Modbus Conversion
Modbus Conversion
Inputs
Global Inputs GX0 - GX3777 0 10001 Inputs 10001 - 12048
Inputs X0 - X1777 0 12049 Inputs 12049 - 13072
Special Register SP0 - SP777 0 13073 Inputs 13073 - 13584
Registers
Holding Input
PLC Registers Registers
V Memory 0 40001 30001 Holding Registers
Input Registers
Modbus V Memory
40001 0
30001 0
NOTE: H2-ECOM100, H0-ECOM100, and H4-ECOM100 modules will also support Function 4 over ethernet. The
modules must have firmware versions equal to or greater than those listed below to support this. The feature is used by
requesting EVEN numbers of bytes for 40001+ addresses (function code 3) and ODD numbers of bytes for 30001+
addresses (function code 4).
H0-ECOM100 = 4.0.52
H2-ECOM100 = 4.0.999
H4-ECOM100 = 4.0.1049