Packaged Gas/Electric

Rooftop Units
Voyager™
12½ – 25 Tons — 60 Hz

October 2004 RT-PRC001-EN


Introduction

Packaged Rooftop
Air Conditioners
Through the years,Trane has designed Trane customers demand products that
and developed the most complete line of provide exceptional reliability, meet
Packaged Rooftop products available in stringent performance requirements, and
the market today.Trane was the first to are competitively priced. Trane delivers
introduce the Micro—microelectronic unit with Voyager.
controls—and has continued to improve Voyager features cutting edge
and revolutionalize this design concept. technologies: reliable compressors,Trane
The ReliaTel control platform offers the engineered ReliaTel controls, computer-
same great features and functionality as aided run testing, and Integrated
the original Micro, with additional benefits Comfort™ Systems. So, whether you’re
for greater application flexibility. the contractor, the engineer, or the owner
Voyager continues to provide the highest you can be certain Voyager Products are
standards in quality and reliability, built to meet your needs.
comfort, ease of service, and the It’s HardTo Stop ATrane.®
performance of Trane light commercial
products.

© 2004 American Standard Inc. All rights reserved RT-PRC001-EN


Contents

Introduction 2
Features and Benefits 4
Application Considerations 10
Selection Procedure 11
Model Number Description 13
General Data 14
Performance Data 21
Cooling Performance 21
Fan Performance 31
Heat Performance 43
Controls 46
Electric Power 47
Dimension and Weights 58
Mechanical Specifications 68

RT-PRC001-EN 3
Features and
Benefits

Factory Installed Options Field Installed Options


• Black Epoxy Coated Condenser Coil • CO2 Sensing
• Dehumidification Option • Digital Display Zone Sensor
• High Efficiency Motors • DualThermistor Remote Zone Sensor
• High Pressure Cutout • Low Static Drive
• Hinged Access Doors • High Static Drive
• Novar Unit Controls • Manual Outside Air Damper
• Novar Return Air Sensor • Motorized Outside Air Dampers
• Powered or Unpowered Convenience • Powered Exhaust
Outlet • Downflow – Roof Curb
• Supply and/or Return Air Smoke • Horizontal – Economizer
Detector • Remote Potentiometer
• Thermal Expansion Valve/Face-Split • Ventilation Override Accessory
Evaporator Coil Option • Zone Sensors
• Through the Base Electrical with Circuit
Breaker
• Through the Base Electrical With
Disconnect Switch
• Through the Base Utilities Access
• Two-Inch Pleated Filters
Factory or Field Installed Options
• Clogged Filter/Fan Failure Switch
• Differential Pressure Switches
• Discharge Air Sensing Kit
• Downflow – Economizer
• Frostat
• LonTalk® Communications Interface
• Oversized Motors
• Reference or Comparative Enthalpy
• Tool-less Hail Guards
• Trane Communications Interface (TCI)

4 RT-PRC001-EN
Features and
Benefits

Easy to Install, Service and Quality and Reliability are enhanced ReliaTel Makes Testing Easy
Maintain through ReliaTel control and logic: ReliaTel requires no special tools to run
—prevents the unit from short cycling, the Voyager unit through its paces.
Because today’s owners are very cost- Simply place a jumper betweenTest 1
conscious when it comes to service and considerably improving
compressor life. andTest 2 terminals on the Low Voltage
maintenance, the Trane Voyager was Terminal Board and the unit will walk
designed with direct input from service —ensures that the compressor will run through its operational steps
contractors.This valuable information for a specific amount of time which automatically.
helped to design a product that would get allows oil to return for better —The unit automatically returns
the serviceman off the job quicker and lubrication, enhancing the reliability of control to the zone sensor after
save the owner money. Voyager does the compressor. stepping through the test mode a
this by offering: Voyager with ReliaTel reduces the single time, even if the jumper is
Quality and Reliability number of components required to left on the unit.
operate the unit, thereby reducing As long as the unit has power and the
ReliaTel™ Controls (LCI-R) possibilities for component failure. “system on” LED is lit, ReliaTel is
ReliaTel Makes Installing and operational.The light indicates that the
Servicing Easy controls are functioning properly.
ReliaTel eliminates the need for field ReliaTel features expanded diagnostic
installed anti-shortcycle timer and time capabilities when utilized withTrane
delay relays. ReliaTel controls provide Integrated Comfort™ Systems.
these functions as an integral part of the
unit.The contractor no longer has to Some zone sensor options have central
purchase these controls as options and control panel lights which indicate the
pay to install them. mode the unit is in and possible
diagnostic information (dirty filters for
The wiring of the low voltage connections example).
to the unit and the zone sensors is as
easy as 1-1, 2-2, and 3-3.This simplified Other ReliaTel Benefits
ReliaTel controls provide unit control for The ReliaTel built-in anti-shortcycle timer,
heating, cooling and ventilating utilizing system makes wiring easier for the
installer. time delay relay and minimum “on” time
input from sensors that measure outdoor control functions are factory tested to
and indoor temperature. assure proper operation.
ReliaTel softens electrical “spikes” by
staging on fans, compressors and
heaters.
Intelligent Fallback is a benefit to the
building occupant. If a component goes
astray, the unit will continue to operate at
ReliaTel™ predetermined temperature setpoint.
Intelligent Anticipation is a standard
ReliaTel feature. It functions continuously
as ReliaTel and zone sensor(s) work
together in harmony to provide much
tighter comfort control than conventional
electro-mechanical thermostats.
The same ReliaTel Board fits all Voyager
Packaged Gas/Electrics, Cooling with
Electric Heat, and Heat Pump models.
This provides standardization of parts for
contractors. Less money is tied up in
inventory with ReliaTel.

RT-PRC001-EN 5
Features and
Benefits

Drum and Tube Heat Exchanger


• The heat exchanger is manufactured
using aluminized steel with stainless
steel components for maximum
durability.The requirement for cycle
testing of heat exchangers is 10,000
cycles by ANSI Z21.47.This is the
standard required by both UL and AGA
for cycle test requirements. American
Standard requires the design to be
tested to 2½ times this current
standard.The drum and tube design has
been tested and passed over 150,000
cycles, which is over 15 times the
current ANSI cycling requirements.
• The negative pressure gas valve will
not allow gas flow unless the
combustion blower is operating.This is
one of our unique safety features.
• The forced combustion blower supplies
pre-mixed fuel through a single
stainless steel burner screen into a
sealed drum where ignition takes place.
It is more reliable to operate and
maintain than a multiple burner system.
• The hot surface ignitor is a gas ignition
device which doubles as a safety device
utilizing a continuous test to prove the
flame.The design is cycle tested at the
factory for quality and reliability.
• Our gas/electric rooftops exceed all
California seasonal efficiency
requirements and perform even better
than the California NOx emission
requirements.

Forced Combustion Blower

Negative Pressure Gas Valve


Hot Surface Ignitor

Drum and Tube Heat Exchanger

6 RT-PRC001-EN
Features and
Benefits

Outstanding Standard and Dehumidification (Hot Gas Reheat) High Static Drive Accessory
Optional Components Option Available on many models, this high
This option allows for increased outdoor static drive accessory extends the
Black Epoxy Coated Condenser Coil
air ventilation. It capability of the standard motor. Avoid
The coil provides corrosion protection to
reduces humidity expensive motors and operating costs by
condenser coils for seacoast application.
levels while installing this optimized sheave
Cabinet Integrity increasing accessory.
For added water integrity, Voyager has a comfort level in Hinged Access Doors
raised 11/8" lip around the supply and the air space. These doors permit easy access to the
return of the downflow units to prevent Cooling can filter, fan/heat, and compressor/control
water from blowing into the ductwork. operate without a sections. They reduce the potential roof
Clogged Filter/Fan Failure Switch demand for damage from screws or sharp access
A dedicated differential pressure switch is dehumidification. door corners.
available to achieve active fan failure The hot gas reheat
LonTalk® Communications Interface
indication and/or clogged filter indication. coil is designed to
The LonTalk communications interface
CO2 Sensing deliver maximum
allows the unit to communicate as a
The CO2 sensor has the ability to monitor reheat
Tracer™LCI-V device or directly with
space occupancy levels within the temperature.
generic LonTalk Network Building
building by measuring the parts per Digital Display Zone Sensor Automation System Controls.
million of CO2 (Carbon Dioxide) in the air. The Digital LCD (Liquid Crystal Display)
Power Exhaust Option
As the CO2 levels increase, the outside air zone sensor has the look and functionality
This option is available on downflow units
damper modulates to meet the CO2 of standard zone sensors. This sensor
and provides exhaust of the return air,
space ventilation requirements.The CO2 should be utilized with ReliaTel™ controls.
when using a downflow economizer, to
sensor kit is available as a field installed Discharge Air Sensing Kit maintain proper building pressurization.
accessory. Provides true discharge air sensing in Great for relieving most building
Colored And Numbered Wiring heating models. The kit is functional only overpressurization problems.
Save time and money tracing wires and with the ReliaTel Options Module.
Quick-Access Panels
diagnosing the unit. Downflow And Horizontal Economizers Remove three or fewer screws for
Compressors The economizers come with three control access to the standardized internal
Voyager contains the best compressor options — dry bulb is standard, enthalpy components and wiring.
technology available to achieve the and differential enthalpy are optional.
Quick-Adjust Idler Arm
highest possible performance. Dual Dual Thermistor Remote Zone Sensor With the Quick-Adjust Idler Arm, the belt
compressors are outstanding for This sensor will reduce the total number and sheaves can be quickly adjusted
humidity control, light load cooling of remote sensors to obtain space without moving the mounted fan motor.
conditions and system back-up temperature averaging. This sensor The result is a major savings in time and
applications. Dual compressors are should be utilized with ReliaTel controls. money.
available on all models.
Factory Built Roof Curbs
Refrigerant Circuits Available for downflow units. Only two
All Voyager 12½-25 ton units shall have roof curbs for the entire Voyager line
crankcase heaters, low and high pressure simplifies curb selection.
controls as standard.
Fresh Air
Condenser Coil 0 - 25% manual or 0 -
Voyager boasts a 50% motorized outside
patent-pending air hoods are available.
1+1+1 condenser
coil, permanently Low Static Drive
gapped for easy Accessory
cleaning. This option shall allow
the standard motor to
operate at lower static
performance. (See Fan
Performance tables).

RT-PRC001-EN 7
Features and
Benefits

Reference or Comparative Enthalpy VariTrac Actual shipping tests were performed to


Measures and communicates humidity When Trane’s changeover VAV System determine packaging requirements. Units
while maximizing comfort control. for light commercial applications is were test shipped around the country to
Sloped Drain Pans coupled with Voyager, it provides the determine the best packaging. Factory
Standard on every unit. latest in technological advances for shake and drop tests were used as part
comfort management systems and can of the package design process to help
Standardized Components allow thermostat control in every zone assure that the unit arrives at the job site
Components are placed in the same served by VariTrac. in top condition.
location on all Voyager units. Familiarize
yourself with one Voyager and you are Ventilation Override Accessory Rigging tests include lifting a unit into the
familiar with every Voyager. With the Ventilation Override Accessory air and letting it drop one foot, assuring
installed, the unit can be set to transition that the lifting lugs and rails hold up under
Due to standardized components to up to 3 different pre-programmed stress.
throughout the Voyager line, contractors/ sequences for Smoke Purge,
owners can stock fewer parts. We perform a 100% coil leak test at the
Pressurization, and Exhaust.The factory. The evaporator and condenser
Supply and/or Return Air Smoke transition occurs when a binary input on coils are leak tested at 200 psig and
Detector the RTOM is closed (shorted).This would pressure tested to 450 psig.
With this option installed, if smoke is typically be a hard wired relay output
detected, all unit from a smoke detector or fire control All parts are inspected at the point of final
operation will be shut panel.The ventilation override kit is assembly. Sub-standard parts are
down. Reset will be available as a field installed accessory. identified and rejected immediately.
manual at the unit. Zone Sensors Every unit receives a 100% unit run test
Return Air Smoke Available in programmable, automatic before leaving the production line to
Detectors require and manual styles. make sure it lives up to rigorousTrane
minimum allowable requirements.
airflow when used Rigorous Testing Voyager units incorporate either a one
with certain models. The fan and idler arm assembly designs piece top or theTrane-Tite-Top (T3). Each
Tool-less Hail Guards have been tested to over 300,000 cycles part of the top (either two or three pieces)
Tool-less, hail each. Our combined cycle testing is now overlaps in such a way that water cannot
protection quality coil over 7,000,000 cycles. leak into the unit.These overlapped edges
guards shall be either All of Voyager’s designs were rigorously are gasketed and sealed to ensure
factory or field-installed for condenser rain tested at the factory to ensure water superior water integrity.
coil protection.This option protects the integrity.
condenser coil from vandalism and/or
hail damage.

VariTrac™

Trane Communication Interface (TCI)


Available factory or field installed.This
module when applied with the ReliaTel™
easily interfaces with Trane’s Integrated
ComfortTM System.

8 RT-PRC001-EN
Features and
Benefits

Easy to Install and Service Powered or Unpowered Convenience Factory Installed Options
Outlet A wide variety of Factory Installed
Conversionless Units This option is a GFCI, 120v/15amp, 2 plug, Options (FIOPs) are available.
The dedicated design units (either convenience outlet, either powered or
downflow or horizontal) require no panel unpowered.This option can only be Added Efficiency
removal or alteration time to convert in ordered when theThrough the Base Airflow
the field — a major cost savings during Electrical with either the Disconnect Airflow is outstanding.The Voyager can
installation. Switch, or Circuit Breaker, option is replace an older machine with old
Horizontal units come complete with duct ordered.This option is available on all ductwork and, in many cases, improve
flanges so the contractor doesn’t have to downflow models. the comfort through better air
field fabricate them.These duct flanges distribution.
are a time and cost saver. High Efficiency Motors
Easy Access Low Voltage Terminal Board This option is available with efficiency
Voyager’s Low Voltage Terminal Board is ratings from 86.5 up to 91.0. It is not
external to the electrical control cabinet. It available for all models.
is extremely easy to locate and attach the U-shaped Airflow
thermostat wire.This is another cost and U-shaped airflow allows for improved
time saving installation feature. static capabilities.
Low Ambient Cooling
Cooling capabilities down to 0°F as
standard.
Oversized Motors
Factory or field installed oversized
motors available for high static
applications.
Single Point Power One of our Finest Assets:
A single electrical connection powers the Trane Sales Representatives are a
unit. Support group that can assist you with:
— Product
Single Side Service — Application
Low Voltage Connections Single side service is standard on all — Service
The wiring of the low voltage connections units. — Training
to the unit and the zone sensors is as Through the Base Electrical with Circuit — Special Applications
simple as 1-1, 2-2, and 3-3.This simplified Breaker — Specifications
system makes it easy for the installer to This option is a factory installed thermal — Computer Programs and much more
wire. magnetic, molded case, HACR Circuit Voyager has the features and benefits
Breaker with provisions for through the that make it first class in the light
base electrical connections. This option is commercial rooftop market. Designed
available on all downflow models. with input from field contractors and
Through the Base Electrical with engineers, its U-shaped airflow
Disconnect Switch performance is outstanding.
Factory installed 3-pole, molded case,
disconnect switch with provisions for
through the base electrical connections
are available. This option is available on
all downflow models.
Through the Base Utilities Access
An electrical service entrance shall be
provided allowing electrical access for
both control and main power connections
inside the curb and through the base of
the unit. Option will allow for field
installation of liquid-tight conduit and an
external field installed disconnect switch.

RT-PRC001-EN 9
Application
Considerations

Application of this product should be Power Exhaust Accessory


within the cataloged airflow and cooling The power exhaust accessory is
considerations. available on all 12½-25 tons downflow
Low Ambient Cooling units. This accessory can be field
This Voyager line features, as standard, installed and will assist in relieving
low ambient cooling down to 0°F. The building pressurization.
Voyager™ line features, with ReliaTel™ Condensate Trap
microprocessor controls, low ambient The evaporator is a draw-thru
cooling down to 0°F. The following options configuration. A trap must be field
need to be included/considered when low provided prior to start-up on the cooling
ambient applications are required: cycle.
continuous fan operation, crankcase
heaters, thermal expansion valves, Clearance Requirements
frostat. Contact your localTrane The recommended clearances identified
Representative for more assistance with with unit dimensions should be
low ambient cooling applications. maintained to assure adequate
Barometric Relief serviceability, maximum capacity and
peak operating efficiency. Actual
This product offers an optional clearances which appear inadequate
barometric relief damper included in the should be reviewed with the local Trane
downflow economizer accessory. This sales personnel.
accessory consists of gravity dampers
which open with increased pressure. As Unit Pitch
the building air pressure increases, the These units have sloped condensate
pressure in the unit return air section drain pans. Units must be installed level;
also increases, opening the dampers and any unit slope must be toward access
relieving the conditioned space. side of unit.
NOTE:THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER DURING
ECONOMIZING OPERATION IS SYSTEM
RELATED. PRESSURE DROP OF THE
RETURN AIR SYSTEM SHOULD BE
CONSIDEREDTO CONTROL BUILDING
PRESSURIZATION.
Heating Operation
The heat exchanger is manufactured with
aluminized steel. To prevent
condensation within the heat exchanger,
do not exceed 50% outside air.

10 RT-PRC001-EN
Selection
Procedures

Cooling Capacity To determine the total unit static pressure Heating Capacity
add the external static pressure to the
Step 1 — Calculate the building’s total additional static created by the added Step 1 — Calculate the building heating
and sensible cooling loads at design features: load using theTrane calculation form or
conditions. Use theTrane calculation form other standard accepted method.
or any other standard accepted method. External Static (duct system) 0.45 wg
Step 2 — Size the system heating
Example:The following are the building Standard Filter 2 in. (fromTable PD-36) capacity to match the calculated building
requirements: 0.11 g heating load.The following are building
a. Electrical Characteristics: 460/60/3 Economizer (100% Return Air fromTable heating requirements:
b. Summer Design Conditions: Entering PD-20) 0.05 wg a. Total heating load of 165 MBh
Evaporator Coil: 80° DB/ 67° WB b. 8000 cfm
Outdoor Ambient: 95° DB Total static pressure 0.61 c. Fuel - Natural gas
c. Total Cooling Load: 220 MBh Note: The Evaporator Fan Performance For the YC*240B3, there are two heating
d. Sensible Cooling Load: 140 MBh Table PD-20 has already accounted for capacities available, 250 MBh and 400
e. Airflow: 8000 cfm External Static the pressure drop for standard filters and MBh input models shown inTable PD-35.
Pressure: 0.450 in wg wet coils (see note belowTable PD-20). The output capacities of these furnaces
f. downflow configuration Therefore the actual total static pressure are 175 MBh and 300 MBh respectively.
g. economizer is 0.61-0.11 = 0.50 wg. The low heat model with 175 MBh best
Step 2 — As a starting point, a rough With 8000 cfm and 0.50 inches external matches the building requirements,
determination must be made of the size static pressure. Table PD-20 shows 3.96 indicating aYC*240B3 should be
of the unit. The final selection will be bhp for this model. At these conditions, selected.
made after examining the performance the note below the table gives a formula
at the given conditions. Divide the total to calculate Fan Motor Heat: Air Delivery Selection
cooling load by the nominal BTUH per ton 3.15 X bhp = MBh External static pressure drop through the
(12 MBh per ton); then round up to the air distribution system has been
nearest unit size. 3.15 X 3.96 = 12.47 MBh. calculated to be 0.50 inches of water.
220 MBh / 12 MBh = 18.333 (approx 20 Enter Table PD-20 for a YC*240B3 at 8000
tons). Subtracting the fan motor heat from the cfm and 0.50 static pressure.The
gross cooling capacity of the unit: standard motor at high speed will give
Step 3 — Examine gross capacity:Table NetTotal Cooling Capacity = the desired airflow.
PD-4 shows that a YC*240B3 has a gross 246 MBh - 12.47 = 251.53 MBh
cooling capacity of 246 MBh and 176 Net Sensible Cooling Capacity =
Accessory Selection
MBh sensible capacity at 95 DB ambient 176 MBh - 12.47 = 163.53 MBh. Select accessories needed to
and 8000 cfm with 80 DB/ 67 WB air accommodate the application.
entering the evaporator. Since the NetTotal Cooling Capacity
meets the cooling load requirements of
To Find Capacity at Intermiediate 220 MBh, we are satisfied with this
Conditions Not in the Table selection.
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity.
Note: Extrapolation outside of the table
conditions is not recommended.
Step 4— Verify the unit will have enough
capacity to meet the building
requirements by determining the net
capacity, which includes heat generated
by the fan. In order to select the correct
unit, the fan motor heat must be
deducted from the gross coolingcapacity.
The amount of heat that the fan motor
generates is dependent on the effort by
the motor - cfm and static pressure.

RT-PRC001-EN 11
Selection
Procedure

68°F DB,
Dehumidification Selection OA
67°F WB

Determine normal unit cooling and RA 75°F DB,


52% RH
heating capacities as previously
72°F DB
described in the selection procedures on MA
65°F WB
prior page. SA’ 51.7°F DB,
51.0°F DB
Typical 20 ton YFD241C SA 71°F DB, OA
59°F WB
6400 cfmTotal Supply airflow MA
2560 cfm Outside Air (40%) RA
3840 cfm Return Air SA
SA’ REHEAT
1.00” External Static Pressure

OA Conditions
Part load day and raining
68°F db Chart C-1
67°F wb
66.5 dp Step 5: Determine leaving unit
Step 3a: Determine leaving
95% RH sensible temperature with reheat
evaporator temperature (SA’)
Leaving Unit Temperature = SA’ active (SA)
RA’ conditions
Utilizing the manual selection method as Reheat temperature (obtained in step 4)
75°F db
previously described and the formula + (SA’ + fan heat) = SA
63°F wb (SA’ + fan heat) = leaving unit
52% RH ∆Temp = gross sensible or latent cooling temperature in standard cooling mode
55.9 dp capacity in Bth from step 3b.

Step 1: Determine the mixed/ (cfm)(1.085) 17.55°F db + 53.6°F = 71.2°F db


entering air condition (MA’) Subtract your sensible ∆ temp from the SA=71.2°F
MA’ = (% outside air*outside air dry-bulb entering db and latent ∆ temp from the
temperature) + (% return air*return air entering wb or use the TOPSS™ Since reheat adds only sensible heat,
dry-bulb temperature) program determine the leaving follow the psychrometric chart to find the
MA’ = (0.40*68°F) + (0.60*75°F) evaporator temperature (temperature new wb temperature.
MA’ = 72.20°F db without the addition of fan heat).
Note: Repeat for wet-bulb 51.74 db wb ≅ 58.7°F
temperature (wb). 51.03 wb
Plot on psychrometric chart.
Step 3b: Determine leaving unit Consider Chart C-1. If the space relative
MA’ temperature in standard cooling humidity is equal to or above the space
72.2°F db mode relative humidity setpoint, the
64.7°F wb Repeat Step 3a substituting net sensible Dehumidification option will:
or latent capacity for gross sensible or
Step 2: Determine the additonal latent capacity to find the leaving unit • Energize compressor or both
static pressure drop for a reheat unit temperature including fan heat or refer to compressors (2 stage compressor units).
Table PD-36 shows a static pressure drop yourTOPSS selection. • Hot gas reheat valve is energized and
of 0.35” for the reheat coil and an 53.6 db hot gas is diverted to the reheat coil.
additional .04 for the mandatory 2” 51 wb • Dehumidification/reheat is terminated
pleated filters required when ordering the 84% RH when space humidity is reduced to 5%
dehumidification option.Total static 49% dp below relative humidity setpoint.
pressure =
1.0+0.035+0.04=1.075 Step 4: Determine reheat At MA’, air enters the RTU.The RTU filters,
(≅1.1 for manual calculations) temperature rise cools, and dehumidifies the air as it
Do not forget to also add any additional Using the leaving evaporator temp (SA’), moves through the evaporator coil. Air
static from other accessories. go to PD-37 and determine the reheat leaves the evaporator coil saturated at
temperature rise for that particular cfm: the preset dew point condition (SA’) and
Table PD-29 (airflow table for 20 ton 17.55°F db is reheated by the hot gas reheat coil to
dehumidification units) indicates that a deliver 71°F (SA) supply air to the space.
standard motor and drive is needed for Note: Reheat temperature rise is based
this airflow and static pressure range. on supply airflow and leaving
evaporator coil temperature.
12 RT-PRC001-EN
Model
Number
Description

Packaged Gas/Electric Unit Typical Model Nomenclature

Y C D 1 5 0 C 3 L 0 A A
1 2 3 4 5 6 7 8 9 10 11 12

Digits 1, 2 - Product Type Digit 8 - Electrical Characteristics


YC = Packaged Gas/Electric 3 = 208-230/60/3
4 = 460/60/3
YF = With Factory Installed Options W= 575/60/3
K = 380/60/3
Digit 3 - Airflow Configuration
Digit 9 - Heating Capacity
D = Downflow
H = Horizontal L = Low Heat
M = Medium Heat
Digits 4, 5, 6 - Nominal Gross Cooling H = High Heat
Capacity (MBh)
Digit 10 - Factory-Installed Options
150 = 12½ Ton Standard Efficiency
151 = 12½ Ton High Efficiency 0 = Packed Stock, No Options
180 = 15 Ton Standard Efficiency A = Downflow Economizer
181 = 15 Ton High Efficiency B = Oversized Motor
210 = 17½ Ton Standard Efficiency C = Downflow Economizer and Oversized
211 = 17½ Ton High Efficiency Motor
240 = 20 Ton Standard Efficiency F = Trane Communications Interface (TCI)
241 = 20 Ton High Efficiency G = Downflow Economizer and TCI
300 = 25 Ton Standard Efficiency H = TXV/Face-Split Evaporator
301 = 25 Ton High Efficiency J = Oversized Motor and TXV/Face-Split
Evaporator
Digit 7- Major Development Sequence K = Downflow Economizer, Oversized
Motor, and TXV/Face-Split Evaporator
L = Downflow Economizer with TXV/Face-
Split Evaporator
M= Reheat Coil
N= Downflow Economizer and Reheat Coil
P = Oversized Motor and Reheat Coil
R = Downflow Economizer, Oversized
Motor and Reheat Coil

Digit 11- Minor Design Sequence

Digit 12- Service Digit

RT-PRC001-EN 13
(12½, 15 Ton)
General Data Standard Efficiency

Table GD-1 — General Data


12½Ton Downflow and Horizontal Units 15Ton Downflow and Horizontal Units
YC*150D3,D4,DWL, DK YC*150D3,D4,DWH, DK YC*180B3,B4,BWL, BK YC*180B3,B4,BWH, BK
Cooling Performance1
Gross Cooling Capacity 150,000 182,000
EER2 (Downflow/Horizontal) 9.6 9.7
Nominal CFM / ARI Rated CFM 5,000/4,400 6,000/5,300
ARI Net Cooling Capacity 142,000 174,000
Integrated Part Load Value3 10.3 10.0
System Power (KW) 14.79 17.94
Heating Performance4
Heating Models Low High Low High
Heating Input (Btuh) 150,000 250,000 250,000 350,000
1st Stage 100,000 175,000 175,000 250,000
Heating Output (Btuh) 122,000 203,000 203,000 284,000
1st Stage 81,000 142,000 142,000 203,000
AFUE (%)5 (Downflow/Horizontal) 81.0 80.7/79.9 80.7 / 79.9 80.1 / 79.1
Steady State Efficiency (%) 81.0 81.0 81.0 81.0
No. Burners 1 1
No. Stages 2 2
Gas Supply Pressure (in. w.c)
Natural or LP (minimum/maximum) 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 1/2 3/4
Compressor
No./Type 2/Scrolls 2/Scrolls
Sound Rating (BELS)6 9.2 9.2
Outdoor Coil -Type Hi-Performance Hi-Performance
Tube Size (in.) OD .375 .375
Face Area (sq ft) 24.18 27.12
Rows/FPI 2/16 3/16
Indoor Coil -Type Hi-Performance Hi-Performance
Tube Size (in.) .375 .375
Face Area (sq ft) 17.5 17.50
Rows/FPI 2/15 2/15
Refrigerant Control Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT
Outdoor Fan -Type Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26
DriveType/No. Speeds Direct/1 Direct/1
CFM 10,600 10,200
No. Motors/HP 2/.50 2/.50
Motor RPM 1,100 1,100
Indoor Fan -Type FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/15 X 15 1/15 X 15
DriveType/No. Speeds Belt/1 Belt/1
No. Motors 1 1
Motor HP (Standard/Oversized)9 3.0/5.0 3.0/5.0
Motor RPM (Standard/Oversized)9 1740/3450 1740/3450
Motor Frame Size (Standard/Oversized)9 145T/145T 145T/145T
Filters -Type Furnished Throwaway8 Throwaway8
(No.) Size Recommended
Downflow (2) 20 X 20 X 2, (4) 20 X 25 X 2 (2) 20 X 20 X 2, (4) 20 X 25 X 2
Horizontal (2) 20 X 20 X 2, (4) 20 X 25 X 2 (2) 20 X 20 X 2, (4) 20 X 25 X 2
Refrigerant Charge (Lbs of R-22)7
9.3/9.4/Circuit 17.5/9.5/ Circuit
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the
effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the unitary large equipment certification program, which is based on ARI Standard
340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for
elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. An optional 2 inch pleated filter is also available.
9. For 380V/60Hz units, the oversized mtoor is used as the standard motor. Refer to oversized motor data.

*Indicates both downflow and horizontal units.

14 RT-PRC001-EN
(17½, 20 Ton)
General Data Standard Efficiency

Table GD-2 — General Data


17½ Ton Downflow and Horizontal Units 20 Ton Downflow and Horizontal Units
YC*210C3,C4,CWL, CK YC*210C3,C4,CWH, CK YC*240B3,B4,BWL, BK YC*240B3,B4,BWH, BK
1
Cooling Performance
Gross Cooling Capacity 210,000 242,000
EER2 9.6 9.5
Nominal CFM / ARI Rated CFM 7,000/5,800 8,000/7,000
ARI Net Cooling Capacity 196,000 232,000
Integrated Part Load Value3 9.8 9.8
System Power (KW) 20.41 24.42
Heating Performance4
Heating Models Low High Low High
Heating Input (Btuh) 250,000 350,000 250,000 400,000
1st Stage 175,000 250,000 175,000 300,000
Heating Output (Btuh) 203,000 284,000 203,000 324,000
1st Stage 142,000 203,000 142,000 243,000
AFUE (%)5 Downflow/Horizontal 80.7 / 79.9 80.1 / 79.1 80.2 / 81.0 79.8 / 79.7
Steady State Efficiency (%) 81.0 81.0 81.0 81.0
No. Burners 1 1
No. Stages 2 2
Gas Supply Pressure (in. w.c)
Natural or LP (minimum/maximum) 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 3/4 1/2 3/4
Compressor
No./Type 2/Scrolls 2/Scrolls
Sound Rating (BELS)6 9.4 9.4
Outdoor Coil -Type Hi-Performance Hi-Performance
Tube Size (in.) OD .375 .375
Face Area (sq ft) 27.12 35.3
Rows/FPI 3/16 3/16
Indoor Coil -Type Hi-Performance Hi-Performance
Tube Size (in.) .375 .375
Face Area (sq ft) 17.50 26.00
Rows/FPI 4/15 2/15
Refrigerant Control Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT
Outdoor Fan -Type Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26
DriveType/No. Speeds Direct/1 Direct/1
CFM 13,400 14,600
No. Motors/HP 2/1.0 2/1.0
Motor RPM 1,125 1,125
Indoor Fan -Type FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/15 X 15 1/18 X 18
DriveType/No. Speeds Belt/1 Belt/1
No. Motors 1 1
Motor HP (Standard/Oversized)9 5.0/7.5 5.0/7.5
Motor RPM (Standard)9 3450/3470 3450/3470
Motor Frame Size (Standard/Oversized)9 56HZ/184T 145T/184T
Filters -Type Furnished8 Throwaway Throwaway
(No.) Size Recommended
Downflow (2) 20 X 20 X 2/(4) 20 X 25 X 2) (4) 20 X 20 X 2/(4) 20 X 25 X 2
Horizontal (2) 20 X 20 X 2/(4) 20 X 25 X 2) (8) 20 X 25 X 2
Refrigerant Charge (Lbs of R-22)7
Downflow 21.0/14.3/Circuit 18.9/21.0/Circuit
Horizontal 21.5/14.5/Circuit
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on
ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown
are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. An optional 2 inch pleated filter is also available.
9. For 380V/60Hz units, the oversized mtoor is used as the standard motor. Refer to oversized motor data.
*Indicates both downflow and horizontal units.
RT-PRC001-EN 15
(25 Ton)
General Data Standard Efficiency

Table GD-3 — General Data


25 Ton Downflow and Horizontal Units
YC*300B3,B4,BWL, BK YC*300B3,B4,BWH, BK
Cooling Performance1
Gross Cooling Capacity 290,000
EER2 9.7
Nominal CFM / ARI Rated CFM 10,000 / 8,750
ARI Net Cooling Capacity 272,000
Integrated Part Load Value3 9.8
System Power (KW) 28.05
Heating Performance4
Heating Models Low High
Heating Input (Btuh) 250,000 400,000
1st Stage 175,000 300,000
Heating Output (Btuh) 203,000 324,000
1st Stage 142,000 243,000
AFUE (%)5 Downflow/Horizontal 80.2/81.0 79.8/79.7
Steady State Efficiency (%) 81.4/81.0 80.8/81.0
No. Burners 1
No. Stages 2
Gas Supply Pressure (in. w.c)
Natural or LP (minimum/maximum) 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 3/4
Compressor
No./Type 2/Scrolls
Sound Rating (BELS)6 9.4
Outdoor Coil - Type Hi-Performance
Tube Size (in.) OD .375
Face Area (sq ft) 36.43
Rows/FPI 2/16
Indoor Coil - Type Hi-Performance
Tube Size (in.) .375
Face Area (sq ft) 26.00
Rows/FPI 3/15
Refrigerant Control Short Orifice
Drain Connection No./Size (in.) 1/1.00 NPT
Outdoor Fan - Type Propeller
No. Used/Diameter (in.) 2/28
Drive Type/No. Speeds Direct/1
CFM 16,700
No. Motors/HP 2/1.0
Motor RPM 1,125
Indoor Fan - Type FC Centrifugal
No. Used/Diameter (in.) 1/18 X 18
Drive Type/No. Speeds Belt/1
No. Motors 1
Motor HP (Standard/Oversized)9 7.5/NA
Motor RPM (Standard/Oversized)9 3470/NA
Motor Frame Size (Standard/Oversized)9 184T/NA
Filters - Type Furnished8 Throwaway
(No.) Size Recommended
Downflow (4) 20 X 20 X 2(4) 20 X 25 X 2
Horizontal (8) 20 X 25 X 2
Refrigerant Charge (Lbs of R-22)7
Downflow
Horizontal 17.0/Circuit
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. YC*300B model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown
are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. An optional 2 inch pleated filter is also available.
9. For 380V/60Hz units, the oversized mtoor is used as the standard motor. Refer to oversized motor data.

*Indicates both downflow and horizontal units.

16 RT-PRC001-EN
(12½, 15 Ton)
General Data High Efficiency

Table GD-4 — General Data


12½Ton Downflow and Horizontal Units 15Ton Downflow and Horizontal Units
YC*151C3,C4,CW YC*181C3,C4,CW
Cooling Performance1
Gross Cooling Capacity 154,000 189,000
EER2 11.3010 11.509
Nominal CFM / ARI Rated CFM 5,000 / 4400 6,000 / 5,300
ARI Net Cooling Capacity 146,000 180,000
Integrated Part Load Value3 11.5 13.3
System Power (KW) 12.9210 15.659
Heating Performance4
Heating Models Low High Low High
Heating Input (Btuh) 150,000 250,000 250,000 350,000
1st Stage 100,000 175,000 175,000 250,000
Heating Output (Btuh) 122,000 203,000 203,000 284,000
1st Stage 81,000 142,000 142,000 203,000
AFUE%5 (Downflow/Horizontal) 81.0 / 81.0 80.7 / 79.9 80.7 / 79.9 80.1 / 79.1
Steady State Efficiency (%)5 81.0 81.0 81.0 81.0
No. Burners 1 1 1 1
No. Stages 2 2 2 2
Gas Supply Pressure (in. w.c)
Natural or LP (minimum/maximum) 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 1/2 1/2 3/4
Compressor
No./Type 2/Scrolls 2/Scrolls
Sound Rating (BELS)6 9.2 9.2
Outdoor Coil -Type Hi-Performance Hi-Performance
Tube Size (in.) OD 0.375 0.375
Face Area (sq ft) 27.12 35.30
Rows/FPI 3/16 3/16
Indoor Coil -Type Hi-Performance Hi-Performance
Tube Size (in.) 0.375 0.375
Face Area (sq ft) 17.50 26.00
Rows/FPI 3/15 3/15
Refrigerant Control Short Orifice10 Short Orifice9
Drain Connection No./Size (in.) 1/1.0 NPT 1/1.0 NPT
Outdoor Fan -Type Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26
DriveType/No. Speeds Direct/1 Direct/1
CFM 10,400 11,000
No. Motors/HP 2/.50 2/.50
Motor RPM 1100 1100
Indoor Fan -Type FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/ 15 x 15 1/18 x 18
DriveType/No. Speeds Belt/1 Belt/1
No. Motors 1 1
Motor HP (Standard/Oversized) 3.0/5.0 3.0/5.0
Motor RPM (Standard/Oversized) 1740/3450 1740/3450
Motor Frame Size (Standard/Oversized) 145T/145T 145T/145T

RT-PRC001-EN 17
(12½, 15 Ton)
General Data High Efficiency

Table GD-4 — Continued


12½Ton Downflow and Horizontal Units 15Ton Downflow and Horizontal Units
YC*151C3,C4,CW YC*181C3,C4,CW
Filters -Type Furnished8 Throwaway Throwaway
(No.) Size Recommended
Downflow (2)20 X 20 X 2/(4)20 X 25 X 2 (4)20 X 20 X 2/(4)20 X 25 X 2
Horizontal (2)20 X 20 X 2/(4)20 X 25 X 2 (8)20 X 25 X 2
Optional Hot Gas Reheat Coil -Type Hi-Performance Hi-Performance
Tube Size (in.) OD 0.375 0.375
Face Area (sq. ft.) 17.5 26
Rows/FPI 1/16 1/16
Refrigerant Charge (Lbs of R-22)7/Circuit
Standard 15.0/13.810 25.0/13.09
Optional Hot Gas Reheat Coil 15.3/14.3 27.8/11.4
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the
effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard
340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for
elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE and Steady State Efficiency is rated in accordance with DOE test procedures.
6. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. An optional 2 inch pleated filter is also available.
9. TXV/Face-Split Option (Downflow Only) YCD181C3,4,W (EER):11.4; (System Power kW): 15.79; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 26.0/12.0.
10. TXV/Face-Split Option (Downflow Only) YCD151C3,4,W (EER):11.3; (System Power kW): 12.92; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 13.4/12.0.

*Indicates both downflow and horizontal units.

18 RT-PRC001-EN
(17½, 20, 25 Ton)
General Data High Efficiency

Table GD-5 — General Data


17½Ton 20Ton 25Ton Units
Downflow and Horizontal Units Downflow and Horizontal Units Downflow and Horizontal Units
YC*211C3,C4,CW YC*241C3,C4,CW YC*301C3,C4,CW
Cooling Performance1
Gross Cooling Capacity 220,000 268,0009 300,000
EER2 11.0 10.6 10.4
Nominal CFM / ARI Rated CFM 7,000 / 6,200 8,000 / 7,000 10,000/8,750
ARI Net Cooling Capacity 208,000 250,0009 278,000
Integrated Part Load Value3 12.0 11.2 11.0
System Power (KW) 18.91 23.589 26.73
Heating Performance4
Heating Models Low High Low High Low High
Heating Input (Btuh) 250,000 350,000 250,000 400,000 250,000 400,000
1st Stage 175,000 250,000 175,000 300,000 175,000 300,000
Heating Output (Btuh) 203,000 284,000 203,000 324,000 203,000 324,000
1st Stage 142,000 203,000 142,000 243,000 142,000 243,000
AFUE%5 (Downflow/Horizontal) 80.2 / 81.0 79.3 / 79.7 80.2 / 81.0 79.8 / 79.7 80.2/81.0 79.8/79.7
Steady State Efficiency (%)5 81.0 81.0 81.0 81.0 81.0 81.0
No. Burners 1 1 1 1 1 1
No. Stages 2 2 2 2 2 2
Gas Supply Pressure (in. w.c)
Natural or LP ((minimum/maximum) 2.5/14.0 2.5/14.0 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 3/4 1/2 3/4 1/2 3/4
Compressor
No./Type 2/Scrolls 2/Scrolls 2/Scrolls
Sound Rating (BELS)6 9.4 9.4 9.4
Outdoor Coil -Type High-Performance High-Performance High Performance
Tube Size (in.) OD 0.375 0.375 0.375
Face Area (sq ft) 35.30 35.309 35.30
Rows/FPI 3/16 3/16 3/16
Indoor Coil -Type High-Performance High-Performance High Performance
Tube Size (in.) 0.375 0.375 0.375
Face Area (sq ft) 26.00 26.00 26.00
Rows/FPI 4/15 4/15 4/15
Refrigerant Control Short Orifice Short Orifice9 Short Orifice
Drain Connection No./Size (in.) 1/1.0 NPT 1/1.0 NPT 1/1.0 NPT
Outdoor Fan -Type Propeller Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26 2/26
DriveType/No. Speeds Direct/1 Direct/1 Direct/1
CFM 12,800 13,700 13,700
No. Motors/HP 2/1.0 2/1.0 2/1.0
Motor RPM 1125 1125 1125
Indoor Fan -Type FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter (in.) 1/18 x 18 1/18 x 18 1/18x18
DriveType/No. Speeds BELT/1 BELT/1 BELT/1
No. Motors 1 1 1
Motor HP (Standard/Oversized) 5.0/7.5 5.0/7.5 7.5
Motor RPM (Standard/Oversized) 3450/3470 3450/3470 3470
Motor Frame Size (Standard/Oversized) 145T/184T 145T/184T 184T

RT-PRC001-EN 19
(17½, 20, 25 Ton)
General Data High Efficiency

Table GD-5 — Continued


17½Ton 20Ton 25Ton Units
Downflow and Horizontal Units Downflow and Horizontal Units Downflow and Horizontal Units
YC*211C3,C4,CW YC*241C3,C4,CW YC*301C3,C4,CW
Filters -Type Furnished8 Throwaway Throwaway Throwaway
(No.) Size Recommended
Downflow (4)20 X 20 X 2/(4)20 X 25 X 2 (4)20 X 20 X 2/(4)20 X 25 X 2 (4)20 X 20 X 2/(4)20 X 25 X 2
Horizontal (8)20 X 25 X 2 (8)20 X 25 X 2 (8)20 X 25 X 2
Optional Hot Gas Reheat Coil -Type — Hi-Performance —
Tube Size (in.) OD — 0.375 —
Face Area (sq. ft.) — 26 —
Rows/FPI — 1/16 —
Refrigerant Charge (Lbs of R-22)7/Circuit
Standard 25.7/12.5 21.8/21.89 24.5/24.5
Optional Hot Gas Reheat Coil — 21.3/21.0 —
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the
effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. 17½-20 tons are certified in accordance with the Unitary Large Equipment certification program, which is based
on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE and Steady State Efficiency is rated in accordance with DOE test procedures.
6. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. An optional 2 inch pleated filter is also available.
9. TXV/Face-Split Option (Downflow Only) YCD241C3,4,W (Gross Cooling Capacity):259,000; (ARI Net Cooling Capacity): 244,000; (System Power kW): 23.02; (Refrigerant Control): Expansion Valve;
(Refrigerant Charge): 21.5/22.2
*Indicates both downflow and horizontal units.

20 RT-PRC001-EN
Performance (12½ Ton)
Data Standard Efficiency

Table PD-1 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase YC*150D3, D4, DW, DK
AmbientTemperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 135.0 108.0 153.0 86.0 162.0 59.3 126.0 103.0 146.0 82.0 158.0 56.7 116.0 98.2 138.0 77.7 152.0 53.8 106.0 93.1 127.0 80.0 145.0 50.5
4500 80 136.0 128.0 154.0 105.0 163.0 79.5 127.0 123.0 147.0 101.0 159.0 76.5 117.0 117.0 138.0 97.0 153.0 73.2 110.0 110.0 128.0 92.2 145.0 69.6
85 142.0 142.0 154.0 123.0 164.0 95.9 135.0 135.0 147.0 120.0 159.0 94.2 127.0 127.0 138.0 116.0 153.0 91.7 120.0 120.0 128.0 111.0 146.0 88.5
90 150.0 150.0 155.0 142.0 166.0 112.0 144.0 144.0 148.0 139.0 161.0 111.0 137.0 137.0 139.0 136.0 154.0 109.0 130.0 130.0 130.0 130.0 146.0 107.0
75 139.0 114.0 155.0 89.8 163.0 60.4 129.0 109.0 149.0 85.4 159.0 57.9 120.0 104.0 141.0 89.5 154.0 55.0 109.0 98.9 131.0 85.1 147.0 51.6
5000 80 140.0 136.0 156.0 109.0 164.0 81.3 130.0 130.0 149.0 106.0 160.0 79.1 123.0 123.0 141.0 102.0 155.0 75.8 115.0 115.0 131.0 97.5 147.0 72.2
85 147.0 147.0 157.0 129.0 166.0 98.2 141.0 141.0 150.0 126.0 161.0 96.8 133.0 133.0 141.0 123.0 155.0 94.8 125.0 125.0 131.0 118.0 148.0 91.9
90 155.0 155.0 158.0 148.0 167.0 115.0 149.0 149.0 151.0 147.0 163.0 115.0 143.0 143.0 143.0 143.0 157.0 114.0 135.0 135.0 135.0 135.0 149.0 111.0
75 142.0 120.0 157.0 91.3 164.0 61.5 132.0 115.0 151.0 88.8 160.0 59.0 122.0 110.0 143.0 84.2 155.0 56.1 112.0 104.0 133.0 89.9 148.0 52.9
5500 80 143.0 143.0 158.0 112.0 165.0 82.0 135.0 135.0 152.0 110.0 161.0 80.4 127.0 127.0 143.0 107.0 156.0 78.3 119.0 119.0 134.0 102.0 149.0 74.7
85 152.0 152.0 159.0 133.0 167.0 99.9 145.0 145.0 152.0 132.0 163.0 99.1 138.0 138.0 144.0 129.0 157.0 97.4 130.0 130.0 134.0 125.0 150.0 95.0
90 159.0 159.0 160.0 154.0 169.0 118.0 153.0 153.0 153.0 153.0 164.0 118.0 147.0 147.0 147.0 147.0 158.0 117.0 140.0 140.0 140.0 140.0 151.0 116.0
75 145.0 125.0 158.0 93.3 165.0 62.5 135.0 120.0 153.0 91.2 161.0 60.1 125.0 115.0 145.0 87.3 156.0 57.2 115.0 110.0 136.0 82.8 149.0 54.0
6000 80 147.0 147.0 159.0 115.0 166.0 82.9 140.0 140.0 153.0 114.0 162.0 81.7 132.0 132.0 145.0 111.0 157.0 79.3 123.0 123.0 136.0 107.0 150.0 76.5
85 155.0 155.0 161.0 137.0 168.0 101.1 149.0 149.0 154.0 137.0 164.0 101.0 142.0 142.0 146.0 135.0 158.0 99.8 134.0 134.0 137.0 131.0 151.0 97.8
90 161.0 161.0 162.0 159.0 170.0 120.0 156.0 156.0 156.0 156.0 166.0 121.0 150.0 150.0 150.0 150.0 160.0 121.0 143.0 143.0 143.0 143.0 152.0 119.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

RT-PRC001-EN 21
Performance (15, 17½ Ton)
Data Standard Efficiency

Table PD-2 — Gross Cooling Capacities (MBH) 15 Ton Three Phase YC*180B3, B4, BW, BK
Ambient Temperature
85 95 105 115
Enter.
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 168.0 133.0 188.0 106.0 198.0 73.0 157.0 128.0 181.0 101.0 194.0 70.4 147.0 122.0 172.0 97.0 187.0 67.3 137.0 117.0 162.0 92.1 179.0 63.2
5400 80 168.0 156.0 188.0 128.0 199.0 97.3 155.0 155.0 181.0 125.0 195.0 94.3 149.0 143.0 172.0 120.0 188.0 90.8 140.0 137.0 162.0 115.0 179.0 86.7
85 174.0 174.0 189.0 150.0 200.0 117.0 166.0 166.0 182.0 147.0 196.0 115.0 158.0 158.0 172.0 143.0 189.0 113.0 150.0 150.0 162.0 138.0 180.0 110.0
90 184.0 184.0 190.0 172.0 202.0 136.0 177.0 177.0 183.0 170.0 197.0 135.0 170.0 170.0 170.0 170.0 190.0 133.0 162.0 162.0 165.0 157.0 181.0 131.0
75 172.0 140.0 190.0 110.0 199.0 74.3 161.0 134.0 184.0 106.0 195.0 71.7 151.0 129.0 175.0 101.0 189.0 68.7 140.0 124.0 165.0 96.1 181.0 64.9
6000 80 169.0 169.0 191.0 133.0 200.0 99.4 164.0 157.0 184.0 130.0 196.0 97.2 155.0 151.0 176.0 126.0 190.0 93.8 145.0 145.0 165.0 121.0 182.0 89.9
85 181.0 181.0 192.0 156.0 202.0 119.0 173.0 173.0 185.0 154.0 198.0 118.0 165.0 165.0 176.0 151.0 191.0 116.0 157.0 157.0 166.0 146.0 183.0 113.0
90 189.0 189.0 193.0 179.0 204.0 140.0 183.0 183.0 183.0 183.0 199.0 139.0 176.0 176.0 178.0 171.0 193.0 138.0 168.0 168.0 170.0 166.0 184.0 136.0
75 176.0 147.0 192.0 112.0 200.0 75.5 165.0 141.0 186.0 110.0 196.0 73.0 154.0 136.0 178.0 105.0 190.0 69.8 144.0 130.0 168.0 99.8 182.0 66.1
6600 80 178.0 171.0 193.0 136.0 201.0 101.0 169.0 165.0 187.0 135.0 197.0 98.8 160.0 159.0 178.0 131.0 191.0 96.1 150.0 150.0 168.0 127.0 183.0 92.6
85 185.0 185.0 194.0 161.0 203.0 122.0 179.0 179.0 188.0 160.0 199.0 121.0 171.0 171.0 179.0 158.0 193.0 119.0 163.0 163.0 169.0 153.0 185.0 116.0
90 193.0 193.0 193.0 193.0 205.0 143.0 188.0 188.0 188.0 188.0 201.0 143.0 181.0 181.0 182.0 178.0 195.0 142.0 173.0 173.0 174.0 174.0 186.0 140.0
75 179.0 152.0 194.0 114.0 201.0 76.7 168.0 147.0 188.0 112.0 197.0 74.2 158.0 142.0 180.0 109.0 191.0 71.0 142.0 142.0 170.0 103.0 183.0 67.2
7200 80 182.0 177.0 195.0 140.0 202.0 103.0 173.0 172.0 189.0 139.0 198.0 100.0 164.0 164.0 181.0 136.0 192.0 97.6 155.0 155.0 171.0 132.0 184.0 94.4
85 189.0 189.0 196.0 166.0 204.0 125.0 183.0 183.0 190.0 166.0 200.0 123.0 176.0 176.0 182.0 164.0 194.0 121.0 167.0 167.0 167.0 167.0 186.0 119.0
90 197.0 197.0 197.0 197.0 206.0 146.0 192.0 192.0 193.0 187.0 202.0 146.0 185.0 185.0 186.0 184.0 196.0 146.0 177.0 177.0 177.0 177.0 188.0 144.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-3 — Gross Cooling Capacities (MBH) 17½ Ton Three Phase YC*210C3, C4, CW, CK
AmbientTemperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 195.0 171.0 213.0 127.0 224.0 83.3 182.0 164.0 206.0 124.0 219.0 80.1 169.0 158.0 195.0 119.0 213.0 76.1 155.0 151.0 181.0 113.0 204.0 71.8
6300 80 200.0 200.0 214.0 157.0 226.0 114.0 191.0 191.0 207.0 156.0 221.0 112.0 180.0 180.0 196.0 153.0 214.0 110.0 168.0 168.0 183.0 147.0 205.0 106.0
85 211.0 211.0 217.0 188.0 229.0 140.0 204.0 204.0 209.0 188.0 223.0 139.0 195.0 195.0 199.0 186.0 216.0 139.0 184.0 184.0 187.0 182.0 206.0 137.0
90 219.0 219.0 220.0 217.0 230.0 164.0 214.0 214.0 214.0 214.0 225.0 167.0 207.0 207.0 207.0 207.0 218.0 169.0 198.0 198.0 198.0 198.0 208.0 168.0
75 199.0 181.0 215.0 131.0 225.0 84.7 187.0 176.0 208.0 129.0 221.0 81.4 174.0 169.0 198.0 125.0 215.0 77.7 160.0 160.0 185.0 119.0 206.0 73.4
7000 80 206.0 206.0 217.0 164.0 228.0 116.0 198.0 198.0 210.0 164.0 222.0 114.0 188.0 188.0 200.0 162.0 216.0 113.0 176.0 176.0 187.0 157.0 207.0 110.0
85 216.0 216.0 220.0 197.0 230.0 144.0 210.0 210.0 213.0 198.0 225.0 144.0 202.0 202.0 204.0 198.0 218.0 145.0 192.0 192.0 192.0 192.0 209.0 144.0
90 224.0 224.0 224.0 224.0 233.0 172.0 219.0 219.0 219.0 219.0 227.0 173.0 212.0 212.0 212.0 212.0 221.0 177.0 204.0 204.0 204.0 204.0 211.0 177.0
75 203.0 191.0 217.0 135.0 226.0 86.1 192.0 187.0 211.0 138.0 222.0 82.9 178.0 178.0 201.0 131.0 216.0 79.2 165.0 165.0 188.0 126.0 208.0 75.0
7700 80 211.0 211.0 219.0 169.0 229.0 118.0 204.0 204.0 212.0 171.0 224.0 117.0 194.0 194.0 203.0 170.0 218.0 116.0 183.0 183.0 191.0 167.0 209.0 114.0
85 220.0 220.0 222.0 203.0 232.0 147.0 214.0 214.0 216.0 207.0 226.0 148.0 207.0 207.0 207.0 207.0 220.0 150.0 197.0 197.0 197.0 197.0 211.0 150.0
90 226.0 226.0 226.0 226.0 235.0 176.0 223.0 223.0 222.0 222.0 229.0 179.0 216.0 216.0 216.0 216.0 223.0 184.0 208.0 208.0 208.0 208.0 214.0 186.0
75 206.0 199.0 218.0 138.0 227.0 87.8 195.0 195.0 212.0 143.0 223.0 84.3 183.0 183.0 203.0 136.0 217.0 80.6 171.0 171.0 190.0 132.0 209.0 76.5
8400 80 214.0 214.0 221.0 174.0 230.0 120.0 208.0 208.0 214.0 178.0 226.0 120.0 199.0 199.0 205.0 178.0 219.0 119.0 188.0 188.0 194.0 176.0 211.0 117.0
85 222.0 222.0 224.0 210.0 233.0 150.0 217.0 217.0 218.0 215.0 228.0 151.0 211.0 211.0 211.0 211.0 222.0 155.0 202.0 202.0 202.0 202.0 213.0 156.0
90 229.0 229.0 229.0 229.0 236.0 181.0 225.0 225.0 225.0 225.0 231.0 184.0 220.0 220.0 219.0 219.0 225.0 190.0 212.0 212.0 212.0 212.0 216.0 193.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

22 RT-PRC001-EN
Performance (20, 25 Ton)
Data Standard Efficiency

Table PD-4 — Gross Cooling Capacities (MBH) 20 Ton Three Phase YC*240B3, B4, BW, BK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 223.0 180.0 251.0 143.0 265.0 97.7 209.0 173.0 242.0 137.0 260.0 94.3 195.0 165.0 228.0 130.0 252.0 90.3 180.0 158.0 212.0 135.0 241.0 85.5
7200 80 226.0 214.0 252.0 173.0 267.0 131.0 208.0 208.0 242.0 169.0 261.0 127.0 197.0 197.0 228.0 162.0 253.0 122.0 186.0 186.0 213.0 155.0 242.0 117.0
85 235.0 235.0 253.0 204.0 268.0 158.0 224.0 224.0 242.0 200.0 262.0 156.0 213.0 213.0 229.0 194.0 253.0 153.0 201.0 201.0 214.0 188.0 242.0 149.0
90 248.0 248.0 255.0 234.0 271.0 185.0 239.0 239.0 245.0 232.0 264.0 185.0 228.0 228.0 228.0 228.0 255.0 183.0 217.0 217.0 217.0 217.0 243.0 179.0
75 229.0 190.0 255.0 148.0 267.0 99.4 215.0 183.0 246.0 142.0 262.0 96.1 200.0 175.0 233.0 136.0 254.0 92.2 185.0 168.0 218.0 129.0 244.0 87.1
8000 80 228.0 228.0 256.0 180.0 268.0 134.0 217.0 217.0 246.0 176.0 264.0 131.0 205.0 205.0 233.0 171.0 255.0 127.0 193.0 193.0 218.0 164.0 245.0 121.0
85 243.0 243.0 257.0 212.0 271.0 162.0 233.0 233.0 247.0 210.0 265.0 161.0 222.0 222.0 234.0 206.0 257.0 158.0 210.0 210.0 220.0 199.0 245.0 155.0
90 255.0 255.0 259.0 245.0 273.0 190.0 247.0 247.0 247.0 247.0 267.0 191.0 237.0 237.0 237.0 237.0 258.0 190.0 226.0 226.0 226.0 226.0 247.0 187.0
75 234.0 199.0 257.0 151.0 268.0 101.0 220.0 192.0 249.0 147.0 263.0 97.9 205.0 184.0 237.0 141.0 256.0 93.7 190.0 177.0 222.0 134.0 246.0 88.6
8800 80 236.0 236.0 259.0 185.0 270.0 136.0 224.0 224.0 249.0 183.0 265.0 134.0 212.0 212.0 237.0 178.0 257.0 130.0 200.0 200.0 222.0 172.0 247.0 126.0
85 250.0 250.0 260.0 220.0 273.0 165.0 240.0 240.0 251.0 219.0 267.0 165.0 229.0 229.0 239.0 216.0 259.0 163.0 217.0 217.0 225.0 210.0 248.0 160.0
90 260.0 260.0 263.0 254.0 275.0 194.0 253.0 253.0 253.0 253.0 270.0 196.0 244.0 244.0 244.0 244.0 261.0 196.0 233.0 233.0 233.0 233.0 250.0 194.0
75 238.0 208.0 259.0 154.0 269.0 103.0 224.0 201.0 251.0 151.0 265.0 99.6 209.0 193.0 240.0 146.0 257.0 95.1 194.0 186.0 225.0 139.0 248.0 89.2
9600 80 242.0 242.0 261.0 190.0 271.0 137.0 231.0 231.0 252.0 189.0 266.0 136.0 219.0 219.0 240.0 185.0 259.0 133.0 206.0 206.0 226.0 180.0 249.0 129.0
85 254.0 254.0 263.0 227.0 274.0 167.0 246.0 246.0 254.0 227.0 269.0 168.0 236.0 236.0 243.0 225.0 261.0 167.0 224.0 224.0 229.0 220.0 251.0 165.0
90 264.0 264.0 264.0 264.0 277.0 198.0 258.0 258.0 258.0 258.0 272.0 201.0 249.0 249.0 249.0 249.0 263.0 202.0 239.0 239.0 239.0 239.0 252.0 201.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-5— Gross Cooling Capacities (MBH) 25 Ton Three Phase YC*300B3, B4, BW, BK
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 266 224 299 174 319 118 247 215 285 167 309 113 228 205 266 172 297 108 209 196 244 163 280 99.9
80 270 268 300 215 321 161 252 252 285 209 311 155 237 237 266 200 297 149 221 221 244 190 280 142
9000 85 286 286 301 255 323 196 272 272 286 250 312 194 256 256 267 242 298 189 240 240 246 233 281 183
90 301 301 304 295 326 232 289 289 289 289 314 231 275 275 275 275 300 229 259 259 259 259 282 224
75 272 237 303 180 322 120 253 227 290 174 312 115 234 218 271 165 300 109 214 208 249 156 284 102
80 277 277 304 223 324 171 262 262 290 219 314 161 246 246 271 211 301 155 229 229 249 201 284 147
10000 85 294 294 306 266 327 208 282 282 291 263 316 200 266 266 273 257 302 197 249 249 253 248 285 192
90 308 308 310 309 329 239 297 297 297 297 318 240 284 284 284 284 304 239 268 268 268 268 286 235
75 275 243 305 183 323 122 256 233 291 177 314 117 236 223 273 188 301 111 216 214 251 178 285 103
80 282 282 306 227 325 174 267 267 292 223 315 162 250 250 273 216 302 157 233 233 251 206 286 150
10500 85 298 298 308 272 328 216 286 286 294 270 317 203 270 270 276 264 304 200 253 253 256 255 286 196
90 312 312 311 311 330 256 301 301 301 301 320 244 288 288 288 288 306 244 273 273 272 272 288 241
75 278 248 306 185 324 123 258 239 293 181 315 118 239 229 275 172 302 113 217 217 253 184 286 104
80 286 286 308 231 325 160 271 271 294 228 316 163 254 254 276 221 304 160 237 237 253 212 287 153
11000 85 301 301 310 277 327 224 289 289 296 276 319 205 274 274 278 271 305 204 257 257 257 257 288 200
90 314 314 314 314 330 266 304 304 304 304 321 248 291 291 291 291 307 249 276 276 276 276 289 246
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%.

*Indicates both downflow and horizontal units.

RT-PRC001-EN 23
Performance (12½ Ton)
Data High Efficiency

Table PD-6 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase YC*151C3, C4, CW— Standard Refrigeration System
AmbientTemperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 137.0 116.0 157.0 90.2 166.0 60.8 127.0 110.0 151.0 87.1 163.0 58.5 116.0 105.0 140.0 82.3 158.0 55.8 106.0 99.7 128.0 80.6 152.0 52.8
4500 80 140.0 139.0 158.0 111.0 167.0 82.9 130.0 130.0 151.0 109.0 164.0 80.8 122.0 122.0 141.0 104.0 159.0 77.8 114.0 114.0 128.0 98.5 152.0 74.6
85 149.0 149.0 158.0 132.0 169.0 100.0 142.0 142.0 151.0 131.0 165.0 99.4 133.0 133.0 141.0 126.0 159.0 98.2 125.0 125.0 130.0 121.0 152.0 96.0
90 158.0 158.0 160.0 153.0 170.0 118.0 152.0 152.0 154.0 152.0 166.0 118.0 145.0 145.0 145.0 145.0 160.0 118.0 137.0 137.0 137.0 137.0 153.0 117.0
75 141.0 123.0 159.0 93.4 167.0 61.6 131.0 117.0 154.0 90.9 164.0 59.4 120.0 112.0 144.0 86.6 159.0 56.8 109.0 107.0 132.0 81.0 153.0 53.7
5000 80 145.0 145.0 160.0 116.0 168.0 84.1 136.0 136.0 154.0 114.0 165.0 82.4 128.0 128.0 144.0 110.0 161.0 80.9 119.0 119.0 132.0 105.0 154.0 77.5
85 155.0 155.0 161.0 138.0 170.0 103.0 148.0 148.0 155.0 138.0 166.0 102.0 140.0 140.0 145.0 135.0 161.0 102.0 131.0 131.0 134.0 129.0 154.0 100.0
90 162.0 162.0 163.0 160.0 172.0 121.0 157.0 157.0 157.0 157.0 168.0 122.0 151.0 151.0 151.0 151.0 163.0 123.0 143.0 143.0 143.0 143.0 155.0 122.0
75 145.0 129.0 161.0 95.8 168.0 62.6 134.0 124.0 156.0 94.4 165.0 60.4 123.0 119.0 147.0 90.4 161.0 57.8 112.0 112.0 135.0 85.1 154.0 54.6
5500 80 150.0 150.0 162.0 119.0 169.0 85.2 142.0 142.0 156.0 119.0 167.0 84.0 133.0 133.0 147.0 116.0 162.0 82.4 124.0 124.0 135.0 111.0 155.0 80.1
85 158.0 158.0 163.0 143.0 172.0 104.0 153.0 153.0 157.0 144.0 168.0 104.0 146.0 146.0 149.0 143.0 163.0 105.0 137.0 137.0 137.0 137.0 156.0 104.0
90 165.0 165.0 165.0 165.0 173.0 123.0 161.0 161.0 161.0 161.0 170.0 126.0 156.0 156.0 156.0 156.0 164.0 127.0 149.0 149.0 149.0 149.0 157.0 127.0
75 148.0 136.0 162.0 97.9 168.0 63.5 137.0 131.0 157.0 97.1 166.0 61.4 126.0 125.0 150.0 94.3 162.0 58.9 116.0 116.0 138.0 89.0 155.0 55.6
6000 80 154.0 154.0 163.0 123.0 170.0 86.2 147.0 147.0 158.0 124.0 168.0 85.8 138.0 138.0 150.0 122.0 162.0 83.3 128.0 128.0 138.0 117.0 156.0 82.2
85 161.0 161.0 165.0 147.0 172.0 106.0 157.0 157.0 160.0 150.0 169.0 106.0 151.0 151.0 152.0 150.0 164.0 107.0 142.0 142.0 142.0 142.0 158.0 107.0
90 167.0 167.0 167.0 167.0 174.0 126.0 164.0 164.0 164.0 164.0 171.0 128.0 159.0 159.0 159.0 159.0 166.0 131.0 153.0 153.0 153.0 153.0 159.0 132.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

Table PD-7 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase Y*D151C3, C4, CW— Dehumidification (Hot Gas Reheat) or TXV Option
AmbientTemperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 139.1 110.9 155.6 88.8 173.4 61.6 131.9 106.9 148.0 85.0 165.1 57.9 124.2 102.6 139.7 81.0 156.3 54.0 116.1 98.2 130.8 76.7 146.9 49.9
4000 80 140.0 131.2 155.9 107.2 173.6 82.5 133.0 127.4 148.2 103.3 165.3 78.6 125.5 123.2 139.9 99.1 156.5 74.7 118.1 116.5 131.1 94.7 147.1 70.5
85 144.7 144.7 156.2 127.2 173.8 102.8 138.8 138.8 148.5 123.4 165.5 99.0 132.2 132.2 140.3 119.3 156.7 95.0 125.2 125.2 131.6 114.9 147.3 90.8
90 153.0 153.0 157.3 147.4 174.1 122.9 146.9 146.9 149.8 143.8 165.7 119.1 140.3 140.3 140.5 140.5 156.9 115.2 133.1 133.1 134.0 132.6 147.5 111.0
75 142.5 117.9 159.0 93.8 176.9 63.1 135.1 114.0 151.1 89.9 168.4 59.4 127.1 109.6 142.6 85.9 159.3 55.5 118.8 105.1 133.4 81.5 149.7 51.4
4500 80 143.9 140.7 159.4 113.6 177.1 86.1 136.2 136.2 151.4 109.7 168.6 82.3 129.7 129.7 142.9 105.5 159.5 78.3 122.3 122.3 133.7 101.0 149.8 74.0
85 150.9 150.9 159.9 135.9 177.4 108.8 144.6 144.6 152.0 132.1 168.9 104.9 137.8 137.8 143.5 128.1 159.7 100.8 130.5 130.5 134.6 123.7 150.0 96.6
90 159.6 159.6 161.7 158.5 177.8 131.0 153.2 153.2 154.4 152.1 169.1 127.2 146.2 146.2 146.5 146.5 160.0 123.3 138.7 138.7 139.0 139.0 150.3 119.2
75 145.3 124.7 161.8 98.6 179.7 64.6 137.8 120.8 153.7 94.7 171.0 60.8 129.7 116.4 144.9 90.7 161.8 56.8 121.1 111.9 135.6 86.3 151.9 52.7
5000 80 147.9 146.8 162.2 119.7 180.0 89.7 141.0 141.0 154.0 115.8 171.3 85.8 133.9 133.9 145.3 111.7 162.0 81.7 126.5 126.5 135.9 107.2 152.1 77.5
85 156.3 156.3 163.1 144.3 180.4 114.5 149.7 149.7 154.9 140.6 171.6 110.6 142.7 142.7 146.3 136.6 162.2 106.5 135.0 135.0 137.3 132.3 152.3 102.3
90 165.4 165.4 166.2 165.6 180.8 138.8 158.6 158.6 158.9 158.9 172.0 135.1 151.4 151.4 151.7 151.7 162.6 131.2 143.7 143.7 143.9 143.9 152.7 127.1
75 147.8 131.2 164.2 103.4 182.1 65.9 140.1 127.4 155.8 99.5 173.3 62.0 131.9 123.0 146.9 95.3 163.8 58.1 123.2 118.5 137.4 90.9 153.7 54.0
5500 80 151.7 151.7 164.7 125.6 182.5 93.0 145.1 145.1 156.3 121.8 173.5 89.1 137.9 137.9 147.3 117.7 164.0 85.0 130.1 130.1 137.8 113.2 153.9 80.8
85 161.0 161.0 165.8 152.4 182.8 119.8 154.2 154.2 157.6 148.8 173.8 116.0 146.9 146.9 148.9 145.0 164.3 112.0 139.0 139.0 139.2 139.2 154.1 107.7
90 170.4 170.4 170.7 170.7 183.5 146.3 163.4 163.4 163.7 163.7 174.4 142.7 155.9 155.9 156.2 156.2 164.9 138.8 147.9 147.9 148.2 148.2 154.8 134.8
75 150.0 137.6 166.2 108.1 184.1 67.2 142.2 133.8 157.7 104.1 175.1 63.4 133.9 129.5 148.6 100.0 165.5 59.4 124.5 124.5 138.9 95.6 155.3 55.3
6000 80 155.6 155.6 166.8 131.4 184.5 96.3 148.8 148.8 158.2 127.6 175.4 92.3 141.3 141.3 149.1 123.5 165.8 88.2 133.4 133.4 139.5 119.1 155.5 84.0
85 165.2 165.2 168.4 160.4 185.0 125.0 158.1 158.1 158.4 158.4 175.8 121.2 150.6 150.6 150.8 150.8 166.0 117.3 142.5 142.5 142.7 142.7 155.8 113.1
90 174.9 174.9 175.2 175.2 185.8 153.7 167.7 167.7 168.0 168.0 176.6 150.1 160.0 160.0 160.2 160.2 166.9 146.3 151.7 151.7 152.0 152.0 156.8 142.3
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

24 RT-PRC001-EN
Performance (15 Ton)
Data High Efficiency

Table PD-8— Gross Cooling Capacities (MBH) 15 Ton Three Phase YC*181C3, C4, CW— Standard Refrigeration System
AmbientTemperature
85 95 105 115
Enter.
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 172 144 194 112 205 75.2 159 138 185 107 200 71.9 147 131 172 101 193 68 130 130 158 97 183 63.4
5400 80 175 169 195 138 207 103 164 162 186 134 202 99.7 153 153 173 128 194 95.4 142 142 158 122 183 90.5
85 185 185 196 164 209 126 176 176 186 161 203 124 165 165 174 156 195 122 155 155 155 155 184 117
90 195 195 195 195 211 149 188 188 190 184 204 148 178 178 179 179 196 147 168 168 167 167 184 144
75 177 153 197 116 207 76 164 147 189 112 202 73.2 151 140 176 106 195 69.3 138 131 162 99.8 185 64.8
6000 80 181 180 198 144 209 105 170 170 189 142 204 103 159 159 177 136 196 99.4 148 148 162 130 186 94.6
85 192 192 199 172 211 129 183 183 190 171 206 129 173 173 173 173 197 127 162 162 162 162 186 124
90 201 201 200 200 214 153 194 194 195 194 208 155 185 185 185 185 199 154 175 175 175 175 187 152
75 181 162 198 123 208 76.6 168 155 191 117 204 74.4 152 152 180 111 197 70.6 142 139 165 105 187 66.2
6600 80 186 186 200 151 210 107 177 177 192 148 206 105 166 166 180 144 198 102 154 154 166 137 188 98.6
85 197 197 202 179 213 131 189 189 194 180 208 132 179 179 183 173 199 132 168 168 170 166 189 129
90 204 204 205 202 215 157 199 199 199 199 209 159 191 191 191 191 201 160 181 181 181 181 190 160
75 184 170 200 127 209 79.1 168 168 193 121 206 76.4 156 156 182 116 198 71.9 145 145 168 110 189 67.4
7200 80 191 191 202 153 211 108 182 182 194 154 207 107 171 171 183 151 199 105 159 159 169 145 190 102
85 200 200 204 185 214 134 194 194 194 194 209 136 185 185 187 181 201 135 174 174 174 174 191 134
90 207 207 208 207 217 160 203 203 203 203 211 163 195 195 195 195 203 166 186 186 186 186 192 167
Notes:
1 All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-9— Gross Cooling Capacities (MBH) 15 Ton Three Phase Y*D181C3, C4, CW— Dehumidification (Hot Gas Reheat) or TXV Option
AmbientTemperature
85 95 105 115
Enter.
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 170.7 136.0 190.4 106.1 211.6 75.2 162.3 131.1 181.4 101.4 201.8 70.6 153.6 126.0 172.0 96.5 191.5 65.9 144.5 120.8 162.0 91.4 180.7 61.0
4800 80 171.7 160.6 190.8 130.7 211.9 100.2 160.6 160.6 181.9 125.9 202.1 95.5 153.2 153.2 172.4 121.0 191.9 90.7 146.9 139.9 162.3 115.8 181.1 85.8
85 177.7 174.7 191.1 154.8 212.4 124.6 170.2 168.8 182.2 150.0 202.6 119.9 162.7 162.7 172.9 144.9 192.4 115.0 154.8 154.8 163.1 139.7 181.6 110.0
90 187.3 187.3 192.5 179.3 212.8 148.8 180.0 180.0 179.9 179.9 203.0 144.1 172.3 172.3 174.8 164.7 192.6 139.0 164.2 164.2 166.1 157.7 181.9 133.9
75 174.9 144.5 194.5 112.1 216.0 77.0 166.3 139.5 185.3 107.3 205.8 72.4 157.3 134.3 175.6 101.5 195.2 67.6 147.9 129.0 165.4 96.4 184.0 62.7
5400 80 174.5 174.5 194.9 138.5 216.4 104.7 168.9 161.1 185.6 133.5 206.3 99.9 160.7 156.2 175.9 128.4 195.7 95.0 152.2 147.5 165.8 123.2 184.6 90.0
85 184.9 184.9 195.7 165.2 216.9 131.7 177.3 177.3 186.6 160.3 206.8 126.9 169.4 169.4 177.0 155.3 196.2 122.0 161.1 161.1 166.9 150.0 185.2 116.9
90 195.2 195.2 195.2 195.2 217.1 158.5 187.5 187.5 189.8 182.7 207.1 153.6 179.4 179.4 181.1 173.6 196.5 148.5 170.9 170.9 172.1 166.5 185.6 143.3
75 178.4 152.6 198.2 116.1 219.6 78.7 169.6 147.6 188.6 111.3 209.2 74.0 160.5 142.3 178.6 106.3 198.2 69.2 150.9 137.0 168.1 101.1 186.8 64.3
6000 80 182.0 177.3 198.5 145.8 220.1 108.9 174.1 168.5 189.0 140.8 209.7 104.1 165.7 161.8 179.0 135.7 198.8 99.2 156.8 154.9 168.6 130.4 187.5 94.1
85 191.4 191.4 199.7 175.4 220.7 138.6 183.6 183.6 190.3 170.4 210.3 133.8 175.4 175.4 180.5 165.2 199.4 128.8 166.7 166.7 166.6 166.6 187.8 123.6
90 202.3 202.3 204.1 198.8 221.0 167.8 194.3 194.3 195.6 189.2 210.7 162.8 185.8 185.8 186.7 182.3 200.0 157.7 176.9 176.9 177.3 175.3 188.8 152.5
75 181.5 160.5 201.1 120.8 222.6 80.3 172.6 155.4 191.4 115.9 212.0 75.6 163.3 150.2 181.1 110.9 200.8 70.8 150.6 150.6 170.4 105.7 189.1 65.7
6600 80 186.8 182.2 201.6 153.0 223.2 113.0 178.6 175.7 191.9 147.9 212.6 108.2 170.0 169.1 181.8 142.7 201.5 103.2 161.0 161.0 171.1 137.4 189.9 98.1
85 197.1 197.1 203.2 185.2 223.8 145.3 189.1 189.1 193.7 180.2 212.9 140.3 180.5 180.5 180.4 180.4 201.9 135.2 171.5 171.5 171.4 171.4 190.3 129.9
90 208.4 208.4 209.5 204.4 224.3 176.8 200.1 200.1 200.8 197.7 214.0 171.8 191.4 191.4 191.5 190.9 203.0 166.7 182.1 182.1 182.1 182.1 191.5 161.4
75 184.4 168.2 203.7 125.4 225.2 81.9 175.3 163.1 193.7 120.5 214.3 77.0 163.0 163.0 183.0 115.3 202.9 72.1 154.3 154.3 172.2 109.9 191.0 67.1
7200 80 191.1 189.2 204.2 159.9 225.9 116.9 182.5 182.5 194.4 154.9 215.0 112.0 174.0 174.0 184.1 149.7 203.7 107.1 165.0 165.0 173.3 144.2 191.9 101.9
85 202.2 202.2 202.1 202.1 226.2 151.6 193.9 193.9 193.8 193.8 215.5 146.5 185.1 185.1 187.2 181.0 204.2 141.4 175.8 175.8 177.4 169.9 192.5 136.0
90 214.0 214.0 214.4 212.7 227.3 185.7 205.3 205.3 205.2 205.2 216.8 180.7 196.3 196.3 196.2 196.2 205.6 175.5 186.8 186.8 186.7 186.7 194.0 170.1
Notes:
1 All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Indicates both downflow and horizontal units.


*

RT-PRC001-EN 25
Performance (17½ Ton)
Data High Efficiency

Table PD-10 — Gross Cooling Capacities (MBH)17½ Ton Three PhaseYC*211C3, C4, CW— Standard Refrigeration System
AmbientTemperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 200.0 169.0 224.0 130.0 233.0 86.2 184.0 162.0 215.0 125.0 231.0 83.3 169.0 154.0 199.0 118.0 226.0 79.3 147.0 147.0 180.0 113.0 214.0 74.2
6300 80 202.0 202.0 225.0 161.0 236.0 118.0 190.0 190.0 216.0 158.0 234.0 117.0 177.0 177.0 200.0 151.0 227.0 112.0 164.0 164.0 181.0 142.0 214.0 107.0
85 216.0 216.0 227.0 191.0 239.0 143.0 206.0 206.0 217.0 190.0 236.0 146.0 193.0 193.0 202.0 184.0 228.0 144.0 180.0 180.0 185.0 176.0 215.0 139.0
90 227.0 227.0 230.0 221.0 242.0 169.0 220.0 220.0 220.0 220.0 239.0 175.0 209.0 209.0 209.0 209.0 229.0 174.0 196.0 196.0 195.0 195.0 217.0 171.0
75 205.0 180.0 226.0 134.0 234.0 87.6 190.0 172.0 219.0 131.0 233.0 84.8 174.0 164.0 204.0 124.0 228.0 80.8 155.0 155.0 184.0 116.0 218.0 76.0
7000 80 210.0 210.0 228.0 167.0 237.0 119.0 198.0 198.0 220.0 167.0 236.0 120.0 185.0 185.0 205.0 160.0 229.0 117.0 171.0 171.0 186.0 152.0 218.0 112.0
85 223.0 223.0 230.0 199.0 241.0 145.0 215.0 215.0 222.0 202.0 238.0 150.0 202.0 202.0 209.0 197.0 231.0 150.0 188.0 188.0 191.0 189.0 219.0 147.0
90 232.0 232.0 233.0 230.0 244.0 173.0 227.0 227.0 227.0 227.0 241.0 180.0 218.0 218.0 218.0 218.0 232.0 182.0 205.0 205.0 204.0 204.0 221.0 181.0
75 210.0 190.0 228.0 138.0 235.0 88.9 195.0 183.0 222.0 137.0 234.0 86.0 179.0 175.0 208.0 130.0 229.0 82.4 161.0 161.0 188.0 122.0 220.0 77.7
7700 80 217.0 217.0 231.0 173.0 239.0 120.0 206.0 206.0 223.0 174.0 237.0 121.0 192.0 192.0 209.0 169.0 231.0 121.0 178.0 178.0 190.0 161.0 221.0 116.0
85 228.0 228.0 232.0 206.0 242.0 148.0 221.0 221.0 226.0 211.0 240.0 153.0 210.0 210.0 214.0 209.0 234.0 156.0 196.0 196.0 195.0 195.0 222.0 154.0
90 235.0 235.0 235.0 235.0 245.0 176.0 232.0 232.0 232.0 232.0 243.0 185.0 224.0 224.0 224.0 224.0 235.0 189.0 213.0 213.0 212.0 212.0 224.0 191.0
75 214.0 200.0 230.0 141.0 236.0 90.3 200.0 193.0 224.0 141.0 235.0 87.4 181.0 181.0 211.0 136.0 230.0 83.8 166.0 166.0 191.0 128.0 222.0 79.2
8400 80 222.0 222.0 232.0 177.0 239.0 133.0 213.0 213.0 226.0 181.0 238.0 123.0 199.0 199.0 213.0 178.0 233.0 124.0 184.0 184.0 194.0 170.0 223.0 121.0
85 231.0 231.0 234.0 211.0 243.0 149.0 226.0 226.0 229.0 220.0 241.0 155.0 216.0 216.0 216.0 216.0 235.0 161.0 203.0 203.0 202.0 202.0 224.0 162.0
90 238.0 238.0 238.0 238.0 246.0 178.0 235.0 235.0 235.0 235.0 244.0 189.0 229.0 229.0 229.0 229.0 237.0 195.0 219.0 219.0 219.0 219.0 227.0 199.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

Table PD-11 — Gross Cooling Capacities (MBH)17½ Ton Three PhaseYC*211C3, C4, CW— TXV Option
AmbientTemperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 199.5 157.9 221.6 122.1 245.5 85.7 190.5 153.0 212.0 117.4 234.9 81.2 180.9 147.9 201.7 112.4 223.8 76.5 171.0 142.6 190.9 107.3 212.2 71.6
5600 80 200.9 187.5 221.9 150.5 245.8 114.8 192.2 182.6 212.3 145.8 235.3 110.1 179.9 179.9 202.0 140.8 224.1 105.2 173.8 166.9 191.2 135.6 212.5 100.2
85 207.3 204.9 222.5 179.2 246.2 142.9 199.3 198.8 213.0 174.6 235.4 138.1 190.6 190.6 202.7 169.6 224.4 133.3 182.0 182.0 192.0 164.4 212.8 128.2
90 217.4 217.4 224.2 208.4 246.5 171.0 209.5 209.5 214.9 203.9 235.8 166.2 201.4 201.4 201.3 201.3 224.8 161.4 192.6 192.6 195.4 187.3 213.2 156.4
75 203.9 167.7 226.2 127.9 250.3 87.7 194.8 162.9 216.2 123.2 239.2 83.0 185.0 157.7 205.6 118.1 227.8 78.4 174.8 152.4 194.5 112.9 215.8 73.5
6300 80 202.9 202.9 226.5 159.5 250.5 119.7 195.2 195.2 216.6 154.8 239.4 114.8 188.9 182.8 206.0 149.7 228.1 110.1 179.6 175.4 194.9 144.5 216.1 105.0
85 214.6 214.6 227.5 191.5 250.9 150.9 206.7 206.7 217.4 186.6 239.8 146.1 198.1 198.1 207.2 181.8 228.5 141.3 189.1 189.1 196.3 176.6 216.5 136.2
90 226.3 226.3 226.2 226.2 251.4 182.3 218.0 218.0 221.1 212.1 240.4 177.4 209.4 209.4 211.9 204.9 228.9 172.4 200.2 200.2 202.0 197.2 217.2 167.6
75 207.8 177.3 229.9 133.4 254.2 89.6 198.5 172.5 219.7 128.6 242.8 84.9 188.5 167.4 208.8 123.5 231.1 80.1 178.2 162.0 197.4 118.3 218.8 75.1
7000 80 212.0 205.1 230.4 168.2 254.5 124.4 203.5 198.3 220.0 163.5 243.1 119.6 194.3 190.9 209.4 158.4 231.4 114.7 184.7 183.5 198.1 153.1 219.2 109.6
85 221.9 221.9 231.8 203.6 254.9 158.8 213.4 213.4 221.6 198.6 243.5 153.8 204.7 204.7 211.2 193.7 231.8 149.0 195.4 195.4 200.2 188.5 219.6 143.9
90 234.1 234.1 236.8 229.0 255.6 193.4 225.4 225.4 227.5 221.6 244.3 188.5 216.5 216.5 217.7 214.0 232.5 183.4 206.9 206.9 207.6 206.7 220.6 178.6
75 211.3 186.8 233.0 138.7 257.4 91.4 201.8 181.9 222.6 133.9 245.7 86.5 191.8 176.7 211.5 128.8 233.8 81.7 181.3 171.3 199.9 123.5 221.3 76.7
7700 80 217.2 212.9 233.7 176.7 257.8 129.0 208.4 206.0 223.3 171.9 246.1 124.1 199.0 198.7 212.3 166.8 234.2 119.3 189.0 189.0 200.8 161.5 221.7 114.1
85 228.2 228.2 235.8 215.3 258.2 166.4 219.5 219.5 225.5 210.3 246.5 161.4 210.4 210.4 210.3 210.3 234.6 156.6 200.8 200.8 200.7 200.7 222.2 151.5
90 241.0 241.0 242.8 238.1 259.2 204.2 231.9 231.9 233.1 230.7 247.7 199.3 222.4 222.4 222.3 222.3 235.7 194.2 212.6 212.6 212.6 212.6 223.5 189.2
75 214.5 195.9 235.7 143.9 260.2 92.9 204.9 191.1 225.0 139.0 248.3 88.0 190.7 190.7 213.7 133.9 236.1 83.2 181.3 181.3 201.9 128.6 223.4 78.2
8400 80 221.9 220.3 236.6 185.0 260.5 133.5 212.1 212.1 225.8 180.0 248.6 128.5 203.1 203.1 214.8 175.0 236.5 123.7 193.4 193.4 203.2 169.7 223.8 118.5
85 233.9 233.9 239.5 226.8 261.0 173.9 224.8 224.8 224.7 224.7 249.2 168.9 215.5 215.5 215.4 215.4 236.9 163.8 205.5 205.5 207.7 200.6 224.4 158.9
90 247.0 247.0 248.0 246.9 262.4 214.8 237.7 237.7 237.6 237.6 250.7 209.8 227.8 227.8 227.8 227.8 238.6 204.7 217.8 217.8 217.7 217.7 226.3 199.7
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

26 RT-PRC001-EN
Performance (20 Ton)
Data High Efficiency

Table PD-12 — Gross Cooling Capacities (MBH) 20 Ton Three Phase YC*241C3, C4, CW— Standard Refrigeration System
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 246 205 273 158 284 105 228 196 263 152 280 101 208 186 246 145 273 96.5 191 176 222 136 261 91.5
7200 80 250 245 274 192 287 142 232 232 264 190 283 141 216 216 246 183 274 135 201 201 223 172 261 130
85 263 263 275 227 290 171 251 251 265 228 285 173 236 236 248 221 275 170 219 219 225 211 262 168
90 274 274 278 262 293 201 266 266 268 265 288 206 254 254 254 254 277 205 239 239 237 237 262 205
75 253 218 275 163 285 107 234 209 267 159 282 103 214 199 252 152 275 98.3 194 189 228 142 266 93.6
8000 80 257 257 277 199 289 144 243 243 268 199 285 143 227 227 252 194 277 140 210 210 228 184 266 136
85 270 270 279 236 292 174 261 261 270 240 288 177 247 247 255 237 278 177 230 230 232 226 266 177
90 280 280 282 273 295 205 274 274 274 274 291 212 264 264 264 264 280 214 250 250 248 248 267 218
75 258 230 278 167 287 109 240 221 270 164 284 105 219 211 256 159 277 100 199 199 232 149 269 95.5
8800 80 264 264 280 204 290 155 252 252 271 208 287 145 236 236 257 205 279 144 218 218 233 195 269 141
85 276 276 282 244 293 177 268 268 274 250 290 181 256 256 260 251 281 182 240 240 238 238 269 185
90 285 285 286 281 297 209 280 280 280 280 293 217 271 271 271 271 283 221 258 258 258 258 271 229
75 262 240 280 169 288 110 246 233 273 169 285 106 225 223 260 166 278 102 205 205 236 156 271 97.1
9600 80 270 270 282 209 291 161 260 260 274 215 288 147 245 245 261 215 281 147 226 226 237 205 271 146
85 280 280 284 250 295 179 274 274 277 260 291 184 263 263 265 263 282 186 248 248 246 246 272 193
90 288 288 288 288 298 212 284 284 284 284 294 222 276 276 276 276 285 228 264 264 265 265 275 240
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-13 — Gross Cooling Capacities (MBH) 20 Ton Three Phase YCD241C3, C4, CW— TXV Option
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 234.3 187.9 260.5 146.4 289.2 103.7 223.9 182.1 249.1 140.7 276.7 98.2 212.8 175.9 237.1 134.8 263.3 92.5 201.1 169.5 224.3 128.7 249.4 86.5
6400 80 235.9 221.8 260.8 180.1 289.4 138.0 225.7 215.9 249.4 174.3 276.9 132.3 214.9 209.8 237.3 168.2 263.6 126.5 202.8 202.8 224.6 161.9 249.6 120.4
85 243.8 243.8 261.4 213.2 289.7 171.3 234.9 234.9 250.1 207.4 277.2 165.6 225.3 225.3 238.2 201.3 264.0 159.7 215.3 215.3 225.7 195.0 250.0 153.6
90 257.1 257.1 263.2 246.7 290.1 204.5 247.9 247.9 252.1 240.8 277.5 198.6 238.1 238.1 240.6 234.8 264.3 192.6 227.7 227.7 228.5 224.2 250.4 186.3
75 239.8 199.6 266.0 153.5 295.0 106.1 229.0 193.6 254.2 147.8 282.1 100.6 217.6 187.4 241.8 141.7 268.2 94.7 205.6 180.9 228.6 138.4 253.8 88.7
7200 80 242.3 237.5 266.3 190.6 295.3 144.0 230.8 230.8 254.6 184.7 282.3 138.3 221.3 221.1 242.2 178.6 268.6 132.4 210.7 210.7 229.2 172.3 254.2 126.2
85 253.7 253.7 267.4 227.6 295.7 181.1 244.3 244.3 255.7 221.6 282.7 175.3 234.3 234.3 243.5 215.5 269.1 169.3 223.6 223.6 230.6 209.1 254.6 163.1
90 267.6 267.6 270.3 265.1 296.0 217.7 257.9 257.9 257.8 257.8 283.2 211.9 247.5 247.5 247.5 247.5 269.6 205.7 236.6 236.6 236.6 236.6 255.3 199.4
75 244.5 210.8 270.7 160.1 299.8 108.3 233.4 204.7 258.5 154.3 286.5 102.8 221.8 198.5 245.8 148.2 272.4 96.9 209.5 191.9 232.3 141.9 257.5 90.8
8000 80 248.1 248.1 271.1 200.8 300.1 149.8 238.5 238.5 259.0 194.8 286.8 144.0 228.4 228.4 246.3 188.7 272.8 138.1 217.6 217.6 232.9 182.3 258.0 131.8
85 262.5 262.5 272.6 241.6 300.5 190.5 252.6 252.6 260.7 235.6 287.3 184.7 242.1 242.1 248.1 229.3 273.3 178.7 231.0 231.0 235.0 222.9 258.3 172.1
90 277.2 277.2 277.0 277.0 301.0 230.6 266.9 266.9 266.8 266.8 288.0 224.7 256.0 256.0 256.0 256.0 274.1 218.5 244.6 244.6 244.5 244.5 259.4 212.1
75 248.5 221.7 274.6 166.6 303.7 110.4 237.3 215.6 262.1 160.6 290.2 104.8 225.4 209.3 249.0 154.6 275.8 98.9 213.0 202.7 235.3 148.3 260.6 92.7
8800 80 255.2 255.2 275.2 210.8 304.0 155.3 245.3 245.3 262.8 204.7 290.6 149.6 234.7 234.7 249.8 198.5 276.2 143.5 223.6 223.6 236.2 192.0 261.1 137.3
85 270.2 270.2 277.2 255.2 304.3 199.4 259.9 259.9 265.1 249.2 291.0 193.6 249.0 249.0 252.3 242.9 276.7 187.4 237.5 237.5 239.1 236.5 261.6 180.9
90 285.5 285.5 285.4 285.4 305.2 243.0 274.8 274.8 274.8 274.8 292.1 237.2 263.5 263.5 263.5 263.5 277.9 231.0 251.5 251.5 251.5 251.5 263.0 224.5
75 252.1 232.3 277.9 172.8 306.9 112.3 240.7 226.2 265.2 166.9 293.3 106.7 228.7 219.9 251.7 160.6 278.6 100.7 216.3 213.3 237.8 154.1 263.2 94.5
9600 80 261.5 261.5 278.7 220.4 307.3 160.6 251.2 251.2 266.1 214.3 293.8 155.0 240.4 240.4 252.8 208.0 279.2 148.9 228.8 228.8 238.9 201.5 263.8 142.6
85 277.0 277.0 281.4 268.6 307.7 208.4 266.4 266.4 269.2 262.5 294.2 202.3 255.1 255.1 254.9 254.9 279.7 196.0 243.1 243.1 243.0 243.0 264.4 189.6
90 292.8 292.8 292.8 292.8 308.7 255.2 281.8 281.8 281.8 281.8 295.6 249.4 270.1 270.1 270.1 270.1 281.3 243.2 257.7 257.7 257.7 257.7 266.2 236.7
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Indicates both downflow and horizontal units.


*

RT-PRC001-EN 27
Performance (20 Ton)
Data High Efficiency

Table PD-14 — Gross Cooling Capacities (MBH) 20 Ton Three Phase Y*D241C3, C4, CW— Dehumidification (Hot Gas Reheat) Option
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 223.7 175.3 250.2 138.3 279.0 98.8 213.5 169.3 239.0 132.3 266.6 93.0 202.6 163.0 227.2 126.1 253.7 87.0 191.3 156.4 214.9 119.7 240.2
6400 80 224.9 206.3 250.6 169.7 279.2 131.4 214.8 200.3 239.4 163.6 266.8 125.3 204.2 194.1 227.7 157.5 253.9 119.2 193.2 187.7 215.2 151.0 240.5
85 230.5 230.5 251.0 200.6 279.6 162.9 221.7 221.7 239.8 194.5 267.2 156.9 212.5 212.5 228.1 188.2 254.3 150.7 202.8 202.8 215.9 181.8 240.9
90 243.6 243.6 252.4 231.7 280.0 194.4 234.6 234.6 241.5 225.7 267.7 188.3 225.1 225.1 230.0 219.5 254.6 181.9 215.2 215.2 215.6 215.6 241.2
75 229.2 185.9 255.7 150.2 284.8 101.3 218.6 179.7 244.1 144.1 272.0 95.4 207.4 173.3 231.9 138.0 258.6 89.4 195.8 166.7 219.1 131.7 244.7
7200 80 231.1 220.6 256.3 179.6 285.1 137.0 220.8 214.5 244.6 173.3 272.3 130.9 208.4 208.4 232.5 167.0 258.9 124.7 199.2 197.3 219.8 160.4 245.0
85 240.3 240.3 256.9 213.7 285.5 172.0 231.1 231.1 245.4 207.5 272.7 165.9 221.4 221.4 233.3 201.2 259.4 159.7 211.2 211.2 220.8 194.7 245.5
90 254.0 254.0 259.2 248.5 286.0 206.7 244.5 244.5 248.0 242.5 273.2 200.5 234.5 234.5 235.0 235.0 259.8 194.1 224.0 224.0 225.1 224.1 246.0
75 233.9 196.0 260.5 150.9 289.7 103.6 223.0 189.8 248.6 144.8 276.5 97.7 211.5 183.3 236.1 138.4 262.7 91.4 199.6 176.7 223.0 131.9 248.4
8000 80 234.8 234.8 261.0 188.8 290.0 142.4 225.4 225.4 249.0 182.5 276.9 136.2 215.6 215.6 236.5 176.1 263.1 129.9 205.3 205.3 223.5 169.5 248.8
85 249.0 249.0 262.0 226.4 290.5 180.8 239.3 239.3 250.1 220.2 277.4 174.6 229.2 229.2 237.8 213.8 263.6 168.3 218.6 218.6 225.1 207.3 249.2
90 263.3 263.3 263.7 263.7 291.0 218.5 253.3 253.3 254.6 253.1 277.9 212.2 242.9 242.9 243.3 243.3 264.2 205.8 231.9 231.9 232.3 232.3 249.9
75 237.9 205.8 264.5 156.8 293.8 105.7 226.7 199.5 252.2 150.6 280.3 99.6 215.1 193.0 239.4 144.2 266.1 93.2 202.9 186.3 226.0 137.6 251.5
8800 80 242.3 242.3 265.0 197.7 294.1 147.5 232.1 232.1 252.7 191.4 280.6 141.3 221.9 221.9 239.9 184.9 266.6 135.0 211.2 211.2 226.6 178.2 251.9
85 256.5 256.5 266.4 238.7 294.7 189.2 246.5 246.5 254.3 232.4 281.0 182.8 235.9 235.9 241.8 226.0 267.0 176.3 224.9 224.9 228.9 219.4 252.4
90 271.4 271.4 271.8 271.8 295.2 229.9 261.0 261.0 261.4 261.4 281.8 223.6 250.1 250.1 250.5 250.5 267.9 217.2 238.7 238.7 239.1 239.1 253.4
75 241.4 215.2 267.8 162.4 297.1 107.4 230.0 208.9 255.3 156.2 283.4 101.2 218.2 202.3 242.2 149.7 269.0 94.8 205.9 195.6 228.4 143.0 254.0
9600 80 248.0 248.0 268.4 206.4 297.6 152.5 237.9 237.9 255.9 200.0 283.8 146.2 227.5 227.5 242.8 193.4 269.5 139.8 216.4 216.4 229.3 186.7 254.6
85 263.1 263.1 270.3 250.7 298.0 197.1 252.8 252.8 258.1 244.3 284.3 190.7 241.9 241.9 245.5 237.9 270.0 184.1 230.5 230.5 230.7 230.7 255.1
90 278.6 278.6 278.9 278.9 298.9 241.1 267.9 267.9 268.3 268.3 285.3 234.7 256.6 256.6 257.0 257.0 271.1 228.2 244.7 244.7 245.1 245.1 256.4
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

28 RT-PRC001-EN
Performance (25 Ton)
Data High Efficiency

Table PD-15 — Gross Cooling Capacities (MBH)25 Ton Three PhaseYC*301C3, C4, CW— Standard Refrigeration System
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 277 243 306 187 316 117 258 234 295 178 314 115 238 224 276 169 305 110 218 214 253 163 292 104
9000 80 284 284 307 225 321 169 269 269 295 225 317 161 252 252 277 217 307 158 235 235 254 207 293 151
85 300 300 309 269 325 198 289 289 298 271 320 202 273 273 280 266 308 201 256 256 259 256 293 198
90 312 312 313 312 329 236 305 305 305 305 321 240 293 293 293 293 310 245 277 277 277 277 295 244
75 284 258 310 188 319 121 264 249 299 185 316 117 244 239 282 178 308 112 224 224 259 168 295 106
10000 80 294 294 310 233 323 175 280 280 300 236 319 170 263 263 283 230 309 163 245 245 260 221 296 158
85 307 307 313 280 327 202 298 298 303 286 322 207 284 284 287 284 312 208 267 267 267 267 297 208
90 318 318 318 318 331 241 312 312 312 312 324 248 301 301 301 301 314 255 287 287 287 287 299 257
75 286 265 311 190 320 122 267 256 300 189 316 118 247 246 284 182 309 113 228 228 261 172 296 107
10500 80 297 297 312 237 324 178 285 285 302 241 320 174 267 267 285 237 310 165 249 249 262 227 298 162
85 310 310 315 285 328 204 302 302 305 293 323 210 289 289 289 289 313 212 272 272 272 272 299 213
90 320 320 320 320 332 244 314 314 314 314 325 251 305 305 305 305 316 260 292 292 292 292 301 264
75 289 272 312 192 321 123 270 264 302 192 317 119 249 249 286 186 309 114 231 231 263 176 297 108
11000 80 300 300 313 240 324 181 289 289 304 246 321 177 272 272 287 243 311 170 253 253 265 234 299 165
85 312 312 316 289 329 205 305 305 307 299 324 212 293 293 293 293 314 215 276 276 276 276 300 217
90 322 322 321 321 332 246 317 317 317 317 326 255 308 308 308 308 317 265 295 295 295 295 303 270
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Indicates both downflow and horizontal units.


*

RT-PRC001-EN 29
Performance (25 Ton)
Data High Efficiency

Table PD-16 — Gross Cooling Capacities (MBH)25 Ton Three PhaseYC*301C3, C4, CW— TXV Option
AmbientTemperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 267.9 224.2 297.7 171.5 330.7 118.0 254.9 216.9 283.7 164.4 315.3 111.1 241.5 209.3 269.2 157.1 299.2 104.0 227.5 201.6 254.0 149.6 282.7 96.8
8000 80 268.8 268.8 298.0 214.0 330.9 161.1 259.3 255.4 284.1 206.8 315.5 154.0 246.8 246.7 269.6 199.5 299.5 146.7 234.0 234.0 254.5 191.9 283.0 139.4
85 284.5 284.5 299.2 256.4 331.2 203.2 273.2 273.2 285.4 249.2 315.9 196.1 261.3 261.3 271.0 241.8 299.8 188.8 248.9 248.9 256.2 234.3 283.3 181.4
90 300.3 300.3 300.2 300.2 331.6 245.2 288.7 288.7 290.5 286.0 316.4 238.0 276.5 276.5 276.4 276.4 300.4 230.6 263.8 263.8 263.7 263.7 284.0 223.1
75 273.6 238.6 303.4 180.1 336.6 120.9 260.4 231.2 289.0 172.8 320.7 114.0 246.7 223.6 273.9 170.7 304.2 106.8 232.5 215.9 258.3 163.2 287.1 99.6
9000 80 279.6 279.5 303.8 227.0 336.8 168.4 267.3 267.3 289.5 219.8 321.0 161.3 255.2 255.2 274.6 212.4 304.5 154.0 242.6 242.6 259.1 204.8 287.5 146.5
85 295.1 295.1 305.6 274.3 337.2 215.2 283.4 283.4 291.5 267.1 321.4 208.1 271.0 271.0 276.9 259.7 304.9 200.7 258.0 258.0 261.9 252.2 287.8 193.1
90 311.9 311.9 311.8 311.8 338.0 261.8 299.6 299.6 299.6 299.6 322.2 254.5 286.9 286.9 286.8 286.8 305.9 247.1 273.5 273.5 273.5 273.5 288.9 239.4
75 278.6 252.6 308.1 188.2 341.5 123.5 265.2 245.2 293.3 180.9 325.3 116.5 251.3 237.6 278.0 173.5 308.4 109.2 234.1 234.1 262.1 165.9 290.8 101.7
10000 80 287.6 287.6 308.7 239.7 341.8 175.5 275.5 275.5 294.0 232.5 325.6 168.3 263.1 263.1 278.8 225.0 308.7 160.9 250.0 250.0 263.1 217.3 291.2 153.4
85 304.6 304.6 311.3 291.9 342.1 226.8 292.3 292.3 297.0 284.7 325.9 219.5 279.4 279.4 279.3 279.3 309.1 212.1 266.0 266.0 267.7 262.9 291.7 204.4
90 322.2 322.2 322.1 322.1 343.3 277.9 309.3 309.3 309.3 309.3 327.2 270.5 295.9 295.9 295.9 295.9 310.6 263.1 282.0 282.0 282.0 282.0 293.3 255.3
75 283.1 266.2 312.0 196.0 345.5 125.9 269.5 258.8 296.9 188.7 329.1 118.9 253.1 253.1 281.2 181.2 311.8 111.5 241.4 237.4 265.1 173.5 293.9 104.0
11000 80 295.1 295.1 312.9 252.1 345.8 182.3 282.8 282.8 297.9 244.7 329.4 175.0 269.9 269.9 282.4 237.2 312.2 167.7 256.4 256.4 266.5 229.4 294.3 160.1
85 312.9 312.9 312.8 312.8 346.2 237.9 300.0 300.0 299.9 299.9 329.9 230.6 286.7 286.7 288.1 285.2 312.8 223.1 272.8 272.8 272.7 272.7 295.0 215.4
90 331.2 331.2 331.1 331.1 347.8 293.5 317.8 317.8 317.8 317.8 331.6 286.2 304.0 304.0 303.8 303.8 314.7 278.6 289.3 289.3 289.3 289.3 297.3 271.0
75 283.8 283.8 315.3 203.6 348.9 128.2 271.5 271.5 299.9 196.2 332.2 121.1 259.9 256.8 284.1 188.6 314.7 113.8 245.2 245.2 267.7 180.9 296.5 106.2
12000 80 301.8 301.8 316.6 264.1 349.2 188.9 289.0 289.0 301.2 256.6 332.6 181.7 275.9 275.9 285.7 249.1 315.2 174.3 262.0 262.0 269.5 241.3 297.0 166.6
85 320.3 320.3 322.4 316.7 349.8 248.8 307.0 307.0 308.0 306.9 333.2 241.5 293.2 293.2 293.1 293.1 315.8 233.9 278.8 278.8 278.8 278.8 297.8 226.2
90 339.1 339.1 339.0 339.0 351.7 308.8 325.4 325.4 325.3 325.3 335.6 301.5 310.9 310.9 310.9 310.9 318.5 294.0 295.9 295.9 295.9 295.9 301.0 286.4
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Indicates both downflow and horizontal units.


*

30 RT-PRC001-EN
Performance (12½ Ton)
Data Standard Efficiency

Table PD-17 — Evaporator Fan Performance — 12½ Ton — YC*150D


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive (2)
4000 — — — — — — 581 0.97 614 1.08 646 1.20 677 1.31 707 1.41 738 1.52 768 1.63
4500 — — — — 588 1.15 622 1.27 652 1.38 682 1.50 711 1.63 738 1.76 766 1.88 793 2.00
5000 571 1.26 602 1.37 631 1.46 663 1.63 693 1.75 720 1.87 747 2.00 773 2.15 798 2.29 823 2.43
5500 621 1.65 650 1.79 678 1.87 704 2.01 734 2.19 760 2.33 786 2.45 810 2.59 834 2.74 858 2.91
6000 674 2.10 699 2.28 727 2.37 749 2.48 775 2.66 802 2.86 826 3.00 849 3.13 872 3.28 894 3.44

3 HP Standard Motor & Field Supplied Low Static Drive (1)

Table PD-17 — Evaporator Fan Performance — 12½ Ton— YC*150D — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive 3 HP Standard Motor & High Static Drive Accessory (2)
4000 799 1.75 829 1.87 856 1.99 884 2.11 911 2.24 937 2.35 962 2.47 987 2.59 1010 2.70 1034 2.82
4500 820 2.12 847 2.24 873 2.36 900 2.50 927 2.64 952 2.77 978 2.91 1003 3.05 1025 3.18 1049 3.32
5000 847 2.56 873 2.70 897 2.83 921 2.96 945 3.09 970 3.24 993 3.38 1017 3.53 1041 3.69 1064 3.85
5500 881 3.06 903 3.22 926 3.37 948 3.52 971 3.67 993 3.80 1015 3.95 1036 4.09 1058 4.25 1081 4.41
6000 916 3.61 938 3.78 959 3.96 980 4.13 1001 4.31 1021 4.46 1042 4.62 1062 4.78 1082 4.93 1103 5.09
5 HP Oversized Motor & Drive (3) 5 HP Oversized Motor & Drive (3)
5 HP Oversized Motor & FieldSupplied High Static Drive (3)

For Standard Evaporator Fan Speed (RPM), reference Table PD-31. Factory supplied motors, in commercial equipment, are
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33. definite purpose motors, specifically designed and tested to
Data includes pressure drop due to filters and wet coils. operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
No accessories or options are included in pressure drop data. our tabular data will not result in nuisance tripping or
Refer to Table PD-36 to determine add’l static pressure drop premature motor failure. Our product’s warranty will not be
due to other options/accessories affected.
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Notes:
1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be necessary.
2 3 HP Standard Motor with Field Supplied Motor Sheave 1VP44 Required. Field Supplied Belt may be necessary.
3. 5 HP Oversize Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt may be necessary.
4. For 380V/60 Hz units, the oversized motor is used as the standard motor, Refer to “Motor and Sheave/Fan Speed” tables to
determine operating range.

RT-PRC001-EN 31
Performance (15 Ton)
Data Standard Efficiency

Table PD-18 — Evaporator Fan Performance — 15 Ton — YC*180B


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive
4800 — — 584 1.22 613 1.33 647 1.49 676 1.59 704 1.71 732 1.84 759 1.98 485 2.13 811 2.26
5200 591 1.41 623 1.53 649 1.61 679 1.78 709 1.93 736 2.04 762 2.17 788 2.31 831 2.46 837 2.62
5600 633 1.76 661 1.89 688 1.96 713 2.09 742 2.29 769 2.43 793 2.55 817 2.69 542 2.84 865 3.00
6000 674 2.10 699 2.28 727 2.37 749 2.48 775 2.66 802 2.86 826 3.00 849 3.13 872 3.28 894 3.44
6400 716 2.52 739 2.73 766 2.85 788 2.94 809 3.08 835 3.30 860 3.50 882 3.65 903 3.79 925 3.94
6800 758 3.00 779 3.22 804 3.38 827 3.47 847 3.58 868 3.77 892 4.01 915 4.21 936 4.37 957 4.52
7200 800 3.54 820 3.76 842 3.96 866 4.07 885 4.17 904 4.32 925 4.54 948 4.81 970 5.01 990 5.17
5 HP Oversized Motor & Drive

Table PD-18 — Evaporator Fan Performance — 15 Ton— YC*180B — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive 3 HP Standard Motor & High Static Drive Accessory
4800 836 2.38 862 2.51 887 2.64 912 2.77 937 2.90 962 3.04 987 3.19 1011 3.34 1034 3.49 1057 3.65
5200 861 2.76 885 2.90 908 3.04 932 3.18 955 3.31 978 3.46 1002 3.60 1025 3.75 1047 3.90 1070 4.06
5600 888 3.17 910 3.33 932 3.49 954 3.64 976 3.79 998 3.93 1020 4.08 1042 4.23 1063 4.38 1085 4.54
6000 916 3.61 938 3.78 959 3.96 980 4.13 1001 4.31 1021 4.46 1042 4.62 1062 4.78 1082 4.93 1103 5.09
6400 946 4.10 967 4.28 987 4.47 1007 4.66 1027 4.85 1047 5.03 1066 5.21 1085 5.38 1104 5.55 — —
6800 977 4.67 997 4.84 1017 5.03 1036 5.22 1055 5.42 1074 5.62 — — — — — — — —
7200 1009 5.33 1028 5.49 1047 5.67 — — — — — — — — — — — — — —
5 HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31. 5 HP Oversized Motor & Field Supplied High Static Drive (2)
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Data includes pressure Drop Due to Wet Coils and Filters. Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
No accessories or options are included in pressure drop data. operate reliably and continuously at all cataloged conditions.
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories Using the full horsepower range of our fan motors as shown in
Notes: our tabular data will not result in nuisance tripping or
1. Field Supplied Fan Sheave BK105 Required. Field Supplied Belt may be necessary. premature motor failure. Our product’s warranty will not be
2. 5 HP Oversize Motor with Field Supplied Motor Sheave 1VP50 required. Field Supplied Belt may be necessary. affected.
3. For 380V/60 Hz units, the oversized motor is used as the standard motor, Refer to “Motor and Sheave/Fan
Speed” tables to determine operating range.

*Indicates both downflow and horizontal units.

32 RT-PRC001-EN
Performance (17½ Ton)
Data Standard Efficiency

Table PD-19 — Evaporator Fan Performance — 17½ Ton — YC*210C


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Low Static Drive Accessory
5600 — — 720 2.27 744 2.39 767 2.51 791 2.65 815 2.79 838 2.93 860 3.08 883 3.23 906 3.39
6300 776 3.02 798 3.16 820 3.29 841 3.42 862 3.56 883 3.72 905 3.88 926 4.04 946 4.20 965 4.36
7000 857 4.11 878 4.26 898 4.41 917 4.56 935 4.70 954 4.86 974 5.03 993 5.21 1013 5.39 1031 5.57
7700 939 5.44 958 5.60 976 5.77 994 5.93 1011 6.09 1028 6.25 1045 6.42 1062 6.60 1080 6.79 1098 6.99
8400 1021 7.03 1038 7.21 1055 7.39 1072 7.57 1088 7.74 1104 7.92 1119 8.09 1135 8.27 1151 8.46 — —
7.5 HP Oversized Motor & Drive

5 HP Standard Motor & Drive

Table PD-19 — Evaporator Fan Performance — 17½ Ton— YC*210C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Drive
5600 929 3.55 951 3.72 974 3.90 996 4.08 1018 4.27 1039 4.45 1060 4.62 1082 4.81 1105 5.01 1127 5.22
6300 984 4.53 1005 4.70 1026 4.88 1047 5.07 1067 5.27 1087 5.46 1106 5.66 1125 5.86 1145 6.07 1164 6.27
7000 1049 5.74 1066 5.92 1084 6.11 1102 6.30 1121 6.49 1139 6.69 1159 6.90 1176 7.11 1194 7.33 1212 7.55
7700 1116 7.20 1132 7.39 1149 7.59 1164 7.78 1180 7.98 1197 8.18 1213 8.39 1230 8.60 — — — —
8400 — — — — — — — — — — — — — — — — — — — —

7.5 HP Oversized Motor & Drive


Factory supplied motors, in commercial equipment, are
For Standard Evaporator Fan Speed (RPM), reference Table PD-31. definite purpose motors, specifically designed and tested to
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33. operate reliably and continuously at all cataloged conditions.
For Standard Motor and Low Static Drive, reference Table PD-34. Using the full horsepower range of our fan motors as shown in
Fan motor heat (MBH) = 3.15 x Fan Bhp. our tabular data will not result in nuisance tripping or
Data includes pressure Drop Due to West Coils and Filters. premature motor failure. Our product’s warranty will not be
No accessories or options are included in pressure drop data. affected.
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories
Notes:
1. For 380V/60 Hz units, the oversized motor is used as the standard motor, Refer to “Motor and
Sheave/Fan Speed” tables to determine operating range.

*Indicates both downflow and horizontal units.

RT-PRC001-EN 33
Performance (20 Ton)
Data Standard Efficiency

Table PD-20 — Evaporator Fan Performance — 20 Ton — YC*240B


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Field Supplied Low Static Drive (1) 5 HP Standard Motor & Drive
6400 511 1.56 538 1.72 564 1.99 590 2.16 615 2.31 639 2.47 663 2.65 688 2.84 711 3.04 735 3.23
7200 555 2.25 587 2.46 614 2.67 640 2.88 663 3.06 685 3.23 706 3.41 728 3.60 749 3.80 771 4.01
8000 609 3.03 639 3.26 665 3.50 690 3.73 712 3.96 733 4.16 753 4.35 772 4.55 792 4.75 811 4.96
8800 664 3.98 692 4.23 717 4.49 740 4.75 762 5.01 782 5.25 801 5.48 820 5.69 838 5.90 855 6.12
9600 719 5.11 745 5.38 770 5.66 792 5.94 813 6.23 832 6.51 851 6.78 869 7.03 886 7.27 902 7.50
(2) 7.5 HP Oversized Motor & Drive

Table PD-20 — Evaporator Fan Performance — 20 Ton— YC*240B — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory
6400 758 3.4 781 3.64 804 3.85 827 4.07 848 4.29 869 4.51 890 4.73 910 4.97 929 5.21 949 5.45
7200 792 4.24 813 4.46 834 4.68 854 4.90 875 5.13 895 5.37 916 5.62 936 5.86 955 6.11 973 6.35
8000 830 5.18 850 5.42 869 5.66 888 5.91 907 6.16 925 6.40 944 6.65 962 6.90 981 7.16 1000 7.44
8800 873 6.34 890 6.58 908 6.82 925 7.08 943 7.34 961 7.61 978 7.88 995 8.16 — — — —
9600 919 7.73 935 7.97 951 8.21 967 8.46 — — — — — — — — — — — —
7.5 HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31. Factory supplied motors, in commercial equipment, are
For Standard Motor and High Static Drive Accessory/Fan Speed (RPM),reference Table PD-32. definite purpose motors, specifically designed and tested to
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33. operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
Fan motor heat (MBH) = 3.15 x Fan Bhp. in our tabular data will not result in nuisance tripping or
Data includes pressure Drop Due to West Coils and Filters. premature motor failure. Our product’s warranty will not be
No accessories or options are included in pressure drop data. affected.
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories
Notes:
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
2. 7.5 HP Oversize Motor with Field Supplied Motor Sheave 1VP50 Required. Field
Supplied Belt may be necessary.
3. For 380V/60 Hz units, the oversized motor is used as the standard motor, Refer to
“Motor and Sheave/Fan Speed” tables to determine operating range.

*Indicates both downflow and horizontal units.

34 RT-PRC001-EN
Performance (25 Ton)
Data Standard Efficiency

Table PD-21— Evaporator Fan Performance — 25 Ton — YC*300B


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Low Static Drive Accessory 7.5 HP Standard Motor & Drive
7000 — — — — 614 2.59 639 2.77 662 2.94 684 3.11 706 3.30 728 3.49 750 3.70 773 3.92
7500 — — 621 2.85 647 3.08 671 3.29 693 3.48 715 3.66 736 3.85 756 4.05 777 4.26 797 4.47
8000 627 3.16 655 3.39 680 3.64 704 3.87 725 4.09 746 4.28 766 4.48 785 4.68 805 4.89 824 5.11
8500 662 3.76 689 4.00 714 4.26 737 4.52 758 4.76 778 4.98 797 5.18 815 5.39 834 5.61 852 5.83
9000 698 4.43 724 4.69 747 4.96 770 5.24 790 5.50 810 5.74 828 5.97 846 6.18 864 6.41 881 6.63
9500 734 5.18 758 5.45 781 5.73 803 6.02 823 6.31 842 6.58 860 6.83 878 7.06 895 7.29 911 7.53
10000 770 6.00 793 6.29 816 6.59 837 6.89 856 7.20 875 7.49 893 7.77 910 8.02 926 8.27 942 8.51
10500 806 6.92 829 7.22 850 7.53 870 7.85 890 8.17 908 8.48 — — — — — — — —
11000 842 7.92 864 8.24 885 8.56 — — — — — — — — — — — — — —
7.5 HP Standard Motor & Drive

7.5 HP Standard Motor & High StaticDrive Accessory

Table PD-21 — Evaporator Fan Performance — 25 Ton — YC*300B — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Drive
7000 795 4.14 816 4.36 837 4.58 858 4.80 879 5.03
7500 818 4.70 839 4.94 859 5.18 879 5.41 899 5.65
8000 843 5.34 862 5.58 882 5.83 901 6.09 920 6.34
8500 870 6.06 888 6.30 906 6.55 924 6.81 943 7.08
9000 898 6.87 916 8.11 933 7.36 950 7.62 967 7.89
9500 928 7.77 944 8.01 960 8.27 977 8.53 — —
10000 — — — — — — — — — —
10500 — — — — — — — — — —
11000 — — — — — — — — — —

7.5 HP Standard Motor & High Static Drive Accessory

For Standard Evaporator Fan Speed (RPM), reference Table PD-31. Factory supplied motors, in commercial equipment,
For Standard Motor and High Static Drive, reference Table PD-32. are definite purpose motors, specifically designed
For Standard Motor and Low Static Drive, reference Table PD-34. and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower
Data includes pressure drop due to filters and wet coils. range of our fan motors as shown in our tabular data
No accessories or options are included in pressure drop data. will not result in nuisance tripping or premature
Refer to Table PD-36 to determine add’l static pressure drop motor failure. Our product’s warranty will not be
due to other options/accessories affected.
Fan motor heat (MBH) = 3.15 x Fan Bhp
Notes:
1. For 380V/60 Hz units, the oversized motor is used as the
standard motor, Refer to “Motor and Sheave/Fan Speed” tables
to determine operating range.

*Indicates both downflow and horizontal units.

RT-PRC001-EN 35
Performance (12½ Ton)
Data High Efficiency

Table PD-22— Evaporator Fan Performance — 12½ Ton — YCD151C— Standard or TXV Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field 3 HP Standard Motor & Drive
Supplied Low Static Drive (1)
4000 — — 497 0.75 551 0.92 598 1.08 641 1.23 680 1.38 716 1.53 750
1.67 782 1.82 812 1.96
4500 — — 531 0.96 583 1.16 629 1.34 671 1.52 709 1.70 745 1.87 778
2.03 810 2.20 840 2.36
5000 506 0.98 565 1.21 616 1.43 661 1.65 701 1.85 739 2.05 774 2.25 807
2.44 838 2.63 868 2.81
5500 544 1.24 600 1.51 649 1.76 693 2.00 733 2.23 770 2.45 804 2.67 837
2.89 868 3.10 897 3.31
6000 582 1.55 636 1.84 684 2.12 726 2.39 765 2.65 801 2.90 835 3.15 867
3.39 898 3.63 927 3.86
3 HP Standard Motor & High Static Drive Accessory 5 HP Oversized Motor & Drive

Table PD-22 — Evaporator Fan Performance — 12½ Ton— YCD151C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard 3 HP Standard Motor & High Static Drive Accessory
Motor & Drive
4000 841 2.09 869 2.23 896 2.36 922 2.50 947 2.63 971 2.76 994 2.89 1016 3.04 1037 3.19 1059 3.35
4500 869 2.52 896 2.68 923 2.84 948 2.99 973 3.14 997 3.30 1020 3.45 1043 3.60 1065 3.75 1087 3.89
5000 897 2.99 924 3.17 950 3.35 976 3.53 1000 3.71 1024 3.88 1047 4.05 1070 4.22 1092 4.39 1113 4.56
5500 925 3.52 952 3.72 978 3.92 1004 4.12 1028 4.32 1052 4.51 1075 4.71 1097 4.90 1119 5.09 1140 5.28
6000 955 4.09 981 4.32 1007 4.54 1032 4.77 1056 4.99 1080 5.21 1103 5.42 1125 5.64 — — — —
5 HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31. Factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table PD-32. definite purpose motors, specifically designed and tested to
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33. operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
Data includes pressure drop due to filters and wet coils. our tabular data will not result in nuisance tripping or
No accessories or options are included in pressure drop data. premature motor failure. Our product’s warranty will not be
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories affected.
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Notes:
1. Field Supplied Fan Sheave BK115 required. Field Supplied Belt may be necessary.

Table PD-23 — Evaporator Fan Performance — 12½ Ton — Y*D151C — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive 3 HP Standard Motor &
High Static Drive Acccessory
4000 640 1.12 677 1.25 711 1.39 745 1.53 776 1.68 806 1.82 835 1.97 864 2.12 891 2.27 916 2.41
4500 711 1.56 745 1.70 776 1.85 806 2.01 836 2.17 864 2.33 891 2.49 917 2.66 944 2.83 969 2.9
5000 783 2.10 813 2.26 843 2.42 870 2.59 897 2.77 924 2.94 950 3.12 975 3.31 998 3.49 1022 3.68
5500 855 2.76 883 2.93 910 3.11 936 3.29 961 3.49 986 3.67 1011 3.87 1035 4.07 1057 4.26 1079 4.46
6000 928 3.54 954 3.74 979 3.93 1003 4.12 1027 4.33 1050 4.54 1072 4.74 1095 4.95 1117 5.16 1138 5.38
5 HP Oversized Motor & Drive

Table PD-23 — Evaporator Fan Performance — 12½ Ton— Y*D151C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
MBHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor Drive & High Static Drive Accessory 5 HP Oversized Motor & Drive
4000 940 2.56 964 2.71 987 2.86 1011 3.01 1034 3.16 1056 3.32 1077 3.47 1098 3.62 1120 3.79 1140 3.95
4500 994 3.16 1016 3.32 1038 3.49 1059 3.66 1080 3.83 1102 4.00 1122 4.17 1143 4.34 1163 4.51 1183 4.68
5000 1046 3.86 1069 4.05 1091 4.23 1112 4.41 1133 4.60 1152 4.78 1172 4.97 1190 5.15 1209 5.34 1228 5.53
5500 1101 4.67 1122 4.87 1143 5.07 1165 5.27 1186 5.48 1206 5.69 — — — — — — — —
6000 1159 5.60 — — — — — — — — — — — — — — — — — —

5 HP Oversized Motor & Drive w/Field Supplied High Static Drive (1)
Factory supplied motors, in commercial equipment, are
For Standard Evaporator Fan Speed (RPM), reference Table PD-31. definite purpose motors, specifically designed and tested to
For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table PD-32. operate reliably and continuously at all cataloged conditions.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33. Using the full horsepower range of our fan motors as shown in
Data includes pressure drop due to filters and wet coils. our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
No accessories or options are included in pressure drop data. affected.
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Notes:
1. Field Supplied Fan Sheave BK120. Field Supplied Belt may be necessary.

36 RT-PRC001-EN
Performance (12½ Ton)
Data High Efficiency

Table PD-24 — Evaporator Fan Performance — 12½ Ton — YCH151C— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive

4000 — — — — 520 1.01 550 1.13 580 1.25 610 1.38 638 1.51 666 1.65 693 1.80 720 1.95
4500 502 1.10 533 1.21 562 1.34 590 1.47 617 1.60 644 1.73 671 1.88 696 2.03 721 2.18 746 2.33
5000 551 1.47 579 1.61 606 1.74 632 1.87 657 2.02 682 2.17 706 2.31 730 2.46 754 2.63 777 2.80
5500 600 2.92 627 2.08 651 2.22 675 237 699 2.52 722 2.68 744 2.85 766 3.00 788 3.16 810 3.34
6000 649 2.46 675 2.64 698 2.79 720 2.94 742 3.11 764 3.28 785 3.46 805 3.64 825 3.81 845 3.98
3 HP Standard Motor & Drive 5 HP Oversized Motor & Drive

Table PD-24 — Evaporator Fan Performance — 12½ Ton— YCH151C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive 3 HP Standard Motor & High Static Drive
4000 746 2.10 771 2.26 795 2.41 819 2.57 842 2.72 864 2.89 886 3.05 908 3.22 929 3.40 951 3.58
4500 770 2.49 794 2.66 818 2.83 841 3.01 863 3.18 885 3.35 906 3.53 927 3.70 947 3.88 967 4.06
5000 799 2.96 821 3.13 843 3.31 965 3.49 887 3.68 908 3.87 929 4.07 949 4.26 969 4.45 988 4.64
5500 831 3.52 852 3.70 873 3.89 893 4.07 913 4.26 933 4.46 953 4.66 972 4.87 992 5.08 1011 5.29
6000 865 4.15 885 4.35 905 4.55 924 4.75 943 4.95 962 5.15 980 5.35 999 5.56 — — — —
5 HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31. Factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table PD-32. definite purpose motors, specifically designed and tested to
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33. operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
Data includes pressure drop due to filters and wet coils. our tabular data will not result in nuisance tripping or
No accessories or options are included in pressure drop data. premature motor failure. Our product’s warranty will not be
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories affected.
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Notes:
1. Field Supplied Fan Sheave BK115 required. Field Supplied Belt may be necessary.

RT-PRC001-EN 37
Performance (15 Ton)
Data High Efficiency

Table PD-25— Evaporator Fan Performance — 15 Ton — YC*181C— Standard or TXV Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive
4800 414 0.81 450 0.94 483 1.06 515 1.20 548 1.35 578 1.50 609 1.66 640 1.83 668 2.00 694 2.18
5400 456 1.11 490 1.26 520 1.39 549 1.54 578 1.70 607 1.87 635 2.03 662 2.21 689 2.39 716 2.58
6000 499 1.48 531 1.65 559 1.81 585 1.96 611 2.12 638 2.29 664 2.48 689 2.67 714 2.85 738 3.05
6600 542 1.92 572 2.12 599 2.3 624 2.46 648 2.63 671 2.81 695 3.00 719 3.20 743 3.41 765 3.62
7200 586 2.45 614 2.67 640 2.88 663 3.06 686 3.24 708 3.42 729 3.61 751 3.82 773 4.04 795 4.26
5 HP Oversized Motor & Drive

Table PD-25 — Evaporator Fan Performance — 15 Ton— YC*181C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive 3 HP Standard Motor & High Static Drive Accessory
\4800 719 2.36 744 2.55 769 2.75 792 2.95 815 3.14 838 3.34 859 3.54 880 3.73 901 3.93 921 4.13
5400 742 2.77 766 2.97 789 3.17 811 3.38 833 3.59 855 3.81 876 4.03 897 4.26 917 4.48 937 4.70
6000 763 3.25 788 3.46 811 3.68 833 3.89 855 4.11 875 4.33 896 4.56 916 4.80 935 5.04 955 5.28
6600 788 3.82 810 4.03 832 4.26 855 4.49 877 4.72 898 4.96 918 5.20 937 5.43 956 5.67 — —
7200 816 4.49 837 4.71 857 4.94 989 5.17 898 5.41 919 5.66 — — — — — — — —
5 HP Oversized Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-31. Factory supplied motors, in commercial equipment, are definite
For Standard Motor and High Static Drive (RPM), reference Table PD-32. purpose motors, specifically designed and tested to operate reliably
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33. and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
Data includes pressure drop due to filters and wet coils. will not result in nuisance tripping or premature motor failure. Our
No accessories or options are included in pressure drop data. product’s warranty will not be affected.
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Notes:
1. Field Supplied Fan Sheave BK120 required. Field Supplied Belt May be necessary.

Table PD-26— Evaporator Fan Performance — 15 Ton — Y*D181C — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive
4800 427 0.88 463 1.03 496 1.16 527 1.31 557 1.46 586 1.61 614 1.77 641 1.93 667 2.10 693 2.29
5400 471 1.21 505 1.38 535 1.53 564 1.69 591 1.85 618 2.02 644 2.19 669 2.36 695 2.54 718 2.72
6000 516 1.61 547 1.81 576 1.98 603 2.15 628 2.33 653 2.51 677 2.70 700 2.88 724 3.07 747 3.26
6600 561 2.09 590 2.32 617 2.52 643 2.71 667 2.90 690 3.09 712 3.29 734 3.49 756 3.70 777 3.90
7200 607 2.67 634 2.92 659 3.16 683 3.36 707 3.56 728 3.77 749 3.98 770 4.20 791 4.42 811 4.64
5 HP Oversized Motor & Drive

Table PD-26 — Evaporator Fan Performance — 15 Ton— Y*D181C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive 3HP Motor and High Static Drive Accessory 5 HP Oversized Motor & Drive
4800 719 2.49 742 2.69 765 2.89 787 3.09 808 3.28 829 3.48 849 3.68 869 3.89 887 4.09 906 4.29
5400 742 2.91 765 3.12 788 3.34 810 3.56 831 3.79 852 4.01 872 4.24 891 4.46 909 4.67 928 4.91
6000 769 3.46 791 3.66 812 3.87 833 4.09 855 4.33 874 4.57 894 4.81 913 5.06 932 5.31 950 5.56
6600 799 4.11 819 4.32 840 4.53 860 4.75 879 4.98 899 5.22 918 5.46 937 5.72 — — — —
7200 830 4.86 850 5.09 870 5.31 888 5.54 — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-31. Factory supplied motors, in commercial equipment, are definite
For Standard Motor and High Static Drive (RPM), reference Table PD-32. purpose motors, specifically designed and tested to operate reliably
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33. and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
Data includes pressure drop due to filters and wet coils. will not result in nuisance tripping or premature motor failure. Our
No accessories or options are included in pressure drop data. product’s warranty will not be affected.
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Notes:
1. Field Supplied Fan Sheave BK120 required. Field Supplied Belt may be necessary.

*Indicates both downflow and horizontal units.

38 RT-PRC001-EN
Performance (17½ Ton)
Data High Efficiency

Table PD-27— Evaporator Fan Performance — 17½ Ton — YC*211C— Standard or TXV Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Field 5 HP Standard Motor & Drive
Supplied Low Static Drive (1)
5600 — — — — 533 1.52 561 1.67 589 1.83 617 2.00 644 2.18 670 2.35 697 2.53 723 2.73
6300 521 1.69 551 1.88 579 2.04 604 2.20 629 2.36 654 2.54 679 2.73 704 2.93 728 3.12 751 3.32
7000 571 2.27 600 2.48 626 2.68 650 2.85 673 3.03 695 3.20 718 3.40 740 3.60 763 3.82 785 4.04
7700 622 2.96 650 3.20 674 3.43 697 3.64 719 3.83 739 4.02 760 4.21 780 4.42 800 4.64 821 4.87
8400 674 3.80 700 4.05 723 4.31 745 4.55 765 4.77 785 4.98 804 5.18 823 5.39 841 5.62 860 5.85
5 HP Standard Motor & High
Static Drive Accessory

7.5 HP Oversized Motor & Drive

Table PD-27 — Evaporator Fan Performance — 17½ Ton— YC*211C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory
5600 749 2.93 773 3.13 796 3.33 818 3.54 840 3.75 861 3.98 882 4.20 903 4.43 923 4.66 943 4.89
6300 775 3.52 798 3.74 822 3.96 844 4.18 866 4.41 887 4.64 907 4.87 926 5.10 945 5.35 964 5.60
7000 806 4.26 828 4.48 849 4.70 870 4.93 891 5.17 912 5.41 932 5.66 952 5.92 971 6.17 990 6.42
7700 841 5.11 861 5.35 881 5.59 900 5.83 920 6.07 939 6.32 958 6.57 977 6.84 996 7.11 — —
8400 878 6.09 897 6.34 916 6.61 934 6.87 953 7.14 971 7.40 988 7.66 — — — — — —
7.5 HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31. Factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table PD-32. definite purpose motors, specifically designed and tested to
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33. operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
Data includes pressure drop due to filters and wet coils. our tabular data will not result in nuisance tripping or
No accessories or options are included in pressure drop data. premature motor failure. Our product’s warranty will not be
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories affected.
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Notes:
1. Field Supplied Fan Sheave BK190 required. Field supplied belt may be necessary.

*Indicates both downflow and horizontal units.

RT-PRC001-EN 39
Performance (20 Ton)
Data High Efficiency

Table PD-28— Evaporator Fan Performance — 20 Ton — YC*241C— Standard or TXV Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Field 5 HP Standard Motor & Drive
Supplied Low Static Drive (1)
6400 527 1.76 558 1.96 586 2.13 611 2.28 635 2.45 660 2.62 684 2.82 709 3.02 733 3.22 756 3.41
7200 585 2.44 614 2.67 640 2.88 664 3.06 686 3.24 708 3.42 729 3.61 751 3.82 773 4.04 795 4.26
8000 643 3.29 670 3.54 965 3.79 718 4.01 739 4.21 759 4.41 778 4.61 798 4.82 817 5.04 837 5.27
8800 702 4.33 727 4.59 750 4.87 772 5.13 792 5.37 811 5.60 830 5.81 848 6.03 866 6.25 883 6.48
9600 761 5.56 784 5.85 807 6.15 827 6.45 847 6.73 865 6.99 883 7.23 900 7.46 916 7.70 933 7.94
(2) 7.5 HP Oversized Motor & Drive

Table PD-28— Evaporator Fan Performance — 20 Ton— YC*241C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory
6400 779 3.62 802 3.83 852 4.05 846 4.27 868 4.49 889 4.72 909 4.96 929 5.20 949 5.45 968 5.71
7200 816 4.49 837 4.71 857 4.94 878 5.17 898 5.41 919 5.65 938 5.90 958 6.14 978 6.38 999 6.63
8000 857 5.57 876 5.76 896 6.01 915 6.26 933 6.51 952 6.76 970 7.01 989 7.26 — — — —
8800 901 6.73 919 6.98 937 7.25 955 7.52 973 7.80 991 8.07 — — — — — — — —
9600 949 8.19 965 8.44 — — — — — — — — — — — — — — — —
7.5 HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31. Factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table PD-32. definite purpose motors, specifically designed and tested to
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33. operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
Data includes pressure drop due to filters and wet coils. our tabular data will not result in nuisance tripping or
No accessories or options are included in pressure drop data. premature motor failure. Our product’s warranty will not be
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories affected.
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Notes:
1. Field Supplied Fan Sheave BK190 required. Field supplied belt may be necessary.
2. 7.5 HP Oversize Motor with Field Supplied Motor Sheave 1VP50 required. Field Supplied Belt may be necessary.
Table PD-29— Evaporator Fan Performance — 20 Ton — Y*D241C — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Field 5 HP Standard Motor & Drive
Supplied Low Static Drive (1)
6400 546 1.92 576 2.14 603 2.33 629 2.51 654 2.70 677 2.89 700 3.08 722 3.28 745 3.48 767 3.67
7200 607 2.67 634 2.92 659 3.16 683 3.36 707 3.56 728 3.77 749 3.98 770 4.20 791 4.42 811 4.64
8000 668 3.60 693 3.87 717 4.15 739 4.40 761 4.63 781 4.84 801 5.07 821 5.31 840 5.55 858 5.80
8800 730 4.74 753 5.03 775 5.33 796 5.62 816 5.90 836 6.14 855 6.39 873 6.63 891 6.89 909 7.16
9600 792 6.10 814 6.41 834 6.73 854 7.06 873 7.38 891 7.68 909 7.95 927 8.20 944 8.47 — —
7.5 HP Oversized Motor & Drive
7.5 HP Oversized Motor & Field Supplied Low Static Drive (2) 5 HP Standard Motor & High Static Drive Accessory
Table PD-29— Evaporator Fan Performance — 20 Ton— Y*D241C — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory
6400 789 3.88 809 4.08 830 4.30 851 4.53 871 4.75 890 4.98 910 5.24 929 5.50 948 5.75 965 6.00
7200 830 4.86 850 5.09 870 5.31 888 5.54 908 5.78 926 6.02 944 6.25 962 6.51 980 6.76 998 7.04
8000 877 6.04 895 6.28 913 6.53 930 6.77 947 7.02 965 7.28 983 7.53 999 7.78 1016 8.05 1033 8.32
8800 925 7.42 942 7.68 959 7.96 975 8.22 992 8.50 — — — — — — — — — —
9600 — — — — — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-31. 7.5 HP Oversized Motor & Drive 7.5 HP Oversized Motor &
For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table PD-32.
Field Supplied High Static Drive(3)
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33.
Data includes pressure drop due to filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories
Factory supplied motors, in commercial equipment, are
Fan motor heat (MBH) = 3.15 x Fan Bhp. definite purpose motors, specifically designed and tested to
Notes: operate reliably and continuously at all cataloged conditions.
1. Field Supplied Fan Sheave BK190 required. Field supplied belt may be necessary. Using the full horsepower range of our fan motors as shown in
2. 7.5 HP Oversize Motor with Field Supplied Motor Sheave 1VP50 required. Field Supplied Belt may be necessary. our tabular data will not result in nuisance tripping or
3. Field Supplied Fan Sheave BK160 required. Field supplied belt may be necessary. premature motor failure. Our product’s warranty will not be
affected.
*Indicates both downflow and horizontal units.

40 RT-PRC001-EN
Performance (25 Ton)
Data High Efficiency

Table PD-30 — Evaporator Fan Performance — 25 Ton — YC*301C— Standard Refrigeration or TXV System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Drive
8000 643 3.29 670 3.54 695 3.79 718 4.01 739 4.21 759 4.41 778 4.61 798 4.82 817 5.04 837 5.27
8500 680 3.92 705 4.18 729 4.44 752 4.69 772 4.92 792 5.13 810 5.33 829 5.55 847 5.77 865 6.00
9000 717 4.61 741 4.89 764 5.17 786 5.44 806 5.69 825 5.92 843 6.14 861 6.36 878 6.59 895 6.83
9500 754 5.39 777 5.68 799 5.98 820 6.27 840 6.55 859 6.80 876 7.04 893 7.27 910 7.50 926 7.74
10000 791 6.26 813 6.56 835 9.87 855 7.18 874 7.48 893 7.76 910 8.02 926 8.27 942 8.51 — —
10500 828 7.21 850 7.52 870 7.85 890 8.18 909 8.50 — — — — — — — — — —
11000 866 8.26 886 8.59 — — — — — — — — — — — — — — — —

7.5 HP Standard Motor & Low Static Drive Accessory 7.5 HP Standard Motor & HighStatic Drive Accessory

Table PD-30— Evaporator Fan Performance — 25 Ton — YC*301C— Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Drive
8000 857 5.51 876 5.76 896 6.01 815 6.26 933 6.51
8500 884 6.24 903 6.50 921 6.76 940 7.03 958 7.30
9000 913 7.07 930 7.32 948 7.59 965 7.86 983 8.15
9500 943 7.99 959 8.25 976 8.51 — — — —
10000 — — — — — — — — — —
10500 — — — — — — — — — —
11000 — — — — — — — — — —

7.5 HP Standard Motor & HighStatic Drive Accessory

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.


For Standard Motor & High Static Drive, reference Table PD-32.
For Standard Motor & Low Static Drive, reference Table PD-34.
Notes:
Data includes pressure drop due to filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically
designed and tested to operate reliably and continuously at all cataloged conditions. Using the
full horsepower range of our fan motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

*Indicates both downflow and horizontal units.

RT-PRC001-EN 41
Performance
Data (12½ - 25 Tons)

Table PD-31— Standard Motor & Drive/Fan Speed (Rpm)


Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn
Tons Model No. Open Open Open Open Open Open Closed
12½ YC*150D3,4,W, YC*151C3,4,W 640 680 720 760 800 840 N/A
YC*150DK 705 756 806 857 907 957 N/A
YC*180B3,4,W 679 721 764 806 849 891 N/A
15 YC*180BK N/A 680 733 785 837 889 941
YC*181C3,4,W 560 600 640 680 720 760 N/A
YC*210C3,4,W 869 923 978 1032 1087 1141 N/A
17½ YC*210CK 869 324 978 1032 1087 1141 N/A
YC*211C3,4,W 615 659 703 747 791 835 N/A
20 YC*240B3,4,W, YC*241C3,4,W 615 659 703 747 791 835 N/A
YC*240BK 590 627 664 701 738 775 N/A
25 YC*300B3,4,W, YC*301C3,4,W 705 742 779 817 854 891 N/A
YC*300BK 701 738 775 812 849 886 N/A
Factory set at 3 turns open.

Table PD-32— Standard Motor & High Static Drive Accessory/Fan Speed (Rpm)
Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn
Tons Model No. Open Open Open Open Open Open Closed
12½ YC*151C3,4,W 807 857 908 958 1009 1059 N/A
15 YC*180B3,4,W 806 849 891 934 976 1019 N/A
YC*181B3,4,W 640 680 720 760 800 840 N/A
17½ YC*211C3,4,W 835 879 923 967 1011 1055 N/A
20 YC*240B/241C3,4,W 835 879 923 967 1011 1055 N/A
25 YC*300B/301C3,4,W 816 853 890 928 965 1002 N/A

Table PD-33— Oversized Motor & Drive/Fan Speed (Rpm)


Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn
Tons Model No. Open Open Open Open Open Open Closed
12½ YC*150D,151C3,4,W 869 923 978 1032 1087 1141 N/A
15 YC*180B3,4,W 806 856 907 957 1008 1058 N/A
YC*181C3,4,W 705 755 806 856 907 957 N/A
17½ YC*210C3,4,W 949 1008 1068 1127 1187 1246 N/A
YC*211C3,4,W 816 853 890 928 965 1002 N/A
20 YC*240B3,4,W, YC*241C3,4,W 816 853 890 928 965 1002 N/A

Table PD-34 — Low Static Fan Drive


Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn
Tons Model No. Open Open Open Open Open Open Closed
17½ YC*210C3,4,W 705 755 806 856 907 957 N/A
25 YC*300B3,4,W,301C3,4,W 594 631 668 705 742 779 N/A

*Indicates both downflow and horizontal units.

42 RT-PRC001-EN
Performance
Data (12½ - 25 Tons)

Table PD-35 — Gas-Fired Heating Capacities


Unit Heating Heating AirTemp.
Tons Model No. Input MBH Output MBH Rise, F
YC*150D-L1 ,YC*151C-L1 150/100 122/81 10-40
12½
YC*150D-H1,YC*151C-H1 250/175 203/142 25-55
YC*180B-L1 250/175 203/142 25-55
15 YC*180B-H1,YC*181C-H1 350/250 284/203 35-65
YC*181C-L1 250/175 203/142 15-45
YC*210C-L1 , YC*211C-L1 250/175 203/142 15-45
17½ YC*210C-H1,YC*211C-H1 350/250 284/203 35-65
YC*240B-L1 ,YC*241C-L1 250/175 203/142 15-45
20 YC*240B-H1,YC*241C-H1 400/300 324/243 25-55
YC*300B-L1,YC*301C-L1 250/175 203/142 15-45
25
YC*300B-H1,YC*301C-H1 400/300 324/243 25-55
Note:
1. Second stage is total heating capacity. Second Stage / First Stage.

*Indicates both downflow and horizontal units.

RT-PRC001-EN 43
Performance
Data (12½ - 25 Tons)

Table PD-36 — Static Pressure Drops Through Accessories (Inches Water Column)
Unit Standard Through 2 Inch Economizer with OA/RA Dampers2
Tons Model No. CFM Filters1 Reheat Coil Pleated Filters3 100% OA 100% RA
4000 0.05 — 0.08 0.19 0.02
YC*150D,YCH151C 5000 0.07 — 0.11 0.26 0.03
6000 0.10 — 0.15 0.33 0.04
12½ 2500 0.02 0.01 0.03 0.07 0.01
YCD151C 4000 0.05 0.03 0.08 0.19 0.02
5000 0.07 0.05 0.11 0.26 0.03
6000 0.10 0.06 0.15 0.33 0.04
4800 0.07 — 0.10 0.25 0.03
YC*180B 6000 0.10 — 0.15 0.33 0.04
7200 0.15 — 0.19 0.40 0.05
3000 0.02/0.01 0.01 0.03/0.02 0.07 0.03
4800 0.04/0.03 0.02 0.07/0.06 0.14 0.03
15 YCD181C 6000 0.06/0.05 0.03 0.10/0.09 0.20 0.04
7200 0.09/0.07 0.04 0.13/0.11 0.27 0.05
4800 0.04/0.03 — 0.07/0.06 0.14 0.03
YCH181C 6000 0.06/0.05 — 0.10/0.09 0.20 0.04
7200 0.09/0.07 — 0.13/0.11 0.27 0.05
5600 0.09 — 0.13 0.30 0.04
YC*210C 7000 0.14 — 0.18 0.39 0.05
8400 0.20 — 0.24 0.47 0.06
3500 0.02/0.02 — 0.03/0.03 0.09 0.03
5600 0.06/0.05 — 0.09/0.08 0.18 0.04
17½ YCD211C 7000 0.09/0.07 — 0.13/0.11 0.26 0.04
8400 0.12/0.10 — 0.17/0.14 0.35 0.06
5600 0.06/0.05 — 0.09/0.08 0.18 0.04
YCH211C 7000 0.09/0.07 — 0.13/0.11 0.26 0.04
8400 0.12/0.10 — 0.17/0.14 0.35 0.06
6400 0.07 — 0.11 0.22 0.04
YCD240 8000 0.11 — 0.15 0.32 0.05
9600 0.16 — 0.20 0.44 0.07
4000 0.03 0.02 0.04 0.11 0.03
20 YCD241C 6400 0.07 0.04 0.11 0.22 0.04
8000 0.11 0.05 0.15 0.32 0.05
9600 0.16 0.07 0.20 0.44 0.07
6400 0.06 — 0.10 0.22 0.04
YCH240, 241C 8000 0.09 — 0.13 0.32 0.05
9600 0.13 — 0.17 0.44 0.07
7000 0.09 — 0.13 0.26 0.04
YCD300B 9000 0.14 — 0.18 0.40 0.07
11000 0.21 — 0.25 0.57 0.10
5000 0.04 — 0.06 0.15 0.03
25 YCD301C 7000 0.09 — 0.13 0.26 0.04
9000 0.14 — 0.18 0.40 0.07
11000 0.21 — 0.25 0.57 0.10
7000 0.07 — 0.11 0.26 0.04
YCH300B,301C 9000 0.11 — 0.15 0.40 0.07
11000 0.17 — 0.22 0.57 0.10
Notes:
1. 2” filters standard on the 12½-25 tons.
2. OA = Outside Air and RA = Return Air.
3. Difference in pressure drop should be considered when utilizing optional 2“ pleated filters.

44 RT-PRC001-EN
Performance
Data

Table PD-37— Hot Gas Reheat Temperature Rise2,3


Leaving Evaporator Dry Bulb [F]1
Tons SCFM 35 40 45 50 55 60 65
2500 23.4 23.8 25.0 26.9 29.5 32.9 37.0
3000 21.4 21.6 22.5 24.0 26.0 28.7 31.9
3500 19.5 19.7 20.4 21.5 23.1 25.2 27.7
12½ 4000 17.8 18.1 18.6 19.6 20.9 22.5 24.5
4500 16.3 16.7 17.3 18.1 19.2 20.5 22.1
5000 14.9 15.5 16.2 17.1 18.0 19.2 20.4
5500 13.5 14.4 15.3 16.2 17.2 18.1 19.1
6000 12.1 13.4 14.6 15.7 16.7 17.6 18.3
Tons SCFM 35 40 45 50 55 60 65
3000 34.4 36.7 38.9 41.2 43.5 45.8 48.1
3600 29.3 31.2 33.1 35.0 36.9 38.8 40.8
4200 25.4 27.0 28.6 30.2 31.9 33.5 35.1
15 4800 22.3 23.7 25.1 26.5 27.9 29.3 30.7
5400 19.9 21.2 22.4 23.7 24.9 26.2 27.4
6000 18.0 19.1 20.3 21.4 22.5 23.7 24.8
6600 16.4 17.5 18.6 19.6 20.7 21.7 22.8
7200 15.1 16.1 17.1 18.1 19.1 20.1 21.1
Tons SCFM 35 40 45 50 55 60 65
4000 22.0 22.5 23.6 25.4 27.7 30.6 34.0
4800 19.1 19.8 20.9 22.3 24.0 26.1 28.5
5600 16.6 17.4 18.4 19.5 20.9 22.4 24.0
20 6400 14.7 15.5 16.3 17.2 18.2 19.3 20.6
7200 13.5 14.1 14.7 15.4 16.2 17.0 17.9
8000 12.9 13.2 13.7 14.2 14.8 15.5 16.2
8800 12.5 12.9 13.3 13.7 14.2 14.8 15.4
9600 12.4 12.8 13.1 13.5 13.9 14.5 15.0
Notes:
1. Temperature rise does not account for indoor fan heat.
2. 70 deg OD Ambient Temperature.
3. For units with the Dehumidification (Hot Gas Reheat) option.

RT-PRC001-EN 45
Controls

Field Installed Control Options Digital Display Zone Sensor CO2 Sensing The CO2 sensor has the
The Digital LCD (Liquid Crystal Display) ability to monitor space occupancy levels
Zone Sensors zone sensor has the look and functionality within the
Zone sensors are the building occupant’s of standard zone building by
comfort control devices.They replace the sensors.This measuring the
conventional electro-mechanical sensor includes a parts per million
thermostats.The following zone sensor digital display of of CO2 (Carbon
options are available for Voyager units set point Dioxide) in the air.
with the ReliaTel™ control: adjustment and As the CO2 levels
Manual Changeover space temperature increase, the
Heat, Cool or Off in F (Fahrenheit) or outside air
System Switch. Fan C (Celsius). damper
Auto or Off Switch. Includes FAN and modulates to
One temperature SYSTEM buttons meet the CO2 space ventilation
setpoint lever. (supports the requirements.The CO2 sensor kit is
service functions of available as a field installed accessory.
the standard Economizer Controls
sensor). E-squared memory stores last The standard equipment offering is a
programmed set points. Requires 24 VAC fixed dry bulb changeover control. In
(Volts AC).This sensor should be utilized addition, there are two optional controls,
Manual/Automatic Changeover with ReliaTel™ controls.
Auto, Heat, Cool or Off System Switch. Enthalpy and Differential Enthalpy
Fan Auto or Off Control.
Programmable Night Setback
Switch.Two Enthalpy Control
Auto or manual changeover with seven-
temperature Replaces the dry bulb control with a wet
day programming. Keyboard selection
setpoint levers. bulb changeover controller which has a
Optional Status fully adjustable set point. Enthalpy control
Indication LED lights, offers a higher level of comfort control,
System On, Heat, along with energy savings potential, than
Cool, or Service. the standard dry bulb control. This is due
to the additional wet bulb sensing
capability.
Differential Enthalpy
Replaces the standard dry bulb control
Remote Sensor with two enthalpy sensors that compare
Sensor(s) available total heat content of the indoor air and
for all zone sensors to of Heat, Cool, Fan, Auto, or On. All outdoor air to determine the most
provide remote programmable sensors have System On, efficient air source.This control option
sensing capabilities. Heat, Cool, Service LED/indicators as offers the highest level of comfort control,
standard. Night Setback Sensors have plus energy efficiency, available.
one (1) Occupied, one (1) Un-occupied, Remote Potentiometer
and two (2) Override programs per day. Minimum position setting of economizer
can be remotely adjusted with this
accessory.
Integrated
ComfortTM Differential Pressure Switches
System This factory or field-installed option
Dual Thermistor Remote Zone Sensor Sensor(s) allows individual fan failure and dirty filter
This sensor will allow the customer to available with indication. The fan failure switch will
reduce the total number of remote optional disable all unit functions and “flash” the
sensors to obtain space temperature temperature Service LED on the zone sensor. The dirty
averaging. This sensor should be utilized adjustment and filter switch will light the Service LED on
with ReliaTel controls. override buttons the zone sensor and will allow continued
to provide central unit operation.
control through a Trane Communication Interface (TCI)
Trane Integrated This factory or field-installed micro-
ComfortTM system. processor interface allows the unit to
communicate toTrane’s Integrated
ComfortTM system.
46 RT-PRC001-EN
Electrical
Data

Table ED-1 — Electrical Characteristics — Evaporator Fan Motors — 60 Cycle


Standard Evaporator Fan Motor Oversized Evaporator Fan Motor
Unit Amps Amps
Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA
YC*150D3,YC*151C3 1 208-230 3 3.00 10.6 81.0 1 208-230 3 5.00 16.7 109.8
12½ YC*150D4,YC*151C4 1 460 3 3.00 4.8 40.5 1 460 3 5.00 7.6 54.9
YC*150DW,YC*151CW 1 575 3 3.00 3.9 31.0 1 575 3 5.00 6.1 41.6
YC*150DK 1 380 3 5.0 9.2 66.5 – – – – – –
YC*180B3,YC*181C3 1 208-230 3 3.00 10.6 81.0 1 208-230 3 5.00 16.7 109.8
15 YC*180B4,YC*181C4 1 460 3 3.00 4.8 40.5 1 460 3 5.00 7.6 54.9
YC*180BW,YC*181CW 1 575 3 3.00 3.9 31.0 1 575 3 5.00 6.1 41.6
YC*180BK 1 380 3 5.0 9.2 66.5 – – – – – –
YC*210C3, YC*211C3 1 208-230 3 5.00 16.7 109.8 1 208-230 3 7.50 24.2 120.4
17½ YC*210C4, YC*211C4 1 460 3 5.00 7.6 54.9 1 460 3 7.50 11.0 74.0
YC*210CW,YC*211CW 1 575 3 5.00 6.1 41.6 1 575 3 7.50 9.0 60.0
YC*210CK 1 380 3 7.5 13.3 83.5 – – – – – –
YC*240B3,YC*241C3 1 208-230 3 5.00 16.7 109.8 1 208-230 3 7.50 24.2 120.4
20 YC*240B4,YC*241C4 1 460 3 5.00 7.6 54.9 1 460 3 7.50 11.0 74.0
YC*240BW,YC*241CW 1 575 3 5.00 6.1 41.6 1 575 3 7.50 9.0 60.0
YC*240BK 1 380 3 7.5 13.3 83.5 – – – – – –
YC*300B3,YC*301C3 1 208-230 3 7.50 24.2 120.4 — — — — — —
25 YC*300B4,YC*301C4 1 460 3 7.50 11.0 74.0 — — — — — —
YC*300BW,YC*301CW 1 575 3 7.50 9.0 60.0 — — — — — —
YC*300BK 1 380 3 7.5 13.3 83.5 — — — — — —

Table ED-2 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Standard Efficiency
Compressor Motor Condenser Fan Motors
Unit Amps1 Amps1
Tons Model No. No. Volts Phase HP3 RPM RLA LRA No. Phase HP FLA LRA
YC*150D3 2 208-230 3 6.0 3450 20.4 156 2 1 .50 3.2 8.8
12½ YC*150D4 2 460 3 6.0 3450 10.8 75 2 1 .50 1.6 3.8
YC*150DW 2 575 3 6.0 3450 8.3 54 2 1 .50 1.3 3.2
YC*150DK 2 380 3 6.0 3450 13.1 70 2 1 .50 1.9 5.2
YC*180B3 2 208-230 3 9.3/5.1 3450 31.9/20.7 253/128 2 1 .50 3.2 8.8
15 YC*180B4 2 460 3 9.3/5.1 3450 16.3/10.0 113/63 2 1 .50 1.6 3.8
YC*180BW 2 575 3 9.3/5.1 3450 13.1/7.4 85/49 2 1 .50 1.3 3.2
YC*180BK 2 380 3 9.3/5.1 3450 19.7/12.1 125/64 2 1 .50 1.9 5.2
YC*210C3 2 208-230 3 9.3/6.0 3450 31.5/20.8 253/156 2 1 1.00 5.5 18.3
17½ YC*210C4 2 460 3 9.3/6.0 3450 15.9/10.0 113/75 2 1 1.00 2.9 9.3
YC*210CW 2 575 3 9.3/6.0 3450 12.8/8.2 85/54 2 1 1.00 2.0 5.7
YC*210CK 2 380 3 9.3/6.0 3450 19.2/12.1 125/70 2 1 1.00 3.5 8.5
YC*240B3 2 208-230 3 9.3 3450 31.7 253 2 1 1.00 5.5 18.3
20 YC*240B4 2 460 3 9.3 3450 16.2 113 2 1 1.00 2.9 9.3
YC*240BW 2 575 3 9.3 3450 13.0 85 2 1 1.00 2.0 5.7
YC*240BK 2 380 3 9.3 3450 19.6 125 2 1 1.00 3.5 8.5
YC*300B3 2 208-230 3 10.0 3450 36.6 278 2 1 1.00 5.5 18.3
25 YC*300B4 2 460 3 10.0 3450 17.9 124 2 1 1.00 2.9 9.3
YC*300BW 2 575 3 10.0 3450 14.9 92 2 1 1.00 2.0 5.7
YC*300BK 2 380 3 10.0 3450 21.7 137 2 1 1.00 3.5 8.5
Notes:
1. Amp draw for each motor; multiply value by number of motors to determine total amps.
2. HP for each compressor.

*Indicates both downflow and horizontal units.

RT-PRC001-EN 47
Electrical
Data (High Efficiency)

Table ED-3 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency
Standard Refrigeration System
Compressor Motor Condenser Fan Motors
Unit Amps1 Amps1
Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP FLA LRA
YC*151C3 2 208-230 3 5.7 3450 20.7 156 2 1 .50 3.2 8.8
12½ YC*151C4 2 460 3 5.7 3450 10.0 75 2 1 .50 1.6 3.8
YC*151CW 2 575 3 5.7 3450 8.2 54 2 1 .50 1.3 3.2
YC*181C3 2 208-230 3 9.3/4.5 3450 31.5/16.9 253/124 2 1 .50 3.2 8.8
15 YC*181C4 2 460 3 9.3/4.5 3450 15.1/8.2 113/59.6 2 1 .50 1.6 3.8
YC*181CW 2 575 3 9.3/4.5 3450 12.1/6.6 85/49.4 2 1 .50 1.3 3.2
YC*211C3 2 208-230 3 10.0/5.7 3450 33.3/20.7 278/156 2 1 1.00 5.5 18.3
17½ YC*211C4 2 460 3 10.0/5.7 3450 16.3/10.0 124/75 2 1 1.00 2.9 9.3
YC*211CW 2 575 3 10.0/5.7 3450 13.2/8.2 92/54 2 1 1.00 2.0 5.7
YC*241C3 2 208-230 3 9.30 3450 31.6 253 2 1 1.00 5.5 18.3
20 YC*241C4 2 460 3 9.30 3450 16.1 113 2 1 1.00 2.9 9.3
YC*241CW 2 575 3 9.30 3450 12.9 85 2 1 1.00 2.0 5.7
YC*301C3 2 208-230 3 10.00 3450 37.6 278 2 1 1.00 5.5 18.3
25 YC*301C4 2 460 3 10.00 3450 18.3 124 2 1 1.00 2.9 9.3
YC*301CW 2 575 3 10.00 3450 14.9 92 2 1 1.00 2.0 5.7
Notes:
1. Amp draw for each motor; multiply value by number of motors to determine total amps.
2. HP for each compressor.

Table ED-4 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency, TXV/Face-Split
Evaporator Coil Option (Downflow Only)
Compressor Motor Condenser Fan Motors
Unit Amps1 Amps1
Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP FLA LRA
YCD151C3 2 208-230 3 5.7/5.7 3450 18.6/18.6 156/156 2 1 .50 3.2 8.8
12½ YCD151C4 2 460 3 5.7/5.7 3450 9.4/9.4 75/75 2 1 .50 1.6 3.8
YCD151CW 2 575 3 5.7/5.7 3450 7.4/7.4 54/54 2 1 .50 1.3 3.2
YCD181C3 2 208-230 3 9.3/4.5 3450 32.1/16.4 253/124 2 1 .50 3.2 8.8
15 YCD181C4 2 460 3 9.3/4.5 3450 15.6/8.7 113/59.6 2 1 .50 1.6 3.8
YCD181CW 2 575 3 9.3/4.5 3450 12.3/7.4 85/49.4 2 1 .50 1.3 3.2
YCD211C3 2 208-230 3 10.00/5.7 3450 34.8/19.5 278/156 2 1 1.00 5.5 18.3
17½ YCD211C4 2 460 3 10.00/5.7 3450 17.0/10.3 124/75 2 1 1.00 2.9 9.3
YCD211CW 2 575 3 10.00/5.7 3450 13.8/8.1 92/54 2 1 1.00 2.0 5.7
YCD241C3 2 208-230 3 9.0/9.3 3500/3450 30.4/32.6 225/253 2 1 1.00 5.5 18.3
20 YCD241C4 2 460 3 9.0/9.3 3500/3450 16.1/16.8 114/113 2 1 1.00 2.9 9.3
YCD241CW 2 575 3 9.0/9.3 3500/3450 12.5/13.4 80/85 2 1 1.00 2.0 5.7
YCD301C3 2 208-230 3 10.00 3450 36.2 278 2 1 1.00 5.5 18.3
25 YCD301C4 2 460 3 10.00 3450 17.7 124 2 1 1.00 2.9 9.3
YCD301CW 2 575 3 10.00 3450 14.3 92 2 1 1.00 2.0 5.7
Notes:
1. Amp draw for each motor; multiply value by number of motors to determine total amps.
2. HP for each compressor.

Table ED-5— Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Dehumidification (Hot Gas Reheat) Option
(Downflow Only)
Compressor Motor Condenser Fan Motors
Unit Amps1 Amps1
Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP FLA LRA
YCD151C3 2 208-230 3 5.7/5.7 3450 18.6/18.6 156/156 2 1 .50 3.2 8.8
12½ YCD151C4 2 460 3 5.7/5.7 3450 9.7/9.7 75/75 2 1 .50 1.6 3.8
YCD151CW 2 575 3 5.7/5.7 3450 7.6/7.6 54/54 2 1 .50 1.3 3.2
YCD181C3 2 208-230 3 8.3/5.7 3450 27.4/19.0 208/156 2 1 .50 3.2 8.8
15 YCD181C4 2 460 3 8.3/5.7 3450 13.8/10.1 100/75 2 1 .50 1.6 3.8
YCD181CW 2 575 3 8.3/5.7 3450 10.7/7.9 68/54 2 1 .50 1.3 3.2
YCD241C3 2 208-230 3 9.0/9.3 3500/3450 30.1/13.7 225/253 2 1 1.00 5.5 18.3
20 YCD241C4 2 460 3 9.0/9.3 3500/3450 15.6/16.2 114/113 2 1 1.00 2.9 9.3
YCD241CW 2 575 3 9.0/9.3 3500/3450 12.1/13.0 80/85 2 1 1.00 2.0 5.7
Notes:
1. Amp draw for each motor; multiply value by number of motors to determine total amps.
2. HP for each compressor. *Indicates both downflow and horizontal units.

48 RT-PRC001-EN
Electrical
Data (Standard Efficiency)

Table ED-6 — Unit Wiring - Standard Efficiency


Standard Indoor Fan Motor Oversize Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum
Tons Model No. Voltage Range Ampacity2 Circuit Breaker1 Ampacity2 Circuit Breaker1
YC*150D3 187-253 63 80 69 80
12½ YC*150D4 414-506 33 40 36 40
YC*150DW 517-633 26 30 28 35
YC*150DK 342-418 43 50 – –
YC*180B3 187-253 78 90 84 100
15 YC*180B4 414-506 39 50 42 50
YC*180BW 517-633 31 40 30 40
YC*180BK 342-418 50 60 – –
YC*210C3 187-253 88 100 96 125
17½ YC*210C4 414-506 44 50 47 60
YC*210CW 517-633 35 45 38 45
YC*210CK 342-418 57 70 – –
YC*240B3 187-253 100 125 107 125
20 YC*240B4 414-506 50 60 54 60
YC*240BW 517-633 40 45 43 50
YC*240BK 342-518 65 80 – –
YC*300B3 187-253 118 150 – –
25 YC*300B4 414-506 58 70 – –
YC*300BW 517-633 46 50 – –
YC*300BK 342-418 70 80 – –
Notes:
1. HACR breaker per NEC.
2. MCA values do not include Power Exhaust accessory. See Table ED-7 for this information.

*Indicates both downflow and horizontal units.

RT-PRC001-EN 49
Electrical
Data (High Efficiency)

Table ED-7— Unit Wiring - High Efficiency— Standard Refrigeration System


Standard Indoor Fan Motor Oversize Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum
Tons Model No. Voltage Range Ampacity2 Circuit Breaker1 Ampacity2 Circuit Breaker1
YC*151C3 187-253 64 80 70 90
12½ YC*151C4 414-506 31 40 34 40
YC*151CW 517-633 25 30 28 35
YC*181C3 187-253 74 90 80 100
15 YC*181C4 414-506 36 50 38 50
YC*181CW 517-633 29 40 31 40
YC*211C3 187-253 91 110 98 125
17½ YC*211C4 414-506 44 60 48 60
YC*211CW 517-633 35 45 38 50
YC*241C3 187-253 99 125 107 125
20 YC*241C4 414-506 50 60 54 60
YC*241CW 517-633 40 50 43 50
YC*301C3 187-253 120 150 N/A N/A
25 YC*301C4 414-506 58 70 N/A N/A
YC*301CW 517-633 47 60 N/A N/A
Notes:
1. HACR breaker per NEC.
2. MCA values do not include Power Exhaust accessory. See Table ED-7 for this information.

Table ED-8 — Unit Wiring - High Efficiency, TXV/Face-Split Evaporator Coil Option (Downflow Only)
Standard Indoor Fan Motor Oversize Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum
2
Tons Model No. Voltage Range Ampacity Circuit Breaker1 Ampacity 2
Circuit Breaker1
YCD151C3 187-253 59 70 65 80
12½ YCD151C4 414-506 30 35 32 40
YCD151CW 517-633 24 30 26 30
YCD181C3 187-253 74 90 80 90
15 YCD181C4 414-506 37 50 39 50
YCD181CW 517-633 30 40 32 40
YCD211C3 187-253 91 125 99 125
17½ YCD211C4 414-506 45 60 49 60
YCD211CW 517-633 36 45 39 50
YCD241C3 187-253 99 125 107 125
20 YCD241C4 414-506 51 60 54 70
YCD241CW 517-633 40 50 43 50
YCD301C3 187-253 117 150 N/A N/A
25 YCD301C4 414-506 57 70 N/A N/A
YCD301CW 517-633 46 50 N/A N/A
Notes:
1. HACR breaker per NEC.
2. MCA values do not include Power Exhaust accessory. See Table ED-7 for this information.

*Indicates both downflow and horizontal units.

50 RT-PRC001-EN
Electrical
Data (High Efficiency)

Table ED-9 — Unit Wiring - Dehumidification (Hot Gas Reheat) Option (Downflow Only)
Standard Indoor Fan Motor Oversize Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum
Tons Model No. Voltage Range Ampacity2 Circuit Breaker1 Ampacity2 Circuit Breaker1
YCD151C3 187-253 59 70 65 80
12½ YCD151C4 414-506 30 35 32 40
YCD151CW 517-633 24 30 26 30
YCD181C3 187-253 71 90 77 100
15 YCD181C4 414-506 36 45 39 50
YCD181CW 517-633 28 35 30 40
YCD241C3 187-253 98 125 105 125
20 YCD241C4 414-506 50 60 53 60
YCD241CW 517-633 39 50 42 50
Notes:
1. HACR breaker per NEC.
2. MCA values do not include Power Exhaust accessory. See Table ED-7 for this information.

*Indicates both downflow and horizontal units.

RT-PRC001-EN 51
Electrical
Data

Table ED-10 — Electrical Characteristics — Combustion Blower Motor


Unit Heating Amps
Model No. Heat Stages HP RPM Volts Phase FLA LRA
YC*150, 151 Low 2 1/20 3500/28001 208-230 1 0.5 0.78
YC*180, 181, 210, 211, 240-300 Low 2 1/10 3500/28001 208-230 1 0.8 2.00
YC*151-YC*301 High 2 1/10 3500/28001 208-230 1 0.8 2.00
1. High/Low Speed.

Table ED-11 — Electrical Characteristics — Power Exhaust Accessory


Accessory
Operating Amps
Tons Voltage Phase HP RPM FLA LRA
208-230 1 3/4 1040 6.6 13.5
12½1,12½2
460 1 3/4 1040 3.2 8.4
15,17½, 20, 25
575 1 3/4 1040 2.1 5.2
Notes:
1. 12½ Ton Standard Unit.
2. 12½ Ton High Efficiency Unit.

52 RT-PRC001-EN
Jobsite
Connections

Zone Sensors
Typical Number Of Wires
DISCONNECT
SWITCH A— Manual Changeover .......................................... 4
(BY OTHERS) Manual/Auto Changeover ................................. 5
Manual/Auto Changeover with
B Status Indication LED’s ............................. 10
Programmable Night Setback
A with Status Indication LED’s ....................... 7
ZONE SENSORS
B— 3 Power Wires + 1 Ground Wire (three phase)
ROOFTOP 2 Power Wires + 1 Ground Wire (single phase)
UNIT

For specific wiring information, see the installation instructions.


All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer.

RT-PRC001-EN 53
Typical
Wiring (12½ - 25 Tons)

54 RT-PRC001-EN
Typical
Wiring (12½ - 25 Tons)

PRINTED FROM 2307-3133

RT-PRC001-EN 55
Typical
Wiring (12½ - 25 Tons)

56 RT-PRC001-EN
Typical
Wiring (12½ - 25 Tons)

RT-PRC001-EN 57
Dimensional 12½ Ton (High Efficiency)
Data 12½, 15, 17½ Ton (Standard Efficiency)

All dimensions are in inches.

1"
1 13/16"
1 1/2" PERIMETER 101 7/8"
20 7/8" 1"
CURB FLANGE
Note: 17 1/8" 1"
66 5/8"
Duct flanges mount 7-7/16" down inside 7 7/16" 63"
28 1/2"
the curb on the 1-1/2" curb flanges. See
recommended duct dimensions on the
RN
TU

55 1/2"
next page.
RE

LY

Roofcurb is intended for downflow use


PP

only.
SU

14 1/16" 2"

7 1/2" 67"
102 1/4"

Downflow Unit Clearance

58 RT-PRC001-EN
Dimensional 12½ Ton (High Efficiency)
Data 12½, 15, 17½ Ton (Standard Efficiency)

All dimensions are in inches. 1"

17 7/8"
Downflow Duct Connections — Field Fabricated
59 7/16"

26 5/16"
52 1/2" 1"

1 1\2"
PERIMETER
14 1/16" CURB FLANGE
N
7 7/16"
T UR
RE

Note: Y
P PL
Duct flanges mount 7-7/16" down inside the SU
curb on the 1-1/2" curb flanges.
Roofcurb is intended for downflow use only.

Horizontal Unit Supply/Return and Unit


Clearance

RT-PRC001-EN 59
Dimensional 15 - 25 Tons (High Efficiency)
Data 20, 25 Ton (Standard Efficiency)

All dimensions are in inches.

1"
1 13/16"
1 1/2" PERIMETER 116 7/8"
22 1/4" 1"
Note: CURB FLANGE
23 1/4" 1"
Duct flanges mount 7-7/16" down inside the 7 7/16"
80 5/8"
77"
curb on the 1-1/2" curb flanges. See 28 9/16"
recommended duct dimensions on the next
RN

page. 69 1/2"
TU
RE

Roofcurb is intended for downflow use only.


LY
PP
SU

14 1/16" 2"

7 1/2" 81"
117 3/16"

Downflow Unit Clearance

60 RT-PRC001-EN
Dimensional 15 - 25 Tons (High Efficiency)
Data 20, 25 Ton (Standard Efficiency)

All dimensions are in inches. 1"

19 5/16"
Downflow Duct Connections — Field Fabricated
73 7/16"

26 5/16"
66 1/2" 1"

1 1\2"
PERIMETER
14 1/16" CURB FLANGE

7 7/16" URN
RET

Note:
Duct flanges mount 7-7/16" down PLY
inside the curb on the 1-1/2" curb S UP
flanges.
Roofcurb is intended for downflow use
only.

Horizontal Unit Supply/Return and Unit


Clearance

RT-PRC001-EN 61
Dimensional (12½ - 25 Tons)
Data Accessories

All dimensions are in inches.

Note:
When applying economizer to horizontal units,
connecting ductwork must be run full size to
allow proper operation of economizer damper.

Table DD-1
Unit
Model # A B1 C2
YC*150-151-180,210 17½ 53¾ 36
YC*181, 211-301 19½ 64¾ 39
Notes:
1. Horizontal dimension only. Downflow economizer is width
of end panel.
2. Power exhaust is applied on downflow economizer only.

62 RT-PRC001-EN
Dimensional Factory Installed
Data Options (FIOPS)

All dimensions are in inches.

Table DD-2
Unit
Model # A B C
YCD150, 151, 180, 210 423/8 663/8 483/8
YCD181-300 291/2 777/8 58

RT-PRC001-EN 63
Dimensional Factory Installed
Data Options (FIOPS)

Fan Failure Switch


Disconnect Switch or Circuit Breaker

Clogged Filter Switch

Powered Or Unpowered Convenience Outlet

Trane Communication Interface


Hinged Access Door

Black Epoxy Coated Outdoor Coils

Hinged Access Door

Through the Base Electrical

High Pressure Cut Out

Supply and/or Return Smoke Detectors

Through the Base Gas Piping

64 RT-PRC001-EN
Dimensional
Data (12½ - 25 Tons)

Table DD-3 — Standard Efficiency Units


Condensate Drain Location
Condensate
Tons Downflow Only Drain Size Downflow Horizontal
A B C D F G H E J E K
12½, 15, 17½ 26-7/16 22-1/2 18-11/16 4-1/4 4-1/4 62-7/16 54-11/16 1 NPT — 25-5/8 — 5-3/8
20, 25 26-7/16 28-3/4 19-15/16 4-1/4 4-1/4 76-5/16 68-11/16 1 NPT — 26-3/4 — 5-3/8

Table DD-4 — High Efficiency Units


Condensate Drain Location
Condensate
Tons Downflow Only Drain Size Downflow Horizontal
A B C D F G H E J E K
12½ 26-7/16 22-1/2 18-11/16 4-1/4 4-1/4 62-7/16 54-11/16 1 NPT — 25-5/8 — 6
15-25 26-7/16 28-3/4 19-15/16 4-1/4 4-1/4 76-5/16 68-11/16 1 NPT — 26-3/4 — 5-3/8

RT-PRC001-EN 65
Weights (12½ - 25 Tons)

Table W-1 — Accessory Net Weights (Lbs)1,2


Oversize LPG All High4 Low4
Unit Economizer Outside Air Damper Roof3 Motor Conversion Zone Power3 Static Static
Model No. Net Motorized Manual Curb Adder Kit Sensors Exhaust Drive Drive
YCD150D,151C 65 60 32 205 5 5 1 95 2 2
YCD180B,210C
YCD181,211,241C 80 75 32 235 5 5 1 95 2 —
YCD240B 80 75 32 235 — 5 1 95 — 2
YCD300B,301C
YCH150D,151C
YCH180B,210C 50 60 32 N/A 5 5 1 N/A 2 —

YCH181,211,241C 65 75 32 N/A 5 5 1 N/A 2 —


YCH240B
YCH300B, 301C 65 75 32 N/A — 5 1 N/A — 2
Notes:
1. Net weight should be added to unit weight when ordering factory installed accessories.
2. YC*150-300 factory installed options for economizers, multiply net capacity x .99, EER x .97.
For oversize motors, multiply net capacity x .98, EER x .93. This is provided in compliance with ARI certification program.
3. Downflow only.
4. Not available on all models (See fan performance tables for specific models).

Table W-2 — Factory Installed Options (FIOPS) Net Weights (Lbs)1,2,3


Accessory Weight Unit Model Number
High Efficiency Motors4 49 YC*150-181 standard size motor
36 YC*211-241 standard size motor
YC*150-181 oversize motor
0 YC*300-301 standard size motor
Hinged Doors 27 AllYC* units
Powered Convenience Outlet 38 AllYC* units
Through the Base Electrical 23 AllYC* units
Unit Mounted Circuit Breaker 5 AllYC* units
Unit Mounted Disconnect 5 AllYC* units
Smoke Detectors
Supply/Return 5 AllYC* units
Tool-less Hail Guard 38 YC*150,151,180,210
43 YC*181,211,240,241,300,301
Novar 2024 7 AllYC* units
Novar 3501 5 AllYC* units
Notes:
1. Weights for FIOP accessories not listed are <5 lbs.
2. Net weight should be added to unit weight when ordering factory installed accessories.
3. See Table W-1 for standard factory installed economizer and oversized motors.
4. Standard factory installed motors are already included in unit net and shipping weights. Values shown for high
efficiency motors are in addition to the standard motor weight.

*Indicates both downflow and horizontal units.

66 RT-PRC001-EN
Weights (12½ - 25 Tons)

Table W-3 — Maximum Unit And Corner Weights (Lbs) and Center Of Gravity Dimensions (In.)
Unit Maximum Weights (Lbs)2 Corner Weights (Lbs)1 Center of Gravity (In.)
Tons Model No. Shipping Net A B C D Length Width
YC*150D/YC*151C 1826/1915 1458/1547 495/523 373/383 254/271 336/370 46/45 29/30
12½
YC*151C (Reheat Units) 1870/1959 1502/1591 506/534 384/394 265/282 347/381 46/45 29/30
15 YC*180B/YC*181C 2033/2464 1665/2005 600/686 395/504 266/345 404/470 43/52 29/35
YC*181C (Reheat Units) 2097/2528 1729/2069 611/697 406/515 277/356 415/481 43/52 29/35
17½ YC*210C/YC*211C 2189/2547 1821/2088 618/701 463/538 317/369 424/480 46/53 29/35
20 YC*240B/YC*241C 2547/2645 2088/2186 738/751 526/568 343/373 481/494 51/53 34/34
YC*241C (Reheat Units) 2567/2665 2108/2206 743/756 531/573 348/378 486/499 51/53 34/34
25 YC*300B/YC*301C 2541/2650 2082/2191 721/755 552/569 351/373 458/495 53/53 33/34
Notes:
1. Corner weights are given for information only. 12½-25 ton must be supported continuously by a curb or equivalent frame support.
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.

*Indicates both downflow and horizontal units.

RT-PRC001-EN 67
Mechanical
Specifications

General UnitTop Gas Heating Section


The units shall be dedicated downflow or The top cover shall be one piece, or The heating section shall have a drum
horizontal airflow.The operating range where seams exist, double hemmed and and tube heat exchanger design using
shall be between 115°F and 0°F in cooling gasket sealed to prevent water leakage. corrosion resistant steel components. A
as standard from the factory for all units. Filters forced combustion blower shall supply
Cooling performance shall be rated in Two inch standard filters shall be factory premixed fuel to a single burner ignited
accordance with ARI testing procedures. supplied on all units. Optional two inch by a pilotless hot surface ignition system.
All units shall be factory assembled, pleated media filters shall be available. In order to provide reliable operation, a
internally wired, fully charged with R-22, negative pressure gas valve shall be
and 100 percent run tested to check Compressors used that requires blower operation to
cooling operation, fan and blower rotation All units shall have direct-drive, hermetic, initiate gas flow. On an initial call for heat,
and control sequence, before leaving the scroll type compressors with centrifugal the combustion blower shall purge the
factory. Wiring internal to the unit shall be type oil pumps. Motor shall be suction heat exchanger 45 seconds before
colored and numbered for simplified gas-cooled and shall have a voltage ignition. After three unsuccessful ignition
identification. Units shall be UL listed and utilization range of plus or minus 10 attempts, the entire heating system shall
labeled, classified in accordance to UL percent of nameplate voltage. Internal be locked out until manually reset at the
1995/CAN/CSA No. 236-M90 for Heat overloads shall be provided with the thermostat. Units shall be suitable for use
Pumps. Canadian units shall be CSA scroll compressors. All models shall have with natural gas or propane (field
Certified. crankcase heaters, low and high pressure installed kit) and shall also comply with
control as standard. California requirements for low NOx
Casing
Unit casing shall be constructed of zinc Refrigerant Circuits emissions.The 12½-25 tons shall have
coated, heavy gauge, galvanized steel. Each refrigerant circuit shall have two stage heating.
Exterior surfaces shall be cleaned, independent fixed orifice or thermostatic Outdoor Fans
phosphatized, and finished with a expansion devices, service pressure The outdoor fan shall be direct-drive,
weather-resistant baked enamel finish. ports, and refrigerant line filter driers statically and dynamically balanced,
Unit’s surface shall be tested 500 hours in factory installed as standard. An area draw-through in the vertical discharge
a salt spray test in compliance with ASTM shall be provided for replacement suction position.The fan motor(s) shall be
B117. Cabinet construction shall allow for line driers. permanently lubricated and shall have
all maintenance on one side of the unit. In Evaporator and Condenser Coils built-in thermal overload protection.
order to ensure a water and air tight seal, Internally finned, 3/8" copper tubes Indoor Fan
service panels shall have lifting handels mechanically bonded to a configured Units above shall have belt driven, FC
and no more thatn three screws to aluminum plate fin shall be standard. centrifugal fans with adjustable motor
remove. All exposed vertical panels and Coils shall be leak tested at the factory to sheaves. Units with standard motors
top covers in the indoor air section shall ensure the pressure integrity.The shall have an adjustable idler-arm
be insulated with a 1/2 inch, 1 pound evaporator coil and condenser coil shall assembly for quick-adjustment of fan
density foil-faced, fire-resistant, be leak tested to 200 psig and pressure belts and motor sheaves. All motors shall
permanent, odorless, glass fiber material. tested to 450 psig. All dual compressor be thermally protected. Oversized motors
The base of the downflow unit shall be units shall have intermingled evaporator shall be available for high static
insulated with 1/2 inch, 1 pound density coils. Sloped condensate drain pans are application. All indoor fan motors meet
foil-faced, closed-cell material.The standard. Patent-pending 1+1+1 the U.S. Energy Policy Act of 1992
downflow unit’s base pan shall have no condenser coil, permanently gapped for (EPACT).
penetrations within the perimeter of the easy cleaning is available.
curb other than the raised 11/8 inch high
supply/return openings to provide an
added water integrity precaution, if the
condensate drain backs up.The base of
the unit shall have provisions for forklift
and crane lifting.

68 RT-PRC001-EN
Mechanical
Specifications

Controls Hinged Access Doors Through the Base Electrical with Circuit
Unit shall be completely factory wired Sheet metal hinges are available on the Breaker
with necessary controls and contactor Filter/Evaporator Access Door and the This option is a thermal magnetic, molded
pressure lugs or terminal block for power Compressor/Control Access Door.This case, HACR Circuit Breaker with
wiring. Unit shall provide an external option is available on all downflow provisions for through the base electrical
location for mounting a fused disconnect models. connections.The circuit breaker will be
device. ReliaTel controls shall be provided High Efficiency Motors installed in a water tight enclosure in the
for all 24 volt control functions.The This option is available with efficiency unit with access through a swinging door.
resident control algorithms shall make all ratings from 86.5 up to 91.0. It is not Factory wiring will be provided from the
heating, cooling, and/or ventilating available for all models. switch to the unit high voltage terminal
decisions in response to electronic signals block.The circuit breaker will provide
from sensors measuring indoor and High Pressure Cutout overcurrent protection, be sized per NEC
outdoor temperatures.The control This option is offered for units that do not and UL guidelines, and be agency
algorithm maintains accurate have High Pressure cutout as standard. recognized by UL/CSA.This option is
temperature control, minimizes drift from Powered or Unpowered Convenience available on all downflow models.
set point, and provides better building Outlet Through the Base Electrical With
comfort. A centralized control shall This option is a GFCI, 120v/15amp, 2 plug, Disconnect Switch
provide anti-short cycle timing and time convenience outlet, either powered or Three-pole, molded case, disconnect
delay between compressors to provide a unpowered. When the convenience outlet switch with provisions for through the
higher level of machine protection. is powered, a service receptacle base electrical connections are available.
Defrost Controls disconnect will be available.The The disconnect switch will be installed in
Adaptive demand defrost shall be convenience outlet is powered from the the unit in a water tight enclosure with
provided to permit defrost wherever coil line side of the disconnect or circuit access through a swinging door. Factory
icing conditions begin to significantly breaker, and therefore will not be wiring will be provided from the switch to
reduce unit capacity. affected by the position of the disconnect the unit high voltage terminal block.The
or circuit breaker.This option can only be switch will be UL/CSA agency recognized.
Factory Installed Options ordered when theThrough the Base Note:The disconnect switch will be sized
Black Epoxy Coated Condenser Coil Electrical with either the Disconnect per NEC and UL guidelines but will not be
The coil provides corrosion protection to Switch, or Circuit Breaker, option is used in place of unit overcurrent
condenser coils for seacoast application. ordered.This option is available on all protection.This option is available on all
The protection is a thermoset vinyl downflow models. downflow models.
coating, bonded to normal aluminum fin Supply and/or Return Air Smoke Through the Base Utilities Access
stock.The uniform thickness of the bonded Detector An electrical service entrance shall be
vinyl layer exhibits excellent corrosion With this option installed, if smoke is provided allowing electrical access for
protection in salt spray tests performed in detected, all unit operation will be shut both control and main power connections
accordance with ASTM B117. down. Reset will be manual at the unit. inside the curb and through the base of
Dehumidification Option Return Air Smoke Detectors require the unit. Option will allow for field
The dehumidification (hot gas reheat) minimum allowable airflow when used installation of liquid-tight conduit and an
option shall provide increased with certain models. See the Installation, external field installed disconnect switch.
dehumidification.The option shall consist Operation, and Maintenance (IOM)
manual for the models affected and the Two-Inch Pleated Filters
of a hot-gas reheat coil located on the Two inch pleated media filters shall be
leaving air side of the evaporator coil minimum allowable airflow required.This
option is available on all downflow available on all models.
prepiped and circuited. Low pressure
switch(es) and thermostatic expansion models.
valve(s) TXV are standard. Frostat™,
ReliaTel options module, and 2”pleated
filters are required but not standard.They
must be ordered and configured
separately.

RT-PRC001-EN 69
Mechanical
Specifications

Factory or Field Installed Electric Heaters Reference or Comparative Enthalpy


Options Electric heat modules shall be available Reference Enthalpy is used to measure
for installation within the basic unit. and communicate outdoor humidity.The
Clogged Filter/Fan Failure Switch Electric heater elements shall be unit receives and uses this information to
A dedicated differential pressure switch is constructed of heavy-duty nickel provide improved comfort cooling while
available to achieve active fan failure chromium elements internally delta using the economizer. Comparative
indication and/or clogged filter indication. connected for 240 volt, wye connected Enthalpy measures and communicates
These indications will be registered with for 480 and 600 volt. Staging shall be humidity for both outdoor and return air
either a zone sensor with status indication achieved through ReliaTel. Each heater conditions, and return air temperature.
lights or an Integrated Comfort™ System. package shall have automatically reset The unit receives and uses this
Differential Pressure Switches high limit control operating through information to maximize use of
These options allow for individual fan heating element contactors. All heaters economizer cooling, and to provide
failure and dirty filter indication.The fan shall be individually fused from the maximum occupant comfort control.
failure switch will disable all unit functions factory, where required, and shall meet Reference or Comparative Enthalpy
and “flash” the Service LED on the zone all NEC and CEC requirements when option shall be available when a factory
sensor.The dirty filter switch will light the properly installed. Power assemblies or field installed Downflow Economizer is
Service LED on the zone sensor and will shall provide single-point connection. ordered.This option is available on all
allow continued unit operation. Electric heat modules shall be UL listed or downflow models.
CSA certified. If ordering theThrough the Tool-less Hail Guards
Discharge Air Sensing Kit Base Electrical option with an Electric
This kit provides true discharge air Tool-less, hail protection quality coil
Heater, the heater must be factory guards are available for condenser coil
sensing in heating models.This sensor is installed.
a status indicator readable through protection.
Tracer™orTracker™.The kit is functional Frostat Trane Communication Interface
only with the ReliaTel Options Module. This option is to be utilized as a safety This factory or field-installed option shall
device. The Frostat opens when be provided to interface ReliaTel™
Economizer - Downflow temperatures on the evaporator coil fall
The assembly includes fully modulating controlled units with theTrane Integrated
below 10°F. The temperature will need to ComfortTM systems.
0-100 percent motor and dampers, rise to 50°F before closing.This option
barometric relief, minimum position should be utilized in low airflow or high
setting, preset linkage, wiring harness outside air applications.
with plug, fixed dry bulb and spring return
actuator.The barometric relief damper LonTalk® Communications Interface
shall be standard with the downflow The LonTalk communications interface,
economizer and shall provide a pressure when installed in a Voyager unit, allows
operated damper that shall be gravity the unit to communicate as aTracer™LCI-
closing and shall prohibit entrance of V device or directly with generic LonTalk
outside air during the equipment “off” Network Building Automation System
cycle. Solid state enthalpy and differential Controls.
enthalpy control shall be field-installed Oversized Motors
Oversized motors shall be available for
high static applications.

70 RT-PRC001-EN
Mechanical
Specifications

Field Installed Options Powered Exhaust


The powered exhaust shall provide
CO2 Sensing exhaust of return air, when using an
The CO2 sensor has the ability to monitor economizer, to maintain better building
space occupancy levels within the pressurization.
building by measuring the parts per
million of CO2 (Carbon Dioxide) in the air. Roof Curb - Downflow
As the CO2 levels increase, the outside air The roof curb shall be designed to mate
damper modulates to meet the CO2 with the downflow unit and provide
space ventilation requirements. support and a water tight installation
when installed properly.The roof curb
Digital Display Zone Sensor design shall allow field-fabricated
The Digital LCD (Liquid Crystal Display) rectangular supply/return ductwork to be
zone sensor has the look and functionality connected directly to the curb. Curb
of standard zone sensors.This sensor design shall comply with NRCA
includes a digital display of set point requirements. Curb shall be shipped
adjustment and space temperature in F knocked down for field assembly and
(Fahrenheit) or C (Celsius). Includes FAN shall include wood nailer strips.
and SYSTEM buttons (supports the
service functions of the standard sensor). Economizer - Horizontal
E-squared memory stores last The horizontal economizer shall contain
programmed set points. Requires 24 VAC the same features as the downflow
(Volts AC).This sensor should be utilized economizer with the exception of
with ReliaTel™ controls. barometric relief.
Dual Thermistor Remote Zone Sensor Remote Potentiometer
This sensor will allow the customer to The minimum position setting of the
reduce the total number of remote economizer shall be adjusted with this
sensors to obtain space temperature accessory.
averaging. This sensor should be utilized Ventilation Override Accessory
with ReliaTel controls. With the Ventilation Override Accessory
High Static Drive installed, the unit can be set to transition
The high static drive option shall allow the up to 3 different pre-programmed
standard motor on the 12½ and 20 ton sequences for Smoke Purge,
units to operate with improved external Pressurization, and Exhaust.The
static capabilities. transition occurs when a binary input on
the RTOM is closed (shorted).This would
Manual Outside Air Damper typically be a hard wired relay output
The rain hood and screen shall provide from a smoke detector or fire control
up to 25 percent outside air. panel.
Motorized Outside Air Dampers Zone Sensors
Manually set outdoor air dampers shall This option shall be provided to interface
provide up to 50 percent outside air. Once with the Micro equipped Voyagers and
set, outdoor air dampers shall open to set shall be available in either manual,
position when indoor fan starts.The automatic, programmable with night
damper shall close to the full closed setback, with system malfunction lights or
position when indoor fan shuts down. remote sensor options.

RT-PRC001-EN 71
*High Efficiency Units only

Literature Order Number RT-PRC001-EN


File Number PL-UN-RT-YCD/YCH 12½-25TONS-PRC001-EN-10-04
Supersedes PL-UN-RT-YCD/YCH 12½-25TONS-PRC001-EN-07-04
Trane
A business of American Standard Companies Stocking Location 07-04 Webb/Mason 10-04 Electronic Only
www.trane.com
For more information contact your local dealer
(distributor), local district office, or e-mail us at Trane has a policy of continuous product and product data improvement and reserves the right to change design
[email protected] and specifications without notice.