Noise Barriers Supply and Installation For Burfiwala Lane & Gokhale Road Junction Flyover
Noise Barriers Supply and Installation For Burfiwala Lane & Gokhale Road Junction Flyover
EMPLOYER:
M/s TPF ENGINEERING PVT LTD.
EPC CONTRACTOR :
CONSULTANT:
REVISION STATUS:
PREPARED CHECKED APPROVED
REVISION DATE DESCRIPTION
BY BY BY
R0 13.09.2019 FOR APPROVAL ABJ ABJ DMK
This document is not to be reproduced,copied or used for any purpose other than for which it is prepared.
1 of 21
INDEX
1.0 INPUT DATA
2.0 CHECK FOR COLUMN SECTION
3.0 CHECK FOR COLUMN DEFLECTION
4.0 CHECK OF BASE PLATE AND ANCHOR BOLT DESIGN.
APPENDIX
A SUPPLIER DATA
B ELEVATION & DETAILS
C HILTI BASE PLATE & ANCHOR BOLT CALCULATION
D PROPERTIES OF JINDAL POST SECTION
2 of 21
1.0 INPUT DATA
As per IS875 (part 3) 2015, Annex A
Wind Speed = 44 m/s
for mumbai city
Design wind speed = Vz
Vz = 44 x 0.91 x 1.03 x 1.0 x 1.0
41.24 m/s
Design wind pressure Pz at 12m from ground level.
Design Wind pressure Pz = 0.6 x Vz^2
= 1020.5 N/m^2
104.027 kg/Sqm
CONSIDER LOADS ON CENTRAL PANEL
MAXIMUM WIND FORCE = 104.03 X 3 X 3 = 936.24 Kg
VERTICAL LOAD COMPONENT FOR BARRIER = 111 X 3 = 333 Kg
3 of 21
2.0 CHECK OF COLUMN SECTION
IT IS PROPOSED TO USE UC152X152X30kg/m FOR COLUMN POST
TOTAL VERTICAL LOAD = 333 + 108 = 441 kg
FACTORED VERTICAL LOAD = 1.5 X 441 = 661.50 kg
SLENDERNESS RATION l/Rmin = 2 x 3X 1000 / 3.83 X 10 = 156.66
Refer Table 9c, IS 800‐2007 using l/r
2
PERMISSIBLE DIRECT STRESS = 572.88 kg/cm SAFE
B) FACTORED BENDING MOMENT = 1404.36 X 1.5 =
(Refer Table 5, IS 800‐2007) 2106.5 kg‐m
DESIGN BENDING MOMENT =
THEREFORE THE ASSUMED COLUMN SECTION IS ADEQUATE & SAFE.
4 of 21
B) COMBINED STRESSES,
As per clause no. 9.3.1.1 from IS800:2007,
661.50 2107
+ = 0.379
106602.8 5652.4 SAFE
3.0 CHECK OF COLUMN DEFLECTION.
δ = 8.44
WIND LOAD ON COLUMN = 104Kg/sqm
udl ON THE COLUMN =104.02 X 3 = 312 Kg/m
3.0m
SWAY AT THE TOP OF COLUMN =
δ = Wl4/8EI
= 312.06x3^ 4 /(8*(2.1*10^11/9.81)*(1748/100000000))*1000
= 8.44 mm
PERMISSIBLE DEFLECTION = HEIGHT / 300 = 3500/300
(Refer Table 6 from IS800:2007
= 10 mm
SAFE
5 of 21
4.0 CHECK OF SIDE PLATE AND ANCHOR BOLT DESIGN.
A) REFER APPENDIX ‐ C FOR MORE DETAILS FOR THE HILTI CALCULATION
6 of 21
APPENDIX -A - SUPPLIER DATA
7 of 21
ELEVATION VIEW
WITH NOISE BARRIERS
NAME OF WORK :
Design and Construction of Nose Barrier
CLIENT :
3600
Municipal Corporation of
Greater Mumbai
CONTRACTOR :
CONSULTANT :
MADE BY M.S
8 of 21
CHECKED BY
S.J
APPENDIX -B - ELEVATION & DETAILS
10 of 21
GI POWER COATED
LOCKING PLATE 160 X 150
MS , GALVANISE STEEL
152 MM X 152 MMX 23 KG UC COLUMN
SIDE PLATE 600 X 400
3000
X 20 MM
NAME OF WORK :
SIDE PLATE
CLEAR PANEL 15 MM PMMA SHEET Design and Construction of Nose Barrier
GI POWDER COATED FRAME
SEALED WITH WITH EPDM RUBBER
152
CLIENT :
POST IS FIX WITH HILT ANCHOR AT
TOP OF RCC PARAPET AND BOLT
WITH POST AT 3m C/C
Municipal Corporation of
Greater Mumbai
L ANGLE 75 X 75 X 130 MM
FOR PANELS RESTING CONTRACTOR :
TOP VIEW DETAILS
CRASH PARAPET WALL
M.E INFRA PROJECT PVT
CHEMICAL ANCHORS M 20 X 200 MM 125
LTD
ALU 1.2 MM
4/5 MM ALU RIVITS
18.5
MS PLATE GI , WELDED WITH 1.2 MM ALU SHEET SEPRATOR
POST , PLATE SIZE 600 X 400 X20 MM CONSULTANT :
1.2 MM ALU SHEET PERFORATED
M/s SANGUINE
5 mm Dia Holes , 70 % PERFORATION
GI FRAME WITH POWERED
498
477
2 MM THICK
60 X 60 GI CLIT
GI BOLT 5/16 FOR FRAME
ALU 1.2 MM WORK :
CRASH PARAPET ASSAMBLY
16.5
NOISE BARRIERS SUPPLY AND
CROSS SECTION CLEAR PANEL ALUMINIUM PANEL
INSTALLATION FOR BURFIWALA LANE
& GOKHALE ROAD JUCTION BRIDGE.
PRODUCT :
PANEL PLACEMENT
CLEAR PANEL NOISE BARRIERS
12 of 21
www.hilti.in Profis Anchor 2.7.2
Company: Page: 1
Specifier: Project: Goregaon Flyover
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 8/31/2019
E-Mail:
Specifier's comments: Hilti HIT-V threaded rod with HIT-RE 500 V3 injection mortar with 200 mm embedment h_ef, M20, Steel galvanized,
Hammer drilled installation per instruction for use, with holes filled with Hilti Dynamic set or any suitable gap solutions
1 Input data
Anchor type and diameter: HIT-RE 500 V3 + HIT-V (8.8) M20
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef,act = 200 mm (hef,limit = - mm)
Material: 8.8
Evaluation Service Report: Hilti Technical Data
Issued I Valid: -|-
Proof: Engineering judgement SOFA BOND - based on ETAG BOND testing
Stand-off installation: eb = 0 mm (no stand-off); t = 13 mm
Anchor plate: lx x ly x t = 400 mm x 600 mm x 13 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, C16/20, fc,cube = 20.00 N/mm2; h = 250 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting according to EOTA TR 029, 5.2.2.6 present.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 13 of 21
www.hilti.in Profis Anchor 2.7.2
Company: Page: 2
Specifier: Project: Goregaon Flyover
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 8/31/2019
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 14 of 21
www.hilti.in Profis Anchor 2.7.2
Company: Page: 3
Specifier: Project: Goregaon Flyover
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 8/31/2019
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 15 of 21
www.hilti.in Profis Anchor 2.7.2
Company: Page: 4
Specifier: Project: Goregaon Flyover
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 8/31/2019
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling
the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• An SLS-check is not performed for SOFA and has to be provided by the user!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 16 of 21
www.hilti.in Profis Anchor 2.7.2
Company: Page: 5
Specifier: Project: Goregaon Flyover
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 8/31/2019
E-Mail:
8 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-RE 500 V3 + HIT-V (8.8) M20
Profile: no profile Installation torque: 0.150 kNm
Hole diameter in the fixture: df = 22 mm Hole diameter in the base material: 22 mm
Plate thickness (input): 13 mm Hole depth in the base material: 200 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 244 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
200 200
75
1 5
150
300
2 6
150
3 7
150
300
4 8
75
75 250 75
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 17 of 21
www.hilti.in Profis Anchor 2.7.2
Company: Page: 6
Specifier: Project: Goregaon Flyover
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 8/31/2019
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan 18 of 21
APPENDIX -D - STEEL COLUMN PROPERTIES
19 of 21
20 of 21
21 of 21