Idmt Relay
Idmt Relay
OVERCURRENT PROTECTION
RELAY
Introduction
Normally-open
contact
PS
2
Plug-setting multiplier, PSM
I relay
PSM
PS
4
Definite Time Over-current relay
• This relay can be adjusted to issue a trip output at a
definite (and adjustable) amount of time, after it pick up
• It has both time-setting and pick-up adjustment
5
Inverse Definite Minimum Time (IDMT)
Over-current relay
• This is possibly the most widely used characteristic
• The characteristic is inverse in the initial part, which
tends to a definite minimum operating time as the
current becomes very high (flux saturations)
• The mathematical relation between the current and
the operating time of IDMT characteristic can be
written as
0.14(TMS)
t op IDMT
(PSM) 0.02
1
80(TMS)
t op Extremely inverse
(PSM) 1
2
8
Find the tripping time of IDMT relay
with TMS = 0.5; PSM = 3
10
Equation involved in IDMT relay setting
American Standard British Standard
11
Application of Definite Time OC relays for
protection of a distribution feeder
12
Cont..
13
Cont..
14
How to set the operating time of the relay
Back-up
primary
15
Selective time interval (STI)
Cont..
19
Cont..
20
Cont..
21
Tripping time for fault at Bus B
Relay A Relay B
Maximum fault 0.77 s 0.2 s
tripping time
Minimum fault 0.8 s 0.226 s
tripping time (approx)
22
Cont..
23
24
Exercise
• Repeat the previous example with the
following assumption:
– Rated CT secondary output current is 1 A
– Permissible over load is 10% of the rated load
– Available plug setting (10%, 20%, 30%, 40%, 50%,
60%, 70%, 80%, 90%, 100%)
– CB tripping time is 5 cycle @ 50Hz
– Overshoot error is 0.3 sec
25
Exercise
26
solution
27
Cont..
28
Cont..
29
Cont..
0.1
30
Cont..
31
EXAMPLE 1
A 33kV power system shown below is installed with IDMT relays at each substation
to provide overcurrent protection scheme. As an engineer, you are required to
determine the Tap Setting (TS) and Time Dial Setting (TDS) Plug Setting (PS) and
Time Multiplier Setting (TMS) for each relay so that the protection system will
function well according to the data given in Table below. In the design, you have to
ensure relay at substation C operates within 0.23 second. You also should consider
time discrimination between each location is 0.5 second.
33 kV A B C
96
PS 100 48%
200 5
5
PS 50%
1925
PSM 19.25
200
0.5 5
5
tope 0.23s
0.14
tchar 2.298
19.25 1
0.02
0.23
TMS 0.1
2.298
Setting for Re lay A [ PS 50%, TMS 0.1] 34
RELAY B (Fault near at C)
148
PS 100 49%
300
PS 50%
1925
PSM 12.83 Setting for Relay B:
300
0 .5 5 [PS = 50%, TMS = 0.27]
5
tope 0.23 0.5 0.73s
0.14
tchar 2.67
12.83 1
0.02
0.73
TMS 0.27
2.67 35
Relay B (Fault near at B)
2975
PSM 19.83
300
0.5 5
5
0.14
tchar 2.27
19.83 1
0.02
tope
TMS
tchar
tope 0.27 2.27 0.61s
36
Relay A (fault at B)
252
PS 100 84%
300
PS 100%
2975
PSM 9.92
300
1 5 Setting for Relay A =
5 [PS = 100%, TMS = 0.37]
0.14
t char 2.98
9.92 0.02
1
t ope 0.61 0.5 1.11s
1.11
TMS 0.37
2.98 37
Repeat the example by determining the Tap Setting (TS) and
Time Dial Setting (TDS) by using the IDMT time-current
characteristic below (CO-7)
38
EXAMPLE 2
Figure below shows a radial system attached with IDMT relay at point A, B and
C. Table below gives details on the CT and relay rating used at each point. Relay
at point B is set with Plug Setting (PS) of 75% and it will operate within 0.84 sec
if a three phase fault with fault current of 8100A occurs close to point C. On the
other hand, if a three phase fault with fault current of 10kA occurs near to point
B, the relay will operate within 0.58 sec. Determine the appropriate setting (PS
and TMS) for each relay by using 0.6 sec of time delay between relays. Use
IDMT relay characteristics for reference.
A B C
CT ratio 300/5 700/5 500/5
Relay Rating 5A 5A 5A
39
IDMT RELAY CHARACTERISTICS
40
PSM
ANSWER
41
RELAY C
Step 1: Find the load current, IL.
S 2.5M
I Load 437.39 A
3VLine 3(3.3kV )
Select 100%
42
Fault at C (Primary)
43
Fault at C (Primary)
44
RELAY B
45
Fault at C (Back up)
Step 3: Find the Plug Setting Multiplier (PSM)
Given I Fault 8100 A
8100
PSM 15.4
700
0.75 5
5
46
Fault at C (Back up)
47
Fault at B (Primary)
48
RELAY A
Step 1: Find the load current, IL.
S 5M
I Load 262.43 A
3VLine 3(11kV )
3.3k
I Fault new 10k 3kA
11k
50
Fault at B (Back up)
51
Fault at B (Back up)
52
EXAMPLE 3
Figure Q3 shows a radial system equipped with IDMT
r e l a y. I m p e d a n c e o f t h e l i n e L 1 a n d L 2 a n d f u l l l o a d
current IB is shown in the diagram. Relay on C and D
will operate simultaneously as secondary protection to
relay on E. Both will operate in three phases 0.65sec
w h e n l e v e l o f d a m a g e 7 0 M VA o c c u r s n e a r p o i n t E .
T r a n s f o r m e r, T x h a s a m a x i m u m f a u l t l e v e l o f 9 7 M VA .
G e t Pl u g Se tti n g ( PS) a n d Ti m e Mu l ti p l i e r Se tti n g
(TMS) suitable for relay on A, B and C by selecting
nearly the current transformer ratio and proportion
r e l a y f r o m Ta b l e Q 3 . A s s u m e t h e g e n e r a t o r i m p e d a n c e
is pure stretching. Use a time interval of 0.4sec
between relay and relay features below:
53
EXAMPLE 3
11/3.3 kV
A B C D E
j0.2 j0.1
11 kV
IB=620A
L1 L2
200MVA
Tx
54
EXAMPLE 3
Rajah S3 menunjukkan satu sistem jejarian yang dilengkapi dengan
geganti IDMT. Galangan bagi talian L1 dan L2 dan arus beban penuh IB
ditunjukkan dalam gambarajah tersebut. Geganti pada C dan D akan
beroperasi secara serentak sebagai perlindungan sekunder kepada
geganti pada E. Kedua-duanya akan beroperasi dalam masa 0.65s
apabila kerosakan tiga fasa dengan aras kerosakan sebanyak 70MVA
berlaku berhampiran titik E. Pengubah Tx mempunyai aras kerosakan
maksimum sebanyak 97MVA. Dapatkan Penatahan Palam (PS) dan
Penatahan Masa Berbilang (TSM) yang sesuai bagi geganti pada A, B
dan C dengan memilih nisbah pengubah arus yang paling hampir dan
kadaran geganti daripada Jadual S3. Anggap galangan penjana adalah
regangan tulen. Gunakan sela masa sebanyak 0.4s antara geganti dan
ciri-ciri geganti di bawah:
55
EXAMPLE 3
11/3.3 kV
A B C D E
j0.2 j0.1
11 kV
IB=620A
L1 L2
200MVA
Tx
56
ANSWER
Relay C (Fault at E)
3.3k
I L 620 186 A Setting for Re lay C
11k [ PS 100%, TMS 0.28]
choose CT : 200 / 5
186
PS 100 93%
200 5 Relay C (Fault at C)
5
PS 100%
97 MVA
70 MVA IF 5091A
IF 3.67 kA 3 11k
3 11k
3.67 k 5091
PSM
200
18.37 PSM 25.46
1 5 200
5 1 5
0.14 5
t ch a r 2.33
18.37 0.0 2 1 0.14
t o p e 0.65s
tchar 2.09
25.46 0.02
1
TMS
0.65
0.28 tope 2.09 0.28 0.59 s
2.33 57
Relay B (Fault near at C)
I L 100 186 286 A Relay B (Fault at B)
choose CT : 300 / 5
V 2 11k 2
PS
286
100 95% Xg 0.605
300 5 S 200M
5
PS 100% X T j 0.605 j 0.2 j 0.1 j 0.905
I F 5091A 11kV
5091 IF 7.02kA
PSM
300
16.97 3 j 0.905
1 5
5 7.02k
0.14 PSM 23.4
t ch a r 2 .4 300
16.97 0.0 2
1 1 5
t o p e 0.59 0.4 0.99 s 5
0.99 0.14
TMS 0.41 tchar 2.15
2 .4 23.4 1
0.02
60
DIGITAL OVERCURRENT & GROUND
OVERCURRENT RELAY
61
OVER CURRENT RELAY FOR
GENERATOR
62
OVER CURRENT RELAY
63
THANK YOU
64