1.1 General Details & Load Calculations - Substation Building (Pess)

The document provides general details and load calculations for the structural design of a substation building. It includes soil data, material properties, and calculations of dead and live loads. Dead loads are calculated for various building elements like the plinth beam, lintel beam, roof beam, and columns. Live loads are also calculated for these elements based on wall thickness and heights, as well as for the roof slab based on thickness of materials. Design parameters like concrete grade, rebar grade, soil properties, and safety factors are also specified.

Uploaded by

Aswin Kumar
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
105 views

1.1 General Details & Load Calculations - Substation Building (Pess)

The document provides general details and load calculations for the structural design of a substation building. It includes soil data, material properties, and calculations of dead and live loads. Dead loads are calculated for various building elements like the plinth beam, lintel beam, roof beam, and columns. Live loads are also calculated for these elements based on wall thickness and heights, as well as for the roof slab based on thickness of materials. Design parameters like concrete grade, rebar grade, soil properties, and safety factors are also specified.

Uploaded by

Aswin Kumar
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

1.

1 GENERAL DETAILS & LOAD CALCULATIONS - SUBSTATION BUILDING(PESS)


1.GENERAL DATA:

1.1 Soil Data:


Net SBC of soil considered @ 2.00 m -------------------------------------------------------------------------
= 307.090 KN/m²
Gross SBC of soil consider @2.00 m -------------------------------------------------------------------------
= 307 x 1.25 + 18 x 2.00 (25% Exes for Wind/Earth)
Gross SBC of soil consider @ = 420.88 KN/m²
2.00 m ------------------- ------------------------------------------------------
= 18.00 KN/m³
Unit weight of soil -------------------------------------------------------------------------
= 32⁰
Angle of repose (ф) -------------------------------------------------------------------------
Co-efficient of friction (μ) --------------------------------------- ---------------------------------
- = 0.4

1.2 Material Properties:

Grade of Concrete (fck) -------------------------------------------------------------------------


= 25 N/mm²
Grade of Steel (fy) -------------------------------------------------------------------------
= 500 N/mm²
Unit weight of concrete -------------------------------------------------------------------------
= 25 KN/m³ Table 1-IS 875 (Part-1)-1987 _pg 08.
To take Factor of Safty (FOS) -------------------------------------------------------------------------
= 1.5
Clear Cover of Footing (d) -------------------------------------------------------------------------
= 50 mm
- = 50 mm
Clear Cover of Column (d) --------------------------------- ---------------------------------------
Clear Cover of Plinth Beam (d) --------------------------- ----------------------------------------------
= 25 mm
Clear Cover of Lintel Beam (d) -------------------------------------------------------------------------
= 25 mm
Clear Cover of Roof Beam (d) -------------------------------------------------------------------------
= 25 mm
Clear Cover of Roof Slab(d) ------------------------------- -----------------------------------------
- = 15 mm
= as per cad
Lateral Dimension of Structure (d-x direction) -------- -----------------------------------------------------------------
= as per cad
Lateral Dimension of Structure (d-z direction) -------- -----------------------------------------------------------------
Height of the of Structure (h) -------------------------------------------------------------------------
= 5.90 m

2.LOAD CALCULATION:

2.1 Dead load:

i) Plinth Beam -------------------------------------------------------------------------


= DL As per STAAD Pro
ii) Lintel Beam -------------------------------------------------------------------------
= DL As per STAAD Pro
iii) Roof Beam -------------------------------------------------------------------------
= DL As per STAAD Pro
iv) Column -------------------------------------------------------------------------
= DL As per STAAD Pro

2.2 Live load:

a) Plinth Beam:

Height of wall in b/t Plinth Beam to Roof Beam -------------------------------------------------------------------------


= 4.500 m
= 20 KN/m³
Unit wt of Brick with Mortar ------------------------------------------------------------------------- Table 1-IS 875 (Part-1)-1987 _pg 10.

a) 230mm thick wall: -------------------------------------------------------------------------


= 20 x 4.5 x 0.23
= 20.7 KN/m =230mm Brick wall
b) 115mm thick wall: -------------------------------------------------------------------------
= 20 x 4.5 x 0.115
= 10.35 KN/m =115mm Brick wall
b) Lintel Beam:

Height of wall in b/t Lintel Beam to Roof Beam -------------------------------------------------------------------------


= 1.500 m
= 20 KN/m³
Unit wt of Brick with Mortar ------------------------------------------------------------------------- Table 1-IS 875 (Part-1)-1987 _pg 10.

a) 230mm thick wall: -------------------------------------------------------------------------


= 20 x 1.5 x 0.23
= 6.90 KN/m =230mm Brick wall
c) Roof Beam:

Height of wall in above Floor Beam (Max) -------------------------------------------------------------------------


= 0.750 m
= 20 KN/m³
Unit wt of Brick with Mortar ------------------------------------------------------------------------- Table 1-IS 875 (Part-1)-1987 _pg 10.

a) 115mm thick wall: -------------------------------------------------------------------------


= 20 x 0.75 x 0.115
= 1.7 KN/m =115mm Brick wall

-----------------------------------------------------------
----------------------------------------

---------------------------------

5 of 121
d) Roof Slab:
Slab thickness -------------------------------------------------------------------------
= 150 mm
Dead load of Slab (DLS) -------------------------------------------------------------------------
= 25 x 0.15
DLS1 = 3.750KN/m²
Thickness of Water Proffing Marter ----------------------------------------------
= 100 mm
Dead load of Marter (DLM) ----------------------------------------------------------------------
= 25 x 0.1

---------------------------------------------------
----------------------------------------
DLM = 2.500KN/m²
Roof Finishing (RF) -------------------------------------------------------------------------
= 0.250 KN/m² Table 2-IS 875 (Part-1)-1987 _pg 30.
Total Roof Load (W1) -------------------------------------------------------------------------
= 3.75+2.5+0.25
W1 = 6.5KN/m²
Total Roof Load (W2) -------------------------------------------------------------------------
= 3.125+2.5+0.25
W2 = 5.9KN/m²

Roof Live Load (LL) -------------------------------------------------------------------------


= 1.50 KN/m² Table 2-IS 875 (Part-2)-1987 _pg 14.

2.3 Wind load:

= II
Wind zone ------------------------------------------------------------------------- Table 1- IS 875 (Part 3)- 1987 _pg 11.
Basic Wind Speed (Vb) -------------------------------------------------------------------------
= 39 m/s Table 1- IS 875 (Part 3)- 1987 _pg 11.
Design Wind Speed (Vz) -------------------------------------------------------------------------
= Vbxk1xk2xk3 IS 875 (Part 3)- 1987 _pg 08.
Risk Co-efficient (k1) -------------------------------------------------------------------------
= 1.06 Table 1- IS 875 (Part 3)- 1987 _pg 11.
Topography factor (k3) -------------------------------------------------------------------------
= 1.00 IS 875 (Part 3)- 1987 _pg 12.
Terrain factor (k2) -------------------------------------------------------------------------
.=> Table 2- IS 875 (Part 3)- 1987 _pg 12.
Terrain Category -------------------------------------------------------------------------
= 2 (1.5 to 10m) Surrounding the Structure
Terrain Category Class -------------------------------------------------------------------------
= B(20 to 50 m) Horizontal or Vertical Dimentions
Terrain Category Height -------------------------------------------------------------------------
= 10
Terrain factor (k2) -------------------------------------------------------------------------
= 0.98
Design Wind Speed (Vz) -------------------------------------------------------------------------
= 39x1.06x0.98x1 IS 875 (Part 3)- 1987 _pg 08.
Vz = 40.51 m/s
= 0.6Vz²
Wind Pressure (Pz) ------------------------------------------------------------------------- IS 875 (Part 3)- 1987 _pg 12.
Pz = 1.0 KN/m²
2.4 Seismic load:

= II
Seismic zone ------------------------------------------------------------------------- Table 2- IS 1893: 2002 _pg 16
Seismic Intensity (Z) -------------------------------------------------------------------------
= 0.10 Table 2- IS 1893: 2002 _pg 16
Structure type -------------------------------------------------------------------------
= Power station Table 6- IS 1893: 2002 _pg 18
Design Seismic Base Shear (VB) -------------------------------------------------------------------------
= Ah*W IS 1893: 2002 _pg 24
Seismic weight of Structure (W) -------------------------------------------------------------------------
= TDL+TLL As per STAAD Pro
Design Horizontal Acceleration (Ah) -------------------------------------------------------------------------
= (Z*I / 2R)*(Sa/g) IS 1893: 2002 _pg 14
Impartance factor (I) -------------------------------------------------------------------------
= 1.50 Table 6- IS 1893: 2002 _pg 18
Response Reduction factor (.R) -------------------------------------------------------------------------
= 5 Table 7- IS 1893: 2002 _pg 23
Spectral Acceleration Coefficient (Sa/g) -------------------------------------------------------------------------
.=> IS 1893: 2002 _pg 16
= 0.09*h / √ d
Fundamental Natural Period (Ta) -------------------------------------------------------------------------
IS 1893: 2002 _pg 24
Lateral Dimension of Structure (d-x direction) -------------------------------------------------------------------------
= 35.53 m
Height of the of Structure (h) -------------------------------------------------------------------------
= 5.90 m
Fundamental Natural Period (Ta) -------------------------------------------------------------------------
= 0.09 sec .=X-direction
Lateral Dimension of Structure (d-z direction) -------------------------------------------------------------------------
= 9.30 m
Height of the of Structure (h) -------------------------------------------------------------------------
= 5.90 m
Fundamental Natural Period (Ta) -------------------------------------------------------------------------
= 0.17 sec .=Z-direction
Type of Soil -------------------------------------------------------------------------
= Rocky or Hard Soil IS 1893: 2002 _pg 16
Spectral Acceleration Coefficient (Sa/g) -------------------------------------------------------------------------
= 2.34
Design Horizontal Acceleration (Ah) -------------------------------------------------------------------------
= 0.035 .=(Z*I / 2R)*(Sa/g)
Design Seismic Base Shear (VB) -------------------------------------------------------------------------
= (TDL+TLL)x0.035 .=Ah*W= VB