TRF
TRF
TRF
Handbook Protection
© ABB Group - 1 -
13-Nov-07
Transformer protection
Power transformers in a power system
400 kV AC Transmission
130 kV Subtransmission
Generation
MV Distribution
LV
© ABB Group - 2 -
M
13-Nov-07
Transformer protection
General
Yy Yd Dy Yd+z
YN yn0 (d1) YN d1 D yn11 YN d11 + zn
© ABB Group - 5 -
13-Nov-07
Transformer protection
Different winding arrangements
x x
U
V
Earth faults
Short-circuits
Inter turn Faults
Core Faults
Tank Faults
Reduced cooling
© ABB Group - 10 -
13-Nov-07
Transformer protection
Abnormal Conditions
Overload
Over voltage
Overexcitation
© ABB Group - 11 -
13-Nov-07
Transformer protection
Differential Protection
Classical application of differential protection
Interposing current transformers for phase shift and
transformation ratio correction
Protection zone, bushing CTs
Influence from OLTC
Harmonic restrained differential protections
© ABB Group - 12 -
13-Nov-07
Transformer protection
Transformer differential protection. Current bias characteristics
I1
< 25
I
High Unrestrained
5
Trips
I2
1 Blocks
I d min
© ABB Group - 13 -
Irestrain
1 5 10 (|I1 |+ |I2 |)/2
13-Nov-07
© ABB Group - 14 -
13-Nov-07
Transformer protection
Transformer protection
Inrush Current
Rise of temperature
0,63
τ
© ABB Group - 24 -
Time
13-Nov-07
Transformer protection
Over excitation protection
Ei = 4.44fNA Bmax
V/ f
( Bmax / Bn) =
Vn / f n
Definite
V/Hz inverse
© ABB Group - 28 -
V/Hz
13-Nov-07
Transformer protection
Time overcurrent relays
Group A Group B
2.3
2.3
• In case of breaker and half switching schemes, the differential protection
schemes, the differential protection C.T’s associated with Main and Tie
breakers should be connected to separate bias windings and these
should not be paralleled in order to avoid false operation due to dissimilar
C.T. transient response.
2.4
2.4
• Triple pole high impedance relay may be provided instead of single
© ABB Group - 42 -
• The current setting of the back up O/C relay shall be set above the
expected maximum load current so as to allow possible overload on
account of loss of one of the parallel transformers
3.2
3.2
• This shall be connected to give only alarm and not for tripping.
© ABB Group - 43 -
13-Nov-07
CBIP manual on Reliable
fault Clearance and Back- Power Transformers
UP Protection for EHV
and UHV Transmission
Network
© ABB Group - 44 -
13-Nov-07
Transformer protection
Power Transformers
In the above paragraphs some important application
aspects connected with the transformer protection
and some recommendations have been brought out
and these should be considered. Few of these are
brought out below
© ABB Group - 45 -
13-Nov-07
Transformer protection
Power Transformers
A true Main-2 protection scheme is usually not
provided in case of transformers. But as operating
requirements change and single contingency limits
are pressed the level of Main-2 protection may need
to be re-evaluated in future.
Numerical relays offer the best characteristic since
digital filters remove harmonics and DC offset
currents from the inrush. Numerical back-up over
current relays can therefore be set much more
sensitive than conventional types and are
© ABB Group - 46 -
recommended to be used
13-Nov-07
Transformer protection
Power Transformers
Harmonic restraint may be required to obtain
sensitive settings in case of zero sequence over
current relays.
Sometimes security is a problem In case of Buchholz
relays. The addition of an over current blocking relay,
which blocks or slows down the tripping, may be
used to improve security of the devices
In case of of mechanical type of fault detectors like
Buchholz and PRDs, for higher reliability, duplicating
of the initiating contacts may be considered on a
© ABB Group - 47 -
case-to-case basis.
13-Nov-07
Transformer protection
Power Transformers
For grid transformers, application of over excitation
protection not considered necessary and present
practice of providing it should be reviewed.
The power transformers have a large thermal heat
sink and can withstand overloads for certain limited
time. Selective protection and monitoring and load
management is necessary. The tripping of the
transformer should be the last action
Fast clearance of faults in the transformer is
important for stability of the system and therefore
adequate protections should be provided.
© ABB Group - 48 -
being followed.
Transformer protection
Power Transformers
Where Fire protection is provided the contacts
should be wired to trip both Group-A and Group-B
trip relays
For 132 kV level transformer where two separate DC
sources are not provided, it is recommended that the
protections be grouped in two groups connected to
separately fused DC sources. One gets to use two
trip relays in this case, which is advantageous
© ABB Group - 50 -
13-Nov-07
Protection Application Transformer
Handbook Protection- settings
© ABB Group - 51 -
13-Nov-07
Transformer protection
Power Transformers
Overloading
Overloading of a transformer will cause high temperatures
of different parts inside the transformer. High temperatures
can lead to degradation of insulation material. This will
cause reduction of the lifetime of the transformer
Load current
Transformer temperature
Load current
Transformer temperature
I diff
operation
no operation
I stab
© ABB Group - 56 -
13-Nov-07
Transformer protection
Percentage setting
Differential current flows due to excitation current of
transformer, due to ratio errors in CT and
predominantly due to position of tap changer if
provided
Dy <100 MVA 13 20
Dy >100 MVA 8 13
13-Nov-07
Transformer protection
Restricted earth fault protection
SETTING
RCT VK > 2 VR
VR
A B
© ABB Group - 59 -
13-Nov-07
Transformer protection
Phase overcurrent relays
The pick up current seting must be set above highest possible load
current
It shall also serve as overload protection
In many cases it can be considered that overload capacity is 1.4 times
rated power
The lowest setting value can be written as
I pickup = 1.2 . I max/K
It should also be able to detect all faults within the zone
I pickup < 0.7. I scmin
The high set relay should be set so as to be selective wrt other relays
I high > 1.2. K t .I scmax
K t is transient overreach and I scmax is largest fault current on low
voltage side
© ABB Group - 60 -
Time setting should be set as to get shortest fault time with maintained
selectivity
13-Nov-07
Transformer protection
Failure to Reset of an Overcurrent Protection
I st
I reset
t
© ABB Group - 61 -
13-Nov-07
Transformer protection
Inverse Time Characteristics Selectivity
Time
Fault current
© ABB Group - 62 -
13-Nov-07
Transformer protection
Residual over current relays
Earth fault current is fed from the transformer in case of
phase to earth fault in the system. Therefore there is a need
to trip the transformer in case of such fault. In most cases it
should be considered as back up to line protection. Current
setting is usually low. Time setting should be long to be
selective wrt line protection.
© ABB Group - 63 -
13-Nov-07
Transformer protection
System Transformer with Impedance Protection
Low V High V
Zone 1
Z<