NOT_LEFT_IN_QUEUE
16642 NETC_RETRANSMISSION_ALREADY_ACTIVE
16643 NETC_INVALID_ED_INDEX
16644 NETC_INVALID_TIME
16645 NETC_INVALID_ME_WRITE_COMMAND
16646 NETC_NO_PRIVILEGE_FOR_THIS_OPERATION
16647 NETC_SIGNAL_WRITE_NOT_ALLOWED
16648 NETC_INVALID_SG_ATTRIBUTE_VALUE
16649 NETC_SIGNAL_NOT_READABLE
16650 NETC_NOT_IMPLEMENTED_IN_NT
16651 NETC_ANALYSATOR_NOT_INITIALIZED
The application accessed to an analysator module which has not been
initialized.

129
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

16652 NETC_KEYSTORAGE_ALREADY_REGISTERED
The setting of the KS attribute is not possible any more since the keystor-
age file is already registered.
16653 NETC_KEYSTORAGE_REGISTRATION_FAILED
The registration of the keystorage file failed. Check the filename and
make sure that the file has been encrypted using a key which has been
generated in the same computer. 

4.3.42 Auto Dialling Status Codes

16700 ACEP_NO_ANSWER_FROM_ACE
The autocaller device does not give an acceptable reply within a certain
time in spite of repeated sendings.
16701 ACEP_ERROR_FROM_ACE
An ERROR reply has been received from the autocaller.
16702 ACEP_DISCONNECTION_FAILED
16703 ACEP_PHYSICAL_DISCONNECTION_FAILED
From the ACE has been received an ERROR reply, an undefined reply
or no reply to a connection break command. The ACE process is set into
IDLE state.
16704 ACEP_DIALING_FAILED
No contact arising, although the dialling may be OK. ACE has answered
to the dialling command by the reply NO CARRIER (3), ERROR (4)
or with an undefined reply, or the ACE has not answered at all.
16705 ACEP_UNKNOWN_ACE_ATTRIBUTE
16706 ACEP_CONNECTION_LIMIT_NOT_BOOLEAN
The CL attribute has been assigned an unallowed value. Allowed values
are 0 and 1.
16707 ACEP_ACE_LINE_IN_USE
The attributes may not be updated while the line is in use.
16708 ACEP_INVALID_CONNECTION_TIME
The CT attribute may not be given a negative value.
16709 ACEP_INVALID_RADIO_WAIT_TIME
The RW attribute may not be given a negative value.
16710 ACEP_PULSE_DIAL_NOT_BOOLEAN
The PU attribute has been assigned an unallowed value. Allowed values
are 0 and 1.
16711 ACEP_INVALID_S_REGISTER_VALUE
16712 ACEC_ZERO_NOT_ALLOWED_AS_FIRST_INDEX
16713 ACEC_S_REGISTER_INDEX_TOO_SMALL

130
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

16714 ACEC_S_REGISTER_INDEX_TOO_LARGE
The number of the S register is >
12.
16715 ACEC_LINE_NUMBER_OUT_OF_RANGE
16716 ACEC_LAST_INDEX_SMALLER_THAN_FIRST
16717 ACEC_S_REGISTERS_FOR_NET_NOT_IMPLEMENTED
16718 ACEC_LINE_DOES_NOT_EXIST
16719 ACEC_AS_ATTRIBUTE_IS_READ_ONLY
16720 ACEP_LINE_AND_ATTRIBUTES_NOT_INITIALIZED
16721 ACEC_YOU_CANNOT_CHANGE_THE_FIRST_REGISTER
16722 ACEC_ESCAPE_CHAR_NOT_AN_ASCII_CODE
16723 ACEC_YOU_CANNOT_CHANGE_THE_THIRD_REGISTER
Unallowed ESCAPE character. Allowed values are the ASCII codes (0
. . 127). The NET programs use the default ( ""+"" = 43), and if this is
changed, NET cannot break the connection.
16724 ACEC_YOU_CANNOT_CHANGE_THE_FOURTH_REGISTER
16725 ACEC_YOU_CANNOT_CHANGE_THE_FIFTH_REGISTER
16726 ACEC_DIALING_TONE_WAIT_OUT_OF_RANGE
Illegal wait time for the dialling tone. Allowed values are 1 . . 255
seconds (default is 2).
16727 ACEC_CARRIER_WAVE_WAIT_OUT_OF_RANGE
Illegal for the carrier wave. Allowed values are 1 . . 255 seconds (default
is 30).
16728 ACEC_DIALING_DELAY_OUT_OF_RANGE
Illegal length of delay caused by the delay character. Allowed values
are 1 . . 255 seconds. Default = 2.
16729 ACEC_CARRIER_DETECTION_DELAY_OUT_OF_RANGE
16730 ACEC_BREAK_DOWN_DELAY_OUT_OF_RANGE
16731 ACEC_LENGTH_OF_MARK_AND_SPACE_TONE_NOT_OK
16732 ACEC_ESCAPE_FRAME_DELAY_OUT_OF_RANGE
16733 ACEP_LINE_IDLE
16734 ACEP_INVALID_RADIO_DISCONNECTION_DELAY
16735 ACEP_NO_MODEM_COMMAND_REPLY

4.3.43 COM-1 Protocol Status Codes (CO)

16750 COPC_COM1_ERROR_WHILE_TRANSMITTING

131
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

16751 COPC_COM1_ERROR_WHILE_WAITING_ACK
16752 COPC_COM1_ERROR_WHILE_RECEIVING_ACK
16753 COPC_COM1_ERROR_DURING_COLLISION
16754 COPC_BUFFER_ERROR_DURING_COLLISION
16755 COPC_TOO_MANY_COLLISIONS
16756 COPC_MESSAGE_RESPONDED_TO_BY_NAK
16757 COPC_TIMEOUT_WHILE_TRANSMITTING
16758 COPC_TIMEOUT_WHILE_WAITING_ACK
16759 COPC_TIMEOUT_WHILE_RECEIVING_ACK

4.3.44 RP570 Master Protocol Status Codes (SR)

16801 SRCP_CTS_LINE_IS_CONTINUOUSLY_INACTIVE
16802 SRCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
16803 SRCP_TIMEOUT_WHILE_WAITING_CTS
16804 SRCP_RTU_NOT_ON_THIS_LINE
16805 SRCP_FAILED_TO_DELIVER_RESPONSE
16806 SRCP_REDUNDANCY_ERRORS_IN_RESPONSE
16807 SRCP_RECEIVE_ERRORS_IN_RESPONSE
16808 SRCP_TIMEOUT_WHILE_WAITING_RESPONSE
16809 SRCP_TIMEOUT_WHILE_WAITING_APPL_ACK
16810 SRCP_LINE_PASSIVATED
16811 SRCP_LINE_IS_PASSIVE
16812 SRCP_BUILD_UP_READY
16813 SRCP_LOOP_CONFIGURATION_FAILED
16814 SRCP_READ_NOT_ALLOWED_HERE
16815 SRCP_INVALID_ATTRIBUTE_VALUE
16816 SRCP_ERROR_IN_APPLICATION_QUEUE
16817 SRCP_NEW_CONFIGURATION_MUST_FIRST_BE_LOADED
16818 SRCP_ONLY_START_OF_BUILD_ALLOWED_HERE
16819 SRCP_ONLY_STOP_COMMAND_ALLOWED_HERE
16820 SRCP_ONLY_STOP_BREAK_DOWN_ALLOWED_HERE
16821 SRCP_LINE_MUST_BE_IN_LOOP_MODE

132
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

16822 SRCP_TRANSMISSION_BLOCKED
16823 SRCP_UNKNOWN_SR_PROTOCOL_MODE
16824 SRCP_NOT_LINE_WITH_SR_PROTOCOL
16825 SRCP_LINE_ACTIVATED_BY_LOCAL
16826 SRCP_LINE_ACTIVATED_BY_REMOTE
16827 SRCP_COMMAND_TO_INOPERABLE_RTU
16828 SRCP_LINE_STOPPED
The RP570 master line has been taken out of use by using the IU attrib-
ute.

4.3.45 P214 Master Protocol Status Codes (PR)

16851 PRCP_DST_STATION_NOT_ON_THIS_LINE
16852 PRCP_RESPONSE_BUFFER_NOT_READY
16853 PRCP_WAITING_CTS_TIMEOUT
16854 PRCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
16855 PRCP_ALTERNATING_BIT_ERROR
16856 PRCP_BUFFER_NOT_READY
16857 PRCP_CTS_LINE_IS_CONTINUOSLY_INACTIVE
16858 PRCP_REDUNDANCY_ERRORS_IN_RESPONSE
16859 PRCP_RECEIVE_ERRORS_IN_RESPONSE
16860 PRCP_DST_STATION_BLOCKED
16861 PRCP_INVALID_ATTRIBUTE_VALUE

4.3.46 FT1.2 Framing Status Codes (TC)

6901 TCPC_INVALID_ATTRIBUTE_VALUE

4.3.47 INSUM Master Protocol Status Codes (IS)

16950 ISCP_ACTIVE_BAG_NOT_FOUND
16951 ISCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
16952 ISCP_REDUNDANCY_ERRORS_IN_RESPONSE
16953 ISCP_RX_ERRORS_IN_RESPONSE

133
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

16954 ISCP_CTS_LINE_IS_CONTINUOSLY_INACTIVE
16955 ISCP_WAITING_CTS_TIMEOUT
16956 ISCP_BUFFER_NOT_READY

4.3.48 COMLI Slave Protocol Status Codes (CL)

17001 CLCP_REPLY_MESSAGE_NOT_ACCEPTED
17002 CLCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
17003 CLCP_BUFFER_NOT_READY
17004 CLCP_WAITING_CTS_TIMEOUT

4.3.49 LCU500 Master Protocol Status Codes (LC)

17101 LCCP_LCU_NOT_ON_THIS_LINE
17102 LCCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
17103 LCCP_TIMEOUT_WHILE_WAITING_RESPONSE
17104 LCCP_CTS_LINE_IS_CONTINUOUSLY_INACTIVE
17105 LCCP_TIMEOUT_WHILE_WAITING_APPL_ACK
17107 LCCP_TIMEOUT_WHILE_WAITING_CTS
17108 LCCP_REDUNDANCY_ERRORS_IN_RESPONSE
17109 LCCP_RECEIVE_ERRORS_IN_RESPONSE
17110 LCPC_OUT_OF_MESSAGE_BUFFERS
17111 LCPC_INVALID_ATTRIBUTE_VALUE
17112 LCPC_UNKNOWN_PROTOCOL_MODE
17113 LCPC_NOT_LINE_WITH_LC_PROTOCOL

4.3.50 ADLP180 Master Protocol Status Codes (AM)

17151 AMCP_RTU_NOT_ON_THIS_LINE
17152 AMCP_TIMEOUT_WHILE_WAITING_CTS
17153 AMCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
17154 AMCP_REDUNDANCY_ERRORS_IN_RESPONSE
17155 AMCP_RECEIVE_ERRORS_IN_RESPONSE
17156 AMCP_TIMEOUT_WHILE_WAITING_RESPONSE

134
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

17157 AMCP_TIMEOUT_WHILE_WAITING_APPL_ACK
17158 AMCP_CTS_LINE_IS_CONTINUOUSLY_INACTIVE
17159 AMCP_LINE_STOPPED
The ADLP180 master line has been taken out of use by using the IU at-
tribute.

4.3.51 SPA Master Protocol Status Codes (SP)

17201 SPCP_TIMEOUT_WHILE_WAITING_CTS
17202 SPCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
17203 SPCP_REDUNDANCY_ERRORS_IN_RESPONSE
17204 SPCP_TIMEOUT_WHILE_WAITING_RESPONSE
17205 SPCP_CTS_LINE_IS_CONTINUOUSLY_INACTIVE
17206 SPCP_LINE_IS_PASSIVE
17207 SPCP_LINE_PASSIVATED
17208 SPCP_CONNECTION_NOT_ESTABLISHED
17230 SPPC_INVALID_ATTRIBUTE_VALUE
17231 SPPC_ERROR_IN_MESSAGE_DATA_FORMAT
17232 SPPC_INVALID_LINE_NUMBER
17233 SPPC_LINE_DOES_NOT_EXIST

4.3.52 General ASCII Protocol Status Codes (AG)

17251 AGCP_BUFFER_NOT_READY
17252 AGPC_UNKNOWN_ASCII_PROTOCOL_MODE
17253 AGPC_NOT_LINE_WITH_AG_PROTOCOL
17254 AGPC_TELEGRAM_LENGTH_PARAMETER_ERROR
17255 AGPC_TELEGRAM_FRAME_LENGTH_PARAM_ERROR
17256 AGCP_SYNC_RECEIVED
17257 AGCP_SYNC_MESSAGE_REJECTED
17258 AGPC_INVALID_CLOCK_SYNC_FORMAT
17259 AGPC_MASTER_CLOCK_NOT_SYNCHRONIZED
17260 AGCP_NO_MESSAGE_RECEIVED

135
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4.3.53 RCOM Master Protocol Status Codes (PC)

17301 PCCP_TIMEOUT_WHILE_WAITING_CTS
17302 PCCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
17303 PCCP_REDUNDANCY_ERRORS_IN_RESPONSE
17304 PCCP_TIMEOUT_WHILE_WAITING_RESPONSE
17305 PCCP_CTS_LINE_IS_CONTINUOUSLY_INACTIVE
17306 PCCP_RECEIVE_ERRORS_IN_RESPONSE
17307 PCCP_STATION_NOT_ON_THIS_LINE
17326 PCPC_UNKNOWN_PC_PROTOCOL_MODE
17327 PCPC_NOT_LINE_WITH_PC_PROTOCOL

4.3.54 Westinghouse F4F Slave Protocol Status Codes (WE)

17351 WECP_REPLY_MESSAGE_NOT_ACCEPTED
17352 WECP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
17353 WECP_BUFFER_NOT_READY
17354 WECP_WAITING_CTS_TIMEOUT

4.3.55 Alpha Protocol Status Codes (AT)

17401 ATCP_APLHA_CONNECTED
17402 ATCP_SESSION_STOPPED
17403 ATCP_SESSION_ABORTTED
17404 ATCP_BUFFER_NOT_READY
17405 ATCP_ERR_REPLY_FROM_ALPHA
17406 ATCP_NO_REPLY_FROM_ALPHA
17407 ATCP_SESSION_READY
17408 ATCP_HANDSHAKING_FAILED
17409 ATCP_LINE_PASSIVATED
17410 ATCP_MODEM_CONNECTED

136
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

4.3.56 IEC1107 Protocol Status Codes (IE)

17450 IECP_SESSION_READY
17451 IECP_SESSION_ABORTED
17452 IECP_LINE_PASSIVATED
17453 IECP_BUFFER_NOT_READY
17454 IECP_ERR_REPLY_FROM_DEVICE
17455 IECP_NO_REPLY_FROM_DEVICE
17456 IECP_SESSION_STOPPED
17457 IECP_SESSION_ENDS_TO_CTS_ERROR
17458 IECP_CONNECTION_ESTABILISHED

4.3.57 General PLC/Modbus Protocol Status Codes (PG)

17500 PGCP_TIMEOUT_WHILE_WAITING_CTS
17501 PGCP_CTS_LINE_FAILURE_WHILE_TRANSMITTING
17502 PGCP_BUFFER_NOT_READY
17503 PGCP_CTS_LINE_IS_CONTINUOUSLY_INACTIVE
17504 PGCP_REDUNDANCY_ERRORS_IN_RESPONSE
17505 PGCP_TIMEOUT_WHILE_WAITING_RESPONSE
17506 PGCP_LINE_PASSIVATED
17507 PGCP_LINE_ACTIVATED_BY_LOCAL
17508 PGCP_LINE_ACTIVATED_BY_REMOTE
17509 PGCP_LINE_IS_PASSIVE
17510 PGCP_CONNECTION_NOT_ESTABLISHED
Returned to SCIL if no connection exists to the commanded station.
17511 PGCP_LINE_STOPPED
The line is stopped.
17520 PGPC_ILLEGAL_ATTRIBUTE_VALUE
The given attribute value is illegal or out of range.

4.3.58 LON Protocol Status Codes (LO)

17550 LOCP_OPEN_FAILED_WITH_INVALID_HANDLE
17551 LOPC_CLOSE_FAILED

137
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

17552 LOPC_INVALID_ATTR_VALUE
17553 LOPC_INVALID_ATTR_INDEX
17554 LOPC_INVALID_LINE_NUMBER
17555 LOPC_LINE_DOES_NOT_EXIST
17556 LOPC_NV_INDEX_NOT_CONFIGURED

4.3.59 IEC60870-5-101/103 Protocol Status Codes (IG)

17600 IGTP_REMOTE_LINK_CONTINUOUSLY_BUSY
The Data Flow Control bit of the messages from the master is set for
more than 15 seconds.
17601 IGTP_TIMEOUT_WHILE_TRANSMITTING
The CTS signal or the end of transmitted message is not received in
correct time. The attribute DE controls CTS waiting time, the transmit
time of message is automatically calculated.
17602 IGTP_TIMEOUT_WHILE_WAITING_RESPONSE
Timeout while waiting for an acknowledgement to a message.
17603 IGTP_LINK_INITIALIZING
17604 IGTP_LINK_NOT_READY
The application level sends a command before the communication
between the master and the slave is established.
17605 IGTP_REMOTE_LINK_BUSY
Data sending fails since the Data Flow Control bit (DFC) is set in remote
station and there is already one data message waiting for its reset. Not
used in unbalanced slave.
17606 IGTP_REMOTE_LINK_NOT_RESPONDING
The slave does not receive a reply from the master.
17607 IGTP_LINE_STARTED
The station has been set in use by using the IU attribute.
17608 IGTP_LINE_STOPPED
The station has been set out of use by using the IU attribute.
17609 IGTP_MESSAGE_RECEIVING_STOPPED
17610 IGTP_RECEIVER_OUT_OF_BUFFERS
Internal software error. This error can for example occur in a situation
where the station is set out of use but commands are received from the
master.
17611 IGTP_LINE_PASSIVATED
The autodialling system controls the line. IEC communication is possible
not until the line is activated with a call.

138
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

17612 IGTP_LINE_ACTIVATED
The line is activated by the autodialling system, but the handshaking
sequence between master and slave is not yet ready.
17613 IGTP_NACK_RESPONSE
The remote station responded with a NACK to a command.
17614 IGTP_LINE_OPERATING_AS_BACKUP
Command cannot be sent since the line is configured to operate as
backup.
17620 IGPC_ILLEGAL_ATTRIBUTE_VALUE
The value written to one of the line attributes is incorrect.

4.3.60 DNP 3.0 Protocol Status Codes (DG)

17650 DGTP_REMOTE_LINK_CONTINUOUSLY_BUSY
The Data Flow Control bit of the messages from the master is set for
more than 15 seconds.
17651 DGTP_TIMEOUT_WHILE_TRANSMITTING
The DCD or CTS signal or the end of transmitted message is not received
in correct time. The attribute DE controls CTS waiting time, the attribute
TI the message time and DCD waiting time is constant.
17652 DGTP_TIMEOUT_WHILE_WAITING_RESPONSE
Timeout while waiting for an acknowledgement to a request.
17654 DGTP_LINK_NOT_READY
The application level sends a command before the communication
between the master and the slave is established.
17655 DGTP_REMOTE_STATION_BUSY
The Data Flow Control bit of the messages from the master is set for too
long.
17656 DGTP_REMOTE_STATION_NOT_RESPONDING
The salve does not receive a reply from the master.
17657 DGTP_LINE_STARTED
The station has been set in use using the IU attribute.
17658 DGTP_LINE_STOPPED
The line has been set out of use using the IU attribute.
17659 DGTP_RECEIVER_OUT_OF_BUFFERS
Internal software error.
17660 DGTP_LINE_PASSIVATED
The autodialling system controls the line. DNP communication is not
possible until the line is activated with a call.

139
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

17661 DGTP_LINE_ACTIVATED
The line is activated by the autodialling system, but the handshaking
sequence between master and slave is not ready yet.
17662 DGTP_REMOTE_LINK_RESPONDS_WITH_NACK
The remote device responds with secondary function code 1 (= NACK).
17670 DGPC_ILLEGAL_ATTRIBUTE_VALUE
The value written to one of the line attributes is incorrect.
17700 DCPC_INVALID_ATTRIBUTE_VALUE
The value written to one of the line attributes is of wrong data type.

4.3.61 LAN Link Status Codes (LN)

17750 LNPC_NONACCEPTABLE_HOSTNAME The given hostname is too


long.
17751 LNPC_NOT_LINE_WITH_LN_PROTOCOL Hostname configuration
impossible since the TCP/IP is has not yet been created.
17752 LNPC_CONFIGURATION_FAILED The starting of the configuration
thread failed.

4.3.62 IEC60870-5-104 Protocol Status Codes (IT)

17800 ITCP_REMOTE_HOST_CONTINUOUSLY_BUSY
Not used at moment.
17801 ITCP_LINE_INITIALIZING
Line status value before the initialization of the TCP interface for the
protocol is completed.
17802 ITCP_LINE_INITIALIZATION_FAILED
Line status value when the initialization of the TCP interface failed.
17803 ITCP_REMOTE_HOST_BUSY
Device status is set to this value when the data transfer is disabled due
to received 'stopdtxd5
frame.
17804 ITCP_REMOTE_HOST_NOT_RESPONDING
Device status is set to this value when the connection to remote host is
not established.
17805 ITCP_LINE_NOT_CONNECTED
Line status is set to this value when there is no connection to any con-
figured host.
17806 ITCP_LINE_STOPPED
Line status value when the line is taken out of use.

140
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

17807 ITCP_RECEIVER_OUT_OF_BUFFERS
Internal error situation.
17808 ITCP_REMOTE_HOST_NOT_READY
Returned to SCIL in case there is no connection to host.
17820 ITPC_ILLEGAL_ATTRIBUTE_VALUE
Returned to SCIL when the attribute value given is out of range.

4.3.63 PLC2 Error Codes (biased by 20000)

In case the returned status code is not listed below, it is a device specific value. Subtract
the offset value 20000 from the error code and seek the resulting value from the manual
of the IED in question.
20000 PLC2_STATUS_BIAS
20002 PLC_DOES_NOT_RESPOND
20016 PLC2_INVALID_CMD_OR_FNC_OR_SIZE_BYTE
The station does not accept the used data type.
20048 PLC2_PROCESSOR_FAULTY_OR_DISCONNECTED
20064 PLC2_INTERFACE_PROCESSOR_COMM_FAILED
The communication unit of the PLC does not get contact to the processor
of the PLC.
20080 PLC2_ACCESS_DENIED
You have tried to write to a station by a protected write command, but
there is no corresponding ACCESS RUNG in the PLC program.
20096 PLC2_EXECUTION_PREVENTED_BY_SWITCHES
The switch settings of the PLC communication unit prevent the command
execution. The reason may be that an unprotected write command has
been used, but the switch PHYSICAL/UNPROTECTED WRITE is in
DISABLED state.
20112 PLC2_STATION_IN_PROGRAM_MODE
20128 PLC2_STATION_IN_ERROR_SHUTDOWN_MODE
20144 PLC2_INTERFACE_MODULE_OUT_OF_BUF_SPACE
20176 PLC2_STATION_IN_DOWNLOAD_MODE

4.3.64 SCA TLS Error Codes

These error codes are related to the Transport Layer Security (TLS). Depending on the
station configurations these error codes can be seen in the Notify window or the User
Activity Log's Extra Info field. These error codes may be originated from communication
lines using DNP 3.0 master or slave protocols.

141
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2000 SCA_ERR_SSL_WANT_READ
Wait for the descriptor to become readable and call again.
2001 SCA_ERR_SSL_WANT_WRITE
Wait for the descriptor to become writable and call again.
2110 SCA_ERR_BIO_SOCK_INIT_FAILED
General socket library initialization failed.
2111 SCA_ERR_THREAD_SETUP_FAILED
Mutex creation for OpenSSL operating system abstraction failed.
2112 SCA_ERR_OPENSSL_INIT_FAILED
OpenSSL library init failed.
2114 SCA_ERR_SSL_SRV_NEW_FAILED
Cannot create a new ssl server connection object from a ssl context.
2115 SCA_ERR_SSL_CONNECTION_CREATION
Internal limitation is reached. Contact an ABB representative.
2116 SCA_ERR_SBIO_ALLOC
Creation of a new socket bio with BIO_new_socket failed.
2117 SCA_ERR_SSL_CLNT_NEW_FAILED
Cannot create a new ssl client connection object from a ssl context.
2118 SCA_ERR_CREATE_SSL
Creation of ssl connection failed.
2119 SCA_ERR_PARTIAL_WRITE
2120 SCA_ERR_UNSUPPORTED_CONNECTION_TYPE
2121 SCA_ERR_CREATE_SSL_SEMAPHORE
Creation of synchronization semaphore failed.
2122 SCA_ERR_INVALID_SOCKET
2123 SCA_ERR_READ_NOT_ALLOWED
2124 SCA_ERR_WRITE_NOT_ALLOWED
2125 SCA_ERR_SSL_CTX_ALLOC_FAILED
Allocation of ssl context filed.
2126 SCA_ERR_UNKNOWN_CERT_FAIL_ACTION
Must be one of SCA_SSL_CONTINUE, SCA_SSL_CLOSE.
2127 SCA_ERR_CREATE_DH_PARAMETERS
2128 SCA_ERR_SSL_DYN_CONNECTION_CREATION
Ssl dynamic connection creation failed.
2129 SCA_ERR_WAIT_SSL_SEMAPHORE
Wait on synchronization semaphore failed.
2150 SCA_ERR_NO_PEER_CERT
The peer did not send a certificate.

142
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2151 SCA_ERR_PEER_CERT_FAILED
Certificate validation failed, connection closed.
2152 SCA_ERR_PEER_CERT_ASK_USER
For human-operated SCA-hosts: the host application must provide to
the user a way to visually inspect the certificate.
2153 SCA_ERR_PEER_CERT_IPADDRESS
Ip-address in peer certificate does not match ip-address of connected
peer.
2200 SCA_ERR_EVP_PKEY_ALLOC
2201 SCA_ERR_X509_ALLOC
2202 SCA_ERR_GEN_RSA_KEY
Generation of private key failed.
2203 SCA_ERR_ASSIGN_RSA_KEY
Assign keyPair to private key structure failed.
2216 SCA_ERR_INVALID_COUNTRY
Must be 2 characters long.
2217 SCA_ERR_INVALID_COMMON_NAME
Must not be empty.
2218 SCA_ERR_INVALID_COMMAND
Must be SCA_CRT_CMD_GENERATE_NEV-
ER,SCA_CRT_CMD_GENERATE_ALWAYS or
SCA_CRT_CMD_GENERATE_IF_NOT_FOUND.
2219 SCA_ERR_SET_COUNTRY
Set country code into certificate/csr failed.
2220 SCA_ERR_SET_ORGANIZATION
Set organization into certificate/csr failed.
2221 SCA_ERR_SET_CN
Set common name into certificate/csr failed.
2222 SCA_ERR_SET_ISSUER
X509_set_issuer_name into certificate failed.
2223 SCA_ERR_SIGN_SELF_SIGNED
Signing certificate/csr with sha1 failed.
2224 SCA_ERR_KEY_CERT_FILE_PATH_TOO_LONG
Internal limitation is reached. Contact an ABB representative.
2226 SCA_ERR_CA_CERTIFICATE_FILE_PATH_TOO_LONG
Internal limitation is reached. Contact an ABB representative.
2227 SCA_ERR_PRIVATEKEY_PASS_PHRASE_TOO_LONG
Internal limitation is reached. Contact an ABB representative.

143
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2228 SCA_ERR_GET_CERT_CHAIN_FAILED
Read certificate from file failed.
2229 SCA_ERR_GET_KEY_FAILED
Read private key from file failed.
2230 SCA_ERR_FOPEN
Cannot open a file with BIO_new_file.
2231 SCA_ERR_WRITE_PRIVATE_KEY
Write private key to file failed.
2232 SCA_ERR_WRITE_CERTIFICATE
Write certificate to file failed.
2233 SCA_ERR_GET_CA_CERT_FAILED
No CA certificates available.
2234 SCA_ERR_CERTIFICATE_TIME_CHECK
Certificate has expired or certificate not yet valid.
2235 SCA_ERR_CERIFICATE_KEY_MISMATCH
Downloaded certificate and key file do not match.
2236 SCA_ERR_CERTIFICATE_VALIDATION_SETUP_ERROR
Setting up certificate chain for validation failed.
2237 SCA_ERR_SET_LOCALITY
Set locality code into certificate/csr failed.
2238 SCA_ERR_SET_STATE_PROVINCE
Set state_or_province code into certificate/csr failed.
2239 SCA_ERR_SET_ORGANIZATION_UNIT
Set organization unit code into certificate/csr failed.
2240 SCA_ERR_CSR_ALLOC
Allocate certificate signing request structure failed.
2241 SCA_ERR_SET_SUBJ_NAME
Set subject name into certificate signing request structure failed.
2242 SCA_ERR_SET_PUBLIC_KEY
Set public key to certificate signing request structure failed.
2243 SCA_ERR_OUT_BUFFER_TOO_SMALL
Internal limitation is reached. Contact an ABB representative.
2244 SCA_ERR_ENCODE_TO_DER
Function to encode/convert object (cert,csr) from C-structure to (binary)
to DER format failed.
2245 SCA_ERR_DECODE_FROM_DER
Function to decode/convert object (cert,csr) from DER format to internal
C-structure failed.

144
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2246 SCA_ERR_MEM_ALLOCATION
Generic memory allocation error, e.g. BIOs.
2247 SCA_ERR_SET_CHLG_PWD
Set challenge password into csr failed.
2248 SCA_ERR_DECODE_KEY_FROM_DER
Function to decode/convert key object from DER format to internal C-
structure failed.
2249 SCA_ERR_PARSE_PKCS12
PKCS12 parse failed.
2300 SCA_ERR_UNKNOWN_HMAC_ALGORITHM
2301 SCA_ERR_HMAC_BUFFER_TOO_SMALL
Internal limitation is reached. Contact an ABB representative.
2302 SCA_ERR_HMAC_CALCULATION
The HMAC algorithm failed.
2303 SCA_IEC_ERR_WRONG_HMAC
Received hmac does not match calculated hmac.
2310 SCA_ERR_WRAP_BUFFER_TOO_SMALL
Internal limitation is reached. Contact an ABB representative.
2311 SCA_ERR_WRAP_KEY
Wrap algorithm failed.
2315 SCA_ERR_UNWRAP_BUFFER_TOO_SMALL
Internal limitation is reached. Contact an ABB representative.
2316 SCA_ERR_SET_DECRYPT_KEY
Setting kek for unwrapping algorithm failed.
2317 SCA_ERR_UNWRAP_KEY
Unwrap algorithm failed.
2318 SCA_ERR_IEC_UNWRAP_AUTH_FAILURE
Unwrapp status does not match input data.
2319 SCA_ERR_IEC_UNWRAPPED_WRONG_KEY_SIZE
Key size from unwrapped data is wrong.
2320 SCA_ERR_UPDATE_KEY_WRONG_SIZE
The size of the kek from the file is not correct.
2321 SCA_ERR_UPDATE_KEY_BUFFER_TOO_SMALL
Internal limitation is reached. Contact an ABB representative.
2322 SCA_ERR_UPDATE_KEY_FILE_NOT_FOUND
The key encryption key file(update key) was not found.
2323 SCA_ERR_RAND_INSECURE_OUTPUT
2324 SCA_ERR_CREATE_IEC_SEMAPHORE
Creation of synchronization semaphore failed.

145
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2330 SCA_ERR_IEC_CONNECTION_CREATION
Internal limitation is reached. Contact an ABB representative.
2331 SCA_ERR_IEC_UNKNOWN_CONNECTION_USER
Connection handle and/or user id is not valid.
2332 SCA_ERR_IEC_CONTROLLING_DIRECTION_REQUIRED
The function is reserved for a controlling station.
2333 SCA_ERR_IEC_MONITORING_DIRECTION_REQUIRED
The function is reserved for a controlled station.
2334 SCA_ERR_IEC_UNKNOWN_KEY_WRAP_ALGORITHM
Only valid value is SCA_IEC_AES_128_KEY_WRAP.
2335 SCA_ERR_IEC_INVALID_USER
User id 0 not valid.
2336 SCA_ERR_IEC_USER_CREATION
Internal limitation is reached. Contact an ABB representative.
2337 SCA_ERR_SET_ENCRYPT_KEY
Setting kek for wrapping algo failed.
2400 SCA_ERR_HASH_BUFFER_TOO_SMALL
Internal limitation is reached. Contact an ABB representative.
2401 SCA_ERR_AES_BUFFER_TOO_SMALL
Internal limitation is reached. Contact an ABB representative.
2410 SCA_ERR_INVALID_ARGUMENT
Interface function argument has invalid range.
2411 SCA_ERR_INVALID_TLS_VERSION
TLS Version range is invalid.
2412 SCA_ERR_NOT_IMPLEMENTED
The requested function is not supported/implemented.
2413 SCA_ERR_MODE_NOT_SUPPORTED
The requested mode is not supported/implemented.
2500 SCA_ERR_STORE_CERT_SEARCH_STRING_TOO_LONG
Internal limitation is reached. Contact an ABB representative.
2501 SCA_ERR_STORE_CA_CERT_SEARCH_STRING_TOO_LONG
Internal limitation is reached. Contact an ABB representative.
2502 SCA_ERR_STORE_INVALID_CERT_LOCATION
Invalid location type SCA_CERT_STORE_PEM,...
2503 SCA_ERR_STORE_SET_CERT_NOT_SUPPORTED
Certificate creation not supported, use SCA_CRT_CMD_GENER-
ATE_NEVER.
2504 SCA_ERR_STORE_OPEN_FAILED
Certificate store could not be opened.

146
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2505 SCA_ERR_STORE_CERT_NOT_FOUND
Certificate specified in 'DeviceCertificateSearchString' not found in
store.
2506 SCA_ERR_STORE_PRIVATE_KEY_NOT_FOUND
Matching private key not found in store.
2507 SCA_ERR_STORE_CA_CERT_NOT_FOUND
2508 SCA_ERR_STORE_SET_CERT_TO_OPENSSL_FAILED
Cannot set device certificate into OpenSSL store.
2509 SCA_ERR_STORE_SET_PRIV_KEY_TO_OPENSSL_FAILED
Possibly key and certificate do not match.
2510 SCA_ERR_STORE_ADD_CA_CERT_TO_OPENSSL_FAILED
Possibly the certificate is already in OpenSSL store.
2511 SCA_ERR_STORE_PARSE_CERT_FAILED
Conversion from platform store format to OpenSSL format failed.
2512 SCA_ERR_STORE_NOT_WRITABLE
The operation cannot be completed because the certificate store is not
writable/read-only.
2513 SCA_ERR_STORE_OBJECT_TYPE_NOT_SUPPORTED
The cert/key store type cannot handle the requested object.
2514 SCA_ERR_STORE_CREATE_SEMAPHORE
Syncronisation semaphore creation failed.
2515 SCA_ERR_STORE_MAX_HANDLES_EXCEEDED
Internal limitation is reached. Contact an ABB representative.
2516 SCA_ERR_STORE_PERSISTENCY_MISSING
SCA_CERT_STORE_PEM_GENERIC is chosen as store but no persist-
ency implementation is provided.
2517 SCA_ERR_STORE_NUM_KEYS_CERT_MISMATCH
Number of private keys and certificates do not match. Possible reason
is that the key could not be loaded due to wrong password.
2518 SCA_ERR_WAIT_STORE_SEMAPHORE
Wait on synchronization semaphore failed.
2550 SCA_ERR_WIN_LOAD_CAPI_ENGINE_FAILED
Engine to access CryptoAPI could not be loaded.
2551 SCA_ERR_WIN_INIT_CAPI_ENGINE_FAILED
Engine to access CryptoAPI could not be initilaized.
2570 SC_ERR_PERSIST_INVALID_PARAMETER
Input parameter not valid.
2571 SC_ERR_PERSIST_INIT
Generic failure while initializing persistency.

147
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2572 SC_ERR_PERSIST_FOPEN
Open persistency failed (e.g. file not found).
2573 SC_ERR_PERSIST_GET_DATA_SIZE
Not possible to determine the size of the persisted data.
2574 SC_ERR_PERSIST_BUFFER_TOO_SMALL
Internal limitation is reached. Contact an ABB representative.
2575 SC_ERR_PERSIST_DATA_TOO_LARGE
Internal limitation is reached. Contact an ABB representative.
2576 SC_ERR_PERSIST_LOAD_DATA
Internal limitation is reached. Contact an ABB representative.
2577 SC_ERR_PERSIST_STORE_DATA
Generic failure while writing/storing data to persistency.
2578 SC_ERR_PERSIST_TERMINATE
Generic failure whil terminating persistency.

4.4 Operating System Status Codes

4.4.1 Win32 Error Codes

0 ERROR_SUCCESS
The operation completed successfully.
1 ERROR_INVALID_FUNCTION
Incorrect function.
2 ERROR_FILE_NOT_FOUND
The system cannot find the file specified.
3 ERROR_PATH_NOT_FOUND
The system cannot find the path specified.
4 ERROR_TOO_MANY_OPEN_FILES
The system cannot open the file.
5 ERROR_ACCESS_DENIED
Access is denied.
6 ERROR_INVALID_HANDLE
The handle is invalid.
7 ERROR_ARENA_TRASHED
The storage control blocks were destroyed.
8 ERROR_NOT_ENOUGH_MEMORY
Not enough storage is available to process this command.

148
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

9 ERROR_INVALID_BLOCK
The storage control block address is invalid.
10 ERROR_BAD_ENVIRONMENT
The environment is incorrect.
11 ERROR_BAD_FORMAT
An attempt was made to load a program with an incorrect format.
12 ERROR_INVALID_ACCESS
The access code is invalid.
13 ERROR_INVALID_DATA
The data is invalid.
14 ERROR_OUTOFMEMORY
Not enough storage is available to complete this operation.
15 ERROR_INVALID_DRIVE
The system cannot find the drive specified.
16 ERROR_CURRENT_DIRECTORY
The directory cannot be removed.
17 ERROR_NOT_SAME_DEVICE
The system cannot move the file to a different disk drive.
18 ERROR_NO_MORE_FILES
There are no more files.
19 ERROR_WRITE_PROTECT
The media is write protected.
20 ERROR_BAD_UNIT
The system cannot find the device specified.
21 ERROR_NOT_READY
The device is not ready.
22 ERROR_BAD_COMMAND
The device does not recognize the command.
23 ERROR_CRC
Data error (cyclic redundancy check).
24 ERROR_BAD_LENGTH
The program issued a command but the command length is incorrect.
25 ERROR_SEEK
The drive cannot locate a specific area or track on the disk.
26 ERROR_NOT_DOS_DISK
The specified disk or diskette cannot be accessed.
27 ERROR_SECTOR_NOT_FOUND
The drive cannot find the sector requested.

149
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

28 ERROR_OUT_OF_PAPER
The printer is out of paper.
29 ERROR_WRITE_FAULT
The system cannot write to the specified device.
30 ERROR_READ_FAULT
The system cannot read from the specified device.
31 ERROR_GEN_FAILURE
A device attached to the system is not functioning.
32 ERROR_SHARING_VIOLATION
The process cannot access the file because it is being used by another
process.
33 ERROR_LOCK_VIOLATION
The process cannot access the file because another process has locked
a portion of the file.
34 ERROR_WRONG_DISK
The wrong diskette is in the drive. Insert %2 (Volume Serial Number:
%3) into drive %1.
36 ERROR_SHARING_BUFFER_EXCEEDED
Too many files opened for sharing.
38 ERROR_HANDLE_EOF
Reached the end of the file.
39 ERROR_HANDLE_DISK_FULL
The disk is full.
50 ERROR_NOT_SUPPORTED
The network request is not supported.
51 ERROR_REM_NOT_LIST
The remote computer is not available.
52 ERROR_DUP_NAME
A duplicate name exists on the network.
53 ERROR_BAD_NETPATH
The network path was not found.
54 ERROR_NETWORK_BUSY
The network is busy.
55 ERROR_DEV_NOT_EXIST
The specified network resource or device is no longer available.
56 ERROR_TOO_MANY_CMDS
The network BIOS command limit has been reached.
57 ERROR_ADAP_HDW_ERR
A network adapter hardware error occurred.

150
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

58 ERROR_BAD_NET_RESP
The specified server cannot perform the requested operation.
59 ERROR_UNEXP_NET_ERR
An unexpected network error occurred.
60 ERROR_BAD_REM_ADAP
The remote adapter is not compatible.
61 ERROR_PRINTQ_FULL
The printer queue is full.
62 ERROR_NO_SPOOL_SPACE
Space to store the file waiting to be printed is not available on the server.
63 ERROR_PRINT_CANCELLED
The file waiting to be printed was deleted.
64 ERROR_NETNAME_DELETED
The specified network name is no longer available.
65 ERROR_NETWORK_ACCESS_DENIED
Network access is denied.
66 ERROR_BAD_DEV_TYPE
The network resource type is not correct.
67 ERROR_BAD_NET_NAME
The network name cannot be found.
68 ERROR_TOO_MANY_NAMES
The name limit for the local computer network adapter card was ex-
ceeded.
69 ERROR_TOO_MANY_SESS
The network BIOS session limit was exceeded.
70 ERROR_SHARING_PAUSED
The remote server has been paused or is in the process of being started.
71 ERROR_REQ_NOT_ACCEP
No more connections can be made to this remote computer at this time
because there are already as many connections as the computer can ac-
cept.
72 ERROR_REDIR_PAUSED
The specified printer or disk device has been paused.
80 ERROR_FILE_EXISTS
The file exists.
82 ERROR_CANNOT_MAKE
The directory or file cannot be created.
83 ERROR_FAIL_I24
Fail on INT 24.

151
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

84 ERROR_OUT_OF_STRUCTURES
Storage to process this request is not available.
85 ERROR_ALREADY_ASSIGNED
The local device name is already in use.
86 ERROR_INVALID_PASSWORD
The specified network password is not correct.
87 ERROR_INVALID_PARAMETER
The parameter is incorrect.
88 ERROR_NET_WRITE_FAULT
A write fault occurred on the network.
89 ERROR_NO_PROC_SLOTS
The system cannot start another process at this time.
100 ERROR_TOO_MANY_SEMAPHORES
Cannot create another system semaphore.
101 ERROR_EXCL_SEM_ALREADY_OWNED
The exclusive semaphore is owned by another process.
102 ERROR_SEM_IS_SET
The semaphore is set and cannot be closed.
103 ERROR_TOO_MANY_SEM_REQUESTS
The semaphore cannot be set again.
104 ERROR_INVALID_AT_INTERRUPT_TIME
Cannot request exclusive semaphores at interrupt time.
105 ERROR_SEM_OWNER_DIED
The previous ownership of this semaphore has ended.
106 ERROR_SEM_USER_LIMIT
Insert the diskette for drive %1.
107 ERROR_DISK_CHANGE
The program stopped because an alternate diskette was not inserted.
108 ERROR_DRIVE_LOCKED
The disk is in use or locked by another process.
109 ERROR_BROKEN_PIPE
The pipe has been ended.
110 ERROR_OPEN_FAILED
The system cannot open the device or file specified.
111 ERROR_BUFFER_OVERFLOW
The file name is too long.
112 ERROR_DISK_FULL
There is not enough space on the disk.

152
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

113 ERROR_NO_MORE_SEARCH_HANDLES
No more internal file identifiers available.
114 ERROR_INVALID_TARGET_HANDLE
The target internal file identifier is incorrect.
117 ERROR_INVALID_CATEGORY
The IOCTL call made by the application program is not correct.
118 ERROR_INVALID_VERIFY_SWITCH
The verify-on-write switch parameter value is not correct.
119 ERROR_BAD_DRIVER_LEVEL
The system does not support the command requested.
120 ERROR_CALL_NOT_IMPLEMENTED
This function is not supported on this system.
121 ERROR_SEM_TIMEOUT
The semaphore timeout period has expired.
122 ERROR_INSUFFICIENT_BUFFER
The data area passed to a system call is too small.
124 ERROR_INVALID_LEVEL
The system call level is not correct.
125 ERROR_NO_VOLUME_LABEL
The disk has no volume label.
126 ERROR_MOD_NOT_FOUND
The specified module could not be found.
127 ERROR_PROC_NOT_FOUND
The specified procedure could not be found.
128 ERROR_WAIT_NO_CHILDREN
There are no child processes to wait for.
129 ERROR_CHILD_NOT_COMPLETE
The %1 application cannot be run in Win32 mode.
130 ERROR_DIRECT_ACCESS_HANDLE
Attempt to use a file handle to an open disk partition for an operation
other than raw disk I/O.
131 ERROR_NEGATIVE_SEEK
An attempt was made to move the file pointer before the beginning of
the file.
132 ERROR_SEEK_ON_DEVICE
The file pointer cannot be set on the specified device or file.
133 ERROR_IS_JOIN_TARGET
A JOIN or SUBST command cannot be used for a drive that contains
previously joined drives.

153
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

134 ERROR_IS_JOINED
An attempt was made to use a JOIN or SUBST command on a drive that
has already been joined.
135 ERROR_IS_SUBSTED
An attempt was made to use a JOIN or SUBST command on a drive that
has already been substituted.
136 ERROR_NOT_JOINED
The system tried to delete the JOIN of a drive that is not joined.
137 ERROR_NOT_SUBSTED
The system tried to delete the substitution of a drive that is not substi-
tuted.
138 ERROR_JOIN_TO_JOIN
The system tried to join a drive to a directory on a joined drive.
139 ERROR_SUBST_TO_SUBST
The system tried to substitute a drive to a directory on a substituted drive.
140 ERROR_JOIN_TO_SUBST
The system tried to join a drive to a directory on a substituted drive.
141 ERROR_SUBST_TO_JOIN
The system tried to SUBST a drive to a directory on a joined drive.
142 ERROR_BUSY_DRIVE
The system cannot perform a JOIN or SUBST at this time.
143 ERROR_SAME_DRIVE
The system cannot join or substitute a drive to or for a directory on the
same drive.
144 ERROR_DIR_NOT_ROOT
The directory is not a subdirectory of the root directory.
145 ERROR_DIR_NOT_EMPTY
The directory is not empty.
146 ERROR_IS_SUBST_PATH
The path specified is being used in a substitute.
147 ERROR_IS_JOIN_PATH
Not enough resources are available to process this command.
148 ERROR_PATH_BUSY
The path specified cannot be used at this time.
149 ERROR_IS_SUBST_TARGET
An attempt was made to join or substitute a drive for which a directory
on the drive is the target of a previous substitute.
151 ERROR_INVALID_EVENT_COUNT
The number of specified semaphore events for DosMuxSemWait is not
correct.

154
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

152 ERROR_TOO_MANY_MUXWAITERS
DosMuxSemWait did not execute, too many semaphores are already
set.
153 ERROR_INVALID_LIST_FORMAT
The DosMuxSemWait list is not correct.
154 ERROR_LABEL_TOO_LONG
The entered volume label exceeds the label character limit of the target
file system.
155 ERROR_TOO_MANY_TCBS
Cannot create another thread.
156 ERROR_SIGNAL_REFUSED T
The recipient process has refused the signal.
157 ERROR_DISCARDED
The segment is already discarded and cannot be locked.
158 ERROR_NOT_LOCKED
The segment is already unlocked.
159 ERROR_BAD_THREADID_ADDR
The address for the thread ID is not correct.
160 ERROR_BAD_ARGUMENTS
The argument string passed to DosExecPgm is not correct.
161 ERROR_BAD_PATHNAME
The specified path is invalid.
162 ERROR_SIGNAL_PENDING
A signal is already pending.
164 ERROR_MAX_THRDS_REACHED
No more threads can be created in the system.
167 ERROR_LOCK_FAILED
Unable to lock a region of a file.
170 ERROR_BUSY
The requested resource is in use.
173 ERROR_CANCEL_VIOLATION
A lock request was not outstanding for the supplied cancel region.
174 ERROR_ATOMIC_LOCKS_NOT_SUPPORTED
The file system does not support atomic changes to the lock type.
180 ERROR_INVALID_SEGMENT_NUMBER
The system detected a segment number that was not correct.
182 ERROR_INVALID_ORDINAL
The operating system cannot run %1.

155
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

183 ERROR_ALREADY_EXISTS
Cannot create a file when that file already exists.
186 ERROR_INVALID_FLAG_NUMBER
The flag passed is not correct.
187 ERROR_SEM_NOT_FOUND
The specified system semaphore name was not found.
188 ERROR_INVALID_STARTING_CODESEG
The operating system cannot run %1.
189 ERROR_INVALID_STACKSEG
The operating system cannot run %1.
190 ERROR_INVALID_MODULETYPE
The operating system cannot run %1.
191 ERROR_INVALID_EXE_SIGNATURE
Cannot run %1 in Win32 mode.
192 ERROR_EXE_MARKED_INVALID
The operating system cannot run %1.
193 ERROR_BAD_EXE_FORMAT
%1 is not a valid Win32 application.
194 ERROR_ITERATED_DATA_EXCEEDS_64k
The operating system cannot run %1.
195 ERROR_INVALID_MINALLOCSIZE
The operating system cannot run %1.
196 ERROR_DYNLINK_FROM_INVALID_RING
The operating system cannot run this application program.
197 ERROR_IOPL_NOT_ENABLED
The operating system is not presently configured to run this application.
198 ERROR_INVALID_SEGDPL
The operating system cannot run %1.
199 ERROR_AUTODATASEG_EXCEEDS_64k
The operating system cannot run this application program.
200 ERROR_RING2SEG_MUST_BE_MOVABLE
The code segment cannot be greater than or equal to 64K.
201 ERROR_RELOC_CHAIN_XEEDS_SEGLIM
The operating system cannot run %1.
202 ERROR_INFLOOP_IN_RELOC_CHAIN
The operating system cannot run %1.
203 ERROR_ENVVAR_NOT_FOUND
The system could not find the environment option that was entered.

156
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

205 ERROR_NO_SIGNAL_SENT
No process in the command subtree has a signal handler.
206 ERROR_FILENAME_EXCED_RANGE
The filename or extension is too long.
207 ERROR_RING2_STACK_IN_USE
The ring 2 stack is in use.
209 ERROR_INVALID_SIGNAL_NUMBER
The signal being posted is not correct.
210 ERROR_THREAD_1_INACTIVE
The signal handler cannot be set.
212 ERROR_LOCKED
The segment is locked and cannot be reallocated.
214 ERROR_TOO_MANY_MODULES
Too many dynamic-link modules are attached to this program or dynam-
ic-link module.
215 ERROR_NESTING_NOT_ALLOWED
Cannot nest calls to LoadModule.
230 ERROR_BAD_PIPE
The pipe state is invalid.
231 ERROR_PIPE_BUSY
All pipe instances are busy.
232 ERROR_NO_DATA
The pipe is being closed.
233 ERROR_PIPE_NOT_CONNECTED
No process is on the other end of the pipe.
234 ERROR_MORE_DATA
More data is available.
240 ERROR_VC_DISCONNECTED
The session was canceled.
254 ERROR_INVALID_EA_NAME
The specified extended attribute name was invalid.
255 ERROR_EA_LIST_INCONSISTENT
The extended attributes are inconsistent.
258 WAIT_TIMEOUT
The wait operation timed out.
259 ERROR_NO_MORE_ITEMS
No more data is available.
266 ERROR_CANNOT_COPY
The copy functions cannot be used.

157
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

267 ERROR_DIRECTORY
The directory name is invalid.
275 ERROR_EAS_DIDNT_FIT
The extended attributes did not fit in the buffer.
276 ERROR_EA_FILE_CORRUPT
The extended attribute file on the mounted file system is corrupt.
277 ERROR_EA_TABLE_FULL
The extended attribute table file is full.
278 ERROR_INVALID_EA_HANDLE
The specified extended attribute handle is invalid.
282 ERROR_EAS_NOT_SUPPORTED
The mounted file system does not support extended attributes.
288 ERROR_NOT_OWNER
Attempt to release mutex not owned by caller.
298 ERROR_TOO_MANY_POSTS
Too many posts were made to a semaphore.
299 ERROR_PARTIAL_COPY
Only part of a ReadProcessMemory or WriteProcessMemory request
was completed.
300 ERROR_OPLOCK_NOT_GRANTED
The oplock request is denied.
301 ERROR_INVALID_OPLOCK_PROTOCOL
An invalid oplock acknowledgment was received by the system.
317 ERROR_MR_MID_NOT_FOUND
The system cannot find message text for message number 0x%1 in the
message file for %2.
487 ERROR_INVALID_ADDRESS
Attempt to access invalid address.
534 ERROR_ARITHMETIC_OVERFLOW
Arithmetic result exceeded 32 bits.
535 ERROR_PIPE_CONNECTED
There is a process on other end of the pipe.
536 ERROR_PIPE_LISTENING
Waiting for a process to open the other end of the pipe.
994 ERROR_EA_ACCESS_DENIED
Access to the extended attribute was denied.
995 ERROR_OPERATION_ABORTED
The I/O operation has been aborted because of either a thread exit or an
application request.

158
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

996 ERROR_IO_INCOMPLETE
Overlapped I/O event is not in a signaled state.
997 ERROR_IO_PENDING
Overlapped I/O operation is in progress.
998 ERROR_NOACCESS
Invalid access to memory location.
999 ERROR_SWAPERROR
Error performing inpage operation.
1001 ERROR_STACK_OVERFLOW
Recursion too deep, the stack overflowed.
1002 ERROR_INVALID_MESSAGE
The window cannot act on the sent message.
1003 ERROR_CAN_NOT_COMPLETE
Cannot complete this function.
1004 ERROR_INVALID_FLAGS
Invalid flags.
1005 ERROR_UNRECOGNIZED_VOLUME
The volume does not contain a recognized file system. Please make sure
that all required file system drivers are loaded and that the volume is not
corrupted.
1006 ERROR_FILE_INVALID
The volume for a file has been externally altered so that the opened file
is no longer valid.
1007 ERROR_FULLSCREEN_MODE
The requested operation cannot be performed in full-screen mode.
1008 ERROR_NO_TOKEN
An attempt was made to reference a token that does not exist.
1009 ERROR_BADDB
The configuration registry database is corrupt.
1010 ERROR_BADKEY
The configuration registry key is invalid.
1011 ERROR_CANTOPEN
The configuration registry key could not be opened.
1012 ERROR_CANTREAD
The configuration registry key could not be read.
1013 ERROR_CANTWRITE
The configuration registry key could not be written.
1014 ERROR_REGISTRY_RECOVERED
One of the files in the registry database had to be recovered by use of a
log or alternate copy. The recovery was successful.

159
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1018 ERROR_KEY_DELETED
Illegal operation attempted on a registry key that has been marked for
deletion.
1019 ERROR_NO_LOG_SPACE
System could not allocate the required space in a registry log.
1020 ERROR_KEY_HAS_CHILDREN
Cannot create a symbolic link in a registry key that already has subkeys
or values.
1021 ERROR_CHILD_MUST_BE_VOLATILE
Cannot create a stable subkey under a volatile parent key.
1022 ERROR_NOTIFY_ENUM_DIR
A notify change request is being completed and the information is not
being returned in the caller's buffer. The caller now needs to enumerate
the files to find the changes.
1051 ERROR_DEPENDENT_SERVICES_RUNNING
A stop control has been sent to a service that other running services are
dependent on.
1052 ERROR_INVALID_SERVICE_CONTROL
The requested control is not valid for this service.
1053 ERROR_SERVICE_REQUEST_TIMEOUT
The service did not respond to the start or control request in a timely
fashion.
1054 ERROR_SERVICE_NO_THREAD
A thread could not be created for the service.
1055 ERROR_SERVICE_DATABASE_LOCKED
The service database is locked.
1056 ERROR_SERVICE_ALREADY_RUNNING
An instance of the service is already running.
1057 ERROR_INVALID_SERVICE_ACCOUNT
The account name is invalid or does not exist.
1059 ERROR_CIRCULAR_DEPENDENCY
Circular service dependency was specified.
1060 ERROR_SERVICE_DOES_NOT_EXIST
The specified service does not exist as an installed service.
1061 ERROR_SERVICE_CANNOT_ACCEPT_CTRL
The service cannot accept control messages at this time.
1062 ERROR_SERVICE_NOT_ACTIVE
The service has not been started.
1063 ERROR_FAILED_SERVICE_CONTROLLER_CONNECT
The service process could not connect to the service controller.

160
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1064 ERROR_EXCEPTION_IN_SERVICE
An exception occurred in the service when handling the control request.
1065 ERROR_DATABASE_DOES_NOT_EXIST
The database specified does not exist.
1066 ERROR_SERVICE_SPECIFIC_ERROR
The service has returned a service-specific error code.
1067 ERROR_PROCESS_ABORTED
The process terminated unexpectedly.
1068 ERROR_SERVICE_DEPENDENCY_FAIL
The dependency service or group failed to start.
1069 ERROR_SERVICE_LOGON_FAILED
The service did not start due to a logon failure.
1071 ERROR_INVALID_SERVICE_LOCK
The specified service database lock is invalid.
1072 ERROR_SERVICE_MARKED_FOR_DELETE
The specified service has been marked for deletion.
1073 ERROR_SERVICE_EXISTS
The specified service already exists.
1074 ERROR_ALREADY_RUNNING_LKG
The system is currently running with the last-known-good configuration.
1075 ERROR_SERVICE_DEPENDENCY_DELETED
The dependency service does not exist or has been marked for deletion.
1076 ERROR_BOOT_ALREADY_ACCEPTED
The current boot has already been accepted for use as the last-known-
good control set.
1077 ERROR_SERVICE_NEVER_STARTED
No attempts to start the service have been made since the last boot.
1078 ERROR_DUPLICATE_SERVICE_NAME
The name is already in use as either a service name or a service display
name.
1079 ERROR_DIFFERENT_SERVICE_ACCOUNT
The account specified for this service is different from the account spe-
cified for other services running in the same process.
1082 ERROR_NO_RECOVERY_PROGRAM
No recovery program has been configured for this service.
1083 ERROR_SERVICE_NOT_IN_EXE
The executable program that this service is configured to run in does not
implement the service.
1100 ERROR_END_OF_MEDIA
The physical end of the tape has been reached.

161
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1101 ERROR_FILEMARK_DETECTED
A tape access reached a filemark.
1102 ERROR_BEGINNING_OF_MEDIA
The beginning of the tape or a partition was encountered.
1103 ERROR_SETMARK_DETECTED
A tape access reached the end of a set of files.
1104 ERROR_NO_DATA_DETECTED
No more data is on the tape.
1105 ERROR_PARTITION_FAILURE
Tape could not be partitioned.
1107 ERROR_DEVICE_NOT_PARTITIONED
Tape partition information could not be found when loading a tape.
1108 ERROR_UNABLE_TO_LOCK_MEDIA
Unable to lock the media eject mechanism.
1109 ERROR_UNABLE_TO_UNLOAD_MEDIA
Unable to unload the media.
1110 ERROR_MEDIA_CHANGED
The media in the drive may have changed.
1111 ERROR_BUS_RESET
The I/O bus was reset.
1112 ERROR_NO_MEDIA_IN_DRIVE
No media in drive.
1113 ERROR_NO_UNICODE_TRANSLATION
No mapping for the Unicode character exists in the target multi-byte
code page.
1114 ERROR_DLL_INIT_FAILED
A dynamic link library (DLL) initialization routine failed.
1115 ERROR_SHUTDOWN_IN_PROGRESS
A system shutdown is in progress.
1116 ERROR_NO_SHUTDOWN_IN_PROGRESS
Unable to abort the system shutdown because no shutdown was in pro-
gress.
1117 ERROR_IO_DEVICE
The request could not be performed because of an I/O device error.
1118 ERROR_SERIAL_NO_DEVICE
No serial device was successfully initialized. The serial driver will un-
load.

162
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1119 ERROR_IRQ_BUSY
Unable to open a device that was sharing an interrupt request (IRQ) with
other devices. At least one other device that uses that IRQ was already
opened.
1120 ERROR_MORE_WRITES
A serial I/O operation was completed by another write to the serial port.
(The IOCTL_SERIAL_XOFF_COUNTER reached zero.)
1121 ERROR_COUNTER_TIMEOUT
A serial I/O operation completed because the timeout period expired.
(The IOCTL_SERIAL_XOFF_COUNTER did not reach zero.)
1122 ERROR_FLOPPY_ID_MARK_NOT_FOUND
No ID address mark was found on the floppy disk.
1123 ERROR_FLOPPY_WRONG_CYLINDER
Mismatch between the floppy disk sector ID field and the floppy disk
controller track address.
1124 ERROR_FLOPPY_UNKNOWN_ERROR
The floppy disk controller reported an error that is not recognized by
the floppy disk driver.
1125 ERROR_FLOPPY_BAD_REGISTERS
The floppy disk controller returned inconsistent results in its registers.
1129 ERROR_EOM_OVERFLOW
Physical end of tape encountered.
1130 ERROR_NOT_ENOUGH_SERVER_MEMORY
Not enough server storage is available to process this command.
1131 ERROR_POSSIBLE_DEADLOCK
A potential deadlock condition has been detected.
1132 ERROR_MAPPED_ALIGNMENT
The base address or the file offset specified does not have the proper
alignment.
1140 ERROR_SET_POWER_STATE_VETOED
An attempt to change the system power state was vetoed by another ap-
plication or driver.
1141 ERROR_SET_POWER_STATE_FAILED
The system BIOS failed an attempt to change the system power state.
1142 ERROR_TOO_MANY_LINKS
An attempt was made to create more links on a file than the file system
supports.
1150 ERROR_OLD_WIN_VERSION
The specified program requires a newer version of Windows.
1151 ERROR_APP_WRONG_OS
The specified program is not a Windows or MS-DOS program.

163
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1152 ERROR_SINGLE_INSTANCE_APP
Cannot start more than one instance of the specified program.
1153 ERROR_RMODE_APP
The specified program was written for an earlier version of Windows.
1154 ERROR_INVALID_DLL
One of the library files needed to run this application is damaged.
1155 ERROR_NO_ASSOCIATION
No application is associated with the specified file for this operation.
1156 ERROR_DDE_FAIL
An error occurred in sending the command to the application.
1157 ERROR_DLL_NOT_FOUND
One of the library files needed to run this application cannot be found.
1158 ERROR_NO_MORE_USER_HANDLES
The current process has used all of its system allowance of handles for
Window Manager objects.
1159 ERROR_MESSAGE_SYNC_ONLY
The message can be used only with synchronous operations.
1160 ERROR_SOURCE_ELEMENT_EMPTY
The indicated source element has no media.
1161 ERROR_DESTINATION_ELEMENT_FULL
The indicated destination element already contains media.
1162 ERROR_ILLEGAL_ELEMENT_ADDRESS
The indicated element does not exist.
1163 ERROR_MAGAZINE_NOT_PRESENT
The indicated element is part of a magazine that is not present.
1164 ERROR_DEVICE_REINITIALIZATION_NEEDED
The indicated device requires reinitialization due to hardware errors.
1165 ERROR_DEVICE_REQUIRES_CLEANING
The device has indicated that cleaning is required before further opera-
tions are attempted.
1166 ERROR_DEVICE_DOOR_OPEN
The device has indicated that its door is open.
1167 ERROR_DEVICE_NOT_CONNECTED
The device is not connected.
1168 ERROR_NOT_FOUND
Element not found.
1169 ERROR_NO_MATCH
There was no match for the specified key in the index.

164
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1170 ERROR_SET_NOT_FOUND
The property set specified does not exist on the object.
1171 ERROR_POINT_NOT_FOUND
The point passed to GetMouseMovePointsEx is not in the buffer.
1172 ERROR_NO_TRACKING_SERVICE
The tracking (workstation) service is not running.
1173 ERROR_NO_VOLUME_ID
The Volume ID could not be found.
1174 ERROR_INVALID_VLM_OPERATION
The specified Very Large Memory (64-bit) operation is invalid.
1175 ERROR_UNABLE_TO_REMOVE_REPLACED
Unable to remove the file to be replaced.
1176 ERROR_UNABLE_TO_MOVE_REPLACEMENT
Unable to move the replacement file to the file to be replaced. The file
to be replaced has retained its original name.
1177 ERROR_UNABLE_TO_MOVE_REPLACEMENT_2
Unable to move the replacement file to the file to be replaced. The file
to be replaced has been renamed using the backup name.
1178 ERROR_JOURNAL_DELETE_IN_PROGRESS
The volume change journal is being deleted.
1179 ERROR_JOURNAL_NOT_ACTIVE
The volume change journal service is not active.
1181 ERROR_JOURNAL_ENTRY_DELETED
The journal entry has been deleted from the journal.
1200 ERROR_BAD_DEVICE
The specified device name is invalid.
1201 ERROR_CONNECTION_UNAVAIL
The device is not currently connected but it is a remembered connection.
1202 ERROR_DEVICE_ALREADY_REMEMBERED
An attempt was made to remember a device that had previously been
remembered.
1203 ERROR_NO_NET_OR_BAD_PATH
No network provider accepted the given network path.
1204 ERROR_BAD_PROVIDER
The specified network provider name is invalid.
1205 ERROR_CANNOT_OPEN_PROFILE
Unable to open the network connection profile.
1206 ERROR_BAD_PROFILE
The network connection profile is corrupted.

165
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1207 ERROR_NOT_CONTAINER
Cannot enumerate a noncontainer.
1208 ERROR_EXTENDED_ERROR
An extended error has occurred.
1209 ERROR_INVALID_GROUPNAME
The format of the specified group name is invalid.
1210 ERROR_INVALID_COMPUTERNAME
The format of the specified computer name is invalid.
1211 ERROR_INVALID_EVENTNAME
The format of the specified event name is invalid.
1212 ERROR_INVALID_DOMAINNAME
The format of the specified domain name is invalid.
1213 ERROR_INVALID_SERVICENAME
The format of the specified service name is invalid.
1214 ERROR_INVALID_NETNAME
The format of the specified network name is invalid.
1215 ERROR_INVALID_SHARENAME
The format of the specified share name is invalid.
1216 ERROR_INVALID_PASSWORDNAME
The format of the specified password is invalid.
1217 ERROR_INVALID_MESSAGENAME
The format of the specified message name is invalid.
1218 ERROR_INVALID_MESSAGEDEST
The format of the specified message destination is invalid.
1219 ERROR_SESSION_CREDENTIAL_CONFLICT
The credentials supplied conflict with an existing set of credentials.
1221 ERROR_DUP_DOMAINNAME
The workgroup or domain name is already in use by another computer
on the network.
1222 ERROR_NO_NETWORK
The network is not present or not started.
1223 ERROR_CANCELLED
The operation was canceled by the user.
1224 ERROR_USER_MAPPED_FILE
The requested operation cannot be performed on a file with a user-
mapped section open.
1225 ERROR_CONNECTION_REFUSED
The remote system refused the network connection.

166
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1226 ERROR_GRACEFUL_DISCONNECT
The network connection was gracefully closed.
1227 ERROR_ADDRESS_ALREADY_ASSOCIATED
The network transport endpoint already has an address associated with
it.
1228 ERROR_ADDRESS_NOT_ASSOCIATED
An address has not yet been associated with the network endpoint.
1229 ERROR_CONNECTION_INVALID
An operation was attempted on a nonexistent network connection.
1230 ERROR_CONNECTION_ACTIVE
An invalid operation was attempted on an active network connection.
1231 ERROR_NETWORK_UNREACHABLE
The remote network is not reachable by the transport.
1232 ERROR_HOST_UNREACHABLE
The remote system is not reachable by the transport.
1233 ERROR_PROTOCOL_UNREACHABLE
The remote system does not support the transport protocol.
1234 ERROR_PORT_UNREACHABLE
No service is operating at the destination network endpoint on the remote
system.
1235 ERROR_REQUEST_ABORTED
The request was aborted.
1236 ERROR_CONNECTION_ABORTED
The network connection was aborted by the local system.
1237 ERROR_RETRY
The operation could not be completed. A retry should be performed.
1238 ERROR_CONNECTION_COUNT_LIMIT
A connection to the server could not be made because the limit on the
number of concurrent connections for this account has been reached.
1239 ERROR_LOGIN_TIME_RESTRICTION
Attempting to log in during an unauthorized time of day for this account.
1240 ERROR_LOGIN_WKSTA_RESTRICTION
The account is not authorized to log in from this station.
1241 ERROR_INCORRECT_ADDRESS
The network address could not be used for the operation requested.
1242 ERROR_ALREADY_REGISTERED
The service is already registered.
1243 ERROR_SERVICE_NOT_FOUND
The specified service does not exist.

167
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1244 ERROR_NOT_AUTHENTICATED
The operation being requested was not performed because the user has
not been authenticated.
1245 ERROR_NOT_LOGGED_ON
The operation being requested was not performed because the user has
not logged on to the network. The specified service does not exist.
1246 ERROR_CONTINUE
Continue with work in progress.
1247 ERROR_ALREADY_INITIALIZED
An attempt was made to perform an initialization operation when initial-
ization has already been completed.
1248 ERROR_NO_MORE_DEVICES
No more local devices.
1249 ERROR_NO_SUCH_SITE
The specified site does not exist.
1250 ERROR_DOMAIN_CONTROLLER_EXISTS
A domain controller with the specified name already exists.
1251 ERROR_ONLY_IF_CONNECTED
This operation is supported only when the user is connected to the
server.
1300 ERROR_NOT_ALL_ASSIGNED
Not all privileges referenced are assigned to the caller.
1301 ERROR_SOME_NOT_MAPPED
Some mapping between account names and security IDs was not done.
1302 ERROR_NO_QUOTAS_FOR_ACCOUNT
No system quota limits are specifically set for this account.
1303 ERROR_LOCAL_USER_SESSION_KEY
No encryption key is available. A well-known encryption key was re-
turned.
1304 ERROR_NULL_LM_PASSWORD
The Windows password is too complex to be converted to a LAN Man-
ager password. The LAN Manager password returned is a NULL string.
1305 ERROR_UNKNOWN_REVISION
The revision level is unknown.
1306 ERROR_REVISION_MISMATCH
Indicates two revision levels are incompatible.
1307 ERROR_INVALID_OWNER
This security ID may not be assigned as the owner of this object.
1308 ERROR_INVALID_PRIMARY_GROUP
This security ID may not be assigned as the primary group of an object.

168
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1309 ERROR_NO_IMPERSONATION_TOKEN
An attempt has been made to operate on an impersonation token by a
thread that is not currently impersonating a client.
1310 ERROR_CANT_DISABLE_MANDATORY
The group may not be disabled.
1311 ERROR_NO_LOGON_SERVERS
There are currently no logon servers available to service the logon re-
quest.
1312 ERROR_NO_SUCH_LOGON_SESSION
A specified logon session does not exist. It may already have been ter-
minated.
1313 ERROR_NO_SUCH_PRIVILEGE
A specified privilege does not exist.
1314 ERROR_PRIVILEGE_NOT_HELD
A required privilege is not held by the client.
1315 ERROR_INVALID_ACCOUNT_NAME
The name provided is not a properly formed account name.
1316 ERROR_USER_EXISTS
The specified user already exists.
1317 ERROR_NO_SUCH_USER
The specified user does not exist.
1318 ERROR_GROUP_EXISTS
The specified group already exists.
1319 ERROR_NO_SUCH_GROUP
The specified group does not exist.
1321 ERROR_MEMBER_NOT_IN_GROUP
The specified user account is not a member of the specified group ac-
count.
1322 ERROR_LAST_ADMIN
The last remaining administration account cannot be disabled or deleted.
1323 ERROR_WRONG_PASSWORD
Unable to update the password. The value provided as the current pass-
word is incorrect.
1324 ERROR_ILL_FORMED_PASSWORD
Unable to update the password. The value provided for the new password
contains values that are not allowed in passwords.
1325 ERROR_PASSWORD_RESTRICTION
Unable to update the password because a password update rule has been
violated.

169
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1326 ERROR_LOGON_FAILURE
Logon failure: unknown user name or bad password.
1327 ERROR_ACCOUNT_RESTRICTION
Logon failure: user account restriction.
1328 ERROR_INVALID_LOGON_HOURS
Logon failure: account logon time restriction violation.
1329 ERROR_INVALID_WORKSTATION
Logon failure: user not allowed to log on to this computer.
1330 ERROR_PASSWORD_EXPIRED
Logon failure: the specified account password has expired.
1331 ERROR_ACCOUNT_DISABLED
Logon failure: account currently disabled.
1332 ERROR_NONE_MAPPED
No mapping between account names and security IDs was done.
1333 ERROR_TOO_MANY_LUIDS_REQUESTED
Too many local user identifiers (LUIDs) were requested at one time.
1334 ERROR_LUIDS_EXHAUSTED
No more local user identifiers (LUIDs) are available.
1335 ERROR_INVALID_SUB_AUTHORITY
The subauthority part of a security ID is invalid for this particular use.
1336 ERROR_INVALID_ACL
The access control list (ACL) structure is invalid.
1337 ERROR_INVALID_SID
The security ID structure is invalid.
1338 ERROR_INVALID_SECURITY_DESCR
The security descriptor structure is invalid.
1340 ERROR_BAD_INHERITANCE_ACL
The inherited access control list (ACL) or access control entry (ACE)
could not be built.
1341 ERROR_SERVER_DISABLED
The server is currently disabled.
1342 ERROR_SERVER_NOT_DISABLED
The server is currently enabled.
1343 ERROR_INVALID_ID_AUTHORITY
The value provided was an invalid value for an identifier authority.
1344 ERROR_ALLOTTED_SPACE_EXCEEDED
No more memory is available for security information updates.
1347 ERROR_CANT_OPEN_ANONYMOUS
Cannot open an anonymous level security token.

170
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1348 ERROR_BAD_VALIDATION_CLASS
The validation information class requested was invalid.
1349 ERROR_BAD_TOKEN_TYPE
The type of the token is inappropriate for its attempted use.
1350 ERROR_NO_SECURITY_ON_OBJECT
Unable to perform a security operation on an object that has no associated
security.
1352 ERROR_INVALID_SERVER_STATE
The security account manager (SAM) or local security authority (LSA)
server was in the wrong state to perform the security operation.
1353 ERROR_INVALID_DOMAIN_STATE
The domain was in the wrong state to perform the security operation.
1354 ERROR_INVALID_DOMAIN_ROLE
This operation is only allowed for the Primary Domain Controller of the
domain.
1355 ERROR_NO_SUCH_DOMAIN
The specified domain did not exist.
1356 ERROR_DOMAIN_EXISTS
The specified domain already exists.
1357 ERROR_DOMAIN_LIMIT_EXCEEDED
An attempt was made to exceed the limit on the number of domains per
server.
1358 ERROR_INTERNAL_DB_CORRUPTION
Unable to complete the requested operation because of either a catastroph-
ic media failure or a data structure corruption on the disk.
1359 ERROR_INTERNAL_ERROR
The security account database contains an internal inconsistency.
1360 ERROR_GENERIC_NOT_MAPPED
Generic access types were contained in an access mask which should
already be mapped to nongeneric types.
1361 ERROR_BAD_DESCRIPTOR_FORMAT
A security descriptor is not in the right format (absolute or self-relative).
1362 ERROR_NOT_LOGON_PROCESS
The requested action is restricted for use by logon processes only. The
calling process has not registered as a logon process.
1363 ERROR_LOGON_SESSION_EXISTS
Cannot start a new logon session with an ID that is already in use.
1364 ERROR_NO_SUCH_PACKAGE
A specified authentication package is unknown.

171
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1365 ERROR_BAD_LOGON_SESSION_STAT
The logon session is not in a state that is consistent with the requested
operation.
1366 ERROR_LOGON_SESSION_COLLISION
The logon session ID is already in use.
1367 ERROR_INVALID_LOGON_TYPE
A logon request contained an invalid logon type value.
1368 ERROR_CANNOT_IMPERSONATE
Unable to impersonate using a named pipe until data has been read from
that pipe.
1369 ERROR_RXACT_INVALID_STATE
The transaction state of a registry subtree is incompatible with the reques-
ted operation.
1370 ERROR_RXACT_COMMIT_FAILURE
An internal security database corruption has been encountered.
1371 ERROR_SPECIAL_ACCOUNT
Cannot perform this operation on built-in accounts.
1372 ERROR_SPECIAL_GROUP
Cannot perform this operation on this built-in special group.
1373 ERROR_SPECIAL_USER
Cannot perform this operation on this built-in special user.
1374 ERROR_MEMBERS_PRIMARY_GROUP
The user cannot be removed from a group because the group is currently
the user's primary group.
1375 ERROR_TOKEN_ALREADY_IN_USE
The token is already in use as a primary token.
1376 ERROR_NO_SUCH_ALIAS
The specified local group does not exist.
1377 ERROR_MEMBER_NOT_IN_ALIAS
The specified account name is not a member of the local group.
1378 ERROR_MEMBER_IN_ALIAS
The specified account name is already a member of the local group.
1379 ERROR_ALIAS_EXISTS
The specified local group already exists.
1380 ERROR_LOGON_NOT_GRANTED
Logon failure: the user has not been granted the requested logon type at
this computer.
1381 ERROR_TOO_MANY_SECRETS
The maximum number of secrets that may be stored in a single system
has been exceeded.

172
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1382 ERROR_SECRET_TOO_LONG
The length of a secret exceeds the maximum length allowed.
1383 ERROR_INTERNAL_DB_ERROR
The local security authority database contains an internal inconsistency.
1385 ERROR_LOGON_TYPE_NOT_GRANTED
Logon failure: the user has not been granted the requested logon type at
this computer.
1386 ERROR_NT_CROSS_ENCRYPTION_REQUIRED
A cross-encrypted password is necessary to change a user password.
1387 ERROR_NO_SUCH_MEMBER
A new member could not be added to a local group because the member
does not exist.
1388 ERROR_INVALID_MEMBER
A new member could not be added to a local group because the member
has the wrong account type.
1389 ERROR_TOO_MANY_SIDS
Too many security IDs have been specified.
1390 ERROR_LM_CROSS_ENCRYPTION_REQUIRED
A cross-encrypted password is necessary to change this user password.
1391 ERROR_NO_INHERITANCE
Indicates an ACL contains no inheritable components.
1392 ERROR_FILE_CORRUPT
The file or directory is corrupted and unreadable.
1393 ERROR_DISK_CORRUPT
The disk structure is corrupted and unreadable.
1394 ERROR_NO_USER_SESSION_KEY
There is no user session key for the specified logon session.
1395 ERROR_LICENSE_QUOTA_EXCEEDED
The service being accessed is licensed for a particular number of connec-
tions. No more connections can be made to the service at this time be-
cause there are already as many connections as the service.
1396 ERROR_WRONG_TARGET_NAME
Logon Failure: The target account name is incorrect.
1397 ERROR_MUTUAL_AUTH_FAILED
Mutual Authentication failed. The server's password is out of date at the
domain controller.
1398 ERROR_TIME_SKEW
There is a time difference between the client and server.
1400 ERROR_INVALID_WINDOW_HANDLE
Invalid window handle.

173
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1401 ERROR_INVALID_MENU_HANDLE
Invalid menu handle.
1402 ERROR_INVALID_CURSOR_HANDLE
Invalid cursor handle.
1403 ERROR_INVALID_ACCEL_HANDLE
Invalid accelerator table handle.
1404 ERROR_INVALID_HOOK_HANDLE
Invalid hook handle.
1405 ERROR_INVALID_DWP_HANDLE
Invalid handle to a multiple-window position structure.
1406 ERROR_TLW_WITH_WSCHILD
Cannot create a top-level child window.
1407 ERROR_CANNOT_FIND_WND_CLASS
Cannot find window class.
1408 ERROR_WINDOW_OF_OTHER_THREAD
Invalid window. The window belongs to another thread.
1409 ERROR_HOTKEY_ALREADY_REGISTERED
Hot key is already registered.
1410 ERROR_CLASS_ALREADY_EXISTS
Class already exists.
1411 ERROR_CLASS_DOES_NOT_EXIST
Class does not exist.
1412 ERROR_CLASS_HAS_WINDOWS
Class still has open windows.
1413 ERROR_INVALID_INDEX
Invalid index.
1414 ERROR_INVALID_ICON_HANDLE
Invalid icon handle.
1415 ERROR_PRIVATE_DIALOG_INDEX
Using private DIALOG window words.
1416 ERROR_LISTBOX_ID_NOT_FOUND
The list box identifier was not found.
1417 ERROR_NO_WILDCARD_CHARACTERS
No wildcards were found.
1418 ERROR_CLIPBOARD_NOT_OPEN
Thread does not have a clipboard open.
1419 ERROR_HOTKEY_NOT_REGISTERED
Hot key is not registered.

174
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1420 ERROR_WINDOW_NOT_DIALOG
The window is not a valid dialog window.
1421 ERROR_CONTROL_ID_NOT_FOUND
Control ID not found.
1422 ERROR_INVALID_COMBOBOX_MESSAG
Invalid message for a combo box because it does not have an edit control.
1423 ERROR_WINDOW_NOT_COMBOBOX
The window is not a combo box.
1424 ERROR_INVALID_EDIT_HEIGHT
Height must be less than 256.
1425 ERROR_DC_NOT_FOUND
Invalid device context (DC) handle.
1426 ERROR_INVALID_HOOK_FILTER
Invalid hook procedure type.
1427 ERROR_INVALID_FILTER_PROC
Invalid hook procedure.
1428 ERROR_HOOK_NEEDS_HMOD
Cannot set nonlocal hook without a module handle.
1429 ERROR_GLOBAL_ONLY_HOOK
This hook procedure can only be set globally.
1430 ERROR_JOURNAL_HOOK_SET
The journal hook procedure is already installed.
1431 ERROR_HOOK_NOT_INSTALLED
The hook procedure is not installed.
1432 ERROR_INVALID_LB_MESSAGE
Invalid message for single-selection list box.
1433 ERROR_SETCOUNT_ON_BAD_LB
LB_SETCOUNT sent to non-lazy list box.
1434 ERROR_LB_WITHOUT_TABSTOPS
This list box does not support tab stops.
1435 ERROR_DESTROY_OBJECT_OF_OTHER_THREAD
Cannot destroy object created by another thread.
1436 ERROR_CHILD_WINDOW_MENU
Child windows cannot have menus.
1437 ERROR_NO_SYSTEM_MENU
The window does not have a system menu.
1438 ERROR_INVALID_MSGBOX_STYLE
Invalid message box style.

175
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1439 ERROR_INVALID_SPI_VALUE
Invalid system-wide (SPI_*) parameter.
1440 ERROR_SCREEN_ALREADY_LOCKED
Screen already locked.
1441 ERROR_HWNDS_HAVE_DIFF_PARENT
All handles to windows in a multiple-window position structure must
have the same parent.
1442 ERROR_NOT_CHILD_WINDOW
The window is not a child window.
1443 ERROR_INVALID_GW_COMMAND
Invalid GW_* command.
1444 ERROR_INVALID_THREAD_ID
Invalid thread identifier.
1445 ERROR_NON_MDICHILD_WINDOW
Cannot process a message from a window that is not a multiple document
interface (MDI) window.
1446 ERROR_POPUP_ALREADY_ACTIVE
Popup menu already active.
1447 ERROR_NO_SCROLLBARS
The window does not have scroll bars.
1448 ERROR_INVALID_SCROLLBAR_RANGE
Scroll bar range cannot be greater than 0x7FFF.
1449 ERROR_INVALID_SHOWWIN_COMMAND
Cannot show or remove the window in the way specified.
1450 ERROR_NO_SYSTEM_RESOURCES
Insufficient system resources exist to complete the requested service.
1451 ERROR_NONPAGED_SYSTEM_RESOURCES
Insufficient system resources exist to complete the requested service.
1452 ERROR_PAGED_SYSTEM_RESOURCES
Insufficient system resources exist to complete the requested service.
1453 ERROR_WORKING_SET_QUOTA
Insufficient quota to complete the requested service.
1454 ERROR_PAGEFILE_QUOTA
Insufficient quota to complete the requested service.
1455 ERROR_COMMITMENT_LIMIT
The paging file is too small for this operation to complete.
1456 ERROR_MENU_ITEM_NOT_FOUND
A menu item was not found.

176
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1457 ERROR_INVALID_KEYBOARD_HANDLE
Invalid keyboard layout handle.
1458 ERROR_HOOK_TYPE_NOT_ALLOWED
Hook type not allowed.
1459 ERROR_REQUIRES_INTERACTIVE_WINDOWSTATION
This operation requires an interactive window station.
1460 ERROR_TIMEOUT
This operation returned because the timeout period expired.
1461 ERROR_INVALID_MONITOR_HANDLE
Invalid monitor handle.
1500 ERROR_EVENTLOG_FILE_CORRUPT
The event log file is corrupted.
1502 ERROR_LOG_FILE_FULL
The event log file is full.
1503 ERROR_EVENTLOG_FILE_CHANGED
The event log file has changed between read operations.
1601 ERROR_INSTALL_SERVICE_FAILURE
Failure accessing installation service.
1602 ERROR_INSTALL_USEREXIT
User cancelled installation.
1603 ERROR_INSTALL_FAILURE
Fatal error during installation.
1605 ERROR_UNKNOWN_PRODUCT
Product is not installed.
1606 ERROR_UNKNOWN_FEATURE
Feature ID not registered.
1607 ERROR_UNKNOWN_COMPONENT
Component ID not registered.
1608 ERROR_UNKNOWN_PROPERTY
Unknown property.
1609 ERROR_INVALID_HANDLE_STATE
Handle is in an invalid state.
1610 ERROR_BAD_CONFIGURATION
Configuration data corrupt.
1611 ERROR_INDEX_ABSENT
Component qualifier not present.
1612 ERROR_INSTALL_SOURCE_ABSENT
Install source unavailable.

177
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1613 ERROR_INSTALL_PACKAGE_VERSION
Database version unsupported.
1614 ERROR_PRODUCT_UNINSTALLED
Product is uninstalled.
1615 ERROR_BAD_QUERY_SYNTAX
SQL query syntax invalid or unsupported.
1616 ERROR_INVALID_FIELD
Record field does not exist.
1617 ERROR_DEVICE_REMOVED
The device has been removed.
1618 ERROR_INSTALL_ALREADY_RUNNING
An installation is in progress.
1619 ERROR_INSTALL_PACKAGE_OPEN_FAILED
Installation package could not be opened.
1620 ERROR_INSTALL_PACKAGE_INVALID
Installation package invalid.
1621 ERROR_INSTALL_UI_FAILURE
Could not initialize installer user interface.
1622 ERROR_INSTALL_LOG_FAILURE
Error opening installation log file.
1623 ERROR_INSTALL_LANGUAGE_UNSUPPORTED
Product language not supported by system.
1624 ERROR_INSTALL_TRANSFORM_FAILURE
Error applying transform to install package.
1625 ERROR_INSTALL_PACKAGE_REJECTED
Install package signature not accepted.
1626 ERROR_FUNCTION_NOT_CALLED
Function could not be executed.
1627 ERROR_FUNCTION_FAILED
Function failed during execution.
1628 ERROR_INVALID_TABLE
Invalid or unknown table specified.
1629 ERROR_DATATYPE_MISMATCH
Data supplied is of wrong type.
1630 ERROR_UNSUPPORTED_TYPE
Data of this type is not supported.
1631 ERROR_CREATE_FAILED
Unable to create requested object.

178
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1632 ERROR_INSTALL_TEMP_UNWRITABLE
Temp folder is full or inaccessible.
1633 ERROR_INSTALL_PLATFORM_UNSUPPORTED
Product platform not supported.
1634 ERROR_INSTALL_NOTUSED
Component not used on this computer.
1635 ERROR_PATCH_PACKAGE_OPEN_FAILED
Patch package could not be opened.
1636 ERROR_PATCH_PACKAGE_INVALID
Patch package invalid.
1637 ERROR_PATCH_PACKAGE_UNSUPPORTED
Patch package unsupported.
1638 ERROR_INVALID_COMMAND_LINE
Invalid command line argument.
1700 RPC_S_INVALID_STRING_BINDING
The string binding is invalid.
1701 RPC_S_WRONG_KIND_OF_BINDING
The binding handle is not the correct type.
1702 RPC_S_INVALID_BINDING
The binding handle is invalid.
1703 RPC_S_PROTSEQ_NOT_SUPPORTED
The RPC protocol sequence is not supported.
1704 RPC_S_INVALID_RPC_PROTSEQ
The RPC protocol sequence is invalid.
1705 RPC_S_INVALID_STRING_UUID
The string universal unique identifier (UUID) is invalid.
1706 RPC_S_INVALID_ENDPOINT_FORMAT
The endpoint format is invalid.
1707 RPC_S_INVALID_NET_ADDR
The network address is invalid.
1708 RPC_S_NO_ENDPOINT_FOUND
No endpoint was found.
1709 RPC_S_INVALID_TIMEOUT
The timeout value is invalid.
1710 RPC_S_OBJECT_NOT_FOUND
The object universal unique identifier (UUID) was not found.
1711 RPC_S_ALREADY_REGISTERED
The object universal unique identifier (UUID) has already been re-
gistered.

179
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1712 RPC_S_TYPE_ALREADY_REGISTERED
The type universal unique identifier (UUID) has already been registered.
1713 RPC_S_ALREADY_LISTENING
The RPC server is already listening.
1714 RPC_S_NO_PROTSEQS_REGISTERED
No protocol sequences have been registered.
1715 RPC_S_NOT_LISTENING
The RPC server is not listening.
1716 RPC_S_UNKNOWN_MGR_TYPE
The manager type is unknown.
1717 RPC_S_UNKNOWN_IF
The interface is unknown.
1718 RPC_S_NO_BINDINGS
There are no bindings.
1719 RPC_S_NO_PROTSEQS
There are no protocol sequences.
1720 RPC_S_CANT_CREATE_ENDPOINT
The endpoint cannot be created.
1721 RPC_S_OUT_OF_RESOURCES
Not enough resources are available to complete this operation.
1722 RPC_S_SERVER_UNAVAILABLE
The RPC server is unavailable.
1723 RPC_S_SERVER_TOO_BUSY
The RPC server is too busy to complete this operation.
1724 RPC_S_INVALID_NETWORK_OPTIONS
The network options are invalid.
1725 RPC_S_NO_CALL_ACTIVE
There are no remote procedure calls active on this thread.
1726 RPC_S_CALL_FAILED
The remote procedure call failed.
1727 RPC_S_CALL_FAILED_DNE
The remote procedure call failed and did not execute.
1728 RPC_S_PROTOCOL_ERROR
A remote procedure call (RPC) protocol error occurred.
1730 RPC_S_UNSUPPORTED_TRANS_SYN
The transfer syntax is not supported by the RPC server.
1732 RPC_S_UNSUPPORTED_TYPE
The universal unique identifier (UUID) type is not supported.

180
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1733 RPC_S_INVALID_TAG
The tag is invalid.
1734 RPC_S_INVALID_BOUND
The array bounds are invalid.
1735 RPC_S_NO_ENTRY_NAME
The binding does not contain an entry name.
1736 RPC_S_INVALID_NAME_SYNTAX
The name syntax is invalid.
1737 RPC_S_UNSUPPORTED_NAME_SYNTAX
The name syntax is not supported.
1739 RPC_S_UUID_NO_ADDRESS
No network address is available to use to construct a universal unique
identifier (UUID).
1740 RPC_S_DUPLICATE_ENDPOINT
The endpoint is a duplicate.
1741 RPC_S_UNKNOWN_AUTHN_TYPE
The authentication type is unknown.
1742 RPC_S_MAX_CALLS_TOO_SMALL
The maximum number of calls is too small.
1743 RPC_S_STRING_TOO_LONG
The string is too long.
1744 RPC_S_PROTSEQ_NOT_FOUND
The RPC protocol sequence was not found.
1745 RPC_S_PROCNUM_OUT_OF_RANGE
The procedure number is out of range.
1746 RPC_S_BINDING_HAS_NO_AUTH
The binding does not contain any authentication information.
1747 RPC_S_UNKNOWN_AUTHN_SERVICE
The authentication service is unknown.
1748 RPC_S_UNKNOWN_AUTHN_LEVEL
The authentication level is unknown.
1749 RPC_S_INVALID_AUTH_IDENTITY
The security context is invalid.
1750 RPC_S_UNKNOWN_AUTHZ_SERVICE
The authorization service is unknown.
1751 EPT_S_INVALID_ENTRY
The entry is invalid.
1752 EPT_S_CANT_PERFORM_OP
The server endpoint cannot perform the operation.

181
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1753 EPT_S_NOT_REGISTERED
There are no more endpoints available from the endpoint mapper.
1754 RPC_S_NOTHING_TO_EXPORT
No interfaces have been exported.
1755 RPC_S_INCOMPLETE_NAME
The entry name is incomplete.
1756 RPC_S_INVALID_VERS_OPTION
The version option is invalid.
1757 RPC_S_NO_MORE_MEMBERS
There are no more members.
1758 RPC_S_NOT_ALL_OBJS_UNEXPORTED
There is nothing to unexport.
1759 RPC_S_INTERFACE_NOT_FOUND
The interface was not found.
1760 RPC_S_ENTRY_ALREADY_EXISTS
The entry already exists.
1761 RPC_S_ENTRY_NOT_FOUND
The entry is not found.
1762 RPC_S_NAME_SERVICE_UNAVAILABLE
The name service is unavailable.
1763 RPC_S_INVALID_NAF_ID
The network address family is invalid.
1764 RPC_S_CANNOT_SUPPORT
The requested operation is not supported.
1765 RPC_S_NO_CONTEXT_AVAILABLE
No security context is available to allow impersonation.
1766 RPC_S_INTERNAL_ERROR
An internal error occurred in a remote procedure call (RPC).
1767 RPC_S_ZERO_DIVIDE
The RPC server attempted an integer division by zero.
1768 RPC_S_ADDRESS_ERROR
An addressing error occurred in the RPC server.
1769 RPC_S_FP_DIV_ZERO
A floating-point operation at the RPC server caused a division by zero.
1770 RPC_S_FP_UNDERFLOW
A floating-point underflow occurred at the RPC server.
1771 RPC_S_FP_OVERFLOW
A floating-point overflow occurred at the RPC server.

182
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1772 RPC_X_NO_MORE_ENTRIES
The list of RPC servers available for the binding of auto handles has
been exhausted.
1773 RPC_X_SS_CHAR_TRANS_OPEN_FAIL
Unable to open the character translation table file.
1774 RPC_X_SS_CHAR_TRANS_SHORT_FILE
The file containing the character translation table has fewer than 512
bytes.
1775 RPC_X_SS_IN_NULL_CONTEXT
A null context handle was passed from the client to the host during a
remote procedure call.
1777 RPC_X_SS_CONTEXT_DAMAGED
The context handle changed during a remote procedure call.
1778 RPC_X_SS_HANDLES_MISMATCH
The binding handles passed to a remote procedure call do not match.
1779 RPC_X_SS_CANNOT_GET_CALL_HANDLE
The stub is unable to get the remote procedure call handle.
1780 RPC_X_NULL_REF_POINTER
A null reference pointer was passed to the stub.
1781 RPC_X_ENUM_VALUE_OUT_OF_RANGE
The enumeration value is out of range.
1782 RPC_X_BYTE_COUNT_TOO_SMALL
The byte count is too small.
1783 RPC_X_BAD_STUB_DATA
The stub received bad data.
1784 ERROR_INVALID_USER_BUFFER
The supplied user buffer is not valid for the requested operation.
1785 ERROR_UNRECOGNIZED_MEDIA
The disk media is not recognized. It may not be formatted.
1786 ERROR_NO_TRUST_LSA_SECRET
The workstation does not have a trust secret.
1787 ERROR_NO_TRUST_SAM_ACCOUNT
The SAM database on the Windows NT Server does not have a computer
account for this workstation trust relationship.
1788 ERROR_TRUSTED_DOMAIN_FAILURE
The trust relationship between the primary domain and the trusted domain
failed.
1789 ERROR_TRUSTED_RELATIONSHIP_FAILURE
The trust relationship between this workstation and the primary domain
failed.

183
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1790 ERROR_TRUST_FAILURE
The network logon failed.
1791 RPC_S_CALL_IN_PROGRESS
A remote procedure call is already in progress for this thread.
1793 ERROR_ACCOUNT_EXPIRED
The user's account has expired.
1794 ERROR_REDIRECTOR_HAS_OPEN_HANDLES
The redirector is in use and cannot be unloaded.
1795 ERROR_PRINTER_DRIVER_ALREADY_INSTALLED
The specified printer driver is already installed.
1796 ERROR_UNKNOWN_PORT
The specified port is unknown.
1797 ERROR_UNKNOWN_PRINTER_DRIVER
The printer driver is unknown.
1798 ERROR_UNKNOWN_PRINTPROCESSOR
The print processor is unknown.
1799 ERROR_INVALID_SEPARATOR_FILE
The specified separator file is invalid.
1800 ERROR_INVALID_PRIORITY
The specified priority is invalid.
1801 ERROR_INVALID_PRINTER_NAME
The printer name is invalid.
1802 ERROR_PRINTER_ALREADY_EXISTS
The printer already exists.
1803 ERROR_INVALID_PRINTER_COMMAND
The printer command is invalid.
1804 ERROR_INVALID_DATATYPE
The specified datatype is invalid.
1805 ERROR_INVALID_ENVIRONMENT
The environment specified is invalid.
1806 RPC_S_NO_MORE_BINDINGS
There are no more bindings.
1807 ERROR_NOLOGON_INTERDOMAIN_TRUST_ACCOUNT
The account used is an interdomain trust account. Use the global user
account or local user account to access this server.
1808 ERROR_NOLOGON_WORKSTATION_TRUST_ACCOUNT
The account used is a computer account. Use the global user account or
local user account to access this server.

184
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1809 ERROR_NOLOGON_SERVER_TRUST_ACCOUNT
The account used is a server trust account. Use the global user account
or local user account to access this server.
1810 ERROR_DOMAIN_TRUST_INCONSISTENT
The name or security ID (SID) of the domain specified is inconsistent
with the trust information for that domain.
1811 ERROR_SERVER_HAS_OPEN_HANDLES
The server is in use and cannot be unloaded.
1812 ERROR_RESOURCE_DATA_NOT_FOUND
The specified image file did not contain a resource section.
1813 ERROR_RESOURCE_TYPE_NOT_FOUND
The specified resource type cannot be found in the image file.
1814 ERROR_RESOURCE_NAME_NOT_FOUND
The specified resource name cannot be found in the image file.
1815 ERROR_RESOURCE_LANG_NOT_FOUND
The specified resource language ID cannot be found in the image file.
1816 ERROR_NOT_ENOUGH_QUOTA
Not enough quota is available to process this command.
1817 RPC_S_NO_INTERFACES
No interfaces have been registered.
1818 RPC_S_CALL_CANCELLED
The remote procedure call was cancelled.
1819 RPC_S_BINDING_INCOMPLETE
The binding handle does not contain all required information.
1820 RPC_S_COMM_FAILURE
A communications failure occurred during a remote procedure call.
1821 RPC_S_UNSUPPORTED_AUTHN_LEVEL
The requested authentication level is not supported.
1822 RPC_S_NO_PRINC_NAME
No principal name registered.
1823 RPC_S_NOT_RPC_ERROR
The error specified is not a valid Windows RPC error code.
1824 RPC_S_UUID_LOCAL_ONLY
A UUID that is valid only on this computer has been allocated.
1825 RPC_S_SEC_PKG_ERROR
A security package specific error occurred.
1826 RPC_S_NOT_CANCELLED
Thread is not canceled.

185
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

1827 RPC_X_INVALID_ES_ACTION
Invalid operation on the encoding/decoding handle.
1828 RPC_X_WRONG_ES_VERSION
Incompatible version of the serializing package.
1829 RPC_X_WRONG_STUB_VERSION
Incompatible version of the RPC stub.
1830 RPC_X_INVALID_PIPE_OBJECT
The RPC pipe object is invalid or corrupted.
1831 RPC_X_WRONG_PIPE_ORDER
An invalid operation was attempted on an RPC pipe object.
1832 RPC_X_WRONG_PIPE_VERSION
Unsupported RPC pipe version.
1898 RPC_S_GROUP_MEMBER_NOT_FOUND
The group member was not found.
1899 EPT_S_CANT_CREATE
The endpoint mapper database entry could not be created.
1900 RPC_S_INVALID_OBJECT
The object universal unique identifier (UUID) is the nil UUID.
1901 ERROR_INVALID_TIME
The specified time is invalid.
1902 ERROR_INVALID_FORM_NAME
The specified form name is invalid.
1903 ERROR_INVALID_FORM_SIZE
The specified form size is invalid.
1904 ERROR_ALREADY_WAITING
The specified printer handle is already being waited on.
1905 ERROR_PRINTER_DELETED
The specified printer has been deleted.
1906 ERROR_INVALID_PRINTER_STATE
The state of the printer is invalid.
1907 ERROR_PASSWORD_MUST_CHANGE
The user must change his password before logging on the first time.
1908 ERROR_DOMAIN_CONTROLLER_NOT_FOUND
Could not find the domain controller for this domain.
1909 ERROR_ACCOUNT_LOCKED_OUT
The referenced account is currently locked out and may not be logged
on to.
1910 OR_INVALID_OXID
The object exporter specified was not found.

186
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

1911 OR_INVALID_OID
The object specified was not found.
1912 OR_INVALID_SET
The object resolver set specified was not found.
1913 RPC_S_SEND_INCOMPLETE
Some data remains to be sent in the request buffer.
1914 RPC_S_INVALID_ASYNC_HANDLE
Invalid asynchronous remote procedure call handle.
1915 RPC_S_INVALID_ASYNC_CALL
Invalid asynchronous RPC call handle for this operation.
1916 RPC_X_PIPE_CLOSED
The RPC pipe object has already been closed.
1917 RPC_X_PIPE_DISCIPLINE_ERROR
The RPC call completed before all pipes were processed.
1918 RPC_X_PIPE_EMPTY
No more data is available from the RPC pipe.
1919 ERROR_NO_SITENAME
No site name is available for this machine.
1920 ERROR_CANT_ACCESS_FILE
The file can not be accessed by the system.
1921 ERROR_CANT_RESOLVE_FILENAME
The name of the file cannot be resolved by the system.
1922 RPC_S_ENTRY_TYPE_MISMATCH
The entry is not of the expected type.
1923 RPC_S_NOT_ALL_OBJS_EXPORTED
Not all object UUIDs could be exported to the specified entry.
1924 RPC_S_INTERFACE_NOT_EXPORTED
Interface could not be exported to the specified entry.
1925 RPC_S_PROFILE_NOT_ADDED
The specified profile entry could not be added.
1926 RPC_S_PRF_ELT_NOT_ADDED
The specified profile element could not be added.
1927 RPC_S_PRF_ELT_NOT_REMOVED
The specified profile element could not be removed.
1928 RPC_S_GRP_ELT_NOT_ADDED
The group element could not be added.
1929 RPC_S_GRP_ELT_NOT_REMOVED
The group element could not be removed.

187
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

2000 ERROR_INVALID_PIXEL_FORMAT
The pixel format is invalid.
2001 ERROR_BAD_DRIVER
The specified driver is invalid.
2002 ERROR_INVALID_WINDOW_STYLE
The window style or class attribute is invalid for this operation.
2003 ERROR_METAFILE_NOT_SUPPORTED
The requested metafile operation is not supported.
2004 ERROR_TRANSFORM_NOT_SUPPORTED
The requested transformation operation is not supported.
2005 ERROR_CLIPPING_NOT_SUPPORTED
The requested clipping operation is not supported.
2010 ERROR_INVALID_CMM
The specified color management module is invalid.
2011 ERROR_INVALID_PROFILE
The specified color profile is invalid.
2012 ERROR_TAG_NOT_FOUND
The specified tag was not found.
2013 ERROR_TAG_NOT_PRESENT
A required tag is not present.
2014 ERROR_DUPLICATE_TAG
The specified tag is already present.
2015 ERROR_PROFILE_NOT_ASSOCIATED_WITH_DEVICE
The specified color profile is not associated with any device.
2016 ERROR_PROFILE_NOT_FOUND
The specified color profile was not found.
2017 ERROR_INVALID_COLORSPACE
The specified color space is invalid.
2018 ERROR_ICM_NOT_ENABLED
Image Color Management is not enabled.
2019 ERROR_DELETING_ICM_XFORM
There was an error while deleting the color transform.
2020 ERROR_INVALID_TRANSFORM
The specified color transform is invalid.
2021 ERROR_COLORSPACE_MISMATCH
The specified transform does not match the bitmap' s color space.
2022 ERROR_INVALID_COLORINDEX
The specified named color index is not present in the profile.

188
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

2202 ERROR_BAD_USERNAME
The specified username is invalid.
2250 ERROR_NOT_CONNECTED
This network connection does not exist.
2401 ERROR_OPEN_FILES
This network connection has files open or requests pending.
2402 ERROR_ACTIVE_CONNECTIONS
Active connections still exist.
2404 ERROR_DEVICE_IN_USE
The device is in use by an active process and cannot be disconnected.
3000 ERROR_UNKNOWN_PRINT_MONITOR
The specified print monitor is unknown.
3001 ERROR_PRINTER_DRIVER_IN_USE
The specified printer driver is currently in use.
3002 ERROR_SPOOL_FILE_NOT_FOUND
The spool file was not found.
3003 ERROR_SPL_NO_STARTDOC
A StartDocPrinter call was not issued.
3004 ERROR_SPL_NO_ADDJOB
An AddJob call was not issued.
3005 ERROR_PRINT_PROCESSOR_ALREADY_INSTALLED
The specified print processor has already been installed.
3006 ERROR_PRINT_MONITOR_ALREADY_INSTALLED
The specified print monitor has already been installed.
3007 ERROR_INVALID_PRINT_MONITOR
The specified print monitor does not have the required functions.
3008 ERROR_PRINT_MONITOR_IN_USE
The specified print monitor is currently in use.
3009 ERROR_PRINTER_HAS_JOBS_QUEUED
The requested operation is not allowed when there are jobs queued to
the printer.
3010 ERROR_SUCCESS_REBOOT_REQUIRED
The requested operation is successful. Changes will not be effective
until the system is rebooted.
3011 ERROR_SUCCESS_RESTART_REQUIRED
The requested operation is successful. Changes will not be effective
until the service is restarted.
3012 ERROR_PRINTER_NOT_FOUND
No printers were found.

189
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4000 ERROR_WINS_INTERNAL
WINS encountered an error while processing the command.
4001 ERROR_CAN_NOT_DEL_LOCAL_WINS
The local WINS can not be deleted.
4002 ERROR_STATIC_INIT
The importation from the file failed.
4003 ERROR_INC_BACKUP
The backup failed. Was a full backup done before?
4004 ERROR_FULL_BACKUP
The backup failed. Check the directory to which you are backing the
database.
4005 ERROR_REC_NON_EXISTENT
The name does not exist in the WINS database.
4006 ERROR_RPL_NOT_ALLOWED
Replication with a nonconfigured partner is not allowed.
4100 ERROR_DHCP_ADDRESS_CONFLICT
The DHCP client has obtained an IP address that is already in use on
the network. The local interface will be disabled until the DHCP client
can obtain a new address.
4200 ERROR_WMI_GUID_NOT_FOUND
The GUID passed was not recognized as valid by a WMI data provider.
4201 ERROR_WMI_INSTANCE_NOT_FOUND
The instance name passed was not recognized as valid by a WMI data
provider.
4202 ERROR_WMI_ITEMID_NOT_FOUND
The data item ID passed was not recognized as valid by a WMI data
provider.
4203 ERROR_WMI_TRY_AGAIN
The WMI request could not be completed and should be retried.
4204 ERROR_WMI_DP_NOT_FOUND
The WMI data provider could not be located.
4205 ERROR_WMI_UNRESOLVED_INSTANCE_REF
The WMI data provider references an instance set that has not been re-
gistered.
4206 ERROR_WMI_ALREADY_ENABLED
The WMI data block or event notification has already been enabled.
4207 ERROR_WMI_GUID_DISCONNECTED
The WMI data block is no longer available.
4208 ERROR_WMI_SERVER_UNAVAILABLE
The WMI data service is not available.

190
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

4209 ERROR_WMI_DP_FAILED
The WMI data provider failed to carry out the request.
4210 ERROR_WMI_INVALID_MOF
The WMI MOF information is not valid.
4211 ERROR_WMI_INVALID_REGINFO
The WMI registration information is not valid.
4212 ERROR_WMI_ALREADY_DISABLED
The WMI data block or event notification has already been disabled.
4213 ERROR_WMI_READ_ONLY
The WMI data item or data block is read only.
4214 ERROR_WMI_SET_FAILURE
The WMI data item or data block could not be changed.
4300 ERROR_INVALID_MEDIA
The media identifier does not represent a valid medium.
4301 ERROR_INVALID_LIBRARY
The library identifier does not represent a valid library.
4302 ERROR_INVALID_MEDIA_POOL
The media pool identifier does not represent a valid media pool.
4303 ERROR_DRIVE_MEDIA_MISMATCH
The drive and medium are not compatible or exist in different libraries.
4304 ERROR_MEDIA_OFFLINE
The medium currently exists in an offline library and must be online to
perform this operation.
4305 ERROR_LIBRARY_OFFLINE
The operation cannot be performed on an offline library.
4308 ERROR_MEDIA_UNAVAILABLE
No media is currently available in this media pool or library.
4309 ERROR_RESOURCE_DISABLED
A resource required for this operation is disabled.
4310 ERROR_INVALID_CLEANER
The media identifier does not represent a valid cleaner.
4311 ERROR_UNABLE_TO_CLEAN
The drive cannot be cleaned or does not support cleaning.
4312 ERROR_OBJECT_NOT_FOUND
The object identifier does not represent a valid object.
4313 ERROR_DATABASE_FAILURE
Unable to read from or write to the database.
4314 ERROR_DATABASE_FULL
The database is full.

191
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4315 ERROR_MEDIA_INCOMPATIBLE
The medium is not compatible with the device or media pool.
4316 ERROR_RESOURCE_NOT_PRESENT
The resource required for this operation does not exist.
4317 ERROR_INVALID_OPERATION
The operation identifier is not valid.
4318 ERROR_MEDIA_NOT_AVAILABLE
The media is not mounted or ready for use.
4319 ERROR_DEVICE_NOT_AVAILABLE
The device is not ready for use.
4320 ERROR_REQUEST_REFUSED
The operator or administrator has refused the request.
4321 ERROR_INVALID_DRIVE_OBJECT
The drive identifier does not represent a valid drive.
4322 ERROR_LIBRARY_FULL
Library is full. No slot is available for use.
4323 ERROR_MEDIUM_NOT_ACCESSIBLE
The transport cannot access the medium.
4324 ERROR_UNABLE_TO_LOAD_MEDIUM
Unable to load the medium into the drive.
4325 ERROR_UNABLE_TO_INVENTORY_DRIVE
Unable to retrieve status about the drive.
4326 ERROR_UNABLE_TO_INVENTORY_SLOT
Unable to retrieve status about the slot.
4327 ERROR_UNABLE_TO_INVENTORY_TRANSPORT
Unable to retrieve status about the transport.
4328 ERROR_TRANSPORT_FULL
Cannot use the transport because it is already in use.
4329 ERROR_CONTROLLING_IEPORT
Unable to open or close the inject/eject port.
4330 ERROR_UNABLE_TO_EJECT_MOUNTED_MEDIA
Unable to eject the media because it is in a drive.
4331 ERROR_CLEANER_SLOT_SET
A cleaner slot is already reserved.
4332 ERROR_CLEANER_SLOT_NOT_SET
A cleaner slot is not reserved.
4333 ERROR_CLEANER_CARTRIDGE_SPENT
The cleaner cartridge has performed the maximum number of drive
cleanings.

192
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

4334 ERROR_UNEXPECTED_OMID
Unexpected on-medium identifier.
4335 ERROR_CANT_DELETE_LAST_ITEM
The last remaining item in this group or resource cannot be deleted.
4336 ERROR_MESSAGE_EXCEEDS_MAX_SIZE
The message provided exceeds the maximum size allowed for this
parameter.
4337 ERROR_VOLUME_CONTAINS_SYS_FILES
The volume contains system or paging files.
4338 ERROR_INDIGENOUS_TYPE
The media type cannot be removed from this library since at least one
drive in the library reports it can support this media type.
4339 ERROR_NO_SUPPORTING_DRIVES
This offline media cannot be mounted on this system since no enabled
drives are present which can be used.
4350 ERROR_FILE_OFFLINE
The remote storage service was not able to recall the file.
4351 ERROR_REMOTE_STORAGE_NOT_ACTIVE
The remote storage service is not operational at this time.
4352 ERROR_REMOTE_STORAGE_MEDIA_ERROR
The remote storage service encountered a media error.
4390 ERROR_NOT_A_REPARSE_POINT
The file or directory is not a reparse point.
4391 ERROR_REPARSE_ATTRIBUTE_CONFLICT
The reparse point attribute cannot be set because it conflicts with an
existing attribute.
4392 ERROR_INVALID_REPARSE_DATA
The data present in the reparse point buffer is invalid.
4393 ERROR_REPARSE_TAG_INVALID
The tag present in the reparse point buffer is invalid.
4394 ERROR_REPARSE_TAG_MISMATCH
There is a mismatch between the tag specified in the request and the tag
present in the reparse point.
5001 ERROR_DEPENDENT_RESOURCE_EXISTS
The cluster resource cannot be moved to another group because other
resources are dependent on it.
5002 ERROR_DEPENDENCY_NOT_FOUND
The cluster resource dependency cannot be found.

193
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

5003 ERROR_DEPENDENCY_ALREADY_EXISTS
The cluster resource cannot be made dependent on the specified resource
because it is already dependent.
5004 ERROR_RESOURCE_NOT_ONLINE
The cluster resource is not online.
5005 ERROR_HOST_NODE_NOT_AVAILABLE
A cluster node is not available for this operation.
5006 ERROR_RESOURCE_NOT_AVAILABLE
The cluster resource is not available.
5007 ERROR_RESOURCE_NOT_FOUND
The cluster resource could not be found.
5008 ERROR_SHUTDOWN_CLUSTER
The cluster is being shut down.
5009 ERROR_CANT_EVICT_ACTIVE_NODE
A cluster node cannot be evicted from the cluster while it is online.
5010 ERROR_OBJECT_ALREADY_EXISTS
The object already exists.
5011 ERROR_OBJECT_IN_LIST
The object is already in the list.
5012 ERROR_GROUP_NOT_AVAILABLE
The cluster group is not available for any new requests.
5013 ERROR_GROUP_NOT_FOUND
The cluster group could not be found.
5014 ERROR_GROUP_NOT_ONLINE
The operation could not be completed because the cluster group is not
online.
5015 ERROR_HOST_NODE_NOT_RESOURCE_OWNER
The cluster node is not the owner of the resource.
5016 ERROR_HOST_NODE_NOT_GROUP_OWNER
The cluster node is not the owner of the group.
5017 ERROR_RESMON_CREATE_FAILED
The cluster resource could not be created in the specified resource
monitor.
5018 ERROR_RESMON_ONLINE_FAILED
The cluster resource could not be brought online by the resource monitor.
5019 ERROR_RESOURCE_ONLINE
The operation could not be completed because the cluster resource is
online.

194
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

5020 ERROR_QUORUM_RESOURCE
The cluster resource could not be deleted or brought offline because it
is the quorum resource.
5021 ERROR_NOT_QUORUM_CAPABLE
The cluster could not make the specified resource a quorum resource
because it is not capable of being a quorum resource.
5022 ERROR_CLUSTER_SHUTTING_DOWN
The cluster software is shutting down.
5023 ERROR_INVALID_STATE
The group or resource is not in the correct state to perform the requested
operation.
5024 ERROR_RESOURCE_PROPERTIES_STORED
The properties were stored but not all changes will take effect until the
next time the resource is brought online.
5025 ERROR_NOT_QUORUM_CLASS
The cluster could not make the specified resource a quorum resource
because it does not belong to a shared storage class.
5026 ERROR_CORE_RESOURCE
The cluster resource could not be deleted since it is a core resource.
5027 ERROR_QUORUM_RESOURCE_ONLINE_FAILED
The quorum resource failed to come online.
5028 ERROR_QUORUMLOG_OPEN_FAILED
The quorum log could not be created or mounted successfully.
5029 ERROR_CLUSTERLOG_CORRUPT
The cluster log is corrupt.
5030 ERROR_CLUSTERLOG_RECORD_EXCEEDS_MAXSIZE
The record could not be written to the cluster log since it exceeds the
maximum size.
5031 ERROR_CLUSTERLOG_EXCEEDS_MAXSIZE
The cluster log exceeds its maximum size.
5032 ERROR_CLUSTERLOG_CHKPOINT_NOT_FOUND
No checkpoint record was found in the cluster log.
5033 ERROR_CLUSTERLOG_NOT_ENOUGH_SPACE
The minimum required disk space needed for logging is not available.
5035 ERROR_NETWORK_NOT_AVAILABLE
A cluster network is not available for this operation.
5036 ERROR_NODE_NOT_AVAILABLE
A cluster node is not available for this operation.
5037 ERROR_ALL_NODES_NOT_AVAILABLE
All cluster nodes must be running to perform this operation.

195
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

5038 ERROR_RESOURCE_FAILED
A cluster resource failed.
5039 ERROR_CLUSTER_INVALID_NODE
The cluster node is not valid.
5040 ERROR_CLUSTER_NODE_EXISTS
The cluster node already exists.
5041 ERROR_CLUSTER_JOIN_IN_PROGRESS
A node is in the process of joining the cluster.
5042 ERROR_CLUSTER_NODE_NOT_FOUND
The cluster node was not found.
5043 ERROR_CLUSTER_LOCAL_NODE_NOT_FOUND
The cluster local node information was not found.
5044 ERROR_CLUSTER_NETWORK_EXISTS
The cluster network already exists.
5045 ERROR_CLUSTER_NETWORK_NOT_FOUND
The cluster network was not found.
5046 ERROR_CLUSTER_NETINTERFACE_EXISTS
The cluster network interface already exists.
5047 ERROR_CLUSTER_NETINTERFACE_NOT_FOUND
The cluster network interface was not found.
5048 ERROR_CLUSTER_INVALID_REQUEST
The cluster request is not valid for this object.
5049 ERROR_CLUSTER_INVALID_NETWORK_PROVIDER
The cluster network provider is not valid.
5050 ERROR_CLUSTER_NODE_DOWN
The cluster node is down.
5051 ERROR_CLUSTER_NODE_UNREACHABLE
The cluster node is not reachable.
5052 ERROR_CLUSTER_NODE_NOT_MEMBER
The cluster node is not a member of the cluster.
5053 ERROR_CLUSTER_JOIN_NOT_IN_PROGRESS
A cluster join operation is not in progress.
5054 ERROR_CLUSTER_INVALID_NETWORK
The cluster network is not valid.
5056 ERROR_CLUSTER_NODE_UP
The cluster node is up.
5057 ERROR_CLUSTER_IPADDR_IN_USE
The cluster IP address is already in use.

196
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

5058 ERROR_CLUSTER_NODE_NOT_PAUSED
The cluster node is not paused.
5059 ERROR_CLUSTER_NO_SECURITY_CONTEXT
No cluster security context is available.
5060 ERROR_CLUSTER_NETWORK_NOT_INTERNAL
The cluster network is not configured for internal cluster communication.
5061 ERROR_CLUSTER_NODE_ALREADY_UP
The cluster node is already up.
5062 ERROR_CLUSTER_NODE_ALREADY_DOWN
The cluster node is already down.
5063 ERROR_CLUSTER_NETWORK_ALREADY_ONLINE
The cluster network is already online.
5064 ERROR_CLUSTER_NETWORK_ALREADY_OFFLINE
The cluster network is already offline.
5065 ERROR_CLUSTER_NODE_ALREADY_MEMBER
The cluster node is already a member of the cluster.
5066 ERROR_CLUSTER_LAST_INTERNAL_NETWORK
The cluster network is the only one configured for internal cluster com-
munication between two or more active cluster nodes. The internal
communication capability cannot be removed from the network.
5067 ERROR_CLUSTER_NETWORK_HAS_DEPENDENTS
One or more cluster resources depend on the network to provide service
to clients. The client access capability cannot be removed from the net-
work.
5068 ERROR_INVALID_OPERATION_ON_QUORUM
This operation cannot be performed on the cluster resource as it the
quorum resource. The quorum resource cannot be brought offline, or
modify its possible owners list cannot be modified.
5069 ERROR_DEPENDENCY_NOT_ALLOWED
The cluster quorum resource is not allowed to have any dependencies.
5070 ERROR_CLUSTER_NODE_PAUSED
The cluster node is paused.
5071 ERROR_NODE_CANT_HOST_RESOURCE
The cluster resource cannot be brought online. The owner node cannot
run this resource.
5072 ERROR_CLUSTER_NODE_NOT_READY
The cluster node is not ready to perform the requested operation.
5073 ERROR_CLUSTER_NODE_SHUTTING_DOWN
The cluster node is shutting down.

197
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

5074 ERROR_CLUSTER_JOIN_ABORTED
The cluster join operation was aborted.
5075 ERROR_CLUSTER_INCOMPATIBLE_VERSIONS
The cluster join operation failed due to incompatible software versions
between the joining node and its sponsor.
5076 ERROR_CLUSTER_MAXNUM_OF_RESOURCES_EXCEEDED
This resource cannot be created because the cluster has reached the
limit on the number of resources it can monitor.
5077 ERROR_CLUSTER_SYSTEM_CONFIG_CHANGED
The system configuration changed during the cluster join or form oper-
ation. The join or form operation was aborted.
5078 ERROR_CLUSTER_RESOURCE_TYPE_NOT_FOUND
The specified resource type was not found.
5079 ERROR_CLUSTER_RESTYPE_NOT_SUPPORTED
The specified node does not support a resource of this type. This may
be due to version inconsistencies or due to the absence of the resource
DLL on this node.
5080 ERROR_CLUSTER_RESNAME_NOT_FOUND
The specified resource name is supported by this resource DLL. This
may be due to a bad (or changed) name supplied to the resource DLL.
5081 ERROR_CLUSTER_NO_RPC_PACKAGES_REGISTERED
No authentication package could be registered with the RPC server.
5083 ERROR_CLUSTER_DATABASE_SEQMISMATCH
The join operation failed because the cluster database sequence number
has changed or is incompatible with the locker node. This may happen
during a join operation if the cluster database was changing.
5084 ERROR_RESMON_INVALID_STATE
The resource monitor will not allow the fail operation to be performed
while the resource is in its current state. This may happen if the resource
is in a pending state.
6000 ERROR_ENCRYPTION_FAILED
The specified file could not be encrypted.
6001 ERROR_DECRYPTION_FAILED
The specified file could not be decrypted.
6002 ERROR_FILE_ENCRYPTED
The specified file is encrypted and the user does not have the ability to
decrypt it.
6003 ERROR_NO_RECOVERY_POLICY
There is no encryption recovery policy configured for this system.
6004 ERROR_NO_EFS
The required encryption driver is not loaded for this system.

198
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

6005 ERROR_WRONG_EFS
The file was encrypted with a different encryption driver than is currently
loaded.
6006 ERROR_NO_USER_KEYS
There are no EFS keys defined for the user.
6007 ERROR_FILE_NOT_ENCRYPTED
The specified file is not encrypted.
6008 ERROR_NOT_EXPORT_FORMAT
The specified file is not in the defined EFS export format.
6009 ERROR_FILE_READ_ONLY
The specified file is read only.
6118 ERROR_NO_BROWSER_SERVERS_FOUND
The list of servers for this workgroup is not currently available.
7001 ERROR_CTX_WINSTATION_NAME_INVALID
The specified session name is invalid.
7002 ERROR_CTX_INVALID_PD
The specified protocol driver is invalid.
7003 ERROR_CTX_PD_NOT_FOUND
The specified protocol driver was not found in the system path.
7004 ERROR_CTX_WD_NOT_FOUND
The specified terminal connection driver was not found in the system
path.
7005 ERROR_CTX_CANNOT_MAKE_EVENTLOG_ENTRY
A registry key for event logging could not be created for this session.
7006 ERROR_CTX_SERVICE_NAME_COLLISION
A service with the same name already exists on the system.
7007 ERROR_CTX_CLOSE_PENDING
A close operation is pending on the session.
7008 ERROR_CTX_NO_OUTBUF
There are no free output buffers available.
7009 ERROR_CTX_MODEM_INF_NOT_FOUND
The MODEM.INF file was not found.
7010 ERROR_CTX_INVALID_MODEMNAME
The modem name was not found in MODEM.INF.
7011 ERROR_CTX_MODEM_RESPONSE_ERROR
The modem did not accept the command sent to it. Verify that the con-
figured modem name matches the attached modem.
7012 ERROR_CTX_MODEM_RESPONSE_TIMEOUT
The modem did not respond to the command sent to it. Verify that the
modem is properly cabled and powered on.

199
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

7013 ERROR_CTX_MODEM_RESPONSE_NO_CARRIER
Carrier detect has failed or carrier has been dropped due to disconnect.
7014 ERROR_CTX_MODEM_RESPONSE_NO_DIALTONE
Dial tone not detected within the required time. Verify that the phone
cable is properly attached and functional.
7015 ERROR_CTX_MODEM_RESPONSE_BUSY
Busy signal detected at remote site on callback.
7016 ERROR_CTX_MODEM_RESPONSE_VOICE
Voice detected at remote site on callback.
7017 ERROR_CTX_TD_ERROR
Transport driver error.
7022 ERROR_CTX_WINSTATION_NOT_FOUND
The specified session cannot be found.
7023 ERROR_CTX_WINSTATION_ALREADY_EXISTS
The specified session name is already in use.
7025 ERROR_CTX_BAD_VIDEO_MODE
An attempt has been made to connect to a session whose video mode is
not supported by the current client.
7035 ERROR_CTX_GRAPHICS_INVALID
The application attempted to enable DOS graphics mode. DOS graphics
mode is not supported.
7037 ERROR_CTX_LOGON_DISABLED
The user's interactive logon privilege has been disabled. Please contact
the administrator.
7038 ERROR_CTX_NOT_CONSOLE
The requested operation can be performed only on the system console.
This is most often the result of a driver or system DLL requiring direct
console access.
7040 ERROR_CTX_CLIENT_QUERY_TIMEOUT
The client failed to respond to the server connect message.
7041 ERROR_CTX_CONSOLE_DISCONNECT
Disconnecting the console session is not supported.
7042 ERROR_CTX_CONSOLE_CONNECT
Reconnecting a disconnected session to the console is not supported.
7044 ERROR_CTX_SHADOW_DENIED
The request to shadow another session was denied.
7045 ERROR_CTX_WINSTATION_ACCESS_DENIED
The requested session access is denied.
7049 ERROR_CTX_INVALID_WD
The specified terminal connection driver is invalid.

200
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

7051 ERROR_CTX_SHADOW_DISABLED
The requested session is not configured to allow shadowing.
7054 ERROR_CTX_LICENSE_NOT_AVAILABLE
The system has reached its licensed logon limit. Please try again later.
7055 ERROR_CTX_LICENSE_CLIENT_INVALID
The client that is being used is not licensed to use this system. Logon
request is denied.
7056 ERROR_CTX_LICENSE_EXPIRED
The system license has expired. Logon request is denied.
8001 FRS_ERR_INVALID_API_SEQUENCE
The file replication service API was called incorrectly.
8002 FRS_ERR_STARTING_SERVICE
The file replication service cannot be started.
8003 FRS_ERR_STOPPING_SERVICE
The file replication service cannot be stopped.
8004 FRS_ERR_INTERNAL_API
The file replication service API terminated the request.
8005 FRS_ERR_INTERNAL
The file replication service terminated the request.
8006 FRS_ERR_SERVICE_COMM
The file replication service cannot be contacted.
8007 FRS_ERR_INSUFFICIENT_PRIV
The file replication service cannot satisfy the request because the user
is not a member of the Administrators group.
8008 FRS_ERR_AUTHENTICATION
The file replication service cannot satisfy the request because authentic-
ated RPC is not available.
8009 FRS_ERR_PARENT_INSUFFICIENT_PRIV
The file replication service cannot satisfy the request because the user
is not a member of Administrators group on the domain controller.
8010 FRS_ERR_PARENT_AUTHENTICATION
The file replication service cannot satisfy the request because authentic-
ated RPC is not available on the domain controller.
8011 FRS_ERR_CHILD_TO_PARENT_COMM
The file replication service cannot communicate with the file replication
service on the domain controller.
8012 FRS_ERR_PARENT_TO_CHILD_COMM
The file replication service on the domain controller cannot communicate
with the file replication service on this computer.

201
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

8013 FRS_ERR_SYSVOL_POPULATE
The file replication service cannot populate the system volume because
of an internal error.
8014 FRS_ERR_SYSVOL_POPULATE_TIMEOUT
The file replication service cannot populate the system volume because
of an internal timeout.
8015 FRS_ERR_SYSVOL_IS_BUSY
The file replication service cannot process the request. The system
volume is busy with a previous request.
8016 FRS_ERR_SYSVOL_DEMOTE
The file replication service cannot stop replicating the system volume
because of an internal error.
8017 FRS_ERR_INVALID_SERVICE_PARAMETER
The file replication service detected an invalid parameter.
8201 ERROR_DS_MEMBERSHIP_EVALUATED_LOCALLY
The directory service evaluated group memberships locally.
8202 ERROR_DS_NO_ATTRIBUTE_OR_VALUE
The specified directory service attribute or value does not exist.
8203 ERROR_DS_INVALID_ATTRIBUTE_SYNTAX
The attribute syntax specified to the directory service is invalid.
8204 ERROR_DS_ATTRIBUTE_TYPE_UNDEFINED
The attribute type specified to the directory service is not defined.
8205 ERROR_DS_ATTRIBUTE_OR_VALUE_EXISTS
The specified directory service attribute or value already exists.
8206 ERROR_DS_BUSY
The directory service is busy.
8207 ERROR_DS_UNAVAILABLE
The directory service is unavailable.
8208 ERROR_DS_NO_RIDS_ALLOCATED
The directory service was unable to allocate a relative identifier.
8209 ERROR_DS_NO_MORE_RIDS
The directory service has exhausted the pool of relative identifiers.
8210 ERROR_DS_INCORRECT_ROLE_OWNER
The requested operation could not be performed because the directory
service is not the master for that type of operation.
8211 ERROR_DS_RIDMGR_INIT_ERROR
The directory service was unable to initialize the subsystem that allocates
relative identifiers.

202
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

8212 ERROR_DS_OBJ_CLASS_VIOLATION
The requested operation did not satisfy one or more constraints associated
with the class of the object.
8213 ERROR_DS_CANT_ON_NON_LEAF
The directory service can perform the requested operation only on a leaf
object.
8214 ERROR_DS_CANT_ON_RDN
The directory service cannot perform the requested operation on the
RDN attribute of an object.
8215 ERROR_DS_CANT_MOD_OBJ_CLASS
The directory service detected an attempt to modify the object class of
an object.
8216 ERROR_DS_CROSS_DOM_MOVE_ERROR
The requested cross-domain move operation could not be performed.
8217 ERROR_DS_GC_NOT_AVAILABLE
Unable to contact the global catalog server.
8218 ERROR_SHARED_POLICY
The policy object is shared and can only be modified at the root.
8219 ERROR_POLICY_OBJECT_NOT_FOUND
The policy object does not exist.
8220 ERROR_POLICY_ONLY_IN_DS
The requested policy information is only in the directory service.
8221 ERROR_PROMOTION_ACTIVE
A domain controller promotion is currently active.
8222 ERROR_NO_PROMOTION_ACTIVE
A domain controller promotion is not currently active.
8224 ERROR_DS_OPERATIONS_ERROR
An operations error occurred.
8225 ERROR_DS_PROTOCOL_ERROR
A protocol error occurred.
8226 ERROR_DS_TIMELIMIT_EXCEEDED
The time limit for this request was exceeded.
8227 ERROR_DS_SIZELIMIT_EXCEEDED
The size limit for this request was exceeded.
8228 ERROR_DS_ADMIN_LIMIT_EXCEEDED
The administrative limit for this request was exceeded.
8229 ERROR_DS_COMPARE_FALSE
The compare response was false.
8230 ERROR_DS_COMPARE_TRUE
The compare response was true.

203
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

8231 ERROR_DS_AUTH_METHOD_NOT_SUPPORTED
The requested authentication method is not supported by the server.
8232 ERROR_DS_STRONG_AUTH_REQUIRED
A more secure authentication method is required for this server.
8233 ERROR_DS_INAPPROPRIATE_AUTH
Inappropriate authentication.
8234 ERROR_DS_AUTH_UNKNOWN
The authentication mechanism is unknown.
8235 ERROR_DS_REFERRAL
A referral was returned from the server.
8236 ERROR_DS_UNAVAILABLE_CRIT_EXTENSION
The server does not support the requested critical extension.
8237 ERROR_DS_CONFIDENTIALITY_REQUIRED
This request requires a secure connection.
8238 ERROR_DS_INAPPROPRIATE_MATCHING
Inappropriate matching.
8239 ERROR_DS_CONSTRAINT_VIOLATION
A constraint violation occurred.
8240 ERROR_DS_NO_SUCH_OBJECT
There is no such object on the server.
8241 ERROR_DS_ALIAS_PROBLEM
There is an alias problem.
8242 ERROR_DS_INVALID_DN_SYNTAX
An invalid dn syntax has been specified.
8243 ERROR_DS_IS_LEAF
The object is a leaf object.
8244 ERROR_DS_ALIAS_DEREF_PROBLEM
There is an alias dereferencing problem.
8245 ERROR_DS_UNWILLING_TO_PERFORM
The server is unwilling to process the request.
8246 ERROR_DS_LOOP_DETECT
A loop has been detected.
8247 ERROR_DS_NAMING_VIOLATION
There is a naming violation.
8248 ERROR_DS_OBJECT_RESULTS_TOO_LARGE
The result set is too large.
8249 ERROR_DS_AFFECTS_MULTIPLE_DSAS
The operation affects multiple DSAs.

204
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

8250 ERROR_DS_SERVER_DOWN
The server is not operational.
8251 ERROR_DS_LOCAL_ERROR
A local error has occurred.
8252 ERROR_DS_ENCODING_ERROR
An encoding error has occurred.
8253 ERROR_DS_DECODING_ERROR
A decoding error has occurred.
8254 ERROR_DS_FILTER_UNKNOWN
The search filter cannot be recognized.
8255 ERROR_DS_PARAM_ERROR
One or more parameters are illegal.
8256 ERROR_DS_NOT_SUPPORTED
The specified method is not supported.
8257 ERROR_DS_NO_RESULTS_RETURNED
No results were returned.
8258 ERROR_DS_CONTROL_NOT_FOUND
The specified control is not supported by the server.
8259 ERROR_DS_CLIENT_LOOP
A referral loop was detected by the client.
8260 ERROR_DS_REFERRAL_LIMIT_EXCEEDED
The preset referral limit was exceeded.
8301 ERROR_DS_ROOT_MUST_BE_NC
The root object must be the head of a naming context. The root object
cannot have an instantiated parent.
8302 ERROR_DS_ADD_REPLICA_INHIBITED
The add replica operation cannot be performed. The naming context
must be writable in order to create the replica.
8303 ERROR_DS_ATT_NOT_DEF_IN_SCHEMA
A reference to an attribute that is not defined in the schema occurred.
8304 ERROR_DS_MAX_OBJ_SIZE_EXCEEDED
The maximum size of an object has been exceeded.
8305 ERROR_DS_OBJ_STRING_NAME_EXISTS
An attempt was made to add an object to the directory with a name that
is already in use.
8306 ERROR_DS_NO_RDN_DEFINED_IN_SCHEMA
An attempt was made to add an object of a class that does not have an
RDN defined in the schema.

205
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

8307 ERROR_DS_RDN_DOESNT_MATCH_SCHEMA
An attempt was made to add an object using an RDN that is not the RDN
defined in the schema.
8308 ERROR_DS_NO_REQUESTED_ATTS_FOUND
None of the requested attributes were found on the objects.
8309 ERROR_DS_USER_BUFFER_TO_SMALL
The user buffer is too small.
8310 ERROR_DS_ATT_IS_NOT_ON_OBJ
The attribute specified in the operation is not present on the object.
8311 ERROR_DS_ILLEGAL_MOD_OPERATION
Illegal modify operation. Some aspect of the modification is not permit-
ted.
8312 ERROR_DS_OBJ_TOO_LARGE
The specified object is too large.
8313 ERROR_DS_BAD_INSTANCE_TYPE
The specified instance type is not valid.
8314 ERROR_DS_MASTERDSA_REQUIRED
The operation must be performed at the master DSA. The DNS root at-
tribute is missing on the cross-reference object.
8315 ERROR_DS_OBJECT_CLASS_REQUIRED
The object class attribute must be specified.
8316 ERROR_DS_MISSING_REQUIRED_ATT
A required attribute is missing.
8317 ERROR_DS_ATT_NOT_DEF_FOR_CLASS
An attempt was made to modify an object to include an attribute that is
not legal for its class.
8318 ERROR_DS_ATT_ALREADY_EXISTS
The specified attribute is already present on the object.
8321 ERROR_DS_SINGLE_VALUE_CONSTRAINT
An attribute's single value constraint has been violated.
8322 ERROR_DS_RANGE_CONSTRAINT
An attribute's range constraint has been violated.
8323 ERROR_DS_ATT_VAL_ALREADY_EXISTS
The specified value already exists.
8324 ERROR_DS_CANT_REM_MISSING_ATT
The attribute cannot be removed because it is not present on the object.
8325 ERROR_DS_CANT_REM_MISSING_ATT_VAL
The attribute value cannot be removed because it is not present on the
object.

206
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

8326 ERROR_DS_ROOT_CANT_BE_SUBREF
The specified root object cannot be a subref.
8327 ERROR_DS_NO_CHAINING
Chaining is not permitted.
8328 ERROR_DS_NO_CHAINED_EVAL
Chained evaluation is not permitted.
8329 ERROR_DS_NO_PARENT_OBJECT
The operation could not be performed because the object's parent is
either uninstantiated or deleted.
8330 ERROR_DS_PARENT_IS_AN_ALIAS
Having a parent that is an alias is not permitted. Aliases are leaf objects.
8332 ERROR_DS_CHILDREN_EXIST
The operation cannot be performed because child objects exist. This
operation can only be performed on a leaf object.
8333 ERROR_DS_OBJ_NOT_FOUND
Directory object not found.
8334 ERROR_DS_ALIASED_OBJ_MISSING
The aliased object is missing.
8335 ERROR_DS_BAD_NAME_SYNTAX
The object name has bad syntax.
8336 ERROR_DS_ALIAS_POINTS_TO_ALIAS
It is not permitted for an alias to refer to another alias.
8337 ERROR_DS_CANT_DEREF_ALIAS
The alias cannot be dereferenced.
8338 ERROR_DS_OUT_OF_SCOPE
The operation is out of scope.
8340 ERROR_DS_CANT_DELETE_DSA_OBJ
The DSA object cannot be deleted.
8341 ERROR_DS_GENERIC_ERROR
A directory service error has occurred.
8342 ERROR_DS_DSA_MUST_BE_INT_MASTER
The operation can only be performed on an internal master DSA object.
8343 ERROR_DS_CLASS_NOT_DSA
The object must be of class DSA.
8344 ERROR_DS_INSUFF_ACCESS_RIGHTS
Insufficient access rights to perform the operation.
8345 ERROR_DS_ILLEGAL_SUPERIOR
The object cannot be added because the parent is not on the list of pos-
sible superiors.

207
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

8346 ERROR_DS_ATTRIBUTE_OWNED_BY_SAM
Access to the attribute is not permitted because the attribute is owned
by the Security Accounts Manager (SAM).
8347 ERROR_DS_NAME_TOO_MANY_PARTS
The name has too many parts.
8348 ERROR_DS_NAME_TOO_LONG
The name is too long.
8349 ERROR_DS_NAME_VALUE_TOO_LONG
The name value is too long.
8350 ERROR_DS_NAME_UNPARSEABLE
The directory service encountered an error parsing a name.
8351 ERROR_DS_NAME_TYPE_UNKNOWN
The directory service cannot get the attribute type for a name.
8352 ERROR_DS_NOT_AN_OBJECT
The name does not identify an object, it identifies a phantom.
8353 ERROR_DS_SEC_DESC_TOO_SHORT
The security descriptor is too short.
8354 ERROR_DS_SEC_DESC_INVALID
The security descriptor is invalid.
8355 ERROR_DS_NO_DELETED_NAME
Failed to create name for deleted object.
8356 ERROR_DS_SUBREF_MUST_HAVE_PARENT
The parent of a new subref must exist.
8357 ERROR_DS_NCNAME_MUST_BE_NC
The object must be a naming context.
8358 ERROR_DS_CANT_ADD_SYSTEM_ONLY
It is not permitted to add an attribute which is owned by the system.
8359 ERROR_DS_CLASS_MUST_BE_CONCRETE
The class of the object must be structural. An abstract class cannot be
instantiated.
8360 ERROR_DS_INVALID_DMD
The schema object could not be found.
8361 ERROR_DS_OBJ_GUID_EXISTS
A local object with this GUID (dead or alive) already exists.
8362 ERROR_DS_NOT_ON_BACKLINK
The operation cannot be performed on a back link.
8363 ERROR_DS_NO_CROSSREF_FOR_NC
The cross reference for the specified naming context could not be found.

208
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

8364 ERROR_DS_SHUTTING_DOWN
The operation could not be performed because the directory service is
shutting down.
8365 ERROR_DS_UNKNOWN_OPERATION
The directory service request is invalid.
8366 ERROR_DS_INVALID_ROLE_OWNER
The role owner attribute could not be read.
8367 ERROR_DS_COULDNT_CONTACT_FSMO
The requested FSMO operation failed. The current FSMO holder could
not be reached.
8368 ERROR_DS_CROSS_NC_DN_RENAME
Modification of a DN across a naming context is not permitted.
8369 ERROR_DS_CANT_MOD_SYSTEM_ONLY
The attribute cannot be modified because it is owned by the system.
8370 ERROR_DS_REPLICATOR_ONLY
Only the replicator can perform this function.
8371 ERROR_DS_OBJ_CLASS_NOT_DEFINED
The specified class is not defined.
8372 ERROR_DS_OBJ_CLASS_NOT_SUBCLASS
The specified class is not a subclass.
8373 ERROR_DS_NAME_REFERENCE_INVALID
The name reference is invalid.
8374 ERROR_DS_CROSS_REF_EXISTS
A cross reference already exists.
8375 ERROR_DS_CANT_DEL_MASTER_CROSSREF
It is not permitted to delete a master cross reference.
8376 ERROR_DS_SUBTREE_NOTIFY_NOT_NC_HEAD
Subtree notifications are only supported on NC heads.
8377 ERROR_DS_NOTIFY_FILTER_TOO_COMPLEX
Notification filter is too complex.
8378 ERROR_DS_DUP_RDN
Schema update failed: duplicate RDN.
8379 ERROR_DS_DUP_OID
Schema update failed: duplicate OID.
8380 ERROR_DS_DUP_MAPI_ID
Schema update failed: duplicate MAPI identifier.
8381 ERROR_DS_DUP_SCHEMA_ID_GUID
Schema update failed: duplicate schema-id GUID.

209
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

8382 ERROR_DS_DUP_LDAP_DISPLAY_NAME
Schema update failed: duplicate LDAP display name.
8383 ERROR_DS_SEMANTIC_ATT_TEST
Schema update failed: range-lower less than range upper.
8384 ERROR_DS_SYNTAX_MISMATCH
Schema update failed: syntax mismatch.
8385 ERROR_DS_EXISTS_IN_MUST_HAVE
Schema deletion failed: attribute is used in must-contain.
8386 ERROR_DS_EXISTS_IN_MAY_HAVE
Schema deletion failed: attribute is used in may-contain.
8387 ERROR_DS_NONEXISTENT_MAY_HAVE
Schema update failed: attribute in may-contain does not exist.
8388 ERROR_DS_NONEXISTENT_MUST_HAVE
Schema update failed: attribute in must-contain does not exist.
8389 ERROR_DS_AUX_CLS_TEST_FAIL
Schema update failed: class in aux-class list does not exist or is not an
auxiliary class.
8390 ERROR_DS_NONEXISTENT_POSS_SUP
Schema update failed: class in poss-superiors does not exist.
8391 ERROR_DS_SUB_CLS_TEST_FAIL
Schema update failed: class in subclassof list does not exist or does not
satisfy hierarchy rules.
8392 ERROR_DS_BAD_RDN_ATT_ID_SYNTAX
Schema update failed: Rdn-Att-Id has wrong syntax.
8393 ERROR_DS_EXISTS_IN_AUX_CLS
Schema deletion failed: class is used as auxiliary class.
8394 ERROR_DS_EXISTS_IN_SUB_CLS
Schema deletion failed: class is used as sub class.
8395 ERROR_DS_EXISTS_IN_POSS_SUP
Schema deletion failed: class is used as poss superior.
8396 ERROR_DS_RECALCSCHEMA_FAILED
Schema update failed in recalculating validation cache.
8397 ERROR_DS_TREE_DELETE_NOT_FINISHED
The tree deletion is not finished.
8398 ERROR_DS_CANT_DELETE
The requested delete operation could not be performed.
8399 ERROR_DS_ATT_SCHEMA_REQ_ID
Cannot read the governs class identifier for the schema record.

210
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

8400 ERROR_DS_BAD_ATT_SCHEMA_SYNTAX
The attribute schema has bad syntax.
8401 ERROR_DS_CANT_CACHE_ATT
The attribute could not be cached.
8402 ERROR_DS_CANT_CACHE_CLASS
The class could not be cached.
8403 ERROR_DS_CANT_REMOVE_ATT_CACHE
The attribute could not be removed from the cache.
8404 ERROR_DS_CANT_REMOVE_CLASS_CACHE
The class could not be removed from the cache.
8405 ERROR_DS_CANT_RETRIEVE_DN
The distinguished name attribute could not be read.
8406 ERROR_DS_MISSING_SUPREF
A required subref is missing.
8407 ERROR_DS_CANT_RETRIEVE_INSTANCE
The instance type attribute could not be retrieved.
8408 ERROR_DS_CODE_INCONSISTENCY
An internal error has occurred.
8409 ERROR_DS_DATABASE_ERROR
A database error has occurred.
8410 ERROR_DS_GOVERNSID_MISSING
The attribute GOVERNSID is missing.
8411 ERROR_DS_MISSING_EXPECTED_ATT
An expected attribute is missing.
8412 ERROR_DS_NCNAME_MISSING_CR_REF
The specified naming context is missing a cross reference.
8413 ERROR_DS_SECURITY_CHECKING_ERROR
A security checking error has occurred.
8414 ERROR_DS_SCHEMA_NOT_LOADED
The schema is not loaded.
8415 ERROR_DS_SCHEMA_ALLOC_FAILED
Schema allocation failed.
8416 ERROR_DS_ATT_SCHEMA_REQ_SYNTAX
Failed to obtain the required syntax for the attribute schema.
8417 ERROR_DS_GCVERIFY_ERROR
The global catalog verification failed. The global catalog is not available
or does not support the operation. Some part of the directory is currently
not available.

211
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

8418 ERROR_DS_DRA_SCHEMA_MISMATCH
The replication operation failed because of a schema mismatch between
the servers involved.
8419 ERROR_DS_CANT_FIND_DSA_OBJ
The DSA object could not be found.
8420 ERROR_DS_CANT_FIND_EXPECTED_NC
The naming context could not be found.
8421 ERROR_DS_CANT_FIND_NC_IN_CACHE
The naming context could not be found in the cache.
8422 ERROR_DS_CANT_RETRIEVE_CHILD
The child object could not be retrieved.
8423 ERROR_DS_SECURITY_ILLEGAL_MODIFY
The modification was not permitted for security reasons.
8424 ERROR_DS_CANT_REPLACE_HIDDEN_REC
The operation cannot replace the hidden record.
8425 ERROR_DS_BAD_HIERARCHY_FILE
The hierarchy file is invalid.
8426 ERROR_DS_BUILD_HIERARCHY_TABLE_FAILED
The attempt to build the hierarchy table failed.
8427 ERROR_DS_CONFIG_PARAM_MISSING
The directory configuration parameter is missing from the registry.
8428 ERROR_DS_COUNTING_AB_INDICES_FAILED
The attempt to count the address book indices failed.
8429 ERROR_DS_HIERARCHY_TABLE_MALLOC_FAILED
The allocation of the hierarchy table failed.
8430 ERROR_DS_INTERNAL_FAILURE
The directory service encountered an internal failure.
8431 ERROR_DS_UNKNOWN_ERROR
The directory service encountered an unknown failure.
8432 ERROR_DS_ROOT_REQUIRES_CLASS_TOP
A root object requires a class of ' top' .
8435 ERROR_DS_UNABLE_TO_SURRENDER_ROLES
The directory service was unable to transfer ownership of one or more
floating single-master operation roles to other servers.
8436 ERROR_DS_DRA_GENERIC
The replication operation failed.
8437 ERROR_DS_DRA_INVALID_PARAMETER
An invalid parameter was specified for this replication operation.

212
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

8438 ERROR_DS_DRA_BUSY
The Windows directory service is too busy to complete the replication
operation at this time.
8439 ERROR_DS_DRA_BAD_DN
The distinguished name specified for this replication operation is invalid.
8440 ERROR_DS_DRA_BAD_NC
The naming context specified for this replication operation is invalid.
8441 ERROR_DS_DRA_DN_EXISTS
The distinguished name specified for this replication operation already
exists.
8442 ERROR_DS_DRA_INTERNAL_ERROR
The replication system encountered an internal error.
8443 ERROR_DS_DRA_INCONSISTENT_DIT
The replication operation encountered a database inconsistency.
8444 ERROR_DS_DRA_CONNECTION_FAILED
The server specified for this replication operation could not be contacted.
8445 ERROR_DS_DRA_BAD_INSTANCE_TYPE
The replication operation encountered an object with an invalid instance
type.
8446 ERROR_DS_DRA_OUT_OF_MEM
The replication operation failed to allocate memory.
8447 ERROR_DS_DRA_MAIL_PROBLEM
The replication operation encountered an error with the mail system.
8448 ERROR_DS_DRA_REF_ALREADY_EXISTS
The replication reference information for the target server already exists.
8449 ERROR_DS_DRA_REF_NOT_FOUND
The replication reference information for the target server does not exist.
8450 ERROR_DS_DRA_OBJ_IS_REP_SOURCE
The naming context cannot be removed because it is replicated to another
server.
8451 ERROR_DS_DRA_DB_ERROR
The replication operation encountered a database error.
8452 ERROR_DS_DRA_NO_REPLICA
The naming context is in the process of being removed or is not replicated
from the specified server.
8453 ERROR_DS_DRA_ACCESS_DENIED
Replication access was denied.
8454 ERROR_DS_DRA_NOT_SUPPORTED
The requested operation is not supported by this version of the Windows
directory service.

213
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

8455 ERROR_DS_DRA_RPC_CANCELLED
The replication remote procedure call was cancelled.
8456 ERROR_DS_DRA_SOURCE_DISABLED
The source server is currently rejecting replication requests.
8457 ERROR_DS_DRA_SINK_DISABLED
The destination server is currently rejecting replication requests.
8458 ERROR_DS_DRA_NAME_COLLISION
The replication operation failed due to a collision of object names.
8459 ERROR_DS_DRA_SOURCE_REINSTALLED
The replication source has been reinstalled.
8460 ERROR_DS_DRA_MISSING_PARENT
The replication operation failed because a required parent object is
missing.
8461 ERROR_DS_DRA_PREEMPTED
The replication operation was preempted.
8462 ERROR_DS_DRA_ABANDON_SYNC
The replication synchronization attempt was abandoned because of a
lack of updates.
8463 ERROR_DS_DRA_SHUTDOWN
The replication operation was terminated because the system is shutting
down.
8464 ERROR_DS_DRA_INCOMPATIBLE_PARTIAL_SET
The replication synchronization attempt failed as the destination partial
attribute set is not a subset of source partial attribute set.
8465 ERROR_DS_DRA_SOURCE_IS_PARTIAL_REPLICA
The replication synchronization attempt failed because a master replica
attempted to sync from a partial replica.
8467 ERROR_DS_INSTALL_SCHEMA_MISMATCH
A schema mismatch is detected between the source and the build used
during a replica install. The replica cannot be installed.
8468 ERROR_DS_DUP_LINK_ID
Schema update failed: An attribute with the same link identifier already
exists.
8469 ERROR_DS_NAME_ERROR_RESOLVING
Name translation: Generic processing error.
8470 ERROR_DS_NAME_ERROR_NOT_FOUND
Name translation: Could not find the name or insufficient right to see
name.
8471 ERROR_DS_NAME_ERROR_NOT_UNIQUE
Name translation: Input name mapped to more than one output name.

214
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

8474 ERROR_DS_NAME_ERROR_NO_SYNTACTICAL_MAPPING
Name translation: Unable to perform purely syntactical mapping at the
client without going out to the wire.
8475 ERROR_DS_CONSTRUCTED_ATT_MOD
Modification of a constructed att is not allowed.
8476 ERROR_DS_WRONG_OM_OBJ_CLASS
The OM-Object-Class specified is incorrect for an attribute with the
specified syntax.
8477 ERROR_DS_DRA_REPL_PENDING
The replication request has been posted; waiting for reply.
8479 ERROR_DS_INVALID_LDAP_DISPLAY_NAME
The LDAP display name of the class or attribute contains non-ASCII
characters.
8480 ERROR_DS_NON_BASE_SEARCH
The requested search operation is only supported for base searches.
8481 ERROR_DS_CANT_RETRIEVE_ATTS
The search failed to retrieve attributes from the database.
8482 ERROR_DS_BACKLINK_WITHOUT_LINK
The schema update operation tried to add a backward link attribute that
has no corresponding forward link.
8483 ERROR_DS_EPOCH_MISMATCH
Source and destination of a cross domain move do not agree on the ob-
ject's epoch number. Either source or destination does not have the latest
version of the object.
8484 ERROR_DS_SRC_NAME_MISMATCH
Source and destination of a cross domain move do not agree on the ob-
ject's current name. Either source or destination does not have the latest
version of the object.
8485 ERROR_DS_SRC_AND_DST_NC_IDENTICAL
Source and destination of a cross domain move operation are identical.
Caller should use local move operation instead of cross domain move
operation.
8486 ERROR_DS_DST_NC_MISMATCH
Source and destination for a cross domain move are not in agreement
on the naming contexts in the forest. Either source or destination does
not have the latest version of the Partitions container.
8487 ERROR_DS_NOT_AUTHORITIVE_FOR_DST_NC
Destination of a cross domain move is not authoritative for the destination
naming context.

215
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

8488 ERROR_DS_SRC_GUID_MISMATCH
Source and destination of a cross domain move do not agree on the
identity of the source object. Either source or destination does not have
the latest version of the source object.
8489 ERROR_DS_CANT_MOVE_DELETED_OBJECT
Object being moved across domains is already known to be deleted by
the destination server. The source server does not have the latest version
of the source object.
8490 ERROR_DS_PDC_OPERATION_IN_PROGRESS
Another operation which requires exclusive access to the PDC PSMO
is already in progress.
8491 ERROR_DS_CROSS_DOMAIN_CLEANUP_REQD
A cross domain move operation failed such that the two versions of the
moved object exist - one each in the source and destination domains.
The destination object needs to be removed to restore the system.
8495 ERROR_DS_CR_IMPOSSIBLE_TO_VALIDATE
The directory cannot validate the proposed naming context name because
it does not hold a replica of the naming context above the proposed
naming context.
8496 ERROR_DS_DST_DOMAIN_NOT_NATIVE
Destination of a cross domain move must be in native mode.
8497 ERROR_DS_MISSING_INFRASTRUCTURE_CONTAINER
The operation cannot be performed because the server does not have an
infrastructure container in the domain of interest.
8498 ERROR_DS_CANT_MOVE_ACCOUNT_GROUP
Cross domain move of account groups is not allowed.
8499 ERROR_DS_CANT_MOVE_RESOURCE_GROUP
Cross domain move of resource groups is not allowed.
8500 ERROR_DS_INVALID_SEARCH_FLAG
The search flags for the attribute are invalid. The ANR bit is valid only
on attributes of Unicode or Teletex strings.
8501 ERROR_DS_NO_TREE_DELETE_ABOVE_NC
Tree deletions starting at an object which has an NC head as a descendant
are not allowed.
8502 ERROR_DS_COULDNT_LOCK_TREE_FOR_DELETE
The directory service failed to lock a tree in preparation for a tree deletion
because the tree was in use.
8503 ERROR_DS_COULDNT_IDENTIFY_OBJECTS_FOR_TREE_DE-
LETE
The directory service failed to identify the list of objects to delete while
attempting a tree deletion.

216
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

8505 ERROR_DS_SENSITIVE_GROUP_VIOLATION
Only an administrator can modify the membership list of an administrat-
ive group.
8506 ERROR_DS_CANT_MOD_PRIMARYGROUPID
Cannot change the primary group ID of a domain controller account.
9001 DNS_ERROR_RCODE_FORMAT_ERROR
DNS server unable to interpret format.
9002 DNS_ERROR_RCODE_SERVER_FAILURE
DNS server failure.
9003 DNS_ERROR_RCODE_NAME_ERROR
DNS name does not exist.
9004 DNS_ERROR_RCODE_NOT_IMPLEMENTED
DNS request not supported by name server.
9005 DNS_ERROR_RCODE_REFUSED
DNS operation refused.
9009 DNS_ERROR_RCODE_NOTAUTH
DNS server not authoritative for zone.
9010 DNS_ERROR_RCODE_NOTZONE
DNS name in update or prereq is not in zone.
9016 DNS_ERROR_RCODE_BADSIG
DNS signature failed to verify.
9017 DNS_ERROR_RCODE_BADKEY
DNS bad key.
9018 DNS_ERROR_RCODE_BADTIME
DNS signature validity expired.
9501 DNS_INFO_NO_RECORDS
No records found for given DNS query.
9502 DNS_ERROR_BAD_PACKET
Bad DNS packet.
9503 DNS_ERROR_NO_PACKET
No DNS packet.
9505 DNS_ERROR_UNSECURE_PACKET
Unsecured DNS packet.
9551 DNS_ERROR_INVALID_TYPE
Invalid DNS type.
9552 DNS_ERROR_INVALID_IP_ADDRESS
Invalid IP address.
9553 DNS_ERROR_INVALID_PROPERTY
Invalid property.

217
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

9554 DNS_ERROR_TRY_AGAIN_LATER
Try DNS operation again later.
9555 DNS_ERROR_NOT_UNIQUE
Record for given name and type is not unique.
9556 DNS_ERROR_NON_RFC_NAME
DNS name does not comply with RFC specifications.
9557 DNS_STATUS_FQDN
DNS name is a fully-qualified DNS name.
9558 DNS_STATUS_DOTTED_NAME
DNS name is dotted (multi-label).
9559 DNS_STATUS_SINGLE_PART_NAME
DNS name is a single-part name.
9601 DNS_ERROR_ZONE_DOES_NOT_EXIST
DNS zone does not exist.
9602 DNS_ERROR_NO_ZONE_INFO
DNS zone information not available.
9603 DNS_ERROR_INVALID_ZONE_OPERATION
Invalid operation for DNS zone.
9604 DNS_ERROR_ZONE_CONFIGURATION_ERROR
Invalid DNS zone configuration.
9605 DNS_ERROR_ZONE_HAS_NO_SOA_RECORD
DNS zone has no start of authority (SOA) record.
9606 DNS_ERROR_ZONE_HAS_NO_NS_RECORDS
DNS zone has no name server (NS) record.
9607 DNS_ERROR_ZONE_LOCKED
DNS zone is locked.
9608 DNS_ERROR_ZONE_CREATION_FAILED
DNS zone creation failed.
9609 DNS_ERROR_ZONE_ALREADY_EXISTS
DNS zone already exists.
9610 DNS_ERROR_AUTOZONE_ALREADY_EXISTS
DNS automatic zone already exists.
9611 DNS_ERROR_INVALID_ZONE_TYPE
Invalid DNS zone type.
9612 DNS_ERROR_SECONDARY_REQUIRES_MASTER_IP
Secondary DNS zone requires master IP address.
9613 DNS_ERROR_ZONE_NOT_SECONDARY
DNS zone not secondary.

218
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

9614 DNS_ERROR_NEED_SECONDARY_ADDRESSES
Need secondary IP address.
9615 DNS_ERROR_WINS_INIT_FAILED
WINS initialization failed.
9616 DNS_ERROR_NEED_WINS_SERVERS
Need WINS servers.
9617 DNS_ERROR_NBSTAT_INIT_FAILED
NBTSTAT initialization call failed.
9618 DNS_ERROR_SOA_DELETE_INVALID
Invalid delete of start of authority (SOA).
9651 DNS_ERROR_PRIMARY_REQUIRES_DATAFILE
Primary DNS zone requires datafile.
9652 DNS_ERROR_INVALID_DATAFILE_NAME
Invalid datafile name for DNS zone.
9653 DNS_ERROR_DATAFILE_OPEN_FAILURE
Failed to open datafile for DNS zone.
9654 DNS_ERROR_FILE_WRITEBACK_FAILED
Failed to write datafile for DNS zone.
9655 DNS_ERROR_DATAFILE_PARSING
Failure while reading datafile for DNS zone.
9701 DNS_ERROR_RECORD_DOES_NOT_EXIST
DNS record does not exist.
9702 DNS_ERROR_RECORD_FORMAT
DNS record format error.
9703 DNS_ERROR_NODE_CREATION_FAILED
Node creation failure in DNS.
9704 DNS_ERROR_UNKNOWN_RECORD_TYPE
Unknown DNS record type.
9705 DNS_ERROR_RECORD_TIMED_OUT
DNS record timed out.
9706 DNS_ERROR_NAME_NOT_IN_ZONE
Name not in DNS zone.
9707 DNS_ERROR_CNAME_LOOP
CNAME loop detected.
9708 DNS_ERROR_NODE_IS_CNAME
Node is a CNAME DNS record.
9709 DNS_ERROR_CNAME_COLLISION
A CNAME record already exists for given name.

219
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

9710 DNS_ERROR_RECORD_ONLY_AT_ZONE_ROOT
Record only at DNS zone root.
9711 DNS_ERROR_RECORD_ALREADY_EXISTS
DNS record already exists.
9712 DNS_ERROR_SECONDARY_DATA
Secondary DNS zone data error.
9713 DNS_ERROR_NO_CREATE_CACHE_DATA
Could not create DNS cache data.
9714 DNS_ERROR_NAME_DOES_NOT_EXIST
DNS name does not exist.
9715 DNS_WARNING_PTR_CREATE_FAILED
Could not create pointer (PTR) record.
9716 DNS_WARNING_DOMAIN_UNDELETED
DNS domain was undeleted.
9717 DNS_ERROR_DS_UNAVAILABLE
The Windows directory service is unavailable.
9718 DNS_ERROR_DS_ZONE_ALREADY_EXISTS
DNS zone already exists in Windows directory service.
9719 DNS_ERROR_NO_BOOTFILE_IF_DS_ZONE
DNS server not creating or reading the boot file for the directory service
integrated DNS zone.
9751 DNS_INFO_AXFR_COMPLETE
DNS AXFR (zone transfer) complete.
9752 DNS_ERROR_AXFR
DNS zone transfer failed.
9753 DNS_INFO_ADDED_LOCAL_WINS
Added local WINS server.
9801 DNS_STATUS_CONTINUE_NEEDED
Secure update call needs to continue update request.
9851 DNS_ERROR_NO_TCPIP
TCP/IP network protocol not installed.
9852 DNS_ERROR_NO_DNS_SERVERS
No DNS servers configured for local system.
10004 WSAEINTR
A blocking operation was interrupted by a call to WSACancelBlockingC-
all.
10009 WSAEBADF
The file handle supplied is not valid.

220
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

10013 WSAEACCES
An attempt was made to access a socket in a way forbidden by its access
permissions.
10014 WSAEFAULT
The system detected an invalid pointer address in attempting to use a
pointer argument in a call.
10022 WSAEINVAL
An invalid argument was supplied.
10024 WSAEMFILE
Too many open sockets.
10035 WSAEWOULDBLOCK
A non-blocking socket operation could not be completed immediately.
10036 WSAEINPROGRESS
A blocking operation is currently executing.
10037 WSAEALREADY
An operation was attempted on a non-blocking socket that already had
an operation in progress.
10038 WSAENOTSOCK
An operation was attempted on something that is not a socket.
10039 WSAEDESTADDRREQ
A required address was omitted from an operation on a socket.
10041 WSAEPROTOTYPE
A protocol was specified in the socket function call that does not support
the semantics of the socket type requested.
10044 WSAESOCKTNOSUPPORT
The support for the specified socket type does not exist in this address
family.
10045 WSAEOPNOTSUPP
The attempted operation is not supported for the type of object referenced.
10046 WSAEPFNOSUPPORT
The protocol family has not been configured into the system or no im-
plementation for it exists.
10047 WSAEAFNOSUPPORT
An address incompatible with the requested protocol was used.
10048 WSAEADDRINUSE
Only one usage of each socket address (protocol/network address/port)
is normally permitted.
10049 WSAEADDRNOTAVAIL
The requested address is not valid in its context.

221
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

10050 WSAENETDOWN
A socket operation encountered a dead network.
10051 WSAENETUNREACH
A socket operation was attempted to an unreachable network.
10052 WSAENETRESET
The connection has been broken due to keep-alive activity detecting a
failure while the operation was in progress.
10053 WSAECONNABORTED
An established connection was aborted by the software in your host
machine.
10054 WSAECONNRESET
An existing connection was forcibly closed by the remote host.
10055 WSAENOBUFS
An operation on a socket could not be performed because the system
lacked sufficient buffer space or because a queue was full.
10056 WSAEISCONN
A connect request was made on an already connected socket.
10057 WSAENOTCONN
A request to send or receive data was disallowed because the socket is
not connected and (when sending on a datagram socket using a sendto
call) no address was supplied.
10058 WSAESHUTDOWN
A request to send or receive data was disallowed because the socket had
already been shut down in that direction with a previous shutdown call.
10059 WSAETOOMANYREFS
Too many references to some kernel object.
10061 WSAECONNREFUSED
No connection could be made because the target machine actively refused
it.
10062 WSAELOOP
Cannot translate name.
10063 WSAENAMETOOLONG
Name component or name was too long.
10064 WSAEHOSTDOWN
A socket operation failed because the destination host was down.
10065 WSAEHOSTUNREACH
A socket operation was attempted to an unreachable host.
10066 WSAENOTEMPTY
Cannot remove a directory that is not empty.

222
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

10067 WSAEPROCLIM
A Windows Sockets implementation may have a limit on the number of
applications that may use it simultaneously.
10068 WSAEUSERS
Ran out of quota.
10069 WSAEDQUOT
Ran out of disk quota.
10070 WSAESTALE
File handle reference is no longer available.
10071 WSAEREMOTE
Item is not available locally.
10091 WSASYSNOTREADY
WSAStartup cannot function at this time because the underlying system
it uses to provide network services is currently unavailable.
10092 WSAVERNOTSUPPORTED
The Windows Sockets version requested is not supported.
10101 WSAEDISCON
Returned by WSARecv or WSARecvFrom to indicate the remote party
has initiated a graceful shutdown sequence.
10102 WSAENOMORE
No more results can be returned by WSALookupServiceNext.
10103 WSAECANCELLED
A call to WSALookupServiceEnd was made while this call was still
processing. The call has been canceled.
10104 WSAEINVALIDPROCTABLE
The procedure call table is invalid.
10105 WSAEINVALIDPROVIDER
The requested service provider is invalid.
10106 WSAEPROVIDERFAILEDINIT
The requested service provider could not be loaded or initialized.
10107 WSASYSCALLFAILURE
A system call that should never fail has failed.
10108 WSASERVICE_NOT_FOUND
No such service is known. The service cannot be found in the specified
name space.
10109 WSATYPE_NOT_FOUND
The specified class was not found.
10110 WSA_E_NO_MORE
No more results can be returned by WSALookupServiceNext.

223
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

10111 WSA_E_CANCELLED
A call to WSALookupServiceEnd was made while this call was still
processing. The call has been canceled.
10112 WSAEREFUSED
A database query failed because it was actively refused.
11001 WSAHOST_NOT_FOUND
No such host is known.
11002 WSATRY_AGAIN
This is usually a temporary error during hostname resolution and means
that the local server did not receive a response from an authoritative
server.
11003 WSANO_RECOVERY
A non-recoverable error occurred during a database lookup.
11005 WSA_QOS_RECEIVERS
At least one reserve has arrived.
11006 WSA_QOS_SENDERS
At least one path has arrived.
11007 WSA_QOS_NO_SENDERS
There are no senders.
11008 WSA_QOS_NO_RECEIVERS
There are no receivers.
11009 WSA_QOS_REQUEST_CONFIRMED
Reserve has been confirmed.
11010 WSA_QOS_ADMISSION_FAILURE
Error due to lack of resources.
11011 WSA_QOS_POLICY_FAILURE
Rejected for administrative reasons, bad credentials.
11012 WSA_QOS_BAD_STYLE
Unknown or conflicting style.
11013 WSA_QOS_BAD_OBJECT
Problem with some part of the filterspec or providerspecific buffer in
general.
11014 WSA_QOS_TRAFFIC_CTRL_ERROR
Problem with some part of the flowspec.
11015 WSA_QOS_GENERIC_ERROR
General QOS error.

224
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

4.5 Data Transfer Status Codes

4.5.1 DDE Status Codes

0 DMLERR_NO_ERROR
16384 DMLERR_ADVACKTIMEOUT
16385 DMLERR_BUSY
16386 DMLERR_DATAACKTIMEOUT
16387 DMLERR_DLL_NOT_INITIALIZED
16388 DMLERR_DLL_USAGE
16389 DMLERR_EXECACKTIMEOUT
16390 DMLERR_INVALID_PARAMETER
16391 DMLERR_LOW_MEMORY
16392 DMLERR_MEMORY_ERROR
16393 DMLERR_NOTPROCESSED
16394 DMLERR_NO_CONV_ESTABLISHED
16395 DMLERR_POKEACKTIMEOUT
16396 DMLERR_POSTMSG_FAILED
16397 DMLERR_REENTRANCY
16398 DMLERR_SERVER_DIED
16399 DMLERR_SYS_ERROR
16400 DMLERR_UNADVACKTIMEOUT
16401 DMLERR_UNFOUND_QUEUE_ID
20483 DMLERR_ITEM_TOO_LONG

4.5.2 ODBC Status Codes

-1 SQL_ERROR
0 SQL_SUCCESS
1 SQL_SUCCESS_WITH_INFO
2 SQL_STILL_EXECUTING
99 SQL_NEED_DATA
100 SQL_NO_DATA_FOUND
2001 SQL_UNSUPPORTED_DATATYPE

225
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

4.5.3 ODBC Error Codes

01000 General warning


01002 Disconnect error
01004 Data truncated
01006 Privilege not revoked
01S02 Option value changed
01S03 No rows updated or deleted
01S04 More than one row updated or deleted
07001 Wrong number of parameters
07006 Restricted data type attribute violation
08001 Unable to connect to data source
08002 Connection in use
08003 Connection not open
08004 Data source rejected establishment of connection
08007 Connection failure during transaction
08S01 Communication link failure
21S01 Insert value list does not match column list
21S02 Degree of derived table does not match column list
22003 Numeric value out of range
22005 Error in assignment
22008 Datetime field overflow
22012 Division by zero
23000 Integrity constraint violation
24000 Invalid cursor state
25000 Invalid transaction state
28000 Invalid authorization specification
34000 Invalid cursor name
37000 Syntax error or access violation
40001 Serialization failure
42000 Syntax error or access violation
IM001 Driver does not support this function
IM002 Data source name not found and no default driver specified
IM003 Specified driver could not be loaded

226
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

IM004 Driver's SQLAllocEnv failed


IM005 Driver's SQLAllocConnect failed
IM006 Driver's SQLSetConnect-Option failed
IM009 Unable to load translation DLL
IM013 Trace file error
S0001 Base table or view already exists
S0002 Base table not found
S0011 Index already exists
S0012 Index not found
S0021 Column already exists
S0022 Column not found
S1000 General error
S1001 Memory allocation failure
S1002 Invalid column number
S1003 Program type out of range
S1008 Operation cancelled
S1009 Invalid argument value
S1010 Function sequence error
S1011 Operation invalid at this time
S1012 Invalid transaction operation code specified
S1090 Invalid string or buffer length
S1092 Option type out of range
S1109 Invalid cursor position
S1C00 Driver not capable
S1T00 Timeout expire

4.6 Status Codes Transmitted by NET to External Devices

4.6.1 Status Codes Transmitted by NET to a PLC

0 OK_STS

227
SYS600 9.4 MicroSCADA Pro 1MRS758116

Status Codes
Technical Description

10H NET_NETWORK_LAYER_ERROR_STS
PLC Error word = 81
a) Error in the reception of an ABM command
b) ABM transmission error in STA-STA communication
20H NET_APPLICATION_LAYER_ERROR_STS
PLC Error word = 82
ABM-SCM transformation error, probably memory area definition error.
30H SPLIT_TOTAL_FAIL_STS
PLC Error word = 83
NET failed to forward a message to the original destination (i.e. the DST
of the original message) and all secondary destinations or at least one
secondary destination (depending on value of SP-attribute).
31H SPLIT_NEAR_TOTAL_FAIL_STS
INTERNAL Status Code:
NET failed to forward a message to the original destination (i.e. the DST
of the original message) but message is forwarded at least to one (not
all) secondary destination. Depending on the value of SP-attribute, the
Status Code sent to substation may be:
SP=1 ==> SPLIT_TOTAL_FAIL_
SP=2 ==> OK_STS
SP=3 ==> SPLIT_TOTAL_FAIL_STS
SP=4 ==> SPLIT_ORIG_DEST_FAIL_STS (Not implemented yet)
SP=5 ==> SPLIT_ORIG_DEST_FAIL_STS (Not implemented yet)
40H SPLIT_ORIG_DEST_FAIL_STS
PLC Error word = 84
NET failed to forward a message to the original destination (i.e. the DST
of the original message).
Depending on the value of SP-attribute, message must be forwarded to
all secondary destinations or at least t one secondary destination.
50H SPLIT_SEC_DEST_FAIL_STS
PLC Error word = 85
Message must be forwarded to the original destination (i.e. the DST of
the original message), but failed to forward it to all secondary destinations
or at least one secondary destination (depending on the value of SP-at-
tribute).

228
1MRS758116 MicroSCADA Pro SYS600 9.4
Issued: 3.6.2016 Status Codes
Version: C/3.6.2016
Technical Description

51H SPLIT_NEAR_SEC_DEST_FAIL_STS
INTERNAL Status Code:
Message must be forwarded to the original destination (i.e. the DST of
the original message) and at least to one (not all) secondary destination.
Depending on the value of SP-attribute, the Status Code sent to substation
may be:
SP=1 ==> SPLIT_SEC_DESTL_FAIL_STS
SP=2 ==> OK_STS
SP=3 ==> OK_STS
SP=4 ==> OK_STS (Not implemented yet)
SP=5 ==> OK_STS (Not implemented yet)
60H SCM_MESSAGE_FORWARDING_FAILURE
PLC Error word = 86
a) SCM message transmission error
b) SCM message routing error
c) SCM message handling error in SCS rev 6.2 and earlier
70H PROC_SCM_MESSAGE_ERROR
PLC Error word = 87
Generated by SCS program (rev 7.0 and later) in certain error situations.
0C0H INVALID_SCM_MESSAGE_ERROR
PLC Error word = 8C
a) The PLC is undefined in NET
b) The PLC does not have the station address defined in NET
c) The PLC is not in use
0D0H INVALID_COMMAND_DESTINATION_STS
PLC Error word = 8D
a) The destinaiton device is undefined in NET
b) The destination device does not have the station address defined in
NET
c) The destination line is undefined in NET
d) The destination line is not in use
0E0H INVALID_DESTINATION_STATION_TYPE_STS
PLC Error word = 8E
Destination device is not STA, SYS or NET.

229
Contact us

1MRS758116 C/3.6.2016 © Copyright 2016 ABB. All rights reserved.


ABB Oy
Grid Automation Products
P.O. Box 614
FI-65101 Vaasa
Finland
Tel. +358 10 22 11
Fax. +358 10 224 1094

www.abb.com/substationautomation