Dynamic Wind Response

This document provides design specifications for a SWITH YARD located in Odisha, India. It includes the dimensional details of the structure with a height of 21.3m, length of 2.5m, and width of 2.5m. It then lists the design wind speed calculation and wind pressure based on Indian code IS 875. Solidity ratio and wind load calculations are presented for the lattice tower members. Force coefficients are listed from the code. The document also includes member weight forces calculated at each node of the structure.

Uploaded by

jatin kalra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
224 views7 pages

Dynamic Wind Response

This document provides design specifications for a SWITH YARD located in Odisha, India. It includes the dimensional details of the structure with a height of 21.3m, length of 2.5m, and width of 2.5m. It then lists the design wind speed calculation and wind pressure based on Indian code IS 875. Solidity ratio and wind load calculations are presented for the lattice tower members. Force coefficients are listed from the code. The document also includes member weight forces calculated at each node of the structure.

Uploaded by

jatin kalra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 7

SWITH YARD

LOCATION ODISHA
DIMENSION

HEIGHT 21.3 M
LENGTH 2.5 M
WIDTH 2.5 M

H/w 8.52

BASIC WIND SPEED(Vb) 50 m/sec


K1 1.08 From table 1(d) of IS 875 part 3 2015
k2 1.08 From Table 2 For Terrain category 2 of IS 875 Part 3 2015
k3 1 As per cl 6.3.3
k4 1 As per cl 6.3.4

Design Win Speed 58.32 m/sec

Wind Pressure 0.208026 T/m2

Ka 1 As perTable 4(i)
Kd 1 As per 7.2.1
Kc 0.9 As per 7.3.3.13

Design Wind Pressure 0.187223 T/m2

SOLIDITY RATIO
FOR ONE PANEL OF
Length 2.5 m
Height 1.4 m
Diagonal length of 2.86 m
Panel
Assuming 150*150*16 on Vertical Side
90*90*6 on Bracing

Coverd area 0.6774


Area of panel 3.5

Solidity Ratio 0.193542857

Force Coefficient for Lattice tower (Cf) 3.4 (As per Table 33 of IS 875 part 3 2015)

Wind Load on Members


Wind ward members
Assuming Vertical Member is an angle of 150*150*16
Wind Load on Vertical Member 0.095484 TON/M
Assuming Bracing Member is an angle of 90*90*6
Wind Load on Diagonal Members 0.05729 TON/M

Leeward Members
Shielding Factor 1 (As per Table 32 of IS 875 Part 3 2015)
This Force will Act Simultaniously with above windward forces

Assuming Vertical Member is an angle of 150*150*16


Wind Load on Vertical Member 0.095484 TON/M

Assuming Bracing Member is an angle of 90*90*6


Wind Load on Diagonal Members 0.05729 TON/M
SWITH YARD

LOCATION ODISHA
DIMENSION

HEIGHT 21.3 M
LENGTH 2M
WIDTH 2M
of IS 875 part 3 2015
H/w 10.65

BASIC WIND SPEED(Vb) 50 m/sec


K1 1.08 From table 1(d) of IS 875 part 3 2015
k2 1.08 From Table 2 For Terrain category 2 of IS 875 Part 3 2015
k3 1 As per cl 6.3.3
k4 1.3 As per cl 6.3.4

Design Win Speed 75.816 m/sec

Wind Pressure 0.351564 T/m2

Ka 1 As perTable 4(i)
Kd 1 As per 7.2.1
Kc 0.9 As per 7.3.3.13

Design Wind Pressure 0.316407 T/m2

AS per cl 9.1(a) h/w > 5 so Dynamic effect of wind will occur

Design wind Force CF*A*Pd*G

Cf 2.8 AS per Table 33 For Solidity Ratio 30%

Longitudanl Turbulence Intensity(Ihi)


Z 5M AS per 6.3.2.1
Z01 0.002 M For Terrain Category 1
Z02 0.02 M For Terrain Category 2
Z03 0.2 M For Terrain Category 3
Z04 2M For Terrain Category 4
log10(z/z01) 3.39794
log10(z/z02) 2.39794
log10(z/z03) 1.39794
log10(z/z04) 0.39794

Iz,1 0.16891
Iz,4 0.41196

Iz,2 0.203632 (Required)

Roughness Factor 0.407263


Peak factor for upward wind 3 For Terrain Category 2
velocity(gv)

Background Factor(Bs)

bsh Average width of Str. Between height s And h


h Total Height of Str
s Height at which background factor is to be calculated
Lh Measure of effective turbulence = 102.6866
of IS 875 part 3 2015

Part 3 2015
Vertical Horizontal Moment
Node L/C Fy Mton Fz Mton Mx MTon- My MTon- Mz MTon-m
4 WEIGHT 0.052 0.002 0 0 0
6 WEIGHT 0.052 0.002 0 0 0
10 WEIGHT 0.052 -0.002 0 0 0
11 WEIGHT 0.052 -0.002 0 0 0
12 WEIGHT 0.126 0.003 0 0 0
13 WEIGHT 0.135 0.004 0 0 0
14 WEIGHT 0.126 -0.003 0 0 0
15 WEIGHT 0.135 -0.004 0 0 0
16 WEIGHT 0.083 0 0 0 0
17 WEIGHT 0.083 0 0 0 0
18 WEIGHT 0.083 0 0 0 0
19 WEIGHT 0.083 0 0 0 0
20 WEIGHT 0.082 0 0 0 0
21 WEIGHT 0.09 0 0 0 0
22 WEIGHT 0.082 0 0 0 0
23 WEIGHT 0.09 0 0 0 0
24 WEIGHT 0.079 0 0 0 0
25 WEIGHT 0.079 0 0 0 0
26 WEIGHT 0.079 0 0 0 0
27 WEIGHT 0.079 0 0 0 0
28 WEIGHT 0.077 0 0 0 0
29 WEIGHT 0.084 0 0 0 0
30 WEIGHT 0.077 0 0 0 0
31 WEIGHT 0.084 0 0 0 0
32 WEIGHT 0.076 0 0 0 0
33 WEIGHT 0.076 0 0 0 0
34 WEIGHT 0.076 0 0 0 0
35 WEIGHT 0.076 0 0 0 0
36 WEIGHT 0.075 0 0 0 0
37 WEIGHT 0.082 0 0 0 0
38 WEIGHT 0.075 0 0 0 0
39 WEIGHT 0.082 0 0 0 0
40 WEIGHT 0.074 0 0 0 0
41 WEIGHT 0.074 0.001 0 0 0
42 WEIGHT 0.074 0 0 0 0
43 WEIGHT 0.074 -0.001 0 0 0
44 WEIGHT 0.073 0 0 0 0
45 WEIGHT 0.073 0 0 0 0
46 WEIGHT 0.073 0 0 0 0
47 WEIGHT 0.073 0 0 0 0
48 WEIGHT 0.072 0 0 0 0
49 WEIGHT 0.072 0 0 0 0
50 WEIGHT 0.072 0 0 0 0
51 WEIGHT 0.072 0 0 0 0
52 WEIGHT 0.072 0 0 0 0
53 WEIGHT 0.072 0 0 0 0
54 WEIGHT 0.072 0 0 0 0
55 WEIGHT 0.072 0 0 0 0
56 WEIGHT 0.069 0 0 0 0
57 WEIGHT 0.069 0 0 0 0
58 WEIGHT 0.069 0 0 0 0
59 WEIGHT 0.069 0 0 0 0
60 WEIGHT 0.062 0 0 0 0
61 WEIGHT 0.062 0 0 0 0
62 WEIGHT 0.062 0 0 0 0
63 WEIGHT 0.062 0 0 0 0
64 WEIGHT 0.029 0.001 0 0 0
65 WEIGHT 0.029 0.001 0 0 0
66 WEIGHT 0.029 -0.001 0 0 0
67 WEIGHT 0.029 -0.001 0 0 0
68 WEIGHT 0.085 0 0 0 0