GMS100C/S: Features
GMS100C/S: Features
EC Series
Features:
• Rotate speed governor: Mechanical governor
• Excitation system: Self excited
• Emergency stop switch
•2x12V sealed for life maintenance free battery
• Lockable battery isolator switch
• 50℃radiator
• Steel base frame with fork holes
• Vibration isolators between the engine/alternator and
base frame
Output Ratings
• Dry type air filter
Generating Set
• Base fuel tank for daily running Prime Power Standby Power
Model
• Drain points for fuel tank
GMS100C 100kVA/80kW 105kVA/84kW
• Operation Manual / Specifications
GMS100CS 100kVA/80kW 105kVA/84kW
Ratings at 0.8 power factor
www.powerlinkworld.com 1/6
GMS100C/S
EC Series
Engine model:6BT5.9-G2
Engine Technical Data
Cooling System
No. of Cylinders / Alignment: 6 / In Line
Cooling System Capacity: L 9.9
Cycle: 4 Stroke
Maximum coolant Friction Head 28
Bore / Stroke: mm 102X120 External to Engine: kPa
Induction: Turbocharged
Maximum Static Head of Coolant
Cooling Method: Water
Above Engine Crank Centerline : 14
Governing Type: Mechanical m
Governing Class: ISO 8528 G2
Standard Thermostat (Modulating) 82-95
Compression Ratio: 16.8:1 Range: °C
Displacement: L 5.9 Minimum Pressure Cap: kPa 69
Moment of Inertia:kg.m² 0.25 Maximum Top Tank Temperature for
104/100
Engine Electrical System: Standby / prime Power: °C
- Voltage / Ground 12/Negative
- Battery Charger 63
Designed to operate in ambient conditions up to 50°C (122°F).
Weight: kg - Dry 411 Contact your local PowerLink Dealer for power ratings at specific site
conditions
- Wet
Performance Fuel System
Engine Speed: RPM 1500
Injection System Type: A pump _ GAC governor/BYC ASIMCO
Gross Engine Power: kWm
Recommended Fuel Type:
-Prime 86 (115)
Diesel Fuel No.2-D(ASTMD975)
- Standby 92(123)
Fuel Consumption: l/hr
BMEP: kPa
110% 100% 75% 50%
- Prime Prime Load Load Load Load
- Standby
GMS100C 25 22 17 11
Lubrication System GMS100CS 25 22 17 11
www.powerlinkworld.com 2/6
GMS100C/S
EC Series
The weights are approximate and without fuel.
Alternator Physical Data Alternator Operating Data
Excitation System: Self excited
Alternator GMS100C
GMS100CS
Performance Data:
Time constants/400V:Ms
Voltage Technical Data GMS100C Voltage Technical Data GMS100CS
www.powerlinkworld.com 3/6
GMS100C/S
EC Series
ControlSystem
PLC-7420
FEATURES
Mains supply and generator operation monitoring.
Indicating operation status and fault conditions.
Real time clock for time and date
display, overall
runtime display, 99 log entries
.
Overall power output display.
Engine ECU is available.
Common USB cable is usable for parameter
configuration.
Multi-language is available.
PLC-920(Optional)
FEATURES
Statistics records;
Remote start/stop;
ECU powers, ECU stop, STOP
or fuel solenoid
selection;
Automatic transfer switching control and engine
control;
Adjustable start, load and stop timers.
www.powerlinkworld.com 4/6
GMS100C/S
EC Series
Optional
Engine Alternator Generator Set Fuel System Canopy
z Water Jacket z Winding Temperature z Tools with the z Low fuel level z Trailer
Preheater z Measuring Instrument machine alarm
z Oil Preheater z Alternator Preheater z Automatic fuel
z PMG feedingsystem
z Anti-damp z Fuel T-valves
andanti-corrosion
treatment
z Anti-condensationheater
The
following lists are optional by the needs of customers.
6B Series 1000 Hour Maintaining List
www.powerlinkworld.com 5/6
GMS100C/S
EC Series
Local Distributor
If you have any question or inquiry, please contact
PowerLink sales organization. Or contact by:
[email protected]