Calculate Size of Diesel Generator 22-8-12

This document calculates the sizing requirements for a diesel generator set based on the connected electrical loads. It lists various loads such as air conditioners, fridges, and lighting along with their power ratings. It then calculates the starting and running power requirements in kVA and kW as well as the starting current. Based on these calculations, it recommends a generator rating of 26kVA. It also provides calculations to determine the diesel generator set efficiency, operating cost per unit of power generated, and approximate fuel consumption rate.

Uploaded by

moosuhaib
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
89 views1 page

Calculate Size of Diesel Generator 22-8-12

This document calculates the sizing requirements for a diesel generator set based on the connected electrical loads. It lists various loads such as air conditioners, fridges, and lighting along with their power ratings. It then calculates the starting and running power requirements in kVA and kW as well as the starting current. Based on these calculations, it recommends a generator rating of 26kVA. It also provides calculations to determine the diesel generator set efficiency, operating cost per unit of power generated, and approximate fuel consumption rate.

Uploaded by

moosuhaib
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

CALCULATE SIZE OF DIESEL GENERATOR SET Jignesh.N.Parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.

com
System Voltage ( P-P ) 415 Volt Linear Load: General Equipments, Heater
System Voltage ( P-N ) 230 Volt Non-Linear Load: UPS,Invertor,Ballast,VFD
Future Load Expansion 0% % 1
Average Intermittent Use of
0.8 (0.7 To 1.0) 0.8
Equipment
Total Connected Load on Diesel Generator Set Starting Condition Running Condition
Load Full Full Full
Sr. Starting Running Diversity Motor Starting Starting Starting
Equipment Load Type Supply Qty Load Load Load
No Load Kw/Hp P.F P.F Factor Starter Amp Kva Kw
Kva Kw Amp RESULTS
AC1 Motor 1Ph 1 2 Kw 0.8 0.8 1 Dol 109 15 12 3 2 11 Starting Kva 33
AC2 Motor 1Ph 1 2 Kw 0.8 0.8 1 Dol 109 15 12 3 2 11 Starting Kw 26
fridge Motor 1Ph 1 0.3 Kw 0.8 0.8 1 Dol 16 2 2 0 0 2 Starting Amp 236
lighting Linear 1Ph 1 0.4 Kw 0.8 0.8 1 2 1 0 1 0 2 Running Kva 6
0 0 0 0 0 0 Running Kw 5
0 0 0 0 0 0 Running Amp 26
0 0 0 0 0 0 Alternator Details
0 0 0 0 0 0 Voltage (P-N) 230
0 0 0 0 0 0 Efficiency 80%
0 0 0 0 0 0 Engine Overload Capacity 130% (Appro 130% To 150%)
0 0 0 0 0 0
0 0 0 0 0 0 Required Generator Rating
0 0 0 0 0 0 Generator KVA 26 (Select D.G near This Value)
0 0 0 0 0 0 Engine KW 5
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0 Calculate D.G Set Efficiency & Unit Calculate Approximate
0 0 0 0 0 0 Rate of Power Fuel Consumption
0 0 0 0 0 0 D.G Size ( Kva ) 1000
0 0 0 0 0 0 D.G P.F 1 D.G Size (Kva) 115
0 0 0 0 0 0 D.G Running Hours 20 D.G P.F 0.8
0 0 0 0 0 0 Diesel Consumption (Liter) 1000 D.G Operation Full Load
0 0 0 0 0 0 KWH Reading of Meter 10000
0 0 0 0 0 0 M.F of KWH Meter 1 Required Diesel
0 0 0 0 0 0 Diesel Rate /Liter (Rs) 40 Liter/Hour 23.11
0 0 0 0 0 0 Efficiency of D.G 63%
0 0 0 0 0 0 KWH/Liter (Unit Per Liter) 10
0 0 0 0 0 0 Unit Rate of Power (Rs) 4.0
0 0 0 0 0 0